Sunteți pe pagina 1din 6

CPS2000 (Cabinet Power System)

Input (Nominal): 100 Vac to 240 Vac (Autoranging) Output (Nominal): 48 Vdc (up to 30 A) 50 VA Ringing Generator

The low-maintenance, outside-plant CPS2000 (Cabinet Power System) integrates advanced technology in a modular system with unique shelf configurations for both 19 inch and 23 inch racks.

Dual Configurations

The 19 in. and 23 in. shelf assemblies are available in the following configurations:
n n

Rectifier plant with four power module positions Ringer-rectifier plant with up to three rectifiers and two ringing generators

Wide Temperature Range

The CPS2000 is a high-reliability system incorporating temperature hardened-electronics. It is suited for use in remote applications at an extremely wide temperature range, 40 C to +75 C (40 F to +167 F) with fan-assisted cooling, or 40 C to +50 C (40 F to +122 F) with natural convection cooling.

The single-shelf assembly, equipped with plug-in modules, is just 5.25 in. (3U) high and 12 in. deep, and it can accommodate a variety of equipment and functions, including:
n n

7.2 A, 48 V nominal rectifier 50 VA 100 Vac/20 Hz ringing generator (halfwidth power module) Monitor and Control Unit (MCU) or Alarm and Control Unit (ACU) Low battery-voltage disconnect/reconnect (optional) Slope-compensated thermal management

Multiple Outputs

The multiple power bus architecture supports applications requiring 48 V and ringing voltage, which can eliminate the need for separate power plants.

n n

Applications
n n n n

Digital loop carrier Fiber to the curb Remote switching cabinets Broadband/CATV cabinets
n

Benefits
n

System Safeguards Thermal management options, overcurrent/overvoltage protection, and low-voltage battery disconnect provide protection for equipment and batteries. Compatible with standard office alarms (Form-C contact closure). Safety/Standards Compliance UL-recognized* CSA certified VDE Licensed CE Marked

Monitor and Control Unit


n

Model ES446 MCU provides display of primary output voltage and current, output alarms, plant battery voltage control, thermal management, and alarm LEDs.

Alarm and Control Unit


n

Maximum Design Efficiency The low-profile shelf assembly is a space-saving 5.25 in. high by 12 in. deep by 17.35 in. or 21.35 in. wide. The system is available for mounting on 19 in. or 23 in. racks. Adapters are available for ETSI mounting (500 mm). Power modules, ringing generators, monitor and control unit, manual battery disconnect switches, lowvoltage battery disconnect, and thermal management are all housed in one compact shelf. All equipment is frontaccessible, ideally suited for use in cabinets and other space-restrictive environments. The system is compatible with a wide range of input voltages. Cost Efficiency Unique, lightweight components and front-access system architecture reduce installation and maintenance expenses. Near-unity power factor correction can result in lower utility costs. Enhanced Reliability The CPS2000 has been designed by Lucent Technologies Bell Labs using the latest technology, strictly controlled manufacturing processes, and the highest quality standards to ensure excellent performance, superior reliability, and an extended service life. Continuous Operation Plug-in modules can be easily added or replaced without any interruption of service.

Economical alternative to MCU provides plant alarm and control functions; Model ES447 ACU provides test points for reading and adjusting plant voltage.

Features CPS2000 (Cabinet Power System)


n n n

Output Distribution
n

High power factor

Includes primary and secondary output distribution built into the shelf. The 23 in. shelf output distribution section houses the low battery-voltage disconnect/ reconnect contactor, connection for thermal probes, battery connection points, and optional battery disconnect switches. Fourteen GMT-type fuse outputs are available on the primary bus. Nine of the outputs are connectorized and rated for up to 10 A each and the other five terminal block outputs are rated for up to 15 A each. The 19 in. shelf output distribution section provides either a bulk output or seven connectorized, GMT fused outputs on the primary bus and connectorized output on the secondary bus.

