PROJECT PROPOSED A&A BODY CONTOURS (NAIL SPA AND BEAUTY SERVICES CONCESSION) AT BASEMENT DESCRIPTION: 2 NORTH, TERMINAL 3, SINGAPORE CHANGI AIRPORT PROJECT NO.: A 106 PREPARED BY: ZAW MOE SENSIBLE HEAT LOAD FACTORS (KWim2) COOLING ITEMS DIRECTIONS AREA (m2) WITH BLINDS LOAD (KVV) N, NW - 0.3 - S,E,NE,SE - 0.23 - EXPOSED GLASS SW - 0.3 - W - 0.4 - SHADED - 0.05 - MEDIUM LIGHT HEAVY CONSTRUCTI CONSTRUCTION CONSTRUCTION ON N, NW - 7 x 10-3 6.42 x 10-3 4.08 x 10-3 - EXPOSED WALLS S,E,NE,SE - 6.42 x 10-3 5.25 x 10-3 5.25 x 10-3 - SW - 8.75 x 10 -3 7 x 10 -3 6.42 x 10 -3 - W - 8.75 x 10-3 7.59 x 10-3 6.42 x 10-3 - SHADED - 2.334x10-3 - WITH - 9.336 x 10 -3 5.84 x 10 -3 2.92 x 10 -3 - CEILING ROOF WITHOUT - 2.51 x 10 -3 14.0 x 10 -3 5.84 x 10 -3 - CEILING GLASS - 1.75 x 10-3 - PARTITION WALL - 1.167 x 10- 3 - INTERNAL SENSIBLE HEAT LOAD (DINING AREA) NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 60 0.06 3.6
LIGHTS W/m 2 128.90 30 3.87 ELECT. APPLIANCES KW 6 0.5 3.00 OUTDOOR AIR 20CMH/PERSON 2.05 (1) TOTAL ROOM SENSIBLE HEAT : 12.52 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 5,364.43 TOTAL DESIGN CMH: 5,750.00 CAAS PROVIDE CMH 3,030.00 NEW ADDITIONAL AIR CON (DINING AREA) 2,720.00
INTERNAL SENSIBLE HEAT LOAD (BODY MASSAGE 1)
NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 2 0.06 0.12
LIGHTS W/m 2 7.43 30 0.22 ELECT. APPLIANCES W/m 2 7.43 27 0.20 OUTDOOR AIR 20CMH/PERSON 0.07 (1) TOTAL ROOM SENSIBLE HEAT : 0.61 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 262.22 DESIGN CMH: 270 INTERNAL SENSIBLE HEAT LOAD (BODY MASSAGE 2) NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 2 0.06 0.12
LIGHTS W/m 2 8.20 30 0.25 ELECT. APPLIANCES W/m 2 8.20 27 0.22 OUTDOOR AIR 20CMH/PERSON 0.07 (1) TOTAL ROOM SENSIBLE HEAT : 0.66 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 281.03 DESIGN CMH: 320 INTERNAL SENSIBLE HEAT LOAD (FACIAL 1) NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 2 0.06 0.12
LIGHTS W/m 2 5.50 30 0.17 ELECT. APPLIANCES W/m 2 5.50 27 0.15 OUTDOOR AIR 20CMH/PERSON 0.07 (1) TOTAL ROOM SENSIBLE HEAT : 0.50 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 215.07 DESIGN CMH: 220 INTERNAL SENSIBLE HEAT LOAD (FACIAL 2) NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 2 0.06 0.12
LIGHTS W/m 2 5.55 30 0.17 ELECT. APPLIANCES W/m 2 5.55 27 0.15 OUTDOOR AIR 20CMH/PERSON 0.07 (1) TOTAL ROOM SENSIBLE HEAT : 0.50 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 216.29 DESIGN CMH: 220 INTERNAL SENSIBLE HEAT LOAD (OFFICE) NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 2 0.06 0.12
LIGHTS W/m 2 5.50 30 0.17 ELECT. APPLIANCES W/m 2 5.50 27 0.15 OUTDOOR AIR 20CMH/PERSON 0.07 (1) TOTAL ROOM SENSIBLE HEAT : 0.50 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 215.07 DESIGN CMH: 220 INTERNAL SENSIBLE HEAT LOAD (SHOULDER MASSAGE ) NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 8 0.06 0.48
LIGHTS W/m 2 10.90 30 0.33 ELECT. APPLIANCES W/m 2 10.90 27 0.29 OUTDOOR AIR 20CMH/PERSON 0.27 (1) TOTAL ROOM SENSIBLE HEAT : 1.37 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 589.13 DESIGN CMH: 600 INTERNAL SENSIBLE HEAT LOAD (FOOT SPA) NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 24 0.06 1.44
LIGHTS W/m 2 35.40 30 1.06 ELECT. APPLIANCES W/m 2 35.40 27 0.96 OUTDOOR AIR 20CMH/PERSON 0.82 (1) TOTAL ROOM SENSIBLE HEAT : 4.28 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 1,833.34 DESIGN CMH: 1900 INTERNAL SENSIBLE HEAT LOAD (RECEPTION & MANICURE) NO. OF DESCRIPTION UNIT UNIT FACTORS PEOPLE PERSON 8 0.06 0.48 LIGHTS W/m 2 23.80 30 0.71 ELECT. APPLIANCES W/m 2 23.80 27 0.64 OUTDOOR AIR 20CMH/PERSON 0.27 (1) TOTAL ROOM SENSIBLE HEAT : 2.11 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 904.26 DESIGN CMH: 970 INTERNAL SENSIBLE HEAT LOAD (CORRIDOR & MANICURE) NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 6 0.06 0.36
LIGHTS W/m 2 15.80 30 0.47 ELECT. APPLIANCES W/m 2 15.80 27 0.43 OUTDOOR AIR 20CMH/PERSON 0.21 (1) TOTAL ROOM SENSIBLE HEAT : 1.47 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 628.11 DESIGN CMH: 710 INTERNAL SENSIBLE HEAT LOAD (PANTRY) NO. OF DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 4 0.06 0.24
LIGHTS W/m 2 6.50 30 0.2 ELECT. APPLIANCES W/m 2 6.50 27 0.18 OUTDOOR AIR 20CMH/PERSON 0.14 (1) TOTAL ROOM SENSIBLE HEAT : 0.75 TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 320.21 DESIGN CMH: 320 TOTAL 5,464.74 TOTAL DESIGN CMH: 5750