Sunteți pe pagina 1din 19

Installation Manual

MODELS
MINISPLIT MHC-MHH/MOC-MOH 07
MHC-MHH/MOC-MOH 09
HIGH WALL MHC-MHH/MOC-MOH 12
MHC-MHH/MOC-MOH 18
AIR CONDITIONER MHC-MHH/MOC-MOH 25
MHC-MHH/MOC-MOH 35

Installation Manual EN

Manuel d’installation FR

Installationsanleitung DE

Manual de instalación ES

Installatiehandleiding NL

Installationshandledning SE

Manuale d’installazione IT
Installation Manual

Manual de Instalação PT

Εγχειρίδιο Εγκατάστασης GR

035T78001-000

01EN_01Cover 1 14/3/01, 09:59


CONTENTS

Safety Precautions ...................................... 4

Part List ......................................................... 5

Preparation Before Installation .................. 6

Installation Diagram .................................... 8

Installation Procedure ................................. 9

Test operation ............................................ 13

Trouble Shooting Guide ............................ 14


Please read this installation manual
carefully before starting the installa- Technical Specification ............................. 16
tion. It will tell you necessary informa-
tion.

Quality POLICY
We will continuously strive to satisfy
our customers with consistent reliabil-
ity in product, service and support.

2 ENGLISH

01EN_02Install 2 03/15/2001, 13:10 PM


REQUIRED TOOLS EXTENDED PARTS
1. Screw driver 1. Refrigarant Pipe
2. Hexagonal wrench
MHC-MHH/MOC-MOH
Models
3. Torque wrench 07-09 12 18-25-35
4. Spanner Liquid size 1/4 inch 1/4 inch 3/8 inch
5. Reamer Gas size 3/8 inch 1/2 inch 5/8 inch

6. Hole core drill


2. Pipe Insulation Material (Polyethylene foam
7. Tape measure 9 mm thick)
8. Thermometer 3. Vinyl tape
9. Manifold Guage 4. Putty
10. Gas leak detector
11. Vaccum pump
12. Pipe clamp
13. Pipe Cutter
14. Flare Tool Set
15. Electrical Circuit tester

EN

ENGLISH 3

01EN_02Install 3 03/15/2001, 13:10 PM


SAFETY PRECAUTIONS

• Please read this installation manual carefully before starting installation of the unit.
• This air conditioning system contains refrigerant under pressure, rotating parts and
electrical connection which may be dangerous and can cause injury. Installation
and maintenance of this air conditioning system should only be carried out by trained
and qualified personnel.
• After unpacking, please check the unit carefully for possible damage.
• Before undertaking any work on the unit, make sure that the power supply has
been disconnected.

CAUTIONS FOR INSTALLATION

Do not store or unpack the unit in a wet area or expose Do not install in a place where flammable gas may
to rain or water. leak.

It may cause fire.

It may cause the unit to short circuit and may result electric
shocks or fire.
This system is designed for domestic or residential
use only.

Do not conduct installation in wet area or in the rain.

It is a high risk to cause the electrical shocks. If used in certain envionments, such as a manufacturing
workplace, the equipment may not function efficiently.

4 ENGLISH

01EN_02Install 4 03/15/2001, 13:10 PM


PART LIST

Name of part
Part No. Quantity
MHC-MHH/MOC-MOH 07, 09, 12 MHC-MHH/MOC-MOH 18, 25 MHC-MHH/MOC-MOH 35
Mounting Plate and Mounting Templat

1 X1

Indoor Unit

2
X1

Drain Hose

*Included with indoor unit


3
X1

Central mounting bracket EN

4 X1
*Not supplied *Not supplied

Screws and Anchor Set

5
X4

Remote Control and Battaries Set

X1
SLEEP TEMP SLEEP TEMP SLEEP TEMP
ON/OFF ON/OFF ON/OFF

Installation and owner’s manaul

7 Installation
Manual Owner's Ma
nual
Installation
Manual Owner's Ma
nual
Installation
Manual Owner's Ma
nual X1

ENGLISH 5

01EN_02Install 5 03/15/2001, 13:10 PM


PREPARATION BEFORE INSTALLATION

• Before doing any work, check the interior power supply cord and the main breaker capacity are sufficient and the
installation area is sufficient and complies with the requirements.
• Check that the power supply available agrees with nameplate voltage.
• Electrical work, wiring and cables must be performed in compliance with national and local wiring codes and
standard.
• Do not use the extension cables. In the case extended cables are needed, use the terminal block.

