Sunteți pe pagina 1din 12

. _._.

P.
WOODWARD

PART III

PARALLEL OPERATION OF ALTERNATORS


*c ii .J

THE CONTROL OF PRIME MOVER SPEED is published as a series of four manuals, each complete in itself, which together constitute a complete manual on general theory. The Table of Contents for all of the four parts is as follows:

SYSTEM PART I . . . . . .THE CONTROLLED Fundamental Mechanics Speed Control Methods Effects of Prime Mover Characteristics Effects of Load Characteristics PARTII . . . , .SPEED GOVERNOR FUNDAMENTALS
Speed Sensing Devices Centrifugal Ballhead Hydraulic Servomotor Speed Droop and Regulation Temporary Speed Droop (Compensation) lsochronous Governor Derivative Control (Acceleration Sensitive Load Sensitive Governor Summary of Woodward Governor Types

Governor)

PART Ill..

. . .PARALLEL

OPERATION

OF ALTERNATORS

Fundamental Electricity and Magnetism Elementary Generator and Motor Alternating Current Three-Phase Alternating Current Infinite Bus Synchronizing Torque Load Division Amortisseur or Damping Windings Natural Frequency of Oscillation Resonance Computation of Natural Frequency

. c

PART IV. . . . .MATHEMATICAL

ANALYSIS

Equations of Motion Approximations Solution of Second Order Equation Critical Damping Frequency Response Assumptions of Linearity Uncompensated lsochronous Governor Uncompensated lsochronous Governor Stabilizing Effect of Speed Droop First Order Time Lag Time Constant Dead Time or Transportation Lag Spring Driven Oil Damped Ballhead Absolute Damping Relative Damping

on Hydraulic Transmission on Diesel Engine

P c

@Woodward

Governor

Company

1981

MANUAL THE CONTROL

2503 I

OF PRIME MOVER SPEED

PART III PARALLEL OPERATION OF ALTERNATORS

This manual, with Parts I and of Speed Governing. It also Driven Alternators and much ward Governor Application to

II, replaces our Manual 25010 Fundamentals replaces 25016 Parallel Operation of Engine of 25012 General Requirements for WoodInternal Combustion Engines.

t i i :

THE CONTROL PART Ill: PARALLEL

OF PRIME MOVER SPEED OPERATION OF ALTERNATORS

Despite the fact that alternating current generators, commonly called alternators, with their driving prime movers and controlling governors, have been in widespread use in parallel operation for many years, there is a general lack of understanding of such systems even on the part of many operators and engineers directly concerned. As a result we are frequently called upon to correct troubles which not only do not originate in the governor but about which the governor can do little or nothing. A simple engine driven alternator supplying an isolated nonsynchronous load is relatively easy to understand; but parallel two synchronous units and tremendous changes take place. Governor knobs that adjusted speed now affect load division, mechanical oscillations of the throttle and periodic exchanges of load between alternators arise, and units that performed beautifully alone kick up such a fuss that they wont stay on the line. Paralleling obviously does not always produce such violent results, but the potential for such behavior in some degree always exists in parallel operation, and this degree is greatly influenced by the characteristics of the controlled unit. For a better understanding of these characteristics we will turn our attention to the alternating current generator. It is obvious that a of alternating current comprehensive, but havior can be made .Ithe oversimplified which will follow. simple, nontechnical discussion and alternators cannot be very it is hoped that alternator beto seem reasonable by means of and nonrigorous explanations

