Documente Academic
Documente Profesional
Documente Cultură
1.1.1 - 1/2
3. Normal temperature NT
3.1 NT technique System description ................................. 3.1.1 Carrier pipe matrix ................................... 3.1.2 Tracer pipes ............................................ 3.1.3 3.2 NT Components Steel pipe system Pipe St. 37.0 BW .................................. 3.2.1 Pipe St. 35.8 I ...................................... 3.2.2 Pipe AISI 304 L/AISI 316 L ................... 3.2.3 Pipe AISI 316 TI ................................... 3.2.4 Pipe AISI 316 L (Dairy pipes) ................ 3.2.5 Pipe Mapress ....................................... 3.2.6 Fix pipe .................................................... 3.2.7 Reduction fitting ...................................... 3.2.8 Elbow 90 - St. 37.0 BW/St. 35.8 I .......... 3.2.9 Elbow 90 - AISI 316 L .......................... 3.2.10 T-fitting straight, St. 37.0 BW/St. 35.8 I 3.2.11 T-fitting straight AISI 316 L ................. 3.2.12 T-fitting St. 37.0 BW/ St. 35.8 I .......... 3.2.13 Anchor .................................................. 3.2.14
Version/06.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Table of contents
Generel introduction Generelt Introduktion Generelt - Introduktion
3.5 NT Components Joint FXI .......................................................... 3.5.1 FXC ......................................................... 3.5.2 BX ........................................................... 3.5.3 LM .......................................................... 3.5.4 LMC ........................................................ 3.5.5 BM .......................................................... 3.5.6 TMC ........................................................ 3.5.7 TMC-C .................................................... 3.5.8 EC ........................................................... 3.5.9 DHEC .................................................... 3.5.10 HEC ...................................................... 3.5.11 HDHEC .................................................. 3.5.12
1.1.1 - 2/2
5. High temperature HT3
5.1 HT3 technique System description ................................. 5.1.1 Operating Temperature and Heat Loss .... 5.1.2 Thermal expansion .................................. 5.1.3 Expansion Absorption ............................. 5.1.4 Anchors .................................................. 5.1.5 Trenches and Soil Covering ..................... 5.1.6 5.2 HT3 components Steel pipe system Pipe ........................................................ 5.2.1 Reduction ................................................ 5.2.2 Elbow ...................................................... 5.2.3 Expansion Pipes ...................................... 5.2.4 T-fitting straight ....................................... 5.2.5 T-fitting .................................................... 5.2.6 Anchoring ................................................ 5.2.7 Anchor elbow .......................................... 5.2.8 Compensator .......................................... 5.2.9 5.3 HT3 components Joints HBXS ...................................................... 5.3.1 HEW ....................................................... 5.3.2 HDHEC .................................................... 5.3.3 5.4 HT3 installation HBXS ...................................................... 5.4.1 HEW ....................................................... 5.4.2 HDHEC .................................................... 5.4.3
Version/06.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Logstor
Generel introduction Generelt Introduktion Generelt - Introduktion
Logstor has manufactured pre-insulated pipe systems since 1992. They all adjust the demands on the industrial market. Our primary markets for the pipe systems are provisions industry, chemical industry, wood industry, cold stores and marine. With a wide product range and flexibility the preinsulated pipe systems are adaptable to even very specific demands. The pre-insulated pipe systems are characterized as follows: Pre-insulated systems with PUR- insulation have a very high insulation capacity. Pipe supports are to be fitted outside the jacket to avoid thermal bridges Insulation and the jacket material have a high mechanical strength, which make the preinsulated pipe systems resistant to physical influences, for instance when they are used as footbridge. The jacket joints are 100 % sealed, so that the pipes are cleanable, and result in low maintenance costs.
1.1.2 - 1/2
the pre-insulated pipes are available on the spot, for instance at a shipyard. Logstor and its customers Over 40 years experience with the development and sale of complete pre-insulated pipe systems, known with a worldwide reputation. A well developed network of distributors and subsidiaries has resulted in thousands of kilometres of the characteristic Logstor pipes being laid all over the world. Our distributors and subsidiaries represent us in over 30 countries around the world. We regularly attend international exhibitions manned by personnel from Logstor and local distributors. Extensive service Logstors engineers and technicians provide an extensive service for any given project right from initial planning to commission, engineering and follow-up servicing and training of fitters. Years of experience of the installation of joints and devising customized solutions have given us the expertise to carry out installation work and supervision within our market areas. Production locations Logstor was founded in the early 60s, in Lgstr, Northern Jutland, in Denmark, which is still the site of most of our production today. Over the years, the factory has expanded to cover 50,000 m2 on a site of 420,000 m2. To cope with rising demand in Eastern Europe, a new factory was opened in Zabrze, Poland. This new facility combines the latest technology and well-proven Logstor traditions. Large orders for remote areas are generally produced using our mobile production units, in particular offshore pipe systems one of Logstors specialities.
The pipes are all dimensionally stable, sturdy and high-insulated. The installation is simple and quick. This means, lower total costs, higher security and longer validity. For the marine market Logstor has developed an insulation system, which is called LT pipe system, for the low temperature area, which has the abovementioned advantages contrast with the traditional insulated pipe systems. The properties of the insulation system are higher, the installation is quick and simple, and the system is maintenance-free after installation. If you wish to save time and costs,
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Logstor
Generel introduction Generelt Introduktion Generelt - Introduktion
Quality assurance Logstor has been DS/ISO 9001 certified by Lloyds since 1992 for product development and manufacturing, plus project management, which has entailed introduction of the strictest requirements for quality assurance in the whole company. Quality control is also the customers guarantee that all Logstor products and services fulfil our industrys strictest standards.
1.1.2 - 2/2
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Catalogue layout
Generel introduction Generelt Introduktion Generelt - Introduktion
This product catalogue describes Logstors industrial standard products. It describes how these products can be combined to form systems, and how they should be handled and installed. This chapter gives an overview of the standard systems of the industrial program. Furthermore, general information is provided on material specifications and handling of the products. The subsequent chapters from 2 to 5 describe the individual pipe systems. The chapters dealing with the individual systems, all have the same basic layout and contain chapters concerning technique, components and joints.
1.1.3 - 1/1
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Product programme
Generel introduction Generelt Introduktion Generelt - Introduktion
Logstor industrial systems are designed as complete systems for specific applications and as such, can only be used within those areas. LT Low temperature Operating temperature 200- +140 C Bonded system Freely suspended systems only See system description page 2.1.1 NT Normal temperature Operating temperature 60 - -10 C freely suspended system Operating temperature -10 - +140 C freely suspended and directly buried system Bonded system only See system description page 3.1.1 HT2 High temperature Operating temperature +140 C - +315 C Bonded system Freely suspended systems only See system description page 4.1.1 HT3 High temperature Operating temperature +140 C - +315 C Sliding system Directly buried systems only See system description page 5.1.1 Flexible system Logstor offers flexible pipe systems for temperatures ranging from -200 C up to +120 C. A characteristic feature of the flexible systems is the carrier pipe, which is manufactured in a flexible material. In general, expansion can be left out of consideration, when it comes to flexible systems. In the flexible systems, the stresses are absorbed from temperature effects in the carrier pipe. Minor pipe dimensions are delivered in coils. The pipes can be bent on site for the desired layout of the pipeline.
1.1.4 - 1/3
The pipes move as a single entity. Movements can be restricted by pipe supports or other friction against the jacket pipes. Freely suspended pipe systems must be able to move freely. Change of temperature in directly buried systems can be absorbed as stresses in the system. A sandwich construction consisting of mineral wool and PUR foam is applied in the temperature range from +140 C to + 315 C. Used as a directly buried system (HT3), the pre-insulated high temperature system operates as a sliding system (see sliding system), and when used as a freely suspended system it operates as a bonded system (HT2).
System types Bonded system In a bonded system, the carrier pipe insulation and jacket are bonded together by adhesion, which allows them to expand and move as a single entity. The outer surface of the carrier pipe and the inner surface of the jacket pipe are pretreated, so that the foam adheres to the pipes, and that stresses can be transmitted through the insulation. Sliding system In a sliding system, the carrier pipe moves inside the insulation, which adheres to the jacket pipe. Therefore, the jacket pipe must be retained from the outside, e.g. by the soil friction in the case of directly buried pipe systems. The expansion is absorbed in special components within the jacket of the system. Consequently, the carrier pipe must be fixed with anchors (compensators and expansion bends).
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Product programme
Generel introduction Generelt Introduktion Generelt - Introduktion
Carrier pipes Logstors industrial products are manufactured and supplied in different pipe systems including carrier pipes of different types. The choice of the carrier pipe depends on the transported medium. The carrier pipe is available in steel, stainless steel, copper or in plastic. The pipe can be supplied with tracer pipes. Insulation The type of insulation depends on the medium temperature. Logstor cooling pipes are insulated with a special HCFC/CFC free PUR- foam, which is applicable in the temperature area -200 C - +120 C. Furthermore, flexible foam pipe systems are available within temperature variations from -200 C - +120 C. During temperatures between 140 C and 315 C, the insulation is composed of mineral wool and PUR foam according to the present temperature. Jacket pipes The industrial pipes are available with black or white HPDE jackets (polyethylene), as standard. The jacket is UV resistant. Warning wires The steel- and copper programme is available with integrated warning wires for registration of moisture in the insulation, which is caused by damages on the jacket or carrier pipe. In this way, moisture damages can be discovered in time and be repaired, before corrosive damages on the carrier pipe arise. See the Logstor district heating catalogue. Certificates Logstor offers you complete traceability if we are informed by placing of the order. Joints The Logstor industrial programme is primarily based on straight pipes and joints. We offer you a range of joints, which fit applications for pipes and components. Logstor supplies two different joint solutions: - Joints for foaming on site. - Joints consisting of pre-manufactured PUR half shells. All joints are produced of shrinkable PE plastic materials. Straight pipes and sleeves up to and including 315 are used for freely suspended pipe systems. The product programme includes bend joints, straight joints, T- joints, reduction and repair joints plus end caps. Logstor district heating joints are used for directly buried pipe systems. Fittings Logstor offers you a complete fitting programme of joint solutions in St.35.8,St. 37.0 BW, AISI 304 L and AISI 316 L, which complements our joint solutions. The programme includes: A: Jacket pipe B: Insulation C: Carrier pipe - Elbows - T-joints - Reductions - Anchors
Version/05.2004.UK Text/ 18-05-2004
1.1.4 - 2/3
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Product programme
Generel introduction Generelt Introduktion Generelt - Introduktion
Centring The insulation centring of carrier pipes is performed using centring spacers. The spacers are made of heat resistant materials with low thermal conductivity. Tracer pipes All pipe types can be supplied with an empty pipe laid directly into the insulation, within which selfregulating heat cables can be laid, or a fluid heat medium can be passed through.
1.1.4 - 3/3
Example
Thermal life A correct installation of the complete pipe system secures a thermal life of more than 10 years, depending on operational conditions.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Carrier pipes
Steel pipe systems
1.2.1 - 1/5
Seamless steel pipes St. 35.8 I to P235 GH TC1 according to EN 10216 equivalent to St. 35.8 I according to the previous DIN 17175 (05.79). Measures and weight according to DIN 2448. Mill certificate to EN 10204/3.1 B. Ends, in dimensions from 3.2 mm wall thickness, are bevelled according to DIN 2559/2.2 or 2.1. Ends < 3.2 mm wall thickness are bevelled according to DIN 2559/1. Supplied in lengths of 6 and 12 m. Application Heat, steam and condensate. Mechanical properties of St. 35.8 l: Density Tensile strength Yield stress Youngs modulus Thermal properties: Coefficient of expansion Specific heat Thermal conductivity 1.210-5 C-1 0.43 kJ/kgC 76 W/mC 7850 > 360 > 235 2,1105 kg/m3 N/mm2 N/mm2 N/mm2
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Carrier pipes
Stainless steel pipe systems
1.2.1 - 2/5
Welded pipes AISI 316L according to EN 10217-7 equivalent to the previous DIN 17457. Welding factor 1.0. Tolerances according to DIN 2463. Mill of certificate according to EN 10204/3.1.B. Supplied in lengths of 6 m. Application Chemistry, food and condensate. Mechanical properties of AISI 316 L: Density 7950 Tensile strength (20C) > 490 Yield stress (20C) > 190 Youngs modulus (20C) 1.9510-5 Thermal properties: Coefficient of expansion (20C) Specific heat Thermal conductivity Dairy pipes (wst1.4432) Stainless steel pipes are also supplied as abrasive welded dairy pipes in the quality AISI 316 L, and the inside is yielded and calibrated. Application Milk and dairy products 1.710-5 C-1 0.50 kJ/kgC 15 W/mC kg/m3 N/mm2 N/mm2 N/mm2
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Carrier pipes
Stainless steel pipe systems
1.2.1 - 3/5
High-alloyed, austenitic CrNiMo- steel (w. 1.4401) according to EN 1008. Suitable for all types of potable water. Suitable for all types of treated water from softened to desalinated. Corrosion resistant. No corrosion caused by foreign substances. The supply is based on the blucher pipes or similar quality.
