Sunteți pe pagina 1din 33

Low Voltage General Purpose Motors

LV Open drip proof motor section

Making you more competitive


ABBs General purpose motor is designed for use in general industry, meeting the demands of standard applications for OEM's. Motors are readily available from central stock locations and distributors around the world. The motors have high build quality, are available with all the features needed by the OEM market and can be modied to meet most specications.

ABB is a global leader in power and automation technologies that enable utility and industry customers to improve their performance while lowering environmental impact. The ABB Group of companies operates in around 100 countries and employs about 107,000 people.

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

Low Voltage General Purpose Motors


Sizes 56 to 400, from 0.055 to 630 kW

Contents

Page

1 2 3 4 5 6 7 8

General information Aluminum motors Steel motors Cast iron motors Open drip proof motors Global motors Brake motors Single phase motors

4 11 79 111 145 165 189 215

1 1 2 3 4 5 6 7 8

ABB reserves the right to change the design, technical specication and dimensions without prior notice.

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

General information
Standards
ABB motors are of the totally enclosed and open drip proof, single or three phase squirrel cage type, built to comply with international IEC and EN standards. Motors conforming to other national and international specications are also available on request. IEC / EN Electrical IEC/EN 60034-1 IEC/EN 60034-2 IEC 60034-8 IEC 60034-12 Mechanical IEC 60072 IEC/EN 60034-5 IEC/EN 60034-6 IEC/EN 60034-7 IEC/EN 60034-9 IEC 60034-14

All production units are certied to ISO 9001 international quality standard as well ISO 14000 environmental standard and conrm to all applicable EU Directives.

M000001

M000003

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

M000329

M000002

Motors for EU motor efciency levels


A Europe-wide agreement will ensure that the efciency levels of electric motors manufactured in Europe are clearly displayed. In contrast to the American legislation on motor efciency the European agreement does not establish mandatory efciency levels. It basically establishes three classes giving motor manufacturers an incentive to qualify for a higher class. ABB is one of only a handful of leading motor manufacturers in Europe to have a motor range to meet or exceed the minimum efciencies stated in the highest level of the EU agreement of LV motors. These efciency levels apply to 2- and 4-pole, three phase squirrel cage induction motors rated for 400V, 50Hz with S1 duty class with the output 1.1 to 90 kW, which account for the largest volume on the market. The efciency of motors from different manufacturers are collated in a database, EURODEEM, published by the European Commission. It is accessible over the Internet at http://iamest.jrc. it/projects/eem/eurodeem.htm.

1
M000005

EU efciency classes for 2-pole motors


Output kW 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 2-pole Boarderline EFF2/EFF3 76.2 78.5 81.0 82.6 84.2 85.7 87.0 88.4 89.4 90.0 90.5 91.4 92.0 92.5 93.0 93.6 93.9

ABB Three phase induction motors, 400 V 50 Hz - EU motor efciency levels

EFF1/EFF2 82.8 84.1 85.6 86.7 87.6 88.6 89.5 90.5 91.3 91.8 92.2 92.9 93.3 93.7 94.0 94.6 95.0

EU efciency classes for 4-pole motors


M000006

Output kW 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90

4-pole Boarderline EFF2/EFF3 76.2 78.5 81.0 82.6 84.2 85.7 87.0 88.4 89.4 90.0 90.5 91.4 92.0 92.5 93.0 93.6 93.9 EFF1/EFF2 83.8 85.0 86.4 87.4 88.3 89.2 90.1 91.0 91.8 92.2 92.6 93.2 93.6 93.9 94.2 94.7 95.0

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

General technical specication Mechanical and electrical design


Mounting arrangements
CodeI/CodeII Foot-mounted motor. IM B3 IM V5 IM V6 IM B6 IM B7 IM B8 IM 1001 IM 1011 IM 1031 IM 1051 IM 1061 IM 1071
M000007

Product code pos. 12 A = foot-mounted, term.box top R = foot-mounted, term.box RHS L = foot-mounted, term.box LHS B = ange mounted, large ange

1
Flange-mounted motor, large ange

IM B5 IM V1 IM V3 *) *) *) IM 3001 IM 3011 IM 3031 IM 3051 IM 3061 IM 3071


M000008

Flange-mounted motor, small ange


M000009

IM B14 IM V18 IM V19 *) *) *) IM 3601 IM 3611 IM 3631 IM 3651 IM 3661 IM 3671

C = ange mounted, small ange

Foot- and ange-mounted IM B35 IM V15 IM V36 *) *) *) motor with feet, IM 2001 IM 2011 IM 2031 IM 2051 IM 2061 IM 2071 large ange
M000010

H = foot/ange-mounted, term.box top S = foot/ange-mounted, term.box RHS T = foot/ange-mounted, term.box LHS

Foot-mounted motor, shaft with free extensions IM 1002 IM 1012 IM 1032 IM 1052 IM 1062 IM 1072
M000012

*) Not stated in IEC 60034-7.

M000011

Foot- and ange-mounted IM B34 IM V17 motor with feet, IM 2101 IM 2111 IM 2131 IM 2151 IM 2161 IM 2171 small ange

J = foot/ange-mounted, small ange

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

Cooling
Designation system concerning methods of cooling refers to standard IEC 60034-6.
Example

IC
International Cooling Circuit arrangement 0: Free circulation (open circuit) 4: Frame surface cooled

(A)

(A)

Primary coolant A for air (omitted for simplied designation) Method of movement of primary coolant 0: Free convection 1: Self-circulation 6: Machine-mounted independent component Secondary coolant A for air (omitted for simplied designation) W for water Method of movement of secondary coolant 0: Free convection 1: Self-circulation 6: Machine-mounted independent component 8: Relative displacement

Degrees of protection: IP code/IK code


Classication of degrees of protection provided by enclosures of rotating machines are refers to: - Standard IEC 60034-5 or EN 60529 for IP code - Standard EN 50102 for IK code IP protection: Protection of persons against getting in contact with (or approaching) live parts and against contact with moving parts inside the enclosure. Also protection of the machine against ingress of solid foreign objects. Protection of machines against the harmful effects due to the ingress of water
IP Characteristic letter Degree of protection to persons and to parts of the motors inside the enclosure 2: Motors protected against solid objects greater than 12 mm 4: Motors protected against solid objects greater than 1 mm 5: Dust-protected motors Degree of protection provided by the enclosure with respect to harmful effects due to ingress of water 3: Motors protected against spraying water 4: Motors protected against splashing water 5: Motors protected against water jets 6: Motors protected against heavy seas 5 5

IK code : Classication of degrees of protection provided by enclosure for motors against external mechanical impacts.
IK International mechanical protection Characteristic group Relation between IK code and impact energy: IK cod IK 0 IK 01 IK 02 IK 03 IK 04 Impact * 0.15 0.2 0.35 0.5 energy Joule * not protected according to EN 50102 IK 05 0.7 IK 06 1 IK 07 2 IK 08 5
ABB Standard

08

IK 09 10

IK 10 20

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

Insulation
ABB uses class F insulation systems, which, with temperature rise B, is the most common requirement among industry today. The use of Class F insulation with Class B temperature rise gives ABB products a 25 C safety margin. This can be used to increase the loading by up to 12 per cent for limited periods, to operate at higher ambient temperatures or altitudes, or with greater voltage and frequency tolerances. It can also be used to extend insulation life. For instance, a 10 K temperature reduction will extend the insulation life. Class F insulation system Max ambient temperature 40 C Max permissible temperature rise 105 K Hotspot temperature margin + 10 K Class B rise Max ambient temperature 40 C Max permissible temperature rise 80 K Hotspot temperature margin + 10 K Insulation system temperature class Class F 155 C Class B 130 C Class H 180 C

Safety margins per insulation class

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

M000013

Frequency converter drives


Squirrel cage induction motors offer excellent availability, reliability and efciency. With a frequency converter a variable speed drive (VSD) the motor will deliver even better value. A variable speed drive motor can be started softly with low starting current, and the speed can be controlled and adjusted to suit the application demand without steps over a wide range. Also the use of a frequency converter together with a squirrel cage motor usually leads to remarkable energy and environmental savings. However, all motors are not suitable for variable speed drive. There are several points that have to be taken into account in the design and selection of the motor, if it is intended for variable speed operation. Within the General purpose motor range ABB offers motors designed for both Direct On Line (DOL) and variable speed applications. For more demanding applications the use of ABB Process performance motors is recommended. When selecting general purpose motors to variable speed drives, following points shall be taken into consideration: 1. Dimensioning The voltage (or current) fed by the frequency converter is not purely sinusoidal. This may increase the losses, vibration, and noise of the motor. Furthermore, a change in the distribution of the losses may affect to the temperature rise of the motor. In each case, the motor must be correctly sized according to the instructions supplied with the selected frequency converter. When using ABB converters, please use ABB's DriveSize dimensioning programme or the loadability curves of the corresponding converter type for sizing the motors. The loadability curve for applicable General purpose motors used with ABB's ACS 800- frequency converters with DTC-control can be found in gure 3. 2. Speed range In a frequency converter drive, the actual operating speed of the motor may deviate considerably from its nominal speed (i.e. the speed stamped on the rating plate). For higher speeds, ensure that the highest permissible rotational speed of the motor or the critical speed of the entire equipment is not exceeded. When high speed operation exceeds the nominal speed of the motor, the following points should be checked: Maximum torque of the motor Bearing construction Lubrication Balancing Critical speeds Shaft seals Ventilation Fan noise
ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006 9

