Authors Lutz Hulka | lutz.hulka@omicron.at Markus Ptter | markus.puetter@omicron.at Date Jul 21, 2010 Related OMICRON Product CPC 100 Application Area Cables & Transmission Lines Analysis Version v1.0 Document ID ANP_10002_ENU
OMICRON
Page 1 of 21
Contents
1 Using This Document...................................................................................................................... 3 1.1 Operator Qualifications and Safety Standards ........................................................................... 3 1.2 Safety Measures ....................................................................................................................... 3 1.3 Conventions and Symbols Used ............................................................................................... 3 1.4 Related Documents .................................................................................................................. 4 Safety Instructions for Connecting CP CU1 to Power Lines ......................................................... 5 2.1 Before Starting.......................................................................................................................... 5 2.2 Recommended Current Range Settings .................................................................................... 5 2.3 Estimating the Open-Line Voltage ............................................................................................. 5 2.4 Connecting the Measurement Setup to Power Lines ................................................................. 7 k Factor and Mutual Coupling Factor Measurement...................................................................... 9 3.1 Why k Factor Measurement? .................................................................................................... 9 3.2 Mutual Coupling.......................................................................................................................10 3.3 Performing Measurements .......................................................................................................12 3.4 Interpretation of Measurement Results.....................................................................................17
3.4.1 Excel CPC 100 File Loader ........................................................................................................ 18
Please use this note only in combination with the related product manual which contains several important safety instructions. The user is responsible for every application that makes use of an OMICRON product. OMICRON electronics GmbH including all international branch offices is henceforth referred to as OMICRON. OMICRON 2010. All rights reserved. This application note is a publication of OMICRON. All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON. Reprinting, wholly or in part, is not permitted. The product information, specifications, and technical data embodied in this application note represent the technical status at the time of writing and are subject to change without prior notice. We have done our best to ensure that the information given in this application note is useful, accurate and entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be present. OMICRON translates this application note from the source language English into a number of other languages. Any translation of this document is done for local requirements, and in the event of a dispute between the English and a nonEnglish version, the English version of this note shall govern.
OMICRON 2010
Page 2 of 21
1.1
Moreover, additional relevant laws and internal safety standards have to be followed.
1.2
Safety Measures
Before starting a measurement, read the safety rules in the CPC 100 User and Reference Manual and CP CU1 Reference Manual carefully and observe the application specific safety instructions in this Application Note when performing measurements to protect yourself from high-voltage hazards.
1.3
Symbol
OMICRON 2010
Page 3 of 21
1.4
Related Documents
The following documents complete the information covered in this Application Note: Title CPC 100 User Manual CPC 100 Reference Manual Description Provides basic information on the CPC 100 test system and relevant safety instructions. Provides detailed hardware and software information on the CPC 100 test system including relevant safety instructions. Provides information on the CP CU1 coupling unit and the CP GB1 grounding box including typical application examples.
OMICRON 2010
Page 4 of 21
2
2.1
Caution: Connecting the measurement setup to overhead lines with a life parallel system brings about high-voltage hazards. It is strongly recommended to take all parallel lines out of service before proceeding. Before connecting CP CU1 to overhead lines or power cables (further on referred to as power lines), you must estimate the open-line voltage as described in 2.3 Estimating the Open-Line Voltage. Follow the instructions below exactly and sequentially to protect yourself from high-voltage hazards. In addition to the following safety instructions, observe "Safety Rules" on page 7 of the CP CU1 Reference Manual V1.4.
2.2
2.3
2.
Switch off, short-circuit and ground the power line on both sides using an installed grounding switch or, if no grounding switch is available on site, using grounding cables (further on, the grounding switch or these extra grounding cables are referred to as grounding switch). Make sure that the connection to ground at the far end of the power line is not removed during the complete test procedure.
OMICRON 2010
Page 5 of 21
3.
4. 5. 6.
In addition to the grounding switch, ground the line at the near end using a grounding set consisting of three cables rated for the maximum short-circuit current possible on the line (further on, this connection is called working ground). Open the grounding switch at the near end of the power line and measure the current through the working ground using a clamp-on ammeter on all three phases. Close the grounding switch. Calculate the estimated open-line voltage after removal of the grounding cables as follows: [] = [] 0.4[/] 2 []
(1)
or
[] is the estimated open-loop voltage in volts, is the highest measured current in amperes, 0.4[/] = 0.64[/] is the constant of a typical overhead line per wire and [] and [] is the length of the line in km and miles respectively. Caution: If the estimated open-line voltage is
where
[] = [] 0.64[/] 2 []
(2)
> 500 V, stop. The measurement is not possible due to high-voltage hazard. Try to take parallel lines out of service. 250500 V, the measurement is possible only in the 10 A range. 100250 V, the measurement is possible in the 10 A or 20 A range. 50100 V, the measurement is possible in the 10 A, 20 A or 50 A range. < 50 V, the measurement is possible in all current ranges.
