Founded in 1947, STULZ acquired Air Technology Systems (ATS) in March 2001, naming the new company Stulz Air Technology Systems, Inc. (SATS). SATS is dedicated to providing innovative solutions for critical temperature and humidity control needs. SATS designs and manufactures specialized environmental control equipment for commercial, industrial and custom military applications. SATS serves a diverse marketplace including telecommunications, information technology, medical, financial, educational, industrial process and government contracts - utilizing world-class "island" manufacturing processes in a modern, 150,000 ft2 facility. The addition of SATS to the STULZ family of companies solidifies STULZ as a global leader in the Precision Air Conditioning marketplace. SATS combines a global network of sales and service companies with an extensive factory engineering staff and highly flexible manufacturing resources dedicated to providing world-class quality, innovation and customer service.
Mini-Space vertical, floor mounted air conditioning units provide precision temperature and humidity control for computer rooms and other critical areas where continuous 24 hrs/day, 365 days/yr operation is required. Designed for front only access, Mini-Space systems require minimal floor space. The units are designed with a wide range of options to handle both precision and comfort cooling applications. Typical applications include:
INDUSTRIES:
Telecommunications Internet / Web Hosting Financial / Banking Insurance Legal Services Airlines / Mass Transit Entertainment Government Colleges / Universities
APPLICATIONS:
Computer / LAN Rooms Telecommunications Rooms Colocation Centers ISP (Internet Service Providers)
1-1
Table of Contents
SECTION - 1
Introduction to SATS .......................................................... 1-1 Table of Contents ............................................................... 1-2
SECTION - 5
ELECTRICAL DATA: (FLA / MCA / MFS)
DX - Compressorized Systems: Air Cooled Systems .......................................................... 5-1 Water Cooled Systems ..................................................... 5-1 Glycol Cooled Systems .................................................... 5-1 Chilled Water Systems: Chilled Water Systems ..................................................... 5-2
SECTION - 2
Mini-Space SYSTEMS:
Outstanding Advantages ................................................... 2-1 User Oriented Features & Options .................................... 2-2 Available Configurations ................................................. 2-3/4
MODEL NOMENCLATURE:
Nomenclature Chart .......................................................... 2-5 Model Nomenclature Specifications .................................. 2-6
SECTION - 6
DIMENSIONAL / INSTALLATION DRAWINGS:
Dimensional Data Index .................................................... 6-1 Standard Mini-Space Systems: 1 to 3.5 Ton, Up-Flow Systems ......................................... 6-2 1 to 3.5 Ton, Down-Flow Systems .................................... 6-3 5 to 7 Ton, Up-Flow Systems ............................................ 6-4 5 to 7 Ton, Down-Flow Systems ....................................... 6-5
SECTION - 3
GUIDE SPECIFICATIONS:
Standard Features Index ................................................... 3-1 Standard Guide Specifications ....................................... 3-2/6 Standard Equipment Warranty .......................................... 3-7 Optional Features Index .................................................... 3-8 Microprocessor Controls Specifications ....................... 3-9/10 Optional Features Guide Specifications ..................... 3-11/13
SECTION - 4
PERFORMANCE / CAPACITY SPECIFICATIONS:
Performance Data Index .................................................... 4-1 DX - Air Cooled Systems ................................................ 4-2/3 DX - Water Cooled Systems ........................................... 4-4/5 DX - Glycol Cooled Systems .......................................... 4-6/7 Chilled Water Systems ................................................... 4-8/9
1-2
Mini-Space Systems
Mini-Space floor mounted A/C's are designed to be the compact solution to your Precision Air Conditioning requirements. Systems are available in six incremental sizes from 1 to 7 tons in the following cabinet foot-prints:
1 to 3.5 tons = 23.6" W x 23.6" D 5 to 7 tons = 39.4" W x 31.9" D
Smartly designed for 100% front service access, Mini-Space units can easily be tucked into a corner, between cabinetry or side-by-side. Mini-Space units are especially adaptable to raised floors and are available in both up-flow and down-flow air pattern configurations.
Microprocessor Controls
Precision temperature and/or humidity control with unrivaled, user-friendly C-1002 series controls, offer a wide range of functions and alarms.
Versatility
Plenum Box Spot Cooling & Ducted systems Self-Contained & Split systems
Non-Proprietary Parts
Mini-Space systems incorporate non-proprietary components where possible. Most major HVAC, refrigeration and electrical distributors stock an exact model cross reference or an alternate to most factory provided components.
2-1
Quiet Operation
Low sound power Scroll compressors coupled with low RPM blowers, acoustically lined cabinets and low velocity grilles provide the optimum in quiet operation.
Warranty
- 2 Year Parts Standard - Optional 5 Year Compressor
Mini-Space
(Model CCU-110-CW Shown)
2-2
WCS-( )
CCU/D- ( 41/121)-(A)
CCU/D- ( 171/201)-(A)
CCU/D- ( 41/121)-(W)
CCU/D- ( 41/121)-(G)
CCU/D- ( 171/201)-(W)
CCU/D- ( 171/201)-(G)
CCU/D- 110-CW
CCU/D- 200-CW
2-3
Down-Flow Systems:
Top "Free" Return with: Top "Ducted" Return with:
2-4
Model Nomenclature
Nomenclature
- Model Nomenclature Chart
- "CCU/D" Systems
U D
A CW G W LGA
= = = = =
Air Cooled Chilled Water System Glycol Cooled Water Cooled Outdoor Glycol Drycooler
Nominal Capacity in kW
2-5
Nomenclature
Integral Self-Contained
(Models CCU/D-( )-G) The system shall be a self-contained, floor mounted precision air conditioner to include integral glycol cooled condenser with factory installed head pressure glycol regulating control valve. Condenser (source) glycol solution shall be provided via a SATS model GPS-( )-( ) / FSS-( ) remote glycol pump package and drycooler system. The system shall require only single point supply power connection and shall ship from the SATS factory with a full operating refrigerant (R-22) charge. Glycol Regulating Valves: Head pressure shall be automatically controlled by a factory installed 2-way glycol regulating valve rated for 150 psig w.w.p.
Note: 3-way and high pressure (350 to 400 psig) rated valves are optionally available, page 3-12.
WCS-( )-V:
Low Ambient Head Pressure Control down to a minimum ambient temperature of -20F via Variable Fan Speed Head Pressure Control.
Air Cooled
(Models CCU/D-( )-A) The system shall be a remote (split) air cooled, floor mounted precision air conditioner evaporator. The evaporator section shall house, as a minimum, the evaporator coil, expansion valve, compressor, evaporator blower/ motor and associated electrical and refrigeration components. The CCU/D-( )-A evaporator section shall be located at some distance from its corresponding SATS model WCS-( ) outdoor air cooled condenser. The evaporator system shall require only single point main power supply connection; and the system shall ship from the SATS factory with a dry nitrogen holding charge ready for field refrigerant (R-22) charging.
WCS-( )-F:
Low Ambient Head Pressure Control down to a minimum ambient temperature of -30F via Flooded Head Pressure Control.
