Synchronous Motors Induction motors Squirrel cage Single cage Double cage Slip ring induction motors. Induction motors are also available which work in single-phase. Split phase induction motor Capacitor induction motors, Universal induction motors, shaded pole induction motors, Repulsion motors. Motors are also classified According to speed According to mounting According to duty cycle According to enclosure
Rotor:
Rotating part of the motor supported at the two ends with the bearings. Made up of silicon steel laminations with slots near the periphery. Copper or alluminium bars are housed inside the closed slots and are riveted / welded to solid metallic rings on either side called end rings. Some rotors have double cage winding. Generally the outer cage is built with brass and inner cage is built with copper conductor with larger cross section compared to the outer cage.
Faults that can occur in Induction Motors: Electrical faults in a motor are Short circuit in the winding
It reduces the resistance value of one phase In star connected motor the healthy phases will have line voltages instead of phase voltage In delta connected motor it is effectively shorting the two phases In either cases the healthy phases will draw higher current that the rated one Overheat the windings and burn if the protective device fails to act The short circuit in one phase produces a strong unbalance of he field polarity of the motor since there is absence of the field poles in the unhealthy phase winding. It fails to start or starts very slowly with noise. Leads to heating of main wires leading to burning of the wires. Mainly due to ageing of the insulation. Can be located with measuring the resistance of each phase winding Complete rewinding of the motor is the only solution
Failure of insulation between the winding and the body of the motor
The current instead of returning to the mains partly flow to ground through the motor frame. Aging and deterioration of insulating varnish Bad workmanship while inserting the oils into the slots of the stator. Abrasion of winding wires during assembly of motors Testing is by insulation tester.
Single Phasing
Discontinuity in one of the supply phases
Rotor faults
Mechanical damage in the squirrel cage rotor bars or end rings Winding problem in the case of wound rotor
Short circuit protection: Short circuits in the motor winding or external to the winding causes excess drawal of current as the short circuit practically reduces the load resistance to zero. Overload results in the overcurrents depending on the extent of overload Since the load resistance is zero in short circuit condition leads to very high value of overcurrents May cause damage to the associated equipments Protection is provided by Fuses in the circuit of every motor.
Standstill motor will not start in single phasing condition and gives humming sound. If the fault occurs when the motor is running, it will continue to run with squeezing sound till it gets isolated by the protective device. Generally bimetallic overload relay provides phase failure protection also since this also results in overcurrent. Protection against single phasing is provided in the cases of large motors and critical duty motors.
Electrical checks:
Maintenance of Motors:
Cleaning of motors:
Dirt, metal dust etc get into motors with cooling air and weaken the insulation Clog the cooling ducts and the air gap Blow motors periodically with low pressure dry air. Blowing should be in a direction opposite to that of the cooling air.
Insulation resistance:
Check periodically Depends on temperature, moisture cleanliness of motor, its age, test voltage and duration of its application. Observations to be made under similar conditions and at regular intervals. The recommended test voltage is 500 volts dc. applied for a period of one minute. To avoid damage to insulation, low test voltage may be applied in the case of low voltage motors which also happen to be dirty and wet. The windings to be tested should be allowed time to discharge any residual charge. The recommended values for insulation resistance in mega ohms for 220 Volts motor is 0.2 and for 440 V motor is 0.4.
Rotor Maintenance:
Check Rotor bars for loose or break in the slots Jarring noise while staring the motor is the indication of broken rotor bars Where the visual inspection is not possible, application of low voltage to the stator and rotating the rotor manually can detect the fault. The variation more than 3% in the current is an indication of the fault. Repair of bars is only by welding, brazing though it is tough since it is copper to copper aluminium to aluminium welding. Check windings similar to the methods adopted for stator winding. Bearings: Ball bearing, Sleeve bearings, Roller bearings are normally used for motors.
Ensure Lubrication Frequency of lubrication Maintain oil level Oil change at regular intervals. Maintenance of Lubricating wick wherever applicable. Correct grade of oil should be used. Follow standard procedure while mounting and removing.
