GEI-52590A
Description
Instructions
Site Analysis Guides
GEI-52590A
Notice
The information contained in this document is subject to change without notice.
GE makes no warranty of any kind with regard to this material, including, but not limited
to, the implied warranties of merchantability and fitness for a particular purpose. GE shall
not be liable for errors contained herein or incidental consequential damages in
connection with the furnishing, performance, or use of this material.
This document contains proprietary information which is protected by copyright. All rights
are reserved. No part of this document may be photocopied or otherwise reproduced
without consent of GE.
Copyright (c) 1999 by GE
Published in a limited copyright sense, and all rights, including trade secrets, are
reserved.
Document Edition
- Preliminary
- First
- Second
10/96
6/99
4/01
kV, Lexan, MeterMate, OPTOCOM, Power Guard, Site Genie, Fitzall, and
SMARTCOUPLER are trademarks of GE.
Fitzall Guide
page 2
GEI-52590A
Table of Contents
Introduction to Fitzall Metering.
Basic Application Guidelines for New Installations..
Class 200, Form 9S Application Guidelines..
Fitzall Operation of the kV Meter.
Using the kV Site Analysis Guides..
kV Site Analysis guides for converting existing installations...
kV Site Genie Worksheet.
Fitzall and MeterMate - Operating Tips.....
Lower Nameplate Retrofits..
Meter
Form
9S
16S
10A
16A
48A
2W-1
10
23
30
43
50
Type of Service
3W-Net
4W-Y
3W-1
3W-
Page Number of the kV Site Analysis Guide
11,12,13
14
15
16,17,18,19
24,25
26
27
28
31, 32, 33
34
35
36,37,38,39
44,45
46
47
48
52,
53
51,
54
55
56,57,58,59
4
5
6
7
8,9
see below
63
64
65
4W-
20,21,22
29
40,41,42
49
60,61,62
Page numbers in bold adhere to Blondels Theorem for optimum metering accuracy
Fitzall Guide
page 3
GEI-52590A
page 4
CT
VT
9S Class 20
B solution L
LONDE
N
C
N/B
9S Fitzall
2 Wire
9S Fitzall
9S Fitzall
3 Wire
N
C
N/B
9S Fitzall
2 Wire
9S Fitzall
16S
Fitzall
Fitzall Guide
2 Wire
9S Fitzall
3 Wire
GE kV Fitzall Self-Contained
1,2, & 3 Phase
2,3, & 4 Wire
N/B
GEI-52590A
requirements.
16S
Fitzall
3 Wire
4 Wire
4Wire
Network, Y, &
A
16S
Fitzall
4 Wire
page 5
GEI-52590A
solution L
BLONDE
requirements.
GE kV Fitzall Self-Contained
(with separate voltage inputs)
9S Class 200
N
Network, Y, &
N/B
N/B
Fitzall Guide
page 6
GEI-52590A
ELE
4W-Y
MO 9-6
MO 36-2
MO 45-3
16S, 16A
4W
MO 9-6
3W-
3W-Network
3W-1
MO 45-3
MO 45-0
MO 45-4
MO 45-4
2W-1
MO 2-1
MO 12-0
MO 16-6
MO 12-4
MO 3-5
MO 12-4
MO 16-6
Form 9S
1 2 3
A
K Y Z
Fitzall Instantaneous
Power
pA = eA iA
pB = eB iB
pC = eC iC
pTOTAL = pA + pB + pC
0
C
9,10,16,48
MO 45&12 0
9,10,16,48
MO 2
MO 36
MO 45
MO 45&12
MO 3
MO 9&16
9,10,48
9,10,48
9,10,16,48
9,10,16,48
9,10,16,48
Fitzall Guide
1
2
3
4
5
6
eA
eC
eA
eA
eA
eA
eA
eA
Form 16S
1
GEI-52590A
Fitzall Guide
page 8
GEI-52590A
kV Site Analysis
2
3
L
i
n
e
Need rewiring
Need no wiring change
A
3-Wire, Delta
L
o
a
d
C
A
5
solution L
BLONDE
9S Fitzall
8
270
IC
180
270
EBC
EBA
IC
(ABC)
0
VC
VA
180
IA
IA
SERVICE
kV METER
Lagging
Lagging
IA
180
EBA
11
IC
TA 2.5
180
VA
IC
PF= 1
90
IA
(CBA)
EBC
744x9_____
VC
10
90
Kt 0.3
MO 45-0
Fitzall Guide
page 9
GEI-52590A
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
L
i
n
e
L
o
a
d
Need rewiring
Need no wiring change
N
2-Wire
Singlephase
L N
i
n A
e
L
o
a
d
solution L
BLONDE
9S Fitzall
9S Fitzall
270
270
ENA
180
IA
180
VA
IA
SERVICE
kV METER
90
Lagging
PF= 1
Fitzall Guide
CL 20 120-480V
TA 2.5
90
Lagging
Kt 0.3
MO 3-5
page 10
GEI-52590A
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
L N
i
C
n
e A
L
o
a
d
L
i
n
e
Need rewiring
Need no wiring change
C
3-Wire
Singlephase
L
o
a
d
C
A
solution L
BLONDE
9S Fitzall
9S Fitzall
270
270
ENA
IC
180
IA
ENC
IC
180
VC
VA
SERVICE
kV METER
90
Lagging
PF= 1
Fitzall Guide
IA
CL 20 120-480V
TA 2.5
90
Lagging
Kt 0.3
MO 45-4
page 11
GEI-52590A
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
Most old
installations:
L
o
a
d
270
C
3-Wire
Singlephase
L
o
a
d
270
ENA
IC
ENC
Need rewiring
Need no wiring change
L N
i
C
n
e A
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
180
L N
i
C
n
e A
9S Fitzall
VA
180
IA
IA
SERVICE
kV METER
90
Lagging
PF= 1
90
Lagging
Note: The three-wire circuit is summed in the transformers, thus allowing a 2-wire MeterMate
serVice selection.
