08-PC7630-B0-EM, 08/30/2010

Power input

SPECIFICATIONS
20V~250V AC/DC, 50/60Hz Less than 7VA -10~55 C (with no icing) -20~70 C (with no icing) 20%~85% RH non-condensed Counter, Chronmeter, T achometer 30Hz (contact type) 20kHz (solid state type) up, dn, upup, updn, Gate-up, Gate-dn, dir, ph

MODE SELECT
Single Counting
Accept Pre2 default value, the system will pull high at Relay 2 while count over Pre2

PARAMETER DIAGRAM
Mode Select
Single Segmented Counting Dual Segmented Counting Batch Counting Accumulation Counting

PC-7630
MULTIFUNCTION COUNTER OPERATION MANUAL

Content of the packaging Noumenon Washer User's Manual Bracket


Thank you for buying FineTek's products. Please read the user's manual first before using it. It is important to be familiar with product's performance and function. Please keep the user's manual so that consult in future. Modbus Communication can be downloaded from http: //www.fine-tek.com

1. Really lock the end Terminals screw, if the screw has not been locked but lost by causing the fire or mechanical breakdown. 2. Please don't be using this product and having places where we can fire gas, cause the risk of exploding by the fact that it may. 3. The life-span of the relay must depend on the user's usage, the use of the relay must be in specified load and life-span of electric apparatus that it labels, if the use of the relay exceeds its life-span, the danger that may melt or cause the fire in the contact of the relay. 4. Don't disassemble, repair or revise the products without authorization, this measure may cause the short circuit of the electric apparatus, trouble or fire. 5. Don't drop inside products by chip or chip of wire metal, will cause the short circuit and account or fire.

Power consumption Ambient temperature Storage temperature Ambient humidity Functions Counting frequency Counting input mode

Dual Segment Counting


Accept Pre1 & Pre2 default values, the system will pull high at Relay 1 & Relay 2 separately while count over Pre1 & Pre2
Dual Operation Counting Chron Mode Tacho Mode

, Counting output mode N, F, C, R, K1, K2, P Q, S1, S2, S3, A, H Timer operation mode A, A1, A2, A3, B, B1, B2, B3, D, E, F Z, Toff, T H , on, keypad protection Display Display range Reset Signal Input Signal 5 Level protection Double-line, 10-digit LED display -999,999,999~9,999,999,999 Front Panel Reset key & External trigger Reset1 Reset2 at bottom terminal (Positive/negative trigger selectable) IN1 & IN2 at bottom terminal Non-voltage input (NPN) Voltage input (PNP) selectable (output impedance: 7.8kW input impedance: 3.9 kW) High level: 4 to 30Vdc, Low level: 0 to 3Vdc Two 1C Relays Capacity 3A / 250V or 2 S.S Output (200Vdc 120mA ) 0.1s ~99,999.9s

Dual Operation Counting


IN1 & IN2 can independent counting and operate fundamental calculation (Add/Subtract).The Relay 2 will be pulled high while the calculation equal to default value (Pre2)

Please strictly follow the instructions below, it can guarantee the safe operation of the controller. 1. Environmental Concerns: Don't use the PC counter in heavy vibrating place or direct contact with water or oil. Don't use the PC counter in applications with dust, corrosive gasses, or direct sunlight. . Separate the power cables and signal cable to avoid static signal interference. Keep the PC counter away from the source of static electricity (e.g., Blender & Liquid transportation Pipe). Organic solvents (such as paint, benzene), strong acidic or alkaline solutions might damage the outer casing of PC counter series. 2. Operation Concerns: Store the PC counter at specific temperature. If the PC counter is stored under -10C, please allow the PC counter to stand at room temperature for at least 3 hours before use. Using different voltage might seriously damage internal components. Suggest warming up the PC counter for 30 minutes after turning it on.

Counter
Default 1 Setting Digital Range: 0~9,999,999,999

Time Counter
Default 1 Setting EX: 056"50 are 56.5sec

Tacho meter
Default 1 Setting Digital Range: 0~99,999,999

Batch Counting
Batch counting function, default port (IN 1, REST 2 & Relay 1) to set batch number and port (IN 2 REST1 & Relay 2) to set counting number for each batch process. In operation, while the counting number reaches setting value the Relay 2 will be active, and the same for batch process, Relay 1 will be active. If the counting number is over Pre2, then the "Relay 2 " will be active; if the batch times is over Pre1, then "Relay 1" will be active until rest1 acts

Output Signal Output retain Time Communication Data Retention. Housing type Housing Ambient pollution degree Dimension

