Transformer Protection in Transmission Networks

Transformer Protection in Transmission Networks


ABB Power Automation Ltd
T2314 / trafoprot_a.ppt / F1 of 44

ABB

Transformer Protection in Transmission Networks


Power transformers in a power system 400 kV AC Transmission

130 kV Subtransmission Generation MV Distribution LV

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F2 of 44

ABB

Transformer Protection in Transmission Networks


Different vector group and neutral connections

Yy YN yn0 (d1)

Yd YN d1

Dy D yn11

Yd+z YN d11 + zn

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F3 of 44

ABB

Transformer Protection in Transmission Networks


Different winding arrangements

2 windings + unloaded tertiary

3 windings e.g. Yy 6 d1

Autotransformer + tertiary e.g. YN Auto d1

2-winding transf. + Auxiliary transformer

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F4 of 44

ABB

Transformer Protection in Transmission Networks


Possible Faults Insulation breakdown Short circuits phase-to-phase Inter-turns Ground faults Overvoltage U> (overexcitation U/f>) Overtemperature Oil leakage or contamination Oil level monitor Reduced cooling
ABB Power Automation Ltd
T2314 / trafoprot_a.ppt / F5 of 44

ABB

Transformer Protection in Transmission Networks


Possible Transformer Failures Winding failures Tap changer failures Bushing failures Core failures Miscellaneous failures

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F6 of 44

ABB

Transformer Protection in Transmission Networks


Selective Protection of:

- two or - three winding transformer - autotransformer - generator-transformer unit


Detection of:

- all-phase faults - earth-faults at solidly or low-impedance earthed systems - interturn faults


ABB Power Automation Ltd
T2314 / trafoprot_a.ppt / F7 of 44

ABB

Transformer Protection in Transmission Networks


Recommended Transformer Protection
Functions up to 2 MVA Gas Detector Relay (Buchholz) Overload Protection (Thermal or temperature monitoring relay) Overcurrent Protection Differential Protection Ground Fault Protection Voltage Regulating Relay Overexcitation Oil level monitor for exposed overvoltage situations Rating 2 - 5 MVA less 60 MVA over 60 MVA

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F8 of 44

ABB

Transformer Protection in Transmission Networks


Transformer Protection Basic Versions
Transformer Protection Basic Versions
Type of Transformer Unit Prot.
Transformer Rating High-Voltage Side Medium-Voltage Side Low-Voltage Sid S < 60 MVA S > 60 MVA Prot. 2 Prot. 1 Prot. 2 (Back-up) (Main) (Back-up)

Prot. 1 (Main)

2-Winding (Star/Delta)

Id Id Id Id Id Id Id Id Id Id Id + REF Id + REF

REF

I> + IN + TH + SBEF I> + IN + TH + SBEF I> + IN + TH I> + IN + TH I> + IN + TH I> + IN + TH I> + IN + TH I> + IN + TH I> + IN + TH I> + IN + TH I> + IN + TH I> + IN + TH

I> I> I> + IN + SBEF I> + IN + SBEF I> + IN + SBEF I> + IN + SBEF I> + IN + SBEF I> I> + IN + SBEF I> I> + IN I> + IN I> + IN I> + IN I> I> + IN + SBEF I> + IN + SBEF

2-Winding (Star/Stern)

REF

REF

2-Winding (Star/Delta) + Earth.transf.

REF

3-Winding (Star/Star/Delta)

REF

REF

3-Winding (Star/Star/Delta) + Earth.transf.