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 3-5
page 12
GEI-52590A
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
Most old
installations:
Need rewiring
Need no wiring change
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
9S Fitzall
270
270
ENA
IC
ENC
180
VA
IC
kV METER
90
Lagging
PF= 1
Fitzall Guide
IA
IA
SERVICE
744x9_____
C
3-Wire
Singlephase
L N
i
C
n
e A
L
o
a
d
180
L N
i
C
n
e A
9S Fitzall
CL 20 120-480V
TA 2.5
90
Lagging
Kt 0.3
MO 2-1
page 13
GEI-52590A
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
Network
N
L
i
n
e
N
L
i
n C
e A
L
o
a
d
C
A
L
o
a
d
solution L
BLONDE
9S Fitzall
9S Fitzall
270
270
(ABC)
ENC
ENA
180
SERVICE
VC
IC
IA
IC
180
Lagging
VA
IA
Lagging
kV METER
(CBA)
ENA
180
IA
IC
VC
PF = 1.0
90
Meter Nameplate marking
Mult by _______ VTR ______:1 CTR ________:5
SERVICE: 4Y
4
3 3N 3W
2W
ELEMENTS: 3
21/2
2
1
Fitzall Guide
CL 20 120-480V
TA 2.5
IA
IC
ENC
744x9_____
VA
180
90
Kt 0.3
MO 45-4
page 14
GEI-52590A
kV Site Analysis
L B
i
C
n
e A
L
o
a
d
Need rewiring
Need no wiring change
A
3-Wire, Delta
L B
i
n C
e A
L
o
a
d
solution L
BLONDE
9S Fitzall
9S Fitzall
270
IC
180
270
EBC
EBA
IC
(ABC)
0
VC
VA
180
IA
IA
SERVICE
kV METER
Lagging
Lagging
IA
180
EBA
IC
TA 2.5
180
VA
IC
PF= 1
IA
(CBA)
EBC
90
744x9_____
VC
90
Kt 0.3
MO 45-0
Fitzall Guide
page 15
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
GEI-52590A
Need rewiring
Need no wiring change
4-Wire, Wye
N
L C
i
n B
e A
L C
i
n B
e A
L
o
a
d
L
o
a
d
solution L
BLONDE
9S Fitzall
9S Fitzall
270
270
IC
ENC
ENA
180
(ABC)
0
VA
180
IA
IB
VB
Lagging
ENA
180
IC
IA
90
Fitzall Guide
IB
VB
VA
180
IA
VC
90
PF= 1
CL 20 120-480V
(CBA)
IC
ENC
744x9_____
kV METER
Lagging
IB
ENB
IA
IB
ENB
SERVICE
IC
VC
Kt 0.3
MO 9-6
page 16
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
Most old
installations:
GEI-52590A
B
4-Wire, Wye
*(Except 29S)
N
L C
i
n B
e A
L
o
a
d
L C
i
n B
e A
L
o
a
d
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
9S Fitzall
9S Fitzall
270
270
IC
ENC
(ABC)
ENA
180
VA
180
IA
IB
IC
VC
IA
IB
ENB
SERVICE
Lagging
IB
ENB
IB
ENA
180
(CBA)
0
VC
PF= 1
90
Meter Nameplate marking
Mult by _______ VTR ______:1 CTR ________:5
SERVICE: 4Y
4
3 3N 3W
2W
ELEMENTS: 3
21/2
2
1
Fitzall Guide
TA 2.5
IA
IC
ENC
CL 20 120-480V
VA
180
IA
IC
744x9_____
kV METER
Lagging
90
Kt 0.3
MO 36-2
page 17
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
N
L
i
n
e
GEI-52590A
Need rewiring
Need no wiring change
4-Wire, Wye
L B
i
n C
e A
L
o
a
d
C
A
L
o
a
d
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
9S Fitzall
9S Fitzall
270
270
IC
IC
ENC
(ABC)
ENA
180
IB
VC
IA
180
0
VA
IA
ENB
SERVICE
kV METER
Lagging
Lagging
ENB
(CBA)
IB
ENA
180
VA
180
IA
IC
IA
VC
ENC
IC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 18
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
GEI-52590A
Need rewiring
Need no wiring change
4-Wire, Wye
N
L C
i
n B
e A
L C
i
n B
e A
L
o
a
d
L
o
a
d
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
9S Fitzall
9S Fitzall
270
270
IC
ENC
180
IC
ENA
(ABC)
0
VC
IA
180
IA
IB
VA
ENB
SERVICE
kV METER
Lagging
Lagging
ENB
(CBA)
IB
ENA
180
VA
180
IA
IC
IA
VC
IC
ENC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 19
GEI-52590A
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
4-Wire, Delta
N
N
L C
i
n B
e A
L C
i
n B
e A
L
o
a
d
L
o
a
d
solution L
BLONDE
9S Fitzall
9S Fitzall
270
270
VC
ENC
IC
180
(ABC)
ENB
ENA
IB
IA
180
IC
VA
VB
IA
IB
SERVICE
kV METER
Lagging
IB
Lagging
IA
180
(CBA)
0
ENB
IC
VC
PF= 1
Fitzall Guide
0
VA
VB
IC
90
CL 20 120-480V
IA
IB
180
ENA
ENC
744x9_____
TA 2.5
90
Kt 0.3
MO 9-6
page 20
GEI-52590A
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
4-Wire, Delta
N
L C
i
n B
e A
L
o
a
d
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
270
270
VC
ENC
IC
180
ENB
ENA
IB
IC
(ABC)
0
VA
180
IA
IA
SERVICE
kV METER
Lagging
