Sunteți pe pagina 1din 6

Faculty of Electrical Engineering VOL. 11, NO.

2, 2009, 34-39
Universiti Teknologi Malaysia ELEKTRIKA
http://fke.utm.my/elektrika

Voltage Sag Effects on a Refinery with Induction


Motors Loads
Mahmoud A. El-Gammal1, Amr Y. Abou-Ghazala1 and Tarek I. El-Shennawy2*
1
Faculty of Electrical Engineering, Alexandria University, Alexandria 21544, Egypt.
2
Alexandria National Refining and Petrochemicals Co. (ANRPC), Alexandria 23111, Egypt.
*
Corresponding author: tshennawy@yahoo.com, Tel: 203-4402128, Fax: 203-4446785

Abstract: Process continuity of industrial plants (like a refinery) is subjected to several shutdowns due to voltage sags
causing large induction motors (IM) to trip. In this paper, the response of induction motors to voltage sags is investigated
through computer simulations using the MATLAB/SIMULINK toolbox. The simulations are verified by actual performance.
The basic observed effects of voltage sags on IM are speed loss and current and torque transients associated with both
voltage reduction and recovery. Results have also showed that three-phase voltage sags and sags occurring at zero crossing
are the most severe events. Transient currents occurring at the instants of voltage sag and voltage recovery are directly
proportional to the voltage drop, not to the remaining voltage magnitude. Transient currents and torques induced at the
instant of sag recovery are higher than those induced at the instant of sag starting. Unloaded motors and motors operated at
voltages higher than the nominal voltage are less affected by voltage sags. Conservative protection settings may cause IM to
trip leading to plant unnecessary shutdown. Readjusting the motor protection relays based on the procedure proposed in this
paper may be adequate to ride-through most of voltage sags. No compensation equipment are required.

Keywords: Induction motors, power quality, voltage sags.

In [4], It was shown that voltage sag will reduce the


1. INTRODUCTION motor torque proportional to the square of the motor
The IEEE defines voltage sag as a decrease to between terminal voltage, the motor will slow down and the
0.1 and 0.9 pu in rms voltage or current at the power continuity of the output may be lost. Depending on the
frequency for durations of 0.5 cycle to 1 min. The depth and the duration of the voltage, the motor speed
amplitude of voltage sag is the value of the remaining may recover to its normal value as the voltage amplitude
voltage during the sag [1]. recovers. Otherwise, the motor speed may slow down and
The IEC terminology for voltage sag is dip. The IEC the torque exerted by the motor could not supply the load.
defines voltage dip as: A sudden reduction of the voltage Figure 2, reproduced from [5], shows three different
at a point in the electrical system, followed by voltage torque speed characteristics of an IM, along with a
recovery after a short period of time, from half a cycle to
constant load torque. Curve A shows this relation during
a few seconds. The amplitude of a voltage dip is defined
normal conditions. Voltage sag will reduce the motor
as the difference between the voltage during the voltage
dip and the nominal voltage of the system expressed as a torque proportional to the square of the motor terminal
percentage of the nominal voltage [2]. voltage. The IM may undergo a limited amount of
Figure 1 shows an rms representation of voltage sag, retardation and may be able to reaccelerate on voltage
the sag starts when the voltage decreases to lower than recovery, as shown in curve B. Otherwise, the electric
the threshold voltage Vthr (0.9 pu) at time T1. The sag torque produced by the IM may become less than that of
continues till T2 at which the voltage recovers to a value the load, the IM may decelerate, and the continuity of the
over the threshold value, hence the duration of the voltage output may be lost, as shown in curve C.
sag is (T2-T1) and the magnitude of the voltage sag is sag
to Vsag [3].

