Sunteți pe pagina 1din 2

Australasian Standard Project

Room Data Sheets Department Room Name Standard Components Ultrasound Room Tag: 4680 Room Code: ULTR

Area No of Rooms Subtotal of Area Hours of Operation Occupancy Also covers these Rooms Description/ Special Requirements

14.0 M2 1 14.0 M2 Available 24 Hours 1 patient with up to 1 support person; 1-2 staff

Room for diagnostic ultrasound procedures, located close to patient toilet and change rooms. The room will require access for patients on hospital beds. Acoustics: Acoustic privacy required Body Protected electrical area

Amendment

14.03.05, - First Draft 20.04.05, - BOB User review, room area & fittings modified

Room Fabric and outline specifications


ID Fabric Material Finish Specification Selection Remarks

5060 6030 8010 8040 9110 1000 2000 3000 3060

Ceiling Cornice Door protection Door protection Doors Floor finish Skirting Wall finish Wall finish

Acoustic Aluminium Composite Composite Solid Core Vinyl Vinyl Paint Vinyl

Prefinished Powdercoat Prefinished PVC Prefinished PVC Paint Standard slip resistant Prefinished Acrylic, washable Prefinished

Drop-in tiles, 600x1200 24mm shadow angle Protection plate to 900 AFFL To door frame 1 1/2 leaf Seamless, coved Floor vinyl coved, 150 mmH

flush set plasterboard ceiling also acceptable

Equal to 'Acrovyn' Equal to 'Acrovyn' 1400mm clear opening

Splashback

to basin

Fittings and Furniture (FF)


ID Description Category Group Qty Selection

1050 23400 2100 2600 3350 3400 4345 4410 4460 4700 5250

Bench: laminate Bracket: television, ceiling Chair: ergonomic, office Chair: visitor, office Clock: battery operated Coathook Cupboard: sliding doors, adj shelves Cupboard: under bench Cupboard: wall mounted Curtain track: privacy screen Curtain: privacy screen

Furniture/ Fitting Metalwork Furniture/ Fitting Furniture/ Fitting Furniture/ Fitting Metalwork Furniture/ Fitting Furniture/ Fitting Furniture/ Fitting Metalwork Furniture/ Fitting
Provided by HPI for : HCAMC

1 1 3 3 3 1 3 1 1 1 3

1 1 1 2 1 1 1 1 1 1 1

at 1000H, open under part

optional

lockable, optional under part bench, adjustable shelf over bench, adjustable shelves to entry door to entry door
Print Date: 11 May 2006 Page 1 of 2

Issue No: 1 Issue Date: 11 May 2006

This document is for advisory purpose only

Australasian Standard Project


Room Data Sheets Department Room Name
ID Description

Standard Components Ultrasound


Category Group Qty

Room Tag: 4680 Room Code: ULTR


Selection

6152 6154 6156 6158 7500 8100 18445 23950 24100

Dispenser: disposable glove Dispenser: paper/ hand towel Dispenser: soap Dispenser: soap antiseptic Examination couch Footstool Rack: scanhead storage Trolley Waste bin: paper, 20 Litre

Furniture/ Fitting Furniture/ Fitting Furniture/ Fitting Furniture/ Fitting Furniture/ Fitting Furniture/ Fitting Furniture/ Fitting Furniture/ Fitting Furniture/ Fitting

2 2 2 2 3 3 3 3 3

1 1 1 1 1 1 1 1 1 under bench to basin to basin to basin to basin mobile

Fixtures, Equipment and associated Services (FE)


ID Description

Group Qty Ele Data CdW HtW


1 3 3 3 1 1 1 1 ___ ___ yes ___ ___ yes yes ___ yes ___ ___ ___ ___ ___ ___ ___

WmW Tap Dns Gas Selection


yes ___ ___ ___ yes ___ ___ ___ yes ___ ___ ___ ___ ___ ___ ___ ceiling mounted refer to BHWS-B (sim)

2800 57800 54510 54550

Basin: handwash, Type B IMG: Ultrasound scanning unit Telephone: handset, standard Television: 34 cm

Services
ID Description Service Category Qty Remarks

1006 5000 6110 6000 8080 8005 8000 8010 9040 9015 9001 9000 9060

Voice / Data outlet: double Airconditioning Downlights: dimmable General fluorescent Emergency call Patient call handset Patient/ Staff call Staff/ Nurse assist call Body protected GPO: Cleaner GPO: Double GPO: Single GPO: Special: for equipment

Communications HVAC Lighting Lighting Nurse Call Nurse Call Nurse Call Nurse Call Power Power Power Power Power

1 1 1 1 1 3 2 1

+ indicator button & light call button on the handset + indicator button & light + indicator button & light as required 2 - staff workstation; 1- bench exam couch Ultrasound machine

Provided by HPI for : HCAMC

Issue No: 1 Issue Date: 11 May 2006

Print Date:

11 May 2006 Page 2 of 2

This document is for advisory purpose only