IB
Lagging
IA
180
(CBA)
0
VA
180
ENA
ENB
IA
IC
IC
ENC
VC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 21
GEI-52590A
kV Site Analysis
Form 9S (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
4-Wire, Delta
N
L C
i
n B
e A
L
o
a
d
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
270
270
VC
ENC
IC
180
ENB
ENA
IB
IC
(ABC)
0
VA
180
IA
IA
SERVICE
kV METER
Lagging
IB
Lagging
IA
180
(CBA)
0
ENA
ENB
IC
VA
180
IA
IC
VC
ENC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 22
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
N
2-Wire
Singlephase
A
Line
16S
Fitzall
solution L
BLONDE
Load
270
270
ENA
180
IA
IA
90
Lagging
SERVICE
VA
180
90
Lagging
kV METER
PF = 1.0
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
Fitzall Guide
page 23
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
C
3-Wire
Singlephase
Line
16S
solution L
BLONDE
Fitzall
Load
270
270
IC
180
ENA
IA
ENC
VA
IC
180
IA
VC
SERVICE
kV METER
90
Lagging
90
Lagging
PF = 1.0
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
MO 12-4
page 24
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
C
3-Wire
Singlephase
Line
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
16S
Fitzall
Load
270
270
ENA
IC
180
IC
VA
IA
ENC
SERVICE
0 180
IA
90
Lagging
90
Lagging
kV METER
PF = 1.0
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
MO 2-1
page 25
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
Network
N
Line
solution L
BLONDE
16S
Fitzall
Load
270
270
(ABC)
ENC
VC
IC
ENA
180
IA
180
Lagging
SERVICE
IC
VA
IA
Lagging
kV METER
(CBA)
ENA
180
IA
IC
VA
180
IC
ENC
IA
VC
PF = 1.0
90
90
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
MO 12-4
page 26
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
A
3-Wire, Delta
Line
16S
solution L
BLONDE
Fitzall
Load
270
270
(ABC)
EAC
EBA
180
IB
VC
IC
IC
0
VA
180
IA
IA
ECB
Lagging
SERVICE
Lagging
ECB
kV METER
(CBA)
IA
IB
180
IA
0
EBA
180
0
VA
IC
IC
EAC
PF = 1.0
90
VC
90
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
MO 12-0
page 27
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
B
4-Wire, Wye
C
Line
16S
solution L
BLONDE
Fitzall
Load
270
270
(ABC)
VC
ENC
IC
IC
ENA
180
IA
IB
VA
180
IB
ENB
VB
Lagging
Lagging
SERVICE
(CBA)
ENB
IB
180
IA
IC
VA
180
IA
IC
ENC
kV METER
VB
IB
ENA
IA
VC
PF = 1.0
90
90
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
3-Element Automatic
Kt 3.0
MO 16-6
page 28
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
4-Wire, Delta
N
C
Line
16S
solution L
BLONDE
Fitzall
Load
270
270
(ABC)
VC
ENC
180
IC
ENB
ENA
180
IA
IB
IC
VB
IA
IB
Lagging
Lagging
SERVICE
VA
kV METER
(CBA)
IB
180
ENB
IB
IA
IA
180
VA
VB
ENA
IC
IC
VC
ENC
PF = 1.0
90
90
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
3-Element Automatic
Kt 3.0
MO 16-6
page 29
GEI-52590A
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
Fitzall
N
2-Wire
Singlephase
Fitzall
10A
10A
solution L
BLONDE
N LINE
N LOAD
N LINE
N LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
ENA
180
IA
180
VA
IA
SERVICE
kV METER
90
Lagging
PF= 1
Fitzall Guide
CL 20 120-480V
TA 2.5
90
Lagging
Kt 0.3
MO 3-5
page 30
GEI-52590A
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
Fitzall
C
3-Wire
Singlephase
Fitzall
10A
10A
solution L
BLONDE
N LINE
C LINE
N LOAD
C LOAD
N LINE
C LINE
N LOAD
C LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
ENA
IC
180
IA
ENC
IC
180
VC
VA
SERVICE
kV METER
90
Lagging
PF= 1
Fitzall Guide
IA
CL 20 120-480V
TA 2.5
90
Lagging
Kt 0.3
MO 45-4
page 31
GEI-52590A
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
10A
N LINE
C LINE
Most old
installations:
Need rewiring
Need no wiring change
C
3-Wire
Singlephase
Fitzall
10A
N LINE
C LINE
N LOAD
C LOAD
A LOAD
A LINE
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
Fitzall
N LOAD
C LOAD
A LOAD
A LINE
NOTE: Use half
the CT ratio in
determining
meter multiplier.
