Section G

ECONOMIZERS

yogesh rade

CONTENTS

FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRODUCT OFFERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Optional Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIMENSIONS AND WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-3 G-4 G-4 G-4 G-4 PERFORMANCE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-4 ENGINEERING DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-6 SAMPLE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-15

G-1
09-06

Section G
ILLUSTRATIONS Figure G-1. E+Plus Economizer Mounting to Firetube Boiler (Model CBBoilers) . . . . . . . . . . . . . . Figure G-2. Economizer Above Industrial Watertube Boiler (Example) . . . . . . . . . . . . . . . . . . . . . Figure G-3. Economizer on Side of Industrial Watertube Boiler (Example) . . . . . . . . . . . . . . . . . Figure G-4. Typical Economizer Feedwater Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure G-5. Typical Economizer Feedwater Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure G-6. Typical Economizer Feedwater Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure G-7. Typical Economizer Feedwater Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure G-8. Typical Economizer Feedwater Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure G-9. Typical Economizer Feedwater Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TABLES Table G-1. Firetube Boiler E+Plus Economizers Dimensions and Weights (Model CB Boilers) . . . . Table G-2. Industrial Watertube Boiler Rectangular Economizers, Dimensions and Weights . . . . . . Table G-3. Firetube Boiler E+Plus Economizer, Performance Data (Model CB Boilers) . . . . . . . . . Table G-4. Industrial Watertube Boilers Rectangular Economizer Performance Data . . . . . . . . . . . Table G-5. Firetube Boiler E+Plus Economizers, Efficiencies (Model CB Boilers) . . . . . . . . . . . . . Table G-6. Industrial Watertube Boiler Rectangular Economizers, Efficiencies . . . . . . . . . . . . . . . .

G-8 G-9 G-10 G-11 G-11 G-12 G-12 G-13 G-13 G-5 G-5 G-6 G-7 G-7 G-7

This section contains information on Economizers. An economizer recovers heat from flue gases and uses it to increase boiler feedwater temperatures, prior to entering the boiler. Cleaver-Brooks offers a variety of types, sizes, and custom designs. Each assures proper match for your specific firetube or watertube boiler.

G-2
09-06

Section G

FEATURES AND BENEFITS


Reduces Fuel Use and Cost: Recovers heat from flue gases that would otherwise be wasted. Heat is used to raise boiler feedwater temperature prior to entering the boiler.

Load Changes: Rapid changes in load demands can be met faster due to higher feedwater temperature.

Emissions: Reduced fuel-firing rates for any given steam output means reduced NOx emissions.

ASME Construction: Ensures high quality design and manufacturing standards. Provides safety and reliability.

High Efficiency Heat Exchanger: Provides uniform fin-to-tube contact for maximum heat transfer. Fin tubing offers up to 12 times the heat exchange surface of bare tubing of the same diameter.

Self-Draining Design: Suitable for outdoor installation.

Low Pressure Drop: Provides low gas side pressure drops. Permits use of smaller forced draft fans. Permits use of existing fans in almost all installations.

Gas Tight Combustion Stack: Provides inner casing of carbon steel (watertube boilers). Stainless Steel casing for the E+Plus on firetube boilers. Compact dimensions provide for easy installation.

Feedwater Preheating System: (watertube boilers) Controls cold end corrosion through all flow rates. Prevents the forming of corrosive acids in the economizer. Prevents stack corrosion.

Guaranteed Efficiency on Model CB Firetube Boilers: $10,000 rebated for every full 1.0% efficiency point less than guaranteed.

G-3
09-06

Section G

PRODUCT OFFERING
Cleaver-Brooks offers a line of custom-engineered economizers for boiler sizes up to and including 150 MMBtu/hr. input. The model E+Plus Fuel Economizers, are available for firetube boilers up to 1800 HP . Standard Equipment Equipment described is for the standard E+Plus Fuel Economizer, as defined later in the specifications, and in the current literature. Standards for both cylindrical and rectangular E+Plus Economizers include: Optional Equipment Designed and fabricated in accordance with the ASME Boiler and Pressure Vessel Code, UM stamp standard, U stamp and Section I optional. Thermometer and safety valve connections at the feedwater headers. Incorporates self-draining design. Safety valve. Vertical or horizontal flue gas flow patterns on rectangular design. Utilization of waste gas. Soot blowers for oil firing. Feedwater and sootblower piping from economizer to boiler (watertube boilers only). Feedwater preheating system (watertube boilers only).