SELECTION OF THE LOCATION


• Select a place which provides the space around the units as shown in the diagram below.

Indoor Outdoor

MHC-MHH/MOC-MOH MHC-MHH/MOC-MOH
Models Models
07 09 12 18 25 35 07 09 12 18 25 35
A 60cm 60cm 60cm 60cm 60cm 60cm A 20cm 20cm 20cm 20cm 20cm 40cm
B 70cm 70cm 70cm 70cm 70cm 70cm B 60cm 60cm 60cm 60cm 60cm 80cm
C 60cm 60cm 60cm 60cm 60cm 60cm C 40cm 40cm 40cm 40cm 40cm 20cm
D 10cm 10cm 10cm 10cm 10cm 10cm D 20cm 20cm 20cm 20cm 20cm 30cm

Cautions
• Do not install in a place that cannot bear the weight of the unit.

133.5 497 133.5

429
248

64
230
268

24
64
234
315

287
335

MO 07-12
24

144 517 144 100 100


150 550 150
296

260
316

MO 25-35

MO 18

6 ENGLISH

01EN_02Install 6 03/15/2001, 13:10 PM


INSTALLATION IN THE FOLLOWING PLACES MAY RESULT IN TROUBLE

Installation of the indoor unit in direct sun light.

Installation in the unit in wrong direction.

EN

Installation of the indoor unit in a place where there


is an obstacle near the air inlet or outlet.
Installation of outdoor units too close or, blowing
discharged air into each other.
10 cm

Installation of the outdoor unit in a place exposed


regularly to a strong wind.
Installation of the indoor unit at too low a position

ENGLISH 7

01EN_02Install 7 03/15/2001, 13:10 PM


INSTALLATION DIAGRAM

10 cm or more

Installation plate

Remove the cover plate screw


to have access to the terminal
board.
60 cm or more

60 cm or more

70 cm or more

Auto louver (vertical)


Manual louver (horizontal)

Vinyl tape
Apply after carrying out a drainage
test.
* To carry out the drainage test,
remove the air filters and pour
water into the heat exchanger.

Connecting cable
20
cm
or
mo
re

Additional drain hose 20 cm or more

Liquid side piping

Gas side piping

60 cm or more
Vinyl tape

8 ENGLISH

01EN_02Install 8 03/15/2001, 13:10 PM


■ Wiring
INSTALLATION • This indoor unit is ready for connection to the outdoor
unit.
PROCEDURE
Cautions
• Never modify the unit by removing any of the safety
guards or by bypassing any of the safety interlock
INDOOR UNIT swithces.
• Connect the interconnecting cable correctly and
connect the connecting cable to terminal as identified
■ Fixing with their respective marking.
• Place the installation guide pattern on the designated
• Do not damage the conductor core or inner insulation
installation place and mark the hole position.
of power supply cables and do not deform or crush
• Drill a hole and mount installation plate
the cables.

■ Piping

ø70 mm

A Right

• After determining the pipe B Right


hole position. Drill the hole
.. .
... ...
at a slight downward slant ... ..... ..
.. .
... ...... ..
D Right
. . . ...
.. .... .. C Right F Left
towards the outdoor side. .. .
... ...... ..
. . Outdoor
E Rear Bottom
Note : When installing .. .
EN
... ... 5
... ..... ..
the refrigerant pipes from Indoor .. .
... ...... .. The auxiliary piping can be connected in the diections
.. .
... ...... .
others side. A hole must .. ..
... ..... ..
.
shown the above diagram. To connect in the D, E and F
... ....

be place to allow fall direction, pipes will need to be extended.


towards the outdoor unit.
Cautions
• Make ø5mm. 4-6 holes, in the wall at the four corners • Bend pipes carefully to avoid flattening or obstructing
of mouting plate (bracket) then insert appropriate them if the pipes are bent incorrectly, the indoor unit
mouting devices. may be unstable on the wall.
• Install the mounting plate using 4-6 pieces of mounting • Carefully arrange pipes so that pipes do not stick out
screw securely at four corners and tighten the screw of the rear plate of the indoor unit
completely. Do not over tighten the screws and deform
the back plate.