270
270
ENA
IC
180
ENC
VA
180
IA
IA
SERVICE
kV METER
90
Lagging
PF= 1
90
Lagging
Note: The three-wire circuit is summed in the transformers, thus allowing a 2-wire MeterMate
serVice selection.
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 3-5
page 32
GEI-52590A
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Fitzall
Need rewiring
Need no wiring change
C
3-Wire
Singlephase
Fitzall
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
10A
10A
N LINE
C LINE
N LOAD
C LOAD
N LINE
C LINE
N LOAD
C LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
ENA
IC
180
ENC
180
VA
IC
SERVICE
kV METER
90
Lagging
PF= 1
Fitzall Guide
IA
IA
CL 20 120-480V
TA 2.5
90
Lagging
Kt 0.3
MO 2-1
page 33
GEI-52590A
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
Network
Fitzall
Fitzall
10A
10A
solution L
BLONDE
N LINE
C LINE
N LOAD
C LOAD
N LINE
C LINE
N LOAD
C LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
(ABC)
ENC
ENA
180
SERVICE
VC
IC
IA
IC
180
Lagging
VA
IA
Lagging
kV METER
(CBA)
ENA
180
IA
IC
VC
PF = 1.0
90
Meter Nameplate marking
Mult by _______ VTR ______:1 CTR ________:5
SERVICE: 4Y
4
3 3N 3W
2W
ELEMENTS: 3
21/2
2
1
Fitzall Guide
CL 20 120-480V
TA 2.5
IA
IC
ENC
745x0_____
VA
180
90
Kt 0.3
MO 45-4
page 34
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
Fitzall
A
3-Wire, Delta
Fitzall
10A
10A
solution L
BLONDE
C LINE
B LINE
A LINE
C LINE
B LINE
A LINE
C LOAD
B LOAD
A LOAD
270
IC
180
C LOAD
B LOAD
A LOAD
270
EBC
EBA
IC
(ABC)
0
VC
VA
180
IA
IA
SERVICE
kV METER
Lagging
Lagging
IA
180
EBA
IC
TA 2.5
180
VA
IC
PF= 1
IA
(CBA)
EBC
90
745x0_____
VC
90
Kt 0.3
MO 45-0
Fitzall Guide
page 35
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
GEI-52590A
Fitzall
4-Wire, Wye
Fitzall
10A
10A
solution L
BLONDE
N LINE
C LINE
B LINE
A LINE
N LINE
C LINE
B LINE
A LINE
N LOAD
C LOAD
B LOAD
A LOAD
N LOAD
C LOAD
B LOAD
A LOAD
270
270
IC
ENC
ENA
180
(ABC)
0
VA
180
IA
IB
VB
Lagging
ENA
180
IC
IA
90
Fitzall Guide
IB
VB
VA
180
IA
VC
90
PF= 1
CL 20 120-480V
(CBA)
IC
ENC
745x0_____
kV METER
Lagging
IB
ENB
IA
IB
ENB
SERVICE
IC
VC
Kt 0.3
MO 9-6
page 36
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Fitzall
N LINE
C LINE
B LINE
A LINE
Fitzall
10A
N LOAD
C LOAD
B LOAD
A LOAD
270
270
IC
ENC
(ABC)
ENA
180
IC
VC
VA
180
IA
IB
4-Wire, Wye
N LINE
C LINE
B LINE
A LINE
N LOAD
C LOAD
B LOAD
A LOAD
A
B
Need rewiring
Need no wiring change
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
10A
GEI-52590A
IA
IB
ENB
SERVICE
Lagging
IB
ENB
IB
ENA
180
(CBA)
0
VC
PF= 1
90
Meter Nameplate marking
Mult by _______ VTR ______:1 CTR ________:5
SERVICE: 4Y
4
3 3N 3W
2W
ELEMENTS: 3
21/2
2
1
Fitzall Guide
TA 2.5
IA
IC
ENC
CL 20 120-480V
VA
180
IA
IC
745x0_____
kV METER
Lagging
90
Kt 0.3
MO 36-2
page 37
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Fitzall
N LINE
C LINE
B LINE
A LINE
Need rewiring
Need no wiring change
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
10A
4-Wire, Wye
Fitzall
10A
N LINE
C LINE
B LINE
A LINE
N LOAD
