Sunteți pe pagina 1din 3

Low Voltage Power Cable

Single Core 600/1000 V Cable with Circular Stranded Conductor, PVC Jacket

XLPE Insulation Binding Tape PVC Bedding Copper or Aluminum Conductor

Jacket

Aluminum Wire Armor

Standards / Testing Specications Detail Description or Construction


Single cross-linked polyethylene insulated conductor of stranded copper or aluminum, with aluminum wire armor and thermoplastic jacket of PVC (Polyvinyl Chloride). IEC 60502-1

Marking
0.6/1 KV XLPE/AWA/PVC A x B SQ.MM., PHELPS DODGE A = Number of cores B = Size of conductor (SQ.MM.)

Application
For use in ducts, trays and direct burial in ground. The cable is subject to immerse in water all the time.

Installation
Low voltage power cable can be installed in duct, tray or direct burial. It is recommended that the installation instructions indicated by the Local Electric Code, or any equivalent, be followed, so that the safeguarding of persons and the integrity of the product will not be affected by deciencies in the installation.

www.pdic.com

PDIC01176 | 09.24.04

Low Voltage Power Cable


Single Core 600/1000 V Cable with Circular Stranded Conductor, PVC Jacket

Nominal CrossSectional Area of Conductor1) mm 50 70 95 120 150 185 240 300 400 500 630 800 1000
2

Thickness of Insulation

Thickness of Extruded Bedding mm 0.8 0.8 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.4 1.4
1)

Nominal Aluminum Armor Wire Diameter mm 0.9 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5

Thickness of Oversheath

Approximate Overall Diameter mm 17.5 20.2 22.3 24.2 27.4 30.0 32.8 35.6 40.5 44.2 48.8 55.4 60.6 Copper 805 995 1285 1555 1905 2325 2935 3590 4615 5700 7195 9365 11550

Cable Weight kg / km

Standard packing

mm 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4 2.6 2.8

mm 1.5 1.5 1.6 1.6 1.7 1.8 1.8 1.9 2.0 2.1 2.2 2.4 2.5

Aluminum 465 565 695 805 975 1155 1385 1645 2140 2620 3195 4255 5025

m 500/R 500/R 500/R 500/R 500/R 500/R 500/R 500/R 500/R 500/R 500/R 500/R 500/R

Circular or compacted circular stranded conductor (class2). R = Packing in reel

www.pdic.com

PDIC01176 | 09.24.04

Low Voltage Power Cable


Single Core 600/1000 V Cable with Circular Stranded Conductor, PVC Jacket

Current carrying capacities in amperes for 600/1000 V XLPE insulation Single core cable in free Air (30C) and in ground (20C)
Nominal Cross-sectional Area of Conductor1

Conductor in Free Air @ 30C

Conductor in Ground @ 20C

mm2 50 70 95 120 150 185 240 300 400 500 630

Copper 207 268 328 383 444 510 607 703 823 946 1088

Aluminum 159 206 253 296 343 395 471 547 663 770 899

Copper 144 178 211 240 271 304 351 396 -

Aluminum 112 138 164 186 210 236 272 308 -

* Ampacity for 1/C (Copper) in Air * Note: Ampacity of single core Copper conductor, XLPE insulation based on conductor temperature of 90C and ambient air temperature of 30C per Table A. 52-12(52-C11) of IEC Standard Publication No. 60364-5-52 : 2001 column 5 * Ampacity for 1/C (Aluminum) in Air * Note: Ampacity of single core copper Aluminum conductor, XLPE insulation based on conductor temperature of 90C and ambient air temperature of 30C per Table A. 52-13(52-C12) of IEC Standard Publication No. 60364-5-52 : 2001 column 5 * Ampacity Direct Burial 1/C * Note: Ampacity of single core cable, XLPE insulation based on conductor temperature of 90C and ground temperature of 20C per Table A. 52-5(52-C4) of IEC Standard Publication No. 60364-5-52 : 2001 column 7

www.pdic.com

PDIC01176 | 09.24.04