Sunteți pe pagina 1din 3

POWER GENERATION SYSTEM

DongGuan Calsion Power System


Remarks:
Model CM280 is available for an unlimited no of hours per year with variable load not exceed 70% (average per 24 hours) of rated power, a 10% overload capacity is allowable.
Model CM300S is applicable for supplying standby emergency power for the operating time not exceed 500 hours per year, no overload is permitted.

Model No
CM280 CM300S

Power output
224/ 280 (KW/KVA) 224/ 280 (KW/KVA) 50 H Z, 2 30V / 400 V , C O S0 . 8

CALSION / MTU SERIES


All Calsion genset features with engine, alternator, control panel and engine driven fan radiator assembly installed on a common steel base-frame, complete with heavy-duty rubber type anti-vibration mountings.
Compliance Standard

Calsion generator set meets or exceeds the requirements of the following codes and standards: GB/T2820-97,GB1105,YD/T502-2007,ISO8528,ISO3046
MTU Diesel Engine OPEN TYPE GENERATOR SET

Excellent load acceptance behavior Advanced electronic MDEC /ADEC management system Faults self-diagnosis function Easy to service Low fuel consumption Emission optimized, meet German TA-Luft standard and America EPA standard. Low noise level 90dB (A) LP7M
LEROY SOMER Alternator

Compact in structure, low noise and high reliability. 2/3 winding pitch Class H insulation High efficiency Patented AREP excitation system High transient overcurrent capability Short-circuit current capability 300% in 10S Low non-linear load voltage waveform distortion Stable starting capability
Warranty and After-Sales Services

ACOUSTIC CANOPY TYPE

Worldwide services support for major equipment and components. 12 months after T&C or 14 months after delivery which ever comes first.

20 / 40FT CONTAINER TYPE

YOU R GL OB AL PAR TNER IN PO WER GENERA TI ON SYST EM


05-2010

Genset Specification

www.calsion-cn.com

Genset Performance Data


Voltage Regulation Variation from 0-100% Steady State Variation Transient Variation Recovery time _ 5% + _ 1% + _ + 0.5% _ + 15%-20% 1-3sec Frequency _ + 1 0% _ 0.2 5 % + Isochronous _ + 7%-10% 1-3sec

Available Options
Engine
Coolant heater Auto refill lube oil pump system Heavy duty air filter

Cooling system
50 ambient radiator Remote radiator Heat exchanger Oil temperature indication

Engine Performance Data


Type
4-stroke, reciprocating type

Starting system
24V DC Drive

Alternator
Anti-condensation heater Thermistors PMG / AREP Excitation

Cylinder
V arrangement

Battery charging alternator


28V DC Dynamo

Aspiration
Turbocharged, Air- Air intercooled

Air filter
Dry element air cleaner w/ indicator

Other accessaries
Residential type silencer Maintenance-free battery Ni-cd battery

Governor
Electronic

Fuel filter
Fuel prefilter with water separator

Cooling system
water cooled
4 0 ambient radiator with engine -driven pusher fan

Lube oil filter


Spin-on paper element full flow

Protection breaker
4 pole MCCB / ACB

Fuel System
Daily fuel tank Under ground storage tank High / Low fuel level warning

Alternator Performance Data


Type
Brushless

Cooling method
Air cooled

Control System
Remote control and monitoring Fully auto synchronizing Under volt relay

Excitation System
Shunt excitation / PMG / AREP

Total harmonic distortion (THD)


3 %

Pitch winding
2/3

Wave form (TIF)


50

Earth fault protection relay L.V. Switchboard


4 Pole ATS / MTS Synchronizing panel Cap bank

Bearing
Single

Wave form ( THF)


2%

Insulation class
Class H

Overspeed
2 2 5 0 R PM

Protection class
IP 23

Standard Accessories and Manuals


Industrial type silencer Flexible pipe Flange Exhaust pipe elbow Tool kits Lead acid battery and battery cable Engine Manual Alternator Manual O&M Manual Testing report and certificate Control diagram

Silenced Genset
Weather-proof canopy set Sound-proof canopy set Container type acoustic set Towable genset Mobile genset

Genset Data
Genset model Engine make Engine mode: Bore and stroke: (mm) CM280/CM300S MTU 6R1600G10F 122x150 6In-Line 10. 5 17. 5: 1 (rpm) (m 3/h ) 1500 Turbo charged 1080 15 3240 495 Fresh water forced circulation 22680 1.7/1.3 90 45 48 El ect roni c/ AD EC Direct inj ect ion 88 Ler oy Som er LSA 46. 2 L9 ( KW/KVA ) 224/ 280 Shunt Brushless R448 3- phase ,4- wire IP23 H 300%(3In):10s

Number of Cylinder and arrangement Displacement (liter) Compression ratio: Engine speed Aspiration Combustion air flow Exhaust gas flow(m 3/h ) Exhaust gas temperature () Cooling method Cooling air flow (m 3/h ) Min. air intake/exhaust area Heat rejection to coolant Oil pan capacity Fuel consumption Governor Combustion type Noise level at 7mm Alternator make Alternator model Nominal rating Exciter type Alternator type AVR model Connection Protection class Insulation class Sustained short circuit current (m ) (KW) (liter) (L/h)
2

Max. exhaust back pressure(kPa)

Prime rating: CM280


VoltageV 380/220 400/230 415/240 CurrentA 425 404 390 KW/KVA 224/280 224/280 224/280

Standby rating: CM300S


VoltageV 380/220 400/230 415/240 CurrentA 456 433 417 KW/KVA 240/300 240/300 240/300

Dimension and weight


Length(L) mm 2800 Width( W) mm 1150 Height(H) mm 1650 Net weightkg 2500
Dongguan Calsion Power System Co.,Ltd.

Email: root@calsion.cn

www.calsion-cn.com

INFORMATION AND DATA MAY SUBJECT TO CHANGE WITHOUT NOTICE

S-ar putea să vă placă și