DIMENSIONS AND WEIGHTS


Information in this section outlines typical dimensions and weights of an economizer, and typical ratings and efficiencies when utilizing an economizer. Table G-1 lists dimensions and weights for a E+Plus Economizer typically installed with a firetube boiler. (Model CB Boilers). Table G-2 lists dimensions and weights for a rectangular Economizer typically installed with an industrial watertube boiler. The selection of a cylindrical or rectangular economizer for a particular application will depend on type and capacity of the boiler and job site conditions.

PERFORMANCE DATA
Tables listed here contain performance data for: Gas fired, 100 through 800 hp firetube boilers operating at 125 psig, and utilizing a E+Plus fuel economizer. Gas fired, industrial watertube boilers operating at 150 psig and utilizing a rectangular fuel economizer.

For additional operating pressures, load capacity or fuel selections, contact your local Cleaver-Brooks authorized representative. Table G-3 lists typical water and gas side temperatures when utilizing a E+Plus Economizer with a firetube boiler (Model CB & CB-LE Boilers).
Do not use on boilers equipped with flue gas recirculation. Contact your local Cleaver-Brooks authorized representative.

Notice

Table G-4 lists typical water and gas side temperatures when utilizing a rectangular
G-4
09-06

Section G

Table G-1. Firetube Boiler E+Plus Economizers Dimensions and Weights (Model CB Boilers)
DIMENSIONS (APPROX) WIDTH (IN.) 100 hp 125 hp 150 hp 200 hp 250 hp 300 hp 350 hp 400 hp 500 hp 600 hp 700 hp 800 hp CBC 16A6AL CBC 18D7AL CBC 18D7AL CBC 18E6AL CBR 30H7AL CBR 30H7AL CBR 30F7AL CBR 36F7AL CBR 36G 6AL CBR 36H5AL CBR 36J5AL CBR 36J5AL 30RD 30RD 30RD 30RD 52 52 52 60 60 60 60 60 DEPTH (IN.) 43 43 43 50 50 50 50 50 HEIGHT (IN.) 25 37 37 41 58.3 58.3 50 50 54.2 58.3 66.8 66.8 270 380 381 410 1320 1320 1120 1470 1596 1716 1961 1961 DRY UNIT WEIGHT (LBS)

BOILER HP

ECONOMIZER MODEL NUMBER

NOTES: 1. Dimensions in inches. 2. Boiler firing natural gas. 3. Boiler operating pressure is 125 psig (acceptable tolerance is 5 psig). 4. Contact your local Cleaver-Brooks representative for sizing detail. Model CBCs are cylindrical Model CBRs are rectangular

Table G-2. Industrial Watertube Boiler Rectangular Economizers, Dimensions and Weights
ECONOMIZER GAS FLOW DIRECTION (EXAMPLE) VERTICAL HORIZONTAL VERTICAL VERTICAL APPROXIMATE DIMENSIONS (INCHES) LENGTH 105 49 140 155 WIDTH 29 110 47 59 HEIGHT 76 47 76 80 DRY UNIT WEIGHT (LBS) 4400 5800 8800 11600

BOILER MODEL D-34 D-52 D-76 D-94

NOTES: 1. Dimensions in inches. 2. Data indicated is for select applications. Each Economizer is designed on a job to job basis. 3. Boiler is firing natural gas. 4. Boiler operating pressure is 150 psig (acceptable tolerance is 5 psig). 5. Economizer gas flow direction can be either horizontal or vertical.

G-5
09-06

Section G
Table G-3. Firetube Boiler E+Plus Economizer, Performance Data (Model CB Boilers)
WATER SIDE BOILER HP LOAD % ECONOMIZER MODEL NO. FLOW PPH TEMPERATURE IN F OUTF PRESS. DROP PSIG FLOW PPH GAS SIDE TEMPERATURE IN F OUT F PRESS. DROP IN. WC ENERGY SAVED BTU/HR HEATING SURFACE SQ-FT

100 125 150 200 250 300 350 400 500 600 700 800

100 100 100 100 100 100 100 100 100 100 100 100

CBC-16A6AL CBC-18D6AL CBC-18D7AL CBC-18E6AL CBC-30H7AL CBC-30H7AL CBC-30F7AL CBC-36F7AL CBC-36G6AL CBC-36H5AL CBC-36J5AL CBC-36J5AL

