LV AC CABLE SIZING CALCULATION


A.S

A.S
BY

19.10.09

13.12.09
DATE
NO.

REVISIONS
DESIGNED

BY:- A.S

DATE:- 13.12.09

CHECKED

BY:- A.R/KH.A

DATE:- 13.12.09

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT DATE


DOCUMENT TITLE INDEX PLANT DOCUMENT NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OF LV AC CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C173 CE-113347
CERTIFIED AND CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
DATED

RIYADH SAUDI ARABIA JOB ORDER NO. 1-0931045.02 DOC. CONT. SHT.
APP'D CERT'D

Saudi Electricity Company ‫ودية للكهرباء‬


CHEK'D

KH.A

KH.A

INDEX

SHEET
CONTENT
NO.
2 Index
03 Reference Documents / Design basis
REVISED AS PER SEC COMMENTS IN LETTER # 09-50294-030343 DATED 07.12.09

04-05 Sizing calculation of ACDB Incomer cables


06-17 Sizing calculation of auxiliary AC cables

Attachments List

Attachment-1 RIYADH Cable Co. Cataloug


ISSUED FOR APPROVAL
DESCRIPTION

A.S

A.S
BY

19.10.09

13.12.09
DATE
NO.

REVISIONS
DESIGNED

BY:- A.S

DATE:- 13.12.09

CHECKED

BY:- A.R/KH.A

DATE:- 13.12.09

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT DATE


DOCUMENT TITLE INDEX PLANT DOCUMENT NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OF LV AC CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C173 CE-113347
CERTIFIED AND CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
DATED
RIYADH SAUDI ARABIA JOB ORDER NO. 1-0931045.02 DOC. CONT. SHT.
APP'D CERT'D

Saudi Electricity Company ‫ودية للكهرباء‬


CHEK'D

KH.A

KH.A

Reference Documents :
1 Transmission Engineering Standard – TES-P-104.03: Cable Sizing & Selection
2 Transmission Engineering Standard – TES-P-119.29: LV Cable Selection & Sizing(600 V & Belo
3 Transmission Material Standard Specification 11-TMSS-10: Power and/or AL. Conductor,600 /10
4 Dwg. No. CA-113554 – One Line Diagram - 220/127V AC
5 Doc. No. CE-113342 – AC Load Schedule & Aux. TR. Sizing Calculation
6 Dwg. No. CA-113549– Substation Overall layout -Plan
7 Scope of Work and Technical Specification - PTS # 08CN300
REVISED AS PER SEC COMMENTS IN LETTER # 09-50294-030343 DATED 07.12.09

8 RIYADH Cable Co. Catalouge ( attachment-1)


Note :-
All 0.6/1kV Cable Data are referred from RIYADH Cable Co. Catalogues
(for calculation purpose)
ISSUED FOR APPROVAL
DESCRIPTION

Design Basis:-

1 The following type of cables are considered:


a) Power cables – 0.6/1kV, Cu., XLPE insulated, LMDPE sheathed for 630Sqmm cable.
b) Power cables – 0.6/1kV, Cu., XLPE insulated, PVC ST2 sheathed for other cables

2 The following are the limits of voltage drop considered for design:
AC Circuits:-
a) Auxiliary Transformer to ACDB 0.8

b) ACDB to Indoor Lighting panel (ILP) 1.6


Lighting Panel (ILP) to Indoor lighting circuits 2.6

c) ACDB to Outdoor Lighting Panel (LP-OD) 1.6


Lighting panel (LP-OD) to Outdoor lighting 2.6
A.S

A.S
BY

d) ACDB to SDB 1.6


SDB to SDB various loads 2.6
19.10.09

13.12.09
DATE

e) ACDB to Battery charger, Oil filtration sockets, etc… 4.2


NO.

REVISIONS
DESIGNED

BY:- A.S

DATE:- 13.12.09

CHECKED

BY:- A.R/KH.A

DATE:- 13.12.09

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT DATE


DOCUMENT TITLE INDEX PLANT DOCUMENT NO.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OF LV AC CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C173 CE-113347
CERTIFIED AND
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
DATED
RIYADH SAUDI ARABIA JOB ORDER NO. 1-0931045.02 DOC. CONT. SHT.
‫الشركة السعودية للكهرباء‬

ABLE SIZING CALCULATION

SHEET NO. REV.

01 OF 17 1

DOC. CONT. SHT. CE-113302


‫الشركة السعودية للكهرباء‬

SHEET NO. REV.

02 OF 17 1
DOC. CONT. SHT. CE-113302
‫الشركة السعودية للكهرباء‬

d – TES-P-119.29: LV Cable Selection & Sizing(600 V & Below)


ecification 11-TMSS-10: Power and/or AL. Conductor,600 /1000V rating

%
%

%
%

%
%

DATE
SHEET NO. REV.

03 OF 17 1
DOC. CONT. SHT. CE-113302
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION

Incomer cable sizing from Aux. Trafo to ACDB ( Q101, Q102,Q103

Cable From : 2000KVA AUX. TR


Cable To : ACDB
System Voltage (V) = 220
Connected Load (S) = ###
Current through the feeder = S/√3xV
= 5249
Current considered for design (I) = 5249
Cable size selected 6x 1C x
and 3x 1C x
No. of runs (N) = 6
Underated current carrying capacity of the cable (Ic) = 1117

Derating Factors
Type of Cable laying : Trefoil touching in cable trench
a) K1 - Air Rating factor at 40˚C = 0.91 (As Per Riyadh cable Co. catalouge table 10)
b) K2 - Group rating factor = 0.87 (As per TES-P-119.29 Cl. 7.1.7.a.i)

Net derating Factor (K) = 0.79


Derated current carrying capacity of the cable = K x Ic x N
= 5306

The derated current carrying capacity of the cable is higher than the maximum

CE-113347, REV.01 7 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫أعمال الوسطى‬

Calculation of Voltage Drop

Unit AC resistance of the cable @ 90oC (R) = 0.04


Unit reactance of the cable (X) = 0.09
Total route length of the cable (L) = 13.5
Net Resistance of the cable (Rl = L x R / N x 1000) = 0.0001
Net Reactance of the cable (Xl = L x X / N x 1000) = 0.0002
Load Power Factor - cos φ = 0.85
sin φ = 0.53
Total Voltage drop (Vd) = √ 3 x I x [Rl cos φ
= 1.71
% Voltage drop = Vd x 100 / V
= 0.78

Permissible Voltage drop = 0.8

The actual voltage drop is lesser than the permissible voltage drop --> 2

Check for Short circuit withstand capacity of the cable

The conductor size is checked for short circuit with the following formulae:
Isc =143 x S / √ t , where
t = Duration of Short circuit = 1
S = Cross sectional area of the cable = 630
Substituting in the above equation, we get
Isc = 90090
= 90
Rated fault withstanding current at the Tranformer = 80.325

Short circuit current withstand capacity of the cable is higher than that at the

CE-113347, REV.01 8 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫أعمال الوسطى‬

From 1,2 & 3 the design is safe.