Integral Self-Contained
(Models CCU/D-( )-W) The system shall be a self-contained, floor mounted precision air conditioner to include integral water cooled condenser with factory installed head pressure water regulating control valve. Condenser (source) water shall be provided by a cooling tower or some other remote water source. The system shall require only single point supply power connection and shall ship from the SATS factory with a full operating refrigerant (R-22) charge. Water Regulating Valves: Head pressure shall be automatically controlled by a factory installed 2-way water regulating valve rated for 150 psig w.w.p.
Note: 3-way and high pressure (350 to 400 psig) rated valves are optionally available, page 3-12.
- Mini-Space Systems
2-6
"CCU/D" Series
41/61
81/110
Standard Standard Optional Optional Standard Standard
121
Standard N/A Standard Optional Standard Standard
171/201/200
Standard N/A Standard Optional Standard Standard
HUMIDITY CONTROL
Electrode Canister Steam Humidifier Dehumidification Mode Electric Reheat
CONTROLS
C-1002 Advanced Micropressor w/ Alarms C-5000 Advanced Micropressor w/ Alarms Standard Optional Standard Optional Standard Optional Standard Optional
CABINET
Galvannealed Steel, Powder Coated Finish Insulated Aluminum Condensate Drain Pan 2 lb Density Thermal & Sound Insulation Floor Stand (Adjustable, turning vanes optional) 1", 30% Avg. Eff. Pleated Filters 2", 30% Avg. Eff. Pleated Filters 2", 60% Avg. Eff. Pleated Filters 2 or 3-way Plenum Box (Up-Flow Units) HCFC-R22 Refrigerant Scroll Compressors Rotolock Service Valves High Efficiency, Aluminum Fin / Copper Tube Coils Thermal Expansion Valves Refrigerant Sight Glasses & Filter/Drier Strainers HFC-R407 Refrigerant Standard Standard Standard Optional Standard N/A N/A Optional Standard Standard Standard Standard Standard Standard Optional Standard N/A Standard Standard Standard Optional Standard N/A N/A Optional Standard Standard Standard Standard Standard Standard Optional Standard N/A Standard Standard Standard Optional Standard N/A N/A Optional Standard Standard Standard Standard Standard Standard Optional Standard N/A Standard Standard Standard Optional N/A Standard Optional Optional Standard Standard Standard Standard Standard Standard Optional N/A Standard
FILTERS / PLENUMS
DX-REFRIGERATION CIRCUIT
BLOWERS / MOTORS
Direct-Drive Evaporator Blower / Motor Belt-Drive Evaporator Blower / Motor
ELECTRICAL
1 or 3-Phase Power Supply Multi-Voltage Control Transformer (24V Class 2) - - - - - - - - - - - - See Electrical Tables Section 5 - - - - - - - - - - - Standard Standard Standard Standard
SAFETY FEATURES
C1002 Visual Local & Remote Alarms Main Power Non-Fused Disconnect, unit mounted High / Low Refrigerant Pressure Switches (DX units) Motor Overload Protection Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard
3-1
Standard Equipment
Guide Specifications
munications or other highly sensitive heat load equipment where continuous 24 hour-a-day, 365 days-a-year air conditioning is required. Designed for front-only access, Precision A/C systems require minimal floor space. The supplied system shall be provided with ETL Certification. The environmental control system shall be a SATS Mini-Space, factory-assembled, Precision A/C unit. The unit shall be designed for corner installation, requiring front only access through a removable front access panel. No allowance for side service access shall be required. The Mini-Space Series Precision A/C units are especially adapted to raised floors and are available in both down-flow and upflow air pattern configurations. The evaporator section shall be specifically designed for high sensible heat ratio. The system shall be manufactured by Stulz Air Technology Systems, Inc. in Frederick, Maryland, USA. 100% Front Access The air conditioner shall require front only access for all routinely maintenanced components. No allowance for side service access shall be required. Cabinet Construction Access panels shall be fabricated from heavy gauge steel and shall be securely attached to the base and top plates. Both access panels shall be powder coated to match and provide corrosion protection. The panels shall be lined with 1/2" (13 mm), 2 lb (.90 kg), high-density sound and thermal insulation and sealed with self-extinguishing gasketing conforming to NFPA 90A and 90B.
Electrical System
- Standard Equipment
The system shall incorporate modular motor controllers utilizing motor start protectors and circuit breakers eliminating the need for fusing, as well as providing: Motor branch circuit short circuit protection Motor load switching controllers (contactors) Motor overload protection The system shall incorporate overcurrent and overload protection in accordance with UL 1995 requirements. Each blower motor, compressor, electric heater stage and humidifier (if applicable) shall be provided with a factory mounted and wired starter/contactor. The control circuit shall be a 24 VAC Class 2 low voltage circuit including a circuit breaker for protection. Low voltage, high voltage and grounding wires shall be color coded and shall be individually numbered at each end for ease of service tracing. All wiring shall be in accordance with the National Electric Code (NEC).
The SATS Mini-Space vertical floormounted air conditioning system shall provide precision temperature and humidity control for computer rooms or rooms containing telecom-
3-2
Standard Equipment
pressor shall be complete with charging and service schraeder ports, internal vibration isolation, internal thermal overloads, an internal pressure relief valve, an internal discharge gas vibration eliminator and external vibration mounting isolation.
DX Refrigeration System
Thermal Expansion Valves
Included in the systems electrical control circuit shall be a 2pin terminal connection for remote stop/ start of the Mini-Space air conditioner by remote source.
Main Power Service Switch
Sight Glasses
The indoor evaporator shall be provided with a unit mounted main power service switch. The service switch shall be a dust-proof, nonfused type with lockable handle.
All refrigeration piping shall be refrigerant grade tubing. Each refrigerant circuit shall include, as a minimum a refrigerant drier/strainer, sight glass with moisture detector, a thermal expansion valve with rapid bleed port feature and external equalizer, an evaporator coil, a compressor, a high pressure switch with manual reset and a low pressure switch with automatic reset. Split/ Remote systems shall have a liquid line solenoid for refrigerant isolation to prevent liquid slugging. All high pressure joints shall be brazed, and the entire system shall be pressure tested at the factory with dry nitrogen, evacuated to at least 50 microns and fully charged with refrigerant.
Note: All split / remote DX systems ship with a dry nitrogen holding charge. All self-contained DX systems ship with a full refrigerant (R-22) operating charge.
DX Evaporator Coils
The system shall be configured for a draw-thru air pattern to provide uniform air distribution over the coil face. The coils shall be designed to provide maximum coil surface area and minimum depth to provide a high sensible cooling capacity. The coils shall be seamless drawn copper tubes, mechanically bonded to tempered aluminum fins with a raised lanced fin design for maximum heat transfer. Coil end plates shall be hot dipped galvanized steel. The evaporator coil shall be mounted in an insulated aluminum condensate drain pan. Refrigerant flow shall be controlled by an externally equalized thermostatic expansion valve.
Scroll Compressors
Cooling capacity shall be controlled by a factory installed 3-way, modulating control valve rated for a maximum 300 psig w.w.p.
Note: 2-way valves are optionally available, page 3-12.
Blowers / Motors
The compressor shall be a high efficiency, high reliability and low noise scroll compressor. The com-
3-3
Guide Specifications range. The blower shall be corrosion protected. The blower motor shall have internal overload protection.
Standard Equipment
Guide Specifications
C-1002 Controller
(Microprocessor Controller w/ Alarms)
Additionally, the fan speed shall have a manual adjustment via a potentiometer to meet specific air-flow requirements. The fan motor shall be 1075 rpm.
