Sunteți pe pagina 1din 142

A1800 ALPHA meter

Technical manual
TM42-2410E
www.elster.com
Technical manual i Contents
Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
A1800 ALPHA meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Standards Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
IEC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
IEEE/ANSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
DLMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
DIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Maintainability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
ANSI standard communication open protocol . . . . . . 1-4
Adaptability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Economy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Meter types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Meter series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Metercat software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Alpha Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
2 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Physical description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Optical port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Utility information card . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Cover tamper detection switches . . . . . . . . . . . . . . . . . 2-5
Terminal configurations . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Communication protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
System architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
General theory of operation . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Main power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Auxiliary power supply . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Current and voltage sensing . . . . . . . . . . . . . . . . . . . . . . 2-8
Meter engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Microcontroller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Billing data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Metered energy and demand quantities . . . . . . . . . . . 2-10
Average power factor . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Demand calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Rolling interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Block interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Thermal time constant . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Maximum demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Cumulative maximum demand . . . . . . . . . . . . . . . . . . 2-12
Continuous cumulative maximum demand . . . . . . . . 2-12
Technical manual ii Contents
Coincident demand or power factor . . . . . . . . . . . . . . . 2-13
Demand forgiveness . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Primary and secondary metering . . . . . . . . . . . . . . . . . 2-13
TOU data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Power failure data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Always Positive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Logs and data sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Event log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
History log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Self reads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Load profiling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Load profiling pulse divisor . . . . . . . . . . . . . . . . . . . . . 2-17
Instrumentation profiling . . . . . . . . . . . . . . . . . . . . . . . . 2-17
TRueQ Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Voltage sag log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
User-defined tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Physical dimensions and mass . . . . . . . . . . . . . . . . . . . . . . 2-19
3 Operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Indicators and controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Quantity identifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Display quantity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Phase indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Energy direction indicators . . . . . . . . . . . . . . . . . . . . . . 3-2
Power/energy units identifier . . . . . . . . . . . . . . . . . . . . 3-3
Alternate display indicator . . . . . . . . . . . . . . . . . . . . . . 3-3
Error indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Low battery indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Active COM port indicator . . . . . . . . . . . . . . . . . . . . . . . 3-3
Display indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Push buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
RESET button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Using the backlight . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Normal mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Alternate mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Test mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Read without Power mode . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Demand reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Demand reset lockout . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Demand reset data area . . . . . . . . . . . . . . . . . . . . . . . . 3-10
4 Meter tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
System instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
System service tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Service voltage test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
System service locking . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Initiating service voltage tests . . . . . . . . . . . . . . . . . . . . 4-7
Restarting the service voltage test in diagnostic mode 4-9
Service current test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Initiating the service current test . . . . . . . . . . . . . . . . . 4-10
System service error codes . . . . . . . . . . . . . . . . . . . . . . 4-10
TRueQ monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
TRueQ timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
TRueQ display items . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
TRueQ and relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
TRueQ log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Technical manual iii Contents
Voltage sags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Voltage sag counter and timer . . . . . . . . . . . . . . . . . . 4-13
TRueQ tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
TRueQ event counters and timers . . . . . . . . . . . . . . . 4-15
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-25
Meter passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-25
Antitampering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-26
Program protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-26
5 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Energy pulse outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Using pulse divisor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Using pulse value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Relay-related alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
LED pulse outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Output specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
6 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Meter self test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Codes and warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Warning codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Communication codes . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Meter shop testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Test equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Test setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Meter testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Using relay outputs for testing . . . . . . . . . . . . . . . . . . 6-10
Using LCD pulse count for testing . . . . . . . . . . . . . . . 6-10
7 Installation and removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Preliminary inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Placing the meter into service . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Installing a TOU battery . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Initial setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
Marking the utility information card . . . . . . . . . . . . . . . . 7-5
Removing the meter from service . . . . . . . . . . . . . . . . . . . . . 7-6
Removing the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
8 Loss compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
What is Loss Compensation? . . . . . . . . . . . . . . . . . . . . . . 8-1
Availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Software support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Calculating the correction values . . . . . . . . . . . . . . . . . . . . . . 8-1
Gather necessary data . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Calculate the meter configuration parameters . . . . . . . 8-2
Calculating line loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Gather necessary data . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Calculation example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
Gather necessary data . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
Enter Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
Internal meter calculations . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
Meter outputs affected by compensation . . . . . . . . . . . . . . 8-15
Technical manual iv Contents
Testing a meter with compensation . . . . . . . . . . . . . . . 8-15
A Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
B Display table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Display format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Display list items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Default display formats . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
LCD test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
General meter information . . . . . . . . . . . . . . . . . . . . . . . . B-4
Meter configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
Metered quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Average power factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-8
Coincident demand and power factor . . . . . . . . . . . . . . B-8
Cumulative demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-8
System instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . B-9
System service tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-11
Errors and warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-12
Communication codes . . . . . . . . . . . . . . . . . . . . . . . . . . B-12
C Nameplate and style number information . . . . . . . . . . . . . . . C-1
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Utility information card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2
Style number information . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-3
D Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Direct connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
CT-connected meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-2
E Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Absolute maximums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Operating ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Operating characteristics . . . . . . . . . . . . . . . . . . . . . . . . . E-1
General performance characteristics . . . . . . . . . . . . . . . E-2
Dimensions and mass . . . . . . . . . . . . . . . . . . . . . . . . . . . E-2
Technical manual v Contents
Disclaimer of Warranties and Limitation of Liability
There are no understandings, agreements, representations, or warranties either
expressed or implied, including warranties of merchantability or fitness for a particular
purpose, other than those specifically set out by any existing contract between the parties.
Any such contract states the entire obligation of the seller. The contents of this technical
manual shall not become part of or modify any prior or existing agreement, commitment,
or relationship.
The information, recommendations, descriptions, and safety notices in this technical
manual are based on Elster Electricity, LLC experience and judgment with respect to the
operation and maintenance of the described product. This information should not be
considered as all-inclusive or covering all contingencies. If further information is required,
Elster Electricity, LLC should be consulted.