Guideline values of maximum speeds for General purpose aluminum motors described in gure 1. Exact values are available on request.
Figure 1. Guideline values of maximum speeds for General purpose motor in aluminum frame: Motor size 63-80 90-100 112-200 225-280 Speed r/min 2-pole 4-pole 6000 6000 4500 3600 4500 6000 4500 3600

At low speed operation the cooling capacity of the fan decreases, which may cause higher temperature rises in the motor. A separate constant speed fan can be used to increase cooling capacity and loadability at low speed. It is also important to check the performance of the grease at low speeds. 3. Lubrication Variable speed operation affects on the bearing temperature, which must be taken into account when selecting the lubrication method and grease type. For example the life time of sealed bearings can be remarkably shorter than in direct on line operation. 4. Insulation protection Frequency converter supply causes higher voltage stresses at the windings of the motor than the sinusoidal supply. Thus, the insulation system and possible lters must be selected according to the used voltage and converter type. For selection of insulation system and lters, see gure 2. 5. Bearing currents Bearing voltages and currents must be avoided in all motors. For reliability issues, insulated bearings and/or properly dimensioned lters at the converter output must be used according to the instructions in gure 2. When ordering, clearly state which alternative will be used. For more information about bearing currents and voltages, please contact ABB.

6. Cabling, grounding and EMC The use of a frequency converter puts higher demands on the cabling and grounding of the drive system. The motor must be cabled by using shielded symmetrical cables and cable glands providing 360 bonding (also called EMC-glands). For motors up to 30 kW unsymmetrical cables can be used, but shielded cables are always recommended. More information about grounding and cabling of a variable speed drive can be found from the manual

Grounding and cabling of the drive system (Code: 3AFY 61201998 R0125 REV B) and the ABBs Low Voltage Motors Manual. For fullling the EMC requirements, special EMC cable(s) must be used in addition to the correct cable gland mounting, with special, extra earthing pieces. Please refer to the manuals of the frequency converter.

Validity of gure 2 Measures mentioned in Figure 2 apply to the applicable motors within the General motors range (not high-output versions) with ACS 800 and ACS 550 drives with uncontrolled DC-voltage. For other alternatives and converter types, please contact ABB.
Figure 2. Selection rules for insulation and ltering in variable speed drives
Motor nominal power PN or frame size PN < 100 kW UN 500 V Standard motor PN 100 kW or IEC 315 Frame size IEC 355 Standard motor + Insulated N-bearing Standard motor + dU/dt-lter (reactor) + Insulated N-bearing OR Reinforced insulation + Insulated N-bearing PN 350 kW or IEC 400 Standard motor + Insulated N-bearing + Common mode lter Standard motor + Insulated N-bearing + dU/dt-lter (reactor) + Common mode lter OR Reinforced insulation + Insulated N-bearing + Common mode lter Reinforced insulation + Insulated N-bearing + dU/dt-lter (reactor) + Common mode lter

UN 600 V

Standard motor + dU/dt-lter (reactor) OR Reinforced insulation

UN 690 V

Reinforced insulation + dU/dt-lter (reactor)

Reinforced insulation + dU/dt-lter (reactor) + Insulated N-bearing

dU/dt lter (reactor) Series reactor. DU/dt -lter decreases the changing rate of the phase and main voltages and thus reduces voltage stresses in the windings. DU/dt -lters also decrease so-called common mode currents and the risk of bearing currents. Common mode Common mode lters reduce so-called common mode currents in VSD applications and thus decrease the risk of bearing currents. Common mode lters do not signicantly affect the phase or main voltages on the motor terminals. Insulated Bearings Bearings with insulated inner or outer races are used as the standard solution. So-called hybrid bearings, i.e. bearings with non-conductive ceramic balls, can also be used in special applications. More information for spare part selection is available on request.

Figure 3. Motor loadability with ACS 800, Field weakening point 50 Hz.

10

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

M000014

General Purpose Open Drip Proof Motors


Open drip proof squirrel cage three phase low voltage motors, Sizes 280 - 400, 110 to 800 kW

5
www.abb.com/motors&drives
> Motors > Low voltage motors > General purpose motors
Mechanical design ..............................146 Ordering information...........................151 Technical data......................................152 Variant codes .......................................157 Dimension drawings............................159 Rating plates........................................163 Open drip proof motors in brief .........164

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

145

Mechanical design
Stator
The stator frame is made of prole-pressed sheet steel, giving the motor high mechanical stregth, low weight and a good surface nish. The stator core is welded into the stator frame and contributes to its excellent mechanical properties. Feet and lifting eyes are welded to the stator frame. The terminal box and end shields are of cast iron.

Drain holes
Motors that will be operated in very humid or wet environments, and especially under intermittent duty, should be provided with drain holes. The appropriate IM designation, such as IM V3 (IM 3031), is specied, on the basis of the method of motor mounting. M2FA motors are tted with drain holes and plugs. The plugs are open on delivery. Check that the drain holes and grease outlet face downwards, when mounting designation differs from standard horizontal mounting. In the case of vertical mounting, the upper plug must be hammered home completely. In very dusty environments the drain hole plug should be knocked in.

closed

5
open open

Terminal box
Terminal boxes are mounted either on the top of the motor, or on either side of the motor, see ordering information page . In basic version the terminal box can be rotated 2x180 to allow cable entry from either side of the motor. The terminal box is equipped with cable glands or cable boxes as standard, and terminations are suitable for Cu- and Al-cables. Cables are connected to the terminals by cable lugs which are not included with the motor. To enable us to supply suitable terminations for the motor please state cable type, quantity and size when ordering. For dimension drawings of terminal boxes, see drawings.

146

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

M000103

Co-ordination of terminal boxes and cable entries


If no ordering information on the cable is given, it is assumed to be p.v.c. -insulated type and termination parts are supplied according to the table below and on next page. Deviations from standard design according to the following tables are available on request.

M2FA 280 to 400 motors with top-mounted terminal box Standard cable entries and cable boxes
Motor size M2CA
280 315 355 SA 355 M_ 355 L_

Voltage 380 - 690 V, 50 Hz


Max. connection Terminal cable area bolt size mm2
2x150 2x240 2x240 4x240 2x240 4x240 M12 M12 M12 M12 M12 M12

Terminal box
122/4 142/4 142/4 162/4 142/4 162/4

Flange or adapter
3GZF 294730-749 3GZF 294730-753 3GZF 294730-753 3GZF 294730-944 3GZF 294730-944

Cable box or cable gland


2x 3GZF 294730-613 2x 3GZF 294730-613 2x 3GZF 294730-613 3GZF 294730-301 3GZF 294730-301 3GZF 294730-301

Gland thread

Cable diameter
2x 32-49 2x 32-49 2x 32-49 2x 48-60 2x 48-60 2x 48-60

Voltage/ freq. code

3000 r/min (2 poles)

D E

1500 r/min (4 poles)


280 315 355 S_ 355 M_ 355 LA 355 LKD 400 LKA 400 LKB 122/4 142/4 142/4 162/4 142/4 162/4 162/4 162/9 162/4 162/9 3GZF 294730-749 3GZF 294730-753 3GZF 294730-753 3GZF 294730-944 3GZF 294730-944 3GZF 294730-944 3GZF 294730-944 3GZF 294730-944 3GZF 294730-944 2x 3GZF 294730-613 2x 3GZF 294730-613 2x 3GZF 294730-613 3GZF 294730-301 3GZF 294730-301 3GZF 294730-301 3GZF 294730-501 3GZF 294730-501 3GZF 294730-501 3GZF 294730-501 2x 32-49 2x 32-49 2x 32-49 2x 48-60 2x 48-60 2x 48-60 2x 60-80 2x 60-80 2x 60-80 2x 60-80 2x150 2x240 2x240 4x240 2x240 4x240 4x240 4x240 4x240 4x240 M12 M12 M12 M12 M12 M12 M12 M12 M12 M12

D E

D E

1000 r/min (6 poles)


280 315 355 S_ 122/4 142/4 142/4 3GZF 294730-749 3GZF 294730-753 3GZF 294730-753 2x 3GZF 294730-613 2x 3GZF 294730-613 2x 3GZF 294730-613 2x 32-49 2x 32-49 2x 32-49 2x150 2x240 2x240 M12 M12 M12

750 r/min (8 poles)


280 315 355 S_ 122/4 142/4 142/4 3GZF 294730-749 3GZF 294730-753 3GZF 294730-753 2x 3GZF 294730-613 2x 3GZF 294730-613 2x 3GZF 294730-613 2x 32-49 2x 32-49 2x 32-49 2x150 2x240 2x240 M12 M12 M12

Voltage/frequency codes: D - 380-420 VD 50 Hz, 660-690 VY 50 Hz, 440-480 VD 60 Hz E - 500 VD 50 Hz, 575 VD 60 Hz

Examples:

Terminal box Flange with cable gland Flange with cable box

Adapter E-D (standard) 3GZF294730-944

Adapter E-2D (optional) 3GZF294730-945 Cable box Optional 3GZF294730-301

Cable box 3GZF294730-501

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

147

M000065

Alternatives for cable entries and cable boxes


The tables on previous pages show the standard terminal boxes and termination parts that are delivered when no information on the cable is given. The table below shows the different alternatives availMotor size Terminal box Opening type Max.rate current A (Y/D-conn.) 210/360 370/640 370/640 550/950 Max. size of conductor mm2 2x150 2x185 2x240 4x240

able for cable boxes and cable entries. Other types on request.