CE-113347, REV.01 9 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬

‫منطقة أعمال الوسطى‬


LE SIZING CALCULATION

Aux. Trafo to ACDB ( Q101, Q102,Q103 )

2000KVA AUX. TR

V
VA
S/√3xV
A
A
630 mm2 Cu./ Phase
630 mm2 Cu./ Neutral

As Per Riyadh cable Co. catalouge table 10)

K x Ic x N
A

f the cable is higher than the maximum feeder current --> 1

CE-113347, REV.01 10 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬

‫منطقة أعمال الوسطى‬

Ω / km
Ω / km
m

Ω 31.79

√ 3 x I x [Rl cos φ + Xl sin φ ]


V
Vd x 100 / V
%

he permissible voltage drop --> 2

second
mm2

A
KA, for one second
KA

of the cable is higher than that at the Tranformer -->3

CE-113347, REV.01 11 of 42
‫‪CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP‬‬

‫الشركة السعودية للكهرباء‬

‫منطقة أعمال الوسطى‬

‫‪CE-113347, REV.01‬‬ ‫‪12 of 42‬‬


CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

PANEL : MAIN DISTRIBUTION BOARD BUS-A 220/127V AC


1 ACDB BUS-A INDOOR LIGHTING PANEL -1( LOC -CONTROL ROOM) 134.190 3 220 0.85 414.3 2 207.1 XLPE 4C 150 407 0.91 0.7 0.64 259.26 500

2 ACDB BUS-A INDOOR LIGHTING PANEL -2( LOC -AC/DC ROOM) 130.770 3 220 0.85 403.7 2 201.9 XLPE 4C 120 355 0.91 0.7 0.64 226.14 500

3 ACDB BUS-A OUTDOOR LIGHTING PANEL-2 (LOC -380KV GIS ROOM) 117.90 3 220 0.85 364.0 2 182.0 XLPE 1C 630 1117 0.91 0.7 0.64 711.53 500

4 ACDB BUS-A OUTDOOR LIGHTING PANEL -3( LOC -132KV GIS ROOM) 66.06 3 220 0.85 204.0 2 102.0 XLPE 4C 240 551 0.91 0.7 0.64 350.99 320

5 ACDB BUS-A 300A OIL FILTERATION SOCKET (REACTOR AREA-1) 77.74 3 220 0.85 240.0 1 240.0 XLPE 4C 185 469 0.91 0.7 0.64 298.75 320

6 ACDB BUS-A SDB-1A (LOC -380KV GIS BLD) 80.75 3 220 0.85 249.3 2 124.7 XLPE 4C 150 407 0.91 0.7 0.64 259.26 320

7 ACDB BUS-A SDB-2 (LOC -132KV GIS BLD) 56.087 3 220 0.85 173.2 2 86.6 XLPE 4C 240 551 0.91 0.7 0.64 350.99 320

PORTABLE 125V DC BATTERY CHARGER


8 ACDB BUS-A 62.50 3 220 0.85 193.0 1 193.0 XLPE 4C 120 355 0.91 0.7 0.64 226.14 250
(380KV DC SYSTEM BATTERY CHARGER)

9 ACDB BUS-A SDB-1B (LOC -380KV GIS BLD) 43.977 3 220 0.85 135.8 2 67.9 XLPE 4C 185 469 0.91 0.7 0.64 298.75 200

10 ACDB BUS-A INDOOR LIGHTING PANEL -5( LOC -132KV GIS ROOM) 50.360 3 220 0.85 155.5 2 77.7 XLPE 4C 185 469 0.91 0.7 0.64 298.75 200

11 ACDB BUS-A TELECOM ROOM ACDB 31.095 3 220 0.85 96.0 1 96.0 XLPE 4C 35 160 0.91 0.7 0.64 101.92 125

PORTABLE 125V DC BATTERY CHARGER


12 ACDB BUS-A 31.250 3 220 0.85 96.48 1 96.5 XLPE 4C 35 160 0.91 0.7 0.64 101.92 125
(132KV DC SYSTEM BATTERY CHARGER)

13 ACDB BUS-A SGT-1 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100

14 ACDB BUS-A SGT-1 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100

15 ACDB BUS-A SGT-3 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100

CE-113347, REV.01 13 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

16 ACDB BUS-A SGT-3 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100

17 ACDB BUS-A SGT-5 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 50 195 0.82 0.7 0.57 111.93 100

18 ACDB BUS-A SGT-5 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 50 195 0.82 0.7 0.57 111.93 100

19 ACDB BUS-A 100A WELDING RECEPTACLE AT HVAC PACU-1 25.91 3 220 0.85 80.0 1 80.0 XLPE 4C 70 247 0.82 0.7 0.57 141.78 100

20 ACDB BUS-A 48V DC BATTERY CHARGER-1 8.50 3 220 0.85 26.2 1 26.2 XLPE 4C 10 73 0.91 0.45 0.41 29.89 63

21 ACDB BUS-A HVAC CONTROL PANEL 15.00 3 220 0.85 46.3 1 46.3 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63

LIGHTING & SOCKETS,ONLINE GAS ANALYSER


22 ACDB BUS-A 0.425 3 220 0.85 1.3 1 1.3 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32
REACTOR-1

LIGHTING & SOCKETS,ONLINE GAS ANALYSER


23 ACDB BUS-A 0.425 3 220 0.85 1.3 1 1.3 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32
REACTOR-2

SGT-1 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil


24 ACDB BUS-A 3.732 1 220 0.85 20.0 1 20.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32
Monitor & Receptacle)

25 ACDB BUS-A SGT-1 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

26 ACDB BUS-A SGT-2 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

27 ACDB BUS-A SGT-5 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

28 ACDB BUS-A SUMP PUMP CONTROL BLD BASEMENT 1.800 3 220 0.85 5.6 1 5.6 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

SUMP PUMP TUNNEL-A1


29 ACDB BUS-A (380KV CONTROL CABLES TUNNEL) 3.60 3 220 0.85 11.1 1 11.1 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

30 ACDB BUS-A REACTOR -1 PIT PUMP 2.98 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

31 ACDB BUS-A AUXILIARY SUPPLY FOR GT-1 2.914 3 220 0.85 9.0 1 9.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

PANEL : MAIN DISTRIBUTION BOARD BUS-B 220/127V AC

CE-113347, REV.01 14 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

32 ACDB BUS-B HVAC PANEL-3(LOC -132KV GIS BLD) 210.17 3 220 0.85 648.9 4 162.2 XLPE 1C 630 1117 0.91 0.7 0.64 711.53 800

33 ACDB BUS-B INDOOR LIGHTING PANEL -1( LOC -CONTROL ROOM) 134.190 3 220 0.85 414.3 2 207.1 XLPE 4C 150 407 0.91 0.7 0.64 259.26 500

34 ACDB BUS-B INDOOR LIGHTING PANEL -2( LOC -AC/DC ROOM) 130.770 3 220 0.85 403.7 2 201.9 XLPE 4C 120 355 0.91 0.7 0.64 226.14 500

35 ACDB BUS-B OUTDOOR LIGHTING PANEL-2 (LOC -380KV GIS ROOM) 117.90 3 220 0.85 364.0 2 182.0 XLPE 1C 630 1117 0.91 0.7 0.64 711.53 500

36 ACDB BUS-B OUTDOOR LIGHTING PANEL -3( LOC -132KV GIS ROOM) 66.06 3 220 0.85 204.0 2 102.0 XLPE 4C 240 551 0.91 0.7 0.64 350.99 320