7.
If the current range allowed by the estimated open-line-voltage is lower as the current range set according to Table 1: Recommended Current Range Settings on page 5, set the current range switch of CP CU1 to the value allowed by the open-line voltage.
Caution: While the grounding switch at the near end of the power line is open, the area around CP GB1 in the range of 5 m/15 ft and around CP CU1 in the range of 2 m/5 ft is a dangerous zone due to high-voltage and mechanical hazards. Do not enter the dangerous zone. Keep the grounding switch open for a time as short as possible.
Caution: If you see or hear anything uncommon in the test equipment, for example noise of electrical discharge or lightening of surge arrestors, close the grounding switch before touching the measurement setup.
OMICRON 2010
Page 6 of 21
2.4
Make sure that the grounding switch is closed. Connect CP GB1 to ground using the delivered cable near the place where the connection to the line is made. Make sure that the grounding stud is in good condition, clean and free of oxidation. Caution: Depending on the type of grounding points in the substation, the appropriate connection set and socket clamp have to be used. Connecting socket clamps of one type to a grounding point of another system is highly dangerous on both the connection of the grounding set to CP GB1 and the connection of CP GB1 to the grounding point in the substation. The 16 to 20 mm socket clamps are designed and tested for fault currents up to 26.5 kA, the 25 mm (1 inch) socket clamp for fault currents up to 30 kA, both for a maximum duration of 100 ms. On locations where higher fault currents are possible, CP CU1 and CP GB1 must not be used.
3. 4. 5. 6. 7.
Disconnect the grounding cables from the ground (the grounding switch is closed!) and connect them to the CP GB1s line studs. Position CP CU1 at a minimum distance of 5 m/15 ft from CP GB1. Position CPC 100 at a minimum distance of 5 m/15 ft from CP CU1 and 10 m/30 ft from CP GB1. Ground CP CU1 using a cable of at least 6 mm2 cross-section close to CPC 100 and the position of the operator. Connect CP CU1 with CP GB1 as shown in Figure 1: Wiring the Measurement Setup on page 7.
OMICRON 2010
Page 7 of 21
8. 9. 10. 11.
Ground CPC 100 using a cable of at least 6 mm2 cross-section close to the position of the operator. Connect CP CU1 with CPC 100 as shown in Figure 1: Wiring the Measurement Setup above. Mark the area around CP GB1 in the range of at least 5 m/15 ft and around CP CU1 in the range of at least 2 m/5 ft as dangerous zone. Open the grounding switch and read the voltmeter on the CP CU1s front panel from outside of the dangerous zone. Caution: If the voltmeters reading is
> 500 V, stop. The measurement is not possible due to high-voltage hazard. 250500 V, the measurement is possible only in the 10 A range. 100250 V, the measurement is possible in the 10 A or 20 A range. 50100 V, the measurement is possible in the 10 A, 20 A or 50 A range. < 50 V, the measurement is possible in all current ranges.
If the open-line voltage allows measurement, proceed as described in 3.3 Performing Measurements on page 12. Make sure that the grounding switch is always closed when no measurement is performed and especially when the wiring is modified or the current range switch of CP CU1 is set.
OMICRON 2010
Page 8 of 21
3
3.1
0 1 1
(3)
the complex ratio of the zero-sequence impedance 0 and the positive-sequence impedance 1(see Figure 2: Zero-Sequence Impedance Definition below) 0 =
0 1
(4)
(5)
(6)
where and are the real and imaginary parts respectively of the ground impedance and and are the real and imaginary parts respectively of the line impedance.
OMICRON 2010
Page 9 of 21
The single-phase zero-sequence impedance corresponds to a serial connection from the line impedance 0 and the triple ground impedance . The k factor is an important setting of distance protection relays. The precision of this setting affects the accuracy of distance protection relays dramatically. The k factor can be calculated, but the calculation results give only a rough estimate of the actual value. As a wrong k factor setting can cause worse power quality, higher risk to lose the system stability and loss of power supply, k factor measurements are essential for fast, selective and reliable distance protection. Because there are usually strong disturbances by other lines in service, measurement at the mains frequency is not feasible. All measurements running according to the templates are done below and above the mains frequency and the results are interpolated. From these results the positive- and zero-sequence impedances as well as the k factor in various formats are calculated.