Bearing replacement:
Use of bearing puller Application of force to only to the races (inner or outer depending on the case) Bearing should be removed from the carton just before the assembly. Bearing fit should be adhered. Only tapping force should be applied. Shaft should be free from rust, dirt etc. Attention should be paid to end clearance so that the rotor can take a position exactly in the magnetic centre of the winding. Otherwise there will be end thrust on the bearing leading to overheating. The normal temperature of a correctly fitted bearing will be around 50 degree centigrade.
Motor overhauling:
Overhaul periodically, depending upon the severity of service. Motor windings should be cleaned with solvent like carbon tetra chloride, after blowing away all dirt etc. Dry after the cleaning, if necessary, apply varnish
Alignment of Motors:
Check air gap all round the rotor. Measure the gap at 12.00 and 6.00 clock positions in vertical plane and 3.0 clock and 9.0 clock positions in horizontal plane. Turn one shaft through 90o check the gap in all the four positions. The difference in corresponding readings should not exceed 0.05mm. Turn the same shaft is turned further though 90o and the gaps are measured once again. The difference between the readings should be the same as before. In the case of belt driven loads the two shafts should be level as well as parallel. Final checking of the level should be done with a level indicator.
Storage: Store in a clean and dry place. The machined parts have a protective coat of anti rust preservative which should not be taken off during normal storage. In case of long storage periodic examinations should be carried out and fresh preservative be applied if necessary.
Drying:
In a drying oven Blocking the rotor and circulating current at low voltage of about 10% of the rated voltage, Using incandescent lamps. Glow heaters.
According to the starting methods the single phase motors can be classified as follows: Split Phase Motors Plain split phase motor Capacitor start induction run motor Capacitor start capacitor rum motor Permanent capacitor motor Shaded pole motor Repulsion motors Plain repulsion motor Repulsion start induction run motor Repulsion induction motor Universal Motor
Split phase induction motor: Consists of two windings main winding with high reactance and auxiliary winding with high resistance. Current in two windings differ in phase. Two sets of poles produce a kind of rotating flux, which starts the motor. When rotor comes to speed, a centrifugal device opens the switch and disconnects the auxiliary winding.
Universal Motor
Repulsion motor:
It is a form of series motor with the rotor energized inductively. Rotor winding is made for a low working voltage, and its brushes are joined by a short circuiting connector to provide a closed current path.
Period
Dripping liquids, blockage for Weekly ventilation Lubrication oil level and associated arrangement Unusual noise, unusual odour, Bearing housing vibration unhealthy noise, creepage of grease etc. Sparking, Colour, surface condition of commutator , pig tail, connections, black spots, roughness on commutator surface Air gap , Mild blowing, cleaning of dust Observe for any moisture.
Mechanical inspection
Belt for suitable slack and surface condition, couplings. Check shunt, series and commutating filds for tightness Check field spools machine cable Every 1-2 months connections etc. Check holders for fit, free play, brush spring pressure, replace worn out brushes. Commutator surface, mica insulations, Lubrication and Greasing
Commutators
Sleeve bearings
Bearing wear, end play, bearing surfaces. Check at the drain plug and oil flow for presence of metal scale, sand, or water. Take suitable action
Enclosed gears
Couplings and other drive Replacement of belts if needed. detail. Loads Check loads for changed conditions and whether correction needed. Once a year Check insulation resistance, clean surface and check moisture, varnishing, baking, drying of windings etc.
Windings
Check thoroughly, and replace the bearings if needed. Replace the wicks for lubrication of bearings Check the rotors, check for any local heating, check fan blades Clean the collector rings, washers and connections, clean the rings on lathe if necessary. Clean thoroughly all air passages check for surface condition of bars, high mica eccentricity turn the commutator if necessary Check belt , couplings, replace if necessary, align the couplings, Read load on motor with instruments at no load, fu; load, or through cycle as check on mechanical conditions of the driven machine.