37 ACDB BUS-B SDB-1A (LOC -380KV GIS BLD) 67.77 3 220 0.85 143.0 2 71.5 XLPE 4C 95 305 0.91 0.7 0.64 194.29 320

38 ACDB BUS-B SDB-2 (LOC -132KV GIS BLD) 75.449 3 220 0.85 232.9 3 77.6 XLPE 4C 185 469 0.91 0.7 0.64 298.75 320

OIL FILTERATION SOCKET FOR AUXILIARY


39 ACDB BUS-B 77.74 3 220 0.85 240.00 2 120.0 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320
TRANSFORMER

125V DC BATTERY CHARGER-2


40 ACDB BUS-B 62.50 3 220 0.85 193.0 1 193.0 XLPE 4C 120 355 0.91 0.7 0.64 226.14 250
(380KV DC SYSTEM BATTERY CHARGER)

41 ACDB BUS-B OUTDOOR LIGHTING PANEL-1 (LOC -AC/DC ROOM) 45.90 3 220 0.85 141.7 1 141.7 XLPE 4C 70 247 0.91 0.7 0.64 157.34 200

42 ACDB BUS-B SDB-1B (LOC -380KV GIS BLD) 43.937 3 220 0.85 135.6 2 67.8 XLPE 4C 185 469 0.91 0.7 0.64 298.75 200

43 ACDB BUS-B INDOOR LIGHTING PANEL -3( LOC -380KV GIS ROOM) 50.360 3 220 0.85 155.5 1 155.5 XLPE 4C 150 407 0.91 0.7 0.64 259.26 200

44 ACDB BUS-B INDOOR LIGHTING PANEL -4( LOC -380KV GIS ROOM) 50.360 3 220 0.85 155.5 2 77.7 XLPE 4C 150 407 0.91 0.7 0.64 259.26 200

45 ACDB BUS-B INDOOR LIGHTING PANEL -5( LOC -132KV GIS ROOM) 50.360 3 220 0.85 155.5 2 77.7 XLPE 4C 185 469 0.91 0.7 0.64 298.75 200

PORTABLE 125V DC BATTERY CHARGER


46 ACDB BUS-B 31.250 3 220 0.85 96.48 1 96.5 XLPE 4C 35 160 0.91 0.7 0.64 101.92 125
(132KV DC SYSTEM BATTERY CHARGER)

47 ACDB BUS-B 100A WELDING RECEPTACLE AT HVAC PACU-2 25.91 3 220 0.85 80.0 1 80.0 XLPE 4C 70 247 0.91 0.7 0.64 157.34 100

48 ACDB BUS-B 48V DC BATTERY CHARGER-2 8.50 3 220 0.85 26.2 1 26.2 XLPE 4C 10 73 0.91 0.45 0.41 29.89 63

CE-113347, REV.01 15 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp
SGT-2 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil
49 ACDB BUS-B 3.732 1 220 0.85 11.5 1 11.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32
Monitor & Receptacle)

SGT-5 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil


50 ACDB BUS-B 3.732 1 220 0.85 11.5 1 11.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32
Monitor & Receptacle)
SUMP PUMP TUNNEL-B1
51 ACDB BUS-B (132KV CONTROL CABLES TUNNEL) 3.600 3 220 0.85 11.1 1 11.1 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20

52 ACDB BUS-B SGT-1 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

53 ACDB BUS-B SGT-2 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

54 ACDB BUS-B SGT-5 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

55 ACDB BUS-B SGT-1 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

56 ACDB BUS-B SGT-2 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

57 ACDB BUS-B SGT-5 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

58 ACDB BUS-B WATER TRANSFER PUMP 2.237 3 220 0.85 6.9 1 6.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

59 ACDB BUS-B LIGHTING SIGN BOARD 0.550 3 220 0.85 1.7 1 1.7 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

60 ACDB BUS-B GATE HOUSE LIGHTING 0.392 4 127 0.85 2.1 1 2.1 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

61 ACDB BUS-B AUXILIARY SUPPLY FOR GT-2 2.914 3 220 0.85 9.0 1 9.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

PANEL : MAIN DISTRIBUTION BOARD BUS-C 220/127V AC

62 ACDB BUS-C HVAC PANEL-2(LOC -380KV GIS BLD) 309.22 3 220 0.85 954.7 5 190.9 XLPE 1C 630 1117 0.91 0.7 0.64 711.53 1250

63 ACDB BUS-C HVAC PANEL-1(LOC -CONTROL BLD) 195.72 3 220 0.85 604.2 2 302.1 XLPE 4C 240 551 0.91 0.7 0.64 350.99 800

64 ACDB BUS-C 300A OIL FILTERATION SOCKET (TRF AREA) 77.74 3 220 0.85 240.0 1 240.0 XLPE 4C 150 407 0.91 0.7 0.64 259.26 320

CE-113347, REV.01 16 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp
125V DC BATTERY CHARGER-1
65 ACDB BUS-C 62.50 3 220 0.85 193.0 1 193.0 XLPE 4C 120 355 0.91 0.7 0.64 226.14 250
(380KV DC SYSTEM BATTERY CHARGER)

66 ACDB BUS-C OUTDOOR LIGHTING PANEL-1 (LOC -AC/DC ROOM) 45.90 3 220 0.85 141.7 1 141.7 XLPE 4C 70 247 0.91 0.7 0.64 157.34 200

67 ACDB BUS-C INDOOR LIGHTING PANEL -3( LOC -380KV GIS ROOM) 50.360 3 220 0.85 155.5 1 155.5 XLPE 4C 150 407 0.91 0.7 0.64 259.26 200

68 ACDB BUS-C INDOOR LIGHTING PANEL -4( LOC -380KV GIS ROOM) 50.360 3 220 0.85 155.5 2 77.7 XLPE 4C 150 407 0.91 0.7 0.64 259.26 200

PORTABLE 125V DC BATTERY CHARGER


69 ACDB BUS-C 31.250 3 220 0.85 96.48 1 96.5 XLPE 4C 35 160 0.91 0.7 0.64 101.92 125
(132KV DC SYSTEM BATTERY CHARGER)

70 ACDB BUS-C 100A RECEPTACLE FOR TRF AREA 25.91 3 220 0.85 80.0 1 80.0 XLPE 4C 50 195 0.91 0.7 0.64 124.22 100

71 ACDB BUS-C 100A RECEPTACLE FOR REACTOR AREA 25.91 3 220 0.85 80.0 1 80.0 XLPE 4C 50 195 0.91 0.7 0.64 124.22 100

72 ACDB BUS-C SGT-2 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100

73 ACDB BUS-C SGT-2 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100

74 ACDB BUS-C SGT-4 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100

75 ACDB BUS-C SGT-4 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100

SGT-3 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil


76 ACDB BUS-C 3.732 1 220 0.85 11.5 1 11.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32
Monitor & Receptacle)

SGT-4 MK ( Lamp , Heater , Thermostat , Moisture-In-Oil


77 ACDB BUS-C 3.732 1 220 0.85 11.5 1 11.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32
Monitor & Receptacle)

78 ACDB BUS-C SGT-3 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

79 ACDB BUS-C SGT-4 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

80 ACDB BUS-C SGT-3 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

81 ACDB BUS-C SGT-4 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

CE-113347, REV.01 17 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

82 ACDB BUS-C SGT-3 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

83 ACDB BUS-C SGT-4 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

84 ACDB BUS-C BOASTER PUMP 2.237 3 220 0.85 6.9 1 6.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

85 ACDB BUS-C AUXILIARY SUPPLY FOR GT-3 2.914 3 220 0.85 9.0 1 9.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

86 ACDB BUS-C AUXILIARY SUPPLY FOR GT-4 2.914 3 220 0.85 9.0 1 9.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20

SUB-DISTRIBUTION BOARD-1A (BUS-A)

