Rev 2: Added L20WP1X coil to rung creating L20WP1C. Added L20WP2X coil to rung creating L20WP2O. Added
L20WP3X coil to rung creating L20WP3C. Each coil replaced its respective coil in the wiring definition and will be used to
drive the valve defined in the wiring definition.
TABLE OF CONTENTS
1.0 System Summary
2.0 Application
3.0 Design Standard
3.1 Hardware explanation
3.2 Supporting Documentation
3.3 Software Description
4.0 System Schematics/MCC Elementaries
4.1 System Schematics
4.2 MCC Elementaries
5.0 Device Summary Entries
6.0 Instruction Book Information
7.0 Integrated System Conceptual Verification Plan
APPENDIX A – MARK V INFORMATION
APPENDIX B – MARK VI INFORMATION
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 2 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
NO
NO
Atomizing
33AA-1,2 To
Air
Manifold Endcover
96WP-2A,2B,2C 96PL-1A,1B,1C
dP to CPD dP to CPD
20WP-3 20WP-1 20PL-1 20PL-3
33WP-2 33PL-2
NC NC
To Drain VA33-1L VA19-1L To Drain
The purge system receives air from the discharge of the gas turbine compressor through a cooler to provide added
temperature margin for the fuel nozzle distributor valves or to precool prior to boosting with a compressor. While on gas
fuel, the air will bypass the AA compressor (un-boosted) by use of a motor actuated valve (20AA-1). This air flows through
the (normally open) main purge feed valves (VA19-1 & VA33-1). This valve is a solenoid controlled valve (20PL-1 and
20WP-1) with instrument air actuated with a limit switch monitoring position (33PL-1 and 33WP -1). Down stream of the
purge feed valves are the purge manifolds. The manifolds are used to distribute the purge air to each combustion can. To
prevent back flow of fuel/water into the purge system, each purge line is equiped with a (normally open) pneumatically
actuated isolation valve (VA19-3-1 thru n & VA33-3-1 through n, where n = # of combustion chambers). A single
solenoid valve (20PL-3 and 20WP-3) provides the actuation air to all of the isolation valves. The manifolds are equiped
with a (normally closed) small drain valve (VA19-2 & VA33-2), with a limit switch to monitor position (33PL-2 and
33WP-2). The drain valve is solenoid controlled (20PL-2 and 20WP-2). There is also a (normally closed) small or low
flow feed valve (VA19-1L & VA33-1L) operated by a solenoid (20PL-1L and 20WP-1L) for soft purge flow introduction.
There are two additional AA pressure ratio control valves (20AA-2 & 20AA-5). The valves are to control the system
pressure during transient conditions. Prior to liquid fuel purge opening, the 20AA-2 valve should be open during liquid fuel
operation, closed during gas fuel operation. The 20AA-5 is open during normal operation and it is closed prior to water
injection purge introduction when at high loads. This valve is to provide back pressure on the compressor, when on liquid
fuel, with full water injection purge to maintain flow on the compressor curve. All three of the 20AA valves have both
closed and open position switches (33AA1C & 33AA1O for example). The switches are used for startup position checking
as pressure ratio detection is not reliable at the time of startup due to very low CPD pressures (ambient + inches of water).
All standards contain the Overview. This Standard contains the sequencing related to the Water Injection purge
sequencing, with valve position fault tracking, Pressure Ratio Fault Detection for the Water Injection purge, and the code
change required for the system.
2.0 Application
This design standard is to be first applied at Baltimore Power & Light, without the 20AA-5 valve.
This design standard applies to all dual fuel DLN-2 or higher combustion systems (DLN-2.6, 2+ etc). 9FA AO DCI
96005546, 7FA AO DCI 96004823, 6FA AO 96005445, Lessons Learned 97004801, GR0383 97002255
3.0 Design Standard
3.1 Hardware explanation
See Top level system standard for hardware requirements.
Slew times of valves effect control performance; expected for system are:
The main feed valve closing time: ~ 0.5 seconds +/- 0.25 seconds
The main feed valve opening time: ~ 5 seconds +1.0, - 0.5, seconds
The small feed valve open/closing time: ~ 0.5 seconds +/- 0.25 seconds
The drain valve open/closing time: ~ 0.5 seconds +/- 0.25 seconds
The isolation valve closing time: ~ 0.5 seconds +/- 0.25 seconds
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 4 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
The isolation valve opening time: ~ 1.25 seconds +/- 0.25 seconds
MK 5 hardware: Due to the number of 4 - 20 mA inputs which MUST go into <Q> core, NEW units must be ordered with a
TCQF card, and use GHD prom set. Bobcat will call out termination point to the TCQF card. MNQC units may not require
the additional card. CM&Us will need to be reviewed on a case by case basis.
3.1.1 Scope of Responsibilty
Combustion Engineering provides the nominal purge pressure ratio, the Alarm level, the Action level, and any upper limit
required.
