Documente Academic
Documente Profesional
Documente Cultură
6.1 AIM
To become familiar with various aspects of the transient and small signal stability
analysis of Single-Machine Infinite Bus (SMIB) system.
6.2 OBJECTIVES
i. To understand modelling and analysis of transient and small signal stability of a
SMIB power system.
ii. To examine the transient stability of a SMIB and determine the critical clearing
time of the system through simulation by trial and error method and by direct
method.
iii. To determine transient stability margin (MW) for different fault conditions.
iv. To obtain linearised swing equation and to determine the roots of characteristics
equation, damped frequency of oscillation and undamped natural frequency.
6.4.1. Stability:
Transient Stability
When a power system is under steady state, the load plus transmission loss equals to
the generation in the system. The generating units run at synchronous speed and
system frequency, voltage, current and power flows are steady. When a large
disturbance such as three phase fault, loss of load, loss of generation etc., occurs the
power balance is upset and the generating units rotors experience either acceleration
or deceleration. The system may come back to a steady state condition maintaining
synchronism or it may break into subsystems or one or more machines may pull out of
synchronism. In the former case the system is said to be stable and in the later case it
is said to be unstable.
6-1
Small Signal Stability
When a power system is under steady state, normal operating condition, the system
may be subjected to small disturbances such as variation in load and generation,
change in field voltage, change in mechanical torque etc. The nature of system
response to small disturbances depends on the operating condition, the transmission
system strength, types of controllers etc. Instability that may result from small
disturbances may be of two forms
For small disturbance, the non-linear equations characterising the dynamics of power
system may be linearised around an operating point for the purpose of analysis. Small
signal analysis using linear techniques provides valuable information about the
dynamic characteristics of the system and assists in its design. The location of the
roots of the characteristic equation of the linearised differential equation will reveal
the stability status of the system. We can also obtain the response of rotor angle and
frequency of the rotor of the synchronous machines.
6-2
6.4.2. Mathematical Modelling For Transient Stability
Consider a single machine connected to an infinite bus shown in fig. 6.3. An infinite
bus is a source of invariable frequency and voltage.
Line 1
G
Line 2 Infinite bus
Generator Et x
Transformer EB
The equivalent circuit with the generator represented by classical model and all
resistances neglected is shown in fig. 6.4.
jX1
EB o
jX’d jXtr
It Et
E’ e jX2
jX
E’ EB
o
Pe
E’ = E t + jX’ dIt
X = X’ d +XE where XE = Xtr + X1 || X2
6-3
D o = synchronous speed of rotor
Pe = electrical power output of generator in p.u
Consider that the generator output power and the terminal voltage magnitude |Et| are
specified.
jX1
It
|Et| jXtr
EH jX2 EB
Xd ’ Xtr jX3
|Et|
|E’| E F EB E
G o
Assume Et = |Et| E
G o
as reference
P
IR =
Et
-Q
II =
Et
EB = Et – jX4 (IR + jII)
EB = |EB| - H IKJ)LNMPO
6-4
Q = tan -1
X4P / Et
QX 4
( Et − )
Et
(6.4)
Angle of EB with respect to Et R Q
Let E’ = |E’| S T UWV5XY4Z1[ \^]`_\;abY)Y<ced t = |Et| f
g o
= (Et – X’ d II )+ jIRX’ d
|Et| |Et|
= E’ R + jE’ I
where
ER = |Et| + QX’ d
|Et|
EI = PX’ d
|Et|
h
UijY#kml -1
(E’ I / E’ R)
(6.5)
|E’| = (E 2R + E2 I) ½
Swing Equation
During any disturbance in the system, the rotor will accelerate or decelerate with
respect to synchronously rotating axis and the relative motion begins. The equation
describing the relative motion is called as swing equation.
The fundamental equation of motion of the rotor of the synchronous machine is given
by
6-5
2H . d2 – Pmax (6.6)
o dt
m
where
Pm = mechanical power input in p.u
Pmax = max. electrical power out in p.u
H = Inertial constant in seconds
P <$¢¡;£¤¥§¦©¨£1¦^¥-¦tªb «6¨§ª8¡t¥W ¡;¬¨§¡
£5¦ asured from synchronous by rotating reference
frame.