No warranties, either expressed or implied, including warranties of fitness for a particular
purpose or merchantability, or warranties arising from the course of dealing or usage of
trade, are made regarding the information, recommendations, descriptions, warnings,
and cautions contained herein.
In no event will Elster Electricity, LLC be held responsible to the user in contract, in tort
(including negligence), strict liability, or otherwise for any special, indirect, incidental, or
consequential damage or loss whatsoever, including but not limited to: damage or loss of
use of equipment, cost of capital, loss of profits or revenues, or claims against the user by
its customers from the use of the information, recommendations, descriptions, and safety
notices contained herein.
Safety Information
Installation, operation, and maintenance of this product can present potentially hazardous
conditions (for example, high voltages) if safety procedures are not followed. To ensure that
this product is used safely, it is important that you:
Review, understand, and observe all safety notices and recommendations within this
manual.
Do not remove or copy individual pages from this manual, as this manual is intended for
use in its entirety. If you were to remove or copy individual pages, cross references and
safety notices may be overlooked, possibly resulting in damage to the equipment,
personal injury, or even death.
Inform personnel involved in the installation, operation, and maintenance of the product
about the safety notices and recommendations contained in this manual.
Within this manual, safety notices appear preceding the text or step to which they apply.
Safety notices are divided into the following four classifications:

Notice is used to alert personnel to installation, operation, or maintenance
information that is important but not hazard related.

Caution is used to alert personnel to the presence of a hazard that will or can
cause minor personal injury, equipment damage, or property damage if the
notice is ignored.
Technical manual vi Contents

Warning is used to alert personnel to the presence of a hazard that can cause
severe personal injury, death, equipment damage, or property damage if notice
is ignored.

Danger is used to alert personnel to the presence of a hazard that will cause
severe personal injury, death, equipment damage, or property damage if the
notice is ignored.
Revisions to This Document
The A1800 ALPHA Meter Technical Manual can be referred to by its document number:
TM422410. Each revision of this manual is designated with a letter, with the first revision
being A, the second being B, and so forth. The document number and its revision are
located at the bottom of each page.
The following table lists the revisions to this document, the date of the release, and any
notes about the changes made.
Revision Date Brief Description
A 31 August 2005 Initial release of the document.
B 22 June 2006 Grammatical corrections and corrections for clarity made throughout the manual.
Addition of partially-transparent cover in Security in Chapter 1. Addition of A1880
meter functions and other meter types in Table 1-4. Renamed manufacturer
nameplate to nameplate and renamed utility nameplate to utility information
card. Renamed open cover detection switches to cover tamper detection
switches. Added Auxiliary Power Supply in Chapter 2. Added backlight information
to LCD in Chapter 3 and Using the Backlight in Chapter 3. Program mode
renamed to program protection and is now included in Program Protection in
Chapter 4. Clarified meter types and output options in Relay Outputs in Chapter 5.
Clarified the pulse constant information in Using Pulse Divisor in Chapter 5. Added
Style Number Information in Appendix C. Corrected Appendix E, Technical
Specifications.
23 June 2006 Corrected typographical error for Pulse count for quantity (alternate-delivered) in
Appendix B.
C 31 August 2006 Grammatical corrections and corrections for clarity made throughout the document.
Corrected and clarified output specifications in Chapter 5, Outputs.
D 09 February 2007 Added IEEE standards information in Table 1-2. Added information regarding direct
connect-rated meters in Chapter 1, Chapter 5, Chapter 7, Appendix C, and Appendix
E. Corrected wiring diameter sizes in Placing the Meter into Service, in Chapter 7.
Clarified the Note regarding two-element meters in Chapter 8. Corrected Figure D-7
in Appendix D.
E 01 July 2009 In addition to grammatical corrections and minor corrections throughout the
manual: Added DLMS to Standards Compliance in Chapter 1; added Meter series
in Chapter 1; revised Communications in Chapter 2; added Communication
protocols in Chapter 2; revised General theory of operation in Chapter 2; revised
Physical dimensions and mass in Chapter 2; added Read without Power mode in
Chapter 3; revised TRueQ tests in Chapter 4; revised Warning codes in Chapter 6.
Technical manual 1-1 Introduction
1 Introduction
A1800 ALPHA meter
The A1800 ALPHA meter family provides a platform that supports a variety of metering
requirements. The A1800 ALPHA meter family is a totally electronic polyphase electricity
meter and integral register for commercial and industrial applications. The meter is
available in 3- and 4-wire configurations for 2 and 3 phases.
See Figure 1-1 for an illustration of an A1800 ALPHA meter.
Figure 1-1. A1800 ALPHA meter
CT
VT
A
V
imp/kWh(kVARh)
ELSTER SAMPLE
SERIAL #
01234567
UUf11
*01234567*
STYLE
ZE3JF4R00LM 01
R1 2-06210102AG-000000
3 x 58/100...277/480V, 60 Hz
1(10)A
0 2S
Made in USA 2006
5 000 imp/kWh
5 000 mp/kVarh
TYPE A1800
MODEL 1830RALN
T1 T2 T3 T4 T5 T6 T7 T8 EOI LC TC TST
- P +
Q
Q
L L L 1 2 3
COM 0 1 2
Technical manual 1-2 Introduction
Standards Compliance
IEC. The A1800 ALPHA meter meets or exceeds the following IEC standards for electricity
metering.
IEEE/ANSI. The A1800 ALPHA meter meets or exceeds the following IEEE/ANSI standards
for electricity metering, and it is intended for use by commercial and industrial utility
customers.
Table 1-1. IEC standards supported by the A1800 ALPHA meter
Number Date Edition Title
62052-11 2003 1 General requirements, tests and test conditions.
