Documente Academic
Documente Profesional
Documente Cultură
MEMORIA DE CLCULO
SALA DE CELDAS Y CONTROL
Documento N
23680-A4
Rev. 0
NUEVASUBESTACINMARISCAL
110/2312KV
CONTRATISTA
DOCUMENTO
Elabor
Revis
Aprob
Nombre
Fecha
Eleconsult
31-08-2010
Firma
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
LISTA DE DISTRIBUCIN
Margarita Fernndez - Karla Matteo
Margarita Fernndez - Karla Matteo
Jorge Latife A.
CGE Transmisin
Dise
Ejecut
Revis
Aprob
Fecha
31-08-2010
Pginas
28
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 2 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
TABLA DE CONTENIDOS
1.
1.1
2.
2.1
2.2
2.3
2.4
2.5
2.6
2.7
3.
4.
4.1
4.2
4.3
5.
GENERAL ............................................................................................................................................. 4
ALCANCE ............................................................................................................................................. 4
BASES DE DISEO.............................................................................................................................. 4
NORMAS Y DOCUMENTOS APLICADOS .......................................................................................... 4
MATERIALES ....................................................................................................................................... 5
SOLICITACIONES ................................................................................................................................ 5
SUELO .................................................................................................................................................. 7
DEFORMACIONES ADMISIBLES (CUBIERTA) ................................................................................. 7
COMBINACIONES DE CARGA ........................................................................................................... 7
ESTRUCTURACIN ............................................................................................................................. 9
ESQUEMA ........................................................................................................................................... 10
CLCULO ESTRUCTURAL ............................................................................................................... 11
CALCULO DE LAS COSTANERAS Y CERCHAS ............................................................................ 11
VERIFICACIN DE MUROS .............................................................................................................. 14
CLCULO DE FUNDACIONES .......................................................................................................... 26
CONCLUSIONES ................................................................................................................................ 27
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 3 de 28
1.
GENERAL
1.1
ALCANCE
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
La presente memoria de clculo se refiere al anlisis, diseo y clculo de la Sala de Celdas y Control a
instalar en la S/E Mariscal, correspondiente al proyecto Nueva Subestacin Mariscal 110/23-12 kV en la
Subestacin Mariscal, propiedad de CGET.
De acuerdo a lo indicado por CGET, se permite utilizar la memoria de clculo ejecutada para el proyecto
Nueva S/E Padre Hurtado 110/23 kV, debido a que la Sala de Control a instalar en S/E Mariscal es idntica
a la instalada en S/E Padre Hurtado, en trminos de materialidad, dimensiones, calidad del suelo de
fundacin, etc., mientras que para el caso de la Sala de Celdas, en S/E Mariscal esta crece en 12 metros,
manteniendo el ancho de muros entre pilares, considerado para S/E Padre Hurtado.
Es por ello que a continuacin, se desarrolla la Memoria de Clculo entregada para el proyecto de S/E Padre
Hurtado, para finalmente concluir por qu se puede reutilizar el presente documento para el proyecto de S/E
Mariscal.
La Sala de Control est estructurada en muros de albailera confinados con cadenas de hormign armado
La superficie en planta de la sala de celdas y control, para el caso de S/E Padre Hurtado es
aproximadamente 228 m2. Esta rea considera la sala en una primera etapa, ya que se estima un
crecimiento futuro. Asimismo, en el caso de S/E Mariscal, la superficie aproximada de laSala de Celdas y de
Control es aproximadamente 304 m2.
La estructura de techo est definida en base a perfiles metlicos tipo canales para las costaneras y
elementos de las cerchas, adems se consideran colgadores longitudinales para arriostrar estos elementos.
Las Fundaciones sern del tipo zapata corrida, delimitadas bajo los muros de la sala. La sala considera una
canaleta de cables, una de las paredes de esta canaleta mantiene el mismo eje de uno de los muros de la
sala.
2.