REF

REF

2-Winding (Auto) 3-Winding (Auto)

Remark: The SBEF-Function (Stand-by EF Prot.) is only needed if earthing resistor is installed

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F9 of 44

ABB

Transformer Protection in Transmission Networks


Transformer protection example (1)
I >> I> IN TH

Bu / LOL OT / WT

I IN
REF

IN I>

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F10 of 44

ABB

Transformer Protection in Transmission Networks


Transformer protection example (2)
- Differential prot. (87T) - REF (87N) - Overcurrent (51T) - E/F protection (51N) - Thermal overload prot. (49) - Overvoltage prot. (59)

I> 51T 87T REF 87N

u 49 I0 51N

87T

U> 59

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F11 of 44

ABB

Transformer Protection in Transmission Networks


Transformer protection example (3)

I> IN
Bu / LOL OT / WT

TH

Id I> I> IN

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F12 of 44

ABB

Transformer Protection in Transmission Networks


Transformer protection example (4)
I >> I> IN TH

REF

Bu / LOL OT / WT

I REF

Id I> IN I>

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F13 of 44

ABB

Transformer Protection in Transmission Networks


Differential protection (87T) Causes phase faults in the protection zone effects high currents potential damage to transformer winding expensive outage and repair due to damage Features / requirements
low impedance principle for two and three-winding transformers non-linear current-dependant tripping characteristic high stability during throughfault and CT-saturation compensation for vector group compensation for current amplitude (CT-ratio) inrush restraint

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F14 of 44

ABB

Transformer Protection in Transmission Networks


Features

Differential Protection includes:


C.T. Ratio adaption Connection group adaption Back-up functions Large setting ranges

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F15 of 44

ABB

Transformer Protection in Transmission Networks


Differential protection (87T)
Id= I1+I2 by external faults can due to -ratio errors -saturation -losses in the transfomer -tapchanger a differential current can occur, therefore a stabilized tripping characteristic is needed Inrush can also provoke differential current

87T

Protection zone

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F16 of 44

ABB

Transformer Protection in Transmission Networks


Differential protection (87T)
Features True measurement for three-wind. transformer compares the greatest current the with sum of the two others I-instantaneous independ. of inrush Inrush eval.ratio 2nd.harm to fundamental detection of largest phase current detection of energised transformer using load current Adaptive characteristic (b-line)

Id/ IN
Trip Trip for I1 / IN < b or I2 / IN < b

g-high g b

No Trip

Ih/ IN

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F17 of 44

ABB

Transformer Protection in Transmission Networks


Differential protection (87T)

A
AI 1,2,3

DIFF

A
AI 7,8,9

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F18 of 44

ABB

Transformer Protection in Transmission Networks


Differential protection for 3 windings

AI 4,5,6

DIFF

AI 1,2,3

A D
AI 7,8,9

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F19 of 44

ABB

Transformer Protection in Transmission Networks


Differential protection 87T

800/ 5 300MVA 220/ 18 KV 30MVA 18/ 6 KV

87GT

10'000/ 5

CT's at the Aux. transformer must have the same ratio as the other two. Correction of the ratio with Ref.-Value or a-Factor in the protection function

300MVA 18 KV

10'000/ 5

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F20 of 44

ABB

Transformer Protection in Transmission Networks


Fault inside protected zone

I1

I2

DI 4 3

cos a < 0 IH = 0

2 1 g 1 2 3 4 5 IH

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F21 of 44

ABB

Transformer Protection in Transmission Networks


Fault outside protected zone Low short circuit current Load
I < (1.5...3) * Irated

I1

I2

DI 4

cos a = 1

3 2 1 g 1 2 3 4 5 IH v=50%

IH =

I1 I2 cos a

IH = I1 = I2 = ILoad < (1.5...3)*Irated


ABB Power Automation Ltd
T2314 / trafoprot_a.ppt / F22 of 44

ABB

Transformer Protection in Transmission Networks


Fault outside protected zone High short circuit current Isc
I > (1.5....3) * Irated

I1

I2

DI 4

v= infinite

cos a = 1

3 2 1 g 1 2 3 4 5 IH v=50%

IH =

I1 I2 cos a

IH = I1 = I2

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F23 of 44

ABB

Transformer Protection in Transmission Networks


Operating characteristic of the RE..16 differential protection
Operation Operation for
I1 <b IN I2 <b IN