The Mini-Space precision A/C unit shall be provided with SATS C-1002 Microprocessor based Temperature and Humidity controller with Alarms. The control shall provide the user with an easy to read, LED display showing operating mode status, set points and actual values. Display:
Sensor Location As a standard, the C-1002 shall be provided with an internal temperature/humidity sensor. Remote Sensor Option The C-1002 temperature and humidity sensor shall be shipped loose for remote wall mounting. Interconnect cabling shall not be provided as the standard with the remote sensor option, but an optional 75 ft. cable or 150 ft. cable is also available. Recovery Delay: After a power loss, the C-1002s Recovery Delay feature allows the Precision A/C to operate without initiating any high or low temperature or humidity alarms for a delayed period. This feature allows the A/C time (15 to 60 minutes adj.) to pulldown the conditioned spaces load without nuisance alarms during initial startup or power loss restart. Cold Start Time Delay: Each compressor of a DX Split system shall be provided with the C1002s Cold Start compressor time delay. The Cold Start timer delays and therefore, overrides the systems refrigerant low suction pressure switch during system startup. This allows the system time to build sufficient discharge pressure during cold weather startup.
- Standard Equipment
The C-1002 shall provide visual indication of the following alarm conditions:
High Temperature Low Temperature High Humidity Low Humidity High Head Pressure Low Suction Pressure Dirty Filter Loss of Airflow Sensor Failure Summary Alarm- Includes condensate overflow/water detection, smoke detector, firestat (if applicable).
Controls
The standard Mini-Space floor A/C includes the C-1002 Advanced Microprocessor Controller, Canister Steam Humidifier and Dehumidification Mode with Electric Reheat/Heat providing precision temperature and humidity control.
A standard non-powered summary alarm contact is available for all systems. The C-1002 shall be provided with a RS-485 Serial Port as a standard.
SECURITY:
Multiple security levels prevent unauthorized adjustment of critical system parameters. The user may select a four-digit password for
3-4
Guide Specifications setpoint and configuration changes. Password Protection: The C-1002 includes a selectable password protection feature that prevents unauthorized users from making changes to system setpoints and settings available directly from the multi-function keypad/display. Two Unit Sequencing: Critical control applications shall be addressed with the C-1002 two-unit sequencing program logic. Under an A/C failure condition the controller will automatically initiate the unit operation of the designated standby/ backup unit, as well as, locally and remotely alert the alarm condition. The two-unit sequencing control logic shall automatically initiate the current standby unit upon a system failure alarm condition. The control is programmed to automatically change from the current primary unit operation to secondary/standby unit operation via two methods: 1) Automatic Timed (every 7 days) 2) Automatic Changeover on Unit Failure As well, the control shall also enable the standby/backup unit in the event that the primary unit is not able to handle the cooling requirement. As the maximum room temperature limits are reached with the primary unit, the standby/backup unit shall become enabled to assist in the cooling requirement until room conditions are back within a satisfactory range.
Standard Equipment
conductor. Included shall be one automatic resetting over-temperature safety device (pilot duty), and a nonresettable over-temperature safety device (located in main power line).
Guide Specifications
- Standard Equipment
The humidifier shall be an electrode steam canister type and shall have an adjustable humidity output setting from 25 to 100% of the full rated humidifier capacity. The humidifier shall incorporate an automatic flush cycle that senses the current consumption of the humidifier and controls mineral concentration of the water. A Change Cylinder light shall notify service personnel when the humidification output is below rated requirements and when maintenance is due. Dehumidification Cycle: (standard) The floor A/C shall be provided with a refrigeration based dehumidification mode. Moisture is condensed on the cooling coil and discharged through the condensate drain. Reheat (electric, hot gas or hot water) shall be provided to offset sensible cooling during the dehumidification cycle.
(CCU/CCD 171 to 201) A factory mounted and wired low-watt density, plated fin-tubular design electric resistance heater shall be included to provide automatic sensible re-heating as required during the dehumidification cycle and automatic heating mode. Electric heaters shall be provided with miniature thermal/magnetic circuit breakers, which shall protect each ungrounded conductor. Also included will be one automatic reset and one manual reset over-temperature safety device (pilot duty). Two stages of electric reheat/heat shall be provided as standard.
UP-FLOW:
(CCU-( )-( )) The air conditioner shall be configured for an up-flow air pattern with free evaporator return air through front filtered grille and conditioned supply air through the top of the unit. Top Ducted Discharge with: Front Free Return; or Rear Ducted Return Top Discharge Through two or three-way grille Plenum Box with: Front Free Return; or Rear Ducted Return
Dehumidification Mode
(CCU/CCD 41 to 121) A factory mounted and wired electric resistance heater element shall be included to provide an automatic sensible reheating mode during the dehumidification cycle and an automatic heating mode as required. Electric heaters shall be provided with thermal / magnetic circuit breakers which shall protect each
3-5
Standard Equipment
Guide Specifications
pressure control features are offered: WCS-( )-P: Head pressure control to 0F ambient . WCS-( )-V: Head pressure control to -20F ambient . WCS-( )-F: Head pressure control to -30F ambient .
Note: Please refer to page 3-11, for specification details of Mini-Space air cooled condenser "Low Ambient Control" options: 0F, -20F & -30F
(A top duct connection shall be available as an option. 2 & 3-way top discharge plenum boxes are available, page 3-12.)
The A/C shall have slide out, 1" deep (CCU/D 41 to 121) or 2" deep (CCU/ D 171 to 201), class 2 (per U.L. Standard 900) filters. The filters shall be easily accessed through the front. The filters shall have an average efficiency rating of 30% in accordance with ASHRAE Standard 52-76 test method.
- Standard Equipment
DOWN-FLOW:
(CCD-( )-( )) The air conditioner shall be configured for a down-flow air pattern with free evaporator return air to the top and conditioned supply air discharge through bottom of the A/C into the raised floor.
AIR COOLED
The air-cooled system shall consist of a split air cooled unit with remote outdoor condenser.