62053-21 2003 1 Particular requirements-static meters for active
energy (Classes 1.0 and 2.0)
62053-22 2003 1 Particular requirements-static meters for active
energy (classes 0,2 S and 0,5 S)
62053-23 2003 1 Particular requirements-static meters for
reactive energy (classes 2 and 3)
62053-31 1998 1 Particular requirements-pulse output devices
for electromechanical and electronic meters
(two wires only)
62053-61 1998 1 Particular requirements-power consumption
and voltage requirements
62056-21
1
1
Complies with optical port requirements only.
2002 1 Electricity metering-data exchange for meter
reading, tariff and load control-direct local data
exchange
62052-21 2004 Electricity metering-tariff and load control-
particular requirements for time switches
Table 1-2. IEEE/ANSI standards supported by the A1800 ALPHA meter
Number Date Title
IEEE 1701/
ANSI C12.18
1996 Protocol Specification for ANSI Type 2 Optical
Port
IEEE 1377/
ANSI C12.19
1997 Utility Industry End Device Data Tables
IEEE 1702/
ANSI C12.21
1999 Protocol Specification for Telephone Modem
Communications
Technical manual 1-3 Introduction
DLMS. The A1800 ALPHA meter meets or exceeds the following IEC standards for DLMS
protocol support (when the meter is enabled for DLMS protocol support). See
Communication protocols on page 2-6 for more information.
DIN. The A1800 ALPHA meter meets or exceeds the following DIN standards for electricity
metering.
Benefits
Reliability. The A1800 ALPHA meter, part of the ALPHA line of meters, uses the patented
ALPHA meter technology for measurement and accurate calculation of energy quantities.
With over 3 million ALPHA polyphase meters in operation throughout the world, the
A1800 ALPHA continues the tradition of reliable electronic meters.
The power supply in the meter operates from any available phase. A three-phase, four-
wire A1800 ALPHA meter maintains operation if the neutral line and any one or two of the
line voltages become disconnected. The meter can also operate using the auxiliary power
supply, which can power the meter from an independent power source in the situation
where main power is unavailable.
The A1800 ALPHA meter can use its internal crystal oscillator or the power line frequency to
maintain time and date functions. The crystal oscillator can be used when the power line
frequency is known to be too unstable for accurate timekeeping.
The A1800 ALPHA meter has been designed to function to provide long battery life.
Because of the low current drain, the service life of the lithium battery can exceed the life of
the meter.
The A1800 ALPHA meter uses nonvolatile memory to store billing and other critical data.
The data is preserved even if the power fails.
Maintainability. The A1800 ALPHA meter is easy to maintain. Meter register functions and
communication interfaces are fully integrated on a single, surface-mount technology
circuit board.
The meter firmware resides in flash memory, allowing the firmware to be upgraded in the
field.
Table 1-3. IEC standards supported by the A1800 ALPHA meter for DLMS protocols
Number Date Edition Title
62056-42 2002-02 1.1 Physical layer services and procedures for
connection-oriented asynchronous data
exchange
62056-46 2007-02 1.1 Data link layer using HDLC protocol
62056-53 2006-12 2 COSEM Application layer
62056-61 2006-11 2 Object identification system (OBIS)
62056-62 2006-11 2 Interface classes
Table 1-4. DIN standards supported by the A1800 ALPHA meter
1
1
For meter width and location of lower mounting holes
Number Date Title
DIN 43857 Part 2 1978 Watthour meters in moulded insulation case
without instrument transformers, up to 60 A
rated maximum current; principal dimensions
for polyphase meters.
Technical manual 1-4 Introduction
ANSI standard communication open protocol. The A1800 ALPHA meter complies
with the ANSI C12.18, C12.19, and C12.21 standards. These standards include
communication protocols for a wide range of metering products. They are the basis for
common industry data structures and a common protocol for transporting the data
structures. Supporting the ANSI protocols makes it easier to add products to existing
systems and provide an open standard for meter data communications.
Adaptability. The A1800 ALPHA meter allows configuration for custom TOU rates (tariffs),
offering a broad range of demand and TOU operations.
Most common services and mounting configurations are supported, and functional
upgrades are easily performed as new situations arise. The wide operating range allows
installation at any of the common meter voltages. Additionally, the factory-configurable
optical port accommodates ANSI and IEC standards. The 16-segment character liquid
crystal display (LCD) improves readability and provides flexibility for displaying meter
information. As an added feature, the main meter circuit board provides selectable,
independent, serial remote interfaces for RS-232 or RS-485 communication.
Economy. The A1800 ALPHA meter saves both time and money. It can increase personnel
productivity because of the following features:
no user calibration required (factory calibrated)
reduced testing times
fewer styles to learn and maintain
dual serial communications interfaces on the main meter circuit board
automated data retrieval
system service verification
on-site instrumentation displays
tamper restraint and quality monitoring (TRueQ) tests
event logging
Security. The A1800 ALPHA meter is tamper-resistant. Passwords may be specified that
prevent unauthorized access to meter data. The standard TRueQ feature or the optional
instrumentation profiling (or both) can be used to detect possible tampering of energy
measurements.
All A1800 ALPHA meters provide auditing capabilities that can be used to indicate potential
meter tampering like terminal cover open detection and per phase outage recording.
The A1800 ALPHA meter can be ordered with a partially-transparent terminal cover,
making it easier to see obvious tampering.
Accuracy. The A1800 ALPHA meter meets or exceeds requirements of IEC standards.
The meter precisely measures demand and energy across a wide range of voltage and
current despite variations in temperature and power factor.
The low current sensor burden may also improve the accuracy of external current
transformers when measuring light loads.
Configuration
IEC 62053-22 IEC 62053-21 IEC 62053-23
1
Class 0.2 S Class 0.5 S Class 1.0 Class 2.0 Class 2.0 Class 3.0
direct connect
1
1
Actual reactive energy accuracy is substantially better than required by the standard.
9 9 9 9
transformer-rated 9 9 9 9
Technical manual 1-5 Introduction
Meter types
Different meters within the A1800 ALPHA meter family have specific capabilities (see
Table 1-5 and Figure 1-2).
Note: Throughout this manual, the term A1800 ALPHA is used to describe any meter in
the meter family. When necessary, a specific meter designation (for example,
A1830 meter) will be used to indicate that the description applies to only one meter
in the meter family.