®
o = Synchronous angular velocity rad/sec
¬1¯ °²± r) ³
´ µ ¶¸·e¹4º¼»¢½<¾ m - Pmax ¿ÀÁÃÂ^»
dt
Ä Â ÅÇÆ (6.7)
r- Æ ÅȲÆ
o r
dt
Changing rotor speed in to per unit and introducing damping torque, equation (6.7)
become
Ä ½<È²Æ r ) = 1 (Pm - Pmax ¿ÀÉÁ - KD È²Æ r )
dt 2H
Ä Â ÅÇÆ ÈÊÆ o r
(6.8)
dt
where
ÈÊÆr = rotor speed deviation in p.u
Pm = mechanical input in p.u
KD = damping co-efficient in p.u
Numerical Integration Techniques
The differential equations (6.8) are to be solved using numerical techniques. There
are several techniques available and two of them are given below.
(iv) Compute the average derivative : PXav (t) = ½ [PX(t) + PX(t+ Ý¢Þ#ß
6-6
(v) Compute the final estimate: X (t+ ã¢ä#åæç5è«ä«å¢éêØç av (t) ãä
II. Fourth order Runge-Kutta Method
This is an explicit algorithm. The general formula giving the value of X for the
(n+1)th step is
K4 = f (X + K , t +ë¢ì#ï¢ë¢ì
n 3 n
6.4.6. Critical Clearing Time and Clearing Angle From Equal Area Criteria
This method can be used for quick prediction of stability but is applicable only to
single machine connected to infinite bus. The fundamental concepts and principles of
stability can be explained very well. Consider the system shown in fig. 6.3. and its
model in Fig 6.5. The terminal power is given by equation 6.1 and the power angle
curves for various operating condition is given in fig. 6.7.
6-7
A Pe - before fault
P
.
fB
. ..
a e A2
d g
Mechanical Power
.
A1
After fault clearing
c
b C During fault
ñ o ñ 1 ñ max
The steady state operating condition is given by point a and the corresponding rotor
ò
óôWõ4ö1÷«ø ñ
o. Consider a three phase fault at location F on line 2 as shown in fig. 6.3.
The fault is cleared by opening the circuit breakers at both ends of the line. The p- ñ
plot for three network conditions are shown in fig. 6.7.
When the fault occurs, the operating point changes from a to b. Since Pm > Pe, the
rotor accelerates until the operating point reaches c where the fault is 1. ù õ«ö;ò
ú ö8ûüòmý ñ
þÿ $ÿ
The operation shifts to e. Now Pe>PM
! bÿ þ +ÿ +ÿ @ÿ
increase until the kinetic energy gained during the period of acceleration (Area A1) is
transferred to the system. The operating point moves from e to f such that area A2 is
equal to A1. The rotor angle will oscillate back and forth around at its natural
frequency such that |area A1| = |area A2|. This is known equal area criterion.
.
P3max "
e 2
P
a. .. .d
f
A2
Pm
A1
b. c 3
P2max # !
o max
6-8
L M N O!PHQ
Pm RTS c - S o) - UWV X Y Z\[][_^ U
2max # V 3max sin [?][ – Pm `T[ max - [ c)
a b c d
T
ef3ghij*klgm,f.i?nogHprq"mshqtkJf!s=q"ou v.m,fixwTo3jzy
c
{}|!~ {|!~t {|~
(P3max – P2max)
The corresponding critical clearing time is given by te =
T3I
- o.. oPm)
.,FH;*;0r
r !I
¿ ¾ e ËFÌ=ÍÎÉÏ
where
|E’|E B ÐÑ}Ò Í#Ï o , called synchronising co-efficient.
Ks =
X
The state equations (6.8) are rewritten as
where Tm , Te ÙJÚÛ9Ü ÝÞß à!á ÎÉÕ ÚrÜ Í ÞÛÚ\àÝ!Ü Ø Í Þ!ÛBÛ ÓâÓ ÛBã!Ü;Ù Ø Ü Ò Ý!á Ï Ü Í ØHä ÛåÚ Ò Ø Ò ÚrÙÝ.æç;ÛèÜ Ý
o is
the base (rated) rotor speed in electrical radians per second,
Û
çÛ
é Ø Ú*Üé
ÙçÚ*Ù Ó Ü;ÙBÝ Í á Õ
KD is the damping coefficient in p.u., H is in p.u (seconds).
6-9
(d2 ìÄíîï 2ðzñlò<íôó o
ð±õ9ö#ò"í÷3øùûúëü
m – ýxþ úì
– KD îì (6.16)
.. .