3356 4195 5034 6711 8389 10067 11745 13423 16779 20134 23490 26846

227 227 227 227 227 227 227 227 227 227 227 227

258 275 265 256 271 265 259 262 251 247 245 245

1.5 3.92 5.44 10.4 0.01 0.01 0.01 0.02 0.03 0.03 0.03 0.04

3611 4586 5432 7191 9158 10910 12638 14470 17883 21399 24895 28491

410 465 420 395 460 435 410 425 385 370 365 370

303 301 290 295 310 304 301 304 299 305 300 304

0.22 0.13 0.18 0.2 0.1 0.14 0.26 0.24 0.24 0.24 0.24 0.31

125500 247800 229900 229400 451800 466800 447500 571900 490900 476200 513600 597700

151 316 316 309 733 733 611 733 699 645 753 753

NOTES: 1. Feedwater temperature to economizer is at least 220 F (Deaerated). 2. Boiler operating pressure is 125 psig (acceptable tolerance 5 psig). 3. Gas side flow (pph) determined with 10% excess air (50 to 100% of capacity). 4. Continuous modulated feedwater flow must be provided. 5. Boiler firing natural gas 6. Contact your local Cleaver-Brooks representative for sizing detail.

E+Plus Economizer with an industrial watertube boiler. Table G-5 lists typical increases in efficiency for a firetube boiler (Model CB & CBLE Boilers). Table G-6 lists typical increases in efficiency for an industrial watertube boiler.

ENGINEERING DATA
Information in this section outlines typical installation. Actual installation and piping arrangements will be dictated by design, state, provincial or local codes, and job-site conditions. Firetube Boilers (Model CB & CB-LE Boilers) Installation - economizer above boiler: All standard firetube boilers (100 hp and above) can support up to 2,000 lbs without additional reinforcement. Firetube boilers up to 250 hp can be reinforced to support 2,500 lbs, however, this must be specified. Firetube boiler sizes 250 hp through 800 hp can be reinforced to support 3,000 lbs, however, this must be specified. All weights listed inTable G-1 are shipping weights. When installed, the water weight must be added to obtain total load to be supported. Use an average addon of 200 lbs. Add the weight of any stack (if unsupported) from the economizer to the outside.

G-6
09-06

Section G
Table G-4. Industrial Watertube Boilers Rectangular Economizer Performance Data
ECONOMIZER MODEL NO. LOAD % WATER SIDE FLOW PPH 15000 31000 51500 63000 TEMPERATURE IN F 225 225 225 225 OUT F 292 292 280 269 PRESS. DROP PSIG 6.8 5.6 8.1 9.9 FLOW PPH 15884 32582 53999 66018 GAS SIDE TEMPERATURE IN F 532 532 498 459 OUT F 318 318 318 318 HEAT PRESS- RECOVERED DROP BTU/HR IN. WC (MAX) 0.75 0.75 0.75 0.75 1237000 2530000 3424000 3260000 HEATING SURFACE SQ-FT 786 1616 2370 2462

D-34 D-52 D-76 D-94

100 100 100 100

NOTES: 1. Feedwater temperature to Economizer is at least 220 F (Deaerated). 2. Boiler operating pressure is 150 psig (acceptable tolerance 5 psig). 3. Gas side flow (pph) determined with 10% excess air. 4. Continuous modulated feedwater must be provided. 5. Data indicated is for select application. Each Economizer is designed on a job to job basis. 6. Boiler is firing natural gas.

Table G-5. Firetube Boiler E+Plus Economizers, Efficiencies (Model CB Boilers)


BOILER HP LOAD % ECONOMIZER MODEL NO. EFF W/0 ECON % FUEL SAVED EFF WITH ECON

Table G-6. Industrial Watertube Boiler Rectangular Economizers, Efficiencies


BOILER MODEL LOAD % FLOW PPH EFF W/O ECON % FUEL SAVED EFF WITH ECON

100 hp 125 hp 150 hp 200 hp 250 hp 300 hp 350 hp 400 hp 500 hp 600 hp 700 hp 800 hp