3-6
Stulz Air Technology Systems, Inc., warrants to the original buyer of its products that the goods are free from defects in material and workmanship. Stulz Air Technology Systems, Inc.s obligation under this warranty is to repair or replace, at its option, free of charge to the customer, any part or parts which are determined by Stulz Air Technology Systems Inc. to be defective for a period of 24 months from date of shipment when a completed start-up form has been submitted to Stulz Air Technology Systems, Inc. within 90 days from shipment. In the event that a completed start-up form is not received by Stulz Air Technology Systems, Inc. within 90 days from shipment, the companys obligation will be for a period of 12 months from date of shipment. Parts repaired or replaced under this warranty are shipped FOB Factory, and warranted for the balance of the original warranty period or for 90 days from the date of installation, whichever is greater. Stulz Air Technology Systems, Inc.s warranty does not cover failures caused by improper installation, abuse, misuse, misapplication, improper or lack of maintenance, negligence, accident, normal deterioration (including wear and tear), or the use of improper parts or improper repair. Purchasers remedies are limited to replacement or repair of non-conforming materials in accordance with the written warranty. This warranty does not include costs for transportation, costs for removal or reinstallation of equipment or labor for repairs or replacement made in the field. If any sample was shown to the buyer, such sample was used merely to illustrate the general type and quality of the product, and not to represent that the equipment would necessarily conform to the sample. This is the only warranty given by the seller, and such warranty is only given to buyers for commercial or industrial purposes. This warranty is not enforceable until the invoice(s) is paid in full. THE FOREGOING SHALL CONSTITUTE SATS ENTIRE LIABILITY AND YOUR EXCLUSIVE REMEDY. IN NO EVENT SHALL SATS BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, CONSEQUENTIAL, OR EXEMPLARY DAMAGES, INCLUDING LOST PROFITS (EVEN IF ADVISED OF THE POSSIBILITY THEREOF) ARISING IN ANY WAY OUT OF THE INSTALLATION, USE OR MAINTENANCE OF THE EQUIPMENT. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
3-7
Optional Features -
Guide Specifications
Optional Features
Accessories
Floor Stands - Seismic Floor Stand ........................................... 3-12 - Turning Vanes .................................................... 3-12 2 or 3-Way Plenum Discharge Box ..................... 3-12 Condensate Pump ............................................... 3-13
Selected Options
Filtration ................................................................ 3-11 Reheat Options - Hot Gas Reheat ................................................. 3-11 - Hot Water Reheat / Heat .................................... 3-11
Smoke Detection ................................................. 3-13 Firestat ................................................................. 3-13 Remote Water Detector: - Qty. One, Spot Type ........................................... 3-13 - Qty. Two, Spot Type ............................................ 3-13 - 25 Ft. - Strip/Cable Type ..................................... 3-13
- Index
DX - Capacity Modulation
Snap-Acting, Hot Gas Bypass ............................. 3-12
3-8
Guide Specifications
ALARM CONDITIONS: Alarm conditions activate an audible and visual indicator. An alarm shall be acknowledged through a button located on the keypad display. The C-5000 alerts to the following alarm conditions (if applicable):
High Temperature Low Temperature High Humidity Low Humidity High Head Press Low Suction Press Loss of Air Flow Dirty Filter Smoke Detection Firestat Leak Detection GC Pump Failure Sensor Failure Comm. Failure
The A/C unit shall be provided with SATS CompTrol 5000 Microprocessor based Temperature and Humidity controller with Alarms. The controller shall incorporate a userfriendly operating environment, to allow easy system setup and operation. The CompTrol 5000 (C-5000) is a complete microprocessor based control system designed for operating, controlling and monitoring the precision air conditioning unit. The C-5000 controller shall include a full-featured LCD graphical display for visual indication of the unit operating conditions.
SYSTEM SETUP & ADJUSTMENTS: The C-5000 shall be completely factory preprogrammed, and therefore, most applications will require no field setup. However, the default set points and their ranges are easily adjusted from C-5000 keypad/ display. Summary Alarm Contact: A summary alarm dry-contact (n/o) connection shall be available for remote annunciation of an alarm condition. Alarm History: The C-5000 controller provides users with a recorded history of the previous 80 alarms, including the time and date of the alarm.
UNIT STATUS DISPLAY: The C-5000 keypad displays current unit functions and room status:
Current Dry Bulb Temp Current Relative Humidity Actual Time
CONTROL INPUTS / OUTPUTS: The C-5000 is capable of both digital (on/off) and analog input and output device control. Prior to shipment, each Precision AC units C-5000 is factory program configured to match the units system operational requirements. Temperature Anticipation: The C-5000 shall incorporate a selfcalibrating and self-adjusting control logic that adjusts the response of the SATS air conditioner to changes in temperature and humidity. The system shall provide premium
USER INTERFACE:
The User Interface shall feature an easy to read, liquid-crystal, graphical display. The attractive unit mounted interface, allows the operator to
Run Times The historical run-time in hours of the following major components is available directly from the C-5000 keypad/display: (if applicable)
3-9
Optional Features setpoint accuracy while controlling the room conditions rate of change, minimizing the equipment energy consumption and maximizing the systems operating life and reliability.
Guide Specifications
Guide Specifications
compressor ON and minimum compressor OFF short cycle timers. Cold Start Time Delay: Each compressor of a DX Split System shall be provided with the C5000s Cold Start compressor time delay. The Cold Start timer delays, and therefore, overrides the systems refrigerant low suction pressure switch during system startup. This allows the system time to build sufficient discharge pressure during cold weather startup.
POWER LOSS RESTART: In the event of a loss of power to the system, the C-5000 can be configured for Automatic or Manual Restart. The C-5000s non-volatile memory enables the system to restart when power is restored, without the loss of the last stored setpoints and other system configuration settings. Sequential Load Activation: To minimize the total in rush current loads during system startup/restart, the C-5000 controller shall be configured for time-delay sequence startup. The user can designate specific unit restart time-delays, as well as, each units respective compressor, electric heater and/or humidifier. Unit restart delay can be adjusted from 0 to 10 minutes. Unit compressor, electric heater and/or humidifier restart delay can be adjusted from 0 to 60 seconds. Recovery Delay: After a power loss, the C-5000s Recovery Delay feature allows the Precision A/C to operate without initiating any high or low temperature or humidity alarms for a delayed period. This feature allows the A/C time (15 to 60 minutes adj.) to pulldown the conditioned spaces load without nuisance alarms during initial startup or power loss restart.
Critical control applications shall be addressed with the C-5000 two-unit sequencing program logic. Under an A/C failure condition the controller will automatically initiate the unit operation of the designated standby/ backup unit, as well as, locally and remotely alert the alarm condition. The two-unit sequencing control logic shall automatically initiate the current standby unit upon a system failure alarm condition. The control is programmed to automatically change from the current primary unit operation to secondary/standby unit operation via two methods: 1) Automatic Timed (every 7 days) 2) Automatic Changeover on Unit Failure As well, the control shall also enable the standby/backup unit in the event that the primary unit is not able to handle the cooling requirement. As the maximum room temperature limits are reached with the primary unit, the standby/backup unit shall become enabled to assist in the cooling requirement until room conditions are back within a satisfactory range.
SECURITY:
Multiple security levels prevent unauthorized adjustment of critical system parameters. The user may select a four-digit password for setpoint and configuration changes. Password Protection: The C-5000 includes a selectable password protection feature that prevents unauthorized users from making changes to system setpoints and settings available directly from the multi-function keypad/display.
The C-5000 incorporates a unique self-diagnostics algorithm that continually tests system functions and hardware operation. In the event of such a failure, the user will be alerted to the condition via a visual and audible alarm. Control Board: Initiates a self-test of the control system. Input Diagnostics: All system inputs and output devices are continuously monitored for proper operation.
COMPRESSOR OPERATIONS: Short Cycle Protection: Each compressor shall be protected from frequent compressor cycling through the C-5000s minimum
3-10
Guide Specifications
Head Pressure Control
AIR COOLED - Low Ambient
0F, Pressure Fan CyclingThe air cooled system shall incorporate a low ambient pressure fan cycling control for year-round A/C system operation down to 0F DB minimum ambient air temperature.
SELECTED OPTIONS
Mini-Space floor systems include the C-1002 Microprocessor Controller, Electrode Canister Steam Humidifier and Dehumidification Mode with Electric Reheat/ Heat for total temperature and humidity control, as a standard. However, these standard features can be deleted and/or substituted with alternate features to allow you the flexibility to select the configuration best suited for your unique application.