Mechanical properties of AISI 316 TI: Density 7950 Tensile strength (20C) > 500 Yield stress (20C) > 210 Youngs modulus (20C) 1.9510-5 Thermal properties: Coefficient of expansion (20C) Specific heat Thermal conductivity 1.710-5 C-1 0.50 kJ/kgC 15 W/mC kg/m3 N/mm2 N/mm2 N/mm2
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Carrier pipes
Copper pipe systems
1.2.1 - 4/5
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Carrier pipes
Plastic pipe systems
1.2.1 - 5/5
PE80/PE100 pressure pipes High-density polyethylene according to DIN 8074 (the industrial pipe standards). Produced according to DS2119/SBC 218. Pipe certificate type 2.2. Application Provisions. Mechanical properties of PE80: Density Yield stress Thermal properties: Coefficient of expansion 1.7 . 10-4 C-1 Thermal conductivity 0.4 W/mC Melt flow rate 0.85 g/10 min. > 958 kg/m3 > 19 N/mm2
Mechanical properties of PE100: Density Yield stress Thermal properties: Coefficient of expansion 1.7 . 10-4 C-1 Thermal conductivity 0.4 W/mC Melt flow rate 0.22 g/10 min. > 945 kg/m3 > 23 N/mm2
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Insulation
Material specifications Generelt Introduktion Generelt - Introduktion
The pre-insulated straight pipes and components for bonded systems are supplied with a hard polyurethane foam insulation. Pre- insulated pipes in coils are supplied with semi-flexible foam. PUR insulation Hard polyurethane foam (PUR) which fulfils the functional requirements of EN 253: Material: Polyurethane foam made from polyol and isocyanate. The foam is homogeneous with an average cell size of max. 0.5 mm. Density Closed cells Water absorption if boiled Compressive strength 10% deformation Axial shear strength Tangential shear strength Max. operating temperature 60 kg/m3 > 88% 10% (Vol) 0.3 N/mm2 0.12 N/mm2 0.20 N/mm2 140 C HT3 insulation Two-part insulation is used in directly buried systems where temperatures exceed 140 C. The pipe is designed as a two-part insulation, of which the inner part consists of a half shell of mineral wool and the outer part of a PUR foam layer. HT3 operates as a sliding system and is applied at max. temperatures of 210 C or 315 C. Mineral wool Hard mineral wool. Density: < 323 mm < 323 mm 75 kg/m3 40 kg/m3 < 1% (vol) 0.01 N/mm2 0.04 W/m C 315 C
1.2.2 - 1/1
Thermal conductivity at 50 C < 0.03 W/m C Insulation PUR- mineral wool (HT2/HT3) Jacket Mineral wool
The technical requirements are tested according to the EN 253 standard, which is valid for district heating pipes. The material parameters are subject to revision due to technical developments. NT and LT insulation Logstor pipe systems are insulated with PUR foam, which ensures high insulation properties. The PUR foam must not be subject to temperatures exceeding 140 C, by continuous operation. HT2 insulation This system is applied at temperatures above 140 C. The pipe is designed as a two-part insulation, of which the inner part consists of a half shell of mineral wool and the outer part of a PUR foam layer. The system operates as a bonded system, and is used as a freely suspended system at max. temperatures of 210 C or 315 C.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Jacket pipes
Material specifications Generelt Introduktion Generelt - Introduktion
LR products with steel carrier pipes complying with EN 253 are supplied with PEH jackets, or with extruded jackets, which fulfill the technical requirements, stated in EN 253. HDPE jackets High-density polyethylene. Mechanical properties of HDPE: Density Yield stress Max. load (during transport) (continually) Thermal properties: Coefficient of expansion Thermal conductivity Melt flow rate 2 . 10-4 C-1 0.43 W/m C 0.3-0.8 g/10 min. 3 0.5 N/mm N/mm2 > 940 > 19 kg/m3 N/mm2
1.2.3 - 1/1
Material parameters are subject to revision due to technical developments. Pre-insulated straight pipes are supplied with black as well as white HDPE jackets. Pipes in coils are supplied with black LDPE jackets (low-density polyethylene). Black HDPE jacket pipes are UV-resistant as a result of addition of UV-impeded additives. Black jacket pipes are therefore suitable outdoor as well as indoor. White jacket pipes are moderate UV- resistant and are only suitable for indoor insulation.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Joints
Material specifications Generelt Introduktion Generelt - Introduktion
Properties Shrink sleeves are made of elastic, shrinkable modified PE plastic material. Black shrink sleeves are UV- stabilized. White shrink sleeves are not UV-stabilized and is only for indoor installation. Packing Black sleeves: White bag, white tape White sleeves: White bag, yellow tape with black writing. Do not remove packing before installation. It is recommended to leave the protective bag on the pipe until the installation has been completed. Cleaning High pressure cleaning: Max. pressure 160 bar Max. water temperature 60 C Cleaning distance between nozzle and product surface: Min. 30 cm. Cleaning materials: Topax 18 (with chlorine) or Topax 66(without chlorine) or similar. Cellosolve (for removal of grease) Chemicals The product is resistant to the following chemicals: Lye, petrol, turpentine, petroleum products, salt, sodium sulphate, chlorine etc. The product has a short-term resistance to the following chemicals: Acetone, cellulose, hydrochloric acid (0.1 M), acetic acid (0.1 M), sulphuric acid (0.1 M). Test The values of the joints observe the following: ASTM E96 permeability test < 0.8 g per joint per day at 38 C and 90% relative air humidity. ISO 3127 drop test (- 20 C, 0 faults in 100 drops)
1.2.4 - 1/1
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Fittings
Material specifications Generelt Introduktion Generelt - Introduktion
The specification for carrier pipes, insulation and jackets apply to all pre-insulated components. The Logstor components comply with the technical requirements of EN 448. Components with steel carrier pipes are supplied with bevelled ends according to DIN 1626/4.10.5. Elbows The angle of deflection is defined as the deviation from a straight pipe. The bending radius, R, depends on the pipe dimension, as follows: St. 37.0 BW d d 508.0 mm bended R = 2.5 St. 35.8 I Other components dd 323 weld elbow: DIN 2605 Bauart 3 Stainless ISO dimension Weld elbows R-1651/ABE-211 Stainless metric dimension Weld elbows R-1651/ABE-111 Compensators, valves and other components integrated in the Logstor standard systems are provided by recognised suppliers. The pipe ends on the pre-insulated components have the same dimension as the pipes with which they are to be joined. The assembly length depends on the component. Compensators are supplied fully expanded and ready for use. If the compensator is to be integrated in an operational hot system, it is possible to change the presetting. Compensators and valves have been designed to resist the tensile and compressive stresses that may appear in the pipe system. T-fittings The main pipe is supplied with a branch connection stub which is flared into the main pipe, so that the wall thickness of the branch connection is not reduced. Branch pipes are welded with a regular circumferential seam, which ensures ideal stress distribution. Movable T-fittings only permit expansion in direction of the main pipe. The branch pipe has to be ensured with an anchoring pipe or an expansion element. Anchoring pipes The anchor plate consists of a circular flange fully welded to the carrier pipe. The circular flange has been proportioned to transmit the stresses that arise in connection with axial tension in the carrier pipe of 150 N/mm2.
1.2.5 - 1/1
Standard bjninger
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Tracer pipes
Material specifications Generelt Introduktion Generelt - Introduktion
Tracer pipes can be supplied as copper or PE. PE tracer pipe material Mechanical properties of PE: Density Yield stress Thermal properties: Coefficient of expansion Thermal conductivity Melt flow rate Cu tracer pipe material Hard copper F37 according to DIN 1784/17671 corresponding to SIS 5015-04. Tolerances according to EN 1057 Mechanical properties of hard copper: Density Tensile strength Elongation at rupture Thermal properties: Coefficient of expansion Specific heat Thermal conductivity Electrical conductivity 1.68 . 10-5 C-1 385 kJ/kg C 365 W/m C 57 Sm/mm 2 8940 kg/m3 > 280 N/mm2 > min. 5 % 2 . 10-4 C-1 0.43 W/m C 0.3-0.8 g/10 min. > > 940 kg/m3 19 N/mm2
1.2.6 - 1/1
Foamed tracer pipes, for heat cables or liquids heat media, can partly frost-proof a pipe system and partly maintain the required temperature. A conductive material is installed between the tracer pipe and the carrier pipe in order to ensure a sufficient conductivity of the heat transmission. A defective cable can be replaced by moulding a tracer pipe, and an assembly of the cable every 612 m will not be necessary. For further information on tracer pipes, see chapter 2-5 for each individual system.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
1.3.1 - 1/2
Thermal resistance values calculated by: Di RPUR = ln[ Di / d ] / [2 PUR] RR RM RJ RH = ln[ d / di ] / [2 R ] = ln[ D / Di ] / [2 PE ] = ln[ 4(z + 0,0685 E) / D ] / [2 E ] = ln[ 1 + (2(z + 0,0685 E))2 /C2] / [2 PUR] Int. dia. Jacket Ext. dia. Jacket Int. dia. carrier pipe Ext. dia. carrier pipe Thermal conductivity, PUR Thermal conductivity, carrier pipe Thermal conductivity, jacket Thermal conductivity, soil Laying depth Distance between axes
Where: Di [m] : D [m] : di [m] : d [m] : PUR [W/m K]: R [W/m K]: PE J z C [W/m K]: [W/m K]: [m] : [m] :
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
1.3.1 - 2/2
The calculations above can also be used to calculate other media than air if the values exist. Radiation transmission coefficient hR [W/m2K] : hR = 4 T 3 Where: [-] : Emmissivity [W/m2K4]: Stefan-Bolzmann constant T [K] : Air temperature, Kelvin
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe dimensioning
Dimensioning oduktion Generelt Introduktion Generelt - Intr
This chapter describes the method used to calculate pressure loss. You can choose either to optimise the pipe, or calculate the capacity of a given pipe. Optimisation calculation Pipe dimensioning is calculated using the medium volume and a criterion, either the pressure gradient or the flow. The total volume to be conveyed in a pipe is: Q=V Where: Q [kg/s] [kg/m3] V [m3/s] Speed is: v = 4 Q / di 2 Where: v [m/sec.] di [m] Giving: di MIN = ( 4 Q / v )0,5 Pressure loss p (Pa) is calculated as follows: p = 0,5 v2 f L / di Where: p [Pa] f [-] L [m] : Pressure loss : Friction factor : Pipe length : Velocity : Int. dia. carrier pipe : Water flow : Density : Volume flow
1.3.2 - 1/1
A direct calculation can also be made using the following formula: f = 0,25 / [ log[ K / 3,7 di + 5,74 / Re0,9 ]]2 5000 < Re < 108 10-6 < k/di < 10-2 Capacity calculation The calculation above can also be used to calculate pressure loss and capacity of a given pipe. Calculation program These and many other calculations can easily be performed using the calculation programme StaTech. StaTech The programme is available at Logstor.
To calculate friction factor using Colebrook & White, interpolation has to be applied. This is done using a start value to gradually reach a convergence level. 1 / f0,5 = 1,14 2 log[ k / di + 9,35/Re f0,5 ] Where: k [mm] Re [-] n [m2/s] : Roughness factor : Reynolds formula (vR/n) : Kinematic viscosity
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Design rules
Freely suspended system
1.3.3 - 1/2
Minimal mounting distance between jacket/ jacket and jacket/wall: L > 320 at installation of the T-joint. L > 150 after installation of the pipe lengths.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Design rules
Directly buried system
1.3.3 - 2/2
Backfilling should be carried out with a shovel, and the material around the pipes should be compacted by hand. As the backfilling progresses any supports under the pipes should be removed. Warning tape is placed at least 200 mm above both pipes, and the trench is refilled, rather during recycling of the excavated material. Compaction of the backfilling from 200-500 mm above the pipes can be carried out using a vibratory plate with a maximum surface pressure of 100 k Pa. In areas with substantial traffic load, or where a soil cover of min. 500 mm cannot be observed, the pipes must be protected, e.g. by means of a steel plate. Fitting To avoid leaks and corrosion, all joints should be free of sand and impurities. During the process the pipes are placed above or directly next to the deepening, to obtain an optimum joint and tightening test.