a current to flow through the conductor in the magnetic field, force is required to restrain the conductor from moving, and if it is permitted to move against such a restraining force, mechanical work is done. This is the simplest element of a MOTOR. In an ALTERNATOR the magnetic field is generally established by causing direct current to flow through coils wound on part of the iron structure of the magnetic path - usually, in the larger machines, on the rotating member or ROTOR. Since voltage is generated whether the conductor moves across the field or the field across the conductor, we may choose that the conductor remain stationary while the field rotates. Such an arrangement of nonrotating conductors and iron constitutes the STATOR. If alternate north and south magnetic poles pass a conductor in the stator, the direction of the induced voltage, and hence the current, reverses periodically and an ALTERNATING CURRENT results The generated voltage in this instance will rise to a c maximum value in one direction, decrease through zero to a like maximum in the other direction, again decrease through zero and rise to a maximum in the initial direction. The variation of voltage from one maximum to the next maximum in the same direction constitutes one CYCLE. In most power generating alternators the machines are so designed and the speeds so chosen that a cycle is completed sixty times per second. That-is, the generated voltage has a FREQUENCY of 60 cycles per second. The conductors of the stator, arranged in coils, can be so placed that the maximum voltage in two separate windings will be reached at different times. For instance, consider again a rotor having one north and one south pole. A conductor at a given point in the stator will have a 60-cycle voltage generated in it if the rotor makes 60 revolutions per second or 3600 rpm. Another conductor, placed 120 around the stator in the direction of rotation, will reach its maximum at a later time. If we consider one cycle to include 360 electrical which in this example is produced in 360 mechani cal degrees rotation of the rotor, the

If an electrical conductor (a wire) is passed sidewise through a magnetic field, a voltage is induced in it, and if a circuit including the conductor is completed, this generated voltage will cause a current to flow. As soon as the current is established, force is required to move the conductor through the field and electrical power is developed from the mechanical work done in the conductor during such movement. This is a GENERATOR in its simplest form. Conversely, if some outside source of voltage causes

0 ; !

will reach its maximum 120 later than the first and may be said to be lagging the first in PHASE by 120 electrical degrees, If a third conductor is placed an additional 120 around the stator, the three voltages generated will differ in phase by 120. This is the usual 3-phase voltage relationship. Had the rotating field been made with 4 poles instead of 2, the stator conductors would have been spaced 60 mechanical degrees apart and 60 cycles would have been produced at 1800 rpm. The electrical phase relationship, however, would have remained 120 electrical degrees. The conductors of such a stator are so connected, that, normally, three terminals result, the voltage between any pair being 120 electrical degrees out of phase with the other two voltages. Since this 3-phase voltage at the terminals results from a rotating magnetic field of constant strength, it is not unreasonable to assume that if, conversely, an identical 3-phase voltage were connected to the terminals from an external source, a rotating magnetic field of constant strength would result. This is, in fact, the case, and accounts for some of the phenomena with which we will be concerned. Consider a source of such a voltage having a fixed frequency, unchangeable by anything which we can onnect to it; this is the so-called INFINITE BUS. f this source is connected to one side of an open 3-blade switch and our engine-driven alternator so connected to the other side that phase-rotation, phase, frequency, and voltage are respectively the same, the switch may be closed with no flow of power to or from our alternator. Thus, so far as the engine is concerned, the condition is no different than before the switch was closed so long as the above conditions exist. However, the dynamic characteristics of the system which the governor must control have changed greatly, and the effect of this change will be discussed later. The operation just described is performed whenever an alternator is SYNCHRONIZED and put on the line. If now fuel is increased to the engine, it will try to speed up, but it is no longer free to do so, except momentarily, being forced to run at the average dictated by the infinite bus frequency so long as the alternator SYNCHRONIZING TORQUE is not exceeded. This torque results from the interaction between the rotating field established by connection of the alternator stator to the bus (the synchronous field) and the DC field of the alternator rotor. So long as they are in phase (that is, lined up) no torque or turning effort exists; if the rotor field

leads in phase a restraining torque is exerted, work has to be done by the engine and power flows to the bus; if the rotor lags a driving torque results, power is taken from the bus and the alternator is said to be motored. Thus there is a torque proportional to the angle between rotor field and synchronous field and in the direction tending to decrease that angle to zero. The effect of this is as though the engine were connected to its load through a torsion spring. Since the speed normally changes only a very small percentage, the power fed to the bus or taken from it is also proportional to the angle by which the rotor leads or lags the rotating AC field; that is the amount the torsion spring is wound up, one way or the other. If two alternators are paralleled a synchronizing torque exists between them whether connected to a load or not because they are connected to each other, in effect, by the torsion springs. In this case, however, speed changes are possible if there is no isochronous (constant speed) governor in the system, as will be shown later. This wind-up of the spring in the comparison above is equivalent to displacement of the alternator DC field to lead the synchronous field set up by the line frequency in the actual case. The analogy also holds for the condition of lagging DC field in which power is taken from the line to motor the alternator; and for all intermediary conditions including the lined-up configuration of now power transmitted, which is desired when putting the unit on or off the line. We will now consider the effect of this synchronizing torque on the steady-state parallel operation of governed engine-alternator units. One of the primary considerations in the parallel operation of power generating machines is the proper division of load. As implied in Part I I of The Control of Prime Mover Speed series, this can be accomplished by providing a governor with speed droop which results in governor system regulation. This relationshp of regulation to load division is perhaps best explained by reference to the speed vs. load characteristic curves for the governor-engine combinations involved, bearing in mind that the units, when paralleled through alternators, are compelled to run at the same or, if the alternators have different numbers of poles, proportional speeds. For simplicity we will refer to the normal speed as 100%