SDB-1A
87 100A,HIGH VOLTAGE TEST SOCKET-1 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 25 130 0.91 0.7 0.64 82.81 100
( BUS-A)

SDB-1A
88 100A,RECEPTACLE AT HVAC PACU-3 25.91 3 220 0.85 80.00 1 80.00 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100
( BUS-A)

SDB-1A
89 63A,GAS FILLING RECEPTACLE-1 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63
( BUS-A)
SUMP PUMP TUNNEL-A1
SDB-1A
90 (380KV CONTROL CABLES TUNNEL) 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)
SUMP PUMP TUNNEL-A2
SDB-1A
91 (380KV CONTROL CABLES TUNNEL) 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-1A
92 380KV LCC (C02-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-1A
93 380KV LCC (C02-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-1A
94 380KV LCC (C02-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-1A
95 380KV LCC (C03-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

CE-113347, REV.01 18 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

SDB-1A
96 380KV LCC (C03-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-1A
97 380KV LCC (C03-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-1A
98 380KV LCC (C04-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-1A
99 380KV LCC (C04-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-1A
100 380KV LCC (C04-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SUB-DISTRIBUTION BOARD-1A (BUS-B)

SDB-1A
101 100A,HIGH VOLTAGE TEST SOCKET-2 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 70 247 0.91 0.7 0.64 157.34 100
( BUS-B)

SDB-1A
102 HVAC CONTROL PANEL-2(380KV GIS BLD) 20.000 3 220 0.85 61.75 1 61.75 XLPE 4C 25 130 0.91 0.7 0.64 82.81 100
( BUS-B)

SDB-1A
103 EOT CRANE 6.750 3 220 0.85 20.84 1 20.84 XLPE 4C 10 73 0.91 0.45 0.41 29.89 63
( BUS-B)

SDB-1A SUMP PUMP TUNNEL-A3


104 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B) (380KV O/G CABLES TUNNEL)

SDB-1A
105 ROLLING SHUTTER MOTOR-1 1.70 3 220 0.85 5.25 1 5.25 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A
106 380KV OUTDOOR CT'S MISCELLANEOUS HEATERS 2.610 3 220 0.85 8.06 1 8.06 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A
107 380KV LCC (C05-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A
108 380KV LCC (C05-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A
109 380KV LCC (C05-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

CE-113347, REV.01 19 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

SDB-1A
110 380KV LCC (C06-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A
111 380KV LCC (C06-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A
112 380KV LCC (C06-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A
113 380KV LCC (C07-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A
114 380KV LCC (C07-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A
115 380KV LCC (C07-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SUB-DISTRIBUTION BOARD-1B (BUS-A)

SDB-1B
116 100A,RECEPTACLE AT HVAC PACU-2 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100
( BUS-A)

SDB-1B
117 63A,GAS FILLING RECEPTACLE-2 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63
( BUS-A)

SDB-1B
118 380KV OUTDOOR CT'S MISCELLANEOUS HEATERS 1.740 3 220 0.85 5.37 1 5.37 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20
( BUS-A)

SUB-DISTRIBUTION BOARD-1B (BUS-B)

SDB-1B
119 100A,RECEPTACLE AT HVAC PACU-1 25.91 3 220 0.85 80.00 1 80.00 XLPE 4C 50 195 0.82 0.7 0.57 111.93 100
( BUS-B)

SDB-1B
120 63A,GAS FILLING RECEPTACLE-3 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63
( BUS-B)

SDB-1B
121 ROLLING SHUTTER MOTOR-2 1.70 3 220 0.85 5.25 1 5.25 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SUB-DISTRIBUTION BOARD-2 (BUS-A)

CE-113347, REV.01 20 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

SDB-2
122 100A,RECEPTACLE AT HVAC UNITS -1 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100
( BUS-A)

SDB-2
123 63A,GAS FILLING RECEPTACLES # 1,2,3 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 25 130 0.91 0.7 0.64 82.81 63
( BUS-A)

SDB-2
124 EOT CRANE 6.750 3 220 0.85 20.84 1 20.84 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63
( BUS-A)

SDB-2
125 ROLLING SHUTTER MOTOR DOOR-1 1.70 3 220 0.85 5.25 1 5.25 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-2
126 SUMP PUMP-1&2 132KV GIS BASEMENT 3.60 3 220 0.85 11.11 1 11.11 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-A)

SDB-1A SUMP PUMP TUNNEL-B2


127 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B) (132KV O/G CABLES TUNNEL)

SUB-DISTRIBUTION BOARD-2 (BUS-B)

SDB-2
128 100A,RECEPTACLE AT HVAC UNITS -2 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 70 247 0.82 0.45 0.37 91.14 100
( BUS-B)

SDB-2
129 100A,RECEPTACLE AT HVAC UNITS -3 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 70 247 0.82 0.45 0.37 91.14 100
( BUS-B)

SDB-2
130 63A,GAS FILLING RECEPTACLES # 4,5,6 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63
( BUS-B)

SDB-2
131 HVAC CONTROL PANEL-2(132KV GIS BLD) 2.00 3 220 0.85 6.17 1 6.17 XLPE 4C 10 73 0.91 0.45 0.41 29.89 63
( BUS-B)

SDB-2
132 SUMP PUMP-3 132KV GIS BASEMENT 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-2
133 ROLLING SHUTTER MOTOR DOOR-2 1.70 3 220 0.85 5.25 1 5.25 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B)

SDB-1A SUMP PUMP TUNNEL-B3


134 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
( BUS-B) (132KV O/G CABLES TUNNEL)

