Sunteți pe pagina 1din 34

1TM10

Trip Circuit Supervision Relay

THE RELAY SPECIALISTS

relay monitoring systems pty ltd www.rmpl.com.au


Trip Circuit Supervision Function

Trip circuit supervision is a critical function in a protection


scheme.

Continuously monitors the status of circuit breaker trip


circuits to detect:

ƒ Wiring damage
ƒ Loose terminal screws
ƒ Poorly crimped terminal wiring
ƒ CB coil open circuit
ƒ CB pallet switch misaligned
ƒ Trip circuit supply failure (Blown fuse)
Trip Circuit Supervision
Options

Integrate into the numeric protection relay:

+ Low cost

- Uses up 2 or more status inputs


Adds back cost
Reduces functionality of protection relay)

- Not fail safe (What failed, the relay or the circuit?)


- Scheme may not supervise entire circuit
- Scheme may not supervise with CB both open and closed
Trip Circuit Supervision
Options

Stand alone trip circuit supervision relay:

+ Fail safe operation (Detects it’s own failure)


+ Highly reliable
+ Supervision of the complete circuit
+ Supervision with CB in both open and closed state
+ Similar cost to numeric relay solution if status inputs needed

- Adds some cost


- Adds some additional wiring
1TM
Supervision Relays

The 1TM Series Relays provide fail safe supervision of CB


trip circuits with the CB open and closed:

ƒ Trip supply supervision


ƒ Trip circuit continuity
ƒ Trip coil continuity
ƒ Trip relay circuit and coil continuity
1TM10
System De-energised

+ Trip Relay
CB Aux Switch Trip Coil
52 - a
52
T
52 - b

13 R1
RL1 14
2
21 R2 22

RL1-1 5

3 1 Monitored circuits

RL1-2 6

4 2
1TM
Supervision Relays

A significant safety feature of the 1TM series are the


internal power resistors wired in series with the TCS
circuit.

These act to limit the trip coil supervision current to


well below the circuit breaker trip coil operate current.

This feature ensures there will be no mal operation of


the circuit breaker.
1TM10
CB Open

+ Trip Relay
CB Aux Switch Trip Coil
52 - a
52
T
52 - b

13 R1
RL1 14
2
R2
Trip supply
21 22
Trip circuit
Trip coil

RL1-1 5

3 1

RL1-2 6

4 2
1TM10
CB Closing

CB Aux Switch
+ Trip Relay 52 - a Trip Coil

52
T

R1 52 - b
13 RL1 14
2
Transient
21 R2 22
condition

RL1-1 5

3 1

RL1-2 6

4 2
1TM10
CB Closed

+ Trip Relay
CB Aux Switch Trip Coil
52 - a
52
T

52 - b
13 R1
RL1 14
2

21 R2 22
Trip supply
Trip circuit
Trip coil
RL1-1 5

3 1

RL1-2 6

4 2
1TM10
CB Trip

+ Trip Relay
CB Aux Switch Trip Coil
52 - a
52
T

52 - b
13 R1
RL1 14
2

21 R2 22
Trip supply
Trip circuit
Trip coil energized
RL1-1 5

3 1

RL1-2 6

4 2
1TM10
CB Opening

CB Aux Switch
+ Trip Relay 52 - a Trip Coil

52
T

R1 52 - b
13 RL1 14
2 Transient
R2
21 22 condition

RL1-1 5

3 1

RL1-2 6

4 2
1TM10
CB Open
(Trip contact closed)

+ Trip Relay
CB Aux Switch Trip Coil
52 - a
52
T
52 - b

13 R1
RL1 14
2 Trip supply
21 R2 22
Trip circuit
Trip coil

RL1-1 5

3 1

RL1-2 6

4 2
1TM10
CB Open
(Trip contact open)

+ Trip Relay
CB Aux Switch Trip Coil
52 - a
52
T
52 - b

13 R1
RL1 14
2
R2
Trip supply
21 22
Trip circuit
Trip coil

RL1-1 5

3 1

RL1-2 6

4 2
1TM
Supervision Relays

Four models are available depending


on the degree of supervision required
& wiring configuration.
1TM
Selection Chart

Model Number
Supervision 1TM10 1TM11 1TM12 1TM13
CB 52a contact Yes No Yes No
CB 52b contact Yes No Yes No
Trip supply Yes Yes Yes Yes
Trip coil continuity Yes No Yes No
Trip wiring continuity Yes No Yes No
Trip relay circuit No No No Yes
Cross Reference Chart

6RX Series Trip Circuit Supervision Relays


RMS Alstom Functional Description Contacts MATRIX
6RX11 MVAX11 Trip relay supervision 2 1TM13
6RX12 MVAX12 Trip supply supervision 2 1TM11
6RX21 MVAX21 Trip circuit supervision 2 1TM10
6RX31 MVAX31 Trip circuit supervision – 3 element 2 1TM12
Contact Ratings

Make & Carry Continuously


3,000 VA AC resistive with maximums of 660V & 12A
3,000 W DC resistive with maximums of 660V & 12A
Make & Carry for 3 Seconds
7,500 VA AC resistive with maximums of 660V & 30A
7,500 W DC resistive with maximums of 660V & 30A
AC Break Capacity
3,000 VA AC resistive with maximums of 660V & 12A
DC Break Capacity (Amps)

Voltage 24V 48V 125V 250V


a 12 2 0.5 0.25
Resistive rating b 12 12 10 5
Maximum a 12 1 0.25 0.15
L/R=40ms break b 30 15 5.5 3.5
1K operations
(N3 Rating) b 12 12 5 2.5
a = Without magnetic blowouts b = With magnetic blowouts
1TM10 Modular Construction
Mixed Elements in a Single Case
Mixed Elements in a Single Case
4 Element Flag Relay
Relay Module Partially Withdrawn
2M28
Case Details
4M56
Case Details
Module Product Label
Module Wiring Label
Transit Shipping Flag Wedge
Terminal Screws
Mounting

ƒ M4 Size
ƒ Self threading
ƒ Suit Rack or flush mounting
Semi Projection Mount Kit
19 Inch Sub Rack Frames
1TM
Ordering Codes

1 2 3
1TM

1 RELAY FUNCTION
Specify relay functional number from table 5.

2 NOMINAL OPERATE VOLTAGE


A 24V DC D 110V DC
B 32V DC E 125V DC
C 48V DC F 250V DC

3 CONTACT DUTY
1 Heavy duty contacts – magnetic blowouts fitted
2 Heavy duty contacts

ELEMENT TEXT (Optional)


Element part number is used as the default
1TM10
Additional Information

ƒ Technical Bulletin
ƒ User Guide
ƒ Auto Cad Mounting Drawings
ƒ Price & Availability
www.rmspl.com.au/6RMATRIX.htm

ƒ Test Manuals
www.rmspl.com.au/search.asp

ƒ Other Products
www.rmspl.com.au/Products.htm