100 100 100 100 100 100 100 100 100 100 100 100

CBC-16A6AL CBC-18D6AL CBC-18D7AL CBC-18E6AL CBC-30H7AL CBC-30H7AL CBC-30F7AL CBC-36F7AL CBC-36G6AL CBC-36H5AL CBC-36J5AL CBC-36J5AL

82.05 80.76 81.81 82.40 80.87 81.46 82.05 81.89 82.83 83.07 83.30 83.18

2.50 3.84 3.04 2.34 3.52 3.07 2.55 2.84 2.01 1.63 1.54 1.55

84.55 84.6 84.85 84.74 84.39 84.53 84.6 84.73 84.84 84.7 84.84 84.73

D-34 D-52 D-76 D-94

100 100 100 100

15000 31000 51500 63000

77.47 78.07 79.17 80.15

6.3 6.3 5.2 4.1

82.72 83.34 83.54 83.59

NOTES: 1. Feedwater temperature to Economizer is at least 220 F (Deaerated). 2. Savings depend on total design of the system. 3. Data indicated is for select applications. Each Economizer is designed on a job to job basis. 4. Boiler is firing natural gas. 5. Boiler operating pressure is 150 psig (acceptable tolerance 5 psig).

NOTES: 1. Feedwater temperature to Economizer 227 F (Deaerated). 2. Selections are based on best Btu savings per dollar costs. 3. Boiler is firing natural gas. 4. Boiler operating pressure is 125 psig (acceptable tolerance 5 psig). 4. Contact your local Cleaver-Brooks representative for sizing detail.

Although the economizer can support additional weight, the total weight of economizer and stack will very likely exceed the allowable weight on the boiler. Be certain that either the economizer or the stack, or both, are supported external from the boiler. If an expansion joint is used, the economizer and stack must be supported to ensure all loading is removed from the expansion joint.

G-7
09-06

Section G

BOLT SPECIFICATIONS Boiler hp No. of Bolts Bolt Size Bolt Circle Vent Opening (OD) 13-7/8 12 100 8 125-200 12 250-350 12 400-800 16

3/8 - 16 (threads per inch) 17-7/8 16 21-7/8 20 25-7/8 24

NOTES: 1. Dimensions in inches. 2. For allowable weights on vent stub refer to dimensions and weights in this section. 3. For information on stacks refer to Section F.

Figure G-1. E+Plus Economizer Mounting to Firetube Boiler (Model CB Boilers) Refer to Figure G-1 for suggested mounting to a firetube boiler (Model CB & CBLE Boilers).

For information on other Cleaver-Brooks Firetube Boilers, contact your local CleaverBrooks authorized representative. Note: Spool between economizer and boiler may be required to clear front head davit arm (consult factory). Industrial Watertube Boilers Installation - economizer above boiler: Maximum vertical loading of top mounted economizer and stack at the boiler connection must not exceed 2,000 lbs. The stack must be top-guided to prevent any overturning moment at boiler connection. The economizer and stack must be supported to ensure all loading is removed from the expansion joint. All weights listed in Table G-2 are shipping weights. When installed, the water weight must be added to obtain total load to be supported. Water weights will vary and can only be obtained after economizer is selected. Refer to Figure G-2 for suggested mounting above an industrial watertube boiler.

G-8
09-06

Section G

Figure G-2. Economizer Above Industrial Watertube Boiler (Example) Installation - economizer on side of boiler: Breeching must be supported to ensure all loading is removed from expansion joints. Concrete must be suitably reinforced. Piers and footings must be designed to meet soil conditions and local ordinances at job site. The economizer support stand must be designed to support the economizer and water weight. All weights listed in Table G-2 are shipping weights. When installed, the water must be added to obtain total load to be supported. Water weights will vary and can only be obtained after economizer is selected. Refer to Figure G-3 for suggested mounting on side of an industrial watertube boiler.

Feedwater Piping Piping arrangements are dictated by ASME Code, location of the economizer in relation to the boiler, and feedwater regulating system. Figure G-4 outlines typical feedwater piping per ASME Code jurisdiction. If the economizer can be shut off from the boiler by valve(s), the economizer must have a safety valve and the boiler must have feed and check valves. Refer to Figure G-5. Figure G-5 outlines feedwater piping with the economizer mounted above the boiler. Figure G-6 outlines feedwater piping with the economizer mounted and the economizer outlet at or below water level in boiler drums. Figure G-7, Figure G-8, and Figure G-9 outline different feedwater piping arrangements with the economizer mounted above the boiler and with gas and water isolation by-passes.
G-9
09-06

Section G

Figure G-3. Economizer on Side of Industrial Watertube Boiler (Example)

G-10
09-06

Section G

Figure G-4. Typical Economizer Feedwater Piping

REFER TO PRODUCT OFFERING, PAGE G-3.