Table 1-5. Meter designations of the A1800 ALPHA meter family
Meter Market segment Class Standard features Optional features
A1880
1
1
See Elster for availability.
Interchange meter 0.2 Multi-protocol communications
(Modbus, DNP 3.0, DL/T 645, or
TCP/IP)
4-quadrant metering
transformer and line loss
compensation (C)
load profiling (L)
instrumentation profiling (N)
extended MB memory (X)
auxiliary power supply
4 relays
TRueQ
2 additional relays
1
A1860 Large C&I 0.2, 0.5 2 communications ports
load profiling (L)
4 relays
TRueQ
transformer and line loss
compensation (C)
4-quadrant metering (A)
extended 1 MB memory (X)
instrumentation profiling (N)
auxiliary power supply
2 additional relays
1
A1830 Large C&I 0.5, 1.0 1 communications port
load profiling (L)
4 relays
TRueQ
transformer and line loss
compensation (C)
4-quadrant metering (A)
instrumentation profiling (N)
extended 1 MB memory (X)
auxiliary power supply
Class 0.2 accuracy
2 additional relays
1
internal telephone modem (PSTN)
2
2
Same wide temperature range rating as the meter (-40 C to +85 C inside meter cover; -40 C to +60 C outside)
A1810 Mid C&I 1.0 no communications ports
no relays
TRueQ
4-quadrant metering
load profiling (L)
instrumentation profiling (N)
extended 1 MB memory (X)
auxiliary power supply
Class 0.2 or 0.5 accuracy
4 relays
internal telephone modem (PSTN)
2
A1805 Small/Mid C&I 1.0 no communication ports
no relays
TRueQ
Limited to watt/var or bidirectional
active energy only
2 relays
Technical manual 1-6 Introduction
Figure 1-2. A1800 ALPHA meter family application pyramid
Meter series
The meter series is used to indicate the options and capabilities available for the
A1800 ALPHA meter.
Series 110 and later
Optional DLMS/COSEM protocol support available
Series 150
Optional Read without Power feature available
Metercat software
Beginning with Metercat release 2.3, the following features are supported:
Enhanced TRueQ test set
Up to 8 metered quantities
Independent TOU switch times for energy and demand
Alpha Keys
Alpha Keys

software allows A1800 ALPHA meters to be upgraded so they provide


additional functionality. Upgrading with Alpha Keys software means that the meter does
not have to be returned to the factory and new meters do not have to be purchased to gain
functionality.
The following features can be added to the meter by using Alpha Keys:
load profiling
instrumentation profiling
transformer and line loss compensation
1
4-quadrant metering
DLMS/COSEM protocol support
1
1
Contact Elster for availability.
Residential
Light C & I
Mid C & I
A1810
Large C & I
A1860
A1830
A1880
A
1
8
0
0

A
L
P
H
A

m
e
t
e
r

f
a
m
i
l
y
Interchange
metering
A1805
Technical manual 2-1 Product description
2 Product description
Physical description
The A1800 ALPHA meter is designed for indoor mounting. The cover assembly of the
A1800 ALPHA meter exceeds the environmental requirements of IEC 62053-11. The case of
the A1800 ALPHA meter provides an IP54 degree of protection for the meter.
The physical components of the A1800 ALPHA meter consist of the following:
terminal cover
long terminal cover (see Figure 2-1)
short terminal cover (see Figure 2-2)
partially-transparent terminal cover
meter cover assembly
inner cover assembly
base electronic assembly
Figure 2-1. Front view of the A1800 ALPHA meter
Active energy LED
Alternate energy LED
* (ALT) button
RESET button
(sealable)
Optical port
(IEC configuration)
Utility information
card area
Long wiring
cover
Terminal cover
screws
(sealable)
Nameplate
LCD
Technical manual 2-2 Product description
The terminal cover and meter cover assembly are manufactured using a UV-protected
polycarbonate plastic. The terminal cover is available in either the long version or the short
version. The meter cover assembly has a clear plastic window that allows the meter LCD
and nameplates to be viewed.
Figure 2-2. Front view of A1800 ALPHA meter with short terminal cover (transformer rated)
The A1800 ALPHA meter can be sealed using any or all of the following methods:
The four cover screws can be individually sealed (Figure 2-1). The two terminal cover
screws limit access to the main terminals and auxiliary wiring connections only. Therefore,
only the terminal cover seals must be broken to access these connections. The two meter
cover screws are located on the lower front of the meter under the terminal cover. Sealing
these screws seals the main enclosure and limits access to the metering circuit board and
sensing elements.
For maximum protection of the metering components, seal all four screw seals.
Seal location Purpose
Meter cover screws
(certification)
Prevents access to the meter except for the main
connections, relay connections, communication
interface connections, and nameplate. Also can
prevent reprogramming and recalibration of the
meter.
Terminal cover screws
(utility)
Prevents non-utility access to the main connections,
relay connections, and utility information card
RESET push button Prevents unauthorized manual demand resets
Technical manual 2-3 Product description
Figure 2-3. A1800 ALPHA meter with cover removed (transformer rated)
Optical port. The A1800 ALPHA meter provides an optical port that can be ordered with
either an ANSI-compliant or IEC-compliant interface (see Figure 2-4). To use Elster meter
support software to read or program the meter through the optical port, an optical probe is
required. This probe connects from the serial port of the computer to the optical port on the
meter.
Figure 2-4. Comparison of ANSI-compliant and IEC-compliant optical port interface
Elster recommends use of the UNICOM III probe to reliably read the A1800 ALPHA meter.
For information on ordering the UNICOM III probe, visit www.elsterelectricity.com or contact
your local Elster representative.
LCD. The A1800 ALPHA meter is equipped with a 16-segment character liquid crystal
display. See Indicators and controls on page 3-1 for details.
Nameplate. Elster installs the nameplate at the factory. See Appendix C, Nameplate and
style number information, for details on the nameplate.