Cable entry mm 1xPg29...42 2xPg29...42 1xPg36...42 2xPg36...48 1xPg36...42 2xPg36...48 1xPg36...42 2xPg36...48 2x1Pg36...42 2x2Pg36...48

Cable box

Blank plate

280 315 355, 400

122/4 142/4 142/4 162/4

C (FL21) D (FL33) D (FL33) E-D 1)

1x36...52/48...60 1x36...52/48...60 1x36...52/48...60 2x48...60/50...68 1x36...52/48...60 2x48...60/50...68 1x36...52/48...60 2x48...60/50...68 2x268.. .80 2x1x36...52/48...60 2x2x48...60/50...68 2x268...80

MKLN 20 MKLN 30 MKLN 30

E-2D1)

550/950

4x240

1)

Terminal box type 162/4 is used with a combination of one E-opening and one or two D-openings, as described below:

Terminal box 162 with adapting ange 3GZF 294730-501 (E-D) or optional 3GZF 294730-301 (E-2D):
E-opening Adapter E-2D

Terminal box 162 with adapting ange:


M000103

5
Adapter E-D D-openings

Adaptor E - D

M000088

Opening C (FL 21) D (FL 33) E (FL 40)

c 62 100 115

e 193 300 370

f 62 80 100

g 193 292 360

d M8 M10 M12

148

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

Bearings
The motors are normally tted with single-row deep groove ball bearings as listed in the table on the right. The complete ball bearing designation is stated on the rating plate. If the bearing at the D-end is replaced with a roller bearing (NU- or NJ-), higher radial forces can be handled. Roller bearings are suitable for belt drive applications. When there are high axial forces, angular-contact ball bearings should be used. This option is available on request. When a motor with angular-contact ball bearings is ordered, the method of mounting and direction and magnitude of the axial force must be specied. For special bearings, please see variant codes.

Standard bearing types


Basic version with Motor size 280 315 355 400
1)

Version with roller bearings, variant code 037 D-end (NU 319/C3) (NU319/C3) (NU 322/C3) (NU 322/C3)

Number of poles 2 4-8 2 4-8 2 4


1)

deep groove ball bearings D-end 6316/C4 6319/C3 6316/C4 6319/C3 6322/C3 6322/C3 N-end 6316/C4 6316/C3 6316/C4 6316/C3 6319/C3 6319/C3

4-8

Please check technical construction with ABB.

Bearing seals
M2FA motors have, as standard, V-rings at both ends. The size and type of suitable seals are in accordance with the table below:
Motor size Number of poles 2 4-8 2 4-8 2 4-8 4-8 d1 d2 B1 b Standard design Axial seal D-end N-end VS 80 VS 80 VS 80 VS 95 VS 95 VS 110 VS 110 VS 80 VS 80 VS 80 VS 80 VS 95 VS 95 VS 95 Alternative design Radial seal (DIN 3760) 80x100x10 1) 95x120x12 80x100x10 1) 95x120x12 95x120x12 1) 110x140x12 1) 110x140x12 1)

280 315 355 400


1)

80 95 80 95 95 110 110

100 120 100 120 120 140 140

13.5 13.5 13.5 13.5 13.5 15.5 15.5

10 12 10 12 12 12 12

Viton-seal

V-Ring

Radial seal

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

M000072

149

Permissible radial forces


The table below gives the permissible radial force in Newtons, assuming zero axial force. The values are based on normal conditions at 50 Hz and calculated bearing lives of 40,000 h. Motors are B3 version with force directed sideways. In some cases the strength of the shaft affects the permissible forces. At 60 Hz the values must be reduced by 10 %. For two-speed motors, the values must be based on the higher speed. Permissible loads of simultaneous radial and axial forces will be supplied on request.

Permissible radial and axial force for a bearing life of 40,000 hours
Permissible radial force for: Horizontal mounting, sideways direction of force Length of shaft extension E (mm) 140 170 170 170 140 170 170 170 140 210 210 210 170 210 210 210 Ball bearing at point of application: FXmax FX0 N N 5850 8900 10200 11200 5800 9000 10200 11300 6200 12100 13800 15200
2)

Permissible axial force for 1): Horizontal Vertical mounting with shaf mounting extension downwards Direction of force Outwards Upwards N N 3800 5300 6500 7450 3700 5000 6350 7300 2100 4100 5500 6900
2)

Motor size 280

Number of poles 2 4 6 8 2 4 6 8 2 4 6 8 2 4 6 8

Roller bearing at point of application: FX0 FXmax N N 26100 29500 32100 26200 29600 32300 36500 41500 45000 37500
2) 2)

Downwards N 2250 3800 4700 5500 1800 2750 3300 4300


2) 2) 2) 2) 2) 2) 2) 2)

4500 7050 8100 8900 4800 7300 8350 9200 5400 9800 11200 12300
2)

11400 11300 11100 14000 14200 14300 18100 20200 21000 13500
2) 2)

7150 8800 10100 11200 7450 9250 10800 12200


2) 2) 2) 2) 2) 2) 2) 2)

315

355

400

5
1)

12200
2) 2)

10500
2) 2)

3900
2) 2)

Flange-mounted motors with deep groove ball bearings at D-end. Other designs on request. No simultaneuous radial forces allowed. 2) On request. If the radial force is applied between points X0 and Xmax, the permissible force FR can be calculated from the following formula: FR = Fxo - X (Fxo - Fx max) E E = length of shaft extension in basic version

150

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

M000145

Ordering information
Sample order
When placing an order, please state the following minimum data in the order, as in the example. The product code of the motor is composed in accordance with the following example. Motor type M2FA 315SMA Pole number 2 Mounting arrangement (IM-code) IM B3 (IM 1001) Rated output 200 kW Product code 3GFA312210-ASB Variant codes if needed

A B M2FA 315 SMA

C D,E,F, G 3GFA 312 210 - ADA, 003 etc.


1-4 5-6 7 8-10 11 12 13 14

A Motor type B Motor size C Product code D Mounting arrangement code E Voltage and frequency code F Generation code G Variant codes

Explanation of the product code:


Positions 1 to 4 3GFA = Open drip proof squirrel cage three phase motor with steel frame Positions 5 and 6 IEC-frame size 28 = 280 35 = 355 31 = 315 40 = 400 Position 7 Speed (pole pairs) 1 = 2 poles 6 = 8 poles 2 = 4 poles 7 => 12 poles 3 = 6 poles 8 = Two-speed motors 4 = 8 poles 9 = Multi-speed motors 5 = 10 poles Position 8 to 10 Serial number Position 11 - (dash) Position 12 Mounting arrangement A = Foot-mounted, top-mounted terminal box L = Foot-mounted, terminal box LHS, seen from D-end R = Foot-mounted, terminal box RHS,seen from D-end B = Flange-mounted L = Foot-mounted, terminal box LHS, seen from D-end R = Foot-mounted, terminal box RHS,seen from D-end H = Foot- and ange-mounted, top-mounted terminal box S = Foot- and ange-mounted, terminal box LHS seen from D-end T = Foot- and ange-mounted, terminal box RHS seen from D-end Position 13 Voltage/frequency code See tables below Position 14 Generation code A, B, C... The product code must, if needed, followed by variant codes.
Code letters for supplementting the product code for voltage and frequency single speed motors: A 380 VY 50 Hz B 380 V 50 Hz D 380-420 V 50 Hz 660-690 VY 50 Hz 440-480 V 60 Hz U 690 V 50 Hz E 500 V 50 Hz 575 V 60 Hz F 500 VY 50 Hz 575 VY 60 Hz H 415 V 50 Hz

S 220-240 V 50 Hz 380-420 VY 50 Hz 440-480 VY 60 Hz

T 660 V 50 Hz

X Other rated voltage, connection or frequency, max. 690 V

Code letters for supplementting the product code for voltage and frequency two-speed motors: A 220 V 50 Hz B 380 V 50 Hz D 380-400 V 50 Hz 440-480 V 60 Hz E 500 V 50 Hz 575 V 60 Hz H 400-415 V 50 Hz 460-480 V 60 Hz S 220-230 V 50 Hz

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

151

General purpose open drip proof motors


Technical data for squirrel cage three phase motors, steel frame
IP 23 S IC 01 Insulation class F, temperature rise class B
Efciency Speed % Power factor 100% Current IN cos A Is IN Torque TN Nm Ts TN Tmax TN

Output kW

Motor type

Product code r/min

3000 r/min = 2 poles


132 160 200 250 315 355 400 400 450 500 560
2)