speed and full load as 100% load, and will assume diesel engines as prime movers. In the controlled system we will be concerned with three types of governor operation: isochronous, speed droop and load limit (which is fixed throttle operation when in control). These we represent, as suggested, as plots of engine load (assumed proportional to servo or rack position) versus speed. The isochronous governor performance may be represented by a family of horizontal lines, each line representing a speed setting. If set to maintain the speed represented by line A, in Figure 1, and connected to an increasing nonsynchronous load, the speed would vary as follows. Beginning with no load, the speed will remain constant at A as load is increased until the capacity of the engine is reached, and then as load is further increased, speed will drop, the rack remaining at its maximum position.

100%

SPEED

I I
I I I I I 50%

\
Ai 1 I

MAX. RACK 1 POSITION 1

_.

LOAD

1 ; I , 1 100%

Figure 2

100%

I
I SPEED I I I MAX. I RACK 1 POSITION / I

I
0

/
LOAD 100%

;t
I I

Figure 1

, The speed droop governor has a similar family of curves, but slanted as shown; the greater the regulation, the greater the slope (Figure 2). Similarly loaded the speed will drop down the regulation line until maximum rack is reached and continue to drop at maximum rack as load is further increased. Suppose now that load limit is set at 50% in either case. The behavior is the same as before except that now the speed drops from the setting line when load limit torque (50%) is reached instead of

when the normal rack limit is encountered. Assume the speed droop governed machine is connected to a synchronous system so large that our engine cannot affect its frequency (an infinite bus). Now we must remember that the speed of the engine is no longer determined by the speed setting, but by the frequency of the bus so long as maximum synchronizing torque is not exceeded. What is accomplishedby a change in speed setting in this case is a change in load, not in speed. Referring again to Figure 2, we must have setting A for which the no load speed is equal to bus speed (or frequency) in order to synchronize. Once on the line, if we increase speed setting to B we do notdange speed but we pick up approximately l/2 load. Further increase in setting to line C will fully load the engine. If regulation, as indicated by slope of lines, is 4%, and the alternator is disconnected from the bus while carrying l/2 load, the free engine will go up in steady-state speed 2%. If set on line C, carrying full load and similarly disconnected, the no load speed would be 4% above synchronous or 100% speed. If the speed droop were zero, that is, if the governor were isochronous, paralleling with an infinite bus would be impractical for the reason that a speed setting above synchronous speed by however small an amount would, since actual speed would be below the setting, call for full rack. Similarly if th setting were even slightly below actual speed,

A.---

racks would go to fuel off position. Therefore, governors should not be paralleled isochronously with any system so big that the governed unit cannot affect its speed. If two identical units having speed droop governors are paralleled with each other and there are no other generating units in the system, the frequency will be determined by the speed settings of the governors, the regulation of the governor-engine combination and the total load on the system. Here, as before, it must be remembered that the actual speeds of both units must be identical even through their speed settings may be different. Assume both units to be set on curve A, in Figure 3, and the total load equal to the capacity of one unit, that is 100%.

load B, so the effective capacity of the system is only 150% instead of the 200% it would have if the speed settings were identical. If the load were dropped to 50%, it would all be carried by B and A would be unloaded with system frequency at f3. If the regulations are not the same a similar improper division of load results.