High power density Mountable in 19 in. or 23 in. rack, optional ETSI brackets (500 mm) available Totally front accessible Temperature-hardened electronics Battery thermal management Input voltage autoranging Built-in fuse distribution Hot-insertion modular design Overvoltage/overcurrent protection Low battery-voltage disconnect option

n n

n n n n n

Rectifier
n

Model ES460 operates from a nominal 100 Vac, 120 Vac, 200 Vac, 208 Vac, 220 Vac, and 240 Vac source. Provides adjustable output voltage over the range of 48 V to 56 V at 7.2 A. Provides highly regulated, lownoise power for the system loads and for charging the system batteries.

Batteries
n

Designed to operate with Lucent Technologies IR and HR series batteries or any other type of valve-regulated battery.

Ringer Generator
n

* UL is a registered trademark of Underwriters Laboratories, Inc. CSA is a registered trademark of Canadian Standards Association, Inc. VDE is a registered trademark of Verband Deutscher Elektrotechniker E.V.

Operates at 50 VA, 100 Vac/ 20 Hz (Model ES421) or 100 Vac/25 Hz (Model ES422) using the output of the ES460 rectifiers or the system batteries.

Outline Drawings

11.85 in. (301.0 mm)

5.25 in. (133.4 mm)

21.35 in. (542.3 mm) enclosure 22.31 in. (566.7 mm) mounting centers 22.96 in. (583.2 mm) mounting ears

CPS 2000 23 in. Shelf

11.85 in. (301.0 mm)

5.25 in. (133.4 mm)

CPS 2000 19 in. Shelf

17.35 in. (440.7 mm) enclosure 18.31 in. (465.1 mm) mounting centers 19.86 in. (504.5 mm) mounting ears

CPS2000 (Cabinet Power System) Specifications


Electrical and Thermal Input Voltage Ranges 90 Vac to 264 Vac, single phase (includes 100 Vac/120 Vac/200 Vac/208 Vac/220 Vac/240 Vac nominal) autoranging 5.0 A at 90 Vac, 3.8 A at 120 Vac, 2.5 A at 180 Vac, 1.9 A at 240 Vac 47 Hz to 63 Hz >0.98 for loads; >60% full load >85% for loads; >75% full load 40 C to +75 C (40 F to +167 F) with fan-assisted cooling 40 C to +50 C (40 F to +122 F) with natural convection cooling <5% for loads; >60% full load

ac Drain (Rectifier) Frequency Power Factor Efficiency Operating Temperature Range Harmonic Distortion Primary Output (Rectifier) Voltage Nominal Range Current Output Voltage Regulation Output Ripple Physical Rectifier (ES460) Ringer (ES421) Shelf (23 in. with LVD) Shelf (19 in. with LVD) Environmental Operating/Storage Relative Humidity Storage Temperature Audible Noise Safety/Standards Compliance Safety 23 in. System 19 in. System Electromagnetic Compliance: Emission Immunity

48 Vdc/52 Vdc/54.5 Vdc 48 Vdc to 56 Vdc Up to 28.8 Adc (7.2 Adc per rectifier) +0.5% 50 mV peak-to-peak maximum over the range 10 Hz to 20 MHz Width Height Weight Depth 10.5 in. 3.0 in. 4.8 in. 5.25 lb. 121.9 mm) (2.4 kg) (266.7 mm) (76.2 mm) 1.6 in. 4.8 in. 2.0 lb. 10.5 in. (121.9 mm) (0.9 kg) (266.7 mm) (40.6 mm) 11.85 in. 21.35 in. 5.25 in. 17.75 lb. (301.0 mm) (542.3 mm) (133.4 mm) (8.1 kg) 11.85 in. 17.35 in.* 5.25 in. 13.25 lb. (301.0 mm) (440.7 mm) (133.4 mm) (6.0 kg) 5% to 95% 40 C to +85 C (40 F to +185 F) <65 dBA

L21, 22 UL-Listed (UL 1950/CSA 950; UL 1801) L23-25 UL-Listed (UL 1950/CSA 950;UL 1801), CSA certified, VDE Licensed (EN60950/VDE 0805) EN55022 (CISPR22) Radiated/Conducted Emission, Class B Meets FCC Part 15 Class B IEC/EN61000-3-2 IEC/EN61000-3-3 IEC/EN61000-4-2 ESD level 3 and 4 IEC/EN61000-4-3 Radiated Immunity, 10 Vm IEC/EN61000-4-4 Electrical Fast Transients/Burst, level 4 IEC/EN61000-4-5 Lightning Surge, level 4 IEC/EN61000-4-6 Conducted Immunity 19 in. shelves, L23, L24, and L25 CE Marked per European Union Council Directives: Low Voltage Directive (73/23/EEC) and EMC Directives (89/336/EEC) as amended by CE Marking Directive (93/68/EEC)

CE Marking

*List 100 mounting brackets support mounting in a 500 mm frame (515 mm).