HVAC PANEL-1

CE-113347, REV.01 21 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

135 HVAC-1 PACU-1A (DUTY) 68.300 3 220 0.85 210.87 1 210.87 XLPE 4C 150 407 0.82 0.7 0.57 233.62 320

136 HVAC-1 PACU-2A (DUTY) 73.470 3 220 0.85 226.83 1 226.83 XLPE 4C 185 469 0.82 0.7 0.57 269.21 320

137 HVAC-1 PACU-1B (STANDBY) 68.300 3 220 0.85 210.87 1 210.87 XLPE 4C 150 407 0.82 0.7 0.57 233.62 320

138 HVAC-1 PACU-2B (STANDBY) 73.470 3 220 0.85 226.83 1 226.83 XLPE 4C 185 469 0.82 0.7 0.57 269.21 320

139 HVAC-1 ELECTRIC DUCT HEATER (AC/DC ROOM) 45.000 3 220 0.85 138.93 1 138.93 XLPE 4C 70 247 0.91 0.7 0.64 157.34 200

SUPPLY FAN- TUNNEL A1


140 HVAC-1 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(380KV CONTROL CABELS TUNNEL)

EXHAUST FAN- TUNNEL A1


141 HVAC-1 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(380KV CONTROL CABELS TUNNEL)

SUPPLY FAN- TUNNEL B1


142 HVAC-1 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(132KV CONTROL CABELS TUNNEL)

EXHAUST FAN- TUNNEL B1


143 HVAC-1 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(132KV CONTROL CABELS TUNNEL)

HVAC PANEL-2

144 HVAC-2 PACU-1A (DUTY) 100.090 3 220 0.85 309.01 1 309.01 XLPE 4C 240 551 0.82 0.7 0.57 316.27 400

145 HVAC-2 PACU-2A (DUTY) 100.090 3 220 0.85 309.01 2 154.51 XLPE 4C 185 469 0.82 0.7 0.57 269.21 400

146 HVAC-2 PACU-3A (DUTY) 100.090 3 220 0.85 309.01 1 309.01 XLPE 4C 240 551 0.82 0.7 0.57 316.27 400

147 HVAC-2 PACU-1B (STANDBY) 100.090 3 220 0.85 309.01 1 309.01 XLPE 4C 240 551 0.82 0.7 0.57 316.27 400

148 HVAC-2 PACU-2B (STANDBY) 100.090 3 220 0.85 309.01 2 154.51 XLPE 4C 185 469 0.82 0.7 0.57 269.21 400

CE-113347, REV.01 22 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

149 HVAC-2 PACU-3B (STANDBY) 100.090 3 220 0.85 309.01 1 309.01 XLPE 4C 240 551 0.82 0.7 0.57 316.27 400

SUPPLY FAN- TUNNEL A2


150 HVAC-2 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(380KV CONTROL CABELS TUNNEL)

EXHAUST FAN- TUNNEL A2


151 HVAC-2 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 16 96 0.91 0.45 0.41 39.31 20
(380KV CONTROL CABELS TUNNEL)

SUPPLY FAN- TUNNEL A3


152 HVAC-2 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(380KV O/G CABLES TUNNEL)

EXHAUST FAN- TUNNEL A3


153 HVAC-2 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(380KV O/G CABLES TUNNEL)

HVAC PANEL-3

154 HVAC-3 PACU-1A (DUTY) 132KV GIS HALL 65.170 3 220 0.85 201.20 1 201.20 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320

155 HVAC-3 PACU-2A (DUTY) 132KV GIS HALL 65.170 3 220 0.85 201.20 1 201.20 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320

156 HVAC-3 PACU-3A (DUTY) 132KV GIS BASEMENT 70.880 3 220 0.85 218.83 1 218.83 XLPE 4C 150 407 0.82 0.7 0.57 233.62 320

157 HVAC-3 PACU-1B (STANDBY) 132KV GIS HALL 65.170 3 220 0.85 201.20 1 201.20 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320

158 HVAC-3 PACU-2B (STANDBY) 132KV GIS HALL 65.170 3 220 0.85 201.20 1 201.20 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320

159 HVAC-3 PACU-3B (STANDBY) 132KV GIS BASEMENT 70.880 3 220 0.85 218.83 1 218.83 XLPE 4C 150 407 0.82 0.7 0.57 233.62 320

SUPPLY FAN- TUNNEL B2


160 HVAC-3 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(132KV O/G CABLES TUNNEL)

EXHAUST FAN- TUNNEL B2


161 HVAC-3 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(132KV O/G CABLES TUNNEL)

SUPPLY FAN- TUNNEL B3


162 HVAC-3 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(132KV O/G CABLES TUNNEL)

CE-113347, REV.01 23 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company


Central Operating Area

LV AC CABLE SIZING CALCULATION


Derating Factors: %VD = (Voltage Drop / Supply Voltage
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated


I Selected Cable C.B current
S.No. From To KW Phase VOLT PF cables I req. Over current
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp

EXHAUST FAN- TUNNEL B3


163 HVAC-3 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20
(132KV O/G CABLES TUNNEL)

TELECOM ROOM ACDB

TELECOM
164 SMK PANELS LIGHT & HEATER 10.36 3 220 0.85 32.00 1 32.00 XLPE 4C 16 96 0.91 0.7 0.64 61.15 40
ACDB

TELECOM
165 FMK PANELS LIGHT & HEATER 10.36 3 220 0.85 32.00 1 32.00 XLPE 4C 16 96 0.91 0.7 0.64 61.15 40
ACDB

TELECOM
166 RTU PANELS LIGHT & HEATER 10.36 3 220 0.85 32.00 1 32.00 XLPE 4C 16 96 0.91 0.7 0.64 61.15 40
ACDB

CE-113347, REV.01 24 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


52 0.16 0.09 1.56 %VD is <1.6% Hence Safe

FL Current<Derated Current &


16 0.20 0.09 0.55 %VD is <1.6% Hence Safe

FL Current<Derated Current &


130 0.04 0.09 1.56 %VD is <1.6% Hence Safe

FL Current<Derated Current &


130 0.10 0.09 1.38 %VD is <1.6% Hence Safe

FL Current<Derated Current &


65 0.13 0.09 1.94 %VD is <4.2% Hence Safe

FL Current<Derated Current &


85 0.16 0.09 1.53 %VD is <1.6% Hence Safe

FL Current<Derated Current &


150 0.10 0.09 1.35 %VD is <1.6% Hence Safe

FL Current<Derated Current &


18 0.20 0.09 0.59 %VD is <4.2% Hence Safe

FL Current<Derated Current &


175 0.13 0.09 1.47 %VD is <1.6% Hence Safe

FL Current<Derated Current &


165 0.13 0.09 1.59 %VD is <1.6% Hence Safe

FL Current<Derated Current &


26 0.67 0.10 1.22 %VD is <1.6% Hence Safe

FL Current<Derated Current &


22 0.67 0.10 1.04 %VD is <4.2% Hence Safe

FL Current<Derated Current &


60 0.93 0.10 2.20 %VD is <4.2% Hence Safe

FL Current<Derated Current &


60 0.93 0.10 2.20 %VD is <4.2% Hence Safe

FL Current<Derated Current &


110 0.93 0.10 4.03 %VD is <4.2% Hence Safe

CE-113347, REV.01 25 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


110 0.93 0.10 4.03 %VD is <4.2% Hence Safe

FL Current<Derated Current &


160 0.49 0.10 3.28 %VD is <4.2% Hence Safe

FL Current<Derated Current &


160 0.49 0.10 3.28 %VD is <4.2% Hence Safe

FL Current<Derated Current &


30 0.34 0.10 0.65 %VD is <4.2% Hence Safe

FL Current<Derated Current &


25 2.33 0.11 1.05 %VD is <4.2% Hence Safe

FL Current<Derated Current &


10 1.47 0.11 0.47 %VD is <4.2% Hence Safe

FL Current<Derated Current &


75 2.33 0.11 0.16 %VD is <4.2% Hence Safe

FL Current<Derated Current &


90 2.33 0.11 0.19 %VD is <4.2% Hence Safe

FL Current<Derated Current &


60 2.33 0.11 2.22 %VD is <4.2% Hence Safe

FL Current<Derated Current &


60 2.33 0.11 0.89 %VD is <4.2% Hence Safe

FL Current<Derated Current &


80 2.33 0.11 1.18 %VD is <4.2% Hence Safe

FL Current<Derated Current &


160 2.33 0.11 2.37 %VD is <4.2% Hence Safe

FL Current<Derated Current &


21 2.33 0.11 0.19 %VD is <4.2% Hence Safe

FL Current<Derated Current &


60 2.33 0.11 1.07 %VD is <4.2% Hence Safe

FL Current<Derated Current &


75 2.33 0.11 1.11 %VD is <4.2% Hence Safe

FL Current<Derated Current &


57 2.33 0.11 0.82 %VD is <4.2% Hence Safe

CE-113347, REV.01 26 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


137 0.04 0.09 1.46 %VD is <1.6% Hence Safe

FL Current<Derated Current &


52 0.16 0.09 1.56 %VD is <1.6% Hence Safe

FL Current<Derated Current &


16 0.20 0.09 0.55 %VD is <1.6% Hence Safe

FL Current<Derated Current &


130 0.04 0.09 1.56 %VD is <1.6% Hence Safe

FL Current<Derated Current &


130 0.10 0.09 1.38 %VD is <1.6% Hence Safe

FL Current<Derated Current &


85 0.25 0.09 1.24 %VD is <1.6% Hence Safe

FL Current<Derated Current &


150 0.13 0.09 1.44 %VD is <1.6% Hence Safe

FL Current<Derated Current &


10 0.20 0.09 0.20 %VD is <1.6% Hence Safe

FL Current<Derated Current &


18 0.20 0.09 0.59 %VD is <4.2% Hence Safe

FL Current<Derated Current &


16 0.34 0.10 0.61 %VD is <1.6% Hence Safe

FL Current<Derated Current &


175 0.13 0.09 1.47 %VD is <1.6% Hence Safe

FL Current<Derated Current &


70 0.16 0.09 1.58 %VD is <1.6% Hence Safe

FL Current<Derated Current &


137 0.16 0.09 1.54 %VD is <1.6% Hence Safe

FL Current<Derated Current &


165 0.13 0.09 1.59 %VD is <1.6% Hence Safe

FL Current<Derated Current &


22 0.67 0.10 1.04 %VD is <4.2% Hence Safe

FL Current<Derated Current &


195 0.34 0.10 4.20 %VD is <4.2% Hence Safe

FL Current<Derated Current &


25 2.33 0.11 1.05 %VD is <4.2% Hence Safe

CE-113347, REV.01 27 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


80 2.33 0.11 1.71 %VD is <4.2% Hence Safe

FL Current<Derated Current &


160 2.33 0.11 3.42 %VD is <4.2% Hence Safe

FL Current<Derated Current &


31 2.33 0.11 0.55 %VD is <4.2% Hence Safe

FL Current<Derated Current &


60 2.33 0.11 0.86 %VD is <4.2% Hence Safe

FL Current<Derated Current &


80 2.33 0.11 1.15 %VD is <4.2% Hence Safe

FL Current<Derated Current &


160 2.33 0.11 2.29 %VD is <4.2% Hence Safe

FL Current<Derated Current &


60 2.33 0.11 0.05 %VD is <4.2% Hence Safe

FL Current<Derated Current &


80 2.33 0.11 0.07 %VD is <4.2% Hence Safe

FL Current<Derated Current &


160 2.33 0.11 0.13 %VD is <4.2% Hence Safe

FL Current<Derated Current &


60 2.33 0.11 0.67 %VD is <4.2% Hence Safe

FL Current<Derated Current &


300 2.33 0.11 0.82 %VD is <4.2% Hence Safe

FL Current<Derated Current &


290 2.33 0.11 1.95 %VD is <4.2% Hence Safe

FL Current<Derated Current &


105 2.33 0.11 1.52 %VD is <4.2% Hence Safe

FL Current<Derated Current &


120 0.04 0.09 1.51 %VD is <1.6% Hence Safe

FL Current<Derated Current &


40 0.10 0.09 1.25 %VD is <1.6% Hence Safe

FL Current<Derated Current &


110 0.16 0.09 3.82 %VD is <4.2% Hence Safe

CE-113347, REV.01 28 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


18 0.20 0.09 0.59 %VD is <4.2% Hence Safe

FL Current<Derated Current &


16 0.34 0.10 0.61 %VD is <1.6% Hence Safe

FL Current<Derated Current &


70 0.16 0.09 1.58 %VD is <1.6% Hence Safe

FL Current<Derated Current &


137 0.16 0.09 1.54 %VD is <1.6% Hence Safe

FL Current<Derated Current &


22 0.67 0.10 1.04 %VD is <4.2% Hence Safe

FL Current<Derated Current &


110 0.49 0.10 3.27 %VD is <4.2% Hence Safe

FL Current<Derated Current &


65 0.49 0.10 1.93 %VD is <4.2% Hence Safe

FL Current<Derated Current &


80 0.93 0.10 2.93 %VD is <4.2% Hence Safe

FL Current<Derated Current &


80 0.93 0.10 2.93 %VD is <4.2% Hence Safe

FL Current<Derated Current &


135 0.67 0.10 3.64 %VD is <4.2% Hence Safe

FL Current<Derated Current &


135 0.67 0.10 3.64 %VD is <4.2% Hence Safe

FL Current<Derated Current &


110 2.33 0.11 2.35 %VD is <4.2% Hence Safe

FL Current<Derated Current &


135 2.33 0.11 2.88 %VD is <4.2% Hence Safe

FL Current<Derated Current &


110 2.33 0.11 1.63 %VD is <4.2% Hence Safe

FL Current<Derated Current &


135 2.33 0.11 2.00 %VD is <4.2% Hence Safe

FL Current<Derated Current &