Control Development Engineer to develop code to meet system operational requirements.
Requisition Engineer to select constants for frame size and or Combustion type (pressure drop).
STARTUP
Gas Fuel OR Liquid Fuel
SHUTDOWN
Gas Fuel OR Liquid Fuel
The water injection purge manifold pressure is measured with three delta pressure transducer to calculate a pressure ratio.
Prior to starting the unit, the ratio should be ~ 1.00 +/- 0.01. It is not exactly 1.0 because of calibration errors on the delta
pressure transducers. The calibration error at startup is large compared to the CPDABS ~ 14.7. Once the unit is higher in
speed, the CPD increases and the error becomes small relative to the signal. However, checks can be made to determine if the
transducer(s) is/are functional. The transducer signal should not be at the Upper or Lower level values. The pressure ratio
should not be BELOW the lower Alarm level, or ABOVE the High level.
3.3.3 SHUTDOWN
The water injection purge system is in the normal default condition, purging during a fired shutdown.
3.3.4 WATER INJECTION ON, PURGE OFF
The water injection purge isolation valves are closed when the water stop valve is open to minimize the risk of back flowing
water into the purge manifold. The water injection purge main feed valve is closed at the same time as the isolation valve.
There is a short time delay of ~ 0.5 seconds on opening the drain valve.
A method to check whether all of the endcover isolation valves have closed is as follows: The endcover valves and feed
valves are closed with the drain line left open. Once the pressure in the purge manifold has dropped below the detectable level
(-20 psid), the purge drain valve is closed. It will remain closed for a period of time which is proprotional to the compressor
discharge pressure. Because the pressure in the manifold is now fixed (less leakage in or out), the pressure ratio could change
as result of changing load (increasing or decreasing CPD). The time needs to be as short as possible yet be long enough that if
water flow is back flowing into the manifold, the pressure will rise above the pressure ratio action level. At high loads, CPD
willbe high and water flow rates will be high, so the time can be short. Unloading the unit from high CPD with the pressure
bottled may cause a false indication.
If back flow of water is detected in the manifold, then a Forced Fired Shutdown is performed. The logical “L94WP” is the
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 5 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
water injection purge fast fired shutdown signal. This signal is applied to the L94DLN signal which may need to be added for
the MNQC system to pick up the STOP command. This is done in part to take advantage of the fact that L94DLN already
picks up the lower command and then the fast rate logic (L83JD10 = 1) is selected. SEE the Startup, shutdown and Trip
standard ADV_PR_S.DOC. Due to the liquid fuel/water injection nozzle design of the DLN - 2.0 / 2.6 / 2.0 + the delay time
on opening the water injection purge system is not considered a risk to the nozzles for the show down period.
When the back flow is detected (L94WP = 1), the purge system goes into a fully blocked configuration, ALL valves are
closed (feed valve, isolation and drain valve). When the unit reaches 95 % speed it is tripped. After flame out the drain valve
is opened for 60 seconds. After another 60 second delay, the feed valve and isolation valves are opened and the drain valve is
closed. This allows the manifold to be drained without risk of back flowing hot combustion gases, damaging the nozzles, and
keeping large amounts of water from being sent into the turbine after flame out. The unit is tripped at 95% speed to minimize
the amount of time with no purge verses a trip at high load.
If NO back flow is detected after the time limit, the drain valve is opened.
3.3.5 WATER INJECTION OFF, PURGE ON
Two basic objections exist: to drain the manifold of any water that may have leaked in and soft purge introduction.
To drain the manifold, the isolation valves are left closed when the water stop valve is closed stopping the water, and the small
feed valve is opened to pressurize the manifold. After a small time delay of ~ 5 seconds, the main feed valve is opened.
After a short drain time of ~ 10 seconds (if the generator breaker is closed, ~20 seconds if it is open), the small and main feed
valves are closed. Due to the liquid fuel/water injection nozzle design of the DLN - 2.0 / 2.6 / 2.0 +, the delay time on
opening the water injection purge system is not considered a risk to the nozzles.
After the feed valves are closed, the pressure in the manifold will decay. Once the pressure has dropped to the action level of ~
0.95%, the drain valve is closed, the small feed valve and the isolation valves are opened. This provides the soft purge at both
a low introduction pressure and at a low flow rate.
After a short low flow purge of ~ 10 seconds, the main feed valve is opened and high flow and pressure flushes the any
remaining water out. The system is now in the steady state purging condition.
Provisions are made in case the drain valve is blocked or fails to open the purge feed and isolation valves after some
maximum allowable period ~ 45 seconds.
The three delta pressure transducer signals will be checked against the median value for a failed single transducer alarm. The
median valve is used to calculate the pressure ratio (WIPPR) with the CPDABS signal. The median delta pressure (WIPDP)
is added to CPDABS to give the manifold pressure in psia, then divided by CPDABS to produce the pressure ratio, WIPPR.