Cautions
• Be careful when handling the sharp edge of the
mounting plate.

ENGLISH 9

01EN_02Install 9 03/15/2001, 13:10 PM


■ Drain hose ■ Indoor Unit Fixing
• Drain hose is flexible and can be routed to suit various • Thread the indoor unit piping and cable through the
piping arrangements. The drain line must include elbow hole.
trap (U bend). Connect a plastic condensate pipe with • Hang the top of the unit onto the upper ridge of them
an internal diameter of 12 mm. in mounting plate.
• Make sure that the unit is correctly hung in place by
sliding it to the left, then to the right.
• Press the bottom left and bottom right hand corners of
the unit against the mounting plate until the fixing
prongs click into place in the retainers provided to that
effect.

Drainage line

Interconnection cable
(MHC-MHH/MOC-MOH 07, 09, 12 only)
Note: Do not put the drain hose end into water.
• For the model MHC-MHH 18, 25 and 35, install the
• The drain hose can be connected to the left or the central mounting bracket as shown in the below
right side. diagram.

For left and left rear piping

Drain hose (MHC-MHH18, 25 and 35)


Drain cap

Mounting Plate
For left and left rear piping

Central Mounting Bracket


(MHC-MHH18, 25 and 35)
Drain cap

Drain hose

Verification of condensate water drainge:


Fill the drain pan with water and observe evacuation.

a a) Access plate for the


condensate drainage
Condensate pump detection
drainage line (condensate pump is
Condensate available as an
drainage line accessorey).

Note: The condensate evacuation line should be taped to


the refrigerant lines with vinyl tape.

10 ENGLISH

01EN_03Install 10 20/3/01, 13:11


- Evacuate the piping. This operation, which should last
OUTDOOR UNIT at least 15 minutes if there are large piping lengths
and changes in elevation, should be followed by a leak
■ Fixing and Piping test.
• Piping must be performed by qualified personnel To this effect, when the piping has been evacuated,
according to good refrigeration systems practices. close the pressure gauge tap, note the value on the
• Piping materials and insulation materials must be of gauge, then wait for 15 minutes. If the needle moves,
there is a leak in the system. Make the necessary
refrigerant quality.
adjustments or repairs and repeat this procedure until
• Select the pipe diameters according to the size of unit the needle no longer moves.
and cut the pipe to design length by using pipe cutter. - Open the service valves and top up the refrigerant
• Install the flare nuts and flare the end of the pipes. charge if necessary.
• Check that no foreign bodies are inside the piping.
• Align the central of the connecting pipes and tighten Installation
the flare nut.
• Fix piping with pipe clamps and check that any pipe
vibrations cannot be transmitted to the building
structure.
Note
• Connect the pipe correctly.
• Do not apply the excessive torque. Minimum thickness 6 mm
• Use an appropriate bending tool to form curves and
avoid over-tightening the refrigerant tubes. Heat pump L
(discharge)
• To prevent heat loss, the two lines must be insulated
separately.
Heat pump

■ Maximum piping lengths


Liquid
Unit size 7 9 12 18 25 35 D
D (m) 10 12 15 15 22 20 Cooling Cooling
L (m) 12 15 18 18 25 25 (suction)

H (m) 7 10 12 12 20 22

Note : Where the difference in elevation between the indoor Heat pump EN
(discharge)
unit and the outdoor unit is greater than 5 meters,
install an oil trap every 5 meters.
L
The suction line must have a 2% gradient up to the Heat pump
compressor on horizontal sections.
Where piping lengths are unusually long and include a Liquid H
large number of oil traps, it may be necessary to adjust GASS
to compressor charge.
Cooling Cooling
(suction)
Refrigerant charge to be added per extra
metre of piping length when more than 7.5
meters.
Low pressure High pressure
Unit size MHC-MHH/MOC-MOH
7 9 12 18 25 35 Manifold
g/m 15 15 15 40 40 40

■ Refrigerant piping connections


(FLARE connections)
To avoid alteration of unit capacities, check that piping Gas valve
Liquid valve
lengths and changes in elevation are kept to a strict Pressure tap
minimum.
Outdoor Unit Indoor Unit
Gas Line
Before connectiong the refrigerant lines, follow the
procedures below (if pre-charged connection lines are Liquid Line
not supplied):

- Select copper pipe diameters according to the size of R22


unit to be installed.
- Install the refrigeration lines, checking that no foreign This unit is shipped complete with a charge of R22 refrigerant
boodies get inside the piping. that will be sufficient for an interconnecting piping length of
5 meters.
- Install the flare connectors and flare the ends of the
pipes.

