WRU25 WRU25/RA WIRING DIAGRAMS

EMISSION COIL EXTERNAL TEST EXTERNAL RESET EXTERNAL TEST

EMISSION COIL

USE

Tripping by EMISSION COIL - M.R.: Manual reclose Relay reset / External reset - A.R.: Self Reclosing

* Voltage reading proportional to the earth leakage current (terminals Z1 Z2) Sensitivity 0.03A (2.25 mV/mA) Sensitivity 0.1A (0.68 mV/mA) Sensitivity 0.3A (0.25 mV/mA) Sensitivity 0.5A (0.15 mV/mA) Sensitivity 1A (0.07 mV/mA) Sensitivity 3A (0.025 mV/mA)
USE

Trip by EMISSION COIL Manual reclose and automatic reset (M.R.)


UNDERVOLTAGE COIL EXTERNAL TEST

UNDERVOLTAGE COIL EXTERNAL TEST EXTERNAL RESET

USE

Tripping by UNDERVOLTAGE COIL - M.R.: Manual reclose Relay reset / External reset - A.R.: Self Reclosing

USE

Trip by UNDERVOLTAGE COIL Manual reclose and automatic reset (M.R.)

MOST IMPORTANT FEATURES


* Coupling with symmetrical rail DIN 46277 (EN 50022). * The relay includes the earth leakage protection transformer. * Leakage detection is done via sampling the differential current and calculating its true effective value. * Selectable sensitivity from 0.03A to 3A. 0.03A, 0.1A, 0.3A, 0.5A, 1A, 3A. * Selectable tripping delay from 0.02s to 1s. 0.02s, 0.1s, 0.3s, 0.5s, 0.75s, 1s. * Reclosing type: Manual or Automatic (according to model) WRU25 WRU25/RA AUT. REC: The earth leakage protector recloses 6 times following an exponential progression for times between reclosures with the following values 8s, 16s, 30s, 59s, 115s, and 224s. It will remain permanently disconnected if the leakage continues after 6 reclosures. If the leakage drops below the threshold value, according to the preset sensitivity, before reaching 6 reclosures, the earth leakage protector will remain connected and the reclosure counter will automatically return to zero after 15 minutes. * Leakage LED: 1 flash every 2s. Leakage between 25% and 50% selected sensitivity. * Leakage LED: 1 flash every 1s. Leakage between 50% and 75% selected sensitivity. * Leakage LED: 1 flash every 0.5s. Leakage above 75% selected sensitivity. * Leakage LED: permanent on. Earth leakage protector tripped. * Pre-sealable relay.

TECHNICAL FEATURES
* * * * * * * * * * * Type of relay: Electronic. Calculates leakage current in TRMS. Sensitivity: Selectable. Delay: Selectable. Reclosure type: Selectable. Reset: Manual / Automatic. Nominal Voltage: 230 V AC 20%. Nominal Frequency: 50 Hz 60 Hz. Operating temperature: -10 C +50 C. Weight. 208 g. Output contact features: Nominal isolating voltage Ui: 250 V AC. Test voltage between contacts and power supply: 2500 V AC. Electrical endurance: 2 x 105 operations. with resistive load Ue/Ie: 250 V / 8 A AC. with inductive load: AC11 Ue/Ie: 250 V / 2.5 A AC. DC11 Ue/Ie: 24 V / 5 A DC. Current through relay circuit with open contact: IRC 500 uA * Test: Test button in the earth leakage protector. It is also possible to test via an external button that joins terminals Y1 A1/Y2
75 70 70

85

A B

D
C

87

45

25

Mounting profile
DIN 46277 (EN 50022)

A B C D

Relay reclose and reclosure counter reset button (RESET). Relay and transformer test button (TEST). Sensitivity adjustment dial. Delay adjustment dial.