Sunteți pe pagina 1din 1

De la TUPS

NHXH E90 5x6


PE N L3 L2 L1
Tablou TEArhiveV
min. IP40
montaj aparent
intrari / iesiri : sus / sus
Rezerva spatiu: 25%

L1
L2
L3
N
1 3 5
1Q1 1 3 5 1
3P 1Q2 1Q3
25A 3P 1P
40A 6A

2 4 6
2 4 6 2

3 1 N 1 N 1 N 1 N 1 N 1 N 1 N 1 N 1 3 1 3 1 3
F1 1Q4 2Q4 3Q4 5Q4 6Q4 7Q4 8Q4 9Q4 1Q5 2Q5 3Q5
Descarcator
1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N 1P+N
Clasa I+II 10A/C 10A/C 10A/C 10A/C 10A/C 10A/C 10A/C 10A/C 16A/30mA 16A/30mA 16A/30mA
TN-S 4
3x230V/400Vac
2 N 2 N 2 N 2 N 2 N 2 N 2 N 2 N
2 4 2 4 2 4
H1

ROSU

Semnalizare
avarie protectie
suptratensiune

L1 N PE L2 N PE L3 N PE L1 N PE L2 N PE L3 N PE L1 N PE L2 N PE L3 N PE L1 N PE L2 N PE

Denumire Circuit 0 1 CL1 CL2 CL3 CL4 CL5 CL6 CL7 CL8 CF1 CF2 CF3
Pi/Pa [ kW ] 9.25 - 0.48 0.48 0.39 0.44 0.48 0.39 0.48 0.48 2.0 / 1.6 2.0 / 1.6 2.0 / 1.6
Ic [ A ] 16.7 - 2.24 2.24 1.85 2.07 2.24 1.85 2.24 2.24 8.7 8.7 8.7
Sect [ mmp ] NHXH E90 5x6 - NHXH E90 3x2.5 NHXH E90 3x2.5 NHXH E90 3x2.5 NHXH E90 3x2.5 NHXH E90 3x2.5 NHXH E90 3x2.5 NHXH E90 3x2.5 NHXH E90 3x2.5 3x2.5 3x2.5 3x2.5
Protectie IA 3P/25A/C IA 3P/40A/C IA 1P+N/10A/C IA 1P+N/10A/C IA 1P+N/10A/C IA 1P+N/10A/C IA 1P+N/10A/C IA 1P+N/10A/C IA 1P+N/10A/C IA 1P+N/10A/C IA 1P+N/16A/30mA/C IA 1P+N/16A/30mA/C IA 1P+N/16A/30mA/C
Repartitie faza L1,L2,L3 L1,L2,L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2
Surse incendiu arhiva 1+camera butelii
Destinatie Tablou electric Vitali Arhive Semnalizare avarie protectie supratensiune Iluminat arhiva 1, tavan Iluminat arhiva 2, tavan Iluminat arhiva 3, tavan Iluminat arhiva 4, tavan Iluminat arhiva 1, podina rafturi Iluminat arhiva 2, podina rafturi Iluminat arhiva 3, podina rafturi Iluminat arhiva 4, podina rafturi Surse incendiu arhiva 2 Surse incendiu arhiva 3
stingere

1 3 5 7
1Q7 SPECIFICATIE TEHNICA TABLOU ELECTRIC TEArhiveV
4P
10A
NR. CRT. DENUMIREA ECHIPAMENTULUI SPEC BUC
2 4 6 8

Intrerupator automat, iC60L, 3P, 25A, curba C, cu Schneider


1 3
4Q5
1 3
5Q5
1 3
6Q5
1 3 5 1 3 5 1 3 5 1 3
7Q5
Q1 protectie la suprasarcina si scurtcircuit sau similar
1
1Q6 2Q6 3Q6
1P+N 1P+N 1P+N 3P 3P 3P 1P+N
16A/30mA 16A/30mA 16A/30mA 10A 10A 10A 16A/30mA
Intrerupator automat, iC60N, 3P, In=40A, curba C, cu Schneider
2 4 6 2 4 6 2 4 6 LEGENDA: Q2 protectie la suprasarcina si scurtcircuit sau similar
1
2 4 2 4 2 4 2 4