BASES DE DISEO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 4 de 28
ACI 3185-05
ASD-AISC
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
2.2 MATERIALES
Hormign
Acero de refuerzo
Acero Estructural
2.3 SOLICITACIONES
a)
b)
Techo: 100 Kg./m2. La cual deber ser reducida de acuerdo a los factores por pendiente y rea
tributaria. Debe ser mayor o igual a 30 Kg/m2.
c)
d)
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 5 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Q CIP
En que:
0.05
0.4
: Aceleracin efectiva.
: Razn de amortiguamiento.
Segn la Nch 2369 el factor ssmico C puede obtener su valor mximo segn la tabla 5.7, la
cual depender del factor R de la tabla 5.6 y de la razn de amortiguamiento segn la tabla 5.6.
Para hormign armado R=4 y la razn de amortiguamiento es 0.05, Por lo tanto el valor mximo
para el C es igual a 0.17.
Para determinar los las fuerzas horizontales producto del sismo se utilizara el anlisis esttico.
La determinacin de las fuerzas ssmicas de deben distribuir en la altura segn la expresin
siguiente:
Fk
Ak Pk
AP
n
Ak 1
Z k 1
Z
1 k
H
H
Donde:
Fk
Pk , Pj
Ak
j.
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 6 de 28
: Numero de niveles
Q0
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
No aplica al sector
2.4 SUELO
Segn informe de Mecnica de Suelos entregado por CGET, los parmetros de diseos para las
fundaciones son los siguientes:
= 2,00 ton/m,
ADM(e)
= 4.5 kg/cm,
ADM(n)
= 3 kg/cm,
Combinaciones eventuales
PP+V
PP+0.75V+0.75N
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 7 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
PP+0.75V+0.75SCr
0.6PP+V
En que:
PP
SCr
N
V
b) Hormign armado:
Combinaciones normales:
1.4PP
1.2PP+1.6N
1.2PP+1.6SCr
Combinaciones eventuales:
1.2PP+1.6SCr+0.8V
1.2PP+1.6N+0.8V
1.2PP+1.6V+0.5SCr
1.2PP+1.6V+0.5N
1.2PP+1.4(Sx o Sy)+0.2N+1.4Mt
0.9PP+1.6V
0.9PP+1.4(Sx O Sy)
En que:
PP
SCr
Sx
Sz
N
Mt
V
c) Albaileras:
Combinaciones normales:
PP+SC
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 8 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Combinaciones eventuales:
PP+V
PP+ Sx o Sz+Mt
En que:
PP
SC
Sx
Sz
Mt
V
2.7 ESTRUCTURACIN
La estructura transversal existente esta compuesta por muros de albailera confinada de 15 cm de espesor.
Los muros sern modelados estructuralmente mediante placas de elementos finitos. Las cargas admisibles
de los muros quedaran determinadas en base a la norma NCh 2123 of07.
La estructura de techo estar compuesta por costaneras y cerchas en base a perfiles metlicos, que sern
fijadas a las cadenas de hormign armado. Las cerchas son diseadas en base a las cargas resultantes del
anlisis estructural.
La sala ser proyectada considerando una ampliacin futura, para lo cual cuenta con dos muros perimetrales
en base a perfiles livianos tipo Metalcon, Estos muros no sern considerados en al anlisis estructural
desarrollado mas adelante.
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 9 de 28
3.
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
ESQUEMA
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 10 de 28
4.
