Sunteți pe pagina 1din 13

GPRB1

IN OUT 1 (003)
STT Sym. Lockout
Chức năng K/h Out ĐK
1 Overload protection 32 Gen.
2 Over excitation 24 CB90♦
3 Overcurrent 50P Τrip 1
4 Under/ Over Frequency 81O
5 Generator differential 87 88QT - ON N/A
6 Out of step protection 78
SEL300G

7 Loss of excitation 40
8 Negative phase sequence 46 75S - ON

Lockout Relay 86 - 1(1)


9 Undervoltage 27

Emergency Stop
10 Mini. impenance Ger. 21C
CB90♦
11 100% stator earth fault 64F Exc. Trip 1
Opn
12 Over voltage 59P
13 Earth fault Pro. for rotor 64G
14 Self - test alarm* N/A Quick
SC & 86-MT(1) lockout N/A shutdown
15 LCU fault for 86-1 Oper. N/A
N/A

16 Excitation trip 86EX Eme. N/A


17 Bus trip 87 SD. for
18 Self - test alarm* N/A g.Val.
19 Overcurrent exc. 51PT Seq. of
SEL501

20 Overcurrent exc. 50H Event


21 Overcurrent exc. 49 module

Ghi chú: * t/h đưa trực tiếp tới sequence of event module
75S - Mechanical solenoid;
75V - Pneumatic break valve;
88QT - oil lift pump;
63QT - Oil lift pump pressure switch;
14LT - Time delay for 14L (stop);
SC - Synchronus condenser mode
TS - tốc độ tổ máy.
GPRB1
OUT 2 (006)
Out ĐK
Gen.
CB90♦ N/A
Τrip 1

88QT - ON TS ≤ 90%

1. Bre. Pres. Nor.


75S - ON 2. TS < 25%
3. 14L not Stop
Exc. Trip 1
Quick
shutdown N/A
Eme.
SD. for
g.Val.

1. TS < 25%
2. Spe. sig. not fail
75V - ON 3. TS < 50%
4. 14LT not ON
5. Bre. pres. Nor.
GPRB2
IN OUT 1 (004) OUT 2 (006)
STT Sym. Lockout
Chức năng K/h Out ĐK Out ĐK
1 Overload protection 49 Gen. Gen.
2 Over excitation 24 CB90♦ N/A CB90♦Τrip 2
3 Overcurrent 51V Τrip 2
Exc. Trip 2
4 Under/ Over Frequency 81O
CB90♦O N/A
5 Reverse power 32 Exc. Trip 2 Quick
SEL300G

pn
6 Out of step protection 78 shutdown

Lockout Relay 86 - 1(2)


7 Loss of excitation 40 Eme. SD. for
8 Negative phase sequence 46 Quick gVal.

Quick Stop
9 Undervoltage 27 shutdown 63QT not &
88QT - ON
10 90 - 95% stator earth fault 59G TS > 90%
11 Over voltage 59P 1. TS < 25%
Self - test alarm* N/A 2. Spe. sig. not fail
Eme. SD. for 75S - ON
12 Over Cur. For Exc. Trans. 51PT N/A 3. TS < 50%
RK SEL
649 501

gVal.
13 Self - test alarm* N/A 4. 14LT not ON
14 Shaft Current 38 1. TS < 25%
15 Loss of EL N/A 2. Spe. sig. not fail
16 Generator fire Seq. of event 75V - ON 3. TS < 50%
N/A

Syn. Cond. Mode và N/A module 4. 14LT not ON


17
86 - MT lockout 5. Bre. pres. Nor.
Ghi chú: * t/h đưa trực tiếp tới sequence of event module;
75S - Mechanical solenoid;
75V - Pneumatic break valve;
88QT - oil lift pump;
63QT - Oil lift pump pressure switch;
14LT - Time delay for 14L (stop);
TS - tốc độ tổ máy.
MSPRB1
IN OUT 1 (003)
STT Sym. Lockout
Chức năng K/h Out ĐK
1 Breaker failure 50BF
SEL SEL
387E 501

SC mode
2 Breaker failure 50BF 86-1(1)
SET
3 Transformer differential 87
4 Self - test alarm* N/A Gen.
5 Directional Overcurrent 67P CB90♦ N/A
6 Directional earth fault 67G Trip 1
7 Overcurrent protection 50P
SEL351

Excitation CB23♦
8 Overcurrent pro. on HV side 51P
trip 1 Opn
9 Earth fault pro. On HV side 51G
10 Earth fault pro.(90 - 95% ) 59G
Excitation CB90♦
11 Self - test alarm* N/A
trip 1 Opn

Lockout Relay
12 Overcurrent protection 51PT

86 - MT(1)
SEL501

13 Overcurrent protection 50H


14 Over load protecton 49 CB23♦ trip1 N/A
15 Self - test alarm* N/A
16 Overcurrent protection 51PT Sequence of
X,Y SET

17 Overcurrent protection 50H event N/A


SEL501

18 Over load protecton 49 module


19 Restricted earth fault 51G
DS
20 Self - test alarm* N/A
CB200 trip 23♦−9
21 MTR. Fire fighting N/A
Cls
22 Buchholz trip (oil flow) 30F5
23 Press. Relife trip 30F6
N/A

