SYSTEM OVERVIEW
A. SYSTEM OVERVIEW
This chapter describes each of the CS3000/1000 system components
A-1
A. SYSTEM OVERVIEW
Console type The floor-mounted console comes with a 21 inch CRT which has touch panel operation function. It has both an operation keyboard and an engineering keyboard. However, this type of HIS is only available for CS3000 system.
A-2
A. SYSTEM OVERVIEW
A-3
A. SYSTEM OVERVIEW
A-4
A. SYSTEM OVERVIEW
A-5
A. SYSTEM OVERVIEW
A-6
A. SYSTEM OVERVIEW
Processor Card The processor card performs calculation and control computation. Some models of the FCS have two processor cards as a dual redundant feature. One of the card is in control status and the other is in standby status Each processor unit has two CPUs, which perform the same control computation. The computation results are compared by a collator during each computation cycle. If the computation results from the two CPUs match, the collator determines that the computation is normal and sends data to locations such as the main memory and bus interface unit. Because the main memory has an ECC, transient bit inversion errors occurring in the main memory can be repaired.
If computation results from CPU1 and CPU2 do not match, the collator judges that a computation error has occurred, and the control right will be transferred to the standby side. The standby processor unit performs the same computation as the control side, even though it is in the standby state. Therefore, it can immediately resume the output of control computation data to the bus interface when it takes over the control right. Self-diagnostics will be executed on the processor unit in which an error has occurred. If no CPU error is detected as a result of diagnostics, the error will be judged a transient computation error, and the error-state will return to standby. The processor unit on standby performs the same computation concurrently with the control side. Therefore, CPUs within the same unit collate each others computation data, being sure to detect any computation errors. Because the unit on standby performs the same control computation concurrently with the control side, it can take over the control computation at any point without interruption, even for the shortest time.
A-7
A. SYSTEM OVERVIEW
A4. NETWORK
CS1000 / CS3000 uses VL / V net and Ethernet for control data communications.
Transmission Speed Cable Transmission distance Access Method Repeater - Coaxial Cable - Optical Fiber
V Net 10Mbps 10BASE2 cable used by HIS stations 10BASE5 cable used by FCS, ACG etc. 500 m/segment (for 10Base5) 185 m/segment (for 10Base2) Token Passing Maximum 8 sets, 1.6 km Maximum 4 sets, 20km
VL Net 10Mbps 10BASE2 cable used by stations 185 m/segment (for 10Base2) Token Passing Maximum 8 sets, 1.6 km Maximum 4 sets, 20km
Ethernet HIS and ENG, HIS and Supervisory systems can be connected by Ethernet LAN; supervisory computers and PC on the Ethernet LAN can access messages and trend data in the CS3000 / 1000 system. The Ethernet can also be used for sending trend data files from the HIS to supervisory computers or for equalizing the data in the 2 HIS station rather than using the V / VL net to do this. A system with only a single HIS with engineering functions does not need Ethernet. V net versus Ethernet Since CS1000 is a small-scale system (max 24 stations) and the information net and V net will not be heavily loaded, Ethernet has been optional. In contrast, for CS3000, Ethernet is a standard equipment for communication between the HISs to prevent the V net from being overloaded since CS3000 is a large scale system.
A-8
A. SYSTEM OVERVIEW
Max. no. of HIS-monitored tags Max. no. of stations Max. no. of domains Max. no. of stations per domain
A-9
A. SYSTEM OVERVIEW
HIS Station Address setting The dip switches for domain and station no. setting for the HIS can be found on the VHF control bus card, installed in the PC PCI card slot.
A - 10
A. SYSTEM OVERVIEW
LABORATORY A
Questions Q1 Which station does the necessary calculation and process the input output electrical signal from the field ? Which station is used for monitoring and operation of the field tags and instrument, displaying the necessary process variable, output variable ? What is the network cable for signal transmission between FCS and HIS for CS3000 and CS1000 ? What software platform is CS1000 and CS3000 installed upon in the HIS and ENG ? What will happen to the FCS memory when the FCS suffer power failure ? For a AFD FCS station, name the 2 basic status of the processor card. What is a node in FCS ? What is the maximum no. of domains in a CS1000/3000 system ? What is the maximum no. of HIS stations in a domain for CS1000/3000 ?
Q2
Q3
Q4 Q5 Q6 Q7 Q8 Q9
A - 11