Default 2 Setting Digital Range: 0~9,999,999,999

Default 2 Setting EX: 056h50 are 56h50min

Default 2 Setting Digital Range: 0~99,999,999

External power supply DC12V or DC24V 100mA RS 485 Modbus (RTU & ASCII) By EEPROM panel mounting Over-voltage category II, pollution degree II (IEC61010-1) IP 65 (Front panel) DIN 96x48x128.5 mm

Accumulation Counting
Accumulation counting function,if the accumulation number reaches preset value, then terminal "Relay 2" will be active. The asynchronous output (Relay 1 & Relay 2) can set time delay from 0.1 sec to 99999.9 secretary. While accumulation count is over 999999 or under -99999, the accumulation count will be reset to zero automatically.
Relay 1 Setting Digital Range: 0.1~99,999.9 sec If set "0",the output will be hold. Relay 1 Setting Digital Range: 0.1~99,999.9 sec If set "0",the output will be hold. Proportional Relationship Setting Digital Range: 0.001~999.999

Chron

Relay 2 Setting Digital Range: 0.1~99,999.9 sec If set "0",the output will be hold.

Relay 2 Setting Digital Range: 0.1~99,999.9 sec If set "0",the output will be hold.

Input Mode Selection Up Gate.up ph

FEATURES
Multi-functional design featuring in Timer, Counter, and Tachometer Accumulation, batch, and dual function DC12V or DC24V power (100mA) for input or external transmitter Selectable input of PNP or NPN Rising / Falling trigger selectable for counting / re-set signal Ratio-Conversion function (pre-scale) is available to indicate input pulse in actual measuring unit Counting speed is switchable as 30 / 20K cps with maximum of 20K cps. Selectable output including relay and transistor 5 user-friendly keypad protection schemes 10 digits with dual channel, dual color LED display RS-485 Communication interface, Data Retention.

DISPLAY PANEL

DIMENSION / PANEL CUTOUT DIMENSION Unit: (mm)


Clearance between panel cutout should be greater than 10mm in horizontal, and 22mm in vertical.
11.5 96 48 117 44.8

Time counting function will show accurate time to user. The calculate mode can display "sec"msec" , "min"sec" and "hr"min". Longest time can be up to 999hr"59min, and the shortest time to display is 10ms. If user select the "H" reset ("rESt=h" in automation reset function), then user can choose either manual / automatic operation,or determine the forward / reverse setting in start. "Relay 2" will keep active while time is up to preset value. Caution: This function only while user set IN1 & IN2 in PNP status

Proportional Relationship Setting Digital Range: 0.001~99,999.999

Time range settung h ` `` hour minute second

Output Mode Selection HiLo ArEA HiHi LoLo

Tacho
Tachometer function, or rotation speed function, is designed to monitor the rotation speed. User can input rotation frequency into "IN1" & "IN2", and follows setting the calculation unit and refresh time. While single input ("Up" mode), the maximum detects limit is 60k rpm, and in "ph" mode, its maximum is only allowable up to 30k rpm. User must care the correct setting of Pre1, Pre_2, Relay 1 and Relay 2 which refer to different setting mode ( HiLo / Area / HiHi / LoLo, see User guide in detail ).

Dual opration Setting Add= IN1+ IN2;Sub=IN1 - IN2 This setting is only used for dual mode

Output Mode Selection A A1 A2 A3 B B1 B2 B3 D E F Z Toff Ton H

Pulse Speed / Revolution Digital Range: 1~999,999

Input Mode Selection Up dn updn upup Gate.up Gate.dn Dir

ph

Reset Selection; actives only under output is in H mode A: automatic H: Manual

Refresh Time for Tacho Mode 0.1s~99.9s

Output Mode Selection H N F C R K1 P A K2 S1 S2 S3

ORDERING INFORMATION Output indicator


20---48X48(6 Digit) Dimension 30---96X48(10 Digit) 40---72X72(8 Digit)
Power Output Communic - ation & data retention. 20V~250V AC/DC

PANEL CUTOUT
102 min.

KEY PROTECTION FUNCTION CODE


ALL: Complete Protect Mod: Mode Protect P1.P2: All protect, except Pre1 & Pre2 rES: Reset Protect rES.Mod: Reset Mode FeEE: No Protect
Reset Selection; actives only under output is in H mode A: automatic H: Manual

Forward / Backward Setting actives only under output is in H mode O=Forward PrE_2=Backward

Average value seeting 1 2 4 8

Display of preset value Display of count value


Use to switch mode and setting item Reduce and mod change
45
+0.6 -0

Start mode setting actives only under output is in H mode STOP 1: IN1 Start & Stop STOP 2: IN1 Start IN2 Stop Key Protect Function ALL rES Mod rES.Mod P1.P2 FreEE

Unit setting 1=rps 60=rpm 3600=rph

Operation
67 min.
While one sets function except of FrEE,presses enter to access edit program. Input 4-digits (ex: 3456) password and press enter to complete program.

