Documente Academic
Documente Profesional
Documente Cultură
Specifying
Jeff Stein, PE, is a senior engineer with Taylor Engineering and a member of ASHRAE Standard Project
Committee 130, Methods of Testing for Rating Ducted Air Terminal Units.
create a new sizing chart, compare it to grounds for rejecting the substitution. and up because:
your box schedule, and issue a revised • The odd sizes (and the 4-in. size)
schedule if any of the boxes are too big EVEN VS. ODD SIZES usually are nothing more than the next-
or too small. Also, see if the new sizes Most VAV-box manufacturers make larger even-sized box with an adapter
and/or the amplification of the new boxes of the following sizes: 4 in., 5 in., at the inlet to accommodate smaller
airflow sensors affect the minimum- 6 in., 7 in., 8 in., 9 in., 10 in., 12 in., inlet duct. This extra fitting can affect
airflow set point for any of your zones. If 14 in., 16 in., and 24 in. by 16 in. While pressure drop, leakage, and airflow-
they significantly increase any of your one might assume that life-cycle cost sensor performance, particularly if it
minimum-airflow set points, consider (first cost, energy cost, etc.) would be is not installed properly (which can be
using the minimum-airflow set points optimized by including all of these sizes difficult to verify in the field).
on your schedule and the amplification in a sizing chart, you should consider • Most contractors do not provide
requirements in your specification as specifying only the even sizes from 6 in. odd-size ducts, making reducers and
expanders necessary.
• Many local dealers do not stock odd-
Continued from Page 43 controls specifications should require
size VAV boxes in their warehouses and, the heating needs, the minimum-airflow that VAV-box controllers be fully
thus, may substitute even sizes anyway. set point can be as low as the controllable programmable. The dual-maximum-
Using only even sizes 6 in. and larger minimum of the VAV box (as long as control sequence still is a new concept to
does not significantly affect average ventilation requirements are met). When most controls vendors; even if they tell
turndown. a dual-maximum-control scheme is used, you that their configurable, pre-
the minimum-airflow set point typically is programmed controllers can implement
REFERENCES
10 to 20 percent of design airflow. the dual-maximum sequence, chances
1) Taylor, S.T., & Stein, J. (2004). Simulation models of typical office that they will not be able to do it correctly
Sizing VAV boxes. ASHRAE Journal, 46, buildings have shown that switching from are good. Therefore, the best way to
30-35. a single-maximum-control approach with ensure that the dual-maximum-control
2) Hydeman, M., Taylor, S., Stein, J., a 40-percent minimum-airflow set point to sequence can be implemented properly is
Kolderup, E., & Hong, T. (2003, Octo- a dual-maximum-control approach with a to require fully programmable controllers.
ber). Advanced variable air volume 20-percent minimum-airflow set point can Another VAV-box control point one
system design guide. California Energy save 30 cents per square foot per year.2 should consider requiring is VAV-box
Commission Publication 500-03-082- For the dual-maximum-control damper position—either modulating
A-11. Available at http://www.energy.ca sequence to be implemented, controls (analog output) or floating (two digital
.gov/reports/2003-11-17_500-03-082_ specifications must require an analog outputs). Knowing VAV-box damper
A-11.PDF input for VAV-box supply-air temperature. position is extremely helpful in implement-
3) Hydeman, M., & Stein, J. (2003, (This is not required for the single- ing static-pressure reset, which can save
May). A fresh look at fans. HPAC Engi- maximum-control scheme.) Additionally, as much as 50 percent of fan energy.3
neering, pp. 28-30, 32, 35-37, 39-41.