3.2
Mutual Coupling
Basically, mutual coupling is nothing but a voltage induced in the parallel system II, which is caused by a current in system I. Due to the voltage induced in system II, a current also flows in the parallel system, which in turn induces a voltage in system I. This relation is shown in the following figure.
For measuring the coupling impedance , the template requires two measurements. The advantage of this measurement is that no measurement is required on system II. Rather, all measurements are conducted on system I. In the first measurement, system II is separated from the ground on at least one end. Consequently, no current can flow through system II. The result is the zero-sequence impedance 01 for the case that no current can flow in system II. For the second measurement, both ends of the line have to be grounded to ensure a flow of current. However, the voltage in system II becomes zero. The result of this measurement is the zero-sequence impedance 02. The coupling impedance 02 is now calculated from 01 and 02:
OMICRON 2010 Page 10 of 21
The coupling factor can be presented in two versions. The following equation shows the complex coupling factor . =
1
= 10102 01 3
(7)
(8)
In the two equations below, the real and imaginary components are split.
(9)
OMICRON 2010
Page 11 of 21
3.3
Performing Measurements
Connect the measurement setup to the overhead lines or power cables under test following 2 Safety Instructions for Connecting CP CU1 to Power Lines on page 5. Note: For line length below 5 km/3 miles it is recommended to connect the V SENSE input of CP CU1 as close as possible to the VT of the line to reduce the additional impedance of the current feed in the path. For longer lines, you can connect the V SENSE input with the Kelvin clamps directly on CP GB1. In the course of the k factor test procedure, the following measurements are performed: Line-to-line impedance measurements: L1-L2, L1-L3, L2-L3 (Figure 4: Line-to-Line Measurements below shows the L1-L2 measurement as example.)
Near end
V1 AC
I AC
I AC
BOOSTER V SENSE
OMICRON 2010
Page 12 of 21
Line-to-ground impedance measurements: L1-E, L2-E, L3-E (Figure 6: Zero-Sequence Impedance Measurement - System II is in operation below shows the L1-E measurement as example.)
Near end
V1 AC
I AC
I AC
BOOSTER V SENSE
Zero-sequence impedance measurements: L1||L2||L3-E (see Figure 6: Zero-Sequence Impedance Measurement - System II is in operation, Figure 7: Zero-Sequence Impedance Measurement System II is off and disconnected from the ground on at least one end, and Figure 8: Zero-Sequence Impedance Measurement - System II is off and connected to the ground on both ends below).
Short the three phases with the delivered three-lead cable as shown in "Shorting the Phases" on page 17 of the CP CU1 Reference Manual V1.4.
OMICRON 2010
Page 13 of 21
Far end
Overhead Line
Near end
V1 AC
I AC
I AC
V1 AC I OUT CP CU1
OMICRON 2010
Page 14 of 21
Near end
V1 AC
I AC
I AC
V1 AC I OUT CP CU1
Figure 7: Zero-Sequence Impedance Measurement - System II is off and disconnected from the ground on at least one end
OMICRON 2010
Page 15 of 21
Far end
Overhead Line
Near end
V1 AC
I AC
I AC
V1 AC I OUT CP CU1
Figure 8: Zero-Sequence Impedance Measurement - System II is off and connected to the ground on both ends
The test procedure is controlled by templates available on the CPC Explorer CD-ROM shipped with your CP CU1 or in the customer area of www.omicron.at. It is recommended to use the same test current for all measurements. To find out the highest test current possible, start the test procedure with the measurement featuring the highest impedance, that is the L1-L3 measurement on power cables and the L1-E measurement on overhead lines. After wiring the measurement setup to the line under test proceed as follows:
1.
Configure CPC 100 as described in 2.3 Configuring CPC 100 on page 22 of the CP CU1 Reference Manual V1.4 for the CP CU1s current range set by the current range switch.
Caution: The configured current range must not exceed the limit by the open-line voltage.
2.
Choose the XML template for the mains frequency (e.g. "Line Imp CU1 60Hz.xmt" for the 60 Hz mains frequency) and open the template.
OMICRON 2010
Page 16 of 21
Caution: Open the grounding switch at the near end before making the test and keep it open only during the measurement. Close the grounding switch after the test and before reconnecting the measurement setup.
3.
4.
5. 6.