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
CLCULO ESTRUCTURAL
2m
1.1 m
2.2 m
11.3 Kg/m
13.5 Kg/m
7850 Kg/m
Sobrecarga
Sobrecarga de techo (SCr):
100 Kg/m
70
CC=1-2.33 tan():
Reduccion por area:
Area tributaria:
A>50 m => CA:
q_red=CC*CA*q:
17
0.29
0.6
30.000 Kg/m
33.000 Kg/m
Viento (W) :
Presion Basica (Pb):
70 Kg/m
C1=1.2sen 0.4:
C2:
q1:
q2:
q1:
q2:
17
0.049
0.4
3.441
28
3.7849
30.8
empuje
succion
Kg/m
Kg/m
Kg/m
Kg/m
empuje
succion
empuje
succion
100 Kg
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 11 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
H=
b=
e=
fluencia=
Area=
150
50
4
253.1
10.01
mm
mm
mm
Mpa
cm2
ia=
it=
wx=
wy=
Ix=
Iy=
2.21
0.133
51
13.9
316
27.5
cm
cm
cm3
cm3
cm4
cm4
parametro alabeo
parametro torsion
modulo resistente x
modulo resistente y
Inercia en x
Inercia en y
Seccin esbelta:
Lm<Lc, considerando un colgador en el centro de cada vano => por lo tanto no existe PLT
Los mximos momentos ocurren para la combinacin que contiene la accin del peso propio y la carga de
montaje (CM+M)
Impresin de diagramas de esfuerzos:
Estados considerados:
C11=CM+M
MIEMBRO
Material
:
:
1
A36
Largo
Seccin
:
:
2.000 [m]
CA 150x50x20x4
Nudo J
Nudo K
:
:
1
2
:
:
2
3
Estado: C11=CM+M
Momentos flectores M33
Momentos [Kg*m], Long [m]
MIEMBRO
Material
:
:
2
A36
Largo
Seccin
:
:
2.000 [m]
CA 150x50x20x4
Nudo J
Nudo K
Estado: C11=CM+M
Momentos flectores M33
Momentos [Kg*m], Long [m]
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 12 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Momento resistente:
M33r=0.6*2531*51*0.9 = 697.03 kgm > 37.14 kgm OK
M22r=0.6*2531*13.9*0.9 = 189.9 kgm > 31.37 kgm OK
A continuacin se presenta un esquema de la cercha utilizada para el diseo:
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 13 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
La combinacin que controla el diseo corresponde a la que contiene la accin conjunta del peso propio y la
sobrecarga de techo:
Diagonal 2L30x30x3:
I3=0.89cm
I2=0.58cm
A=1.74cm2 K=1
=1*50/0.58=86.2 elemento 6
e= 128 Fa=1040.9kg/cm2
Padm=2*1811.3 kg>199.25 Ok
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 14 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 15 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Espesor
Masa ssmica:
Masa ssmica:
P ssmico =142855.9 kg.
Coeficiente ssmico mximo segn NCh 2369, considerando los siguientes parmetros:
R= 4
=0.05
C=0.17
(Estructura de Hormign)
(Amortiguamiento)
Q=CIP=0.17*1.2*142855.9 = 29142.60 kg
Ya que se considera la parte superior como diafragma rgido (envergadura y
arriostramientos del techo), se consideran los momentos de torsin producto de la
excentricidad accidental:
ex=0.1* bkx* Zk/H sismo X
ez=0.1* bkz* Zk/H sismo Z
bkx: dimensin en la direccin de X, de la planta del nivel k
bkz: dimensin en la direccin de Z, de la planta del nivel k
Zk: altura del nivel k, sobre el nivel basal.
H: altura total de la estructura
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 16 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Mx=Q*ez=29142.6*1.56=45462.4 kgm.
Mz=Q*ex=29142.6*2=58285.2 kgm.