400 V 50 Hz
3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 281 210-A 311 110-A 311 210-A 311 320-A 311 330-A 311 510-A 311 520-A 351 110-A 351 310-A 351 320-A 351 510-A 2971 2977 2975 2975 2977 2969 2969 2982 2978 2973 2981 94.5 94.2 94.4 94.5 94.6 94.9 94.8 94.7 95.0 95.1 95.5 0.84 0.86 0.86 0.87 0.84 0.89 0.88 0.88 0.89 0.90 0.89 241 289 353 431 573 606 700 680 765 851 956

Basic design
7.0 6.7 7.1 7.1 7.8 6.8 7.3 7.1 7.4 6.7 8.7 424 513 643 804 1012 1142 1288 1280 1443 1606 1794 2.1 1.6 1.8 1.9 2.1 2.0 2.0 1.1 1.3 1.2 1.5 2.4 2.5 2.6 2.6 2.8 2.5 2.6 2.6 3.0 2.7 3.1

1)

M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA

280 SMA 315 SA 315 SMA 315 MB 315 MC 315 LA 315 LB 355 SA 355 MA 355 MB 355 LA

5) 5) 5) 5)

3000 r/min = 2 poles


160 M2FA 280 MB 3GFA 281 320-A

400 V 50 Hz
2971 94.9 0.88 279

High-output design
7.0 514 2.0 2.7

1500 r/min = 4 poles


110 132 160 200 250 315 M2FA 280 SA M2FA 280 SMA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA 315 SA 315 SMA 315 MB 315 LA 355 SA 355 SB 355 SC 355 MA 355 LA 355 LKD 400 LKA 400 LKB 3GFA 282 110-A 3GFA 282 210-A 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 312 110-A 312 210-A 312 320-A 312 510-A 352 110-A 352 120-A 352 130-A 352 310-A 352 510-A 352 540-A 402 510-A 402 520-A

400 V 50 Hz
1476 1477 1483 1482 1481 1477 1484 1485 1484 1485 1486
4) 4) 4)

Basic design
0.83 0.84 0.83 0.83 0.83 0.83 0.85 0.82 0.82 0.83 0.81 211 245 297 366 452 577 555 653 733 810 920 5.8 5.9 6.5 6.5 6.7 6.7 6.4 6.6 5.9 6.5 7.7 713 853 1030 1287 1611 2036 2027 2282 2574 2896 3213 1.8 1.8 1.8 1.8 1.7 2.2 1.7 1.9 1.7 1.8 2.0 2.4 2.3 2.5 2.3 2.3 2.5 2.4 2.5 2.2 2.4 2.8

93.1 93.8 94.6 94.7 94.9 94.5 95.0 95.4 95.3 95.4 95.4

1)

315 355 400 450 500 600 710 800

2) 2) 2) 1)2)

1500 r/min = 4 poles


160 M2FA 280 MB 3GFA 282 320-A

400 V 50 Hz
1480 94.0 0.81 305

High-output design
7.2 1032 2.5 2.6

The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page).
1) 2) 3) 4) 5)

Temperature rise class F. Special winding for 415V 50 Hz. 415 V 50 Hz and 440 V 60 Hz on request. On request. Please check technical construction with ABB.

152

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

General purpose open drip proof motors


Technical data for squirrel cage three phase motors, steel frame
IP 23 S IC 01 Insulation class F, temperature rise class B
EfPower ciency factor % cos Current IN A EfPower Current ciency factor IN % cos A Moment of Sound inertia pressure J = GD2 Weight level LP kgm2 kg dB(A)

Output kW

Motor type

Speed r/min

Speed r/min

3000 r/min = 2 poles


132 160 200 250 315 355 400 400 450 500 560
2)

380 V 50 Hz
2969 2975 2974 2974 2974 2965 2966 2980 2975 2970 2978 94.4 94.2 94.3 94.4 94.6 94.8 94.7 94.6 94.9 95.1 95.5 0.86 0.87 0.87 0.88 0.86 0.89 0.88 0.90 0.90 0.90 0.90 246 302 370 449 576 635 720 700 795 880 980

415 V 50 Hz
2966 2978 2978 2976 2971 2970 2970 2983 2979 2974
4)

Basic design
0.87 0.84 0.84 0.85 0.88 0.86 0.85 0.87 0.87 0.87 227 282 344 420 530 591 683 663 746 830 0.8 1.2 1.4 1.7 1.7 2.1 2.1 3.2 3.5 3.5 4.8 540 695 770 840 840 975 975 1220 1320 1320 1530 87 92 92 92 92 92 92 93 93 93 93

1)

M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA

280 SMA 315 SA 315 SMA 315 MB 315 MC 315 LA 315 LB 355 SA 355 MA 355 MB 355 LA

94.1 94.2 94.4 94.5 94.6 94.9 94.8 94.7 95.0 95.1

5) 5) 5) 5)

3000 r/min = 2 poles


160 M2FA 280 MB

380 V 50 Hz
2968 94.8 0.88 288

415 V 50 Hz
2973 94.9 0.86 269

High-output design
1.15 580 89

1500 r/min = 4 poles


110 132 160 200 250 315 315 355 400 450 500 600 710 800 M2FA 280 SA M2FA 280 SMA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA 315 SA 315 SMA 315 MB 315 LA 355 SA 355 SB 355 SC 355 MA 355 LA 355 LKD 400 LKA 400 LKB

380 V 50 Hz
1474 1474 1481 1480 1479 1475 1482 1484 1482 1483 1484
4) 4) 4)

415 V 50 Hz
0.85 0.86 0.85 0.85 0.86 0.85 0.86 0.84 0.85 0.85 0.84 217 255 306 379 470 596 584 670 746 835 949 1477 1478 1481 1483 1482 1473 1485 1485 1483 1484 1486 93.1 93.8 94.6 94.8 94.9 93.5 95.0 95.4 95.1 95.4 95.4 0.82 0.83 0.84 0.82 0.83 0.86 0.83 0.83 0.84 0.83 0.83 206 239 283 360 441 540 541 622 685 798 880

Basic design
1.15 1.4 2 2.3 2.9 3.5 5.5 5.5 5.5 6.5 7.8 9.8 445 490 680 735 850 970 1220 1220 1220 1350 1550 1820 2700 2700 81 81 86 86 86 87 89 89 89 89 89

92.8 93.2 94.5 94.6 94.7 94.5 94.8 95.3 95.2 95.3 95.3

1)

2) 2) 2) 1)2)

1500 r/min = 4 poles


160 M2FA 280 MB

380 V 50 Hz
1478 93.9 0.84 310

415 V 50 Hz
1481 94.0 0.81 298

High-output design
1.7 550 87

The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page).
1) 2) 3) 4) 5)

Temperature rise class F. Special winding for 415V 50 Hz. 415 V 50 Hz and 440 V 60 Hz on request. On request. Please check technical construction with ABB.

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

153

General purpose open drip proof motors


Technical data for squirrel cage three phase motors, steel frame
IP 23 S IC 01 Insulation class F, temperature rise class B
Efciency Speed % Power factor 100% Current IN cos A Is IN Torque TN Nm Ts TN Tmax TN

Output kW

Motor type

Product code r/min

1000 r/min = 6 poles


75 90 110 132 160 185 200 250 300
1)

400 V 50 Hz
3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 283 110-A 283 210-A 313 110-A 313 210-A 313 320-A 313 510-A 353 110-A 353 120-A 353 310-A 987 987 988 988 988 987 990 990 990 92.8 93.1 93.5 94.0 94.1 94.4 94.7 94.8 95.1 0.76 0.76 0.81 0.83 0.82 0.83 0.82 0.83 0.81 155 187 210 248 300 346 373 457 541

Basic design
5.8 6.1 7.4 7.6 8.2 8.5 7.1 7.3 7.2 725 870 1062 1275 1545 1788 1927 2409 2894 1.9 2.0 1.7 1.8 1.9 1.9 1.6 1.6 1.7 2.2 2.3 2.6 2.7 2.8 2.9 2.5 2.5 2.4

M2FA 280 SA M2FA 280 SMA M2FA M2FA M2FA M2FA 315 SA 315 SMA 315 MB 315 LA

1)

M2FA 355 SA M2FA 355 SB M2FA 355 MA

1000 r/min = 6 poles


110
1)

400 V 50 Hz
3GFA 283 320-A 987 93.6 0.76 227

High-output design
6.5 1063 2.1 2.3

M2FA 280 MB

750 r/min = 8 poles


55 75 90 110 132 150 185
1)

400 V 50 Hz
3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 284 110-A 284 210-A 314 210-A 314 320-A 314 510-A 354 110-A 354 120-A 738 738 739 739 739 740 740 91.2 91.8 92.9 93.4 93.3 93.4 93.9 0.78 0.76 0.79 0.78 0.78 0.75 0.76 117 161 183 224 268 318 381

Basic design
5.6 6.1 6.8 7.3 7.2 5.3 5.6 711 970 1162 1420 1706 1934 2385 1.2 1.4 1.7 1.8 1.8 1.3 1.4 2.0 2.1 2.5 2.6 2.6 2.0 2.0

M2FA 280 SA M2FA 280 SMA M2FA 315 SMA M2FA 315 MB M2FA 315 LA M2FA 355 SA M2FA 355 SB

1)

1)

750 r/min = 8 poles


90
1)

400 V 50 Hz
3GFA 284 320-A 739 92.6 0.75 192

High-output design
6.7 1162 1.6 2.2

M2FA 280 MB

The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page).
1) 2)

Temperature rise class F. On request.