The WIPPR is then compared to an alarm value and a lower action (trip) valve. A high limit value is also used to test as part of
a startup check. Because there are times when the purge pressure ratio is low, and very low, such as when on liquid fuel and
in the block and bleed configuration, the alarm & action logic are locked out during those times. A timer is used to prevent a
transient signal from tripping the unit. The very low trip pressure ratio signal is also applied to the new liquid fuel purge trip
logic (L4LFPT). The alarm and action level are 0.01 pressure ratio apart, with the alarm value being set at 0.01 pressure ratio
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 6 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
below the minimum value, the system maybe tuned to (0.97 for DLN, 0.98 for MNQC). This puts the alarm and action levels
about ½ way between the nominal untuned value and PCC.
The median value of the delta pressure transducer is used as part of the purge opening and back flow testing (while on liquid
fuel) to produce logic switch point based on pressure, or the lack of it, in the manifold. A test is done to determine if the
median value is out of range, either high or low.
3.3.8 FUEL TRANSFERS
The Water injection is ramped off prior to transfer from liquid fuel to gas fuel. Water Injection purge will occur during the
gas prefill and start the fuel transfer (which will take 66 seconds + gas prefill time). During the liquid fuel purge introduction
and scavenge, the water injection purge is switched to the low flow condition to minimize the load on the AA compressor.
After the scavenge, it returns to the normal high flow purging condition.
Transferring from gas to liquid fuel, the water Injection is started ~10 seconds after reaching total liquid fuel (L84TL = 1) if
the other requirements are met, such as minimum fuel flow and minimum Combustion Reference Temperature. This is to
allow the gas fuel purge transient time to take place prior to turning on water flow.
The attached sketches shows the water injection purge sequence for water on & off as a function of time. The water injection
purge valve position and pressure ratio fault detection block diagrams are also shown.
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 7 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
1.20
WIPPR
0.80
0 1 5 15
Time in Seconds
Water Injection Isolation Valve
=1 Water Inj on
L20WN
=0 Water off
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Note:
Proprietary Timing of manifold pressure changes based on testing at BG&E
information Page 8 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
1.20
WIPPR
0.80
0 5 45
Time in Seconds
Water Injection Isolation Valve
=1 Water Inj on
L20WN
=0 Water off
V20WNY1
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 9 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
DLN-2 Water Inj Purge Main Feed Valve Position Fault Matrix
TD TD
TD TD
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 10 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
High Side
3 Delta Pressure
Transducers
Feed
Valve Low Side CPD
M anifold
A H
+ W IPDP
B MEDIAN
W IPDP_1C -
C L SUB
Drain
Valve
PPKDPLL
A L63W PDPLL
W IPDP A >B
B Lower Limit
FXKW PRH
W IPDP
A L63W PDPUL
PPKDPUL A >B
B Upper Limit
CPDABS
A
W IPPR
(A +B )/A
W IPDP Pressure Ratio
B
W IPPR
A L63W PRH
FXKW PRH A >B
B Upper Limit
L4AKRUN = 1, AA m otor running
FXKLFPVLA
L63W PRVL L86W PRVLA
A
W IPPR A >B
ACTION
B Very Lower Limit
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 11 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
The water injection purge system prevents back flow of hot combustion gases in the water injection portion of the fuel nozzles
when water injection is not flowing water, and to flush out residual water in the nozzles. For dual fuel units, the water
injection purge system is always activated whenever operating on 100% gas fuel. The water injection purge system is
monitored by use of delta pressure measurement to calculate a pressure ratio relative to CPD. An alarm level and an action
level are provided should the pressure ratio drop below the preset limits.
The following table is provided and to be filled out and returned to design engineering. The CTQ #1 is the target value prior
to any adjustments to the pressure ratio value by closing the VM17-1 (see adjustment procedure paragraph). Record the actual
field and values PRIOR to any adjustment of the manual tuning valve VM17-1. If the VM17-1 is used, the final values should
also be recorded and returned with the pre-tuned values.
Legend: AA temp = AA temperature of air out of cooler, T = Target Value, Actual = Actual measured value
No mechanical adjustments are required to set valve open/close times with the advanced compressorless purge. A View2 data
file is needed of the purge system being turned OFF and ON. The output files are to become part of the startup report, and
returned to CASE, Design Engineering.
The desired purge pressure ratio for the liquid fuel purge and water injection purge is based on both nozzle cooling/purge
requirement and a combustion dynamic requirement. A balance between the two. The manual tuning valve (VM17-1) is fully
open prior to first starting of the gas turbine. Once the turbine has reached FSNL, and the AA temperature is a minimum of
120 F, data is taken to be compared to the #1 CTQ table. The water injection (WIPPR), the liquid fuel (FPPR) and AA
(AAPR) pressure ratios, should all be approximately the same value with the AA possibly a little higher. The unit should be
loaded and the data taken again at Base Load.