The material is not to contain damaging organic material. Sharp-edged grains, which may damage pipe and joints, should be avoided.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Project preparation
Dimensioning oduktion Generelt Introduktion Generelt - Intr
Any preparatory component count by Logstor shall not be binding and can only be used for advance planning on the customers behalf for the ordering of materials. The customer shall generally provide a written order indicating the number of components and amounts. A corresponding order confirmation will subsequently be provided. Pipe routing must be inspected prior to placing the order at which point the customer shall be responsible for defining the precise path of the pipe route and the space available. In the case of large multi-branched networks, Logstor personnel should be involved so that any static or system requirements can be taken into account from the beginning. If Logstor is to calculate quantities and the basic layout from drawings and plans, the customer shall provide written confirmation of their accuracy and scope to Logstor. Installations in shafts and channels in particular will require an inspection of existing documentation on-site. Written agreement must be reached as early as possible in the project of the extent to which Logstor is to provide consultation and calculations for the pipe system. Pre-insulated industrial pipes from Logstor are always project-specific special products, and cannot be returned. Pipe routing The LT, NT and HT industrial pipe systems can be subject to significant expansion due to their operating temperatures. Expansion is absorbed using expansion components L-, Z-, or U bends or compensators precisely calculated in accordance with the pipe routing. Installation may therefore only be carried out in accordance with the pipe route agreed with Logstor. Any amendments must be agreed and approved by Logstor before installation, for the purpose of ensuring pipe stability. Upon project completion, the as-build documentation shall be reviewed on-site and forwarded to Logstor.
1.3.4 - 1/1
If no agreement on pipe routing and installation facilities exists, or if installation has been performed in contradiction of the agreement, no claims for deficiencies will be entertained. Please note that freely suspended and directly buried systems may only be used for the purpose for which they are designed, as per chapter 1.1.4.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
1.4.1 - 1/2
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
1.4.1 - 2/2
Pipes with white HDPE - jackets The white jacket pipes are supplied covered with a white or transparent polyethylene bag to protect the pipes against impurities, weather, scratches and discolorations. Handling and storage of the white jacket must take place most carefully, as it is very sensitive to impurities. If a dirty surface cannot be cleaned with water, use solvents for plastic. It is recommended to leave the protective bag on the pipe until the installation has been completed. The protective bag is removed by cutting it open with a scissor along the pipe. The polyethylene bag is to deposit with ordinary garbage, as burned polyethylene is recycled in nature.
Fittings must also be placed on a level surface. It is important to ensure that the free pipe ends point downwards to avoid rainwater collecting on them. White pipes are to be stored on slats preferably indoor. Shrink sleeves, shrink materials and foam components must be stored dry and cool at temperatures of less than 50 C, to avoid a premature shrinking of the material. If components for polyurethane foam become frozen, they must be slowly thawed at a temperature of 35 C. Rigid joints are to be stacked upright to avoid them becoming oval. Coated pipes Coated pipes must be treated with special care. The pipes must be placed on sand beds and be transported on a soft bedding layer.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Installation
Product handling Generelt Introduktion Generelt - Introduktion
It is crucial for the service life of the components that the joints between the two jacket pipes are and remain watertight. If installed correctly, the joint will be just as tight as the jacket pipes and have the same strength. The pre-treatment of the plastic material is crucial to the effectiveness of the joint. It is of importance, that the materials used in the joint are completely clean and dry. Any labels on the jacket pipe within the installation area must be removed. Scratches must be scraped off. Large scratches must be filled with mastic. When components designed to absorb expansion are installed, it has to be ensured that the necessary expansion is possible. During joint installation the working premises must be protected against wind and weather. The joint installation must not be carried out under circumstances, where the activation of the plastic surfaces cannot be maintained throughout the installation process or other circumstances, which might reduce the quality of the joint. Leak and pressure test The leak and pressure test must be carried out in accordance with accepted standards, and in all respects as described by the client. There are five golden rules of how to install a Logstor HDPE- jacket pipe joint:
1.4.2 - 1/7
Installation All components of the joint must be installed in a single work routine without interruptions. Inspection Finally, the fitter ensures that the joint has been made correctly, and that the surface is even and smooth. Follow the fitting instruction of the joints thoroughly. Course K3001 The purpose of the course is to communicate the required knowledge of the materials and their application to the assembly fitters, in order to enable them to carry out insulation of the carrier pipe joints in the Logstor pipe systems, and to store and support them. Furthermore, they get acquainted with the most important components of the product catalogue. Many customers require a valid certificate before start-up of the installation. Qualifications of the participants None, but it is advantageous to have a professional background from the plastic industry. After completion The participant will be qualified for: Installations of closed joints Installations of open T-joints Installations of joints for foaming
Preparation All materials must be at hand when the installation work starts. Cleaning All surfaces must be cleaned. Activation All plastic surfaces must be activated by means of a gas flame to ensure that the plastic oxides are reduced. At the same time, the components are preheated.
This part includes real practical installations which are time-consuming, but give the participant a fundamental experience of joint installations. At the same time, the participants have become acquainted with components, which will enable them to choose the right spare parts at any given time.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Installation
Product handling Generelt Introduktion Generelt - Introduktion
Furthermore, the participant will have a knowledge of the following: Repair materials and auxiliaries Transport and handling Components of the pipe systems Installation of pipe supports Estimation of thermal expansion Certificate A written examination and an evaluation of a chosen assignment are to be carried out. Both are to be passed before a certificate can be issued. Carrier pipe joints The Logstor standard carrier pipe programme includes steel, stainless steel, cobber and plastic. There are different methods to assemble these types of carrier pipes. The table below indicates typical assembling methods for the specific types of carrier pipes. The diagram is intended as a guide. It is recommended, that the customer contacts Logstor for further information, in connection with special media and e.g. pressure and temperature conditions.
Assembling methods Pipe types Steel pipes St. 37.0 BW St. 35.8 I Stainless steel pipes AISI 316 L Copper pipes Hard Soft Plastic pipes PEX () Welding Soldering Press coupling Mechanical coupling
1.4.2 - 2/7
The present instructions are meant as a help to the fitter, as they will enable him to estimate the circumstances of the installation BEFORE the beginning of the process, and to avoid delay caused by commonplace design errors.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Installation
Jacket pipe joints
1.4.2 - 3/7
Half shells used for traditional insulation of pipe joints.
Injection of a suitable volume of mixed polyol and isocyanate. These agents react and develop PUR foam. Activation (plastic): A propane gas flame is used to pre-heat the surface. By this process, the pure basic material stands out and the surface gets dry and temperate. The plastic surfaces of the joint always have to be activated.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Installation
Jacket pipe joints
1.4.2 - 4/7
After a thoroughly activation of the plastic, the surface temperature must be at least 60 C. Once the right temperature has been reached, i.e. when the plastic oxides have been reduced, the surface of the plastic becomes silk-matt. The plastic material must not look shiny or burned. The joint must be installed immediately after activation, since plastic oxides reform quickly. The heat used when activating the surface is also used in the following installation, thereby ensuring a close connection between the surfaces and correct adhesion.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Installation
Branch pipe
1.4.2 - 5/7
In case of branch pipe with offset, TMC and BM are used together. The maximum measures are stated below.
00 2
>5
00
Mu
ffe
3 80 5 50
00 2
>5
00
TMC During branch pipe installation the maximum measures must be observed to use TMC.
Mu 3 80
ffe
5 50
uffe
50 5 80 3
D1
Mu
2 50 ffe 3
D2 20
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Installation
Branch pipe
1.4.2 - 6/7
C
A L
= =
D X C L D1
= = = =
C L
= =
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Installation
Z-offset and EC/DHEC
1.4.2 - 7/7
X = Min. D, but may also be carried out in cases, where welding fittings are welded directly together. L = Pipe section. Max. 400 mm pipe section without using pre-insulated pipe sections.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Shortening of pipes
Product handling Generelt Introduktion Generelt - Introduktion
The following procedure is used when shortening pipes:
1.4.3 - 1/1
1. Place two cuts all the way round the jacket and insulation at a distance of 150 mm from either side of the cutting point. It is easiest to use a coarselytoothed hacksaw, handsaw or eclipse saw.
3. Remove the jacket and insulation material. Use a knife, a chisel or similar to remove the insulation material. Be careful not to damage any sensor wires installed. 4. Scrape off any remaining insulation residue and treat the carrier pipe until the exposed surface is completely clean. Use a steel brush, abrasive cloth, rotating brushes or similar. Cleaning the pipe prevents polyurethane from degassing/burning off during heat-treatment. Before flame treatment, the insulation material must be protected against heat and against catching fire. 5. Cut the carrier pipe When adapting a straight pipe to other components, the straight pipe is the one to be shortened. Where a pipe is to be shortened, special zebra pipes can be used. This makes it easier to remove the insulation, and the risk of polyurethane degassing/burning off during heat-treatment is avoided.
2. Place a diagonal cut through the jacket between the two circumferential cuts. Be careful not to damage the remaining jacket.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe supports
Produkt Generelt - Introduktion Introduktion Generelthandling
Logstor pre-insulated pipes have such an enormous pressure strength that the pipe supports are to be installed on the outside of the jacket. This suspension system has the great advantage over traditionally pre-insulated systems, that it prevents problems deriving from heat and thermal bridges and penetration of water and moisture at the pipe supports from arising, thus avoiding corrosion of the steel pipe, which leads to unnecessary energy losses and heavy maintenance costs. Logstor supplies pipe supports specially produced for pre-insulated pipe systems. These pipe supports can be directly installed on the walls and ceiling or in common racks. Logstor keeps pipe supports as standard stock goods.They are available in a galvanized and a stainless version. Other qualities are available on order. Model A is used for bolting
1.4.4 - 1/3
Calculation of support width The pipe supports,on the pre-insulated pipes, can be placed with the optimal support width. However, the maximum permissible surface pressure of the insulation material must be observed. The length of the support should be calculated as follows: A D G g = (G Lb + Fv) g D sin/2 till.
= Jacket pipe diameter [mm] = Net weight of the pipe, incl. medium [kg/m] = Gravity [9.82]
L b = Distance between supports, or the pipe length to be supported [m] = Support angle [45 - 180] Logstor uses 180 as standard
Fv = The sum of any vertical, external loads [kg] (snow, walk bridge or support to other pipes) til = Permissible surface pressure on the insulation material is 0.1 N/mm2
Fv
D
A
Model B is used for pendular suspension L
Lb
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe supports
Produkt Generelt - Introduktion Introduktion Generelthandling
Installation of pipe supports It is important that the pipe either lies loosely in the support to allow unhindered movement, or that guides are used. It is also possible to place a teflon sliding plate under the support. When the pipe is laid in such a way that it moves in the support, it is important not to place the supports on or near the joints, as these would otherwise be damaged by the movement of the pipe. When expansion is absorbed in the joints, it is important that the support does not block the movement. The supports at the elbows must therefore be able to move in two directions. This can be done by letting the support slide on the plate. Pendular suspensions are not permitted when using axial compensators. Avoid placing the supports directly on or near the joint. If this is impossible use a support type 2. Teflon Type 1
1.4.4 - 2/3
type 2
type 1
type 2
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe supports
Produkt Generelt - Introduktion Introduktion Generelthandling
Supporting distance Logstor recommends that the supporting distance of a pre-insulated pipe, is the same as the one applied on a pipe that has not been insulated. Steel and threaded pipes
DN Dimension Max.distance,metre (max. temperature +210 C) 184C Water 15 20 21.3 x 2.0 21.3 x 2.6 26.9 x 2.0 26.9 x 2.3 26.9 x 2.6 33.7 x 2.0 33.7 x 2.6 33.7 x 3.2 42.4 x 2.0 42.4 x 2.6 42.4 x 3.2 48.3 x 2.6 48.3 x 3.2 60.3 x 2.9 60.3 x 3.6 76.1 x 2.9 88.9 x 3.2 88.9 x 4.0 114.3 x 3.6 139.7 x 4.0 168.3 x 4.0 219.1 x 4.5 219.1 x 6.3 273 x 5 323.9 x 5.6 2.0 2.0 1.8 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.8 3.0 3.0 3.5 3.5 4.0 4.5 4.5 5.0 5.0 7.5 9.0 9.0 10.0 11.0 Steam 2.0 2.0 2.3 2.5 2.5 2.2 2.5 2.7 2.8 3.0 3.2 3.5 3.5 4.0 4.0 4.0 5.0 5.0 6.5 6.5 8.5 10.0 10.0 11.0 11.0 210C Water 1.8 1.8 1.6 1.8 1.8 1.8 2.0 2.0 2.0 2.0 2.5 2.8 2.8 2.8 2.8 3.0 3.5 3.5 4.0 4.5 5.0 5.0 5.0 7.5 9.0 Steam 1.8 1.8 1.8 2.0 2.0 1.8 2.0 2.0 2.5 2.5 2.8 2.8 2.8 3.0 3.0 3.5 4.0 4.0 4.0 5.0 6.5 6.5 6.5 8.5 10.0
1.4.4 - 3/3
Copper pipes
Dimension (Carrier pipe) 10 x 1 mm 12 x 1 mm 15 x 1 mm 18 x 1 mm 22 x 1 mm 28 x 1.2 mm 35 x 1.5 mm 42 x 1.5 mm 54 x 1.5 mm 70 x 2 mm 88.9 x 2.5 mm Distance,metre 1.0 1.1 1.2 1.3 1.4 1.7 1.8 1.9 2.2 2.5 2.6
25
32
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
System description
temperature LT Low temperature
2.1.1 - 1/1
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
AISI 304 L (wst. 1.4307) / AISI 316 L (wst. 1.4432)
2.2.1 - 1/1
Series 5
Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 21.3 2.0 160 3.1 0.2 26.9 2.0 160 3.4 0.4 33.7 2.0 160 3.7 0.7 42.4 2.0 180 4.6 1.2
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
Copper
2.2.2 - 1/1
Series 5
Cu-pipe diameter d, mm Cu-pipe wall thickness, mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 18 1.0 160 1.7 0.2 22 1.0 160 1.9 0.3 28 1.2 160 2.7 0.5 35 1.5 160 3.6 0.8
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
System description
NT Normal temperature
3.1.1 - 1/1
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
3.1.2 - 1/2
Product Pipes applied for transport of liquid products such as dairy products. Cooling Pipes applied to cooling classified in the most applied refrigerants. Water for domestic use Pipes applied to water for domestic use. Approved for this specific use according to Danish regulations.