Figure G-5. Typical Economizer Feedwater Piping

G-11
09-06

Section G

Figure G-6. Typical Economizer Feedwater Piping

Figure G-7. Typical Economizer Feedwater Piping


G-12
09-06

Section G

Figure G-8. Typical Economizer Feedwater Piping

Figure G-9. Typical Economizer Feedwater Piping

G-13
09-06

Section G

Notes

G-14
09-06

Section G
Economizer Sample Specifications E+Plus CBC Cylindrical for Firetube Boilers
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-16 Construction Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-16 Quality Control And Code Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-17

SAMPLE SPECIFICATIONS
The following sample specification is provided by Cleaver- Brooks to assist you in specifying your customers specific needs and application.

G-15
04-02

Section G

PART 1 GENERAL

1.1 GENERAL Specifications for E+Plus cylindrical economizers shall include the furnishing of (__CBC-XXXX) complete packaged, extended surface boiler economizer(s), as furnished by Cleaver-Brooks. 2.1 CONSTRUCTION SPECIFICATIONS A. The economizer's heating surface shall be a multiple circular coil design with manifold for minimum water pressure drop as required: Headers: thickness: Sch80; material: [ ] SA 53 GrB carbon steel or [ ] TP304 stainless steel. Alternate finned tube heating surfaces: [ ] 316L stainless steel tube x .065" minimum wall thickness with aluminum fin x .020" thickness x .50 high brazed to the tube [ ] Carbon steel tube SA 178 ERW GrA x .085" minimum wall thickness with carbon steel fin x .030" thickness x .50 high brazed to the tube [ ] Duplex stainless steel tube x .049" minimum wall thickness with aluminum fin x .020" thickness x .50 high brazed to the tube [ ] 316L stainless steel tube x .065" minimum wall thickness with stainless steel fin x .020" thickness x .50 high brazed to the tube Fins per inch shall be per fuel type fouling requirements. B. The gas tight housing shall consist of a structural reinforced design shell and designed with a 10GA minimum thickness SA36 carbon steel thickness cylindrical lid ([ ] alternate 304 stainless steel). 18GA stainless steel 'gull wing' type access doors shall be provided which can provide for complete access to the heating surface for inspection and/or cleaning. In addition the inspection panels shall be hinged and secured by quick release tension latches requiring no tools to open and close for access to the heating surface. Access doors shall be insulated with 2" thickness of high temperature insulation and shall contain a stainless steel door panel. Customer stack mating flanges and gaskets shall also be provided and designed to match the economizer gas connections. Exterior surfaces other than stainless shall be painted with high temperature paint suitable for exhaust temperatures entering and for outdoor installation. Additional required equipment included shall include: (2) 50-300(F 3" dial bimetallic water thermometers with well, (2) 150-750(F 3" dial adjustable bimetallic flue gas temperature thermometers. (1) 250 PSI ASME safety relief valve. C. Maximum heat transfer performance shall result from counter flow water to the exhaust gas flow, maximizing entering temperature differences. A condensate drain catch ring assembly with 1" NPT drain shall be provided for draining condensation away from the boiler as it could occur either within the economizer and/or economizer outlet stack breaching. The economizer's design shall also include an internal heat resistant design exhaust gas damper, allowing for the reduction of combustion back pressure as required, and/or for controlling exhaust gas temperature exiting, and/or for controlling heat transfer for minimum performance as necessary.

PART 2 PRODUCTS

G-16
09-06

Section G PART 2 PRODUCTS


2.2 SELECTION PARAMETERS Design Requirements Performance design parameters for the economizer are as follows: Primary fuel type: [ ] natural gas [ ] No.2 fuel oil Maximum Firing output rate to the economizer: Exhaust Flow Rate, pph: -Inlet exhaust temperature (f: Cooled exhaust temperature (f: -Pressure drop " W.C. Max.: Water Flow Rate, lbs/hr: -Entering Temp.(f: -HeatedTemp.(f: Press. Drop, psig Heat transferred, MBtu/hr.: QUALITY CONTROL AND CODE REQUIREMENTS A. Economizer is to be designed and fabricated in accordance with the ASME Boiler and Pressure Vessel Code, Section VIII Division I (UM stamp). Options available: [ ] Optional U stamp. [ ] Optional Section I stamp [ ] Optional CRN stamp B. Minimum design temperature is to be 700 F. C. Unit shall be hydrostatically tested at 1.5 times the design pressure in the presence of a Code Inspector. D. Unit is to be ASME Code Stamped, and is to include nameplate and applicable code papers.