1 3
Intrerupator automat, iC60N, 1P, In=6A, curba C, cu Schneider
Q3 protectie la suprasarcina si scurtcircuit sau similar
1
- intreruptor automat magneto-termic, 2P;
Intrerupator automat, iC60N, 1P+N, In=10A, curba C, cu Schneider
2 4
Q4 protectie la suprasarcina si scurtcircuit sau similar
9
1 3 5 7
Intrerupator automat, iC60N, 1P+N, In=16A, curba C, cu
Schneider
1 3
Q5 protectie la suprasarcina, scurtcircuit si protectie
sau similar
7
diferentiala 30 mA
- intreruptor automat magneto-termic, 2P, Intrerupator automat, iC60N, 3P, In=10A, curba C, cu Schneider
Q6 protectie la suprasarcina si scurtcircuit sau similar
1
cu protectie diferentiala 30mA;
2 4
Intrerupator automat, iC60N, 4P, In=10A, curba C, cu Schneider
Q7 protectie la suprasarcina si scurtcircuit sau similar
1
L3 N PE L1 N PE L2 N PE L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE L2 N PE
- intreruptor automat magneto-termic, 4P; Contactor iCT, 2ND, 16A, 2 contacte normal deschise, Schneider
2 4 6 8
K1 tensiunea bobinei de comanda 230V sau similar
1
H1 H2 H3
Verde Verde Verde
Lampa de semnalizare, culoare verde, LED, montare pe Schneider
HL1 H1 usa tabloului sau similar
3
- Lampa semnalizare (culoare verde);
VERDE

CF4 CF5 CF6 CF7 CF8 CF9 R CC


NOTA:
2.0 / 1.6 2.0 / 1.6 2.0 / 1.6 0.75 0.75 0.75 0.1 - Separator cu fuzibil; Toate echipamentele folosite in executia tabloului trebuie sa fie
8.7 8.7 8.7 1.35 1.35 1.35 0.18
3x2.5 3x2.5 3x2.5 NHXH E90 5x2.5 NHXH E90 5x2.5 NHXH E90 5x2.5 5x1.5
construite in conformitate cu SR EN 60947-2;
IA 1P+N/16A/30mA/C IA 1P+N/16A/30mA/C IA 1P+N/16A/30mA/C IA 3P/10A/C IA 3P/10A/C IA 3P/10A/C IA 1P+N/16A/30mA/C IA 4P/10A/C
Toate echipamentele vor avea capacitatea de rupere la scurtcircuit
L3 L1 L2 L1,L2,L3 L1,L2,L3 L1,L2,L3 L2 L1,L2,L3 Prezenta tensiune
- Descarcator supratensiuni, 4P; Ik≥6kA daca in planuri nu se specifica alta valoare;
Alimentare centrala trape de fum tocator
Surse incendiu arhiva 4 Rack camera server B027
si receptie documente
Usa sectionala B022 - receptie documente Usa sectionala B023 - tocator documente Usa sectionala B023 - tocator documente Rezerva Alimentare circuit comanda Tabloul se va realiza in cutie metalica, ventilata natural cu cate
doua prize de aer pe laterale, jos si sus;
- Receptor tip iluminat; Tabloul electric va fi prevazut cu sir de cleme pentru cablurile cu
sectiuni mai mici de 35mmp;
- Receptor tip priza; Toate intrarile si iesirile sunt pe sus;
Rezerva spatiu gol: 25%, conform indicatiilor de pe schema
DATE GENERALE / GENERAL DATA
GRADUL DE REZISTENTA LA FOC / fire resistance = "I" - conf. P118-99
CATEGORIA DE IMPORTANTA / class of importance = "B" - conf. HG766-97
CLASA DE IMPORTANTA / class of importance = "II" - conf. P100-1/2013

VERIF. / EXP.: NUME: SEMANTURA: CERINTA: REFERAT VERIFICARE / RAPORT EXPERTIZA TEHNICA - titlu / nr. / data:

GENERALINSTALCOMPS.R.L

Electrice
Data / Date: SCHEMA ELECTRICA MULTIFILARA Desen / Dwg:
TABLOU ILUMINAT SI RECEPTOARE IET006
02/2018 VITALE ARHIVE - TEArhiveV Rev.: 00

S-ar putea să vă placă și