= Typical application. Indicates the primary application of the pipe system. () = Applicable. Indicates that the pipe system may be applied for this purpose, but that the composition of the medium might require a closer examination of the solution.
- = Irrelevant. Indicates that it is more advantageous to use other pipe types, which typically are applied to this specific purpose. = Not applicable. Indicates that the pipe type in question, must not be used due to temperature conditions and/or medium compositions.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
3.1.2 - 2/2
Scope of application Product (temp.) Cooling (medium) <140C Co 2 N2 Water, domestic use
Chapter LR Industrial pipe systems Steel pipe system St. 37.0 BW St. 35.8 I Stainless steel pipe system AISI 316 L Dairy pipes Copper pipe system Hard Soft Plastic pipe system PEX HDPE 3.4.1 3.4.2 3.3.2 3.3.1 3.2.4 3.2.5 3.2.1 3.2.2 () <95C
<120C
()
()
() ()
()
()
()
= Typical application. Indicates the primary application of the pipe system. () = Applicable. Indicates that the pipe system may be applied for this purpose, but that the composition of the medium might require a closer examination of the solution.
- = Irrelevant. Indicates that it is more advantageous to use other pipe types, which typically are applied to this specific purpose. = Not applicable. Indicates that the pipe type in question, must not be used due to temperature conditions and/or medium compositions.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
3.1.3 - 1/1
Min. angle
Max. angle
1 tracer d [mm] 21.3 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273 323.9 355.6 406.4 457
Version/05.2004.UK
2 tracers min [] max [] 180 180 180 180 180 180 180 180 180 180 180 180 180 180 180
3 tracers min [] 90 90 90 90 60 60 30 30 30 30 30 30 30 30 max [] 120 120 120 120 120 120 120 120 120 120 120 120 120 120
Installed tracers numbers Antal 2 2-3 2-4 2-4 2-4 2-4 2-4 2-4 2-4 2-4 2-4 2-4 2-4 2-4 2-4
x x x x x x x x x x x x x x x x x x
120 90 90 90 90 60 60 30 30 30 30 30 30 30 30
508
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
St. 37.0 BW
3.2.1 - 1/2
Series 1
Steel pipe diameter d, inch Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m Steel pipe diameter d, inch Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 1/2" 21.3 2.6 90 2.2 0.2 8" 219.1 4.5 315 31.1 34.7 3/4" 26.9 2.6 90 2.5 0.4 10" 273.0 5.0 400 45.0 54.3 1" 33.7 3.2 90 3.4 0.6 12" 323.9 5.6 450 58.3 76.8
Series 2
Steel pipe diameter d, inch Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m Steel pipe diameter d, inch Steel pipe diameter d, mm Steel pipe wall thickn., mm
Version/05.2004.UK
1/2" 21.3 2.6 110 2.9 0.2 8" 219.1 4.5 355 35.5 34.7
3/4" 26.9 2.6 110 3.2 0.4 10" 273.0 5.0 450 51.9 54.3
1" 33.7 3.2 110 4.0 0.6 12" 323.9 5.6 500 66.4 76.8
1 1/4" 1 1/2" 42.4 2.6 125 4.5 1.1 14" 355.6 5.6 560 72.8 93.2 48.3 2.6 125 4.3 1.5 16" 406.4 6.3 630 92.7 121.8
2" 60.3 2.9 140 6.5 2.3 20" 508.0 6.3 800 127.8 192.8
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
St. 37.0 BW
3.2.1 - 2/2
3" 88.9 3.2 200 10.9 5.4 4" 114.3 3.6 250 16.3 9.0 5" 139.7 3.6 280 20.0 13.8 6" 168.3 4.0 315 26.0 20.2
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
St. 35.8 I
3.2.2 - 1/2
Series 1
Steel pipe diameter d, inch Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m Length L, m 1/2" 3/4"
21.3 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273 323.9 2.0 90 1.9 0.2 6 2.3 90 2.3 0.4 6 2.6 90 2.9 0.6 6 2.6 110 3.8 1.1 6 2.6 110 4.2 1.5 6 2.9 125 5.6 2.3 2.9 3.2 3.6 4.0 4.5 6.3 6.3 7.1
200 225
250 315
400 450
13.0 17.1 22.6 39.8 53.3 69.8 9.0 13.6 19.9 33.5 53.3 75.3
Series 2
Steel pipe diameter d, inch Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m Length L, m 1/2" 3/4" 1" 1 1/4"1 1/2" 2" 2 1/2" 3" 4" 5" 6" 8" 10" 12"
21.3 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273 323.9 2.0 2.3 2.6 2.6 2.6 125 4.5 1.5 6 2.9 140 6.1 2.3 2.9 3.2 3.6 4.0 4.5 6.3 6.3 7.1
225 250
280 355
450 500
13.9 18.3 24.1 43.1 57.6 74.7 9.0 13.6 19.9 33.5 53.3 75.3
Series 3
Steel pipe diameter d, inch Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m
Version/05.2004.UK
1/2" 3/4"
4"
5"
6"
8"
10"
12"
21.3 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273 323.9 2.0 2.3 2.6 2.6 2.6 140 5.0 1.5 6 2.9 160 6.6 2.3 2.9 3.2 3.6 4.0 4.5 6.3 6.3 7.1
180 200
250 280
315 400
500 560
8.1 10.2 15.1 19.9 26.1 46.6 62.5 81.2 3.9 5.3 9.0 13.6 19.9 33.5 53.3 75.3
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
St. 35.8 I
3.2.2 - 2/2
21.3 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 2.0 2.3 2.6 2.6 2.6 180 6.0 1.5 6 2.9 200 7.8 2.3 2.9 3.2 3.6 315
225 250
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
AISI 304 L wst. 1.4301 / AISI 316 L wst. 1.4432
3.2.3 - 1/2
200 225
250 315
400 450
8.8 10.9 13.0 18.1 29.6 35.3 9.6 14.5 21.2 36.3 56.3 79.8
225 280
225 250
280 355
450 500
9.8 12.1 14.7 20.9 33.8 40.2 9.6 14.5 21.2 36.3 56.3 79.8
200 225
250 315
8,5 10,4 14,0 20,1 28,7 39,7 7.9 12.3 17.7 31.4 49.1 70.7
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
AISI 304 L wst. 1.4301 / AISI 316 L wst. 1.4432
3.2.3 - 2/2
21.3 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273 323.9 2.0 2.0 2.0 2.0 2.0 140 4.4 1.5 2.0 160 5.4 2.5 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6
250 280
315 400
500 560
11.0 13.8 16.8 24.4 38.7 46.8 9.6 14.5 21.2 36.3 56.3 79.8
225 250
280 355
9.4 11.5 15.9 23.4 33.4 46.3 7.9 12.3 17.7 31.4 49.1 70.7
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
AISI 316 TI wst. 1.4571
3.2.4 - 1/1
21.3 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273 323.9 2.0 90 1.9 0.2 2.0 90 2.2 0.4 2.0 90 2.5 0.7 2.0 110 3.3 1.2 2.0 110 3.6 1.5 2.0 125 4.4 2.5 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6
200 225
250 315
400 450
8.8 10.9 13.0 18.1 29.6 35.3 9.6 14.5 21.2 36.3 56.3 79.8
225 250
280 355
450 500
9.8 12.1 14.7 20.9 33.8 40.2 9.6 14.5 21.2 36.3 56.3 79.8
250 280
315 400
500 560
11.0 13.8 16.8 24.4 38.7 46.8 9.6 14.5 21.2 36.3 56.3 79.8
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
AISI 316 L (Dairy pipes) wst. 1.4432
3.2.5 - 1/1
Series 1
Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 25 1.2 90 1.7 0.4 32 1.2 90 1.8 0.7 38 1.2 110 2.4 1.0 51 1.2 110 2.8 1.9
Series 2
Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 25 1.2 110 2.1 0.4 32 1.2 110 2.3 0.7 38 1.2 125 2.7 1.0 51 1.2 125 3.1 1.9 63.5 1.2 140 4.3 2.9 76 2.0 160 6.1 4.1 101.6 2.0 200 8.4 7.5
Series 3
Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 25 1.2 125 2.4 0.4 32 1.2 125 2.6 0.7 38 1.2 140 3.2 1.0 51 1.2 140 3.6 1.9 63.5 1.2 160 4.8 2.9 76 2.0 180 6.6 4.1 101.6 2.0 225 9.3 7.5
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
Mapress wst. 1.4404
3.2.6 - 1/1
Series 1
Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 15 1.0 90 1.4 0.13 18 1.0 90 1.4 0.2 22 1.2 90 1.6 0.3 28 1.2 90 1.8 0.5
Series 2
Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 15 1.0 110 1.8 0.13 18 1.0 110 1.9 0.2 22 1.2 110 2.1 0.3 28 1.2 110 2.2 0.5 35 1.5 125 2.7 0.8 42 1.5 125 3.2 1.2 54 1.5 140 4.1 2.0 76.1 2.0 160 6.2 4.1 88.9 2.0 180 7.3 5.7 108 2.0 200 8.8 8.5
Series 3
Steel pipe diameter d, mm Steel pipe wall thickn., mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 15 1.0 125 2.1 0.13 18 1.0 125 2.2 0.2 22 1.2 125 2.4 0.3 28 1.2 125 2.5 0.5 35 1.5 140 3.0 0.8 42 1.5 140 3.7 1.2 54 1.5 160 4.6 2.0 76.1 2.0 180 6.8 4.1 88.9 2.0 200 8.0 5.7 108 2.0 225 9.8 8.5
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Fix pipe
NT componentsoduktion system Generelt Introduktion Generelt - Intr - Steel pipe
Fix pipes are produced to the same specifications as these of straight pipes. See page: 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 St. 37.0 BW St. 35.8 I AISI 314L/AISI 316L AISI 316TI AISI 316L - Dairy pipes
3.2.7 - 1/1
Fix pipes are used as adaptors. A pipe length must not consist of more than one fix pipe. The insulation of a fix pipe does not adhere to the carrier pipe. It is easy to shorten and strip a fix pipe. Pipes with jacket dimension 90 are supplied with 100 mm exposed pipe ends. Available in series 1, 2 and 3 Supplied as goods made to order. Component no. 20001L
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Reduction fitting
BW, St. 37.0 BW, St. 35.8 I
3.2.8 - 1/1
St. 35.8 I
d1 D1 L1 d2 168.3 219.1 273.0 D2 250 315 400 X X X X 273.0 323.9 400 450
1500 1500
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Elbow 90
BW, St. 37.0 BW, St. 35.8 I
3.2.9 - 1/1
1300 1500
Series 2
d, mm D, mm Length L, mm 219.1 273 323.9 355.6 406.4 508 355 450 500 560 630 800
Series 2
Steel pipe diameter d, mm 219.1 273 323.9 Jacket pipe dia. D, mm Length L, mm 355 450 500
Series 3
d, mm D, mm Length L, mm 219.1 273 323.9 355.6 406.4 508 400 500 560 630 710 900
Series 3
Steel pipe diameter d, mm 219.1 273 323.9 Jacket pipe dia. D, mm Length L, mm 400 500 560
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Elbow 90
AISI 316 L wst.1.4432
3.2.10 - 1/1
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
T-fitting straight
St. 37.0 BW and St. 35.8 I
3.2.11 - 1/1
2
Series 1
d1 D1 L1 d2 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 508.0 D2 90 90 110 110 125 140 160 200 225 250 315 400 450 500 560 710 600 600 600 600 600 600 600 600 600 600 600 600 600 600
600 600 600 600 600 700 700 700 600 600 600 600 600 700 700 700 600 600 600 600 600 700 700 700 600 600 600 600 600 600 700 700 700 600 600 600 600 600 700 700 700 600 600 600 600 700 700 700 600 600 600 700 700 700 600 600 700 700 700 600 700 700 700 700 700 700 700 700 700
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
T-fitting straight
AISI 316 L wst.1.4432
3.2.12 - 1/1
2
104 180
129 200
154 225
204 280
254 355
305 400
1200 1400 1400 1600 1600 1800 L2 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
T-fitting
St. 37.0 BW and St. 35.8 I
3.2.13 - 1/1
2
Series 1
d1 D1 L1 d2 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 508.0 D2 90 90 110 110 125 140 160 200 225 250 315 400 450 500 560 710 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1200 1000 1000 1000 1000 1000 1000 1000 1200 1000 1000 1000 1000 1000 1200 1200 1200 1200 1200 1200 1200 1200 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1600 1600 1800
Total height to casing 450 mm inclusive, H = D1 + D2 + 75 mm. Total height from casing 500 mm, H = D1 + D2 + 100 mm.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Anchor
BW, St. 37.0 BW, St. 35.8 I
3.2.14 - 1/1
Steel pipe diameter d, mm 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3219.1 273 323.9 355.6 406.4 508 Jacket pipe dia. D, mm Anchor flange dia. D1, mm Anchor flange area, Max. load, kN Length L1, mm Total length L, mm cm2 110 215 268 49 110 125 215 215 268 240 56 78 140 160 240 260 298 330 100 129 200 300 392 188 225 300 309 231 250 315 350 415 471 573 310 455 400 450 500 550 707 785 631 840 500 560 600 660 710 810
1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1400 1400 1400 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2500 2500 2500
1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
Copper
3.3.1 - 1/1
Series 1
Cu pipe diameter d, mm Cu pipe wall thickness, mm Jacket pipe diam. D, mm Weight, kg/m Water content, l/m 35 1.5 90 2.3 0.8 42 1.5 110 3.0 1.2 54 1.5 125 3.7 2.0 70 2.0 140 5.7 3.4
Series 2
Cu pipe diameter d, mm Cu pipe wall thickness, mm Jacket pipe diam. D, mm Weight, kg/m Water content, l/m 35 1.5 110 2.7 0.8 42 1.5 125 3.2 1.2 54 1.5 140 4.1 2.0 70 2.0 160 6.0 3.4 88.9 2.5 180 8.7 5.5
Series 3
Cu pipe diameter d, mm Cu pipe wall thickness, mm Jacket pipe diam. D, mm Weight, kg/m Water content, l/m 35 1.5 125 2.9 0.8 42 1.5 140 3.7 1.2 54 1.5 160 4.6 2.0 70 2.0 180 6.6 3.4 88.9 2.5 200 9.3 5.5
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
Cu-Flex
3.3.2 - 1/1
Series 3 Cu pipe diameter d, mm Cu pipe wall thickness, mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m 50 m coil 100 m coil 15 1.0 90 1.3 0.1 X X 18 1.0 90 1.4 0.2 X X 22 1.0 90 1.5 0.3 X X 28 1.2 35 1.5
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
PEX
3.4.1 - 1/1
63 5.8
Straight pipes and pipes in coils are supplied without stripped ends.