R---Relay output S---Solid state output 0--- Without. 1--- RS-485 communication interface only. 2--- Data retention only. 3--- Communication interface and data retention.

Forward / Backward Setting actives only under output is in H mode O=Forward PrE_2=Backward

Boosting delay time 0s~99s

Addition and mod change Position shifft Reset or comfirmation


RES ENT

Decimal Point Shifting

92 +0.8 -0

While in power off, the PC 7630 will retain the present value and the output status; specially, some counting mode likes A3 (Non-reset in power on) must with this retain status that can work functionally.

Rising / Falling Edge Setting for Reset1 Reset2 PP PN NN NP EX: P N reset1Rising reset2Falling

Decimal Point Shifting

Unlock

Key Protect Function ALL rES Mod rES.Mod P1.P2 FreEE

Reset Pulse Width Setting


20ms 1ms

Key Protect Function ALL rES Mod rES.Mod P1.P2 FreEE

TERMINAL SETTING ARRANGEMENT


Please inspect the specification of the power. Don't connect the end Terminals not used. Propose that the signal line uses AWG 18~24 to enclose the isolate wire, the main power cable and relay export the contact and use AWG 25~30.
ON ON ON SW2

Dip Switch in setting window


SW2 SW1

While system presents the protect status,press "MOD" button. The panel will show two rows of digital information.Operate the 4-digits in upper row(i.e,4690)to subtract 1234 (4960-1234= 3456),or directly input 3456 in lower row, to get access into mode select menu.

Rising / Falling Edge Setting for IN1 IN2 PP PN NN NP EX: P N IN1Rising IN2Falling

Reset to factory default Yes / No

Rising / Falling Edge Setting for Reset1 Reset2 PP PN NN NP EX: PN reset1Rising reset2Falling Reset Pulse Width Setting 20ms 1ms

11 12 13 14 15
N.C N.O COM RELAY 2 RS485
IN1

16 17 18 19
N.O COM RELAY 1

20
1 2 1

Do not need "opration" and "Unlock",if sets function "rES".


2
1

Rising / Falling Edge Setting for Reset1 Reset2 PP PN NN NP EX: PN reset1Rising reset2Falling Reset Pulse Width Setting 20ms 1ms

Input Frequency Setting Hi: Above 30Hz Lo: Under 30Hz

N.C

Aux. Power 20~250V DC/AC

INSTALLATION
Step-1. Insert the counter through the panel cutout. Step-2. Insert the mounting bracket into the mounting groove of the counter. Step-3. Push the mounting bracket forward until the bracket to Clip the panel wall. Step-4. Repeat step & to install the other bracket.

Comunication setting

100mA Max. IN2 RST1 RST2 DC 0V DC OUT

Reset to factory default Yes / No

VOUT=24VDC

VOUT=12VDC

10

12V Default

In this case: IN1 are NPN IN2 are PNP "Chron" function only active while user set IN1 & IN2 in PNP status

Reset to factory default Yes / No

TERMINALS DIAGRAM NPN transistor trigger


IN1 IN2 RST1 RST2 DC0V DC OUT

Input Frequency Setting Hi: Above 30Hz Lo: Under 30Hz

NPN contact trigger


IN1 IN2 RST1 RST2 DC0V DC OUT

PNP transistor trigger


IN1 IN2 RST1 RST2 DC0V DC OUT

PNP contact trigger


IN1 IN2 RST1 RST2 DC0V DC OUT

Pin assignment for transistor (200Vdc 120mA).


Press
Input Frequency Setting Hi: Above 30Hz Lo: Under 30Hz

Comunication setting Comunication setting


ModBus Initial Setting RTU ASCII ModBus ID Address 1~255

S.S1

S.S2
LOAD

17 16 15

13 12 11

LOAD Push Push

Comunication setting
A h q B i r C K S d L t E M u F n V G o W H p Y
ModBus Baud Rate Setting ModBus Frame Setting

Timing Chart for Counting Mode Input (Rising Edge Trigger)

Timing Chart for Chron Mode Output


IN1: Count input IN2: Prohibit (gate) input

UP
H IN1 L

Updn
H IN1 L H IN2 L 4 3 3 Counting value 0 0 2 1 2 1 2 3

Gate-Up
H IN1 L H IN2 L

IN1: Count input IN2: Prohibit (gate) input

Gate-dn
H IN1 L H IN2 L 4 3

Dir
H IN1 L H IN2 L

A : Signal ON delay (boosting reset)