C LOAD
B LOAD
A LOAD
GEI-52590A
270
N LOAD
C LOAD
B LOAD
A LOAD
270
IC
IC
ENC
(ABC)
ENA
180
IB
VC
IA
180
0
VA
IA
ENB
SERVICE
kV METER
Lagging
Lagging
ENB
(CBA)
IB
ENA
180
VA
180
IA
IC
IA
VC
ENC
IC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 38
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Fitzall
Need rewiring
Need no wiring change
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
10A
GEI-52590A
4-Wire, Wye
Fitzall
10A
N LINE
C LINE
N LOAD
C LOAD
N LINE
C LINE
N LOAD
C LOAD
B LINE
B LOAD
B LINE
B LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
IC
ENC
180
IC
ENA
(ABC)
0
VC
IA
180
IA
IB
VA
ENB
SERVICE
kV METER
Lagging
Lagging
ENB
(CBA)
IB
ENA
180
VA
180
IA
IC
IA
VC
IC
ENC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 39
GEI-52590A
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Need rewiring
B
Need no wiring change (10A)
Most old
installations:
4-Wire, Delta
Fitzall
Fitzall
10A
10A
solution L
BLONDE
N LINE
C LINE
B LINE
A LINE
N LINE
C LINE
B LINE
A LINE
N LOAD
C LOAD
B LOAD
A LOAD
270
270
VC
ENC
IC
180
N LOAD
C LOAD
B LOAD
A LOAD
(ABC)
ENB
ENA
IB
IA
180
IC
VA
VB
IA
IB
SERVICE
kV METER
Lagging
IB
Lagging
IA
180
(CBA)
0
ENB
IC
VC
PF= 1
Fitzall Guide
0
VA
VB
IC
90
CL 20 120-480V
IA
IB
180
ENA
ENC
744x9_____
745x0_____
TA 2.5
90
Kt 0.3
MO 9-6
page 40
GEI-52590A
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
4-Wire, Delta
Fitzall
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
10A
N LINE
N LOAD
C LINE
C LOAD
B LINE
B LOAD
A LINE
A LOAD
270
270
VC
ENC
IC
180
ENB
ENA
IB
IC
(ABC)
0
VA
180
IA
IA
SERVICE
kV METER
Lagging
IB
Lagging
IA
180
(CBA)
0
VA
180
ENA
ENB
IA
IC
IC
ENC
VC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 41
GEI-52590A
kV Site Analysis
Form 10A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
4-Wire, Delta
Fitzall
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
10A
N LINE
N LOAD
C LINE
C LOAD
B LINE
B LOAD
A LINE
A LOAD
270
270
VC
ENC
IC
180
ENB
ENA
IB
IC
(ABC)
0
VA
180
IA
IA
SERVICE
kV METER
Lagging
IB
Lagging
IA
180
(CBA)
0
ENA
ENB
IC
VA
180
IA
IC
VC
ENC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 42
GEI-52590A
kV Site Analysis
Form 16A (Self-Contained)
Fitzall Application
Need rewiring
Need no wiring change
16A
Fitzall
N
2-Wire
Singlephase
solution L
BLONDE
A LINE
A LOAD
N LINE
N LOAD
270
270
ENA
180
VA
180
IA
IA
90
Lagging
SERVICE
90
Lagging
kV METER
PF = 1.0
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
Fitzall Guide
page 43
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
C
3-Wire
Singlephase
16A
Fitzall
solution L
BLONDE
A LINE
A LOAD
C LINE
N LINE
C LOAD
N LOAD
270
270
IC
180
ENA
IA
ENC
VA
IC
180
IA
VC
SERVICE
kV METER
90
Lagging
90
Lagging
PF = 1.0
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
MO 12-4
page 44
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
C
3-Wire
Singlephase
16A
Fitzall
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
A LINE
A LOAD
C LINE
N LINE
C LOAD
N LOAD