-20F, Variable Fan SpeedThe air cooled system shall incorporate a low ambient variable speed fan head pressure control for yearround A/C system operation down to -20F DB minimum ambient air temperature.
Optional Filtration:
-30F, Flooded ControlMedium Efficiency Filters (Model CCU/CCD-171 to 201 only) The system shall be provided with a 2" filter with an average efficiency rating of 60% in accordance with ASHRAE Standard 52-76 test method.
Remote Air Cooled Condenser Scroll Compressor
High Pressure Switch Flooded Head Pressure Control Valve Relief Valve
HP
LP
Feeler Bulb
Sight Glass
Control Inputs & Outputs shall be remotely monitored (address readable) and remotely controlled (address writable) via any building management system (BMS) / local area network (LAN) control system that can communicate via a ModBus protocol. Each unit configured for BMS communication shall incorporate an optional RS-485 Serial Communication Port that is field connected to a factory provided wall mounted ModBus Gateway.
Reheat Options: Hot Gas Reheat: (Models available CCU/D-( )-A, W& G) A factory piped and wired hot gas reheat valve shall be provided to divert the hot compressor discharge gas from the condenser to the hot gas reheat coil during the dehumidification cycle. This energy saving feature shall require no additional energy to offset the sensible cooling capacity while in the dehumidification mode. Hot Water Reheat/Heat A factory installed copper tube aluminum fin heat/reheat coil and two-way (on/off) valve shall be provided to control the flow of hot water for heating the conditioned air.
The air cooled system shall incorporate a low ambient flooded head pressure control for year-round A/C system operation down to -30F DB minimum ambient air temperature. This option shall include a factory installed crankcase heater, cold-start relay, liquid refrigerant receiver with liquid level sight glass and head pressure-regulating valve for flooded condenser option.
3-11
Guide Specifications
Optional Features
ACCESSORIES
Adjustable Floor Stand:
OPTIONAL TURNING VANE
Scroll Compressor
LP
Flooded Head Pressure Control Valve Hot Gas Regulator Valve (Optional) Relief Valve Sight Glass Liquid Line Solenoid Valve
DX Water Cooled and Glycol Cooled systems are available with following standard and optional head pressure regulating control valves:
2-way, 150 psig (standard) 2-way, 350 psig (optional) 2-way, 400 psig (optional) 3-way, 150 psig (optional) 3-way, 350 psig (optional) 3-way, 400 psig (optional)
Equalizer Line
HP
Feeler Bulb
- Guide Specifications
Two-Way, 350 psig Regulating Valve Each refrigerant circuits head pressure shall be controlled by a factory supplied, high pressure twoway water /glycol regulating valve rated for 350 psig. w.w.p. Three-Way, Head Pressure Regulating Valve Each refrigerant circuits head pressure shall be controlled by a factory supplied: 3-Way, 150 psig w.w.p. head pressure valve or, 3-Way, 350 psig w.w.p. head pressure valve.
An adjustable floor stand shall be provided to allow for ease of installation of the unit onto a raised floor. Floor stand height shall range (nominal 12", 18", & 24") and shall have field adjustment capability.
Note: For additional floor stand heights, please contact your local SATS sales representative.
Chilled Water cooling shall be controlled by the following standard and optional control valves: Models CCU/D-110/200-CW:
3-way, 300 psig (standard) 2-way, 300 psig (optional) 2-way, 400 psig (optional) 3-way, 400 psig (optional)
Turning Vanes:
Turning vanes shall be factory installed to each unit's floor stand.
Standard Valve Control: A ____-way modulating CW cooling control valve rated for a maximum ____ psig w.w.p. shall be factory installed. Precision cooling control shall be accomplished via a C-1002 modulating control signal to the control valve.
3-12
Optional Features shall be provided. The plenum box shall include double-deflecting, adjustable grilles.
Guide Specifications
firestat. The firestat will shut down the air conditioner upon sensing a high return air temperature.
3-13
Optional Features
- Guide Specifications
Condensate Pump:
A high capacity, high temperature condensate pump shall be provided for automatic removal of condensate and humidifier flush water (if applicable). The condensate pump shall be specifically designed to operate with the higher condensate temperatures caused by the flush and drain cycle of the electrode canister humidifiers. As a standard the condensate pump shall ship loose for field installation on all systems. Factory installation of the condensate pump is available as an option on models CCU-171 and CCU-201 (upflow).
A remote single point water/leak detector shall be included to provide additional safety to the standard condensate pan safety float. Upon sensing a water leak, the normally closed water detector control circuit opens, which will cause the air conditioner to shut down. Dual (two) - Spot Type Detectors:
Smoke Detection:
Quantity 2 (two) remote spot type water/leak detectors per A/C unit shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit opens, which will cause the air conditioner to shut down. Remote Water Detector- Strip Type:
A photoelectric smoke detector shall be factory installed and wired in the evaporator section of the suction side of the evaporator blower. The air conditioner will shut down upon sensing smoke in the return air stream.
Firestat:
A 25 ft. in length remote strip/cable type water/leak detector shall be provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the A/C unit The air conditioner shall be provided with a factory wired and mounted
INDEX
Performance Data: Air Cooled, 1- 7 Ton Systems ....................................... 4-2/3 Water Cooled, 1- 7 Ton Systems .................................. 4-4/5 Glycol Cooled, 1- 7 Ton Systems ................................ 4-6/7 Chilled Water Cooled, 3- 7 Ton Systems ...................... 4-8/9
4-1
- Index
1 to 7 Ton "CCU/D"
CC( )-61-A CC( )-81-A CC( )-121-A CC( )-171-A CC( )-201-A
CC( )-41-A
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
75FDB/62.5FWB, 50% RH Total Sensible 72FDB/60FWB, 50% RH Total Sensible 70FDB/58.5FWB, 50% RH Total Sensible 75FDB/61FWB, 45% RH Total Sensible 72FDB/58.5FWB, 45% RH Total Sensible 70FDB/57FWB, 45% RH Total Sensible 17,500 15,900 17,000 15,500 16,000 14,800 24,900 21,500 24,100 21,100 22,800 20,200 32,100 27,800 31,100 27,200 29,800 26,200 44,900 38,800 42,700 37,600 42,200 37,200 56,300 53,800 53,500 51,400 51,500 49,600 72,200 68,500 68,600 65,600 66,500 64,000
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB, (Optional) BTU/H 31,465 31,465 63,475 63,475 114,450 GPM / Press. Drop (ft.wg) 3.2 / (.7) 3.2 / (.7) 6.5 / (.8) 6.5 / (.8) 11.7 / (2.4) Control - - - - - - - - 2-way, 150 psig, Modulating (0-10 Vdc) - - - - - - - -
2-5, (1.7)
Cycling
2-5, (1.7)
Cycling
2-5, (1.7)
Cycling
4-10, (3.4)
Cycling
4-10, (3.4)
Cycling
3/4 Hp
1,180 @ 0.2" Direct
3/4 Hp
1,180 @ 0.2" Direct
3/4 Hp
1,890 @ 0.2" Direct
3.0 Hp
3,450 @ 0.3" Belt
3.0 Hp
4,130 @ 0.3" Belt
Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22
Type, (Qty.) Power Input (Kw)
Tot. Heat of Rej. (BTU/H)
4-2
Performance Data
CC( )-41-A
CC( )-61-A
CC( )-81-A
CC( )-121-A
Filters - 1" deep (41/121) & 2" deep (171/201), 30% Average Efficiency, throwaway
Up-Flow (Free-Front Return): Nom. Size (in.), (Qty.) 38x16, (1) 38x16, (1) 38x16, (1) 38x16, (1) 16x24, (2) 16x24, (2)
Down-Flow & Up-Flow (Rear Ducted Return): Nom. Size (in.), (Qty.) 25x22, (1) 25x22, (1)
25x22, (1)
25x22, (1)
20x25, (2)
20x25, (2)
(Please refer to Mini-Space IOM Manual for proper interconnecting refrigerant line sizing.)