Verificacin muros de albailera:
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 17 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
15
400
26
5.1
0.70
cm
cm
Kg/cm2
Kg/cm2
Seccion 1
sismo z
Muro
M(Kgcm) Na(Kg)
Va(Kg)
FU_Va As req(cm)
S1-S7
290
610.47
245.02
2656.27
1900.44
31835.56
Ok
6825.50
Ok
0.3892
S2-S8
300
16.93
-98.56
2443.56
1442.61
32933.33
Ok
7004.67
Ok
0.3488
0.0186
0.0117
S3-S9
300
115.06
-91.28
2741.92
1093.15
32933.33
Ok
7005.84
Ok
0.3914
0.0103
S4-S10
300
102.9
18.08
2424.98
1481.91
32933.33
Ok
7023.29
Ok
0.3453
0.0012
S65-S63
250
117.05
-372.17
998.47
1302.82
27444.44
Ok
5790.94
Ok
0.1724
0.0372
0.0224
S66-S64
250
130.89
-214.4
823.98
1168.35
27444.44
Ok
5816.12
Ok
0.1417
S6-S12
300
620.02
270.74
2532.97
1968.38
32933.33
Ok
7063.62
Ok
0.3586
0.0208
S21-S22
290
358.29
-101.69
2249.87
1129.8
31835.56
Ok
6770.16
Ok
0.3323
0.0115
S23-S24
300
-83.39
-295.87
1306.59
1824.31
32933.33
Ok
6973.18
Ok
0.1874
0.0303
S25-S26
300
-9.24
-264.17
2275.48
1338.78
32933.33
Ok
6978.24
Ok
0.3261
0.0265
S27-S28
300
553.91
475.85
1762.48
1359.86
32933.33
Ok
7096.35
Ok
0.2484
0.0406
S58-S60
400
589.87
534.18
3438.3
1062.86
43911.11
Ok
9445.80
Ok
0.364
0.0461
S59-S61
400
507.57
447.95
2577
801.16
43911.11
Ok
9432.03
Ok
0.2732
0.0388
15
2.6
26
5.1
1.00
cm
cm
Kg/cm2
Kg/cm2
Seccion 2
sismo z
Muro
M(Kgcm) Na(Kg)
Va(Kg)
FU_Va As req(cm)
S39
265
429.73
45.62
1792.99
635.34
41340.00
Ok
6208.64
Ok
0.2888
0.0028
S41
160
-64390
-123.03
447.83
179.65
24960.00
Ok
3724.58
Ok
0.1202
0.0126
S42
215
132.52
92.61
984.5
808.26
33540.00
Ok
5046.07
Ok
0.1951
0.0065
S62
215
-127.37
-167.89
1103.05
664.75
33540.00
Ok
5004.50
Ok
0.2204
0.0175
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 18 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
sismo x
Muro
M(Kgcm) Na(Kg)
Va(Kg)
FU_Va As req(cm)
S36
195
-21.28
-199.81
443.17
210.56
30420.00
Ok
4531.37
Ok
0.0978
S37
195
-179.92
-305.94
605.64
179.21
30420.00
Ok
4514.44
Ok
0.1342
0.0195
0.0294
S43
320
47.39
-33.96
177.9
712.64
49920.00
Ok
7483.01
Ok
0.0238
0.0043
S44
200
-72.21
-103.71
71.45
191.1
31200.00
Ok
4663.72
Ok
0.0153
0.0103
S46
170
-174.84
-268.46
434.86
101.67
26520.00
Ok
3935.38
Ok
0.1105
0.0261
S48
200
-100.7
-264.7
279.05
173.79
31200.00
Ok
4638.02
Ok
0.0602
0.0254
Combinaciones de servicio
C1 CM+SC
C2 CM+SC+SX+Mtx
C3 CM+SC+SX-Mtx
C4 CM+SC+SZ+Mtz
C5 CM+SC+SZ-Mtz
C6 CM+SX+Mtx
C7 CM+SX-Mtx
C8 CM+SZ+Mtz
C9 CM+SZ-Mtz
ARCHIVO
CDIGO
23680-A4
Combinaciones mayoradas
C10 1.4CM
C11 1.2CM+1.6SC
C12 1.2CM+SC+1.4SX+1.4Mtx
C13 1.2CM+SC+1.4SX-1.4Mtx
C14 1.2CM+SC+1.4SZ+1.4Mtz
C15 1.2CM+SC+1.4SZ-1.4Mtz
C16 0.9CM+1.4SX+1.4Mtx
C17 0.9CM+1.4SX-1.4Mtx
C18 0.9CM+1.4SZ+1.4Mtz
C19 0.9CM+1.4SZ-1.4Mtz
FECHA
31 Agosto 2010
Pgina 19 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Segmento
Estado
S49 (1)
C16 (Mximo)
-15207.90
-7388.25
16782.45
0.44
S13 (2)
C16 (Abajo)
-6379.42
-7045.53
20348.39
0.35
S14 (3)
C12 (Abajo)
-1072.94
-2838.46
22491.75
0.13
------------------------------------------------------------------------------------------------------------------------------------------------------Diagramas de interaccin, P vs. M:
Corte
Vu
*Vn
Vu/*Vn
[Kg]
[Kg]
-------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S49 (1)
C16 (Mximo)
2619.312
28956.135
0.09
S13 (2)
C16 (Arriba)
2884.960
30591.456
0.09
S14 (3)
C16 (Mximo)
2850.290
30780.109
0.09
------------------------------------------------------------------------------------------------------------------------------------Notas:
* Pu = Carga axial
* Pn = Carga axial nominal
* Mu = Momento en la seccin
* Mn = Mximo momento nominal
* Vu = Fuerza de corte de diseo
* Vn = Fuerza de corte nominal
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 20 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Muro S51-S15-S16:
Flexin axial combinada, considerando 1212@20 y estribos 8@20
Pu
Mu
*Mn
Mu/*Mn
[Kg]
[Kg*m]
[Kg*m]
-------------------------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S51(1)
C16 (Mximo)
-21073.19
-7751.02
14131.96
0.55
S15(2)
C16 (Abajo)
-6764.95
-8991.46
20192.67
0.45
S16(3)
C12 (Abajo)
-323.53
-3902.92
22794.45
0.17
------------------------------------------------------------------------------------------------------------------------------------------------------Diagramas de interaccin, P vs. M:
Corte
Vu
*Vn
Vu/*Vn
[Kg]
[Kg]
-------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S51(1)
C16 (Mximo)
2776.487
28076.342
0.10
S15(2)
C16 (Abajo)
3396.489
30222.578
0.11
S16(3)
C16 (Mximo)
3398.832
30847.232
0.11
-------------------------------------------------------------------------------------------------------------------------------------
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 21 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Muro S52-S17-S18:
Flexin axial combinada, considerando 1212@20 y estribos 8@20
Pu
Mu
*Mn
Mu/*Mn
[Kg]
[Kg*m]
[Kg*m]
-------------------------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S52(1)
C17 (Abajo)
-11187.93
-9981.59
18406.17
0.54
S17(2)
C17 (Abajo)
-6581.48
-7556.52
20266.78
0.37
S18(3)
C17 (Abajo)
-857.33
-3338.65
22578.84
0.15
------------------------------------------------------------------------------------------------------------------------------------------------------Diagramas de interaccin, P vs. M:
Corte
Vu
*Vn
Vu/*Vn
[Kg]
[Kg]
-------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S52(1)
C17 (Mximo)
3515.093
29474.158
0.12
S17(2)
C17 (Mximo)
3023.655
30347.809
0.10
S18(3)
C17 (Mximo)
3032.403
30886.368
0.10
-------------------------------------------------------------------------------------------------------------------------------------
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 22 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Muro S53-S19-S61:
Flexin axial combinada, considerando 1212@20 y estribos 8@20
Pu
Mu
*Mn
Mu/*Mn
[Kg]
[Kg*m]
[Kg*m]
-------------------------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S53(1)
C17 (Mximo)
-19734.18
-11697.99
14749.46
0.79
S19(2)
C17 (Abajo)
-7837.57
-10497.04
19759.43
0.53
S20(3)
C13 (Abajo)
-1238.13
-4207.96
22425.03
0.19
------------------------------------------------------------------------------------------------------------------------------------------------------Diagramas de interaccin, P vs. M:
Corte
Vu
*Vn
Vu/*Vn
[Kg]
[Kg]
-------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S53(1)
C17 (Mximo)
3658.447
28277.193
0.13
S19(2)
C17 (Mximo)
3930.433
30158.502
0.13
S20(3)
C17 (Mximo)
3922.387
30729.503
0.13
-------------------------------------------------------------------------------------------------------------------------------------
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 23 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Muro S31-S32:
Flexin axial combinada, considerando 1212@20 y estribos 8@20
Pu
Mu
*Mn
Mu/*Mn
[Kg]
[Kg*m]
[Kg*m]
-------------------------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S31(1)
C16 (Abajo)
21916.47
-18705.32
30831.81
0.61
S32(2)
C16 (Abajo)
6614.29
-7205.22
25437.65
0.28
------------------------------------------------------------------------------------------------------------------------------------------------------Diagramas de interaccin, P vs. M:
Corte
Vu
*Vn
Vu/*Vn
[Kg]
[Kg]
-------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S31(1)
C12 (Arriba)
7509.127
33470.128
0.22
S32(2)
C12 (Mximo)
8178.102
32499.085
0.25
-------------------------------------------------------------------------------------------------------------------------------------