PEX dimension 110 with jacket dimension 160 (series 0) are available in coils in lengths as 90/60. Fix lengths are ordered in min. 10 m. and max. 99 m. The PEX dimensions 110 (series 0), 75 and 90 fix length, are supplied in coils of max. 49 m. The dimensions 20 PEX PN6 and 22 PEX PN10 are supplied in series 2.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
HDPE (10 bar) PE80/PE100
3.4.2 - 1/2
Carrier pipe wall thickness, mm 10.7 Jacket pipe diameter D, mm Weight, kg/m Water content, l/m Lengths L, m 280 13.8 17.0 12
Series 2
Carrier pipe diameter d, mm Carrier pipe wall thickness, mm Jacket pipe diameter D, mm Weight, kg/m Water content, l/m Lengths L, m Carrier pipe diameter d, mm Carrier pipe wall thickness, mm Jacket pipe diameter D, mm
Version/05.2004.UK
63 3.6 140 3.0 2.1 6/12 280 16.6 450 35.1 41.3 12
75 4.3 160 3.9 3.0 6/12 315 18.7 500 43.7 52.2 12
90 5.4 180 4.8 4.3 6/12 355 21.1 560 55.3 66.2 12
110 6.6 225 7.4 6.4 6/12 400 23.7 630 69.9 84.1 12
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
HDPE (10 bar) PE80/PE100
3.4.2 - 2/2
90 5.4 200 5.5 4.3 6/12 355 21.1 630 63.6 66.2 12 110 6.6 250 8.6 6.4 6/12 400 23.7 710 80.9 84.1 12 125 7.4 250 9.3 8.2 12 140 8.3 280 11.6 70.3 12
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Elbow 90
HDPE (10 bar)
3.4.3 - 1/1
Series 1
Carrier pipe diameter d, mm Jacket pipe diameter D, mm Length L, mm 250 400 280 315 400 450 355 400 500 560
Series 2
Carrier pipe diameter d, mm Jacket pipe diameter D, mm Length L, mm 225 355 250 280 450 450 315 355 500 560 400 630
Series 3
Carrier pipe diameter d, mm Jacket pipe diameter D, mm Length L, mm 200 355 225 250 400 500 280 315 500 560 355 630 400 710
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
T-fitting straight
HDPE (10 bar)
3.4.4 - 1/1
2
Series 1
d1 D1 L1 d2 90 110 125 140 160 180 200 225 250 280 315 355 400 D2 160 200 200 225 250 280 280 315 400 400 450 500 560 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 110 200 125 200 140 225 160 250 180 280 200 280 225 315
1200 1200 1200 1400 1400 1400 1400 1600 1600 1600 1800 2000 L2
600 600 600 600 600 600 600 600 600 600 600 600 700 700 700 700 700 700 700 700
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
FXI
Joint with Insulation shells, black
3.5.1 - 1/1
Shrink sleeve
Insulation shells
HM combi-strips
Tissue
77-110 77-110 77-110 125-160125-160125-160180-225180-225180-225250-315250-315 500 500 500 500 500 500 500 500 500 500 500
The FX shrink sleeve is made of cross-linked PE (PEX) material. The joint cannot be pressure tested. The shrink sleeve is wrapped up in a solid white PE foil at delivery. The foil is closed with white tape. The joint is sealed by the means of HM combi-strips. Max. temperature of 70C during transport and storage. The FXI joint can be used for angles up to max. 5. The FXI joint is used for freely suspended systems. FX joint for flexible systems is ordered as FX district heating.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
FXC
Repair joint with Insulation shells, black
3.5.2 - 1/1
Shrink wrap
The shink wrap is made from elastic shrinkable modified UV-stabilized PE (PEX) material.The joint cannot be pressure tested. The shrink wrap and closure patch are wrapped up in a solid white PE foil at delivery. The foil is closed with white tape. The joint is sealed by means of shrink wrap. Max. temperature of 70C during transport and storage.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
BX
Double sealed joint, black
3.5.3 - 1/1
Shrink sleeve
Tissue
Joint BX is also available in series 2 and 3. The BX shrink sleeve is made of cross-linked PE (PEX). The shrink sleeve is wrapped up in a solid white PE foil at delivery. The sleeve is resistant to soil shearing. Max. temperature of 70C during transport and storage. The shrink sleeves must be stored upright. BX joint is designed for above ground as well as under ground installation. The BX joint has been tested against EN 489 to confirm that it is able to withstand forces due to the friction of soil and the pressure of ground water.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
LM
Joint with insulation shells, white
3.5.4 - 1/1
Shrink sleeve
Insulation shells
Tissue HM combi-strips
The LM shrink sleeve is made of cross-linked PE (PEX) material. The joint cannot be pressure tested. The shrink sleeve is not UV-stabilized and is only for indoor installation. The shrink sleeve is wrapped up in a solid white PE foil at delivery. The foil is closed with white tape. The joint is sealed by means of HM combi-strips. Max. temperature of 70C during transport and storage. The LM joint can be used for angles up to max. 15. The LM joint is used for freely suspended systems.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
LMC
Repair joint with insulation shells, white
3.5.5 - 1/1
Shrink sleeve
Insulation shells
Profilplade Tissue
HM combi-strips
The shrink sleeve is made of cross-linked PE (PEX) material. The joint cannot be pressure tested. The shrink sleeve is not UV-stabilized and is only for indoor installation. Retaining tools are necessary to carry out the installation. The tool is to be ordered separately. The shrink sleeve is wrapped up in a solid white PE foil at delivery. The foil is closed with white tape. The joint is sealed by means of HM combi-strips. Max. temperature of 70C during transport and storage. The joint is used for freely suspended systems.
Retaining tools for installation Product code 9000 0000 027 003
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
BM
Elbow joint with insulation shells, black and white
3.5.6 - 1/3
Insulation shells
Tissue HM combi-strips
The BM bending shrink sleeve is made of crosslinked PE (PEX) material. The joint cannot be pressure tested. white shrink sleeves are not UV-stabilized and is only for indoor installation. The shrink sleeve is wrapped up in a solid white PE foil at delivery. The foil is closed with white tape. The joint is sealed by means of HM combi-strips. Max. temperature of 70C during transport and storage. The BM joint is used for freely suspended systems. Insulation shells are stocked according to the weld elbows on the following pages.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
BM
Weld elbow 90 for BM
3.5.6 - 2/3
27.5 28.5
114.3 139.7 168.3 219.1 3.6 152 3.6 190 4.0 229 4.5 305
Mapress
St. 35.8 I
d s R d s R 21.3 26.9 33.7 42.4 48.3 60.3 76.1 88.9 2.0 2.3 2.6 38 2.6 47.5 2.6 57 2.9 76 2.9 95 3.2 114
27.5 28.5
114.3 139.7 168.3 219.1 3.6 152 4.0 190 4.5 229 6.3 305 d s 15 1.0 29 49 88.9 2.0 217 277 18 1.0 33 53 108 2.0 266 341 22 1.2 40 61 28 1.2 49 72 35 1.5 96 122 42 1.5 136 166 54 1.5 165 200 76.1 2.0 182 235
Z L d s
27.5 28.5
Z L
s R
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
BM
Weld elbow 90 for BM
3.5.6 - 3/3
d
d
63
200
75
225
90
110
125
140
160
180
d Z
25 65
32 65
40 74
50 86
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
TMC
T-joint with insulation shells, white
3.5.7 - 1/1
Insulation shells
Tissue
HM combi-strips
Retaining tools for installation Product code 9000 0000 027 003
The shrink sleeve is made of cross-linked PE (PEX) material. The joint cannot be pressure tested. White shrink sleeves are not UV-stabilized and is only for indoor installation. Retaining tools are necessary to carry out the installation. The tool is to be ordered separately. The shrink sleeve is wrapped up in a solid white PE foil at delivery. The foil is closed with white tape. The joint is sealed by means of HM combi-strips. Max. temperature of 70C during transport and storage.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
TMC-C
T-joint with insulation shells, black
3.5.8 - 1/1
Shrink wrap Profile plate
HM combi-strips
Retaining tools for installation Product code 9000 0000 027 003
The shrink sleeve is made of cross-linked PE (PEX) material. The joint cannot be pressure tested. Retaining tools are necessary to carry out the installation. The tool is to be ordered separately. The shrink sleeve is wrapped up in a solid white PE foil at delivery. The foil is closed with white tape. The joint is sealed by means of HM combi-strips. Max. temperature of 70C during transport and storage. The TMC-C joint is used for freely suspended systems.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
EC
End cap, white
3.5.9 - 1/1
End cap
Single-strips Tissue
170A 170A 170A 170A 170A 170A 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 170B 230A 230A 230A 230A 230A 230A 230A 230A 230A 230C 230C 230C 230C
The EC end cap is made of cross-linked PE (PEX) material. The joint cannot be pressure tested. The shrink sleeve is not UV-stabilized and is only for indoor installation.