Run the test procedure. The following measurements are performed: Line-to-line measurements: L1-L2, L1-L3, L2-L3 For each measurement, connect the I OUT and V SENSE inputs of CP CU1 to the corresponding CP GB1s line studs. Line-to-ground measurements: L1-E, L2-E, L3-E For each measurement, connect the I OUT and V SENSE inputs of CP CU1 to the corresponding CP GB1s line studs. Zero-sequence impedance measurements: L1||L2||L3-E If an overload of CPC 100 occurs, reduce the test current or set a lower current range and run the test procedure once again. Lower test currents at the two highest frequencies are recommended. Save the test procedure as a file on CPC 100. Download the test file from CPC 100 to the PC using CPC Explorer.
Load the test file into the Microsoft Excel template. The measurement results are displayed.
3.4
OMICRON 2010
Page 17 of 21
3.4.1
Excel CPC 100 File Loader Excel CPC 100 File Loader allows loading XML files generated with CPC 100 into Microsoft Excel templates for post-processing. Excel CPC 100 File Loader is installed with CPC Explorer. After the installation, a shortcut to start Excel CPC 100 File Loader appears on your desktop. Templates are pairs of XML documents and Microsoft Excel templates designed by OMICRON electronics or end users for designated applications. The XML templates are predefined test procedures, often with comments, that run on CPC 100 and guide the user through the test. Once completed, the XML file is saved, downloaded to the PC using CPC Explorer and then loaded with CPC 100 File Loader into the corresponding Microsoft Excel template. There the results are post-processed and a final test report is generated. The template pairs facilitate and speed testing with CPC 100 and the evaluation of results.
OMICRON 2010
Page 18 of 21
The "Residual Compensation Factor" is the k factor calculated from the determined data for setting the relays. Under "Residual Compensation Factor Format", one of the three manufacturerdependent formats can be selected. Under "Mutual Coupling Factor", the mutual coupling factor is indicated. Like for the k factor, three different display formats are available.
Click the button "Load XML-File" to open the browse menu to load the desired data to the template. Click "Print Report" to print the calculated data. Under "Measurements", the results of the impedances of the nine conducted measurements are shown in Cartesian and Eulerian form. The relevant calculated impedances are listed under "Impedance Results". 1 is the arithmetic mean value of the first three measurements. 0is the triple value of the measured three-phase zerosequence impedance and thus refers to one phase (see Figure 2: Zero-Sequence Impedance (7) on page Definition). The coupling impedance is calculated according to = 1010201 3 11. The coupling zero-sequence impedance 0 corresponds to the triple value of the coupling impedance .
L2
L1
L3
The L2-E measurement features the lowest X component because the line is very close to the ground wire. The X component of the L3-E measurement is decreased by a parallel system taking course close to L3 on the other side of the tower. Short-circuiting of the parallel system during the measurement would have increased the effect and would have lead to erroneous results because this is not the normal operating condition. Another interesting effect can be observed when measuring power cables. If the screen or shield is very close to the conductors but the conductors are relatively wide from each other, the inductive part of the line-to-line measurements is higher than the inductive part of the line-to-ground measurements, resulting in a negative X component of the calculated impedance . This seemingly
OMICRON 2010 Page 19 of 21
strange result is explained as follows. Recalling (see 3.1 Why k Factor Measurement? on page 9) that the zero-sequence impedance is given by 0 = 1 + 3 =
0 1 3
(10)
and hence
(11)
where 1 is the positive-sequence impedance and is defined as a difference between the line-toground loop measurement and a half of the line-to-line loop measurement, the X component of can become negative.
OMICRON 2010
Page 20 of 21
OMICRON is an international company serving the electrical power industry with innovative testing and diagnostic solutions. The application of OMICRON products provides users with the highest level of confidence in the condition assessment of primary and secondary equipment on their systems. Services offered in the area of consulting, commissioning, testing, diagnosis, and training make the product range complete. Customers in more than 130 countries rely on the company's ability to supply leading edge technology of excellent quality. Broad application knowledge and extraordinary customer support provided by offices in North America, Europe, South and East Asia, and the Middle East, together with a worldwide network of distributors and representatives, make the company a market leader in its sector.
Americas OMICRON electronics Corp. USA 12 Greenway Plaza, Suite 1510 Houston, TX 77046, USA Phone: +1 713 830-4660 +1 800-OMICRON Fax: +1 713 830-4661 info@omicronusa.com
Asia-Pacific OMICRON electronics Asia Limited Suite 2006, 20/F, Tower 2 The Gateway, Harbour City Kowloon, Hong Kong S.A.R. Phone: +852 2634 0377 Fax: +852 2634 0390 info@asia.omicron.at
Europe, Middle East, Africa OMICRON electronics GmbH Oberes Ried 1 6833 Klaus, Austria Phone: +43 5523 507-0 Fax: +43 5523 507-999 info@omicron.at