ENGLISH 11

01EN_03Install 11 20/3/01, 13:11


■ Vertical Discharge Condensing Unit ■ Electrical Connections
(H*DA, H*DB, H*RA) All electrical wiring and connections must comply with
The indoor unit and interconnecting voltage is 220 local codes and standards. Power supply cord and
volts. Where the outdoor unit requires a different interconnection cord used must not be lighter than
operating voltage such as 24 volts one of the following Polychloroprene sheated cord (245 IEC 57 or H05RN-F).
solutions can be applied.
1. The coil of the relay switching the compressor and Disconnecting device must have a contact separation
reversing valves should be changed to 220V. of at least 3 mm.
2. A transformer should be installed to sypply 24 volts
and a relay installed with a 220 volt coil to switch the MHC-07-35 -Cooling Only
24 volts required by the outdoor units. The transformer
should not be energised at all times and not switched N 1 2
Indoor
by the start signal from the indoor unit. Switching the Unit
transformer directly will cause electronic noise which
L N 2 Outdoor
may cause malfunction of the electronics. 1
Unit
▲ ▲
Power Supply Power Supply
24 V FROM OUTDOOR UNIT 220-240V/1Ph/50Hz

208-230V/1Ph/60Hz
Cooling Only Units
Indoor
Unit MHH-07-35 -Heat Pump

Indoor
N 1 2 3
Unit

Outdoor
L N 1 2 3
Unit
▲ ▲
■ Wiring Power Supply
220-240V/1Ph/50Hz

208-230V/1Ph/60Hz

For correct installation, a proper ground connection must be


made for unit.

Wiring sizes

Unit size 7 9 12 18 25 35
2
Power supply mm 3x2.5 3x4 5x2.5
Interconnection Cooling mm2 3x2.5 + Ground
(Indoor/Outdoor) Heating mm2 4x2.5 + Ground
Fuse (slow-Blow) A 10 16 20 10
Or as required to meet national and local codes.

Note
L N 1 2
• Terminals N and 1 (see diagrams above) correspond
to power supply to the indoor unit coming from the
outdoor unit.
• Compressor power supply is established by teminal 2.
• Power supply to the 4-way valve is established by
terminal 3.
For further detail on wiring of these units, see the diagrams pasted • For further details on wiring of these units, see the
inside each unit diagrams pasted inside each unit.

Cautions
• Never modify the unit by removing any of the safety
guards or by bypassing any of the safety interlock
swithces.
• Connect the connecting cable correctly and connect
the connecting cable to terminal as identified with their
respective marks.
• Do not scratch the conductive core & inner insulator of
power supply cables and do not deform or smash on
the surface of cables.

12 ENGLISH

01EN_03Install 12 20/3/01, 13:11


TEST OPERATION
CHECK THIS ITEM BEFORE START OPERATION
Outdoor
• Check the flare nut connections, valve stem cap connections and service cap connections for gas leak with a leak
detector or soap water.
Indoor
• Check the unit is firmly fixed.
• Check the connecting pipes are tighten securely.
• Check the pipe insulation.
• Check the drainage.
• Check the connection of the grounding wire.