Figure 1. Voltage Sag Figure 2. Motor and Load Torques before and during
different sags

34
MAHMOUD A. EL-GAMMAL, AMR Y. ABOU-GHAZALA, TAREK I. EL-SHENNAWY / ELEKTRIKA, 11(2), 2009, 34-39

In [6], the situation of reapplication of out of phase In summary, voltage sags affect the operation of IM in
voltage (on voltage recovery) to a motor running with a various ways; on occurrence of a voltage sag, the IM
strong remaining rotor field (during sag) was discussed. It decelerates, its torque decreases in square proportion to
was shown that this may result in electromagnetic and the voltage sag, the IM may not fulfill the load
shaft torque and current transients which may exceed the requirements and may stall. The IM may continue to
starting values, and may be destructive to the motor shaft. operate and deliver power to the load, however, on
voltage recovery, the transient currents and torques may
In [7], the problem of prolonged voltage sag due to
be greater than those of starting, and the motor may be
the presence of motor loads was shown. Depending upon
stressed and damaged.
the initial speed loss and the magnitude of the recovery
voltage after fault clearance, the motors may accelerate, 2. METHODS
taking currents that may approach the starting currents of
the motors. These starting currents of accelerating 2.1 Test Circuit
motors, flowing together through the supply system The test circuit consists of a voltage source adjusted to
impedance, may prevent a fast recovery of voltage. The simulate voltage sags with pre-determined magnitudes
stronger the electrical system in relation to the size of the and durations affecting an induction motor, which drives
accelerating motors, the greater is the power available for a compressor load. The load torque starts from a constant
the motors to accelerate and recover. value of 2000 N.m., and then increases gradually in direct
An experimental study on a small IM had showed that proportion to the speed, till it reaches its full load value
the phenomena of the hot-load pickup arising during the (about 80 % of motor torque).
process of voltage recovery may affect the motor Figure 3 shows the implementation of a simple power
windings due to large thermal stresses [8]. system in the SimPowerSys Blockset in the MATLAB
In [9], an Electro-Magnetic Transient Program workspace. The motor and load parameters are given in
(EMTP) was used to simulate the response of large IM to Tables 1 and 2 respectively. The protection relays settings
voltage dips. It was found that most of induction machine are given in Table 3, the motor calculated parameters are
protection settings are too conservative. This leaves room given in the appendix.
for adjusting these settings without causing any threat to
the motor safety. Many of the unnecessary motor tripping Table 1. Motor Parameters
incidents could be avoided by simple adjustment to the Rated Power 2500 kW
motor protection settings. Rated Voltage 11000 V
In [10], a comparison was drawn between the effects Frequency 50 Hz
of symmetrical and unsymmetrical voltage sags on the
Full Load Current 153 A
behavior of IM. It was found that the most severe sags are
the symmetrical ones, and the least severe are the single- RPM 1496
phase ones. Starting Current 600% FLC
The effect of multiple voltage sags or a sequence of Starting time 22 sec
different sags on a specific IM was carried out in [11].
These consecutive sags had caused damages in the Power factor 0.9
mechanical structure of the machine, such as damages in Moment of Inertia 560 kg.m2
bearings, in the shaft, etc. another effect was the damages Rated Torque (T) 15959 N.m
in the isolation due to the increase of current in the
Locked Rotor Torque 75%
windings, which produces heating. It was noticed that
these damages were evidenced as, for example, audible Pull up Torque 65%
vibrations in the machine. Breakdown Torque 270%

Figure 3. Simulink model for the test circuit

35
MAHMOUD A. EL-GAMMAL, AMR Y. ABOU-GHAZALA, TAREK I. EL-SHENNAWY / ELEKTRIKA, 11(2), 2009, 34-39

Table 2. Load parameters ƒ The motor speed accelerates gradually during the
Max. Absorbed starting period till it reaches its operating speed at
2057 kW
Power 1486 rpm in about 20 seconds.
Maximum ƒ The starting current of the motor rushes to about 930
13092 N.m
Torque A (approximately 600% of full load), then the current
Starting Torque 1960 N.m
Moment of
1000 kg.m2 1500