SPEED

i SS-213% i &, SPEED

50% LOAD

75%

100%

25% ;
0

50% I I LOAD

75% I I

100% I I

Figure 4

Figure 3

In this case each engine carries 50% and the speed is that of line fl, being the same for both units. Suppose now that one unit is set at B, the other remaining at A. The speed at which both units can run and carry a total of 100% load is now f2, and the load is unequally divided, 75% to the unit with the higher setting, 25% to the lower. The increase in system speed however is by no means as great as the increase in speed setting of B. If now, with settings A and B, the load is increased to 150%, the regulation being the same for both units, the additional 50% will be divided equally between them and A will again carry 50% while B carries 100%. The speed of the system will again be back to fl. Further increase, however, will over-

If two units having different regulations are adjusted so as to carry 50% load each at speed fl and the load is subsequently increased to a total of 150%, it will be divided unequally, as for instance in Figure 4 in which regulation B is twice regulation A, the latter will take 2/3 of the load increase and the new speed will be f2. Readjustment of speed setting of B to B1 will again equally divide load and change speed to f3. Any value of speed.can subsequently be achieved by adjusting both A and B, maintaining the intersection of their speed lines at 75% load. A special case of the above is that in which one unit has zero regulation or is isochronous. This is identical with the case of the infinite bus within the ability of the isochronously controlled machine to maintain its set speed. All permanent load changes

.i must be taken by the isochronous machine. As shown in Figure 5, 50% is carried by each. If the load were increased to a total of 150%, the droop unit would still carry 50% and the isochronous unit would be fully loaded. Further increase in load would overload the latter and system speed would drop, allowing the droop unit to pick up part of the load. If load were dropped to 50% total, it would all be carried by the droop unit. Further decrease in To make the transient peculiarities of an enginedriven alternator on synchronous load more apparznt, it will be helpful to consider first the behavior of a unit on nonsynchronous load. Suppose for c . example a gas engine to be operating at fixed throttle with its alternator supplying a nonsynchronous load such as lamps. It is assumed that the throttle is so positioned that the connected load is carried at the desired speed, say that which produces a frequency of sixty cycles per second. If now a small amount of load is added, all that happens is that the speed decreases; not instantaneously because of the flywheel effect, that is, the energy stored in the rotating machine. However, the engine will, in time, come to equilibrium at some lower speed without oscillation. Similarly, a small change in throttle position would cause the system to seek a new equilibrium speed, gradually approaching its new value without overswing. If the governor were operative, it would, of course sense the speed deviation and move the throttle to correct for it. It should be noted that with the governor active a load change may, depending upon the adjustment of the stabilizing mechanism of the governor (compensating system), produce an oscilla- tory return to equilibrium; in fact governors are usually so adjusted in order to secure the most satisfactory recovery from a disturbance. This fact makes the difference between paralleled and nonsynchronous operation much less obvious because the observer sees only the oscillations resulting from a disturbance, and not the reason for the oscillations. Consider now the engine driven alternator paralleled with an infinite7Xls. One important difference is at once apparent; the speed is no longer determined by the throttle position and load but by the frequency of the bus. The throttle position now determines the power output of the engine and hence the load carried by the alternator. Another and less obvious characteristic is that if a sudden change in throttle position or load occurs an oscillatory transition to the new equilibrium condition results even with the governor inoperative. The explanation for this difference in behavior is to be found in the following. The effect of the synchronizing torque has been compared to that of connecting the engine to its load through a torsion spring. Insofar as the dynam- c .. ic characteristics of the system are concerned, this

SPEED

I 1
0

LOAD Figure 5

load would result in an increase in system speed, the isochronous unit being motored by the droop unit at a speed above its setting. In practice such a system has the advantage of maintaining constant system frequency and the extreme conditions described are avoided by readjustment of the speed setting of the droop unit to change its portion of the load so as to keep the isochronous unit as near half load as possible. What has been said above applies to governors which are sensitive only to speed. In cases in which means are provided to respond to unit load as well, it is possible to parallel units, properly divide load, and still maintan isochronous operation. The Woodward Type LSG is capable of such operation. i I Thus far we have been concerned only with the steady-state or equilibrium characteristics of the controlled system in parallel operation, although it was implied that the transient or dynamic characteristics were greatly affected by synchronization. This phase of the problem is especially important to us since governor performance is usually judged by the behavior of the controlled system following a sudden disturbance of equilibrium.