Ordering Information
CPS2000 Shelves, Rectifiers, Ringers, and Control Units Comcode 107733057 108152125 107775215 107775223 107999690 107992190 107775306 601828817 601832454 601832462 107999237 107994717 107999229 107999211 107999294 107999286 107999245 107999260 107999252 601861891 601861909 601861917 601861925 601861933 601861941 601861958 601861966 601861974 601861982 601861990 601862006 601886310 601886328 601869175 601869159 601869142 Apparatus Code ES460 ES460B ES446 ES447 ES421 ES422 EDF J85582R-2 L-21, L-34 J85582R-2 L-22, L-34 J85582R-2 L-22, L-44 J85582R-2 L-21, L-31 J85582R-2 L-21, L-32 J85582R-2 L-21, L-33 J85582R-2 L-22, L-31 J85582R-2 L-22, L-32 J85582R-2 L-22, L-33 J85582R-2 L-22, L-41 J85582R-2 L-22, L-42 J85582R-2 L-22, L-43 J85582R-2 L-24, L-51 J85582R-2 L-24, L-52 J85582R-2 L-24, L-53 J85582R-2 L-24, L-54 J85582R-2 L-25, L-51 J85582R-2 L-25, L-52 J85582R-2 L-25, L-53 J85582R-2 L-25, L-54 J85582R-2 L-25, L-61 J85582R-2 L-25, L-62 J85582R-2 L-25, L-63 J85582R-2 L-25, L-64 J85582R-2 L-23, L-41 J85582R-2 L-23, L-44 J85582R-2 L-23, L-62 J85582R-2 L-23, L-64 J85582R-2 L-100 Description 48 V, 7.2 A Rectifier 48 V, 7.2 A Rectifier (EMI Class B) Monitor and Control Unit Alarm and Control Unit 20 Hz,50 VA Ringing Generator 25 Hz, 50 VA Ringing Generator LED Board (spare or replacement) CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf CPS Shelf Mounting Bracket

Related Product Literature

Document Title Cabinet Power System 2000 (CPS2000) Air Flow Management (Application Note)

Document Number AP97-014LIN

CPS2000 Power System (J85582R-2) Ordering Information


List Number 21 22 23 24 25 31 32 33 34 41 42 43 44 51 52 53 54 61 62 63 64 100 Description Provides ac input with one IEC 320-type receptacle for 23 in. shelf Provides ac input with two IEC 320-type receptacles for 23 in. shelf Provides terminal block for single ac input for 19 in. and 23 in. shelf Provides ac input with one IEC 320-type receptacle for 19 in. shelf Provides dual ac input with two IEC 320-type receptacles powering odd and even slots for 19 in. shelf Provides 23 in. shelf for ringers and 48 V rectifiers, without battery disconnect switches, and without low-voltage battery disconnect (LVBD)6,7 Provides 23 in. shelf for ringers and 48 V rectifiers, with LVBD, without battery disconnect switches6 Provides 23 in. shelf for ringers and 48 V rectifiers, with battery disconnect switches, without LVBD6,7 Provides 23 in. shelf for ringers and 48 V rectifiers, with battery disconnect switches and LVBD6,7 Provides 23 in. shelf for 48 V rectifiers only, without battery disconnect circuit breakers and without LVBD6 Provides 23 in. shelf for 48 V rectifiers only with LVBD, without battery disconnect switches Provides 23 in. shelf for 48 V rectifiers only, with battery disconnect switches, without LVBD6 Provides 23 in. shelf for 48 V rectifiers only, with battery disconnect switches and LVBD6 Provides 19 in. shelf for ringers and 48 V rectifiers, with bulk output, without LVBD1,5 Provides 19 in. shelf for ringers and 48 V rectifiers, with bulk output, with LVBD1,5 Provides 19 in. shelf for ringers and 48 V rectifiers, with fused output, without LVBD2,5 Provides 19 in. shelf for ringers and 48 V rectifiers, with fused output, with LVBD2,5 Provides 19 in. shelf for 48 V rectifiers only, with bulk output, without LVBD3,5 Provides 19 in. shelf for 48 V rectifiers only, with bulk output, with LVBD3,5 Provides 19 in. shelf for 48 V rectifiers only, with fused output, without LVBD4,5 Provides 19 in. shelf for 48 V rectifiers only, with fused output, with LVBD4,5 Mounting brackets to adapt 19 in. shelf to ETSI spacing (515 mm mounting centers)