Version/05.2004.UK
The EC end cap is applicable in temperature ranging from -30 to +70 C. The end cap is sealed by means of single-strips. Max. temperature of 70C during transport and storage. The EC end cap is used for freely suspended systems.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
DHEC
End cap, black
3.5.10 - 1/1
End cap
2100 2100 2200 2300 2400 2400 2500 2600 2700 2700 2800 2800 2900 3000 3000
The DHEC end cap is made of cross-linked PE (PEX) material. The joint cannot be pressure tested. The end cap is applied for protection of the foamed ends against moisture penetration. Applicable for a max. carrier pipe temperature of 100C. Max. temperature of 70C during transport and storage.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HEC
End cap, white
3.5.11 - 1/1
End cap
Single-strips
Tissue
End cap HEC Component no. 55001L The HEC end cap is made of cross-linked PE (PEX) material. The joint cannot be pressure tested. The shrink sleeve is not UV-stabilized and is only for indoor installation. The HEC end cap is applicable in temperature ranging from -200 to +140 C. HEC must be applied in temperature ranging below -30 C and above +120 C. The end cap is sealed by the means of single-strips. Max. temperature of 70C during transport and storage. The HEC end cap is used for freely suspended systems.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HDHEC
End cap, black
3.5.12 - 1/1
End cap HDHEC Component no. 55101L The HDHEC end cap is made of cross-linked PE (PEX) material. The joint cannot be pressure tested. The HDHEC end cap is applicable in temperature ranging from -200 to +140 C. Thw HDHEC must be applied in temperature ranging below -30 C and above +120 C. HDHEC is applicable for freely suspended and directly buried systems. The end cap is applied for protection of the foamed ends against moisture penetration. Is applicable for a max. carrier pipe temperature of 140C. Max. temperature of 70C during transport and storage.
Version/05.2004.UK
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
System Description
Temperatur emperature High Temperature - HT3
5.1.1 - 1/1
Compensator Anchoring Anchor elbow
Operating temperature from +140C to +315C Underground high temperature systems HT3 are laid as compensating sliding systems. In the HT3 system, movements caused by temperature changes are absorbed within the system itself. The jacket pipe is held in place by soil friction and thus does not move. The carrier pipe moves within the insulation, with the movements absorbed by corresponding expansion-absorbing elements such as L, Z or U bends or axial compensators. When laying, the system is broken down into expansion sections that can be calculated. Each section is divided from the next at each end using anchors. The expansion-absorbing elements are placed inside each section, and should ideally be loaded equally from both sides. Insulation The Insulation in the HT 3 system consists of a combination of PUR foam and mineral wool, helping to ensure that neither the PUR foam nor the HDPE jacket temperature capability are exceeded. A: HDPE jacket B: PUR foam C: Mineral wool D: Carrier pipe
Version/06.2004.UK Text/ 18-06-2004
The insulation system comes in two standard versions, for medium temperatures of 210OC and 315OC. Pipe ends Each pipe and all insulated components are filled with foam in the ends. This protects the mineral wool ends from moisture seeping in during storage and handling.
The pipe ends may only be cut and removed after the carrier pipe have been welded and just before installing of the joint. A notch is milled into the HDPE jacket to mark the place where the ends should be cut.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
5.1.2 - 1/2
= ( tM - tE ) x U
Where: tM = Media temperature t E = Soil temperature The U values are calculated on the basis of a soil covering of 600 mm. DN = Nominel diameter D e d
S M = Mineral wool thickness, mm S PUR = Insulation thickness PUR, mm Max. 210C series
DN 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400 d, mm 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 D, mm 140 140 160 160 200 225 225 250 315 355 400 450 500 560 630
U
e, mm 3.0 3.0 3.0 3.0 3.2 3.5 3.5 3.9 4.9 5.6 6.3 7.0 7.8 8.8 9.8
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
5.1.2 - 2/2
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Thermal expansion
HT3 technique oduktion Generelt Introduktion Generelt - Intr
Thermal expansion in straight pipes The linear thermal expansion in metallic pipes can be calculated using material-dependent expansion coefficients. L = L x
5.1.3 - 1/1
Thermal expansion in bends Axial expansion from both directions can occur in bends. The following figure shows the resultant lateral displacement:
x T
Thermal expansion, mm L L Pipe section length, m Expansion coefficient, mm/mK For St 37 / St 35.8 at 200C = 0.0121 For stainless steel at 200C = 0.0175 Lateral displacement can be calculated using the following formula: ( +( LB = ( (L1)2 +(L2)2 )0.5 LMAX NB: LMAX for expansion bends must not be exceeded.
T Operating-installation temp. K
Pure thermal expansion in the HT 3 system is counteracted by friction resistance between the mineral wool and the carrier pipe, soil friction and energy from loading, the pipe bends and compensator. For practical reasons, the expansion calculated for a straight pipe expansion L can thus be reduced by a factor of 0.9 which means: LP = 0.9 x L x
x T
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Expansion Absorption
HT3 technique oduktion Generelt Introduktion Generelt - Intr
Expansion length xpansion The HT 3 system is designed to allow the insulation to absorb expansion of the carrier pipe within the exterior jacket. Maximum expansion absorption LMAX. for each expansion absorption element can be found in catalogue chapters: Elbows Axial compensators 5.2.3 and 5.2.4 5.2.9
5.1.4 - 1/2
The maximum distance LMAX from the anchor to the expansion element is: L MAX = L MAX / x T Expansion absorption in 90 bends Logstor supplies 90 expansion bends for expansion absorption of 20 mm and 40 mm, respectively (see 5.2.3 and 5.2.4)
For special built-in situations, expansion bends can be manufactured as special products with other bend radii. Separate configuration documentation is required for such instances. As a guideline value, the following maximum expansion lengths LMAX can be used from the anchor to the pipe bend. These distances presume full utilisation of the expansion length and temperatures of 210C and 315C respectively. Max. expansion length LMAX St 37 / St 35.8
Operating temperature 210C 315C 0 mm 3.0 m 2.0 m Expansion length 20 mm 10 m 7m 40 mm 20 m 14 m
The bends must be assembled as L, Z or U bends on-site and must not under any circumstances be cut. When bends are supplied in larger dimensions, the shank length will be too long for transport on a truck and they are therefore divided into two pieces: a short bend and two expansion pipes for assembly on-site.
Version/06.2004.UK Text/ 14-06-2004
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Expansion Absorption
HT3 technique oduktion Generelt Introduktion Generelt - Intr
Expansion absorption in 45 - 90 elbows Elbows of 90- 45 can be used for expansion absorption. The resulting lateral expansion is calculated as shown in 5.1.3 and must not exceed 20 or 40 mm respectively. Expansion absorption in 0 - 45 elbows Pipe bends with an angle of less than 45 are not suitable for expansion absorption and must usually be built with an anchor elbow.
5.1.4 - 2/2
Expansion in T-branches There are no expansion elements in T-fittings which must always be directly installed together with an anchor in the main pipe. The maximum distance from a T-fitting to an expansion element in a branch pipe for black steel is: 6 m for the 210C series 4 m for the 315C series
Expansion in HT end pieces The maximum distance from a HT end piece to an anchor for black steel is: 5 m for the 210C series 3 m for the 315C series
Installation examples
Expansion absorption in compensators The expansion absorption capacity of standard compensators LMAX is given in chapter 5.2.9. If the customer requires other compensators, all relevant data regarding expansion absorption must be obtained from the manufacturer and submitted to Logstor before they can be approved for insulation. Only one compensator can be mounted between two anchors, a U-bend or Z-bend for absorption of expansion. The maximum distance between two anchors LMAX on straight pipe lengths is: LMAX = LMAX / x T Where LMAX is the compensator- or expansion elements maximum expansion length.
Version/06.2004.UK Text/ 18-06-2004
Absorption of expansion in reductions Expansions cannot absorb larger expansions, and therefore they are to be installed directly together with a T-fitting or an anchor.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Anchors
HT3 technique oduktion Generelt Introduktion Generelt - Intr
Anchor forces Anchor forces exerted by thermal expansion and internal compressive force have to be absorbed by the concrete blocks in the excavation trench. Absorption of the axial forces exerted is sufficient for the calculation. Consequently, anchor force FP, to be absorbed can be calculated as follows: FP = S x F 1 F 2 Where S is a supplementary safety value and F1>F2. The forces exerted on both sides of the anchor consist of different individual elements, depending on the geometric conditions. They can include: - Friction. - The compensators spring resistance. - The compensators internal resistance. - Resistance from L, Z and U bends. - Internal compressive force in bends. - The compensators start force. The compensators spring resistance and resistance in the bends can be ignored as they are built in to the safety factor. Friction The reactive forces resulting from friction between the carrier pipe and the mineral wool can be calculated by: FR = x d x L x Where: or: FPR = S x ( FR1+ FKP1)+ P - ( FR2+ FKP2) The supplementary safety factors are given in the local instructions but in most instances S=1.2 will be sufficient. Anchor construction Anchors are set in concrete directly onto unprepared ground. Anchor force The resultant anchor force is thus: FPR = S x F1 - F2
5.1.5 - 1/2
The compensators internal compressive force The internal diameter of the compensators corrugation is greater than that of the carrier pipe, resulting in the corrugation creating hydraulic axial force FKP FKP = p x AB AB = The effective corrugated area [cm2] P = Max. operating pressure [N/mm2] AB is given in chapter 5.2.9. Compensator start forc force The compensator is factory-set for maximum fluctuation and separation bolts are used to retain this setting. The bolts will part once the compensator becomes active, and the required force P kN, is given in chapter 5.2.9. P should be calculated as a unilateral force.
d = The carrier pipes dimensioning [m]. L = The pipe length under friction [m].
The concrete block must be dimensioned to be able to absorb reaction force FPR
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Anchors
HT3 technique oduktion Generelt Introduktion Generelt - Intr
The ground will have a slight elasticity making it impossible to define an anchor precisely, i.e. L = 0. Permitted anchor displacement LF will require case-by-case evaluation. Permitted surface pressure against the ground, dependent on the LF that can be tolerated, can then be calculated using the following formula: = 15 x LF The soil pressure in the vertical direction AW can be calculated by reaction force FPR and permitted surface pressure : AW = FPR /
5.1.5 - 2/2
The concrete block must be cast to achieve a compressive force of more than 25 MN/m, and must have sufficient height, length and reinforcement to absorb the transmission forces. Recommended dimensions for the concrete block are calculated on the basis of the following: Soil pressure : 150 kN/m2 against the entire block fyk > 410 N/mm2 Concrete : 20 N/mm2 concrete, fck > 20 N/mm2 Calculating the size of the concrete block is the responsibility of the project engineer.
Steel pipe diameter d, mm 26.9-48.3 60.3-76.1 88.9-114.3 139.7 168.3 219.1 273.0 323.9 355.6 406
Permitted axial force kN 30-60 80-100 130-200 250 300 500 650 850 925 1200
Concrete block L, m 1.0 1.2 1.8 2.3 2.3 2.8 3.0 3.8 4.6 4.8 H, m 0.5 0.5 0.7 0.8 0.9 1.2 1.5 1.5 1.6 1.8 W, m 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.2 1.4
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
5.1.6 - 1/2
315C series
Minimum soil covering H DN/D Groundwater under the pipe HBXS 20/200 25/200 32/225 40/250 50/315 65/315 80/315 100/355 125/450 150/450 200/500 250/560 300/630 350/630 400/710 0.60 0.60 0.60 0.60 0.60 0.60 0.60 HEW 0.60 0.60 0.60 0.60 0.60 0.60 0.70 0.70 0.80 0.90 1.00 Groundwater above the pipe HBXS 0.60 0.60 0.60 0.60 0.80 0.80 0.80 HEW 0.80 0.80 0.80 0.90 0.90 1.10 1.30 1.40 1.50 1.60 1.60
Dimensioning of the trench depends on the pipe dimensions. When establishing a trench, local safety regulations must be observed including regulations for shores or other stabilizing soil equipment. A trench to a minimum depth of 1.7 m with shores or sufficient measures to prevent slippage is recommended in all instances. The minimum trench width for pipes up to DN 400 are the jacket pipe diameter plus 450 mm. The pipes must rest on minimum 100 mm compressed friction material and the distance between the jacket pipe and trench wall shall be no less than 150 mm. A greater distance will be advantageous for welding work and sleeve installation in the trench. Alternatively, proper access around the weld area must be ensured. Pipes should be supported by supports of polystyrene foam or sandbags. If wooden wedges are used, they must be removed before backfilling.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
5.1.6 - 2/2
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Pipe
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
5.2.1 - 1/1
end sections against damp during storage and handling. The pipe ends may only be cut and removed after the carrier pipes have been welded and just before shrinkage of the sleeves. For further details, see chapter 5.1.1, System Description. For specifications for carrier pipes, insulation and jackets, see section 1.2 Material specifications, in chapter 5.1.2 Operating Temperature and Heat Loss.