ó
o dt
Ks
'(
r
_
+ &
'*) 1/2 Hs $ o/ s '+
m _
KD
s2 úÉìñ þ
ð
-þ úÉì
o – 0 + KD ö þ
úÉìñ
þ
ð
- úÉì o
ùûÿ
ýxþ
ó
o
ú}ìñ
þ
ð±õó
o
úÉü
m (s) (6.18)
2H 2H 2H
s2 + KD þ ÿ
ýxþ
ó
o
ú ìñ
þ
ð±õ ñ
þ
ÿ
ý
íH÷3øxðûú
D
ì
o
ÿó
o
úëü
m (s) (6.19)
2H 2H 2H
(s + 20&n
o (6.21)
&
(s2 + 2 0&nV &n)
where 0 ½ KD+&n
s2 + 2 0&nV &n2 = 0
6-10
,.-0/214365798-:;3=<#> ?
Taking inverse Laplace transform of equation (6.20) and (6.21) and taking P Q o = 10o
= 0.1745 radians; we get the equation for motion of rotor relative to synchronously
revolving field and the rotor angular frequency
6.5 EXERCISES
6.5.1 A power system comprising a thermal generating plant with four 555 MVA,
24kV, 60HZ units supplies power to an infinite bus through a transformer and
two transmission lines (refer Fig 6.10)
H.T
L.T line 1
Transformer Infinite Bus
G
Et line 2
P+jQ EB
The data for the system in per unit on a base of 2220 MVA, 24 kV is given
below:
6-11
An equivalent generator representing the four units, characterized by classical
model: Xd’ = 0.3 p.u H= 3.5 MW-s/MVA
Case 1:
It is proposed to examine the transient stability of the system for a three-phase-to-
ground fault at the end of line 2 near H.T bus occurring at time t= 0 sec. The fault
is cleared at 0.07 sec. by simultaneous opening of the two circuit breakers at both
the ends of line 2.
(a) Calculate the initial conditions necessary for the classical model of the
machine for the above pre-fault operating condition, determine the
critical clearing angle and time for the fault using “Equal Area Criterion”
and hence comment on the stability of the system for this fault.
(b) Simulate the above sequence of fault occurrence and clearance using the
software available and plot the swing curve (rotor angle versus time) as
well as the curves showing angular velocity and real power delivered by
the plant versus time.
(c) Determine the critical clearing angle and time for the above fault through
trial and error method by repeating the simulation in (b) for different fault
clearing times and compare the critical clearing angle and time
obtained with that obtained by Equal Area Criterion in (a).
6.5.2 For the system given in exercise 6.5.1 and for the same operating condition,
examine the transient stability using the software available for the following
faults.
Case 2:
Three-phase-to-ground fault at the end of line 2 near infinite bus occurs at
t=0 sec and is cleared at t=0.07 sec by the simultaneous opening of two
breakers in line 2.
Case 3:
Three-phase-to-ground fault at the mid point of line 2 occurs at t=0 sec and is
cleared at t=0.07 sec by the simultaneous opening of two breakers in line 2.
Comment on the transient stability of the system under case 2 and case 3 and
compare the severity of the faults; cases 1,2 and 3 from the point of view of
maximum rotor swing and also by comparing the clearing time margin
available.
6-12
6.5.3 Determine the steady-state stability margin (MW) available for the system
under the given operating condition in exercise 6.5.1. Also determine the
transient stability margin (MW) available for the operating condition given in
exercise 6.5.1. for the three cases of fault, case 1, case 2 and case 3. Can the
severity of the fault be measured using this margin?
(a) Write the linearized swing equation of the system. Obtain the
characteristic equation, its roots, damped frequency of oscillation in Hz,
damping ratio and undamped natural frequency. Obtain also the force-free
µ ¶ response, T` !¡£¢¡¢6;¢=¥¤x¦{¡§¢¨;¢q¡ª©«0r¬L®;¢¡ ¯ °±^²´³ and
o
time
¯r°±²c°¸·º¹4»¼=½¾D¿TÀÁÃÂ0Ä4Â{¼qÅqÂ0ÆÅ=ÁD»ÈǸÉT¿qÊ#ÂË
ÁÌ
6.5.5 Repeat the small-signal stability analysis carried out using the software
package in exercise 6.5.4 with the following parameters and comment on the
relative stability of each case:
(b) KD = 1.5 p.u but with P = 1.2, 1.5 and 2.0 p.u
6-13