The engineer responsible for commissioning the DLN system has the option to reduce the purge flows (to a minimum of 0.970
PR) because it will improve combustion dynamics. The manual-tuning valve VM17-1 is used to reduce the flow, ON LINE.
The WIPPR is then monitored during the loading to base and the data is confirmed across the load range. All three purge
pressure ratios should be approximately the same value. Having water injection purge slightly lower than the liquid fuel purge
is better than the other way around. Checking of the witch hat strainers maybe required if the values are low. If tuning was
required, the final value of WIPPR should also be included in the startup report.
Control and Protection Article Numbers (or GEK Numbers) Name of item
-NA
L20WN
L20WP1C
L20WP2O
L20WP3C
L20WP1LO
WIPRP
Confirm that the real time plot appears the SAME as the “Water Injection ON, Purge OffTime Line”.
Recording the same points on a real time plot, turn the water injection Off, Purge On and Confirm the real time
plot apprears the same as the “Water Injection Off, Purge ON time Line”.
For field verification of the purge system, a VIEW2 (MK V control system) file needs to be run during water turn OFF, purge
ON. The input file is located in APPENDIX. The same VIEW2 (MK V control system) file can be used for turn ON of water,
purge OFF. The output files should be provided with the field verification report.
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 13 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
8.1 CTQ’s
To provide continuous positive flow of purge air to the water injection nozzles when the water injection is OFF is based on
low-pressure loss to the system in an un-boosted condition. The Metric is monitoring the correct range of pressure ratio
(WIPPR), alarm, and action level in case the operation drops below expectable value. Values are set by Combustor type
(pressure drop). Value is to be taken at FSNL and Base Load with the manual tuning valve (VM17-1) FULL open. Too much
purge flow may indicate a design problem and adversely effect combustion dynamics.
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 14 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
A1 Wiring Definition
A2 Required Settings
CODE
C = Constant is calculated per unit
F = Constant can be field adjusted
FXKWPRVLA 0.96 CNT01 ;WATER INJ PURGE RATIO VERY LOW LIMIT MNQC
A2.2.1 Scaling/Calibration
A2.3 IO Assignments
A3 Signal Definitions
?LQ L83WP2C LOG ;OPEN DRAIN FOR PURGE BACK FLOW CHECK LOGIC
?LQ L83WP2CZ LOG ;CLOSE DRAIN FOR PURGE BACK FLOW CHECK LOGIC
?LQ L83WPBKFIL LOG ;WATER INJ PURGE MANIFOLD BACK FILLED LOGIC
?LQ L83WPRVLA LOG ;WATER INJ PURGE PRESS BELOW VERY LOW LIMIT LOGIC
?LQ L94WPY LOG ;TD WATER INJ PURGE FAST FIRED SHUTDOWN, DROPOUT LOGIC
?VQ T20WNY SEC64 ;TD TURN OFF WATER INJ - DELAY FEED VALVE OPENING sec
?VQ T20WNY_MAX SEC64 ;TD MAXIMUM DELAY TO OPEN WATER INJ PURGE sec
?VQ T20WNY1 SEC64 ;TD TO DRAIN H2O PURGE MANIFOLD sec
?VQ T20WNZ SEC64 ;TD AFTER WATER INJ STOP OPEN sec
?VQ T20WNZ1 SEC64 ;TD CHECK FOR HIGH PRESS IN PURGE MANIFOLD sec
?VQ T20WP3CY SEC64 ;TD OPENING WATER INJ PURGE ISO VLVS sec