Component no. 20001L Pipes come in lengths of 6 and 12 m, as described in the following table. As standard they and all other pre-insulated components come in two series, the 210C series and the 315C series. All pipes and pre-insulated components are fully foamed at the ends, protecting the mineral wool
DN d 210C series Jacket D thickness, e 140 140 160 160 200 225 225 250 315 355 400 450 500 560 630 3.0 3.0 3.0 3.0 3.2 3.5 3.5 3.9 4.9 5.6 6.3 7.0 7.8 8.8 9.8 315C series Jacket D thickness, e 200 200 225 250 315 315 315 355 450 450 500 560 630 630 710 3.2 3.2 3.5 3.9 4.9 4.9 4.9 5.6 7.0 7.0 7.8 8.8 9.8 9.8 11.1 L 6m L 12m
26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4
X X X X X X X X X X X X X X X X X X X X X X X X
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Reduction
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
5.2.2 - 1/1
All pipes and pre-insulated components are fully foamed at the ends, protecting the mineral wool end sections against damp during storage and handling. The pipe ends may only be cut and removed after the carrier pipes have been welded and just before shrinkage of the sleeves. For further details, see chapter 5.1.1, System Description. For specifications for carrier pipes, insulation and jackets, see section 1.2 Material specifications and in chapter 5.1.2 Operating Temperature and Heat Loss. Component no. 49001L Reductions come complete in the lengths specified in the table below. Reductions on the carrier pipe are eccentric. Please observe that the white line shall be at the top at installation. As standard, all reductions and pre-insulated components are made in two series: the 210C series and the 315C series.
DN 1 d1, mm DN 2 d2, mm L, mm 210C series D1, mm 25 32 40 50 65 80 100 125 150 200 250 300 350 400 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 20 25 32 40 50 65 80 100 125 150 200 250 300 350 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 140 160 160 200 225 225 250 315 355 400 450 500 560 630 D2,mm 140 140 160 160 200 225 225 250 315 355 400 450 500 560 315C series D1, mm 200 225 250 315 315 315 355 450 450 500 560 630 630 710 D2,mm 200 200 225 250 315 315 315 355 450 455 500 550 630 630
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Elbow
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
As standard elbows and all other pre-insulated components come in two series, the 210C series and the 315C series. Elbows are manufactured in three versions, without expansion and with 20 mm or 40 mm absorption insulation. These expansions must not be exceeded, see chapter 5.1.3. Elbows can be supplied with 45, 60, 75 and 90 angles as standard. Other angles can be supplied with a tolerance of 2.5 by special order. For elbows of less than 45 anchor elbows must be used, see chapter 5.2.8. For transporting, large dimensions are produced in several components: a short elbow with one or two leg extensions, see chapter 5.2.4, Expansion Pipes. All pipes and pre-insulated components are fully foamed at the ends, protecting the mineral wool end sections against damp during storage and handling. The pipe ends may only be cut and removed after the carrier pipes have been welded and just before shrinkage of the sleeves. Type 2 Component no. 25001L
5.2.3 - 1/2
For further details, see chapter 5.1.1, System Description. For specifications for carrier pipes, insulation and jackets, see section 1.2 Material specifications.
Type 1
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Elbow
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
210C series
DN d, mm D, mm Without expansion L, mm 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 140 140 160 160 200 225 225 250 315 355 400 450 500 560 630 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1300 1500 1600 1600 Type 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 mm expansion K, mm 280 280 315 355 400 450 500 560 630 710 L, mm 2200 2500 2600 1200 1200 1500 1500 1500 1500 1500 Type 1 1 1 2 2 2 2 2 40 mm expansion K, mm 225 225 250 250 280 315 315 355 400 450 500 560 630 L, mm 1600 1850 2200 2500 2650 1000 1200 1200 1200 1200 1500 1500 1500 Type 1 1 1 1 1 2 2 2 2 2 2 2 2 -
5.2.3 - 2/2
315C series
DN d, mm D, mm Without expansion L, mm 20 25 32 40 50 65 80 100 125 150 200 250 300 350
Version/06.2004.UK Text/ 14-06-2004
20 mm expansion K, mm 355 355 400 500 500 560 630 710 710 800 L, mm 2200 2500 2600 1200 1200 1500 1500 1500 1500 1500 Type 1 1 1 2 2 2 2 2 -
40 mm expansion K, mm 315 315 315 355 355 400 400 450 560 560 630 710 800 L, mm 1600 1850 2200 2500 2650 1000 1200 1200 1200 1200 1500 1500 1500 Type 1 1 1 1 1 2 2 2 2 2 2 2 2 -
Type 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4
200 200 225 250 315 315 315 355 450 450 500 560 630 630 710
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1300 1500 1600 1600
400
It is not possible to foam the joint for the casing dimension K 800 with Shakemix. Use a foam machine.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Expansion pipe
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
As standard, expansion pipes and all other preinsulated components come in two series, the 210C series and the 315C series. Expansion elbows are produced as three components: a short elbow with two expansion pipes as extensions. Expansion pipes are manufactured in two versions, with 20 mm or 40 mm expansion absorption. These expansion absorptions must not be exceeded and expansion pipes must not be cut. All pipes and pre-insulated components are fully foamed at the ends, protecting the mineral wool end sections against damp during storage and handling. The pipe ends may only be cut and Type 2
5.2.4 - 1/2
removed after the carrier pipes have been welded and just before shrinkage of the sleeves. Please note that the text on expansion pipes must be at the top during installation, as expansion is only permitted in a lateral direction to the text. For further information, see chapter 5.1.1 System Description. For carrier pipe specifications, insulation and jackets, please see section 1.2, Material specifications.
210C series 40 mm expansion L 2250 2650 3200 3850 4250 4500 4650 5450 D 225 225 250 315 355 400 450 500 K 315 315 355 400 450 500 560 630 20 mm expansion L 2100 2550 3050 3500 3850 4250 5000 D 450 450 500 560 630 630 710 K 500 500 560 630 710 710 800
315C series 40 mm expansion L 2250 2650 3200 3850 4250 4200 4650 5450 D 315 315 355 450 450 500 560 630 K 400 450 500 560 560 630 710 710 -
76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Expansion pipe
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
Joint for connection of expansion elbow type 2 and expansion pipes should not be ordered separately. The joint is automatically supplied with the expansion elbow as a HEW joint with extra mineral wool for expansion absorption. On ordering, DN 65 and DN 80 with 40 mm expansion in series 210 are available with HBXS instead. In this case, the HBXS is provided with extra mineral wool. Joint for expansion elbow type 2 20 mm expansion
DN d, mm L, mm 125 150 200 250 300 350 400 139,7 168,3 219,1 273,0 323,9 355,6 406,4 750 750 800 800 800 800 800 D, mm 355 400 450 500 560 630 710 Serie 210OC SM, mm 60 70 70 70 70 70 80 PUR, liter 13,9 15,3 17,3 18,7 23,4 35,8 43,3 Shakemix str. 15 17 22 22 25 2x22 2x25 L, mm 800 800 800 800 800 800 800 D, mm 500 500 560 630 710 710 800 Serie 315OC SM, mm 120 120 120 120 120 120 120 PUR, liter 25,0 19,7 24,2 31,5 44,1 35,3 52,4 Shakemix str. 29 22 29 2x17 2x25 2x22 2x29
5.2.4 - 2/2
40 mm expansion
DN d, mm L, mm 65 80 100 125 150 200 250 300 76,1 88,9 114,3 139,7 168,3 219,1 273,0 323,9 750 750 750 750 800 800 800 800 D, mm 315 315 355 400 450 500 560 630 Serie 210OC SM, mm 70 70 70 80 90 90 90 90 PUR, liter 12,4 11,1 14,5 16,6 19,2 21,4 25,5 33,9 Shakemix str. 15 12 15 17 22 25 29 2x17 L, mm 800 800 800 800 800 800 800 800 D, mm 450 450 500 560 560 630 710 800 Serie 315OC SM, mm 120 120 120 140 140 140 140 140 PUR, liter 24,2 22,4 29,4 32,5 26,6 34,8 46,7 65,1 Shakemix str. 29 25 2x15 2x17 29 2x22 2x25 -
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
T-fitting straight
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
As standard, T-fittings and all other pre-insulated components come in two series: the 210C series and the 315C series. Carrier pipes are made exclusively to the customers specification and the branch pipe is welded on at an angle of 90. T-fittings cannot be used as expansion-absorbing components and must therefore always be directly placed together with an anchor in the main pipe. All pipes and pre-insulated components are fully foamed at the ends, protecting the mineral wool end sections against damp during storage and handling. The pipe ends may only be cut and removed after the carrier pipes have been welded and just before shrinkage of the joints. See also pipe-laying instructions in chapter 5.1.4. Further information is given in chapter 5.1.1 System Description and for specifications for carrier pipes, insulation and jackets, see section 1.2 Material specifications. 210C series
DN d1 D1 d2 26.9 33.7 42.4 48.3 60.3 76.1 88.9 D2 140 140 160 160 200 225 225 L1 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400
5.2.5 - 1/2
Component no. 34001L T-fittings come in the diameter combinations shown in the table below. Other combinations are supplied as special. If the branch pipe of the Tfitting is to be further reduced, use reduction pipes see chapter 5.2.2. Logstor offers T-fittings with terminations as special products.
26.9 33.7 42.4 48.3 60.3 140 140 160 160 200
76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 225 225 250 315 355 400 450 500 560 630
1000 1000 1000 1000 1200 1200 1200 1200 1200 1400 1400 1600 1600 1800 2000 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 800 800 800 800 800
114.3 250 139.7 315 168.3 355 219.1 400 273.0 450 323.9 500 355.6 560
Version/06.2004.UK Text/ 14-06-2004
406.4 630
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
T-fitting straight
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
315C series
DN d1 D1 d2 26.9 33.7 42.4 48.3 60.3 76.1 88.9 D2 200 200 225 250 315 315 315 L1 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400
5.2.5 - 2/2
26.9 33.7 42.4 48.3 60.3 200 200 225 250 315
76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 315 315 355 450 450 500 560 630 630 710
1000 1000 1000 1000 1200 1200 1200 1200 1200 1400 1400 1600 1600 1800 2000 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 800 800 800 800 800
114.3 355 139.7 450 168.3 450 219.1 500 273.0 560 323.9 630 355.6 630 406.4 710
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
T-fitting
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
As standard T-fittings and all other pre-insulated components come in two series: the 210C series and the 315C series. Carrier pipes are made exclusively to the customers specification and the branch pipe is cranked at an angle of 45. T-fittings cannot be used as expansion-absorbing components and must therefore always be directly placed together with an anchor. All pipes and pre-insulated components are fully foamed at the ends, protecting the mineral wool end sections against damp during storage and handling. The pipe ends may only be cut and removed after the carrier pipes have been welded and just before shrinkage of the sleeves. Further information is given in chapter 5.1.1 System Description and for specifications of carrier pipes, insulation and jackets, see section 1.2 Material specifications. 210C series
DN d1 D1 d2 D2 L2 L1 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400
5.2.6 - 1/2
Component no. 30001L T-fittings come in diameter combinations shown in the table below. Other combinations can be supplied on order. If the branch pipe of the T-fitting is to be further reduced, use reductions see chapter 5.2.2.
26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 140 140 160 160 200 225 225 250 315 355 400 450 500 560 630
1000 1000 1000 1000 1200 1200 1200 1200 1400 1400 1600 1600 2000 2000 2000 215 215 215 225 225 235 225 225 235 235 245 245 255 255 275 258 268 268 288 300 268 268 288 300 300 280 300 313 313 325 333 345 345 358 390 365 365 378 410 430 388 400 433 453 475 425 458 478 500 525 508 528 550 575 600 558 580 605 630 660 615 640 665 695 730
26.9 140 1000 33.7 140 1000 42.4 160 1000 48.3 160 1000 60.3 200 1000 76.1 225 1000 88.9 225 1000 114.3 250 1000 139.7 315 1000 168.3 355 1000 219.1 400 1000 273.0 450 1000 323.9 500 1200 355.6 560 1200
Version/06.2004.UK Text/ 18-06-2004
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
T-fitting
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
315C series
DN d1 D1 d2 D2 L2 L1 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400
5.2.6 - 2/2
26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 200 200 225 250 315 315 315 355 415 450 500 560 630 630 710
1000 1000 1000 1000 1200 1200 1200 1400 1400 1600 1600 1800 2000 2000 2000 275 275 275 288 288 300 300 300 313 325 333 333 345 358 390 333 345 358 390 390 345 358 390 390 390 378 410 410 410 430 440 440 440 460 490 458 458 478 508 525 508 528 558 575 600 558 588 605 630 660 623 640 665 695 730 640 665 695 730 730 705 735 770 770 810
26.9 140 1000 33.7 140 1000 42.4 160 1000 48.3 160 1000 60.3 200 1000 76.1 225 1000 88.9 225 1000 114.3 250 1000 139.7 315 1000 168.3 355 1000 219.1 400 1200 273.0 450 1200 323.9 500 1600 355.6 560 1600 406.4 630 1600
The height of the offset H is shown in the table. Total height from the bottom to the top of the jacket < 450, H = D1 +D2 + 75 mm. Total height from the bottom to the top of the jacket > 500, H = D1 +D2 + 100 mm.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Anchoring
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
As standard anchors and all other pre-insulated components come in two series, the 210C series and the 315C series. The anchor plate is sufficiently thermally insulated to ensure that the jacket pipe and shrink seals are not overheated. Its thickness and diameter are designed to ensure that any forces applied to it are transferred to the concrete block, see chapter 5.1.6. All pipes and pre-insulated components are fully foamed at the ends, protecting the mineral wool end sections against damp during storage and handling. The pipe ends may only be cut and removed after the carrier pipes have been welded and just before shrinkage of the sleeves. Further details are given in chapter 5.1.1, System Description.