110 2.33 0.11 1.58 %VD is <4.2% Hence Safe

FL Current<Derated Current &


135 2.33 0.11 1.93 %VD is <4.2% Hence Safe

CE-113347, REV.01 29 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


110 2.33 0.11 0.09 %VD is <4.2% Hence Safe

FL Current<Derated Current &


135 2.33 0.11 0.11 %VD is <4.2% Hence Safe

FL Current<Derated Current &


60 2.33 0.11 0.67 %VD is <4.2% Hence Safe

FL Current<Derated Current &


133 2.33 0.11 1.92 %VD is <4.2% Hence Safe

FL Current<Derated Current &


161 2.33 0.11 2.33 %VD is <4.2% Hence Safe

FL Current<Derated Current &


18 0.93 0.10 0.95 %VD is <2.6% Hence Safe

FL Current<Derated Current &


35 0.67 0.10 1.37 %VD is <2.6% Hence Safe

FL Current<Derated Current &


30 1.47 0.11 1.55 %VD is <2.6% Hence Safe

FL Current<Derated Current &


115 2.33 0.11 1.03 %VD is <2.6% Hence Safe

FL Current<Derated Current &


120 2.33 0.11 1.07 %VD is <2.6% Hence Safe

FL Current<Derated Current &


40 2.33 0.11 0.20 %VD is <2.6% Hence Safe

FL Current<Derated Current &


40 2.33 0.11 0.20 %VD is <2.6% Hence Safe

FL Current<Derated Current &


40 2.33 0.11 0.20 %VD is <2.6% Hence Safe

FL Current<Derated Current &


54 2.33 0.11 0.27 %VD is <2.6% Hence Safe

CE-113347, REV.01 30 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


54 2.33 0.11 0.27 %VD is <2.6% Hence Safe

FL Current<Derated Current &


54 2.33 0.11 0.27 %VD is <2.6% Hence Safe

FL Current<Derated Current &


68 2.33 0.11 0.34 %VD is <2.6% Hence Safe

FL Current<Derated Current &


68 2.33 0.11 0.34 %VD is <2.6% Hence Safe

FL Current<Derated Current &


68 2.33 0.11 0.34 %VD is <2.6% Hence Safe

FL Current<Derated Current &


90 0.34 0.10 1.94 %VD is <2.6% Hence Safe

FL Current<Derated Current &


60 0.93 0.10 2.46 %VD is <2.6% Hence Safe

FL Current<Derated Current &


25 2.33 0.11 0.84 %VD is <2.6% Hence Safe

FL Current<Derated Current &


115 2.33 0.11 1.03 %VD is <2.6% Hence Safe

FL Current<Derated Current &


25 2.33 0.11 0.21 %VD is <2.6% Hence Safe

FL Current<Derated Current &


95 2.33 0.11 1.23 %VD is <2.6% Hence Safe

FL Current<Derated Current &


82 2.33 0.11 0.41 %VD is <2.6% Hence Safe

FL Current<Derated Current &


82 2.33 0.11 0.41 %VD is <2.6% Hence Safe

FL Current<Derated Current &


82 2.33 0.11 0.41 %VD is <2.6% Hence Safe

CE-113347, REV.01 31 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


96 2.33 0.11 0.48 %VD is <2.6% Hence Safe

FL Current<Derated Current &


96 2.33 0.11 0.48 %VD is <2.6% Hence Safe

FL Current<Derated Current &


96 2.33 0.11 0.48 %VD is <2.6% Hence Safe

FL Current<Derated Current &


110 2.33 0.11 0.55 %VD is <2.6% Hence Safe

FL Current<Derated Current &


110 2.33 0.11 0.55 %VD is <2.6% Hence Safe

FL Current<Derated Current &


110 2.33 0.11 0.55 %VD is <2.6% Hence Safe

FL Current<Derated Current &


30 0.67 0.10 1.17 %VD is <2.6% Hence Safe

FL Current<Derated Current &


40 1.47 0.11 2.07 %VD is <2.6% Hence Safe

FL Current<Derated Current &


95 2.33 0.11 0.82 %VD is <2.6% Hence Safe

FL Current<Derated Current &


75 0.49 0.10 2.23 %VD is <2.6% Hence Safe

FL Current<Derated Current &


20 1.47 0.11 1.03 %VD is <2.6% Hence Safe

FL Current<Derated Current &


35 2.33 0.11 0.30 %VD is <2.6% Hence Safe

CE-113347, REV.01 32 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


35 0.67 0.10 1.37 %VD is <2.6% Hence Safe

FL Current<Derated Current &


70 0.93 0.10 2.34 %VD is <2.6% Hence Safe

FL Current<Derated Current &


95 1.47 0.11 2.03 %VD is <2.6% Hence Safe

FL Current<Derated Current &


90 2.33 0.11 0.76 %VD is <2.6% Hence Safe

FL Current<Derated Current &


80 2.33 0.11 1.43 %VD is <2.6% Hence Safe

FL Current<Derated Current &


195 2.33 0.11 1.74 %VD is <2.6% Hence Safe

FL Current<Derated Current &


65 0.34 0.10 1.40 %VD is <2.6% Hence Safe

FL Current<Derated Current &


55 0.34 0.10 1.18 %VD is <2.6% Hence Safe

FL Current<Derated Current &


45 1.47 0.11 2.32 %VD is <2.6% Hence Safe

FL Current<Derated Current &


40 2.33 0.11 0.40 %VD is <2.6% Hence Safe

FL Current<Derated Current &


90 2.33 0.11 0.80 %VD is <2.6% Hence Safe

FL Current<Derated Current &


40 2.33 0.11 0.34 %VD is <2.6% Hence Safe

FL Current<Derated Current &


155 2.33 0.11 1.38 %VD is <2.6% Hence Safe

CE-113347, REV.01 33 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


62 0.16 0.09 1.89 %VD is <2.6% Hence Safe

FL Current<Derated Current &


92 0.13 0.09 2.59 %VD is <2.6% Hence Safe

FL Current<Derated Current &


62 0.16 0.09 1.89 %VD is <2.6% Hence Safe

FL Current<Derated Current &


92 0.13 0.09 2.59 %VD is <2.6% Hence Safe

FL Current<Derated Current &


30 0.34 0.10 1.12 %VD is <2.6% Hence Safe

FL Current<Derated Current &


60 2.33 0.11 0.67 %VD is <2.6% Hence Safe

FL Current<Derated Current &


60 2.33 0.11 0.67 %VD is <2.6% Hence Safe

FL Current<Derated Current &


50 2.33 0.11 0.55 %VD is <2.6% Hence Safe

FL Current<Derated Current &


50 2.33 0.11 0.55 %VD is <2.6% Hence Safe

FL Current<Derated Current &


35 0.10 0.09 1.12 %VD is <2.6% Hence Safe

FL Current<Derated Current &


120 0.13 0.09 2.30 %VD is <2.6% Hence Safe

FL Current<Derated Current &


70 0.10 0.09 2.24 %VD is <2.6% Hence Safe

FL Current<Derated Current &


35 0.10 0.09 1.12 %VD is <2.6% Hence Safe

FL Current<Derated Current &


120 0.13 0.09 2.30 %VD is <2.6% Hence Safe

CE-113347, REV.01 34 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


70 0.10 0.09 2.24 %VD is <2.6% Hence Safe

FL Current<Derated Current &


120 2.33 0.11 1.33 %VD is <2.6% Hence Safe

FL Current<Derated Current &


120 1.47 0.11 0.85 %VD is <2.6% Hence Safe

FL Current<Derated Current &


115 2.33 0.11 1.28 %VD is <2.6% Hence Safe

FL Current<Derated Current &


115 2.33 0.11 1.28 %VD is <2.6% Hence Safe

FL Current<Derated Current &


50 0.20 0.09 1.71 %VD is <2.6% Hence Safe

FL Current<Derated Current &


55 0.20 0.09 1.88 %VD is <2.6% Hence Safe

FL Current<Derated Current &


40 0.16 0.09 1.27 %VD is <2.6% Hence Safe

FL Current<Derated Current &


50 0.20 0.09 1.71 %VD is <2.6% Hence Safe

FL Current<Derated Current &


55 0.20 0.09 1.88 %VD is <2.6% Hence Safe

FL Current<Derated Current &


40 0.16 0.09 1.27 %VD is <2.6% Hence Safe

FL Current<Derated Current &


190 2.33 0.11 2.11 %VD is <2.6% Hence Safe

FL Current<Derated Current &


190 2.33 0.11 2.11 %VD is <2.6% Hence Safe

FL Current<Derated Current &


160 2.33 0.11 1.78 %VD is <2.6% Hence Safe

CE-113347, REV.01 35 of 42
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

‫الشركة السعودية للكهرباء‬


‫منطقة أعمال الوسطى‬
LE SIZING CALCULATION
%VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )

L = Route length in meter.