Power IN1 IN2 REST1

A1 : Signal ON delay (boosting reset)


Power IN1 IN2 REST1 OUT 2

n n-1 n-2

OUT 2

3 Counting value 0 0 2 1 Counting value 0


IN2: Count input IN1: Prohibit (gate) input IN2: Count input IN1: Prohibit (gate) input

3 2 1 2

Counting value 0

2 1

n-3

Counting value 0 0

2 1

Pre_2 Forward

Pre_2 Forward

Backward Pre_2

Backward Pre_2

dn
H IN1 L

UPUP
H IN1 L H IN2 L n-1 n-2 5 4 N-3 N-4 0 Counting value 3 2 1 Counting value 0 0 H IN1 L H IN2 L

Ph
H IN1 L

IN1is rising edge trigger, while time is over Pre_2, "OUT2" will be in active high until REST1 acts, and then stop time calculating.

IN1 is rising edge trigger, while time is over Pre_2, "OUT2" will be in active high and stop time calculating. If the IN1 acts low, then stop time counting.

H IN1 L H IN2 L 5 4

A2 : Power ON delay (boosting reset)


Power IN1 IN2

A3 : Power ON delay (boosting without reset)


Power IN1 IN2 REST1 OUT 2

n n-1 n-2

H IN2 L

REST1

Counting value

3 2 1

Counting value 0

n-3 n-4 Counting value 0 0 1

2 1 0

OUT 2 Pre_2 Forward Backward Pre_2

Pre_2 Forward

Backward Pre_2

Note: Indication in "A" must large than minimum width of signal "In2", and indication in "B" must above the half of minimum width of signal "IN2"

Start counting at the power on, and stop at either IN1 or IN2 is active high.

Start counting at the power on, and "OUT2" acts while time over preset value, this time calculation will stop at either IN1 or IN2 is active high.

Timing Chart for Counting Mode Output


UP / UPUP / Gate-UP N
Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 OUT1 OUT2

B : Repeat cycle (boosting reset)


Power

B1 : Repeat cycle (boosting reset)


Power
IN1 IN2 REST1

Dn / Gate-dn

UPDn / Dir / Ph K-1

UP / UPUP / Gate-UP
Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 OUT1

Dn / Gate-dn

UPDn / Dir / Ph

UPDn / Dir / Ph

IN1 IN2

K-2

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 -999,999,999 OUT1

REST1
OUT 2

Pre_2

OUT 2 Pre_2 Forward Backward Pre_2

Forward Backward Pre_2

IN1 rising edge trigger, while time over preset value, the "OUT2" will act high and act low while time calculation over preset value again

OUT2 OUT2

IN1 rising edge trigger, while time over preset value, the "OUT 2" will act high and start time calculation. This mode will be more useful while repeat time counting

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 0 OUT1 OUT2

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 OUT1

S1

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 -999,999,999 OUT1

B2 : Repeat cycle (boosting without reset)


Power

B3 : Repeat cycle (boosting without reset)


Power

IN1 IN2 REST1


OUT 2 Pre_2

IN1 IN2 REST1


OUT 2 Pre_2 Forward

OUT2 OUT2

Forward Backward

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 0 OUT1 OUT2

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 OUT1

S2

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 -999,999,999 OUT1

Pre_2

Backward Pre_2

IN1 rising edge trigger, while time over preset value, the "OUT2" will act high and act low while time calculation over preset value again

IN1 rising edge trigger, while time over preset value, the "OUT2" will act high. This mode will be more useful while repeat time counting

D : Signal OFF delay (boosting reset)


Power IN1 IN2

E : Interval (boosting reset)


Power IN1 IN2 REST1 OUT 2 Pre_2 Forward

OUT2 OUT2

REST1

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 0 OUT1 OUT2

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 0 OUT1

S3

Reset / Reset 1 9,999,999,999 Pre_2 Pre_1 0 -999,999,999 OUT1

OUT 2 Pre_2 Forward

Backward Pre_2

Backward Pre_2

IN1 rising edge to trigger on and falling edge start to calculate time. During the calculation time, "OUT2" keep active high and will down to low status while time is over preset value.

IN1 rising edge trigger, while time over preset value, the "OUT2" will act low and stop time calculation.