?VQ T30WPDP_FLT SEC64 ;TD WATER INJ PURGE DIFF PRESS XDUCER FAULT sec
?VQ T30WPPTA SEC64 ;TD WATER INJ PURGE MED DIFF PRESS OUT OF RANGE sec
?VQ T30WPRLA SEC64 ;TD WATER INJ PURGE PRESSURE RATIO LOW LIMIT sec
?VQ T33WP1C_ALM SEC64 ;TD WATER INJ PURGE FEED VLV - NOT CLOSED sec
?VQ T33WP1O_ALM SEC64 ;TD WATER INJ PURGE FEED VLV - NOT OPEN sec
?VQ T33WP2C_ALM SEC64 ;TD WATER INJ PURGE DRAIN VLV - NOT OPEN sec
?VQ T33WP2O_ALM SEC64 ;TD WATER INJ PURGE DRAIN VLV - NOT CLOSED sec
?VQ T83WPBKFIL SEC64 ;TD WATER INJ PURGE MANIFOLD BACK FILLED sec
?VQ T86WPRVLA SEC64 ;TD WATER INJ PURGE PRESSURE RATIO VERY LOW LIMIT sec
?VQ T94WP SEC64 ;TD WATER INJ PURGE BACK FLOW, FAST FIRED SHUTDOWN sec
?VQ T94WPY SEC64 ;TD WATER INJ PURGE FAST FIRED SHUTDOWN, DROPOUT sec
?VQ V20WNY1 SEC64 ;TD TO DRAIN H2O PURGE MANIFOLD sec
?VQ V83WPBKFIL SEC64 ;TD WATER INJ PURGE MANIFOLD BACK FILLED sec
?VQ WIPDP PRESS ;WATER INJ PURGE DIFF PRESSURE PSI
?VQ WIPDPAB PRESS ;WATER INJ PURGE DIFF PRESS ABS PSI
?VQ WIPPR CNT01 ;WATER INJ PURGE PRESSURE RATIO CNT01
?VQ WPTCPD SEC64 ;CPDABS BIAS TIMER FOR WATER INJ PURGE BACK FLOW sec
?VQCC FXKPPRH CNT01 ;PURGE PRESS RATIO HIGH, OUT OF EXPECTED RANGE CNT01
?VQCC FXKWPRLA CNT01 ;WATER INJ PURGE RATIO LOWER LIMIT CNT01
?VQCC FXKWPRVLA CNT01 ;WATER INJ PURGE RATIO VERY LOW LIMIT CNT01
?VQCC K20WNY SEC64 ;TD TURN OFF WATER INJ - DELAY FEED VALVE OPENING sec
?VQCC K20WNY_MAX SEC64 ;TD MAXIMUM DELAY TO OPEN WATER INJ PURGE sec
?VQCC K20WNY1C SEC64 ;TD DRAIN H2O PURGE MANIFOLD, BREAKER CLOSED sec
?VQCC K20WNY1O SEC64 ;TD DRAIN H2O PURGE MANIFOLD, BREAKER OPEN sec
?VQCC K20WNZ SEC64 ;TD AFTER WATER INJ STOP OPEN sec
?VQCC K20WNZ1 SEC64 ;TD CHECK FOR HIGH PRESS IN PURGE MANIFOLD sec
?VQCC K20WP3CY SEC64 ;TD OPENING WATER INJ PURGE ISO VLVS sec
?VQCC K30WPDP_FLT SEC64 ;TD WATER INJ PURGE DIFF PRESS XDUCER FAULT sec
?VQCC K30WPPTA SEC64 ;TD WATER INJ PURGE MED DIFF PRESS OUT OF RANGE sec
?VQCC K30WPRLA SEC64 ;TD WATER INJ PURGE PRESSURE RATIO LOW LIMIT sec
?VQCC K33PL1C_ALM SEC64 ;WATER INJ PURGE FEED VLV FAILED CLOSED TIMER K sec
?VQCC K33PL1O_ALM SEC64 ;WATER INJ PURGE FEED VLV FAILED OPEN TIMER K sec
?VQCC K33PL2C_ALM SEC64 ;WATER INJ PURGE DRAIN VLV FAILED CLOSED TIMER K sec
?VQCC K33PL2O_ALM SEC64 ;WATER INJ PURGE DRAIN VLV FAILED OPEN TIMER K sec
?VQCC K33WP1O_ALM SEC64 ;TD WATER INJ PURGE FEED VLV - NOT CLOSED sec
?VQCC K86WPRVLA SEC64 ;TD WATER INJ PURGE PRESSURE RATIO VERY LOW LIMIT sec
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 17 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
?VQCC K94WP SEC64 ;TD WATER INJ PURGE BACK FLOW, FAST FIRED SHUTDOWN sec
?VQCC K94WPY SEC64 ;TD WATER INJ PURGE FAST FIRED SHUTDOWN, DROPOUT sec
?VQCC KSHIFTN2 CNT15 ;SHIFT CONSTANT - 2 CNT15
?VQCC KSHIFTP1 CNT15 ;SHIFT CONSTANT + 1 CNT15
?VQCC PPKDPLL PRESS ;PURGE PRESS DIFF PRESS LOWER RANGE LIMIT PSI
?VQCC PPKDPUL PRESS ;PURGE PRESS DIFF PRESS UPPER RANGE LIMIT PSI
?VQCC WIKDIF_FLT PRESS ;ALMTXT: WATER INJ PURGE DIFF PRESS XDUCER FAULT PSI
?VQCC WPKBKFIL SEC64 ;OFFSET TIMER FOR WATER INJ PURGE BACK FLOW CHECK sec
?VQCC WPKCPD CNT00 ;CPDABS GAIN, TIMER FOR WATER INJ PURGE BACK FLOW CNT00
A4 Alarms
Note Alarm messages can only be 39 characters between the quote mark.