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 24 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Muro S33-S34:
Flexin axial combinada, considerando 1212@20 y estribos 8@20
Pu
Mu
*Mn
Mu/*Mn
[Kg]
[Kg*m]
[Kg*m]
-------------------------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S33(1)
C16 (Abajo)
26096.51
-20293.29
32142.30
0.63
S34(2)
C16 (Abajo)
7971.29
-7860.13
25916.01
0.30
------------------------------------------------------------------------------------------------------------------------------------------------------Diagramas de interaccin, P vs. M:
Corte
Vu
*Vn
Vu/*Vn
[Kg]
[Kg]
-------------------------------------------------------------------------------------------------------------------------------------
Segmento
Estado
S33(1)
C12 (Arriba)
8533.038
33935.183
0.25
S34(2)
C12 (Mximo)
9305.778
32760.937
0.28
-------------------------------------------------------------------------------------------------------------------------------------
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 25 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
Los esfuerzos obtenidos para el diseo de fundaciones, a partir de la modelacin de la estructura, fueron:
Nmax=5313.71 Kg
Comb 3.
Mmax= 302.7(1)+255.22= 557.9 kg m
e(m)= Mmax/ Nmax=0.104<L/6=0.1666m
rea contacto = 100 x 60 = 6000 cm2
b = 1,0 m
MAX
N 6 e
1
AREA
b
<
OK
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 26 de 28
5.
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
CONCLUSIONES
De acuerdo a las indicaciones de CGET, para el proyecto de S/E Mariscal, se permiti reutilizar la memoria
de clculo de la Sala de Celdas y Control de S/E Padre Hurtado, ya que ambas comparten la misma
materialidad y similares dimensiones.
La Sala de Control considerada para el proyecto de S/E Mariscal es idntica a la diseada para S/E Padre
Hurtado, mientras que la calidad del suelo para fundacin y materialidad para construccin se mantienen,
por lo tanto, cumple para ambos proyectos.
En el caso de la Sala de Celdas, para S/E Padre Hurtado se consider paos de albailera de 6 metros
entre pilares de hormign armado, situacin que se mantiene para S/E Mariscal, diferencindose ambas
salas en que esta ltima considera la construccin de dos paos adicionales de 6 metros, es decir, su largo
final es 12 metros mayor que la sala diseada para S/E Padre Hurtado.
Para el diseo de paos de albailera se considera la aplicacin de cargas en reas tributarias, es decir, en
S/E Mariscal se mantienen las condiciones bajo las cuales se dise la sala de S/E Padre Hurtado, ya que
en ambos casos se considera paos de albailera de 6 metros de ancho.
Adems, de acuerdo a los resultados entregados en la presente memoria de clculo, estos se encuentran
muy por debajo de los valores lmite, permitiendo cierta holgura al tratarse de una sala de mayor largo final.
Por ejemplo:
a)
Para el caso de las costaneras, los momentos resistentes M22 y M33 son bastante superiores a los
momentos actuantes sobre ellas:
En el caso de las cerchas, los valores admisibles son bastante superiores a los de trabajo:
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 27 de 28
eleconsult
INGENIEROS ELCTRICOS CONSULTORES S.A.
kg
kg
adm 4,5 2
2
cm
cm
mx 1,43
Por lo tanto, considerando los resultados anteriormente citados, es posible reutilizar la presente memoria de
clculo para S/E Mariscal, debido, principalmente a que en ambos casos se considera el mismo ancho de
pao de albailera y dimensiones de elementos de hormign armado para el confinamiento de ellos,
adems de la holgura de los resultados obtenidos, pues estos indican que todos los elementos que
constituyen la Sala de Celdas y de Control, trabajan muy por debajo de sus capacidades mximas.
ARCHIVO
CDIGO
23680-A4
FECHA
31 Agosto 2010
Pgina 28 de 28