Humidifier Inlet
1/4" OD
1/4" OD
1/4" OD
1/4" OD
Physical Data
Approx. Weight
410lbs
420lbs
430lbs
450lbs
480lbs
510lbs
"CCU/D" Model
Cond. Model @ 95F Amb. Condenser Fan Data CFM @ free discharge Motor Hp, (Qty.) Net Weight (lbs.)
CC( )-41-A
WCS-002B
CC( )-61-A
WCS-003B
CC( )-81-A
WCS-003B
CC( )-121-A
WCS-005B
4,450 1/3 Hp, (1) 107 5/8" OD, (1) 5/8" OD, (1) WCS-005B
4,450 1/3 Hp, (1) 107 5/8" OD, (1) 5/8" OD, (1) WCS-005B
3,900 1/3 Hp, (1) 116 5/8" OD, (1) 5/8" OD, (1) WCS-008B
8,640 1/3 Hp, (2) 164 5/8" OD, (1) 5/8" OD, (1) WCS-008B
8,640 1/3 Hp, (2) 164 5/8" OD, (1) 5/8" OD, (1) WCS-010B
Refrigerant Connections - Copper Liquid Line, (Qty.) 5/8" OD, (1) Hot Gas Line, (Qty.) 5/8" OD, (1) Cond. Model @105F Amb. Condenser Fan Data CFM @ free discharge Motor Hp, (Qty.) Net Weight (lbs.) WCS-003B
3,900 1/3 Hp, (1) 116 5/8" OD, (1) 5/8" OD, (1)
3,900 1/3 Hp, (1) 116 5/8" OD, (1) 5/8" OD, (1)
8,640 1/3 Hp, (2) 164 5/8" OD, (1) 5/8" OD, (1)
8,640 1/3 Hp, (2) 164 5/8" OD, (1) 5/8" OD, (1)
7,780 1/3 Hp, (2) 179 5/8" OD, (1) 5/8" OD, (1)
Refrigerant Connections - Copper Liquid Line, (Qty.) 5/8" OD, (1) Hot Gas Line, (Qty.) 5/8" OD, (1) Low Ambient Control Std Minimum Oper. Amb. Head Press. Method Optional Min. Op. Amb
0F Fan Cycling
-20F or -30F
0F Fan Cycling
-20F or -30F
0F Fan Cycling
-20F or -30F
0F Fan Cycling
-20F or -30F
0F Fan Cycling
-20F or -30F
0F Fan Cycling
-20F or -30F
4-3
1 to 7 Ton "CCU/D"
CC( )-61-W CC( )-81-W CC( )-121-W CC( )-171-W CC( )-201-W
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
75FDB/62.5FWB, 50% RH Total Sensible 72FDB/60FWB, 50% RH Total Sensible 70FDB/58.5FWB, 50% RH Total Sensible 75FDB/61FWB, 45% RH Total Sensible 72FDB/58.5FWB, 45% RH Total Sensible 70FDB/57FWB, 45% RH Total Sensible 18,800 16,900 18,200 16,500 16,600 15,200 26,700 22,700 24,900 21,600 23,700 20,700 33,400 29,300 32,100 27,800 29,200 25,800 48,000 40,800 44,100 38,400 40,200 35,900 60,500 57,500 57,600 55,000 53,300 51,300 76,900 72,300 73,900 69,900 71,800 68,200
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB, (Optional) BTU/H 31,465 31,465 63,475 63,475 114,450 GPM / Press. Drop (ft.wg) 3.2 / (.7) 3.2 / (.7) 6.5 / (.8) 6.5 / (.8) 11.7 / (2.4) Control - - - - - - - - 2-way, 150 psig, Modulating (0-10 Vdc) - - - - - - - -
2-5, (1.7)
Cycling
2-5, (1.7)
Cycling
2-5, (1.7)
Cycling
4-10, (3.4)
Cycling
4-10, (3.4)
Cycling
3/4 Hp
1,180 @ 0.2" Direct
3/4 Hp
1,180 @ 0.2" Direct
3/4 Hp
1,890 @ 0.2" Direct
3.0 Hp
3,450 @ 0.3" Belt
3.0 Hp
4,130 @ 0.3" Belt
Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22
Type, (Qty.) Power Input (Kw) Scroll, (1) 1.6 Scroll, (1) 2.0 Scroll, (1) 2.8 Scroll, (1) 3.5 Scroll, (1) 4.1 Scroll, (1) 4.9
4-4
Performance Data
CC( )-41-W
CC( )-61-W
-----
-----
1/4" OD 7/8" OD
1/4" OD 7/8" OD
1/4" OD 7/8" OD
Filters - 1" deep (41/121) & 2" deep (171/201), 30% Average Efficiency, throwaway
Up-Flow (Free-Front Return): Nom. Size (in.), (Qty.) 38x16, (1) 38x16, (1) 38x16, (1) 16x24, (2) 38x16, (1) 16x24, (2)
Down-Flow & Up-Flow (Rear Ducted Return): Nom. Size (in.), (Qty.) 25x22, (1) 25x22, (1)
25x22, (1)
20x25, (2)
25x22, (1)
20x25, (2)
Physical Data
Approx. Weight 410lbs 420lbs 430lbs 450lbs 480lbs 510lbs
4-5
1 to 7 Ton "CCU/D"
CC( )-61-G CC( )-81-G CC( )-121-G CC( )-171-G CC( )-201-G
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
75FDB/62.5FWB, 50% RH Total Sensible 72FDB/60FWB, 50% RH Total Sensible 70FDB/58.5FWB, 50% RH Total Sensible 75FDB/61FWB, 45% RH Total Sensible 72FDB/58.5FWB, 45% RH Total Sensible 70FDB/57FWB, 45% RH Total Sensible 16,900 15,400 16,400 15,000 16,000 14,800 24,900 21,500 23,300 20,500 22,800 20,200 31,500 27,400 30,000 26,400 29,400 26,000 44,100 38,300 41,900 37,100 40,400 36,100 55,200 52,800 52,500 50,500 50,500 48,700 70,500 67,200 67,000 64,400 65,000 62,800
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB, (Optional) BTU/H 31,465 31,465 63,475 63,475 114,450 GPM / Press. Drop (ft.wg) 3.2 / (.7) 3.2 / (.7) 6.5 / (.8) 6.5 / (.8) 11.7 / (2.4) Control - - - - - - - - 2-way, 150 psig, Modulating (0-10 Vdc) - - - - - - - -
2-5, (1.7)
Cycling
2-5, (1.7)
Cycling
2-5, (1.7)
Cycling
4-10, (3.4)
Cycling
4-10, (3.4)
Cycling
3/4 Hp
1,180 @ 0.2" Direct
3/4 Hp
1,180 @ 0.2" Direct
3/4 Hp
1,890 @ 0.2" Direct
3.0 Hp
3,450 @ 0.3" Belt
3.0 Hp
4,130 @ 0.3" Belt
Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22
Type, (Qty.) Power Input (Kw) Scroll, (1) 2.1 Scroll, (1) 2.6 Scroll, (1) 3.6 Scroll, (1) 4.5 Scroll, (1) 5.3 Scroll, (1) 6.3
