Sunteți pe pagina 1din 2

INSTRUCTIONS

FOR
Basler Electric VOLTAGE REGULATOR Power Systems Group
Phone 618 654-2341 Fax 618 654-2351
MODEL: AVC32-4
Route 143 Box 269 http://www.basler.com
Highland IL 62249 USA
9 2421 00 101 info@basler.com

INTRODUCTION Voltage Build-Up: V/HZ CORNER FREQUENCY SELECTION AND


ADJUSTMENT
The AVC32-4 Voltage Regulator is designed for Internal provisions for automatic build-up from
use on 50/60 Hz brushless generators. The generator residual voltages as low as 2 Vac. The regulator is preset for use with 50 Hz
regulator includes frequency compensation, systems. Cutting the orange jumper (JP2) sets
Droop:
overexcitation foldback, selectable sensing taps, the regulator for use with 60 Hz systems.
dual power inputs, droop, and a solid state build- Adjustable up to 5% when excitation voltage
The corner frequency can be set by adjusting the
up circuit. varies from 7.5 to 30 Vdc.
V/Hz rheostat on the AVR. Clockwise rotation
ELECTRICAL SPECIFICATIONS Terminations: results in raising the corner frequency (shifting the
curve to the right).
Dc Output Power: One-quarter inch Fast-On terminals.
4 Adc at 32 Vdc (128 W) maximum continuous To set the V/Hz rheostat:
Adjustments:
1. Adjust the V/Hz rheostat fully counter
Ac Power Input: VOLT - Voltage regulation setpoint clockwise (CCW).
Power is supplied from two generator windings. LIM - Output current limit 2. Start the generator and set at rated voltage.
One winding connects to terminals X1 and X2 and STAT - Droop 3. Adjust the generator to the desired corner
delivers a voltage proportional to generator STAB - Stability frequency.
terminal voltage at a frequency equal to generator V/Hz - Underfrequency corner 4. Slowly adjust the V/Hz rheostat clockwise
frequency. The other winding connects to (CW) until the generator voltage just begins to
PHYSICAL SPECIFICATIONS
terminals Z1 and Z2 and delivers a voltage decrease.
proportional to generator output current at three Operating Temperature:
OVEREXCITATION CURRENT LIMIT
times generator frequency.
-40C (-40F) to +65C (+149F).
The regulator features a hard current limit that is
X1-X2:
Storage Temperature: adjustable from 3 Amps to 8 Amps with the LIM
35.7 to 55.2 Vac at 50 Hz
-55C (-67F) to +85C (+185F). rheostat. The regulator begins timing at 55% (typ)
42.8 to 66.2 Vac at 60 Hz of the hard limit setpoint. After time out, output
Z1-Z2: Vibration:
current is latched to a reduced level of 0.5 Amps
7.2 to 27.6 Vac at 150 Hz Withstands 1.5 Gs at 5 to 29 Hz; 0.036" double (typ). The time delay is typically 11 seconds.
8.7 to 33.1 Vac at 180 Hz amplitude at 29 to 52 Hz; and 5 Gs at 52 to 500
The regulator can be reset by removing input
Sensing Input: Hz.
power to the regulator. This may be accomplished
Low Range: Shock: by stopping the prime mover or by interrupting the
95 to 140 Vac, single phase, 50/60 Hz regulator input with a reset switch.
Withstands up to 15 Gs in each of three mutually
Medium Range: perpendicular axes. STABILITY ADJUST
180 to 252 Vac, single phase, 50/60 Hz
Weight: The STAB potentiometer provides adjustment to
High Range:
the response rate of the generator output voltage
330 to 504 Vac, single phase, 50/60 Hz 14.38 oz. (0.41kg) net.
to a change in load. The regulator features two
Note Fuses: ranges of response. The regulator is preset for
A 22 k$ customer supplied potentiometer may the slower range of response. Cutting the blue
be added in series with the sensing input to CAUTION jumper (JP1) selects the faster range of response.
allow a ±5% variation of the voltage setpoint. Fuses should be sized to meet the
application. The internal fuses included with OPERATION
Regulation Accuracy: the AVC32-4 are sized to allow for maximum General:
rated output from the regulator. The
Better than ±2%, no load to full load customer may want to replace these with The following system operation procedures
fuses having a lower current rating for the provide instructions for adjusting the AVC32-4
Underfrequency:
specific application. regulator. Symptoms resulting from a faulty
Excitation is reduced when generator frequency regulator and certain generator system problems
falls below the adjustable setpoint. (See V/HZ are included, together with suggested remedies.
Although the AVC32-4 has internal fuses, it is
Corner Frequency Selection and Adjustment for
recommended that fuses with high interruption Complete the following steps before proceeding
description).
capability be installed per the interconnection with the system start-up.
Overexcitation: diagram to protect from faults before the regulator.
Refer to the Interconnection Diagrams. CAUTION
Excitation current from the regulator folds back
and latches to a reduced level after a time delay if Meggers and high potential test equipment
the current exceeds the adjustable setpoint. (See must not be used. Incorrect use of such
Note equipment could damage the
Overexcitation / Current Limit for description). Fuses must be installed per the interconnect semiconductors contained on the regulator.
diagrams to avoid interrupting the field current.