Terminal connectors
Meter cover
screw (sealable)
TOU battery
Meter cover
screw (sealable)
Battery connector
Terminal cover removal
detector switch
Auxiliary power supply
Terminal cover
screw (sealable)
Terminal cover
screw (sealable)
ANSI-compliant optical interface IEC-compliant optical interface
Technical manual 2-4 Product description
Utility information card. The utility information card is removable (after the terminal
cover has been removed) and allows the utility to enter meter site-specific information. See
Utility information card on page C-2 for more information.
Figure 2-5. Removing the utility information card
Communications. The A1830 ALPHA meter provides remote communications interfaces
on the main meter circuit board for RS-232 or RS-485 serial communication. Physical
outputs exist for both RS-232 and RS-485 interfaces; however, only one can be used at any
given time. No configuration is necessary to switch between an RS-232 and RS-485
selection. Additionally, the A1860 ALPHA meter provides a second, independent serial
communication port that supports either RS-232 (see Figure 2-6) or RS-485 (see Figure 2-7).
See Chapter 5, Outputs, for more information on the RS-232 or RS-485 ports.
Figure 2-6. A1860 ALPHA meter with RS-232 as second communication port
Pulse output relay
(optional)
RS-232 connector
RS-485 terminals
RS-232 connector
(optional)*
*Present when optional second communication port is installed
Technical manual 2-5 Product description
Figure 2-7. A1860 ALPHA meter with RS-485 as second communication port
Battery. The terminal block has a battery well and connector for the optional TOU battery.
Cover tamper detection switches. When either the terminal cover or the meter cover is
opened, a detection switch is activated. (See Figure 2-8 for an illustration of the terminal
cover detection switch; the meter cover detection switch is similar.) When either detection
switch is activated, the TC indicator on the LCD turns on and remains on while the cover is
removed. The date and time of the cover removal is logged in the event log. See Event log
on page 2-15 for more information.
Figure 2-8. Terminal cover detection switch
Pulse output relay
(optional)
RS-232
connector
RS-485 terminals
RS-485 connector
(optional)*
*Present when optional second communication port is installed
Cover closed Cover opened
Technical manual 2-6 Product description
Terminal configurations. The A1800 ALPHA meter supports the following terminal
configurations:
10 A transformer-rated (sequential)
10 A transformer-rated (symmetrical)
120 A direct connect-rated (sequential)
120 A direct connect-rated (symmetrical)
1
Communication protocols
The A1800 ALPHA meter supports the ANSI C12 standards for both local and remote
communication.
Additionally, the A1800 ALPHA meter can also support the DLMS standards for both local
and remote communication. When equipped with the optional DLMS communication
support, the meter supports both ANSI C12 and DLMS communication. When establishing
a communication session, the meter automatically determines the protocol being used
and responds in the same protocol.
For series 110 meters and later, DLMS support can be enabled by purchasing the
appropriate Alpha Key and upgrading the A1800 ALPHA meter with the Alpha Keys
support software.
1
See Beginning with Metercat release 2.3, the following features are
supported: on page 1-6 for more information.
For a list of the DLMS OBIS identifiers supported by the A1800 ALPHA meter, see the
A1800 ALPHA meter communication options product guide (PG42-1012).
System architecture
The A1800 ALPHA meter main circuit board contains all the electronics that make up the
meter registers and communication interfaces. See for the meter circuit board block
diagram. The circuit board as shown in contains the following:
meter engine
microcontroller
EEPROM
resistive dividers for the 3 phase voltages
load resistors for the 3 current sensors
power supply
high frequency crystal oscillator
32 kHz low power timekeeping crystal oscillator
optical port components
liquid crystal display (LCD) interface
RS-232 and RS-485 communication interfaces
option board interface
pulse outputs
1
See Elster for availability.
Technical manual 2-7 Product description
Figure 2-9. Meter block diagram
General theory of operation
The A1800 ALPHA meters engine receives analog inputs of voltages and current to
calculate the desired metered quantities. The meter engine samples the input voltages
and current 66 to 88 times per cycle. The actual sampling frequency is based on whether
50 Hz or 60 Hz power systems are being measured.
Using these input signals, the meter engine calculates root mean square (rms) values of
voltage and current, and the meter engine uses the sampled signals to compute Wh, VAh,
and VArh quantities for each phase. These individual phase quantities are summed, and
the totals are transmitted to the microprocessor. The microprocessor processes and stores
the data into memory according to the user-specified program. Once stored, data values
are available to be displayed and communicated as required by the utility or other meter
user.
The very high sampling rate inherent in the meter engine and the additional over sampling
techniques used in the A1800 ALPHA meter results in very high accuracy regardless of
harmonic content, phase angle, or point on the load curve. The meter engine accumulates
and recalculates all quantities after every line cycle. This provides the ability to include the
effect of harmonics up to and beyond the 33
rd
harmonic. Individual harmonics up to and
including the 15
th
harmonic are displayable items and are included in distortion
measurements. Further advanced electronic techniques are used to provide extreme
stability of accuracy over time and over an exceptionally wide range of operating and load
conditions.
The A1800 ALPHA meter can accommodate various tariff structures. The meter also
supports a variety of communication options that allow the meter to be read remotely or
manually. In addition, relays may be used for pulse outputs of user-selected quantities or
for signaling the start of a tariff period.
Pulse
outputs
Wide input
power
supply
5 V linear
power supply
Non
volatile
supply
Precision
reference
Low
power
crystal
Resistive
divider
Resistive
divider
Resistive
divider
Option
connector
Optical
port
Remote
port 1/2
Battery
LCD
Microcontroller
EEPROM Crystal
Meter engine
Clock
varh Rec
varh Del
Wh Rec
Wh Del
C
B
A
2x Line Freq
Power Fail
Phase A voltage
Phase B voltage
Phase C voltage
Current
sensor
Phase A
current
Phase B
current
Phase C
current
Current
sensor
Current
sensor
Technical manual 2-8 Product description
Power supply
Main power supply. Power is supplied to the A1800 ALPHA meter using a wide voltage
range power supply that accepts voltages from 49 V to 528 V AC. At least two lines must
be present to power the meter circuitry. The output from the power supply is then fed to a
low voltage linear regulator to attain the low level voltage.