I1

I IN

Protected unit

I2

ID = I1 + I2 + I3 ....Operating current IH .....................Restraint current IH = I1 I2 cos for cos 0 IH = 0 for cos < 0 where : I1 = greatest of I1; I2 I2 = ID - I1 = (I1; - I2)

or

v g 1 b 2 3

Restraint
IH IN

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F24 of 44

ABB

Transformer Protection in Transmission Networks


Vector group adoption for Yd5 transformer

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F25 of 44

ABB

Transformer Protection in Transmission Networks


Restricted earth-fault protection (REF)
AI

Id
REF

Trip

Used at direct and low impedance earthing Clears internal EFs instantaneously Unaffected by inrush current and external fault

Id
REF

Trip

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F26 of 44

ABB

Transformer Protection in Transmission Networks


Thermal overload protection
Rise of temperature

0,63

t
ABB Power Automation Ltd
T2314 / trafoprot_a.ppt / F27 of 44

Time

ABB

Transformer Protection in Transmission Networks


Overexcitation protection
t

Definite

V/Hz inverse

V/Hz

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F28 of 44

ABB

Transformer Protection in Transmission Networks


Requirements for overcurrent protection Fast operation for primary short circuit Non operation for inrush Discrimination with other overcurrent protection Non operation at short or long term overload Back up protection for network faults, outside the transformer

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F29 of 44

ABB

Transformer Protection in Transmission Networks


Application, typical HV bay
Control unit

OFF 1
R

Busbar protection

C E

ON OFF 2

Transformer protection

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F30 of 44

ABB

Transformer Protection in Transmission Networks


Protection function structure
150 / 1 A Ir1 = 120 A Ir12 = 0,80 A A/D conv. Trip logic DIFF

145 kV 30 MVA

150 / 1 A

IrN12 = 0,80 A

11 kV
Ir2 = 1575 A 1600 / 1 A

11 kV 110 V 3 3 Ur22 = 110/3 V

F i l t e r i n g

TOC REF NOV etc.

Trip

Ir22 = 0,98 A

BI

>1

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F31 of 44

ABB

Transformer Protection in Transmission Networks


Main functions
Compact design including: Basic SW functions and transformer protection functions: - Overcurrent protection - Logic functions, delay & counter - FUPLA - Check functions (I, U) - Disturbance Recording

(Definite time or inverse functions)

- Thermal overload - Differential protection - Overvoltage protection - Distance protection - Overexcitation U/f - Metering U I f P Q

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F32 of 44

ABB

Transformer Protection in Transmission Networks


Main Features
- No interposing CT's - Standard wiring diagram - Inputs for external functions (Buchholz, temperature sensors) - Programmable indication of tripping and signalling - Indication of measuring values - Continuous self-monitoring - Modular SW protection functions - 4 serial interfaces: * one front for local commmunication (PC) * one rear for remote communication SPA or VDEW6 * two others (spare) - Member of the 316*4-family and part of PYRAMID - Fits into ABB solution
ABB Power Automation Ltd
T2314 / trafoprot_a.ppt / F33 of 44

available

ABB

Transformer Protection in Transmission Networks


Transformer Protection Options I> back up Sensitive earth fault I0> for not grounded windings Restricted earth fault (High impedance principle) Thermal overload U>, U< Distance Protection

2W only 2W only

2W only 2W only

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F34 of 44

ABB

Transformer Protection in Transmission Networks


Redundancy
Q1 Q51 Q0 Q53 Q9 Q2

A
Protection Functions Additional Logic Monitoring Communication Power Supply

SCS/ SMS
B8 B9 C1 T1

Station A
T2

C2

B1

B2 B7

B3

B4

B5

B6

C7

B
Protection Functions

1252 123 123 123

123

123

123

123

123

123

123

123

123

123

123

123

DEC 3000 AXP Alpha

Additional Logic Monitoring Communication Power Supply

INTERBAY BUS COMMUNICATION

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F35 of 44

ABB

Transformer Protection in Transmission Networks


Redundancy example
Transformer protection

C E

Transformer protection

C E

ABB Power Automation Ltd


T2314 / trafoprot_a.ppt / F36 of 44