SYSTEM TEST DIAGNOSTICS


Test Operation Mode
1) This is a diagnostic mode to check the functioning of a unit. In installations with multiple units it is possible to start
the Test Operation Mode in all the units sequenially and run the test mode in parallel, thus shortening the time for
service calls. By consulting the status of each unit a diagnosis can be made of any problems or normal operation
can be verified.
2) Test Operation mode carries out the following operational sequence and then returns to the normal mode after
the Test operation is finished. In the case of Cool only systems the sequence will be completed after STEP 2. If a
problem is encountered during Test Operation mode the unit will indicate this as shown in the chart below and the
LED Display will flash according to the LED Diagnostic Codes. If an error occurs the reset shall be when the EMS
switch is pressed for more than 1 second and less than 10 seconds. Upon release, the operation shall return to
normal and the unit shall be off. EN
3) To start this mode, the emergency switch must be pressed for at least 10 seconds and released while in normal
operation mode. To interrupt this mode, press the emergency switch again for at least 10 seconds.
4) If a failure occurs during the test mode operation the unit the board shall:-
- Stop the operating of compressor
- Indicate the error by the lamp out puts
- Remain in that condition until reset

Test Operation Mode


Operation time
In cool only mode Input Minutes
STEP 1 Fan only high 3
STEP 2 Cool mode : fan high 4 Diagnostic
Cool mode : fan med 2
Cool mode : fan low 3
STEP 3 Stop Waiting 3
STEP 4 Heating mode : fan high 4 Diagnostic
Heating mode : fan med 2
Heating mode : fan low 3
STEP 5 Waiting 3

Any timer settings entered before the start of the Test Operation Mode will not be affected by the Test Operation Mode.
Failure display follows the conditions below.
Status Operation Terminating Condition
Low HP temp < 20˚C fan stop and louver full open Coil temp 20˚C
Coil temp > 40˚C (cooling) fan stop and louver full open Coil temp 40˚C
Overheat > 62˚C (heating) louver full open Coil temp 50˚C
Anti Freeze louver full open Coil temp 5˚C
Low voltage halt return to normal range
Sensor fail stop system reset
Cooling fail stop system reset
Heating fail stop system reset

ENGLISH 13

01EN_03Install 13 20/3/01, 13:11


TROUBLE SHOOTING GUIDE

Problem Probable cause Remedy


A. The air conditioner does not run. 1. Power Failure. 1. Wait for Power resume.
2. Fuse blown or circuit breaker 2. Replace the fuse or reset the
open. breaker.
3. Voltage is too low. 3. Find the cause and fix it.
4. Faulty contactor or relay. 4. Replace the faulty component.
5. Electrical connections loose. 5. Retighten the connection.
6. Thermostat adjustment too low 6. Check Thermostat setting.
(in heating mode) or too high (in
cooling mode)
7. Faulty Capacitor 7. Find the cause then replace
Capacitor.
8. Incorrect wiring, terminal loose 8. Check and retighten.
9. Pressure switch tripped 9. Find the cause before reset.
B. The outdoor fan runs but the 1. Motor winding cut or grounded. 1. Check the wiring and the
compressor will not start. compressor winding resistance.
2. Faulty Capacitor. 2. Find the cause then replace
Capacitor.
C. There is insufficient heating or 1. There is a gas leak. 1. Remove charge, repair, evacuate
cooling. and recharge.
2. Liquid and gas line insulated 2. Insulate them separately.
together.
3. The room was probably very hot 3. Wait while unit has enough time to
(cool) when you started the cool the room.
system.
D. The compressor run 1. Thermostat adjustment too low 1. Check Thermostat setting.
continuously. (in heating mode) or too high (in
cooling mode)
2. Faulty fan. 2. Check condenser air circulation.
3. Refrigerant charge too low, leak. 3. Find leak, repair and recharge.
4. Air or incondensables in 4. Remove charge, evacuate and
refrigerant circuit. recharge.
E. The compressor starts but shuts 1. Too much or too little refrigerant. 1. Remove charge, evacuate and
down quickly. recharge.
2. Faulty compressor. 2. Determine the cause and replace
compressor.
3. Air or incondensables in 3. Remove charge, evacuate and
refrigerant circuit. recharge.
4. Changeover valve damaged or 4. Replace it.
blocked open (heat pump unit)
F. Clicking sound is heard from In heating or cooling operation any In heating or cooling operation any
the air conditioner. plastic parts may expand or shrink plastic parts may expand or shrink due
due to a sudden temperatue change to a sudden temperatue change in this
in this event, a clicking sound may event, a clicking sound may occur.
occur.