154

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

General purpose open drip proof motors


Technical data for squirrel cage three phase motors, steel frame
IP 23 S IC 01 Insulation class F, temperature rise class B
EfPower ciency factor % cos Current IN A EfPower Current ciency factor IN % cos A Moment of Sound inertia pressure J = GD2 Weight level LP kgm2 kg dB(A)

Output kW

Motor type

Speed r/min

Speed r/min

1000 r/min = 6 poles


75 90 110 132 160 185 200 250 300
1)

380 V 50 Hz
985 986 986 986 986 986 989 989 988 92.7 92.9 93.4 93.7 94.0 94.2 94.5 94.7 94.9 0.79 0.79 0.85 0.85 0.85 0.85 0.84 0.84 0.85 158 190 212 256 310 352 385 478 546

415 V 50 Hz
986 987 989 989 989 988 990 991 991 92.7 93.1 93.5 94.0 94.1 94.4 94.7 94.8 95.1 0.79 0.78 0.78 0.81 0.8 0.79 0.81 0.81 0.82 146 178 209 242 300 340 364 446 528

Basic design
1.65 2.6 2.9 3.8 4.5 5.4 8.7 10.2 12.5 440 475 630 720 810 915 1220 1320 1550
2) 2) 2) 2) 2) 2) 2) 2) 2)

M2FA 280 SA M2FA 280 SMA M2FA M2FA M2FA M2FA 315 SA 315 SMA 315 MB 315 LA

1)

M2FA 355 SA M2FA 355 SB M2FA 355 MA

1000 r/min = 6 poles


110
1)

380 V 50 Hz
986 93.4 0.79 231

415 V 50 Hz
988 93.6 0.77 219

High-output design
2.9 545
2)

M2FA 280 MB

750 r/min = 8 poles


55 75 90 110 132 150 185
1)

380 V 50 Hz
736 736 738 738 737 739 739 89.9 91.7 92.7 93.2 93.1 93.3 93.7 0.81 0.79 0.80 0.80 0.80 0.77 0.78 119 161 186 233 275 322 393

415 V 50 Hz
739 739 740 740 740 741 741 91.2 91.8 92.9 93.4 93.3 93.4 93.9 0.77 0.75 0.76 0.76 0.76 0.73 0.74 114 157 179 219 262 311 372

Basic design
1.85 2.2 3.8 4.5 5.4 8.7 10.2 460 500 720 810 915 1220 1320
2) 2) 2) 2) 2) 2) 2)

M2FA 280 SA M2FA 280 SMA M2FA 315 SMA M2FA 315 MB M2FA 315 LA M2FA 355 SA M2FA 355 SB

1)

1)

750 r/min = 8 poles


90
1)

380 V 50 Hz
738 92.5 0.78 192

415 V 50 Hz
740 92.6 0.74 188

High-output design
2.9 575
2)

M2FA 280 MB

The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page).
1) 2)

Temperature rise class F. On request.

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

155

General purpose open drip proof motors


Technical data for squirrel cage three phase motors, steel frame, two speed
IP 23 S IC 01 Insulation class F, temperature rise class F
Current Output Motor kW type Product code Speed r/min Efciency % Power factor cos IN A Is IN Torque TN Nm Ts TN Tmax TN
Moment of inertia J = GD2 Weight kgm2 kg

1500/1000 r/min = 4/6-poles


90/30 110/32 132/40 170/50 200/63 260/85 M2FA 280 SMA 3GFA 288 214-A M2FA 280 MB M2FA 315 MB M2FA 315 LA M2FA 355 SA 3GFA 288 324-A 3GFA 318 324-A 3GFA 318 514-A 3GFA 358 114-A 3GFA 358 314-A 3GFA 358 514-A M2FA 315 SMA 3GFA 318 214-A 1480/987 91.0/86.3 0.85/0.76 1482/988 92.3/87.4 0.84/0.77 1484/989 92.6/89.2 0.85/0.79 1486/988 93.4/89.7 0.83/0.78 1486/989 93.9/90.8 0.83/0.76 1487/990 94.5/91.8 0.83/0.78 1488/989 95.0/92.0 0.82/0.79 1487/992 94.9/92.1 0.88/0.78 168/65 204/69 239/84

Fan drive. two separate windings


6.7/7.2 7.4/7.3 6.3/6.4 581/290 709/309 849/386 1092/483 1285/608 1670/820 2182/966 2569/1155 1.7/2.6 2.1/2.7 1.5/2.1 1.8/2.3 2.0/2.8 1.4/2.3 1.5/2.1 1.3/2.3 2.7/2.4 2.8/2.7 2.4/2.4 2.8/2.3 2.9/2.7 2.4/2.4 2.7/2.3 2.4/3.0 1.4 1.7 2.3 2.9 3.5 5.5 6.5 7.8 490 550 735 850 970 1220 1320 1550

310/103 7.3/6.3 362/130 7.7/7.4 473/171 6.3/7.0 620/199 7.0/6.5 680/240 7.0/8.8

340/100 M2FA 355 MA 400/120 M2FA 355 LA

1500/750 r/min = 4-8 poles


100/25 110/28 140/35 185/46 220/55 250/63 315/80 M2FA 280 SMA 3GFA 288 219-A M2FA 280 MB M2FA 315 MB M2FA 315 LA M2FA 355 MA M2FA 355 LA 3GFA 288 329-A 3GFA 318 329-A 3GFA 318 519-A 3GFA 358 319-A 3GFA 358 519-A M2FA 315 SMA 3GFA 318 219-A 1478/735 92.0/87.6 0.85/0.68 1479/735 92.4/88.3 0.86/0.68 1485/740 93.5/89.9 0.83/0.64 1483/738 93.7/90.5 0.85/0.67 1485/739 94.2/91.2 0.83/0.64 1486/740 94.7/92.2 0.86/0.66 1489/741 95.1/93.0 0.84/0.64 185/62 199/67 259/87

Fan drive. Dahlander-Connection


6.2/4.1 6.7/4.1 6.8/4.7 646/325 710/364 900/452 1191/595 1415/711 1607/813 2020/1031 1.5/1.5 1.7/1.5 1.5/1.6 1.5/1.4 1.7/1.5 1.1/1.0 1.7/1.4 2.4/1.7 2.4/1.7 2.6/1.9 2.4/1.7 2.8/2.0 2.3/1.7 2.9/2.0 1.4 1.7 2.3 2.9 3.5 6.5 7.8 490 550 735 850 975 1320 1550

333/110 6.5/4.2 397/136 7.6/4.6 440/148 6.3/4.0 560/195 8.0/5.0

1500/1000 r/min = 4/6 poles


75/50 90/60 M2FA 280 SMA 3GFA 289 214-A M2FA 280 MB 3GFA 289 324-A 3GFA 319 324-A 3GFA 319 514-A 3GFA 359 114-A 3GFA 359 314-A M2FA 315 SMA 3GFA 319 214-A 1480/984 89.6/87.9 0.86/0.77 1481/987 91.0/89.3 0.86/0.73 1486/988 91.8/91.2 0.85/0.75 1488/989 92.6/91.8 0.82/0.75 1486/988 93.4/92.2 0.83/0.73 1487/991 93.5/92.9 0.88/0.83 1489/991 94.1/93.4 0.84/0.84

Constant torque, two separate windings


140/105 6.2/6.3 169/131 6.8/6.9 225/171 6.3/6.2 285/215 7.6/6.6 345/265 7.8/6.8 360/248 7.8/9.0 439/289 8.6/8.8 484/485 580/581 771/773 986/966 1189/1208 1284/1253 1539/1542 1.5/2.4 1.7/2.7 1.5/2.3 1.8/2.5 1.9/2.8 1.2/2.3 1.6/2.4 2.3/2.4 2.5/2.6 2.5/2.3 2.9/2.5 2.9/2.5 3.0/3.2 3.4/2.8 1.4 1.7 2.3 2.9 3.5 8.5 10.2 490 550 735 850 970 1220 1320

120/80

150/100 M2FA 315 MB 185/125 M2FA 315 LA 200/130 M2FA 355 SA 240/160 M2FA 355 MA

1500/750 r/min = 4-8 poles


85/48 100/55 125/80 150/95 M2FA 280 SMA 3GFA 289 219-A M2FA 280 MB 3GFA 289 329-A 1480/740 91.2/89.9 0.84/0.65 1479/740 91.2/90.6 0.87/0.70 1481/739 92.0/91.6 0.88/0.75 1481/739 92.4/91.9 0.88/0.75 1482/739 92.8/92.2 0.88/0.75 1486/743 93.6/91.8 0.91/0.73 1489/744 94.0/92.5 0.88/0.68

Constant torque, Dahlander-Connection


159/119 5.5/5.4 183/125 5.4/5.5 220/164 6.0/5.8 262/194 6.1/5.7 325/247 6.5/5.9 386/271 6.7/6.2 512/368 8.1/7.1 548/619 646/710 806/1034 967/1228 1192/1551 1446/1607 1924/2054 1.5/2.7 1.6/2.5 1.3/1.8 1.4/1.8 1.5/1.9 1.1/1.6 1.5/2.0 2.2/2.3 2.1/2.2 2.1/2.0 2.1/2.0 2.2/2.0 2.4/2.5 2.8/2.9 2.6 2.9 4.1 4.9 5.8 10.2 12.5 475 545 755 845 950 1320 1550

M2FA 315 SMA 3GFA 319 219-A M2FA 315 MB 3GFA 319 329-A 3GFA 319 519-A 3GFA 359 319-A 3GFA 359 519-A

185/120 M2FA 315 LA 225/125 M2FA 355 MA 300/160 M2FA 355 LA

The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page). Data for other number of poles and bigger frame sizes on request.