Auxiliary power supply. The A1800 ALPHA meter may be ordered with an auxiliary
power supply. The auxiliary power supply allows the A1800 ALPHA meter to be powered
by a separate AC or DC power source, such as substations independent power lines.
Should the main power supply be unavailable, the meter will be fully operational provided
the independent power is still available. The A1800 ALPHA meter can also be connected to
both the main power source and auxiliary power source, providing uninterrupted power in
the event that the main power becomes unavailable.
The auxiliary power supply accepts the following voltages:
For independent AC power, from 57 V rms to 240 V rms (nominal)
For independent DC power, from 80 V to 340 V (nominal)
Note: When using independent DC power, the A1800 ALPHA meters auxiliary power
supply is polarity independent. The meter will operate properly without regard to
which wire is positive and which wire is negative.
The output from the independent power supply is then fed to a low voltage linear regulator
to attain the low level voltage.
Current and voltage sensing
Power line currents and voltages are sensed using specialized current sensors and
resistive dividers, respectively. Multiplication and other calculations are performed using a
custom integrated circuit (called the meter engine).
The meter receives each phase current through a precision-wound current sensor that
reduces the line current proportionally. The meter engine samples the individual phase
currents to provide accurate current measurement.
The meter receives each phase voltage through resistive dividers. This ensures that a
linear low level voltage is maintained. It also serves to minimize phase shift over a wide
dynamic range. The meter engine samples the scaled inputs provided by the resistive
dividers to provide accurate voltage measurements.
Meter engine
Multiplication and other calculations are performed using a custom integrated circuit,
called the meter engine. The meter engine contains the digital signal processor (DSP) with
built-in analog-to-digital (A/D) converters capable of sampling each current and voltage
input. The A/D converters measure the voltage and current inputs for a given phase. The
DSP multiplies the signals appropriately, using the factory-programmed calibration
constants.
Microcontroller
The microcontroller performs many different functions, for example:
communicates with the DSP and EEPROM
provides for serial communication over the optical port
provides for serial communication over the remote ports
generates optical output pulses
controls the LCD
controls any option boards
Technical manual 2-9 Product description
The microcontroller and the meter engine communicate with each other constantly to
process voltage and current inputs. When the microcontroller detects a power failure, it
initiates the shutdown and stores billing and status information in EEPROM.
EEPROM
The A1800 ALPHA meter uses electrically erasable programmable read only memory
(EEPROM) for nonvolatile storage of manufacturing data, meter configuration data, and
energy measurement values. The A1800 ALPHA meter is provided with either 128 KB or
256 KB of main board memory. See Style number information on page C-3 for
information regarding how to identify the amount of main board memory on your meter.
The EEPROM provides storage of all information needed to ensure the integrity of the
demand or energy calculations, including the following:
configuration data
billing data
all TOU data
log and profiling data
meter status
constants
energy usage
maximum demand
cumulative demand
Technical manual 2-10 Product description
Billing data
Metered energy and demand quantities
All A1800 ALPHA meters are capable of measuring delivered and received kWh energy
and kW demand. The A1800 ALPHA meters can also measure reactive and apparent
energy and demand. The meter engine samples the voltage and current inputs and sends
these measurements to the microcontroller. In the meter engine, each pulse is equal to
one K
e
defined as one of the following:
secondary rated Wh per pulse
secondary rated varh per pulse
secondary rated VAh per pulse
The following list shows the available metered quantities for the A1800 ALPHA meter. Basic
metered quantities (indicated by * in Table 2-1) can be selected as a source for relay
outputs. The remaining metered quantities are calculated from 2 or more basic metered
quantities.
Average power factor
The A1800 ALPHA meter can calculate the average power factor (AvgPF) using kWh and
kvarh values since the last demand reset.
The meter can store up to two average power calculations, which can be configured in
Elsters meter support software. Average power factor is calculated every second. Upon a
demand reset, the values used in this calculation are set to zero and the AvgPF will be set
to 1.000.
Demand calculations
Demand is the average value of power over a specified time interval. The A1800 ALPHA
meter supports three different methods for demand calculation:
rolling interval
block interval
thermal time constant
An interval is the time over which demand is calculated. The length of a demand interval is
programmable using Elster meter support software, but the value must be evenly divisible
into 60 minutes. Common demand interval lengths are 15 or 30 minutes.
Table 2-1. Metered energy and demand quantities
kVAh delivered (Q1 + Q4)
kVAh Q1
kVAh Q2
kVAh Q3
kVAh Q4
kVAh received (Q2 + Q3)
kVAh sum (delivered + received)
kvarh (Q1 - Q4)
kvarh (Q1 + Q4)*
kvarh (Q2 - Q3)
kvarh (Q2 + Q3)*
kvarh (Q3 - Q2)
kvarh delivered (Q1 + Q2)*
kvarh net
kvarh Q1*
kvarh Q2*
kvarh Q3*
kvarh Q4*
kvarh received (Q3 + Q4)*
kvarh sum (delivered + received)*
kWh delivered*
kWh net
kWh received*
kWh sum*
2 2
kWh h var k
kWh
AvgPF
+
=
Technical manual 2-11 Product description
Rolling interval. Rolling demand interval is defined by two parameters:
the demand interval length - specified in minutes and may be any value that is
evenly divisible into 60
subinterval length - also specified in minutes and may be any value that is evenly
divisible into the interval length
Both of these values are configurable by Elster meter support software. The demand is
calculated at the end of each subinterval, resulting in overlapping demand intervals (or a
rolling demand).
For example, the A1800 ALPHA meter can be configured for a 15-minute demand interval
length and a 5-minute subinterval length. In this case, the demand is calculated every 5
minutes based on the 3 previous subintervals (see Figure 2-10).
Figure 2-10. Rolling demand intervals
The rolling interval calculates demand by using the following equation:
For example, if the demand interval is 15 minutes and the total accumulated energy is
50 kWh, then the demand is 200 kW.