14 ENGLISH

01EN_03Install 14 20/3/01, 13:11


DIAGNOSTIC INFORMATION FUNCTION
Status Power Timer Operation Mode
OFF(with power on) O O O Normal Operation
ON (Temperature satisfied) X O O Normal Operation
Waiting for delay X F-1 O Normal Operation
Compressor started X O X Normal Operation
Sleep mode X X X/O Normal Operation
Start timer set X F-2 X/O Normal Operation
Stop timer set X F-3 X/O Normal Operation
Low HP temp < 20°C X O F-1 Protection
Coil temp > 40°C (cooling) X O F-2 Protection
Overheat > 62° (heating) X F-1 F-1 Protection
Anti Freeze X F-2 F-2 Protection
Low voltage F-2 O O Protection
Sensor fail F-1 O F-1 Reset-Call Service Technician
Cooling fail F-2 O F-2 Reset-Call Service Technician
Heating fail F-3 O F-3 Reset-Call Service Technician
Emergency operation F-3 Note 1 Note 1 Operational
Test operation F-1 F-1 F-1 Operational
Filter F-3 F-3 F-3 Protection

X = ON, O = OFF, F-1 = ON : 0.5 sec, OFF : 0.5 sec


F-2 = ON : 1.5 sec, OFF : 0.5 sec
F-3 = ON : 0.5 sec, OFF : 1.5 sec
Notes
1) In emergency mode, the Power light will flash and the other lights will indicate the operation as above.
2) Lights will flash during the time that the units is held off, due to Low Voltage. If the voltage has passed through
the reset voltage and the unit is waiting for the time delay, the lights will go to normal operation. EN
3) The lights will show the LED Diagnostic Code even when the unit is off.

ENGLISH 15

01EN_03Install 15 20/3/01, 13:11


TECHNICAL SPECIFICATION

MHC-MHH
Indoor Unit
Model 07 09 12 18 25 35
MOC-MOH
Outdoor Unit
07 09 12 18 25 35
Power Supply V/Ph/Hz 220-240/1/50 or 380-415/3/50
Ph 1 1 1 1 1 3 1 3
Maximum Power Consumption kW 0.7 0.85 1.2 2.0 2.8 2.71 3.37 3.29
Running Current A 3.5 4.5 5.6 9.1 11.5 5.34 16.26 6.65
Fuse Size A 10 10 10 16 20 10 32 16
Compressor Type Rotary Rot./Rec. Reciprocating Reciprocating
Suction 3/8" 3/8" 1/2" 5/8" 5/8" 5/8"
Piping Diameter
Liquid 1/4" 1/4" 1/4" 3/8" 3/8" 3/8"
H(mm) 290 290 290 315 315 356
Indoor W(mm) 799 799 799 1019 1019 1156
Dimensions D(mm) 181 181 181 180 180 203
H(mm) 492 492 492 590 696 900
Outdoor W(mm) 764 764 764 820 850 850
D(mm) 230 230 230 280 287 285
Indoor kg 8 8 8 12 12 23
Weights
Outdoor kg 34 36 38 59 65 76
Made in Thailand

CONDENSING UNIT
■ MOC-MOH
Outdoor MOC-MOH
Models
Unit 07 09 12 18 25 35 45 55 65
V/Ph/Hz 220-240/1/50 or 380-415/3/50
Power Supply
Ph 1 1 1 1 3 1 3 1 3 3 3 3
Power Consumption kW 0.82 0.96 1.26 1.82 2.01 2.71 2.64 3.29 3.22 4.62 5.44 5.87
Running Current A 3.77 4.42 5.52 8.42 3.82 12.82 5.02 15.74 6.16 8.26 10.36 11.22
Compressor Rotary Rotary/Reciprocating Reciprocating Scroll
Refrigerant Type R-22
Air Flow m3/h 1220 1220 1220 3310 3310 3832 4748 7885 7646
noise Level dBa 49 49 50 56 57 57 54 57 57
V/Ph/Hz 208-230/1/60 or 380-460/3/60
Power Supply
Ph 1 1 1 1 1 1 3 3 3 -
Power Consumption kW - 0.97 1.2 2.31 3.02 3.65 3.99 5.62 6.67 -
Running Current A - 4.8 5.5 13.62 14.02 16.77 6.67 8.7 11.24 -
Compressor Rotary Reciprocating
Refrigerant Type R-22
3
Air Flow m /h - 1220 1220 3310 3310 3832 4748 7885 -
noise Level dBa - 34 38 56 57 57 54 57 -