Station
24 Oil temp. very high 30F9
service CB N/A
25 Wind temp. very high 30F11 6♦♦ trip
26 Shutter valve trip 30F12
OUT 2 (006)
Out ĐK

N/A

Gen.
CB90♦ N/A
Trip 1
Excitation
N/A
trip 1

N/A

CB23♦ trip1 N/A

N/A

DS
CB200 trip 23♦−9
Cls

Station
service CB N/A
6♦♦ trip
Ghi chú: * t/h đưa trực tiếp tới
sequence of event module;
75S - Mechanical
solenoid;
75V - Pneumatic
break valve;
88QT - oil lift pump;
63QT - Oil lift pump
pressure switch;
14LT - Time delay for
14L (stop);
TS - tốc độ tổ máy.
MSPRB2
IN OUT 1 (003)
STT Sym. Lockout
Chức năng K/h Out
1 Unit differential 87
387E
SEL

86-1(2)
2 Self - test alarm* N/A
3 Directional Overcurrent 67P 90♦ Trip 2

Relay lockout
4 Directional earth fault 67G Exc. Trip 2

86 - MT(2)
SEL351

5 Overcurrent protection 50P Exc. Trip 2


6 Overcurrent pro. on HV side 51P 23♦ Trip 2
7 Earth fault pro. On HV side 51G CB6♦♦ Trip
8 Self - test alarm* N/A
9 Over load protecton 49 CB200 Trip
SEL501

10 Self - test alarm* N/A


11 Breaker failure 50PP C21, C22 Trip
N/A Seq. of event
12 Breaker failure 50NP
mod.
OUT 1 (003) OUT 2 (006)
ĐK Out ĐK
Syn. Conden.
Exc. Trip 2 N/A
Mode SET
N/A
90♦ Trip 2 N/A
90♦ Opn
23♦ Opn
6♦♦ Trip1 N/A
N/A
N/A 23♦-9
200 Trip1
Cls
DS23♦-9 Cls
23♦ Trip2 N/A

DS23♦-♦ Cls N/A


Ghi chú: * t/h đưa trực tiếp tới
sequence of event module;
75S - Mechanical
solenoid;
75V - Pneumatic
break valve;
88QT - oil lift pump;
63QT - Oil lift pump
pressure switch;
14LT - Time delay for
14L (stop);
TS - tốc độ tổ máy.
MSPRB2
IN
STT Sym. Lockout
Chức năng K/h
1 Turbine guide bearing pad temp. high 38TPX
2 Turbine guide bearing oil temp. high 38TX
3 Press. Of oil supply sys. Of gov low 68GBX
♦TAC
4 PLC failure N/A
5 Speed switching point 5 12
6 Stop 3 signal N/A
7 ♦OSD Over speed safety device 13DX
8 Shaft run out turbine BRG(X) trip 88VTX
9 Shaft run out turbine BRG(Y) trip 88VTV
10 Bracket vibration for lower BRG(X) trip 86BLX
N/A
11 Bracket vibration for lower BRG(Z) trip 86BLZ
12 Bracket vibration for turbine BRG(X) trip 86BTX
13 Bracket vibration for turbine BRG(Z) trip 86BTZ

Relay lockout
14 Bracket vibration for upper BRG trip 86VBU

86 - 2
15 Shaft run out upper BRG(X) trip 86VUX
16 N/A Shaft run out upper BRG(Y) trip 86VUY
17 Shaft run out lower BRG(X) trip 86VLX
18 Shaft run out lower BRG(Y) trip 86VLY
19 Gen. stator coil temp. high trip 38GX
20 Gen. upper guide BRG metal temp. high trip 38UX
21 Gen. upper guide BRG oil temp. high trip 38QUX
22 Gen. lower guide BRG metal temp high trip 38LX
23 Gen. lower guide BRG oli temp high trip 38QLX
N/A
24 Thrust pad temp. high trip 38TX
25 Oil cooler inlet oil temp. high trip 38QLX
26 Gen. core temp high 38GCX
27 Gen. lower guide RGoil level high/low 33QBLX
28 ♦OPS Emergency stop switch 5E
29 ♦ULCB1 Emergency stop switch 5E
OUT 1 (003) OUT 2 (006)
Out ĐK Out ĐK

Guide 88QT ON N/A


valve no
901 trip 1
load
position
1. TS < 20%;
2. Speed signal
75V ON not failure;
3. TS < 50%;;
Excitration trip CB90♦ 4. 14LT not ON.
1 Opn

901 Trip1 N/A

Quick
N/A
shutdown Excitation
N/A
trip1

Emergency Emergency
shutdown for N/A shutdown for N/A
guard valve guard valve

Sequence of For quick


N/A N/A
event module shutdown