Vacuum Interrupter
Leader in Electrics & Automation
For your safety, please read user's manual thoroughly before operating. Contact the nearest authorized service facility for examination, repair, or adjustment. Please contact qualified service technician when you need maintenance. Do not disassemble or repair by yourself!
Safety Instructions
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
Electric Equipment
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.
2003. 12
Structure
The internal components of a typical vacuum Interrupter are shown in Figure1. LG Vacuum Interrupter consists of a ceramic insulator, two end plates, arc shield, bellows, a movable and fixed electrode, and contact set. The ambient gas pressure within the evacuated tube is approximately 10-6 torr.
Features
Small Size and Light Weight High performance, reliability, and long life are assured. Maintains High Vacuum High-alumina ceramics provide superior mechanical strength and easy degassing. High speed interruption and short arcing time. The LG Vacuum Interrupter can meet all IEC, ANSI and NEMA performance standards.
Movable electrode
Current path
Bellows
In the closed position, normal current flows through the interrupter. When a fault occurs and interruption is required, the contacts are quickly separated. The arc drawn between the surfaces of contacts is rapidly moved around the slotted contact surface by selfinduced magnetic effects, preventing gross contact erosion and the formation of hot spot on the surface. The arc burns in an ionized metal vapor, which condenses on the surrounding metal shield. At current zero the arc extinguishes and vapor production ceases. The metal vapor plasma is very rapidly dispersed, cooled, recombined, and deionized, and the metal vapor products are quickly condensed so that the contacts withstand the transient recovery voltage.
Bellows shield
() Weld () Bridge explosion () Contact jets () Shield involvement () Arc instability () Interruption
Ceramic
ARC shield
Arc initiation
Current zero
Contact
Recovery voltage
Fixed electrode
Figure 1. Vacuum Interrupter Schematic
Outer view
Rated voltage (kV) Rated power frequency withstand voltage (kV, rms) Rated impulse withstand voltage (kV, crest) Electrical ratings Rated frequency (Hz) Rated normal current (Amp) Rated short circuit current (Sym.) (kA) Rated short circuit making current (kA, peak) Rated duration of short-circuit (sec) Interrupter weight (kg) Moving part weight (kg) Mechanical data Outline dimension (mm) a b c Contact stroke (mm) Opening speed, average 0 to 90% of full stroke (m/s) Overtravel during opening, Max. (mm) Closing speed, average last 20% of full stroke (m/s) Mechanical requirements Contact bounce duration, Max. (sec) Added force from atmospheric pressure (kgf) Contact force from atmospheric pressure (kgf) Contact erosion limit (mm) Mechanical life (Operations)
3.6 11.5 60 50/60 400 4.5 0.48 0.19 114 78 62 3 0.6 1 0.3 0.002 5 9 1 100
7.2 20
7.2 20 60 50/60 630 12.5 32 3 0.85 0.4 132 102 62 6 0.71.0 2 0.71.0 0.002 80 9.1 3 3
7.2 20 60
12 28 95 50/60 1,250
15 36
7.2 20 60
12 28 95 50/60 2,000
15 36
7.2 12 20 28 60
12 17.5 7.2 12 36 95 50 20 60 28
15 17.5 36 50 95
25.8
24
25.8 50 125 50/60 3,150 31.5 79 3 6.1 1.7 272 213 135 17 1.01.3 1.5 1.01.3 0.002 306 25 3 1 SF6 Gas
50/60 3,150 40 100 3 6.05 1.7 247(272) 213 135 12 8 1.0 3 0.71.0 0.002 367 26 3 12 1.2 1.5
20 50
12
1.01.3 0.71.0 2
154
227 16.8 3
Dimensions
LV-07040 LV-07080B LV-07130 LV-07312A LV-07403B LV-24121A
LV-07201
LV-07251
LV-07252
LV-24252A
LV-25313
Ordering Information LV 07 08 0 A
Basic Type L LG
Revision No.
Vacuum V Interrupter
Rated Short Circuit Current 04 4.5kA 08 8kA 12 12.5kA 20 20kA 25 25kA 31 31.5kA 40 40kA