Inertia 1000

rpm
500

0
0 5 10 15 20 25 30

1000

Table 3. Motor protection settings

Amp
500

168 A
Over Current Setting
0
0 5 10 15 20 25 30

Inverse time 1
x 10
5

0.8 pu

Torque
(N.m)
Under Voltage 0

1 sec -1
0 5 10 15 20 25 30
Time

Figure 4. Motor starting speed, current, and torque


2.2 Test Procedure
a) The motor is operated with normal (no sag) decreases to its normal current of about 118 A (the
conditions. From this step, we can quantify the motor operates at 80% of its full load).
transient currents and torques that the motor is ƒ The motor is subjected to a pulsating torque from
subjected to during starting. +72,000 N.m to -54,000 N.m (peak to peak), for a
b) A three-phase balanced voltage sag is simulated with period of 2 seconds. After which, these pulsations
magnitude and duration equal to the existing settings decay and the motor operates with increasing
of the undervoltage relay. From this step we can see unidirectional torque until it reaches its maximum
the actual transient current and torque the motor is value of 50,000 N.m in 20 seconds. After which the
subjected to before tripped by the undervoltage motor torque intersects with the load torque at the
protection. operating point and the motor continues to deliver its
c) The IM is subjected to a set of voltage sags in all normal torque of 13,000 N.m.
three phases at different magnitudes (ranging from
0.1 p.u. to the voltage sag threshold of 0.9 p.u.) with 3.2 Voltage sag at the existing protection setting
a step of 0.05 pu, and for each sag value the duration The motor is subjected to a three phase voltage sag with
is incremented gradually till the motor trips by 80% magnitude and a duration of 1 sec. the sag starts at
overcurrent or locked rotor or mechanical protection t=30 sec and recovers 1 sec later. This situation is
relays. From this step, we can construct a table with presented in Figure 5, and the following observations are
the limiting values of accepted voltage during
different sags affecting the IM under test. 1.2
x 10
4

d) From the previous step, we can construct a sag


Volt

tolerance curve for the IM under test. The voltage 0.8


28 28.5 29 29.5 30 30.5 31 31.5 32 32.5 33

acceptability curves are aides in the determination of 1500

whether the supply voltage to a load is acceptable for 1480


rpm

1460

maintaining the continuity of a load process [12]. 28 28.5 29 29.5 30 30.5 31 31.5 32 32.5 33

e) The undervoltage relay is readjusted using results of 500


Amp

the previous step, and the new setting is verified by 0

new simulation. 28
x 10
4
28.5 29 29.5 30 30.5 31 31.5 32 32.5 33

5
f) Parameters other than magnitude and duration are 0

tested to complete the sensitivity analysis: -5


28 28.5 29 29.5 30 30.5 31 31.5 32 32.5 33

i) Effect of other types of sags Time

ii) Effect of pre-sag voltage. Figure 5. Voltage, speed, current, and torque for a sag to
iii) Operating the motor at ¾ and ½ full load. 80%, 1 sec
iv) Effect of source harmonic distortion. noted:
v) Effect of point on the wave. ƒ The speed drops to a value of 1477 rpm (99% of
normal).
3. RESULTS AND DISCUSSIONS ƒ The motor current increases on occurrence of the sag
3.1 Normal Conditions event reaching a value of 263 A (222% of normal and
The results of this normal situation are shown in Figure 4. 28% of starting), then drops eventually since a new
From these results, the following remarks are noted: operating point is reached. The motor continues running
with increasing current till the voltage recover. At this
instant, the initial operating point is reached and the

36
MAHMOUD A. EL-GAMMAL, AMR Y. ABOU-GHAZALA, TAREK I. EL-SHENNAWY / ELEKTRIKA, 11(2), 2009, 34-39

motor draws a transient current of 337 A (285% of is the inverse current-time characteristics. Since the
normal and 36% of starting). motor voltage decreases, the motor tries to supply the
ƒ The torque also shows two transients on sag load power by drawing higher current, thus triggering
occurrence and on full voltage recovery. The sag transient the overcurrent protection.
approaches 25,500 N.m (196% of normal and 35% of ƒ All sags with remaining magnitude 40% of p.u.
starting), whereas the recovery transient approaches voltage and below result in severe transient torques
30,000 N.m (230% of normal and 42% of starting). that trigger the mechanical protection relays. The
From these observations, it is clear that the criterion here is the speed loss, and it is of constant
undervoltage relay settings are too conservative for the value. As the speed of the motor decreases below the
motor operation. The undervoltage relay settings should threshold (95% of the normal speed), the motor trips
be readjusted, and considered as a backup protection for by mechanical protection.
other motor protection relays.