PART 3 EXECUTION

3.1

G-17
09-02

Section G

NOTES

G-18
09-06

Section G
Economizer Sample Specifications E+Plus CBR Rectangular for Firetube Boilers
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Construction Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Quality Control And Code Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

SAMPLE SPECIFICATIONS
The following sample specification is provided by Cleaver- Brooks to assist you in specifying your customers specific needs and application.

G-19
09-06

Section G

PART 1 GENERAL

1.1 GENERAL Specifications for E+Plus cylindrical economizers shall include the furnishing of (__CBR-XXXX) complete packaged, extended surface boiler economizer(s), as furnished by Cleaver-Brooks. 2.1 CONSTRUCTION SPECIFICATIONS A. The economizer's heating surface shall consist of finned tubes attached to water manifolds as mounted to the exterior of the shell to minimize corrosion and to achieve low liquid pressure drop. The finned tubes shall be attached with compression fittings to the header manifolds for ease of tube replacement requiring no welding. The finned tube shall have a maximum of 2 rows in the exhaust stream in order to achieve visual access of the heating surface and effective cleaning when needed. The finned tubes shall not have any tube to tube welds in the exhaust flow for extended economizer life: Header manifold: thickness: Sch80; material: [ ] SA 53 GrB carbon steel or [ ] TP304 stainless steel. Alternate finned tube heating surfaces: [ ] 316L stainless steel tube x .065" minimum wall thickness with aluminum fin x .020" thickness x .50 high brazed to the tube [ ] Carbon steel tube SA 178 ERW GrA x .085" minimum wall thickness with carbon steel fin x .030" thickness x .50 high brazed to the tube [ ] Duplex stainless steel tube x .049" minimum wall thickness with aluminum fin x .020" thickness x .50 high brazed to the tube [ ] 316L stainless steel tube x .065" minimum wall thickness with stainless steel fin x .020" thickness x .50 high brazed to the tube Fins per inch shall be per fuel type fouling requirements. B. The gas tight housing shall consist of a structural reinforced design exterior and designed with a 10GA minimum thickness SA36 carbon steel thickness ([ ] alternate 304 stainless steel). A hinged access door shall be provided which can provide for complete access to the heating surface for inspection, cleaning, or tube removal. The economizer shall be insulated with 2" thickness of high temperature insulation and shall be lined with 304 stainless steel. A pair of stack adapters and gaskets shall also be provided to connect the economizer flanged exhaust connections with the boiler exhaust diameter size for slip fit connection. C. Exterior surfaces other than stainless shall be painted with high temperature paint suitable for exhaust temperatures entering and for outdoor installation. Additional required equipment included shall include: (2) 50-300(F 3" dial bimetallic water thermometers with well, (2) 150-750(F 3" dial adjustable bimetallic flue gas temperature thermometers, (1) 250 PSI ASME safety relief valve.

PART 2 PRODUCTS

G-20
09-06

Section G
D. Maximum heat transfer performance shall result from counter flow water to the exhaust gas flow, maximizing entering temperature differences. A condensate drain catch ring assembly with 1" NPT drain shall be provided for draining condensation away from the boiler as it could occur either within the economizer and/or economizer outlet stack breaching. The economizer's design shall also include an internal heat resistant design exhaust gas damper, allowing for the reduction of combustion back pressure as required, and/or for controlling exhaust gas temperature exiting, and/or for controlling heat transfer for minimum performance as necessary.