1. The bulk output distribution for the 19 in. combination ringer and rectifier shelf consists of a single, double hole lug, 48 V output, and one connectorized, electronically protected ringer output. 2. The fused distribution for the 19 in. combination ringer and rectifier shelf consists of seven connectorized 48 V outputs with GMT-type fuse protection and one connectorized, electronically protected ringer output. 3. The bulk output distribution for the 19 in. rectifier only shelf consists of a single, double hole lug, 48 V output. 4. The fused output distribution for the 19 in. rectifier shelf only consists of seven connectorized 48 V outputs with GMT-type fuse protection. 5. The 19 in. shelf configurations are not available with battery disconnect switches because of physical space constraints. 6. All 23 in. shelves are equipped with 14 fused 48 V outputs with GMT-type fuses. Nine of the 14 are connectorized, and five of the 14 are accessible by terminal block. 7. The 23 in. ringer/rectifier shelves are equipped with two connectorized, electronically protected ringer outputs.

For additional information, contact your Lucent Technologies Account Manager or the following: POWER SYSTEMS UNIT: Network Products Group, Lucent Technologies Inc., 3000 Skyline Drive, Mesquite, TX 75149, USA +1-800-526-7819 (Outside U.S.A.: +1-972-284-2626, FAX: +1-972-284-2900) (product-related questions or technical assistance) INTERNET: http://www.lucent.com/networks/power E-MAIL: techsupport@lucent.com ASIA PACIFIC: Lucent Technologies Singapore Pte. Ltd., 750D, Chai Chee Road, #07-06, Chai Chee Industrial Park, Singapore 469004 Tel: (65) 240 8041, FAX: (65) 240 8438 CHINA: Lucent Technologies (China) Co., Ltd., SCITECH Place, No. 22, Jian Guo Men Wai Avenue, Beijing 100004, PRC Tel: (86) 10-6522 5566 ext. 4187, Fax: (86) 10-6512 3634 JAPAN: Lucent Technologies Japan Ltd., Mori Building, No. 21, 4-33, Roppongi 1-Chome, Minato-ku, Tokyo 106-8508, Japan Tel: (81) 3 5561 5831, FAX: (81) 3 5561 1616 LATIN AMERICA: Lucent Technologies Inc., Room 416, 2333 Ponce de Leon Blvd., Coral Gables, FL 33134, USA Tel: +1-305-569-4722, FAX: +1-305-569-3820 EUROPE: Data Requests: DATALINE: Tel: (44) 1189 324 299, FAX: (44) 1189 328 148 Technical Inquiries: GERMANY: (49) 89 95086 0 (Munich), UNITED KINGDOM: (44) 1344 865 900 (Ascot), FRANCE: (33) 1 40 83 68 00 (Paris), SWEDEN: (46) 8 594 607 00 (Stockholm), FINLAND: (358) 9 4354 2800 (Helsinki), ITALY: (39) 02 6608131 (Milan), SPAIN: (34) 91 807 1441 (Madrid)
Lucent Technologies Inc. reserves the right to make changes to the product(s) or information contained herein without notice. No liability is assumed as a result of their use or application. No rights under any patent accompany the sale of any such product(s) or information. Copyright 1999 Lucent Technologies Inc. All Rights Reserved Printed in U.S.A.

DS99-120LIN (Replaces DS98-416LIN)

Printed on Recycled Paper