156

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

General purpose open drip proof motors - Variant codes


Code 1) Variant Motor size 280 315 355 400

Balancing
052 417 424 Vibration acc. to grade A (IEC 60034-14). Vibration acc. to grade B (IEC 60034-14). Full key balancing. S P P S P P S P P S P P

Bearings and lubrication


036 037 043 058 107 420 Transport lock for bearings. Roller bearing at D-end. SPM nipples. Angular contact bearing at D-end, shaft force away from bearing. Pt100 2-wire in bearings. Bearing mounted PTC-thermistors. P P P P P P P P P P P P P P P P P P P P P P P P

Branch standard designs


209 Non-standard voltage or frequency (special winding). P P P P

Coupling
035 Assembly of customer supplied coupling-half. P P P P

Heating elements
450 451 Heating element, 100-120 V. Heating element, 200-240 V. P P P P P P P P

Insulation system
014 Winding insulation class H. R R R R

Mounting arrangements
009 066 IM 2001 foot/ange mounted, from IM 1001 (B35 from B3). Modied for non-standard mounting position (please specify IM xxxx). (must be ordered for all mounting arrangements excluding IM B3 (1001) and B5 (3001). P P P P P P P P

Painting
114 Special paint colour, standard grade. P P P P

Protection
005 072 Protective roof, vertical motor, shaft down. Radial seal at D-end. P P P P P P P P

Rating & instruction plates


002 095 135 161 Restamping voltage, frequency and output, continuous duty. Restamping output (maintained voltage, frequency), intermittent duty. Mounting of additional identication plate, stainless. Additional rating plate delivered loose. P P P P P P P P P P P P P P P P

1)

Certain variant codes cannot be used together.

M = On modication of a stocked motor, or on new manufacture, the number per order may be limited. R = On request S = Included as standard P = New manufacture only

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

157

Code 1)

Variant

Motor size 280 315

355

400

Shaft & rotor


069 070 Two shaft extensions as per basic catalogue. One or two special shaft extensions, standard shaft material. P P P P P P P P

Stator winding temperature sensors


121 122 123 125 127 435 436 437 439 441 442 445 446 Bimetal detectors, break type (NCC), (3 in series), 130C, in stator winding. Bimetal detectors, break type (NCC), (3 in series), 150C, in stator winding. Bimetal detectors, break type (NCC), (3 in series), 170C, in stator winding. Bimetal detectors, break type (NCC), (2x3 in series), 150C, in stator winding. Bimetal detectors, break type (NCC), (3 in series, 130C & 3 in series, 150C), in stator winding. PTC-thermistors (3 in series), 130C, in stator winding. PTC-thermistors (3 in series), 150C, in stator winding. PTC-thermistors (3 in series), 170C, in stator winding. PTC-thermistors (2x3 in series), 150C, in stator winding. PTC-thermistors (3 in series, 130C & 3 in series, 150C), in stator winding. PTC-thermistors (3 in series 150C & 3 in series 170C), in stator winding. Pt100 2-wire in stator winding, 1 per phase. Pt100 2-wire in stator winding, 2 per phase. P P P P P P S P P P P P P P P P P P P S P P P P P P P P P P P P S P P P P P P P P P P P P S P P P P P P

Terminal box
021 180 022 468 Terminal box LHS, seen from D-end (= L prod.code). Terminal box RHS, seen from (reconnection from D). Cable entry LHS (seen from D-end). Cable entry from D-end. P P P P P P P P P P P P P P P P

Testing

145 146 147 148 149 222 153 760 761 762 763

Type test report from a catalogue motor, 400 V 50 Hz. Type test with report for motor from specic delivery batch. Type test with report for motor from specic delivery batch, customer witnessed. Routine test report. Testing according to separate test specication. Torque/speed curve, type test and multi-point load test with report for motor from specic delivery batch. Reduced test for classication society. Vibration level test. Vibration spectrum test. Noise level test. Noise spectrum test.

P P P P R P P P P P P

P P P P R P P P P P P

P P P P R P P P P P P

P P P P R P P P P P P

1)

Certain variant codes cannot be used together.

M = On modication of a stocked motor, or on new manufacture, the number per order may be limited. R = On request S = Included as standard P = New manufacture only

158

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

General purpose open drip proof motors


Dimension drawings

Sizes 280 - 315

Foot-mounted; IM B3 (IM 1001), IM B6 (IM 1051), IM B8 (IM 1071), IM V5 (IM 1011) Terminal box top-mounted
M000104

Motor size 280 SA 280 SMA 280 SMA 280 MB 280 MB 315 SA 315 SA 315 SMA 315 SMA 315 MB, MC 315 MB 315 LA, LB 315 LA, LB Motor size 280 SA 280 SMA 280 SMA 280 MB 280 MB 315 SA 315 SA 315 SMA 315 SMA 315 MB, MC 315 MB 315 LA, LB 315 LA, LB

Poles 4-8 2 4-8 2 4-8 2 4-6 2 4-8 2 4-8 2 4-8 Poles 4-8 2 4-8 2 4-8 2 4-6 2 4-8 2 4-8 2 4-8

A 457 457 457 457 457 508 508 508 508 508 508 508 508 F 22 18 22 18 22 20 25 20 25 20 25 20 25

AA 80 80 80 80 80 100 100 100 100 100 100 100 100 G 71 58 71 58 71 62.5 81 62.5 81 62.5 81 62.5 81

AB 545 545 545 545 545 622 622 622 622 622 622 622 622 GA 85 69 85 69 85 74.5 95 74.5 95 74.5 95 74.5 95

AC 555 555 555 555 555 624 624 624 624 624 624 624 624 GD 14 11 14 11 14 12 14 12 14 12 14 12 14

B 368 368 368 419 419 406 406 406 406 457 457 508 508 H 280 280 280 280 280 315 315 315 315 315 315 315 315

B 419 419 457 457 HA 32 32 32 32 32 32 32 32 32 32 32 32 32

BA 100 100 100 100 100 100 100 100 100 100 100 100 100 HC 556 556 556 556 556 625 625 625 625 625 625 625 625

BB 450 501 501 501 501 535 535 540 540 540 540 592 592 HD 730 730 730 730 730 820 820 820 820 820 820 820 848

C 190 190 190 190 190 216 216 216 216 216 216 216 216 K 24 24 24 24 24 28 28 28 28 28 28 28 28

D 80 65 80 65 80 70 90 70 90 70 90 70 90 L 1020 1060 1090 1120 1150 1123 1153 1223 1153 1223 1253 1293 1323

DB M20 M20 M20 M20 M20 M20 M24 M20 M24 M20 M24 M20 M24 LD 415 385 415 385 415 392 422 392 422 392 422 392 422

E 170 140 170 140 170 140 170 140 170 140 170 140 170

EG 40 40 40 40 40 40 48 40 48 40 48 40 48

Tolerances: A,B D F ISO js 14 ISO m6 ISO h9 H 0, -0.5 (M2FA 250) 0, -1.0 (M2FA 280-315) Above table gives the main dimensions in mm. For detailed drawings please see our web-site www.abb.com/motors&drives or contact us. 159

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

General purpose open drip proof motors


Dimension drawings
Flange-mounted; IM B5 (IM 3001), IM V1 (IM 3011)

Sizes 280 - 315

Motor size 280 SA 280 SMA 280 SMA 280 MB 280 MB 315 SA 315 SA 315 SMA 315 SMA 315 MB, MC 315 MB 315 LA 315 LA 315 LB Motor size 280 SA 280 SMA 280 SMA 280 MB 280 MB 315 SA 315 SA 315 SMA 315 SMA 315 MB, MC 315 MB 315 LA 315 LA 315 LB

Poles 4-8 2 4-8 2 4-8 2 4-6 2 4-8 2 4-8 2 4-8 2 Poles 4-8 2 4-8 2 4-8 2 4-6 2 4-8 2 4-8 2 4-8 2

AC 551 551 551 551 551 620 620 620 620 620 620 620 620 620 L 1020 1060 1090 1120 1150 1123 1153 1223 1153 1223 1253 1293 1323 1293