4-6
Performance Data
CC( )-61-G
CC( )-81-G
CC( )-121-G
-----
-----
1/4" OD 7/8" OD
1/4" OD 7/8" OD
1/4" OD 7/8" OD
Filters - 1" deep (41/121) & 2" deep (171/201), 30% Average Efficiency, throwaway
Up-Flow (Free-Front Return): Nom. Size (in.), (Qty.) 38x16, (1) 38x16, (1) 38x16, (1) 16x24, (2) 38x16, (1) 16x24, (2)
Down-Flow & Up-Flow (Rear Ducted Return): Nom. Size (in.), (Qty.) 25x22, (1) 25x22, (1)
25x22, (1)
20x25, (2)
25x22, (1)
20x25, (2)
Physical Data
Approx. Weight 410lbs 420lbs 430lbs 450lbs 480lbs 510lbs
"CCU/D" Model
Dry Cooler Model @ 95F Amb. Selection @ 95F GPM @ 120F EGT/110F LGT No. of Circuits Expansion Tank Pipe Connection (In/Out) 105F Amb. Selections Standard Pump Quantity Horsepower Total Hd Press. (ft. w.g.) Dual Pump Packages
CC( )-41-A
FSS-103A
CC( )-61-A
FSS-103A
CC( )-81-A
FSS-104A
CC( )-121-A
FSS-107A
CC( )-171-A
FSS-107A
CC( )-201-A
FSS-204A
Optional - Please refer to Glycol Pump / Drycooler Engineering Manual GPS-005-S 1(one) 1/2 Hp 48 GPS-005-S 1(one) 1/2 Hp 47 GPS-007-S 1(one) 3/4 Hp 57 GPS-007-S 1(one) 3/4 Hp 56 GPS-007-S 1(one) 1.0 Hp 65 GPS-015-S 1(one) 1.0 Hp 64
4-7
Chilled Water
Performance Data
- Chilled Water (3 to 7 Ton Systems)
"CCU/D" Model
- 3 to 7 Ton "CCU/D"
CC( )-200-CW CC( )-110-CW CC( )-200-CW CC( )-110-CW CC( )-200-CW
CC( )-110-CW
NET COOLING CAPACITY - (includes motor heat @ std CFM & e.s.p. ratings)
75FDB/62.5FWB, 50% RH High Flow (8F Tw) Med. Flow (10F Tw) Low Flow (12F Tw) Total Sens. GPM / (pd. Ft.) Total Sens. GPM / (pd. Ft.) Total Sens. GPM / (pd. Ft.)
BTU/H @ 45F EWT, 0% Glycol Solution BTU/H @ 42F EWT, 0% Glycol Solution BTU/H @ 50F EWT, 0% Glycol Solution
41,670 38,540 10.3/(6.1) 32,990 32,990 6.6/(2.6) 27,020 27,020 4.5/(1.2) 32,190 32,190 8/(3.9) 26,510 26,510 5.3/(1.6) 21,870 21,870 3.6/(0.8) 28,040 28,040 6.9/(2.9) 22,310 22,310 4.5/(1.2) 19,290 19,290 3.2/(0.7) 38,150 38,150 9.5/(5.2) 32,880 32,880 6.5/(2.6) 26,910 26,910 4.5/(1.2) 32,910 32,910 8.0/(3.8) 26,420 26,420 5.2/(1.6) 21,810 21,810 3.6/(0.8) 32,010 32,010 7.9/(3.8) 26,340 26,340 5.2/(1.6) 21,750 21,750 3.6/(0.8)
99,820 89,200 24.8/(9.4) 86,700 81,540 17.2/(4.9) 67,230 37,230 11.1/(2.1) 75,660 75,660 18.8/(5.7) 64,760 64,760 12.9/(2.8) 51,660 51,660 8.6/(1.2) 66,740 66,740 16.6/(4.5) 55,100 55,100 10.9/(2.0) 41,410 41,410 6.9/(0.8) 88,400 88,400 21.9/(7.5) 78,630 78,630 15.6/(4.1) 66,970 66,970 11.1/(2.0) 75,460 75,460 18.7/(5.7) 64,550 64,550 12.8/(2.8) 51,410 51,410 8.5/(1.2) 66,560 66,560 16.5/(4.5) 54,900 54,900 10.9/(2.0) 41,300 41,300 6.8/(0.7)
46,650 35,570 11.6/(7.6) 39,440 32,010 7.8/(3.7) 33,190 28,600 5.5/(1.8) 40,590 37,990 10.0/(5.9) 32,130 33,890 6.4/(2.4) 26,010 26,010 4.3/(1.1) 33,940 33,890 8.4/(4.3) 27,850 27,850 5.5/(1.3) 23,100 23,100 3.8/(0.6) 46,180 43,850 11.4/(5.4) 38,280 38,280 7.6/(2.5) 32,610 32,610 5.4/(1.2) 37,450 37,450 9.3/(3.7 32,030 32,030 6.4/(1.7) 25,910 25,910 4.3/(0.7) 33,440 33,440 8.3/(0.3) 27,750 27,750 5.5/(1.2) 23,050 23,050 3.8/(0.6)
116,840 97,330 29/(12.7) 104,470 90,790 20.8/(6.9) 91,740 83,400 15.2/(3.9) 97,310 88,090 24.1/(9.1) 84,020 80,820 16.7/(4.6) 64,910 64,910 10.7/(1.9) 85,110 80,820 21.1/(7.1) 67,670 67,670 13.4/(3.1) 54,680 54,680 9.1/(1.3) 109,700 101,050 27.2/(11.3) 96,740 93,150 19.2/(6.0) 79,440 79,440 13.2/(2.9) 86,970 86,970 21.5/(7.4) 76,800 76,800 15.3/(3.9) 64,810 64,810 10.7/(1.9) 78,440 78,440 19.5/(6.1) 67,460 67,460 13.4/(3.0) 54,440 54,440 9.0/(1.3)
29,170 29,170 7.3/(2.3) 23,680 23,680 4.7/(0.9) 19,390 19,390 3.2/(0.4) 23,020 23,020 5.8/(1.4) 17,600 17,600 3.5/(0.5) 15,500 15,500 2.6/(0.3) 18,590 18,590 4.7/(0.9) 15,020 15,020 3.0/(0.4) 12,960 12,960 2.2/(0.2.) 29,080 29,080 7.2/(2.3) 23,530 23,530 4.7/(0.9) 19,330 19,330 3.2/(0.4) 22,950 22,950 5.8/(1.4) 17,560 17,560 3.5/(0.5) 15,450 15,450 2.6/(0.3) 18,520 18,520 4.6/(0.9) 14,980 14,980 3.0/(0.4) 12,910 12,910 2.2/(0.2)
68,970 68,970 17.1/(4.8) 58,090 58,090 11.6/(2.3) 44,200 44,200 7.3/(0.9) 55,320 55,320 13.8/(3.2) 42,570 42,570 8.5/(1.2) 33,380 33,380 5.5/(0.5) 45,690 45,690 11.3/(2.2) 32,220 32,220 6.4/(0.7) 27,890 27,890 4.6/(0.4) 68,780 68,780 17.1/(4.7) 57,870 57,870 11.5/(2.2) 43,950 43,950 7.3/(0.8) 55,150 55,150 13.7/(3.2) 42,370 42,370 8.4/(1.2) 33,280 33,280 5.5/(0.5) 45,530 45,530 11.3/(2.1) 32,130 32,130 6.4/(0.7) 37,810 37,810 4.6/(0.4)
72FDB/60FWB, 50% RH High Flow Total (8F Tw) Sens. GPM / (pd. Ft.) Med. Flow (10F Tw) Low Flow (12F Tw) Total Sens. GPM / (pd. Ft.) Total Sens. GPM / (pd. Ft.)
