GENERAL NOTES

1. FOR SYMBOLS LEGEND SEE DRAWING No. M001

2. FOR STANDARD DRAWING NOTES SEE DRAWING No. M002

3. FOR STANDARD DETAILS SEE DRAWING No. M003

SVP FINISHES ABOVE FINISHED 4. ALL DIMENSIONS ARE IN MILLIMETRES.


ROOF LEVEL CAPPED WITH
BIRD GUARD MESH 5. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE
WITH THE NHS ESTATES HTM'S, HBN, DESIGN GUIDES &
MODEL ENGINEERING SPECIFICATIONS.
SVP FINISHES ABOVE FINISHED VENT WITHIN 3m OF
900 mm 6. THIS DRAWINGS SHALL BE READ IN CONJUNCTION WITH
ROOF LEVEL CAPPED WITH OPENING TO BUILDING
EUROPEAN STANDARD: EN BS 12056 BIRD GUARD MESH SCHEMATICS, SERVICES LAYOUTS, SPECIFICATIONS,
PARTS 1,2,3,4,5 RELEVANT ARCHITECTS, STRUCTURAL & FIRE ENGINEERS
300 mm DRAWINGS AND SCHEDULS.
NATIONAL REGULATIONS: BUILDING
REGULATIONS 2010 TECHNICAL FIRE COLLAR FIRE COLLAR ROOF 7. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO
GUIDANCE DOCUMENT H DRAINAGE FABRICATION, ORDER OR DELIVERY.
AND WASTE WATER DISPOSAL.
COMBINE LOCAL DISCHARGE STACKS 8. FINAL DIMENSIONS OF ALL EQUIPMENT, MATERIALS &
LOCAL REGULATIONS: LOCAL ABOVE LAST FOUL CONNECTION TO FITTINGS SHALL BE CHECKED BY THE MECHANICAL
TRAPPED TUNDISH CONNECTS 50∅
AUTHORITIES HAVE DIFFERENT MINIMISE ROOF PENETRATIONS CONTRACTOR PRIOR TO ORDER/ DELIVERY TO SITE.
TO DRAINAGE SYSTEM. 18-45 mm/m
REQUIREMENTS CONCERNING THE USE *10 mm/m
OF IF APPROVED BY MANUFACTURER 9. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

110∅
TYPES OF DRAINAGE SYSTEMS, AND VENTILATION CONNECTS CO-ORDINATING ALL SERVICES ON SITE.
THE USE OF AIR ADMITTANCE VALVES. VENTILATION CONNECTS ABOVE LAST FOUL CONNECTION AC UNIT AC UNIT
ABOVE LAST FOUL CONNECTION 10. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
DRAINAGE SYSTEM NO 1 IS

110∅
THE ACCEPTED METHOD OF GRAVITY 3000 mm CONDENSATE PIPEWORK PROTECTED FROM FAN PRODUCING A FULL SET OF COMBINED CO-ORDINATED
DRAINAGE INSIDE BUILDINGS IN PRESSURE BY TRAP OR SUITABLE PUMP SERVICES WORKING DRAWINGS.
IRELAND. ARRANGEMENT. CHECK MANUFACTURER
CONDENSATE CONNECTIONS

110∅
REQUIREMENTS.

40∅ 40∅
WASH HAND BASIN
TRAP DIAMETER 32mm
DEPTH OF SEAL 75mm

25∅ 25∅
WC
TRAP DIAMETER 100mm
DEPTH OF SEAL 50mm
SECOND

50∅ CE CE
50∅
18-45 mm/m 18-45 mm/m
10000 mm 10000 mm
SINK
TRAP DIAMETER 40mm MEDICAL WASH HAND BASIN (VENTED) MEDICAL WASH HAND BASIN (VENTED)
DEPTH OF SEAL 75mm 3000 mm
FLOOR DRAIN

CE
50∅
URINAL 18-45 mm/m
TRAP DIAMETER 40mm
DEPTH OF SEAL 75mm 4000 mm
MEDICAL WASH HAND BASIN (UNVENTED)

110∅
SYSTEM I
SANITARY APPLIANCES ARE
CONNECTED TO PARTLY FILLED VENTILATION STACK TO
BRANCH DISCHARGE PIPES ATMOSPHERE (OR CONNECT
ABOVE LAST HIGHEST FOUL
THE PARTLY FILLED BRANCH CONNECTION TO STACK)
MAX No. 8 WCs 25∅
DISCHARGE PIPES ARE DESIGNED 40∅
CE
WITH A FILLING DEGREE OF 0.5 (50%) 18-45 mm/m
AND ARE CONNECTED TO A SINGLE
3000 mm
DISCHARGE STACK. CE
CE MEDICAL WASH HAND BASIN (UNVENTED)
50∅
110∅
18-45 mm/m
9-90 mm/m
CHANGING AREA 15000 mm 10000 mm
FIRST
750 mm

NO UNVENTILATED
CONNECTIONS WITHIN 750mm
OF STACK OFFSET
750 mm Revision Date Details By App.
110∅

REVISED TENDER ISSUE

110∅
TENDER ISSUE
STAGE 2C COSTING
PRELIMINARY ISSUE

Drawing Status:
MAX No. 8 WCs MAX No. 4 WHBs
AIR ADMITTANCE VALVE TENDER ISSUE
REQUIRED IF MAIN DRAIN
INSUFFICIENTLY VENTILATED
CE AAV PER EN12380 40∅
CE 18-45 mm/m CE
50∅
110∅
18-45 mm/m
110∅

9-90 mm/m
110∅ 4000 mm
CHANGING AREA 15000 mm 4000 mm 9-90 mm/m
MEDICAL WASH HAND BASIN (UNVENTED) GROUND
PUBLIC WC
2500 mm
450 mm
REFER TO CIVIL ENGINEERS PACKAGE FOR 1500 mm
DETAILS OF UNDERGROUND DRAINAGE

R300 mm
160∅ AJ 160∅ AJ 160∅ AJ

STUB STACK
Drawing Title:

MECHANICAL SERVICES
SOILS & WASTE SCHEMATIC