Block interval. Block demand interval is a special case of rolling interval demand in
which the subinterval is the same size as the interval (see Figure 2-11).
Figure 2-11. Block demand intervals
sub-
interval
sub-
interval
sub-
interval
sub-
interval
sub-
interval
5 0 10 15 20 25
Time (minutes)
15-minute interval
15-minute interval
15-minute interval
hours
t
energy d accumulate total
D =
kW 200
h 0.25
kWh 50
D = =
sub-
interval
sub-
interval
sub-
interval
sub-
interval
Time (minutes)
15 30 45 60 0
interval interval interval interval
Technical manual 2-12 Product description
Thermal time constant. The A1800 ALPHA meter can perform thermal demand
emulation. The meter calculates demand based on a logarithmic scale that accurately
emulates thermal demand meters. The thermal demand time constants vary depending
upon the operational mode of the meter.
Normal mode time constant is 15 minutes.
Test mode time constant is 1 minute.
See Operating modes on page 3-7 for more information.
Maximum demand
Maximum demand (also referred to as indicating or peak demand) is the highest demand
value that occurs in a billing period. The demand for each demand interval is calculated
and compared to an earlier maximum demand value. If the new interval demand exceeds
the previous maximum demand, then the new demand is stored as the maximum
demand (see Figure 2-12). When a demand reset occurs, the maximum demand is reset to
zero. The demand for the first full interval after a demand reset becomes the maximum
demand.
Figure 2-12. Maximum demand
In addition to maximum demand, the A1800 ALPHA meter also stores either the
cumulative or continuous cumulative demand. A1800 ALPHA meters can be programmed
to trigger the recording of a coincident demand or power factor (see Coincident demand
or power factor on page 2-13).
Cumulative maximum demand
Using cumulative maximum demand, a demand reset adds the current maximum
demand value to the cumulative maximum demand. This feature is used to calculate the
previous maximum demand when the demand may have had an unauthorized reset.
Since the cumulative demand is not reset to zero, unauthorized demand resets do not
cause a loss of the maximum demand data.
To determine the maximum demand for a billing period after a demand reset, subtract the
previous cumulative demand from the current cumulative demand.
Continuous cumulative maximum demand
Continuous cumulative maximum demand works similarly to cumulative maximum
demand. Continuous cumulative demand, however, is always equal to the sum of the
previous billing period continuous cumulative demand and the current maximum
demand. This feature is used to calculate the previous maximum demand when the
demand may have had an unauthorized reset.
Interval 6
demand
(9.2 kW)
Interval 8
demand
(9.5 kW)
Interval 7
demand
(9.9 kW)
New maximum
demand (9.9 kW)
Earlier maximum
demand (9.9 kW)
Earlier maximum
demand (9.7 kW)
Technical manual 2-13 Product description
Coincident demand or power factor
The number of coincident values that may be captured by the A1800 ALPHA meter
depends on whether or not the 4-quadrant metering (A suffix) option is present.
A1800 ALPHA meters without 4-quadrant metering record 2 coincident values.
A1800 ALPHA meters with 4-quadrant metering record up to 4 coincident values.
Coincident demand refers to a demand value that occurs at the same time as another
demand reaches its peak value. For example, an electric utility may want to record the kvar
demand at the time of a maximum kW demand. This requires that kvar demand be stored
and reported during the same interval as the maximum kW demand.
Similarly, coincident power factor refers to a power factor that occurs at the same time as a
demand value reaches its peak value. For example, an electric utility may want to record
the power factor at the time of a maximum kvar demand. This requires the power factor be
stored and reported during the same interval as the maximum kvar demand.
Demand forgiveness
Demand forgiveness is the time during which demand is not calculated or stored after a
qualified power outage. Demand forgiveness has two programmable settings:
outage time: the number of minutes a power outage must last to qualify for demand
forgiveness (0 to 15 minutes)
time: the number of minutes that demand is not calculated or stored (0 to 255
minutes) following a qualified power outage; zero disables demand forgiveness
Primary and secondary metering
The A1800 ALPHA meter can be programmed for either primary or secondary metering.
When configured for primary metering, the A1800 ALPHA meter internally converts the
measured energy, demand and instrumentation quantities to primary units using the
voltage transformer ratio and the current transformer ratio. These ratios are programmed
using Elster meter support software. The metered quantities reflect energy, demand and
instrumentation on the primary side of the instrument transformers.
When configured for secondary metering, the A1800 ALPHA meter does not use the
voltage transformer ratio or the current transformer ratio to adjust the metered quantities.
The metered quantities reflect the energy, demand and instrumentation on the secondary
side of the instrument transformers even if the voltage and current ratios are programmed
into the meter.
TOU data
All A1800 ALPHA meters store the total (single-rate) data for energy and demand. TOU
meters can store the total data and the data for up to 4 rates. TOU rates can be based on
any combination of day (up to 4 day types), time (up to 132 switch times), or season (up to
12 seasons). The switch points for energy and demand may be configured independently
of each other.
All selected metered quantities are stored according to the TOU rate. The meter stores the
energy, demand, and average power factor for each rate.
2 2
kWh kvarh
kWh
PF Coincident
+
=
Technical manual 2-14 Product description
Power failure data
The A1800 ALPHA meter monitors and records the total power failure data. The following
information is recorded:
cumulative number of minutes of all power failures
start date and time of the most recent power failure
end date and time of the most recent power failure
These values can be programmed to display on the LCD. See Appendix B, Display table,
for more information about displayable items.
See Event log on page 2-15 for information on loss of phase voltage.
Always Positive
The A1800 ALPHA meter can be ordered with the optional Always Positive feature which
records reverse energy as positive energy flow on a phase-by-phase basis. Always
Positive can be used to deter power theft or minimize the effects of improper meter wiring.
The following equation shows how total active power is calculated using theft-resistant
measurement:
Theft-resistant measurement normally applies to registration of active energy. Apparent
energy registers are calculated and signed normally. Instrumentation values, including
+kWh and -kWh, are also signed normally. Therefore, instrumentation can be used to
investigate the meter service wiring, while the theft-resistant measurement guarantees
that active energy is properly registered.