OUT2 OUT2

F : Cumulative (boosting without reset)


Power IN1 IN2 REST1 OUT 2

Z : ON/OFF duty (boosting reset)


Power IN1 IN2 REST1 OUT 2 Pre_2

N Mode: While counts reach Pre_2 (See detail in Default Setting), counting stop, and keep "OUT2" in active status until user reset. F Mode: While counts reach Pre_2, counting continues, and keep "OUT2" in active status until user reset. C Mode: While counts reach Pre_2, counting resets, and keep "OUT2" in active status until time passes preset value. R Mode: While counts reach Pre_2, counting stops, and keep "OUT2" in active status until time passes preset value then reset the counting.

K-1 mode: While counts reach Pre_2 (See detail in Default Setting), counting continues, and keep "OUT2" in active status until time passes preset value. P mode: While counts reach Pre_2, it first resets counting and follow then continues counting, the display shows the default Pre_2 until time passes preset value. After the preset time passed, the display presents current value Q mode: While counts reach Pre_2, counting continues. And it keeps "OUT2" in active status until time passes preset value then it will reset the counting. A mode: While counts reach Pre_2, counting stops, and it will restart counting while accepts reset input.

K-2 mode: While counts reach Pre_2, the "OUT2" in active status until time passes preset value. S1 mode: While counts less than or equal Pre_1, the "OUT1" will in active status and keep hold. If counts large than Pre_1, the "OUT1" will be reset. S2 mode: While counts less than or equal Pre_1, the "OUT1" will be reset and keep hold. S3 mode: While counts equal Pre_1, the "OUT1" will keep hold, and if counts equal Pre_2, the "OUT2" will keep hold. H mode : Manipulation mode, This mode will act following the set values of "rEst" & "StArt".

Pre_2 Forward

Pre_1

Timing Chart for Counting Mode Output


Acculumation Counting
reset1 reset2 Pre_2 Counting 0 value OUT2 99,999,999 Acculumation value 0 While accumulation count is over -999,999,999 or under 9,999,999,999 the accumulation count will be reset to zero automatically.

Timing Chart for Tacho Mode Output

Backward Pre_2

Forward Backward Pre_1


Pre_2

Dual Operation Counting

HiLo
Pre_2

HiHi
While rotation speed large than Pre_2, the "OUT2" keep active high, and while rotation speed is lower than Pre_1, the "OUT1" keep active high

Pre_2 Speed Pre_1

While IN1 status in high, it begins to calculate time, and stop calculate time while IN1 in low status. If time is over preset value, the "OUT2" will act high and stop time calculation.
While rotation speed large than Pre_2, the "OUT2" keep active high. And if rotation speed is above Pre_1, than "OUT1" acts high.

IN1 rising edge to start calculating time and active high in "OUT2". While the time is between Preset value 1 (Pre_1) and preset value 2 (Pre_2), the "OUT2" will change status down to low. Over the Pre_2, the "OUT2" will change status from low to high again.

ADD : IN1+ IN2


reset1 reset2
Pre_2 Counting value
In1 value 0 In2 value 0

SUB : IN1- IN2


Speed

TOFF : Twin Timer OFF Start (boosting reset)


Power IN1 IN2

TON : Twin Timer ON Start (boosting reset)


Power IN1 IN2 REST1 OUT 2

reset1
Pre_1

reset2
Pre_2 Counting 0 value
0 IN1 value

OUT1

OUT1

REST1 OUT 2

Batch Counting
reset1 reset2 Pre_2
Counting value

Pre_2

Pre_2 Pre_1 Forward Backward Pre_1 Pre_2

OUT2

OUT2

Area
0
Pre_2

LoLo
While rotation speed large than Pre_2 or is lower than Pre_1, the "OUT2" keep active high. And if rotation speed is between the Pre_1 & Pre_2, than "OUT1" acts high.

Pre_1 Forward Backward Pre_1 Pre_2

In2 value

Pre_2 Speed Pre_1

0
Speed

OUT2
Pre_1

OUT2

OUT2
Pre_1

While rotation speed is under Pre_2 the "OUT2" keep active high. And if rotation speed is under Pre_1, than "OUT1" acts high.

IN1 rising edge to start calculating time. While the time is over the Pre_2, the "OUT2" will change status from low to high and reset synchronously. The system will act time counting if "OUT2" in high status and reset time to zero while the time is over Pre_1.

The time calculation will turn on while IN1 rising edge is detected. Synchronously, "OUT2" will act high until time is over Pre_1. Over Pre_1, the system will recalculate time, and "OUT2" will be acted again while time is over Pre_2. Similarly, time will be reset to zero and repeating cycling.

The above is for when the output mode is N. While the display value over preset value(Pre_2), " OUT2 " keep active until "RST1" acts.
OUT1 OUT1

0 OUT1 If the counting number is over Pre_2, the "OUT2 will be active; if the batch times is over Pre_1, then " "OUT1 will be active until rest1 acts

Batch value