270
270
ENA
IC
180
IC
VA
IA
ENC
SERVICE
0 180
IA
90
Lagging
90
Lagging
kV METER
PF = 1.0
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
MO 2-1
page 45
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
Network
16A
Fitzall
solution L
BLONDE
A LINE
A LOAD
C LINE
N LINE
C LOAD
N LOAD
270
270
(ABC)
ENC
VC
IC
ENA
180
IA
180
Lagging
SERVICE
IC
VA
IA
Lagging
kV METER
(CBA)
ENA
180
IA
IC
VA
180
IC
ENC
IA
VC
PF = 1.0
90
90
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
MO 12-4
page 46
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
A
3-Wire, Delta
16A
Fitzall
solution L
BLONDE
A LINE
A LOAD
C LINE
B LINE
C LOAD
B LOAD
270
270
(ABC)
EAC
EBA
180
IB
VC
IC
IC
0
VA
180
IA
IA
ECB
Lagging
SERVICE
Lagging
ECB
kV METER
(CBA)
IA
IB
180
IA
0
EBA
180
0
VA
IC
IC
EAC
PF = 1.0
90
VC
90
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
Kt 3.0
MO 12-0
page 47
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
B
4-Wire, Wye
16A
Fitzall
solution L
BLONDE
A LINE
B LINE
C LINE
N LINE
A LOAD
B LOAD
C LOAD
N LOAD
270
270
(ABC)
VC
ENC
IC
IC
ENA
180
IA
IB
VA
180
IB
ENB
VB
Lagging
Lagging
SERVICE
(CBA)
ENB
IB
180
IA
IC
VA
180
IA
IC
ENC
kV METER
VB
IB
ENA
IA
VC
PF = 1.0
90
90
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
3-Element Automatic
Kt 3.0
MO 16-6
page 48
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
4-Wire, Delta
16A
Fitzall
solution L
BLONDE
A LINE
B LINE
C LINE
N LINE
A LOAD
B LOAD
C LOAD
N LOAD
270
270
(ABC)
VC
ENC
180
IC
ENB
ENA
180
IA
IB
IC
VB
IA
IB
Lagging
Lagging
SERVICE
VA
kV METER
(CBA)
IB
180
ENB
IB
IA
IA
180
VA
VB
ENA
IC
IC
VC
ENC
PF = 1.0
90
90
Fitzall Guide
3N
3W
CL 200 120-480V
2W
1
TA 30
3-Element Automatic
Kt 3.0
MO 16-6
page 49
GEI-52590A
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
Fitzall
N
2-Wire
Singlephase
Fitzall
48A
48A
solution L
BLONDE
N LINE
N LOAD
N LINE
N LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
ENA
180
IA
180
VA
IA
SERVICE
kV METER
90
Lagging
PF= 1
Fitzall Guide
CL 20 120-480V
TA 2.5
90
Lagging
Kt 0.3
MO 3-5
page 50
GEI-52590A
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
Fitzall
C
3-Wire
Singlephase
Fitzall
48A
48A
solution L
BLONDE
N LINE
C LINE
N LOAD
C LOAD
N LINE
C LINE
N LOAD
C LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
ENA
IC
180
IA
ENC
IC
180
VC
VA
SERVICE
kV METER
90
Lagging
PF= 1
Fitzall Guide
IA
CL 20 120-480V
TA 2.5
90
Lagging
Kt 0.3
MO 45-4
page 51
GEI-52590A
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
48A
N LINE
C LINE
Most old
installations:
Need rewiring
Need no wiring change
C
3-Wire
Singlephase
Fitzall
48A
N LINE
C LINE
N LOAD
C LOAD
A LOAD
A LINE
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
Fitzall
N LOAD
C LOAD
A LOAD
A LINE
NOTE: Use half
the CT ratio in
determining
meter multiplier.
270
270
ENA
IC
180
ENC
VA
180
IA
IA
SERVICE
kV METER
90
Lagging
PF= 1
90
Lagging
Note: The three-wire circuit is summed in the transformers, thus allowing a 2-wire MeterMate
serVice selection.