-~--;

-Ic-.--

---.-

__.-

-~~--

____

-~

..-

analogy was incomplete in that the mass or inertia of the rotating machine and the damping forces present were neglected. Since the engine and alternator do have mass, this, in combination with the spring action, results in a system capable of oscillation at some natural frequency. If only the spring action of the synchronizing torque and the inertia of the rotating mass were present, these oscillations would continue for a long time after a disturbance, as would the swings of a frictionless pendulum suspended in air. Also since the power generated by the alternator is roughly proportional to the position of its rotor relative to the synchronous field, such oscillations would result in power swings of like frequency and proportional magnitude. In the case of the pendulum mentioned above, the oscillations would die out much more rapidly if it were immersed in oil. To similarly help damp out the oscillations resulting from a disturbance of the alternator, AMORTISSEUR WINDINGS should be provided in the pole faces of the rotating field structure. These windings act to oppose a change in angle of the rotor relative to the rotating AC field and to damp out the pendulum-like swings by absorbing energy (which is converted to heat) so long as oscillations persist. Their operation depends upon exactly the same natural phenomena as does the generation of useful power. When the rotor is running synchronously and without oscillation the amot-tisseur winding bars or conductors do not move relative to the rotating synchronous field. If the instantaneous speed of rotation of the rotor is greater or less than that of the synchronous field, as is the case during oscillation, this relative motion of conductor and magnetic field induces a voltage in the bar which produces a current resulting in a force opposing the oscillation. Because of the resistance of the bars, this circulating current dissipates the pendulum-like energy of the oscillation in heat, resulting in eventual return to a nonoscillating condition of rotation at constant speed.

combination with the rotating mass result in a pendulum system which oscillates or swings after a disturbance, the amplitude of successive swings being decreased or damped in proportion to the effectiveness of the damping or amortisseur windings. In the nonsynchronous case there is no synchronizing torque and therefore no spring against which the mass of the rotating machine can swing; there is, therefore, no tendency on the part of the unit with fixed throttle to oscillate following a disturbance. This obviously does not mean that an isolated unit cannot oscillate or swing in speed due to other causes such as cyclic variation in developed torque or improper adjustment of the governor. However, oscillations in such cases do not produce the large swings in power which characterize the paralleled case but show up instead as variations in frequency. The paralleled unit has, therefore, in common with all such spring-mass systems a natural frequency of oscillation at which it will swing after a disturbance. It is characteristic of such systems that if they are repeatedly pushed at regular intervals of the proper frequency, the amplitude of the resulting load swings may build up to a large value even though the disturbing impulse is small. When the frequency of the disturbing force is such as to produce the maximum amplitude the system is said to be in resonance. This happens when the forcing impulses occur at the NATURAL FREQUENCY of the system. These periodic forcing impulses may come from a regularly varying load, recurring variations in developed torque due, for instance, to a weak or misfiring cylinder, or to an unstable auxiliary control such as a voltage regulator or fuel gas pressure control. Regardless of the source, if such disturbances occur at frequencies approaching the natural frequency of the system, load swings will result which may become so large as to make parallel operation impossible. The same unit at the same load on an isolated or nonsynchronous system may be and frequenly is perfectly satisfactory in operation, not because the forcing disturbance is any less, but because, lacking the synchronizing torque of parallel operation, there is no resonant condition to produce amplification of the swings. If a resonant condition exists, the governor can do little to correct it; in fact, in some cases it is aggravated by the governor. Nevertheless, it often happens that the throttle movements produced by the governor in response to the small periodic changes that accompany these load exchanges are thought to be the cause rather