R X
Length %VD Remarks
m Ohm/kM Ohm/kM

FL Current<Derated Current &


160 2.33 0.11 1.78 %VD is <2.6% Hence Safe

FL Current<Derated Current &


20 1.47 0.11 0.66 %VD is <2.6% Hence Safe

FL Current<Derated Current &


25 1.47 0.11 0.82 %VD is <2.6% Hence Safe

FL Current<Derated Current &


30 1.47 0.11 0.98 %VD is <2.6% Hence Safe

CE-113347, REV.01 36 of 42
85 C 2-CORE, PVC',
conductor current voltage R90 AC
size rating mV/A/m
PVC 2C 1.5 PVC2CX1.5 21 21.22 15.19
PVC 2C 2.5 PVC2CX2.5 28 13.04 9.3
PVC 2C 4 PVC2CX4 33 8.16 5.79
PVC 2C 6 PVC2CX6 48 5.49 3.87
PVC 2C 10 PVC2CX10 66 3.3 2.3
PVC 2C 16 PVC2CX16 88 2.11 1.44
PVC 2C 25 PVC2CX25 118 1.37 0.91
PVC 2C 35 PVC2CX35 145 1.01 0.66
PVC 2C 50 PVC2CX50 177 0.78 0.49
PVC 2C 70 PVC2CX70 224 0.57 0.34
PVC 2C 95 PVC2CX95 274 0.44 0.24
PVC 2C 120 PVC2CX120 318 0.36 0.19
PVC 2C 150 PVC2CX150 365 0.31 0.16
PVC 2C 185 PVC2CX185 420 0.27 0.13
PVC 2C 240 PVC2CX240 493 0.23 0.1
PVC 2C 300 PVC2CX300 559 0.2 0.08
PVC 2C 400 PVC2CX400 653 0.18 0.06
PVC 2C 500 PVC2CX500 0.16 0.05
PVC 2C 630 PVC2CX630 0.15 0.04
PVC PVCX
PVC PVCX
PVC PVCX current
PVC PVCX 3/4-CORE, PVC',
PVC 4C 1.5 PVC4CX1.5 21 21.22 15.19
PVC 4C 2.5 PVC4CX2.5 28 13.04 9.3
PVC 4C 4 PVC4CX4 33 8.16 5.79
PVC 4C 6 PVC4CX6 48 5.49 3.87
PVC 4C 10 PVC4CX10 66 3.3 2.3
PVC 4C 16 PVC4CX16 88 2.11 1.44
PVC 4C 25 PVC4CX25 118 1.37 0.91
PVC 4C 35 PVC4CX35 145 1.01 0.66
PVC 4C 50 PVC4CX50 177 0.78 0.49
PVC 4C 70 PVC4CX70 224 0.57 0.34
PVC 4C 95 PVC4CX95 274 0.44 0.24
PVC 4C 120 PVC4CX120 318 0.36 0.19
PVC 4C 150 PVC4CX150 365 0.31 0.16
PVC 4C 185 PVC4CX185 420 0.27 0.13
PVC 4C 240 PVC4CX240 493 0.23 0.1
PVC 4C 300 PVC4CX300 559 0.2 0.08
PVC 4C 400 PVC4CX400 653 0.18 0.06
PVC 4C 500 PVC4CX500 0.16 0.05
PVC 4C 630 PVC4CX630 0.15 0.04
trefoil sysem
XLPE 1C 1.5 XLPE1CX1.5 25 21.43 15.43
XLPE 1C 2.5 XLPE1CX2.5 34 13.25 9.45
XLPE 1C 4 XLPE1CX4 44 8.3 5.88
XLPE 1C 6 XLPE1CX6 57 5.58 3.93
XLPE 1C 10 XLPE1CX10 77 3.37 2.33
XLPE 1C 16 XLPE1CX16 102 2.16 1.47
XLPE 1C 25 XLPE1CX25 139 1.41 0.93
XLPE 1C 35 XLPE1CX35 170 1.05 0.67
XLPE 1C 50 XLPE1CX50 208 0.8 0.49
XLPE 1C 70 XLPE1CX70 265 0.58 0.34
XLPE 1C 95 XLPE1CX95 326 0.45 0.25
XLPE 1C 120 XLPE1CX120 381 0.38 0.2
XLPE 1C 150 XLPE1CX150 438 0.33 0.16
XLPE 1C 185 XLPE1CX185 507 0.28 0.13
XLPE 1C 240 XLPE1CX240 606 0.24 0.1
XLPE 1C 300 XLPE1CX300 697 0.21 0.08
XLPE 1C 400 XLPE1CX400 816 0.19 0.06
XLPE 1C 500 XLPE1CX500 933 0.17 0.05
XLPE 1C 630 XLPE1CX630 1117 0.15 0.04
XLPE XLPEX
XLPE XLPEX
XLPE XLPEX
XLPE 2C 1.5 XLPE2CX1.5 24 21.43 15.43
XLPE 2C 2.5 XLPE2CX2.5 32 13.25 9.45
XLPE 2C 4 XLPE2CX4 42 8.3 5.88
XLPE 2C 6 XLPE2CX6 53 5.58 3.93
XLPE 2C 10 XLPE2CX10 73 3.37 2.33
XLPE 2C 16 XLPE2CX16 96 2.16 1.47
XLPE 2C 25 XLPE2CX25 130 1.41 0.93
XLPE 2C 35 XLPE2CX35 160 1.05 0.67
XLPE 2C 50 XLPE2CX50 195 0.8 0.49
XLPE 2C 70 XLPE2CX70 247 0.58 0.34
XLPE 2C 95 XLPE2CX95 305 0.45 0.25
XLPE 2C 120 XLPE2CX120 355 0.38 0.2
XLPE 2C 150 XLPE2CX150 407 0.33 0.16
XLPE 2C 185 XLPE2CX185 469 0.28 0.13
XLPE 2C 240 XLPE2CX240 551 0.24 0.1
XLPE 2C 300 XLPE2CX300 638 0.21 0.08
XLPE 2C 400 XLPE2CX400 746 0.19 0.06
XLPE 2C 500 XLPE2CX500 0.17 0.05
XLPE 2C 630 XLPE2CX630 0.15 0.04
XLPE XLPEX
XLPE 4C 1.5 XLPE4CX1.5 24 21.55 15.43
XLPE 4C 2.5 XLPE4CX2.5 32 13.24 9.45
XLPE 4C 4 XLPE4CX4 42 8.28 5.88
XLPE 4C 6 XLPE4CX6 53 5.57 3.93
XLPE 4C 10 XLPE4CX10 73 3.35 2.33
XLPE 4C 16 XLPE4CX16 96 2.14 1.47
XLPE 4C 25 XLPE4CX25 130 1.39 0.93
XLPE 4C 35 XLPE4CX35 160 1.03 0.67
XLPE 4C 50 XLPE4CX50 195 0.79 0.49
XLPE 4C 70 XLPE4CX70 247 0.57 0.34
XLPE 4C 95 XLPE4CX95 305 0.44 0.25
XLPE 4C 120 XLPE4CX120 355 0.37 0.2
XLPE 4C 150 XLPE4CX150 407 0.32 0.16
XLPE 4C 185 XLPE4CX185 469 0.27 0.13
XLPE 4C 240 XLPE4CX240 551 0.23 0.1
XLPE 4C 300 XLPE4CX300 638 0.21 0.08
XLPE 4C 400 XLPE4CX400 746 0.18 0.06
XLPE 4C 500 XLPE4CX500 0.16 0.05
XLPE 4C 630 XLPE4CX630 0.15 0.04
X

0.17
0.14
0.13
0.12
0.11
0.11
0.1
0.1
0.1
0.1
0.09
0.09
0.09
0.09
0.09
0.09
0.09
0.09
0.09

0.17
0.14
0.13
0.12
0.11
0.11
0.1
0.1
0.1
0.1
0.09
0.09
0.09
0.09
0.09
0.09
0.09
0.09
0.09

0.17
0.15
0.14
0.13
0.13
0.12
0.12
0.12
0.11
0.11
0.1
0.1
0.1
0.1
0.1
0.1
0.09
0.09
0.09

0.17
0.14
0.13
0.12
0.11
0.11
0.1
0.1
0.1
0.1
0.09
0.09
0.09
0.09
0.09
0.09
0.09
0.09
0.09

0.17
0.14
0.13
0.12
0.11
0.11
0.1
0.1
0.1
0.1
0.09
0.09
0.09
0.09
0.09
0.09
0.09
0.09
0.09