70FDB/58.5FWB, 50% RH High Flow Total (8F Tw) Sens. GPM / (pd. Ft.) Med. Flow (10F Tw) Total Sens. GPM / (pd. Ft.)
Low Flow Total (12F Tw) Sens. GPM / (pd. Ft.) 75FDB/61FWB, 45% RH High Flow Total (8F Tw) Sens. GPM / (pd. Ft.) Med. Flow (10F Tw) Low Flow (12F Tw) Total Sens. GPM / (pd. Ft.) Total Sens. GPM / (pd. Ft.)
72FDB/58.5FWB, 45% RH High Flow Total (8F Tw) Sens. GPM / (pd. Ft.) Med. Flow (10F Tw) Low Flow (12F Tw) Total Sens. GPM / (pd. Ft.) Total Sens. GPM / (pd. Ft.)
70FDB/57FWB, 45% RH High Flow Total (8F Tw) Sens. GPM / (pd. Ft.) Med. Flow (10F Tw) Low Flow (12F Tw) Total Sens. GPM / (pd. Ft.) Total Sens. GPM / (pd. Ft.)
4-8
Chilled Water
"CCU/D" Model
- 3 to 7 Ton "CCU/D"
Performance Data
CC( )-110-CW
CC( )-200-CW
Chilled Water Control Valve - Sized for Medium Flow @ 75FDB/62.5FWB EAT Conditions
3-way (standard) - Modulating Size / (Cv) (Optional High Pressure) Valve Pressure Rating (Optional High Pressure) 2-way (optional) - Modulating Size / (Cv) (Optional High Pressure) Valve Pressure Rating (Optional High Pressure) 1/2" / (4.0 Cv) 300 psig (400 psig) 3/4" / (7.5 Cv) 300 psig (400 psig) 1/2" / (4.0 Cv) 300 psig (400 psig) 3/4" / (7.5 Cv) 300 psig (400 psig)
3/4 Hp
1,890 @ 0.2" Direct
3.0 Hp
4,130 @ 0.3" Belt
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB, (Optional) BTU/H 63,475 124,902 GPM / Press. Drop (ft.wg) 6.5 / (.8) 12.8 / (2.8) Control - - - - - - - - 2-way, 150 psig, Modulating (0-10 Vdc) - - - - - - - -
4-10, (3.4)
Cycling
Filters - 1" deep (110) & 2" deep (200), 30% Average Efficiency, throwaway
Up-Flow (Free-Front Return): Nom. Size (in.), (Qty.) 36x16, (1) 16x24, (2)
Down-Flow & Up-Flow (Rear Ducted Return): Nom. Size (in.), (Qty.) 25x22, (1)
20x25, (1)
Connection Sizes - Copper, (Water In/Out connections are sized for flow rates at 75FDB/62.5FWB EAT conditions.)
Condensate Drain, (w/ pump) Humidifier Inlet Water In/Out 7/8" OD 1/4" OD 5/8" OD 7/8" OD 1/4" OD 7/8" OD
Physical Data
Approx. Weight 370lbs 440lbs
4-9
Electrical Data
Electrical Data
- DX Compressorized Systems
- DX Compressorized Systems
Consult the Factory for electrical data for 50Hz power supply requirements.
5-1
Electrical Data
Electrical Data
Consult the Factory for electrical data for 50Hz power supply requirements.
EXAMPLES Example 1:
Suppose an application calls for a nominal 1 Ton Mini-Space model CCU/D-41-A with the following features: CCU/D-41-A 208/3/60 Main Power Supply (both evap and cond) 2Kw Electric Reheat/Heat, (Standard) 5 lb/hr Steam Humidifier, (Standard)
Solution: From DX Compressorized Electrical Data table page 5-1 for model CCU/D-41-A incorporating COOLING with ELECTRIC REHEAT/ HEAT and HUMIDIFIER: CCU/D-41-A @ 208/3/60 with above options: FLA (OEM Rated) MCA MFS = = = 23.7 29.7 35
Solution: From DX Compressorized Electrical Data table page 5-1 for model CCU/D-121-W incorporating COOLING Only with or without Hot Gas Reheat (No Electric Reheat or Humidifier): CCU/D-121-W @ 460/3/60 with above options: FLA (OEM Rated) MCA MFS = = = 7.8 12.9 20
5-2
"Index"
(Drwg. #)
6-1
Dimensional Data
22.6"
23.6"
18.5"
Evaporator
12.3"
- 1 to 3.5 Tons
13.7"
72.8"
Piping Connections
22.6"
23.6"
23.6"
REAR/LEFT
Dimensional Data - Floor Stand Heights "A" Dimension Floor Stand Nominal Height Adjustable Height Minimum 3.5" 5.0" 11.0" 14.0" 17.0" 23.0" Maximum 4.5" 7.0" 15.0" 18.0" 21.0" 26.0"
24.0"
6-2
Air Inlet
Evaporator p Air Inlet
72.8"
Compressor on DX Only
AIR OUTLET
FRONT/RIGHT
REAR/LEFT
22.6"
23.6"
2.0"
6-3
5 to 7 Ton CCU -
Dimensional Data
31.0"
39.4"
- 5 to 7 Tons
Evaporator
15.6"
7.1"
72.8"
Optional p Evaporator nlet Evaporator p Air Inlet
Optio Evapor p Air Inlet Optional p Filter Access Piping p g Connections
39.4"
30.8" 31.8"
REAR/LEFT
39.4"
Dimensional Data - Floor Stand Heights "A" Dimension Floor Stand Nominal Height 4.0" (Upflow Units Only) 6.0" 12.0" 15.0" 18.0" 24.0" Adjustable Height Minimum 3.5" 5.0" 11.0" 14.0" 17.0" 23.0" Maximum 4.5" 7.0" 15.0" 18.0" 21.0" 26.0"
6-4
72.8"
Piping Connections
31.8"
Evaporator Air Outlet
FRONT/RIGHT
REAR/LEFT
Optional Turning Vane
30.9" 39.4"
6-5
Notes
Notes
________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________ ____________________________________________________________________________________________________
6-6