D 80 65 80 80 80 70 90 70 90 70 90 70 90 70 LA 25 25 25 25 25 25 25 25 25 25 25 25 25 25

DB M20 M20 M20 M20 M20 M20 M24 M20 M24 M20 M24 M20 M24 M20 LB 850 920 920 980 980 983 983 1083 983 1083 1083 1153 1153 1153

E 170 140 170 140 170 140 170 140 170 140 170 140 170 140 LD 410 380 410 380 410 390 420 390 420 390 420 390 420 390

EG 40 40 40 40 40 40 48 40 48 40 48 40 48 10 M 600 600 600 600 600 740 740 740 740 740 740 740 740 740

F 22 18 22 18 22 20 25 20 25 20 25 20 25 20 N 550 550 550 550 550 680 680 680 680 680 680 680 680 680

G 71 58 71 58 71 62.5 81 62.5 81 62.5 81 62.5 81 62.5 P 660 660 660 660 660 800 800 800 800 800 800 800 800 800

GA 85 69 85 69 85 74.5 95 74.5 95 74.5 95 74.5 95 74.5 S 23 23 23 23 23 23 23 23 23 23 23 23 23 23

GD 14 11 14 11 14 12 14 12 14 12 14 12 14 12 T 6 6 6 6 6 6 6 6 6 6 6 6 6 6

HB 450 450 450 450 450 505 505 505 505 505 505 505 505 533

Tolerances: D F N 160 ISO m6 ISO h9 ISO js6

Above table gives the main dimensions in mm. For detailed drawings please see our web-site www.abb.com/motors&drives or contact us. ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

M000106

General purpose open drip proof motors


Dimension drawings
Foot-mounted; IM B3 (IM 1001), IM B6 (IM 1051), IM B8 (IM 1071), IM V5 (IM 1011) Terminal box top-mounted

Sizes 355 - 400

Motor size 355 S_ 355 SA 355 SB,SC 355 SB,SC 355 M_ 355 M_ 355 M_ 355 L_ 355 L_ 355 L_ 355 LK_ 355 LK_ 400 LK_ 400 LK_ Motor size 355 S_ 355 SA 355 SB,SC 355 SB,SC 355 M_ 355 M_ 355 M_ 355 L_ 355 L_ 355 L_ 355 LK_ 355 LK_ 400 LK_ 400 LK_ Tolerances: A,B D F H

Poles 2 4-8 4 6-8 2 4 6-8 2 4 6-8 2 4-8 2 4-8 Poles 2 4-8 4 6-8 2 4 6-8 2 4 6-8 2 4-8 2 4-8

A 610 610 610 610 610 610 610 610 610 610 610 610 686 686 F 20 28 28 28 20 28 28 20 28 28 20 28 25 28

AA 110 110 110 110 110 110 110 110 110 110 110 110 140 140 G 67.5 90 90 90 67.5 90 90 67.5 90 90 67.5 90 81 90

AB 714 714 714 714 714 714 714 714 714 714 714 714 820 820 GA 79.5 106 106 106 79.5 106 106 79.5 106 106 79.5 106 95 106

AC 716 716 716 716 716 716 716 716 716 716 716 716 810 810 GD 12 16 16 16 12 16 16 12 16 16 12 16 14 16

B 500 500 500 500 560 560 560 630 630 630 630 630 710 710 H 355 355 355 355 355 355 355 355 355 355 355 355 400 400

B 710 710 800 800 HA 36 36 36 36 36 36 36 36 36 36 36 36 45 45

BA 100 100 100 100 100 100 100 100 100 100 100 100 140 140 HC 713 713 713 713 713 713 713 713 713 713 713 713 805 805

BB 584 584 584 584 644 644 644 714 714 714 802 802 935 935 HD 920 892 920 892 920 920 892 920 920 892 920 920 1003 1003

BC 180 180 220 220 K 28 28 28 28 28 28 28 28 28 28 28 28 35 35

C 254 254 254 254 254 254 254 254 254 254 254 254 280 280 L 1310 1380 1380 1380 1370 1440 1440 1450 1520 1520 1590 1660 1786 1826

D 75 100 100 100 75 100 100 75 100 100 75 100 90 100 LD 397 467 467 467 397 467 467 397 467 467 397 467 438 478

DB M20 M24 M24 M24 M20 M24 M24 M20 M24 M24 M20 M24 M24 M24

E 140 210 210 210 140 210 210 140 210 210 140 210 170 210

M000105

EG 40 48 48 48 40 48 48 40 48 48 40 48 48 48

Above table gives the main dimensions in mm. For detailed drawings please see our web-site www.abb.com/motors&drives or contact us.

ISO js 14 ISO m6 ISO h9 0, -1.0

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

161

General purpose open drip proof motors


Dimension drawings
Flange-mounted; IM B5 (IM 3001), IM V1 (IM 3011)

Sizes 355 - 400

Motor size 355 S_ 355 SA 355 SB,SC 355 SB,SC 355 M_ 355 M_ 355 M_ 355 L_ 355 L_ 355 L_ 355 LK_ 355 LK_ 400 LK_ 400 LK_ Motor size 355 S_ 355 SA 355 SB,SC 355 SB,SC 355 M_ 355 M_ 355 M_ 355 L_ 355 L_ 355 L_ 355 LK_ 355 LK_ 400 LK_ 400 LK_ Tolerances: D F N ISO m6 ISO h9 ISO js6

Poles 2 4-8 4 6-8 2 4 6-8 2 4 6-8 2 4-8 2 4-8 Poles 2 4-8 4 6-8 2 4 6-8 2 4 6-8 2 4-8 2 4-8

AC 716 716 716 716 716 716 716 716 716 716 716 716 810 810 L 1310 1380 1380 1380 1370 1440 1440 1450 1520 1520 1590 1660 1786 1826

D 75 100 100 100 75 100 100 75 100 100 75 100 90 100 LA 25 25 25 25 25 25 25 25 25 25 25 25 28 28

DB M20 M24 M24 M24 M20 M24 M24 M20 M24 M24 M20 M24 M24 M24 LB 1170 1170 1170 1170 1230 1230 1230 1310 1310 1310 1450 1450 1616 1616

E 140 210 210 210 140 210 210 140 210 210 140 210 170 210 LD 395 465 465 465 395 465 465 395 465 465 395 465 438 478

EG 40 48 48 48 40 48 48 40 48 48 40 48 48 48 M 740 740 740 740 740 740 740 740 740 740 740 740 940 940

F 20 28 28 28 20 28 28 20 28 28 20 28 25 28 N 680 680 680 680 680 680 680 680 680 680 680 680 880 880

G 67.5 90 90 90 67.5 90 90 67.5 90 90 67.5 90 81 90 P 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000

GA 79.5 106 106 106 79.5 106 106 79.5 106 106 79.5 106 95 106 S 23 23 23 23 23 23 23 23 23 23 23 23 28 28

GD 12 16 16 16 12 16 16 12 16 16 12 16 14 16 T 6 6 6 6 6 6 6 6 6 6 6 6 6 6

HB 565 537 565 537 565 565 537 565 565 537 565 565 565 565

Above table gives the main dimensions in mm. For detailed drawings please see our web-site www.abb.com/motors&drives or contact us.

162

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

M000107

General purpose open drip proof motors


Dimension drawings
Terminal box in standard design with 6 terminals Top-mounted terminal box:
122/4 142/4 162/4, 162/9 + adapter
M000080

Side-mounted terminal box:


122/5 142/6 162/7, 162/10

Terminal box type

Motor size

A1

B1

H1

Top-mounted terminal box: 122/4 142/4 162/4, 162/9 + Adapter 280 315 - 355 315 - 400 455 536 787 280 349 410 177 197 226

Side-mounted terminal box: 122/5 142/6 162/7, 162/10 280 315 - 355 315 - 400 383 426 508 280 347 412 180 201 226 Further details on terminal boxes on earlier pages. For motor dimensions please see dimension drawings on earlier pages.