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 3-5
page 52
GEI-52590A
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Fitzall
Need rewiring
Need no wiring change
C
3-Wire
Singlephase
Fitzall
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
48A
48A
N LINE
C LINE
N LOAD
C LOAD
N LINE
C LINE
N LOAD
C LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
ENA
IC
180
ENC
180
VA
IC
SERVICE
kV METER
90
Lagging
PF= 1
Fitzall Guide
IA
IA
CL 20 120-480V
TA 2.5
90
Lagging
Kt 0.3
MO 2-1
page 53
GEI-52590A
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
Network
Fitzall
Fitzall
48A
48A
solution L
BLONDE
N LINE
C LINE
N LOAD
C LOAD
N LINE
C LINE
N LOAD
C LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
(ABC)
ENC
ENA
180
SERVICE
VC
IC
IA
IC
180
Lagging
VA
IA
Lagging
kV METER
(CBA)
ENA
180
IA
IC
VC
PF = 1.0
90
Meter Nameplate marking
Mult by _______ VTR ______:1 CTR ________:5
SERVICE: 4Y
4
3 3N 3W
2W
ELEMENTS: 3
21/2
2
1
Fitzall Guide
CL 20 120-480V
TA 2.5
IA
IC
ENC
745x8_____
VA
180
90
Kt 0.3
MO 45-4
page 54
GEI-52590A
kV Site Analysis
Need rewiring
Need no wiring change
Fitzall
A
3-Wire, Delta
Fitzall
48A
48A
solution L
BLONDE
C LINE
B LINE
A LINE
C LINE
B LINE
A LINE
C LOAD
B LOAD
A LOAD
270
IC
180
C LOAD
B LOAD
A LOAD
270
EBC
EBA
IC
(ABC)
0
VC
VA
180
IA
IA
SERVICE
kV METER
Lagging
Lagging
IA
180
EBA
IC
TA 2.5
180
VA
IC
PF= 1
IA
(CBA)
EBC
90
745x8_____
VC
90
Kt 0.3
MO 45-0
Fitzall Guide
page 55
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
GEI-52590A
Need rewiring
Need no wiring change
Fitzall
4-Wire, Wye
Fitzall
48A
48A
solution L
BLONDE
N LINE
C LINE
B LINE
A LINE
N LINE
C LINE
B LINE
A LINE
N LOAD
C LOAD
B LOAD
A LOAD
N LOAD
C LOAD
B LOAD
A LOAD
270
270
IC
ENC
ENA
180
(ABC)
0
VA
180
IA
IB
VB
Lagging
ENA
180
IC
IA
90
Fitzall Guide
IB
VB
VA
180
IA
VC
90
PF= 1
CL 20 120-480V
(CBA)
IC
ENC
745x8_____
kV METER
Lagging
IB
ENB
IA
IB
ENB
SERVICE
IC
VC
Kt 0.3
MO 9-6
page 56
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Fitzall
N LINE
C LINE
B LINE
A LINE
Fitzall
48A
N LOAD
C LOAD
B LOAD
A LOAD
270
270
IC
ENC
(ABC)
ENA
180
IC
VC
VA
180
IA
IB
4-Wire, Wye
N LINE
C LINE
B LINE
A LINE
N LOAD
C LOAD
B LOAD
A LOAD
A
B
Need rewiring
Need no wiring change
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
48A
GEI-52590A
IA
IB
ENB
SERVICE
Lagging
IB
ENB
IB
ENA
180
(CBA)
0
VC
PF= 1
90
Meter Nameplate marking
Mult by _______ VTR ______:1 CTR ________:5
SERVICE: 4Y
4
3 3N 3W
2W
ELEMENTS: 3
21/2
2
1
Fitzall Guide
TA 2.5
IA
IC
ENC
CL 20 120-480V
VA
180
IA
IC
745x8_____
kV METER
Lagging
90
Kt 0.3
MO 36-2
page 57
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Fitzall
N LINE
C LINE
B LINE
A LINE
Need rewiring
Need no wiring change
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
48A
4-Wire, Wye
Fitzall
48A
N LINE
C LINE
B LINE
A LINE
N LOAD
C LOAD
B LOAD
A LOAD
GEI-52590A
270
N LOAD
C LOAD
B LOAD
A LOAD
270
IC
IC
ENC
(ABC)
ENA
180
IB
VC
IA
180
0
VA
IA
ENB
SERVICE
kV METER
Lagging
Lagging
ENB
(CBA)
IB
ENA
180
VA
180
IA
IC
IA
VC
ENC
IC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 58
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Fitzall
Need rewiring
Need no wiring change
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
48A
GEI-52590A
4-Wire, Wye
Fitzall
48A
N LINE
C LINE
N LOAD
C LOAD
N LINE
C LINE
N LOAD
C LOAD
B LINE
B LOAD
B LINE
B LOAD
A LINE
A LOAD
A LINE
A LOAD
270
270
IC
ENC
180
IC
ENA
(ABC)
0
VC
IA
180
IA
IB
VA
ENB
SERVICE
kV METER
Lagging
Lagging
ENB
(CBA)
IB
ENA
180
VA
180
IA
IC
IA
VC
IC
ENC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 59
GEI-52590A
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
4-Wire, Delta
Fitzall
Fitzall
48A
48A
solution L
BLONDE
N LINE
C LINE
B LINE
A LINE
N LINE
C LINE
B LINE
A LINE
N LOAD
C LOAD
B LOAD
A LOAD
270
270
VC
ENC
IC
180
N LOAD
C LOAD
B LOAD
A LOAD
(ABC)
ENB
ENA
IB
IA
180
IC
VA
VB
IA
IB
SERVICE
kV METER
Lagging
IB
Lagging
IA
180
(CBA)
0
ENB
IC
VC
PF= 1
Fitzall Guide
0
VA
VB
IC
90
CL 20 120-480V
IA
IB
180
ENA
ENC
744x9_____
745x8_____
TA 2.5
90
Kt 0.3
MO 9-6
page 60
GEI-52590A
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
4-Wire, Delta
Fitzall
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
48A
N LINE
N LOAD
C LINE
C LOAD
B LINE
B LOAD
A LINE
A LOAD
270
270
VC
ENC
IC
180
ENB
ENA
IB
IC
(ABC)
0
VA
180
IA
IA
SERVICE
kV METER
Lagging
IB
Lagging
IA
180
(CBA)
0
VA
180
ENA
ENB
IA
IC
IC
ENC
VC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 61
GEI-52590A
kV Site Analysis
Form 48A (Transformer Rated)
Fitzall Application
Need rewiring
Need no wiring change
4-Wire, Delta
Fitzall
Accuracy is based
on balanced voltage
assumptions which,
if not fulfilled, will
result in systematic
errors unrelated to
meter calibration.