A5 CSP Information
*************************************************
*************************************************
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º TMV - Time Delay º L20WNY
L20WN Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K20WNY 0ºfinal ³ ³ currº1 T20WNY
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º SEL º LZZ
LTRUE Enable L0º Select Value º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄ Ä Ä Ä Ä Ä Ä×ÄÄÄÄÄÄÄÄÄÄ( )
º º
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 18 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
K20WNY1C 1ºinput_a outputº0 V20WNY1
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄ´ ÃÄÂÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ù ³ º
K20WNY1O 2ºinput_b ù ³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄ´/ÃÄÙ º
L52GX Select_A L1º ù º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÙ º
º º
º º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º TMV - Time Delay º L20WNY1
L20WN Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
V20WNY1 0ºfinal ³ ³ currº1 T20WNY1
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º TMV - Time Delay º L20WNY_MAX
L20WN Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K20WNY_MAX 0ºfinal ³ ³ currº1 T20WNY_MAX
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º TMV - Time Delay º L20WNZ
L20WN Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K20WNZ 0ºfinal ³ ³ currº1 T20WNZ
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º TMV - Time Delay º L20WNZ1
L20WN Input L0º ÚÄÄÄÄÄ¿ º
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 19 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K20WNZ1 0ºfinal ³ ³ currº1 T20WNZ1
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L20 L33 L20 L63W º TMV - Time Delay º L94WP
WP2O WP2C WNZ1 PRVL Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´ ÃÄÄÄÄÄÄ´/ÃÄÄÂÄÄÄ´ ÃÄÄÄÄÄÄ´/ÃÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
³ ³ º ³ TD ³ º
L33 ³ ³ K94WP 0ºfinal ³ ³ currº1 T94WP
WP1O ³ ³ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
ÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÙ ³ º ³ ³ º
³ º dt ³ ³ º
³ º ÄÄÄÄÄÄ´ ³ º
L94WP L28FDX ³ º ÀÄÄÄÄÄÙ º
ÄÄÄ´ ÃÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙ ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º TMV - Time Delay º L94WPY
L94WP Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K94WPY 0ºfinal ³ ³ currº1 T94WPY
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º MPY - Multiply º
LTRUE Enable º º LZZ
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄ Ä Ä Ä Ä Ä ÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º º
CPDABS 1ºmplicandÚÄ¿ ÚÄ¿ outputº0 WPTCPD
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄ´ ÃÄ´ ÃÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³X³ ³X³ º
WPKCPD 2ºmltplier³ ³ ³ ³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄ´ ³Ú´ ³ º
º ÀÄÙ³ÀÄÙ º
º ÚÄÄ¿³ º
KSHIFTN2 3ºshift ³-N³³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄ´2 ÃÙ º
º ÀÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 20 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º SUB º
LTRUE Enable º º LZZ
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×Ä Ä Ä Ä Ä Ä Ä ÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º º
WPKBKFIL 1ºinput_a + outputº0 V83WPBKFIL
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄoÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º -³ º
WPTCPD 2ºinput_b ³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
L63W L3WP
PDPLL L20WN BKFIL
ÄÄÄ´ ÃÄÄÂÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ( )
³
L3WP ³
BKFIL ³
ÄÄÄ´ ÃÄÄÙ
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º TMV - Time Delay º L83WPBKFIL
L3WPBKFIL Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
V83WPBKFIL 0ºfinal ³ ³ currº1 T83WPBKFIL
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
L20 L20W
AA1C L84TG L14HS P1LO
ÄÄÄ´ ÃÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ´ ÃÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ( )
³
L20WN L20 ³
Y_MAX WP3C ³
ÄÄÄ´/ÃÄÄÄÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄ´
³
L20 ³
L20WN WNY1 ³
ÄÄÄ´/ÃÄÄÄÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÙ
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L20 º TMV - Time Delay º L20WP3CY
WP3C Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 22 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
K20WP3CY 0ºfinal ³ ³ currº1 T20WP3CY
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
L20
AA1C L84TG L14HS L20WP1C
ÄÄÄ´ ÃÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ´ ÃÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄ( )
³ ³
L20 L20W L20WN ³ ³
WNY1 P3CY Y_MAX ³ ³ L20WP1X
ÄÄÄ´ ÃÄÄÄÄÄÄ´/ÃÄÄÄÄÄÄ´/ÃÄÄ´ ÀÄÄÄÄÄÄÄÄ( )
³
³
L94WP L94WPY ³
ÄÄÄ´/ÃÄÄÄÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄ´
³
³
L94WP ³
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ´
³
³
L20WNY ³
ÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙ
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L20 L33 º TMV - Time Delay º L33WP1C_ALM
WP1C WP1O Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´ ÃÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K33WP1C_ALM 0ºfinal ³ ³ currº1 T33WP1C_ALM
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L20 L33 º TMV - Time Delay º L33WP1O_ALM
WP1C WP1O Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´/ÃÄÄÄÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K33WP1O_ALM 0ºfinal ³ ³ currº1 T33WP1O_ALM
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 23 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L20 L33 º TMV - Time Delay º L33WP2C_ALM
WP2O WP2C Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´ ÃÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K33WP2C_ALM 0ºfinal ³ ³ currº1 T33WP2C_ALM
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L20 L33 º TMV - Time Delay º L33WP2O_ALM
WP2O WP2C Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´/ÃÄÄÄÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K33WP2O_ALM 0ºfinal ³ ³ currº1 T33WP2O_ALM