Publication: Rev First Printing 06/99 Copyright


9 2421 00 990 None Revised - 1999
to speed change from no load to full load, causing
Preliminary Set-up: Note
the frequency compensation (V/Hz) circuit to
1. Verify that the voltage regulator specifications All voltage reading are to be taken with an
reduce voltage at lower frequencies.
conform with the generator system requirements. RMS reading voltmeter.
OPERATIONAL TEST
2. Ensure the voltage regulator is correctly 2. Start the prime mover and bring up to rated
connected to the generator system. speed. 1. Connect the test setup as shown in Figure 2.
Result: Voltage should build up. If not, perform Do not apply power. Ensure that the light bulb is
3. Install the fuses as described in FUSES. rated for 120V and is less than 100W.
field flashing.
4. Set the regulator VOLT, LIM, STAT, and V/HZ 2. Turn the VOLT adjust to maximum CW and the
adjustments fully CCW (minimum). 3. Slowly turn the regulator VOLT adjust CW until
the generator output voltage reaches the nominal STAB adjust to mid range.
5. Set the regulator STAB adjust and the remote value. If used, adjust the remote pot to set the 3. Apply 200 Vac, 50/60 Hz to the test set.
voltage adjust (if used) to mid range. generator voltage to the exact value desired. Result: The light bulb should illuminate.
System Start-up: 4. Check the regulator under normal operating 4. Slowly turn the VOLT adjust CCW.
1. Perform preliminary set-up as described in the conditions. Result: At the regulation point, the light bulb
above paragraphs. Result: Voltage regulation should be better than should extinguish. Small adjustments above and
+/- 2% no load to full load. If regulation is not below this level should cause the light bulb to go
within this range, verify the prime mover is at rated on and off.
speed. Voltage reduction under load may be due
A 





 ',$
B 

GENERATOR 7<3  3/&6



C
 ',$
Auxiliary Windings 

Exciter Field Shunt Series 7<3  3/&6

F+ F-
1 Remote 

Excitation Adjust 

ON/OFF 22k 


1
(If Used) 

1 1

-3
2 2
-3

E+ E- X1 X2 Z1 Z2 0 110 220 380

'YVG

127(6  ',0(16,216 ,1 3$5(17+(6,6 $5( ,1 ,1&+(6
AVC32-4
Figure 3. Overall Dimensions, Top View

D2851-05.vsd 
1 Items not supplied by Basler Electric. 06-30-99

2 Select fuses based on system requirements and with high interrupting capacity 

Figure 1. Interconnection Diagram
61 ;;;;;;
02'(/ 12

 9$&

 +] 1 2
92/7

Indicator
/,0

Lamp 200 V 200 V 127(6

 ',0(16,216
1
67$7

1:4 1 2:1 1 ,1 3$5(17+(6,6


$5( ,1 ,1&+(6
50 V 400 V
67$%
9+]

E+ E- X1 Z2 0 380

AVC32-4 



'YVG

D2851-06.vsd  


1 Items not supplied by Basler Electric. 06-30-99 

2 Select fuses based on system requirements and with high interrupting capacity Figure 4. Overall Dimensions, Side
View
Figure 2. Operational Test

Publication: Rev First Printing 06/99 Page


9 2421 00 990 None Revised - 2

S-ar putea să vă placă și