/ I

b I I
I

It may be seen from the foregoing that a fundamental and very important difference exists between paralleled or synchronous operation and isolated or non synchronous operation. In the synchronous case the existence of the synchronous field supplied by the bus results in synchronizing and (with amorisseur windings) DAMPING TORQUES which do exist in the isolated alternator. These torques in

than the result of the difficulty, as is actually the case. This can be demonstrated quite easily in most cases by blocking the throttles with the load limit or by other means. If the trouble is of the sort described above, the load swings will continue, although some change in magnitude may be observed. The preferred treatment of this problem is to avoid it by selection of the WKZ to give a natural frequency well away from any possible forcing frequencies, such as the firing frequency of a given cylinder. In any case, the magnitude of the swings will be minimized by the introduction of the maximum feasible amount of damping. This is done in an alternator by the use of fully connected amortisseur windings in the field pole faces. It should be noted that the natural frequency of oscillation of an alternator on synchronous load depends upon its inertia of WK* and the synchronizing torque, which in turn depends upon the design of the alternator, the load carried, and the characteristics of the transmission line and paralleled generating equipment. This fact makes double important the utilization of maximum damping in the amot-tisseur windings so that oscillations which do occur may be of minimum amplitude and die out as quickly as possible. In any event, the implication is that a range of frequencies must be avoided when designing spring drives or considering possible forcing impulses. In determining the required WK* so that resonance is avoided, the natural frequency of oscillation must be determined. For a single machine on an infinite bus this frequency is represented by the following equation:

For two machines paralleled, the natural frequency of load exchange between them may be represented by:

l+
+1,2 =

=I m2

x
\

35200 N1

PC1 x F
X

2 2

l+Lx-

[ li.
P N2 N1 Pr2

For more machines in parallel it is possible by more complicated expressions to determine the natural frequencies of all the various modes of oscillation, as for instance with three units, No. 1 with No. 2, No. 2 with No. 3, No. 1 with No. 3. It is useful to know, however, that if all machines are computed according to the first formula for a single machine against an infinite bus, the natural frequencies of any pai in combination will lie between the lowest and high est figures obtained by such computation. The implication of this is that there should be no forcing frequencies within this entire range, or in fact within 20% of either end of the range. Since in general, the forcing frequencies cannot be controlled, it follows that the range of natural frequencies of oscillation should be so established by choice of WK2 as to avoid resonance. Since this is only one considerati* in the choice of WK*, (others being engine criticals, speed deviation, speed recovery time and cost) difficulty in arriving at a satisfactory compromise is sometimes encountered. The difference in control characteristics between a unit isolated and paralleled is of interest for another reason. The manner in which any control system behaves is determined by the dynamic characteristics of the governed system. The purpose of governor adjustment is to so determine the governor characteristics that, when combined with those of the controlled system, satisfactory results are obtained. This implies first that the system is stable, that it returns to the desired equilibrium speed after disturbance; and second, that the speed (or load)

~~35200

I 1
-

P,xFK

WK2

in which = = Pr F = WK2 = N =

natural frequency in cycles/minute synchronizing power in KW/electrical radian system frequency in cycles/second moment of inertia in pounds feet squared revolutions per minute of the machine

10

.
deviation is not too great and that the error is corrected quickly and without excessive oscillation. It follows therefore that a change in system characteristics such as described above should be accompanied by readjustments of the governor for best results. This can be accomplished in the Woodward water wheel governors by use of the solenoid operated bypass in the compensating system. However, since this is not feasible in the case of the diesel governors, the adjustment used is necessarily a compromise. In general a compromise can be found that is acceptable for all normal conditions of operation, but occasionally a unit has such bad paralleled characteristics that satisfactory performance both on and off the line is impossible with a single set of adjustments.

at the heart of the system

it P._

since 1870

Corporate

Headquarters

Rockford, Illinois, U.S.A.

Branch Plants
Fort Collins, Colorado, U.S.A. Stevens Point, Wisconsin, U.S.A. Sydney, N.S.W., Australia

Subsidiary

Operations

Woodward Governor Nederland B.V. Hoofddorp, The Netherlands Woodward Governor (U.K.) Ltd. Slough, Berks., England Woodward Governor GmbH Lucerne, Switzerland and Hoofddorp, The Netherlands Woodward Governor (Quebec) Ltd. Montreal, Quebec, Canada Woodward Governor (Japan) Ltd. Tomisato, Chiba, Japan Woodward Governor (Reguladores) Limitada Campinas, S.P., Brazil

WOODWARD GOVERNOR COMPANY


Hydraulic Turbine Controls Division 5001 North Second Street P.O. Box 7001 Rockford, Illinois 61125-7001, U.S.A. Phone 615/877-7441-Telex 25-7410

S-ar putea să vă placă și