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
*************************************************
*************************************************
************************************************************
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º XPTS00 - PARALLEL º
º XMTTR SELECTOR º
º º
WIPDP_2A 0º ÚÄÄÄÄÄ¿ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ HIGHÃÄ¿ º
WIPDP_2B 1º ³ ³ ³ º4 WIPDP
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ MEDÃÄ(ÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
WIPDP_2C 2º ³ ³-³+ ÚÄÄÄÄÄ¿ º
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 24 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ LOWÃÄOÄÄ´A ³ º5 L83WIPDP
WIKDIF_FLT 3º ÀÄÄÄÄÄÙ ³ A>=BÃÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄ´B ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L83W º TMV - Time Delay º L30WPDP_FLT
IPDP Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K30WPDP_FLT 0ºfinal ³ ³ currº1 T30WPDP_FLT
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍ»
º CMP º
LTRUE Enable º º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄ¿ º
º ù º
WIPDP 0ºa ÚÄÄÄ¿ ù º L63WPDPUL
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ ù º
º ³ ô ÃÄ×ÄÄÄÄÄÄÄÄÄÄ( )
PPKDPUL 1ºb ³a>b³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ º
º ÀÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍ»
º CMP º
LTRUE Enable º º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄ¿ º
º ù º
PPKDPLL 0ºa ÚÄÄÄ¿ ù º L63WPDPLL
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ ù º
º ³ ô ÃÄ×ÄÄÄÄÄÄÄÄÄÄ( )
WIPDP 1ºb ³a>b³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ º
º ÀÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L63W L4A L20 º TMV - Time Delay º L30WPPTA
PDPLL KRUN WP2O Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´ ÃÄÄÂÄÄÄ´/ÃÄÄÄÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
³ º ³ TD ³ º
L63W ³ K30WPPTA 0ºfinal ³ ³ currº1 T30WPPTA
PDPUL ³ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 25 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
ÄÄÄ´ ÃÄÄÙ º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º ADD º LZZ
LTRUE Enable º º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×Ä Ä Ä Ä Ä Ä Ä ÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º º
CPDABS 1ºinput_a + outputº0 WIPDPAB
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄOÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º +³ º
WIPDP 2ºinput_b ³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
º DVD - Divide º LZZ
LTRUE Enable º º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×Ä Ä Ä Ä Ä Ä Ä Ä ÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º º
WIPDPAB 1ºdividend ÚÄ¿ ÚÄ¿ quotientº0 WIPPR
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄ´ ÃÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ö³ ³X³ º
CPDABS 2ºdivisor ³ ³Ú´ ³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ³³ÀÄÙ º
º ÀÄÙ³ º
º ÚÄÄ¿³ º
KSHIFTP1 3ºshift ³-N³³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄ´2 ÃÙ º
º ÀÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍ»
º CMP º
LTRUE Enable º º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄ¿ º
º ù º
FXKWPRLA 0ºa ÚÄÄÄ¿ ù º L63WPRL
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ ù º
º ³ ô ÃÄ×ÄÄÄÄÄÄÄÄÄÄ( )
WIPPR 1ºb ³a>b³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ º
º ÀÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍ1/4
L3W
L14HM L84TL PRLA
ÄÄÄ´/ÃÄÄÂÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ( )
³
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 26 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
³
L28FDX ³
ÄÄÄ´/ÃÄÄÙ
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L3W L20 L63 º TMV - Time Delay º L30WPRLA
PRLA WP1C WPRL Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´/ÃÄÄÄÄÄÄ´/ÃÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
º ³ TD ³ º
K30WPRLA 0ºfinal ³ ³ currº1 T30WPRLA
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍ»
º CMP º
LTRUE Enable º º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄ¿ º
º ù º
FXKWPRVLA 0ºa ÚÄÄÄ¿ ù º L63WPRVL
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ ù º
º ³ ô ÃÄ×ÄÄÄÄÄÄÄÄÄÄ( )
WIPPR 1ºb ³a>b³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ º
º ÀÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»
L83W º TMV - Time Delay º L86WPRVLA
PRVLA Input L0º ÚÄÄÄÄÄ¿ º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄ( )
³ º ³ TD ³ º
L86W L86MR ³ K86WPRVLA 0ºfinal ³ ³ currº1 T86WPRVLA
PRVLA 1_CPB ³ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄ´ ÃÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
ÄÄÄ´ ÃÄÄÄÄÄÄ´/ÃÄÄÙ º ³ ³ º
º dt ³ ³ º
º ÄÄÄÄÄÄ´ ³ º
º ÀÄÄÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ1/4
ÉÍÍÍÍÍÍÍÍÍÍÍ»
L4A º CMP º
LTRUE KRUN Enable º º
ÄÄÄ´ ÃÄÄÄÄÄÄ´/ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄ¿ º
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 27 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
º ù º
WIPPR 0ºa ÚÄÄÄ¿ ù º L63WPRH
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ ù º
º ³ ô ÃÄ×ÄÄÄÄÄÄÄÄÄÄ( )
FXKPPRH 1ºb ³a>b³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ º
º ÀÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍ1/4
***************************************************************
***************************************************************
***************************************************************
***************************************************************
ÉÍÍÍÍÍÍÍÍÍÍÍ»
º CMP º
LTRUE Enable º º
ÄÄÄ´ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄÄÄÄÄÄÄ¿ º
º ù º
WQ 0ºa ÚÄÄÄ¿ ù º L30WATERON
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ ù º
º ³ ô ÃÄ×ÄÄÄÄÄÄÄÄÄÄ( )
FXKVLVCLS 1ºb ³a>b³ º
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ×ÄÄ´ ³ º
º ÀÄÄÄÙ º
ÈÍÍÍÍÍÍÍÍÍÍÍ1/4
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 28 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
B2 Required Settings
B2.1 Control Constants Information
Data Initial
Name
Type Value
Units Description Code*
*CODE:
C = Constant varies by frame size or installation, and must be calculated.
