Documente Academic
Documente Profesional
Documente Cultură
Output Ratings
Generating Set Model 220-240V, 50 Hz Prime* 45.0 kVA 45.0 kW 240/120V, 60 Hz 50.0 kVA 50.0 kW * Refer to ratings definitions on page 4. Ratings at 1.0 power factor. Standby* 50.0 kVA 50.0 kW 55.0 kVA 55.0 kW
Technical Data
Engine Make & Model: Alternator Model: Base Frame Type: Circuit Breaker Type: Frequency: Engine Speed: RPM Fuel Tank Capacity: litres (US gal) Fuel Consumption, Prime: l/hr (US gal/hr) Fuel Consumption, Standby : l/hr (US gal/hr) 13.8 (3.6) 15.6 (4.1) Perkins 1103A-33TG2 LL2014J Fbc2 - (08Hr) 3 Pole MCCB 50 Hz 1500 219 (57.9) 15.8 (4.2) 17.7 (4.7) 60 Hz 1800
Lubrication system
Oil Filter Type: Total Oil Capacity l (US gal): Oil Pan l (US gal): Oil Type: Cooling Method: Spin-On, Full Flow 8.3 (2.2) 7.8 (2.1) API CG4 / CH4 15W-40 Water
Performance
Engine Speed: RPM Gross Engine Power: kW (hp) -Standby: -Prime: BMEP: kPa (psi) -Standby: -Prime: Regenerative Power: kW
50 Hz
1500 60.5 (81.0) 55.0 (74.0)
60 Hz
1800 69.6 (93.0) 63.3 (85.0)
1467.0 (212.8) 1407.0 (204.0) 1333.0 (193.4) 1279.0 (185.5) 7.0 9.0
Fuel System
Fuel Filter Type: Replaceable Element Recommended Fuel: 110% Load Prime 50 Hz 60 Hz Standby 50 Hz 60 Hz 15.6 (4.1) 17.7 (4.7) 11.3 (3.0) 12.1 (3.2) 7.8 (2.1) 9.2 (2.4) 15.6 (4.1) 17.7 (4.7) 13.8 (3.6) 15.8 (4.2) 10.2 (2.7) 11.8 (3.1) 7.1 (1.9) 8.6 (2.3) Class A2 Diesel Fuel Consumption: l/hr (US gal/hr) 100% Load 75% Load 50% Load
Air System
Air Filter Type: Combustion Air Flow: m/min (cfm) -Standby: -Prime: Max. Combustion Air Intake Restriction: kPa (in H2O) Radiator Cooling Air Flow: m/min (cfm) External Restriction to Cooling Air Flow: Pa (in H2O)
50 Hz
Replaceable Element 3.9 (138) 3.8 (134) 8.0 (32.1)
60 Hz
(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)
Cooling System
Cooling System Capacity: l (US gal) Water Pump Type: Heat Rejected to Water & Lube Oil: kW (Btu/min) -Standby: -Prime: Heat Radiation to Room: kW (Btu/min) -Standby: -Prime: Radiator Fan Load: kW (hp)
50 Hz
10.2 (2.7)
60 Hz
10.2 (2.7)
Exhaust System
Silencer Type: Silencer Noise Reduction Pressure Drop Across Silencer System: kPa (in Hg) Silencer Noise Reduction
50 Hz
60 Hz
Industrial SD80 (1) 0.98 (0.289) 1.22 (0.360) 19 10.0 (3.0) 10.4 (367) 10.1 (357) 571 (1060) 557 (1035) 18 15.0 (4.4) 12.5 (441) 11.8 (417) 564 (1047) 534 (993)
Centrifugal
37.7 (2144) 35.2 (2002) 11.0 (626) 10.0 (569) 1.0 (1.3)
42.8 (2434) 41.0 (2332) 12.0 (682) 11.0 (626) 1.7 (2.3)
Level: dB Max. Allowable Back Pressure: kPa (in. Hg) Exhaust Gas Flow: m/min (cfm) -Standby: -Prime: Exhaust Gas Temperature: C (F) m/min (cfm) -Standby: -Prime:
Cooling system designed to operate in ambient conditions up to 50C (122F). Contact your local Olympian dealer for power ratings at specific site conditions.
60 Hz
162
153
144
127
143
Xd X'd X''d
Reactances shown are applicable to standby ratings. * Based on 30% voltage dip. ** With optional Permanent Magnet generator or AREP excitation.
Operating Data
Overspeed: RPM Voltage Regulation (steady state) (%): Wave Form NEMA = TIF: Wave Form IEC = THF: Total Harmonic Content LL/LN: Radio Interference: 2250 +/- 0.5 50 2.0% 4.0%
Radiant Heat: kW (Btu/min) -50 Hz: -60 Hz: 9.4 (535) 11.9 (677)
Technical Data
Voltage
kVA
240V 230V 220V 45.0 45.0 45.0
Prime
kW
45.0 45.0 45.0
Standby
kVA
50.0 50.0 49.7
Voltage
kW
50.0 50.0 49.7
Prime
kVA kW
Standby
kVA kW
220V/110V 240V/120V
49.0 50.0
49.0 50.0
53.9 55.0
53.9 55.0
Dimensions: mm (in)
Length Width Height 1925 (75.8) 1120 (44.1) 1361 (53.6)
Note: General con guration not to be used for installation. See general dimension drawings for detail.
Definitions
Standby Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as de ned in ISO 8528-3).
General Data
Documents
A full set of operation and maintenance manuals and circuit wiring diagrams.
Quality Standards
BS4999, BS5000, BSEN60034, BSEN61000, IEC60034.
Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
Warranty
All equipment carries full manufacturer's warranty.
Information contained in this publication may be considered con dential. Discretion is recommended when distributing. Materials and speci cations are subject to change without notice. CAT, CATERPILLAR, their respective logos OLYMPIAN, ''Caterpillar Yellow'' and the "Power Edge" trade dress, as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.