3.3 Tripping the IM without Undervoltage Relay 3.4 Voltage Sag Tolerance Curve
The motor is subjected to three phase voltage sags at t=30 Figure 6 is the voltage sag tolerance curve (or ride
sec. The magnitude of the remaining voltage starts from
0.9 p.u. of the rated line voltage and decreases gradually 1

in steps of 0.05 p.u. For each case, the duration of the sag 0.9

will increase gradually till the motor trips, either by


0.8

0.7

overcurrent, locked rotor or mechanical protection. if no

remaining voltage (pu)


0.6

trigger signal comes out from the protection relays, the 0.5

simulation continues till it ends at t=40 sec. The results of 0.4


Trip
0.3 Region
this step are presented in Table 4. 0.2

0.1

Table 4. Limiting values tripping the IM 0


0 1 2 3 4 5
time (sec)
6 7 8 9 10

Sag Sag duration Motor tripped Limiting


voltage (sec) by value Figure 6. Voltage tolerance curve for the IM
(pu)
0.90 > 10 sec No trip - through curve) of the IM under test. It is expected that
0.80 > 10 sec No trip - each motor (and any piece of equipment) has its own
0.70 > 10 sec No trip - curve. The whole plant is sensitive to, and may shut down
0.65 4.488 overcurrent 181 as a result of, the most sensitive piece of equipment.
Note that this curve, constructed from Table 4, is
0.60 2.550 overcurrent 195 A
based only on magnitude and duration. Other factors
0.55 2.093 overcurrent 204 A
characterizing voltage sag such as unbalance of the three
0.50 1.935 overcurrent 209 A
phases, point on the wave of sag occurrence and
0.45 1.900 overcurrent 212 A
recovery, pre-sag voltage, loading percentage, etc… are
0.40 1.760 Speed loss 1410 rpm discussed in the sensitivity analysis.
0.35 1.443 Speed loss 1410 rpm
0.30 1.252 Speed loss 1410 rpm 3.5 Recommended Undervoltage Settings
0.25 1.127 Speed loss 1410 rpm Based on the results obtained from Table 4, the
0.20 1.040 Speed loss 1410 rpm recommended settings for the undervoltage relay are
0.15 0.980 Speed loss 1410 rpm adjusted to 0.75 pu, 1.5 sec.
0.10 0.937 Speed loss 1410 rpm To verify these new settings, a new simulation with
0.0 0.900 Speed loss 1410 rpm these values as the sag magnitude and duration is carried
out and is shown in Figure 7.
From Table 4, the following remarks are noted: It is clear that the current, the torque, and the speed do
ƒ The first sag event that trips the motor occurs for a sag not approach their limiting values of starting. The speed
to 65% p.u., for a duration of 4.5 seconds. This shows drops to 1473 rpm (99% of normal speed). The current
that how the existing settings for the undervoltage transients are 323 A on sag start (273% of normal and
relay is too conservative, and that many shutdowns 35% of starting) and 405 A on voltage recovery (342% of
due to motor tripping could have been avoidable. normal and 43% of starting). The torque transients are
ƒ As the remaining voltage during the sag decreases 28,000 N.m on sag start (215% of normal and 38% of
(voltage drop increases), the tripping time decreases. starting) and 33,500 N.m on voltage recovery (258% of
his is predicted as the criterion used to trip the motor normal and 46% of starting).

37
MAHMOUD A. EL-GAMMAL, AMR Y. ABOU-GHAZALA, TAREK I. EL-SHENNAWY / ELEKTRIKA, 11(2), 2009, 34-39

the normal current decreases to 73 A, and the normal


torque is reduced to 7500 N.m.
12000
10000 The IM response to both situations is presented in
Volt

8000
6000
28 28.5 29 29.5 30 30.5 31 31.5 32 32.5 33
Table 7. It is clear that the possibility of the IM to survive
1490 a sag increases by decreasing the loading conditions.
1480
rpm

1470
1460
28 28.5 29 29.5 30 30.5 31 31.5 32 32.5 33
3.6.4 Effect of source harmonic distortion.
500
Consider again the test signal of Figure 7. Assume that
Amp

0
28 28.5 29 29.5 30 30.5 31 31.5 32 32.5 33
there are some harmonics present at the supply bus.
4
4
x 10
Normally triplen harmonics are eliminated in the power
transformer. What really matters is the distortion level of
Torque
(N.m)