F = Constant can be field adjusted
B2.2 Control Constant Calculation Methods
See Appendix A, Section 2.2
B3 Signal Definitions
Initial
Signal Name Direction Data Type Units Description
Value
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 29 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 30 of 32
Advanced Compressorless Purge Controls Part 3
Controls Design Standard
HARDWARE SUMMARY:
The water injection purge hardware is identical to the liquid fuel hardware for compressorless purge. It is basically a
double block and bleed system. There are two feed valves, a main feed valve (VA33-1, 3” normally open) and a small feed
valve (VA33-1L, 1/2” normally closed), a drain valve (VA33-2, 1/2” norm-ally closed), and an isolation valve (VA33-3-1
through “n” n= number of chambers, 1.0” normally open) for each combustion chamber. A single solenoid valve (20WP-3)
actuates all of the isolation valves. Each of the other valves are actuated by individual solenoid valves (20WP-2, 3). There
is a common manifold with 3 delta pressure transducers (96WP-2A, 2B, and 2C) for monitoring the pressure ratio for fault
protection. There is a position switch on the main feed valve (33WP-1) and drain valve (33WP-2) to indicate the default
position. SEE the “Advanced Compressorless Purge System”.
From Compressor
Discharge
96WP-2A,2B,2C
dP to CPD
20WP-3 20WP-1
Water VA33-1 NO
To Injection
Endcover Purge
NO
Manifold
VA33-3-1
thru 33WP-1
VA33-3-n
n = # of cans 20WP-2
VA33-2 20WP-1L
NC
33WP-2
NC
To Drain VA33-1L
With the water injection “Off”, the steady state purge condition is with all the solenoid valves in the de-energized state; the
main feed valve is open, drain valve is closed, all the isolation valves are open and small feed valve is closed. The pressure
ratio relative to Compressor Discharge Pressure (CPD) during the purge operation, should be ~ 0.985 +/- 0.005 depending
upon the system piping restriction (kept to a minimum with large pipe sizes) and the combustion system pressure drop. A
pressure ratio (PR) alarm level ~ 0.96 and a trip level of ~ 0.95 are used to protect the nozzles from a lack of flow. The
purge flow maybe reduced to a minimum of 0.970 if needed, to reduce combustion dynamics.
While water injection is on, the purge system is closed in the double block and bleed configuration. The feed valves are
closed, the drain valve is open to the atmosphere, and the isolation valves are closed. No pressure should be detected in the
manifold. Because of the use of delta pressure transducers (for better accuracy while in normal purging mode), the
manifold pressure ratio is displayed as ~ 0.8 - 0.85 and not ZERO.
In the event of a generator breaker open with water injection ON, the purge system will add an additional 10 seconds to the
drain time, “time delay”. The added delay of the opening of the water injection purge is to give the turbine a chance
stabilize with the IGVs closed, speed close to 100 % and the unit off minimum FSR, if possible, before opening the purge.
FAULT DETECTIONS:
Permissive to Start:
The normal default position for the purge system at startup would be to open purge the nozzles. The main feed valve
position switch must indicate the valve OPEN to start the unit. The drain valve position switch must indicate the valve
CLOSED to start the unit. The pressure ratio must NOT be in the alarm or trip state to start the unit. The delta pressure
transducer must not be at the positive or negative saturation level (greater or less than 20 PSI) to start the unit. This is
indicated by an ALARM.
©
COPYRIGHT 2000, GENERAL ELECTRIC COMPANY
Proprietary information Page 32 of 32