Rating plate
The rating plate is in table form giving values for speed, current and power factor for six voltages.
M000109

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

163

General purpose open drip proof motors in brief, basic design


Motor frame size Stator Material Paint colour shade Paint thickness Material Paint colour shade Paint thickness D-end N-end Axially-locked bearings Bearing seal Lubrication Rating plate SPM-nipples Terminal box Frame material Cover material Cover screw material Cable Terminals 2 - 4 pole 6 pole 2-pole 4-12 poles 2-pole 4-12 poles 280 315 355 400

Prole-pressed sheet steel Blue, Munsell 8B 4.5/3.25 / NCS 4822-B05G / RAL 5014 Two-pack epoxy paint, thickness 70 m Cast iron GG 20/GRS 200 Blue, Munsell 8B 4.5/3.25 / NCS 4822-B05G / RAL 5014 Two-pack epoxy paint, thickness 70 m 6316/C4 6319/C3 6316/C4 6316/C3 6316/C4 6319/C4 6316/C4 6316/C3 on request 6322/C3 on request 6319/C3 on request 6322/C3 on request 6319/C3

Bearing end shields

Bearings

Inner bearing cover

As standard, locked at D-end V-ring as standard, radial seal on request Regreasing nipples, M10x1 Grease for bearing temperatures -30C to +120C Stainless steel, with individual serial number On request Cast iron GG 15 / GRS 150 Cast iron GG 15 / GRS 150 Steel 5G, coated with zinc and yellow chromated 2 x M63 2 x 50/80 2 x 80 2 x M63 2 x 60 2 x 60/80 6 terminals for connection with cable lugs (not included) Siluminium Sheet steel Blue, Munsell 8B 4.5/3.25 / NCS 4822-B05G / RAL 5014 Two-pack epoxypolyester paint, thickness 80 m Copper Insulation class F; temperature rise class B unless otherwise stated. PTC-thermistors 150C, 3 in series, as standard Pressure die-cast aluminium Half key balancing as standard Closed key way

Connections

Fan Fan cover

Material Material Paint colour shade Paint thickness Material Insulation Winding protection

Stator winding

Rotor winding Balancing method Key way Heating elements Drain holes Enclosure Cooling method

Material

On request

50 W

2x50 W

2x65 W

2x65 W

As standard, open on delivery IP 23S IC 01

164

ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006

ABB Motors total product offer


ABB offers several comprehensive ranges of AC motors and generators. We manufacture synchronous motors for even the most demanding applications, and a full range of low and high voltage induction motors. Our in-depth knowledge of virtually every type of industrial processing ensures we always specify the best solution for your needs.
M000328

Low voltage motors and generators


General purpose motor for standard applications Aluminum motors Steel motors Cast iron motors Open drip proof motors Global motors Brake motors Single phase motors Servomotors Process performance motors for more demanding applications Aluminum motors Cast iron motors (IEC and NEMA) Motors for high ambient temperatures Permanent magnet motors High speed motors Wind turbine generators Smoke venting motors Water cooled motors Motors for roller table drives Motors for hazardous areas Flameproof motors Increased safety motors Non-sparking motors Dust ignition proof motors Marine motors Aluminum motors Steel motors Cast iron motors Open drip proof motors

High voltage and synchronous motors and generators


High voltage cast iron motors Induction modular motors Slip ring motors Motors for hazardous areas Synchronous motors and generators DC motors and generators

234

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

Visit our web site


www.abb.com/motors&drives

Motors & Drives > Motors >> Low Voltage Motors >>> General purpose motors Aluminum motors Steel motors Cast iron motors Open drip proof motors Global motors Brake motors Single phase motors >>> Process performance motors >>> Motors for hazardous areas >>> Marine motors >>> Other applications NEMA motors Permanent magnet motors Smoke venting motors Roller table motors Water cooled motors Fan application motors Roller table motors > Generators

ABB LV Motors / Cat. BU / Low Voltage General Purpose Motors EN 12-2006

235

Low Voltage Motors


Manufacturing sites (*) and some of the larger sales companies.
Australia ABB Australia Pty Ltd 601 Blackburn Road Notting Hill VIC 3168 Tel: +61 (0) 8544 0000 Fax: +61 (0) 8544 0001 Austria ABB AG Clemens Holzmeisterstrasse 4 AT-1810 Wien Tel: +43 (0) 1 601 090 Fax: +43 (0) 1 601 09 8305 Belgium Asea Brown Boveri S.A.-N.V. Hoge Wei 27 BE-1930 Zaventem Tel: +32 (0) 2 718 6311 Fax: +32 (0) 2 718 6657 Canada ABB Inc., BA Electrical Machines 10300 Henri-Bourassa Blvd, West, Saint-Laurent, Quebec Canada H4S 1N6 Tel: +1 514 832-6583 Fax: +1 514 332-0609 China* ABB Shanghai Motors Co., Ltd. 88 Tianning Road Minhang(Economical and Technological Development Zone) 200245 Shanghai Tel: +86 21 5472 3133 Fax: +86 21 5472 5025 Chile Asea Brown Boveri S.A. P.O.Box 581-3 Santiago Tel: +56 (0) 2 5447 100 Fax: +56 (0) 2 5447 405 Denmark ABB A/S Automation Products Emil Neckelmanns Vej 14 DK-5220 Odense S Tel: +45 65 47 70 70 Fax: +45 65 47 77 13 Finland* ABB Oy Motors P.O.Box 633 FI-65101 Vaasa Tel: +358 (0) 10 22 11 Fax: +358 (0) 10 22 47372 France ABB Entrelec ZA La Boisse BP 90145 300 Rue des Prs-Seigneurs FR-01124 Montluel Cedex Tel: +33 4 37 40 40 00 Fax: +33 4 37 40 40 72 Germany ABB Automation Products GmbH Motors & Drives Wallstaedter Strasse 59 DE-68526 Ladenburg Tel: +49 (0) 6203 717 717 Fax: + 49 (0) 6203 717 600 Hong Kong ABB (Hong Kong) Ltd. Tai Po Industrial Estate, 3 Dai Hei Street, Tai Po, New Territories, Hong Kong Tel: +852 2929 3838 Fax: +852 2929 3505 India* ABB Ltd. 32, Industrial Area, N.I.T Faridabad 121 001 Tel: +91 (0) 129 502 3001 Fax: +91 (0) 129 502 3006 Indonesia PT. ABB Sakti Industri JL. Gajah Tunggal Km.1 Jatiuwung, Tangerang 15136 Banten, Indonesia Tel: + 62 21 590 9955 Fax: + 62 21 590 0115 - 6 Ireland Asea Brown Boveri Ltd Components Division Belgard Road Tallaght, Dublin 24 Tel: +353 (0) 1 405 7300 Fax: +353 (0) 1 405 7327 Italy* ABB SACE SpA LV Motors Via dell' Industria 18 IT-20010 Vittuone, Milano Tel: +39 02 90341 Fax: +39 02 9034 7289 Japan ABB K.K. 26-1 Cerulean Tower Sakuragaoka-cho, Shibuya-ku Tokyo 150-8512 Tel: +81 (0) 3 578 46251 Fax: +81 (0) 3 578 46260 Korea ABB Korea Ltd. 7-9, Oksan Bldg., 157-33 Sungsung-dong, Kangnam-ku Seoul Tel: +82 2 528 2329 Fax: +82 2 528 2338 Malaysia ABB Malaysia Sdn. Bhd. Lot 608, Jalan SS 13/1K 47500 Subang Jaya, Selangor Tel: +60 3 5628 4888 Fax: +60 3 5631 2926 Mexico ABB Mxico, S.A. de C.V. Apartado Postal 111 CP 54000 Tlalnepantla Edo. de Mxico, Mxico Tel: +52 5 328 1400 Fax: +52 5 390 3720 The Netherlands ABB B.V. Dept. LV motors (APP2R) P.O.Box 301 NL-3000 AH Rotterdam Tel: +31 (0) 10 4078 879 Fax: +31 (0) 10 4078 345 Norway ABB AS P.O.Box 154 Vollebekk NO-0520 Oslo Tel: +47 22 872 000 Fax: +47 22 872 541 Russia ABB Industrial & Building Systems Ltd. Business Centre "Krugozor" Obrucheva 30/1, Building 2 Moscow 117861 Tel: +7 495 960 2200, 956 93 93 Fax: +7 495 960 2209, 230 63 46 Singapore ABB Industry Pte Ltd 2 Ayer Rajah Crescent Singapore 139935 Tel: +65 6776 5711 Fax: +65 6778 0222 Spain* Asea Brown Boveri S.A. Automation Products - Fbrica Motores P.O.Box 81 ES-08200 Sabadell Tel: +34 93 728 8500 Fax: +34 93 728 8741 Sweden* ABB Automation Technologies AB LV Motors SE-721 70 Vsters Tel: +46 (0) 21 329 000 Fax: +46 (0) 21 329 140 Switzerland ABB Schweiz AG Normelec/CMC Components Motors&Drives Badenerstrasse 790 Postfach CH-8048 Zrich Tel: +41 (0) 58 586 0000 Fax: +41 (0) 58 586 0603 Taiwan ABB Ltd. 6F, No. 126, Nanking East Road, Section 4i Taipei, 105 Taiwan, R.O.C. Tel: +886 (0) 2 2577 6090 Fax: +886 (0) 2 2577 9467 Thailand ABB Limited (Thailand) 161/1 SG Tower, Soi Mahadlekluang 3, Rajdamri, Bangkok 10330 Tel: +66 2 665 1000 Fax: +66 2 665 1042 The United Kingdom ABB Ltd Drives, Motors and Machines Daresbury Park Daresbury, Warrington Cheshire, WA4 4BT Tel: +44 (0) 1925 741 111 Fax: +44 (0) 1925 741 212 USA ABB Inc. Low Voltage Motors 16250 W. Glendale Drive New Berlin, WI 53151 Tel: +1 262 785 3200 Fax: +1 262 780 8888 Venezuela Asea Brown Boveri S.A. P.O.Box 6649 Carmelitas, Caracas 1010A Tel: +58 (0) 2 238 2422 Fax: +58 (0) 2 239 6383

http://www.abb.com/motors&drives http://online.abb.com/motors&drives

Catalogue BU/General purpose motors EN 12-2006

Printed in Finland, 12-2006/8 000, Waasa Graphics

S-ar putea să vă placă și