2
0

the 5th and sometimes the 7th harmonics. Now, if we


-2
28 28.5 29 29.5 30 30.5 31 31.5 32 32.5 33
Time

introduce a 5th harmonic with 20% p.u. and a 7th with


Figure 7. Voltage, speed, current, and torque for
15% p.u. to our test signal, the results show minor
a sag to 75%, 1.5 sec
differences between the two casess, with the exception of
bold torque. This boldness refers actually to the power
3.6 Sensitivity Analysis frequency oscillations in the motor torque due to presence
Factors other than magnitude and duration may have of harmonic distortion.
effect on the response of the IM to the voltage sag. Some
of these factors are examined and discussed in this 3.6.5 Point on the wave of sag occurrence/recovery
section. In all the previously simulated sags, the sag starts at t=30
sec, which corresponds to zero phase angle. Moreover,
3.6.1 Unbalanced voltage sag the voltage recovers at t=31.5 sec, again corresponding to
Although the severity of the three phase voltage sag is zero angle. Consider now that the sag occurs at any
expected to be more than that of the single phase sag, yet instant (angle other than zero) which is almost the actual
the latter is more frequent especially on the distribution case, and recovers at a different angle. A new set of
circuits. The test is repeated for a sag on one phase and simulations is carried out with the same sag magnitude
the results are presented in Table 5, and compared with and duration, but at different instants. Comparison
results of Figure 7. As expected, the single phase sag is between the reference sag and the most significant case
less severe than the three phase one. This can be (with angle = 90°) is given in Table 8.
interpreted, as the full voltage present on the other two It is clear that when the sag occurs/recovers at 90°
healthy phases will support the motor during the sag and angle in the voltage signal, this corresponds to near zero
at recovery. angle in the current signal, current transients in this case
are minimum.
3.6.2 Effect of pre-sag voltage.
As the supply voltage may range from 1.05 p.u. to 0.95 Table 5. Effect of Unbalanced Sag
p.u., transient currents and torques may vary substantially Sag Recovery Sag Recovery
speed
for such tolerance. A summary of the IM response to current current torque torque
these sags are shown in Table 6. Three
phase 1473 323 405 28,000 33,500
Comparing with the reference 1.0 pu pre-sag, there is
sag
almost no change in the IM speed. However, transient
Single
currents and torques on occurrence of sag differ phase 1483 225 255 30,000 28,000
noticeably; transient currents and torques for voltage sag
difference of 20% are less than those for voltage
difference of 30%. This may explain why the IM may trip Table 6. Effect of Pre-sag Voltage
(by the overcurrent relay) on a voltage drop to 75% Sag Recovery Sag Recovery
lasting for 1.5 sec in case of pre-sag voltage equals 1.05 speed
current current torque torque
pu, while the same IM may survive the same voltage sag Pre-sag
in case of pre-sag voltage equals 0.95 pu. 1473 385 405 32,000 33,500
1.05 pu
Pre-sag
1473 264 405 24,400 33,500
3.6.3 Operating the motor at ¾ and ½ of the full load. 0.95 pu
In some cases, the industrial process operates the motor at
¾ or ½ its full load. Note that the basic parameters of the Table 7. Effect of Loading Conditions
motor are now changed. In case of ¾ load, there will exist Sag Recovery Sag Recovery
speed
a new operating point, for which the normal speed current current torque torque
increases to 1489 rpm, the normal current decreases to 95 ¾
1481 317 380 26,000 30,000
A, and the normal torque is reduced to 10,000 N.m. In load
case of ½ load, the normal speed increases to 1493 rpm, ½
1489 315 360 24,000 26,000
load