PART 2 PRODUCTS

2.2

SELECTION PARAMETERS Performance design parameters for the economizer are as follows: Primary fuel type: [ ] natural gas [ ] No.2 fuel oil Maximum Firing output rate to the economizer: Exhaust Flow Rate, pph: -Inlet exhaust temperature (F: Cooled exhaust temperature (F: -Pressure drop " W.C. Max.: Water Flow Rate, lbs/hr: -Entering Temp.(F: -Heated Temp.(F: Press. Drop, PSIG Heat transferred, MBtu/hr.:

PART 3 EXECUTION

3.1

QUALITY CONTROL AND CODE REQUIREMENTS A. Economizer is to be designed and fabricated in accordance with the ASME Boiler and Pressure Vessel Code, Section VIII Division I (UM stamp). Options available: [ ] Optional U stamp. [ ] Optional Section I stamp [ ] Optional CRN stamp B. Minimum design temperature is to be 700 F. C. Unit shall be hydrostatically tested at 1.5 times the design pressure in the presence of a Code Inspector. D. Unit is to be ASME Code Stamped, and is to include nameplate and applicable code papers.

G-21
09-06

Section G

NOTES

G-22
09-06

Section G
Economizer Sample Specifications for Watertube Boilers
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Construction Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Quality Control And Code Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

SAMPLE SPECIFICATIONS
The following sample specification is provided by Cleaver- Brooks to assist you in specifying your customers specific needs and application.

G-23
09-06

Section G

PART 1 GENERAL

1.1

GENERAL A. Specifications for Boilermate cylindrical and rectangular economizers shall include the furnishing of (___________) complete packaged, extended surface boiler economizer(s), as furnished by Cleaver-Brooks. CONSTRUCTION SPECIFICATIONS A. 1.0 General Specifications for Boilermate cylindrical and rectangular economizers shall include the furnishing of (___________) complete packaged, extended surface boiler economizer(s), as furnished by Cleaver-Brooks. B. Common Construction Specifications Tube material is to be SA-178-A boiler tube. Extended surface is to be of solid, continuous, high- frequency, resistance welded carbon steel fins. Serrated fins are not acceptable. Tube arrangement is to be square pitch only. Triangular or staggered tube pitch will not be acceptable. Inner casing is to be a minimum of 10-gauge carbon steel. Insulation type is to be mineral wool. Outer casing is to be weather-proof with a minimum 27- gauge, corrugated, galvanized, carbon steel casing. All exposed surfaces not enclosed by the outer casing are to be painted with high-temperature paint. The economizer shall be completely drainable by gravity, after installation. Safety valve to be supplied. C. 3.0 Specifications Specific To Cylindrical Economizers The economizer shall be of the cylindrical design. Fins are to be not less than .060" thick. The economizer shall be equipped with a built-in sootblower and shall utilize lane blowing to provide maximum cleaning capabilities. Longitudinal or mass blowing shall not be acceptable. For economizers used on boilers which have an on/off type feedwater control system, a modulating feedwater system shall be incorporated into the system to ensure proper economizer operation. D. Specifications Specific To Rectangular Economizers Tubes are to be commercially available 2" OD. Fins are to be not less than .075" thick. Tube sheets are to be of the open lattice design. Tube walls (pressure parts) shall not be in contact with tube sheets. The fins shall rest on the tube sheet. Sootblower wall boxes and distal bearings shall be included and are to be installed on the economizer by the vendor. Sootblowers shall be installed

PART 2 PRODUCTS

2.1

G-24
09-06

Section G
(when specified) transversely to provide maximum cleaning capabilities. Longitudinal or mass blowing shall not be acceptable. An insulated access door of carbon steel construction, 16" square inside-toinside, shall be included in the economizer design. E. Quality Control And Code Requirements Economizer is to be designed and fabricated in accordance with the ASME Boiler and Pressure Vessel Code, Section I, Power Boilers. Minimum design temperature is to be 700 F. Unit shall be hydrostatically tested at 1.5 times the design pressure in the presence of a Code Inspector. Unit is to be ASME Code Stamped, and is to include nameplate and applicable code papers. QUALITY CONTROL AND CODE REQUIREMENTS A. Economizer is to be designed and fabricated in accordance with the ASME Boiler and Pressure Vessel Code, Section VIII Division I (UM stamp), Power Boilers. B. Minimum design temperature is to be 700 F. C. Unit shall be hydrostatically tested at 1.5 times the design pressure in the presence of a Code Inspector. D. Unit is to be ASME Code Stamped, and is to include nameplate and applicable code papers.

PART 3 EXECUTION

3.1

G-25
09-06

Section G

NOTES

G-26
09-06