48A
N LINE
N LOAD
C LINE
C LOAD
B LINE
B LOAD
A LINE
A LOAD
270
270
VC
ENC
IC
180
ENB
ENA
IB
IC
(ABC)
0
VA
180
IA
IA
SERVICE
kV METER
Lagging
IB
Lagging
IA
180
(CBA)
0
ENA
ENB
IC
VA
180
IA
IC
VC
ENC
PF= 1
90
90
Fitzall Guide
CL 20 120-480V
TA 2.5
Kt 0.3
MO 45-3
page 62
GEI-52590A
Meter #: ________________
Site: ___________________
_______________________
_______________________
GE Me t e r
kV Site Genie Worksheet
Service: ________________
FUNDAMENTAL
A
Voltage Angle
C
o
0.0
Voltage
Lagging
Volts
o
Current Angle
Current
Lagging
Amperes
270o Lagging
Diagnostic Counts
D1
D2
D3
D4
D5T
D5A
D5B
D5C
D6
D7
D8
VA
180o
90o Lagging
Meter
Display
Status
Fitzall Guide
0o
Fill-in
Lit
Arrows
Blinking
Off - Blinking
C Off - Blinking
Ca __________
__________
Er __________
page 63
GEI-52590A
Using MeterMate Meter Comm (MMDOS), make sure you program the kV meter first
before using the Program, serVice, commands to set the appropriate service type and
number of active metering elements. MeterMate software will only allow the serVice
command to be performed on programmed meters. (An exception allows meters that are
to be electronically sealed - a special write protected state of the meter - to have the
serVice command executed on unprogrammed meters. MMDOS determines this by the
status of the SealFlag parameter in the MMDOS.INI file.)
There is no need to change the serVice setting from Automatic, 3-element for
installation on 4-wire services, wye or delta, where all 3 elements of the meter are active.
It may be best to leave the meter on Automatic, 3-element so that it may be flexibly
applied to both 4-wire wye and delta services with only a lower nameplate change, no
reprogramming required.
If you are operating the meter as a 2 1/2 element meter on a transformer rated 4-wire
wye service, make sure you set the serVice type correctly (4-wire wye, 2.5 element). If
left on Automatic, 3-element in this scenario (no B phase potential applied to the meter),
the meter will only provide 2/3rds registration for balanced three phase loads. This type
of situation may be easily detected by noting that the B phase potential indicator on the
meters LCD will be blinking, and if enabled, the CA 000400 (low potential) message will
appear in the display. In a Fitzall meter correctly configured for this application (4-wire
wye, 2.5 element) the B phase potential indicator is simply blank since the meter
understands that no B phase potential is supposed to be present. Most (if not all) other
Fitzall applications would provide correct metering values if wired per Application Guides
in this document even if the serVice was inadvertently left on Automatic, 3-element.
Only the diagnostic capabilities of the meter would be ineffective. To ensure proper
operation of both the revenue calculations and diagnostic operation of the kV Fitzall
meter, it is important to make sure the serVice type is set appropriately, as indicated on
the application guide pages of this document.
When you perform the Program, serVice, commands in MMDOS, the service type that
first appears highlighted on the computer screen is the currently active service setting in
the meter.
Different applications may require different diagnostic test tolerance thresholds to be set.
As with any kV meter application (Fitzall or not), to avoid erroneous or meaningless
diagnostic caution messages from appearing in the display, make sure that only the
relevant diagnostics are enabled and set with tolerance thresholds that make sense for
the specific application at hand. To allow the use of a common program, MeterMate
Meter Comm (MMDOS) allows independent setting of the Site Genie diagnostics for
on-site modifications as needed, using the Program, reConfig, Sitegenie, and
Diagnostic or Parameters commands.
Fitzall Guide
page 64
GEI-52590A
9938366001
CL200
9938366002
CL320
9938366003
CL20
9938366004
Fitzall Guide
CL150 (A-Base)
Mult by _________
SERVICE: 4Y 4 3 3N 3W 2W
ELEMENTS:
3
2
1
CL 200 120-480V TA 30 Kt 21.6
Mult by _________
SERVICE: 4Y 4 3 3N 3W 2W
ELEMENTS:
3
2
1
CL320 120-480V TA 50 Kt 27.0
Mult by _________
SERVICE: 4Y 4 3 3N 3W 2W
ELEMENTS:
3
2
1
CL 150 120-480V TA 30 Kt 21.6
page 65