38
MAHMOUD A. EL-GAMMAL, AMR Y. ABOU-GHAZALA, TAREK I. EL-SHENNAWY / ELEKTRIKA, 11(2), 2009, 34-39

Table 8. Effect of Point on the Wave Environment for Low-Frequency Conducted


Sag Recovery Sag Recovery Disturbances and Signalling in Public Power Supply
speed
current current torque torque Systems, May 1990.
90° [3] M. Bollen, Understanding Power Quality Events:
Phase 1473 180 284 28,000 33,500 Voltage Sags and Interruptions, 2nd ed., IEEE Press,
shift NY, 2000.
[4] J. C. Das, “Effects of Momentary Voltage Dips on the
Operation of Induction and Synchronous Motors”,
4. CONCLUSION IEEE Trans. Industry Applications, vol. 26 (4), pp.
711-718, July 1990.
The influences of voltage sags on the behavior of [5] J. Milanovic, M. Aung, and S. Vegunta, “The
induction motors are thoroughly investigated. Upon the influence of induction motors on voltage sag
occurrence of a voltage sag, the induction motor speed propagation”, IEEE Trans. Power Delivery, vol. 23
drops, the motor is subjected to transient currents and (2), pp. 1063 – 1071, Apr. 2008.
torques depending on the sag magnitude, duration, and [6] G. Richards and M. Laughton, “Limiting Induction
the motor and load parameters. Upon voltage recovery, Motor Transient Shaft Torques Following Source
the motor is subjected once more to transient currents and Discontinuities”, IEEE Trans. Energy Conversion,
torques, exceeding in many cases the previous transients, vol. 13 (3), pp. 250-256, Sep. 1998.
but still lower than transients during starting process. [7] M. Bollen, “The Influence of Motor Reacceleration
The following are the main observations of this on Voltage Sags”, IEEE Trans. Industry
research work: Applications, vol. 31 (4), pp. 667-674, July 1996.
- Three-phase voltage sags are the most severe events, [8] J. Gomez, M. Morcos, C. Reineri, and G.
and should be taken in consideration for any evaluation. Campatelli, “Behavior of induction motor due to
- Transient currents are directly proportional to the voltage sags and short interruptions”, IEEE Trans.
voltage drop, not to the remaining voltage magnitude. Power Delivery, vol. 17 (2), pp. 434-440, Apr. 2002.
- Sags occurring at the voltage wave zero crossing are the [9] A. Leiria, P. Nunes, A. Morched, and M. de Barros,
most severe, and should be taken in consideration for any “Induction Motor Response to Voltage Dips”, in
evaluation. Proceedings of the International Conference for
- Motors operating at lower loading ratios are less Power System Transients (IPST' 2003), New Orleans,
sensitive to voltage sags. USA, pp. 1-5.
- Harmonic distortion in the supply source has no [10] L. Guasch, F. Corcoles, and J. Pedra, “Effects of
noticeable effect on the motor performance during sags. symmetrical and unsymmetrical voltage sags on
The following are the main recommendations of this induction machines”, IEEE Trans. Power Delivery,
research work: vol. 19 (2), pp. 774-782, Apr. 2004.
- Undervoltage protection with fixed magnitude and [11] J. Perez, C. Cortes, and A. Gomez, “A study of
duration should not be the main protection relay of the voltage sags in electric motors”, in Proceedings of
induction motors. The authors recommend the use of the 9th International Conference Electrical Power
undervoltage relay with inverse voltage-time Quality and Utilization, 9-11 Oct. 2007, Barcelona,
characteristics Spain, pp. 1-6.
- Readjusting of the protection relay settings may be [12] J. Kyei, R. Ayyanar, G. T. Heydt, R. Thallam, and J.
adequate to counteract voltage sags. No additional power Blevins, “The design of power acceptability curves”,
conditioning equipment is required. IEEE Trans. Power Delivery, vol. 17 (3), pp. 828-
833, July 2002.
ACKNOWLEDGMENT
The authors would like to thank Prof. Dr. Abdel- APPENDIX
Mon’em Moussa, Professor Emeritus at the Faculty of The parameters of the IM under test are calculated by Dr.
Engineering, Alexandria University, and vice president of
Mohamed Yosry, Professor of Electrical Machines at the
the Pharos University at Alexandria. The authors would
Electrical Engineering Department, Alexandria
also like to thank Prof. Dr. Mohamed Yosry, for
University, and are verified by the actual performance of
evaluating the parameters of the induction motor under
test. the motor under test.
Stator Resistance 0.42 Ω
REFERENCES Stator Reactance 2.73 Ω
[1] IEEE Std 1159-2009, IEEE Recommended Practice Rotor Resistance 0.62 Ω
for Monitoring Electric Power Quality, June 2009. Rotor Reactance 4.1 Ω
[2] IEC 61000-2-1, Electromagnetic Compatibility
Magnetizing Reactance 197.8 Ω
(EMC) – Part 2: Environment – Section 1:
Description of the Environment – Electromagnetic

39

S-ar putea să vă placă și