NOTES:

THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND


MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
16 DIA STEP BAR CAST INTO INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
COVER SLAB WITH TOE HOLE CHECKED AND APPROVED AS PART OF THE PROJECT
DUCTILE IRON COVER DRAWING SET.
COVER SLAB DETAIL AS SPECIFIED UV RESISTANCE EPOXY 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
FOR UNPAVED AREA COATING TO ALL SURFACES ABOVE GROUND OTHERWISE STATED.
2. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE

250(VARIES)

100
CL
FGL FGL STATED.
200

3. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND


TO BE TANKED.
4. ALL INTERNAL FACES OF CONCRETE TO BE COATED
250 (VARIES) ( SHAFT ) WITH EPOXY COATING AS SPECIFIED.
CONCRETE SHAFT DIMENSION TO 5. UNLESS OTHERWISE STATED ALL INLET AND OUTLET
BE DETERMINED EPOXY COATING TO PIPES OF MANHOLES SHALL BE LAID SOFFIT TO
ON SITE DURING ALL INTERNAL SOFFIT.
GRP LADDER 6. ALL COVERS IN OPEN AREA TO BE PROVIDED WITH 1No.
SEE DETAIL 1
CONSTRUCTION SURFACES
OF MANHOLE GRAB BAR.
(MAXIMUM 300 7. MANHOLES SHALL BE PROVIDED WITH REINFORCED
TANKING MEMBRANE REINFORCED CONCRETE CONCRETE RINGS (2Nos. AS MINIMUM). THE LOWER

DIA. FROM 1500mm-2400mm)


(MAX. 4200mm FOR PIPE DIA. FROM 2500mm-3000mm)
AND PROTECTION BOARD DEPTH = 6000) REDUCER SLAB
RING SHALL BE 250mm HEIGHT AND THE UPPER RING
TO VARY ACCORDING TO FINAL GROUND LEVEL.

300
EPDM 'O' RING SEAL 8. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm
OR GASKET STRIP(2 Nos
OF MIN SIZE 20mm WIDTH) DEEP SUMP.
9. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
FULL GROUND WATER LEVEL CONDITION WITH 1.1

100
DEPTH VARIES
FACTOR OF SAFETY FOR FLOATATION AND BEARING
SPECIFIED SEALANT

(MAX. 3200mm FOR PIPE


PRESSURE NOT EXCEEDING 200kpa AT FORMATION

STANDARD BASE
REINFORCED CONCRETE WALL FOR JOINT

.
LEVEL.
PROTECTION BOARD 10.DEWATERING OPERATIONS SHALL BE PROVIDED
EPOXY COATING AS
C C SPECIFIED
TANKING MEMBRANE DURING CONSTRUCTION AND MAY ONLY BE
TERMINATED AFTER ROOF SLAB HAS BEEN INSTALLED.

(SEE NOTE 8)
IL PVC WATER 11. ALL STRUCTURAL DETAILS TO BE VERIFIED BY
STOP 100 100 100 DESIGNERS / CONSULTANTS.
CONSTRUCTION

500 500
400

JOINT LEGEND
REINFORCED
CONCRETE BASE
DETAIL 1 REINFORCED CONCRETE
50mm THK. CEMENT/SAND SCALE 1:20 SOIL COMPACTED TO 95% MDD
SCREED 50mm THK. CEMENT/SAND SCREED
1500 TANKING MEMBRANE TANKING MEMBRANE PLAIN CONCRETE
75mm THICK C20 BLINDING 75mm THICK C20 BLINDING FGL FINAL GROUND LEVEL
1000 GAUGE POLYETHYLENE SHEET 1000 GAUGE POLYETHYLENE SHEET FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
400 400 DIA DIAMETER
A = OUTLET PIPE INTERNAL DIAMETER+1200 CL COVER LEVEL
IL INVERT LEVEL OF OUTLET PIPE
GA GENERAL ARRANGEMENT
SECTION A-A SECTION B-B

REFERENCE DRAWINGS AND DOCUMENTS


STANDARD DRAWING - TANKING DETAILS 801
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT 1001
JOINT
STANDARD DRAWING - MISCELLANEOUS DETAILS 207
B FOR MANHOLES
75 THICK PRECAST CONCRETE COVER SLAB DETAIL
FOR PAVED AREA STANDARD DRAWING - REINFORCEMENT DETAILS 1000
SEATING RINGS BEDDED IN 1 PART
SEE DETAIL A FOR HINGE DETAILS (SERIES)
750 CEMENT / 2 PART SAND MORTAR
DUCTILE IRON COVER STANDARD DRAWING - STORM WATER MANHOLE FRAME 213
- DUCTILE IRON COVER AND FRAME 10 DOWEL DRILLED AND SET INTO AND COVER DETAILS
16 DIA STEP BAR CAST INTO
TO SUIT 900 DIA OPENING IN ALL
A = OUTLET PIPE INTERNAL DIAMETER+1200

COVER SLAB AT 300 CENTERS COVER SLAB WITH TOE HOLE


MANHOLES ON STORM WATER
225

PIPELINES WITH DIAMETER RANGING FINISHED LEVEL OF 150 CLASS B CONCRETE


FROM 1500 TO 3000. CARRIAGEWAY (FL) CL SURROUND
- GRP COVER WITH ADEQUATE FRAME

(MIN.)
IS ACCEPTABLE SUBJECT TO THE

450

MAX
600
ENGINEER'S APPROVAL.
A A
No. REVISION-2 APP'D 2021

250
12

± 5°
CLIENT
AT

EN
°±

OP
90
1600

AT
K
C
LO

COVER SLAB DETAIL FOR CARRIAGEWAY &


DETAIL A TITLE
HINGE DETAILS
PARKING AREAS STANDARD DRAWINGS
STORM WATER WORKS
900 1500 900
400 1500 400 DRAWING TITLE
*

B
STANDARD DRAWING G.A. OF
DEEP STORM WATER MANHOLE
NOTE : THIS DRAWING APPLIES WHERE SHAFT DEPTH IS ON PIPELINES 1500 - 3000mm DIA.
NOT GREATER THAN 6000.
SECTION C-C ROOF PLAN ENGINEER / DESIGNER TO UPDATE AND PROVIDE FULL
CALCULATIONS FOR DEPTHS GREATER THAN 6000.
FOR SHALLOW MANHOLES SEE DRAWING No. 204. DRAWN - SCALE 1 : 100
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
205

THIRD EDITION - APRIL 2022