16 ENGLISH

01EN_03Install 16 20/3/01, 13:11


■ R407C
Outdoor MOC
Models
Unit 07G 09G 12G 18G 25G 35G 45G 55G -
V/Ph/Hz 220-240/1/50 380/3/50
Power Supply
Ph 1 1 1 1 1 3 3 3 -
Power Consumption kW 0.7 0.8 1.1 1.6 2.3 3.2 3.6 4.3 -
Running Current A 3.4 4.2 5.4 9.4 11.5 5.6 6.6 7.8 -
Compressor Rotary Reciprocating
Refrigerant Type R407C
Air Flow m3/h 1220 1220 1220 1600 3100 3100 6200 6200 -
noise Level dBa 40 40 40 46 52 52 52 53 -

■ H*DA
Outdoor H*DA
Models
Unit 012 018 024 030 036 048 060 076
V/Ph/Hz 220-240/1/50 380/3/50
Power Supply
Ph 1 1 1 1 3 3 3 3
Compressor Reciprocating
Refrigerant Type R-22

■ H*DB
Outdoor H*DB
Models
Unit 012 018 024 030 036 042 048 060 076
V/Ph/Hz 208/230-1-60 - EN
Power Supply - 460-3-60 - 460-3-60
Ph 1 1 1 1 1/3 1 1/3 1/3 3
Compressor Reciprocating Scroll Recip
Refrigerant Type R-22

■ H*RA
Outdoor H*RA
Models
Unit 018 024 030 036 048 060
V/Ph/Hz 220-240/1/50 380/3/50
Power Supply
Ph 1 1 1 1 3 3 3
Compressor Reciprocating
Refrigerant Type R-22
V/Ph/Hz 208/230-1-60
Power Supply
Ph 1 1 1 1 1 1
Compressor Reciprocating Scroll
Refrigerant Type R-22

ENGLISH 17

01EN_03Install 17 20/3/01, 13:11


■ MMC-MMH
Outdoor MMC-MMH
Models
Unit 018 021 025 036 050
V/Ph/Hz 220-240/1/50 or 380-415/3/50
Power Supply
Ph 1 1 1 1 1
Power Consumption kW 2x0.85 0.85x1.20 2x1.20 2x1.73 2x2.26
Running Current A 2x4.5 4.5x5.7 2x5.7 16.9 26.5
Compressor Rotary Recip
Refrigerant Type R-22
V/Ph/Hz 208-230/1/60
Power Supply
Ph 1 1 1 1 1
Power Consumption kW 2x0.85 0.85x1.20 2x1.20 2x1.73 2x2.26
Running Current A 2x4.5 4.5x5.7 2x5.7 16.9 26.5
Compressor Rotary Recip
Refrigerant Type R-22

18 ENGLISH

01EN_03Install 18 20/3/01, 13:11


DE - COMMISSIONING DISMANTLING & DISPOSAL
This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a EN
danger and cause injury!
All work must only be carried out by competent persons using suitable protective clothing and safety precautions.

Read the Manual Risk of electric shock Unit is remotely controlled and
may start without warning

1. Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure
that all points of electrical and gas isolation are secured in the OFF position. The supply cables and gas pipework may
then be disconnected and removed. For points of connection refer to unit installation instructions.
2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit.
This refrigerant may then be re-used, if appropriate, or returned to the manufacturer for disposal. Under No
circumstances should refrigerant be vented to atmosphere. Where appropriate, drain the refrigerant oil from each
system into a suitable container and dispose of according to local laws and regulations governing disposal of oily
wastes.
3. Packaged unit can generally be removed in one piece after disconnection as above. Any fixing down bolts should be
removed and then unit lifted from position using the points provided and equipment of adequate lifting capacity.
Reference MUST be made to the unit installation instructions for unit weight and correct methods of lifting. Note that
any residual or spilt refrigerant oil should be mopped up and disposed of as described above.
4. After removal from position the unit parts may be disposed of according to local laws and regulations.

YORK® International Corporation

ENGLISH 19

01EN_03Install 19 20/3/01, 13:11

S-ar putea să vă placă și