DN 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400 d 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 L 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 L1 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150
5.2.7 - 1/1
For specifications of carrier pipes, insulation and jackets, see section 1.2, Material specifications.
Anchors can be supplied with HT end cap in L1 or L2 ends. See also chapter 5.3.3.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Anchor elbow
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
As standard anchor elbows and all other preinsulated components come in two series, the 210C series and the 315C series. The anchor plate is sufficiently technically isolated to ensure that the jacket pipe and shrink seals are not overloaded. Its thickness and diameter are designed to ensure that any forces applied to it are transferred to the concrete block, see chapter 5.1.5. All pipes and pre-insulated components are fully foamed at the ends, protecting the mineral wool end sections against damp during storage and handling. The pipe ends may only be cut and removed after the carrier pipes have been welded and just before shrinkage of the sleeves. Further details are given in chapter 5.1.1, System Description.
DN 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400 d 26.9 33.7 42.4 48.3 60.3 76.4 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4 L 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 L1 1015 1015 1015 1015 1015 1015 1015 1015 1015 1015 1015 1015 1015 1015 1015
5.2.8 - 1/1
For specifications of carrier pipes, insulation and jackets, see section 1.2, Material specifications.
210C series D 140 140 160 160 200 225 225 250 315 355 400 450 500 560 630 DR 240 240 260 260 300 300 300 350 415 455 500 550 600 660 760 D
315C series DR 300 300 300 380 415 415 415 455 550 550 600 660 730 730 810 200 200 225 250 315 315 315 355 450 450 500 560 630 630 710
Anchors can be supplied with HT end caps in L1 or L2 ends. See also chapter 5.3.3.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
Compensator
HT3 components - Steel pipe system Generelt Introduktion Generelt - Introduktion
As standard, compensators and all other preinsulated components are supplied in two series, of 210C and 315C, respectively. Compensators are available in standard format of PN 16 or PN 25. Compensators for higher pressures are made to customers specifications. Nominal pressure applies at 120C. At 200C, a pressure reduction factor of 0.91 and at 300C a factor of 0.82 is required. All pipes and pre-insulated components are fully foamed at the ends, protecting the mineral wool end sections against damp during storage and handling. The pipe ends may only be cut and removed after the carrier pipes have been welded and just before shrinkage of the sleeves. The compensator is factory-set for maximum expansion absorption and retaining bolts are used to retain this setting. The bolts will burst once the compensator becomes active, and the required burst force P, is stated below. The expansion-absorbing element is a corrugated section consisting of several layers of stainless steel welded to both ends of the pipe. This section is approved to max. 1000 full load cycles.
d, mm L, mm D, mm 48.3 60.3 76.1 88.9 114.3 139.7 168.3 219.1 273.0 323.9 355.6 406.4
Version/07.2004.UK Text/ 26-07-2004
5.2.9 - 1/1
A housing of either steel or stainless steel protects this construction and the compensator exerts spring force at a constant CA. The effective corrugated surface AB mm2 is stated below.
Component no. 41001L Further details are given in chapter 5.1.1, system description. For specifications of carrier pipes, insulation and jackets, see section 1.2, material specifications.
210C / PN 16 K, mm 225 250 250 315 355 400 450 500 560 630 710 710 Le, mm 100 100 100 100 125 125 125 125 125 125 125 125 P, kN 18 18 18 18 18 23 23 23 41 41 64 64 C A, N/mm 15 43 51 45 27 58 63 53 81 91 101 108 A B, mm2 4100 5500 7600 10800 17300 23700 33200 56000 81000 110700 130500 173800 D, mm 315 355 450 450 500 560 630 630 710 K, mm 450 450 500 560 630 630 710 710 800
315C / PN 25 Le, mm 90 90 90 90 90 90 90 90 90 P, kN 18 18 23 23 23 41 41 64 64 C A, N/mm 37 31 58 45 66 106 153 105 119 A B, mm2 10900 16700 24800 35100 57600 85700 121600 136500 179300
2500 2500 2500 2500 2500 2500 2500 3000 3000 3000 3000 3000
160 200 225 225 250 315 355 400 450 500 560 630
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HBXS
High temperature joint for foaming
5.3.1 - 1/1
sleeve is fitted using a hotmelt adhesive on both ends. The HBXS joint can be used anywhere it has been established that soil friction can firmly hold the jacket pipe in place. See chapter 5.1.6.
Shrink sleeve
Shakemix
S M : Mineral wool thickness in the insulation sleeve S PUR : PUR insulation thickness
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HEW
High temperature joint for foaming
5.3.2 - 1/1
welding strips, making the joint tensile resistant and load carrying from one end to the other. The HEW sleeve should be used in instances where it cannot be ascertained that soil friction alone can hold the jacket pipe in place. See chapter 5.1.6.
Nails
Shrink film
Welding elements
Tissue
Shakemix
It is not possible to foam the joint for the casing dimension 800 with Shakemix. Use a foam machine.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HDHEC
High temperature end cap
5.3.3 - 1/2
For stainless steel. End cap Mineral wool shells Cone Component no. 55101L
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HDHEC
High temperature end cap
5.3.3 - 2/2
Serie 315C D 200 200 225 250 315 315 315 355 450 450 500 560 630 630 710 L 175 195 205 215 215 235 235 235 255 255 275 425 455 485 515
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HBXS
High temperature joint for foaming temperature
5.4.1 - 1/3
If sensor wires:
Shrink sleeve
Accessories:
1. Place the shrink sleeve with packing on one of the pipes, before the carrier pipes are joined.
4. Shorten the mineral wool shells to make them fit tightly between the jacket pipes.
5. Fit the mineral wool shells tightly on the carrier pipe using adhesive tape to seal gaps.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HBXS
High temperature joint for foaming temperature
5.4.1 - 2/3
6c
6. The following only applies for sensor wires: Connect the sensor wires according to the suppliers instructions. Divide the PUR wire retainer in 2 sections. Centre the wire retainers under the sensor wires and fasten them with canvas tape.
10. Wait minimum 30 minutes for degassing. Remove the aluminium foil.
11. Activate the jacket pipes with abrasive cloth grain size 80 at least 150 mm from both jacket ends. 7. Centre the aluminium foil over the joint. Tighten the straps. Wind filament tape round the foil on both sides of the hole.
12. Activate the jacket pipes with a gas burner at least 150 mm from both jacket ends, until the surface has a matt, silky look. 8. Foam the aluminium foil.
Version/06.2004.UK Text/ 14-06-2004
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HBXS
High temperature joint for foaming temperature
5.4.1 - 3/3
13. Place the shrink film so that the marking line encircles the pipe. Attach one edge of the shrink film at 10 oclock position. Pull the film around the pipe by removing the adhesive paper so that the film adheres to the surface beneath.
15b
15c
14. Heat the whole film from the centre outwards, ensuring that the mastic becomes visible at all edges and that the shrink film is tightly fitted.
15. Remove the packing from the shrink sleeve. Check that the sleeve is CLEAN and DRY, inside and out. Centre the shrink sleeve on the joint and mark it. First, shrink from the middle towards one end, then from the middle towards the other end. Avoid heating directly on the jacket. Before shrinking After shrinking
16. Shrink until all expansion marks have vanished and the ends of the sleeve form a smooth encircling edge.
HEW
High temperature joint for foaming
5.4.2 - 1/4
Accessories: Nails
If the surrounding temperature is >30 or the shrinking sleeve is exposed to sunlight, the wrapping foil must remain on the pipeline until the shrinking sleeve has been shrunk. The shrink sleeve must be covered up with wrapping foil when it is not being processed.
1. Place the shrink sleeve with packing on one of the pipes, before the carrier pipes are joined.
4. Shorten the mineral wool shells to make them fit tightly between the jacket pipes.
Version/06.2004.UK Text/ 14-06-2004
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HEW
High temperature joint for foaming
5.4.2 - 2/4
5. Fit the mineral wool shells tightly between the jacket pipes, using canvas tape if required.
9. Wait minimum 30 minutes for degassing. Remove the aluminium foil. Activate the jacket pipes with abrasive cloth grain size 80 at least 150 mm from both jacket ends.
6. Centre the aluminium foil over the joint. Tighten the straps. Wind filament tape round the foil on both sides of the hole.
10. Activate the jacket pipes with gas burner at least 150 mm from both jacket ends, until the surface has a matt, silky look.
11. Place the shrink film so that the marking line encircles the pipe. Attach one edge of the shrink film at 10 oclock position. Pull the film around the pipe by removing the adhesive paper so that the film adheres to the surface beneath.
12. Heat the whole film from the centre outwards, ensuring that the mastic becomes visible at all edges and that the shrink film is tightly fitted.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HEW
High temperature joint for foaming
5.4.2 - 3/4
D > 560mm 13. Remove the packing from the shrink sleeve. Do not use cutting tools. Leave the packing on the pipeline. Check that the sleeve is CLEAN and DRY, inside and out. Centre the sleeve over the jointing area. Mark the placing of the sleeve on the jacket pipes. Write the sleeve number on the sleeve. Fill in the documentation form.
16. Mount the welding elements with nails as shown above and with a nail each 250 mm around the jacket pipes.
14. Pull the sleeve away on the cleaned pipe end. Thoroughly activate the jacket pipes with abrasive cloth, grain size 36-40, exactly touching the marking.
17. Place the sleeve between the marks. Write the joint number and resistance values for the welding element on the sleve/jacket pipes and in the documentation form.
15. Mount the welding elements with the distance X to the marks. D 560 mm X = 20 mm. D > 560 mm X = 30 mm. Stretch the elements uniformly so that the element ends exactly do NOT touch.
18. Shrink the sleeve from the middle towards the ends. Shrink the sleeve until it is in full contact with welding elements, insulation and jacket pipe.
19. Mount clamps 5-10 mm over the sleeve ends. Press the clamps until the jacket pipe starts to deform (max. 0.1 mm). Keep the clamps tightly positioned by using a clamping tool.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HEW
High temperature joint for foaming
5.4.2 - 4/4
20. Adjust the cutoff voltage on the welding machine for each welding element according to the actual welding parameters. Mount the welding clips at the tip of the terminal wires. Start welding. After completed welding wait until the sleeve is handwarm, at least 30 minutes. Wait until the clamps are handwarm underneath, before they are removed.
21. Check the joint. Criteria for approval of EW joint: - No visible welding elements - No severe local melt out - No deformation After approval of the joint, cut off the terminal wires at the joint edge. The joint is complete.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HDHEC
High temperature end cap
5.4.3 - 1/3
End cap
Important: Never apply heat to creases, if any, since the material will be discoloured and the surface will crack. Never apply heat underneath the end cap, as this may damage the end cap permanently. Pockets of air under the end cap can be removed by bending a piece of welding wire into U-shape and pushing it underneath the end cap while it is still warm. Use burner head dia. 51 mm for all dimensions. 3. Cut the jacket and insulation using the marks as a guide.
4. Cut lengthwise through the jacket and remove jacket and insulation material. 1. Place the steel reduction 20-30 mm from the steel pipe end.
HDHEC
High temperature end cap
5.4.3 - 2/3
6. Adjust the mineral wool shells to the length (B) of the steel reduction.
10. Activate the steel reduction and the jacket pipe with abrasive cloth grain size 80 at least 60 mm from the end of the jacket pipe.
7. Place the mineral wool shells on the carrier pipe as close to the PUR insulation as possible.
11. Activate the steel reduction and the jacket with gas burner at least 60 mm from the end of the jacket pipe until the jacket surface has a matt, silky look.
8. Pull the steel reduction onto the carrier pipe and the mineral wool shells. The steel reduction is placed correctly when it is in contact with the PUR insulation.
12. Remove the foil inside the end cap. Check that it is CLEAN and DRY, inside and out. Pull the end cap onto the steel reduction and jacket.
9. Weld the steel reduction to the carrier pipe. The welding has to be tightly.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com
HDHEC
High temperature end cap
5.4.3 - 3/3
13. Start shrinking the end cap onto the jacket pipe only. DO NOT YET shrink the edge of the end cap nor the end surface onto the jacket pipe. The flame must be held at a right angle to the pipe surface.
14. After a pause of approx. 3 min. shrink the end cap onto the steel reduction and at the same time the edge of the end cap and the end surface onto the jacket pipe. The flame must be held at a right angle to the pipe surface.
15. The end cap is complete when the sealing becomes visible on the steel reduction and the end cap is smooth.
Lgstr Rr A/S . Danmarksvej 11 . DK-9670 Lgstr . Tel. +45 99 66 10 00 . Fax +45 99 66 11 80 . lrinfo@logstor.com