Note: When the Always Positive is enabled and, in the rare situation of extremely poor
power factor, 2-element applications where the phase shift of the first element
exceeds 60 will result in overmeasuring of the first element energy and may
result in incorrect overbilling.
Operation of the LCD energy direction indicators is modified by theftresistant
measurement. With the theftresistant option, the -P arrow is not used. The +P energy
direction indicator is on continuously whenever kWh flow of any direction is detected.
Logs and data sets
All A1800 ALPHA meters are equipped with EEPROM. As shown in Figure 2-13, a small
portion of this main board memory is permanently reserved (called reserved memory) by
the meter to store the main billing and configuration information. The remainder of the
memory (called shared memory) is used to store the following logs and data sets:
event log
history log
self reads
load profiling
instrumentation profiling
TRueQ log
voltage sag log
All of the logs and data sets share the meters memory. Using Elster meter support
software, the sizes of each log or data set can be configured to allow more room for a
different log or data set. For example, self reads can be configured to store less data so
that the load profiling can store more data.
3 2 1 total
P P P P + + =
Technical manual 2-15 Product description
Figure 2-13. Allocation of meter memory
In most cases, the 128 KB or 256 KB option is sufficient to meet data logging and profiling
requirements. In some cases (for example, if extensive instrumentation profiling is desired),
more memory may be required. When the data storage cannot be met with the 256 KB
main memory option, extended memory can be used to add shared memory to the
A1800 ALPHA meter.
Event log
All A1800 ALPHA meters have an event log. The A1800 ALPHA meter stores the date and
time that events occur. Elster meter support software is used to define and program the
number of event log entries that the meter will record. Events that can be included in the
event log are as follows:
power fail start and stop (2 event log entries)
date and time change information (2 event log entries)
date and time of demand resets (1 event log entry)
date and time of event log reset (1 event log entry)
date and time of test mode activity (2 event log entries)
start and stop time when the current TOU rate is overridden by the alternate TOU rate
schedule (2 event log entries)
start and stop time of per phase outage (2 event log entries)
date and time of terminal cover removal (1 event log entry)
date and time of main cover removal (1 event log entry)
Note: The meter will detect and log the removal of either the terminal cover or main cover
even when the meter is not powered (provided the TOU battery is functioning).
After the maximum number of entries has been stored, the meter will begin overwriting
the oldest entries. The event log can be disabled through Elster meter support software.
History log
All A1800 ALPHA meters have a history log that stores table information and procedure ID
for configuration-altering writes to the meter. The A1800 ALPHA meter records a sequential
listing of records, along with the date and time. The meter records this information as an
audit trail, maintaining a history of programming changes made to the meter.
After the maximum number of entries has been stored, the meter will begin overwriting
the oldest entries. The history log can be disabled through Elster meter support software.
Reserved memory**
Main circuit board memory
(128 KB or 256 KB)
IP,*
LP*
Billing data, Configuration
data, Manufacturing info,
etc.
Event,
History,
TRueQ,
Voltage sag
Self read,
LP,*
IP*
Extended memory option board
(1 MB)
Shared memory
*Extended memory used only when requested number of days exceeds the capacity of main
board memory. If meter support software is set to maximize data storage, then the extended
memory option board would always be used for LP and IP data storage.
Notes
**Size of reserved memory is fixed and may vary with each firmware release.
Technical manual 2-16 Product description
Self reads
All A1800 ALPHA meters can support self reads. A self read captures the current period
billing data and stores it in memory. The A1800 ALPHA meter can store up to 35 self reads
can be stored depending on memory requirements for logs, data, etc. This data can be
retrieved later for analysis or billing. If the meter has recorded the maximum number of
self reads, the next self read will overwrite the oldest copy.
Self reads are events that can be triggered by any of the following:
scheduled calendar events
every demand reset
communication procedure
Self reads are different from previous billing data copies. The previous billing data copy
stores only one copy of billing data at a time and only when a demand reset occurs. See
Demand reset data area on page 3-10 for more information.
Load profiling
For meters with load profiling capabilities (designated with an L suffix), the A1800 ALPHA
meter is capable of recording 8 channels of information.
Load profiling has its own, separate interval length that is configured independently from
the demand interval length. The length of the load profiling interval must adhere to the
following rules:
the length must be between 1 and 60 minutes
the time must be evenly divisible into an 60 minutes
Table 2-3 show the number of days of load profiling available. These values are estimates
and may vary depending on the firmware used in the meter.
Data in Table 2-3 are based on the following settings:
load profiling at 15-minute intervals
no instrumentation profiling
the meter is programmed for 6 metered quantities, 2 average power factors, and 4
coincident values
Table 2-2. Load profiling sources
kVAh delivered (Q1 + Q4)
kVAh Q1
kVAh Q2
kVAh Q3
kVAh Q4
kVAh received (Q2 + Q3)
kVAh sum
kvarh (Q1 - Q4)
kvarh (Q1 + Q4)
kvarh (Q2 - Q3)
kvarh (Q2 + Q3)
kvarh (Q3 - Q2)
kvarh delivered (Q1 + Q2)
kvarh net
kvarh Q1
kvarh Q2
kvarh Q3
kvarh Q4
kvarh received (Q3 + Q4)
kvarh sum
kWh delivered
kWh net
kWh received
kWh sum
Technical manual 2-17 Product description
The first number shows the number of days of load profiling, assuming all other logs and
self reads record the maximum number of entries. The second number shows the number
of days of load profiling, assuming all other logs and self reads record the minimum
number of entries.
Note: The actual number of days stores varies based on meter firmware release and
other options programmed using Elster meter support software. See the
documentation for the meter support software for more information regarding
memory allocation.
Load profiling pulse divisor. A pulse divisor is used to scale down the number of pulses
recorded in each load profiling interval. This allows recording of data that may exceed the
maximum number of pulses that can be stored in each load profiling interval (each interval
can store 32,767 pulses before overflowing). The range for the value of the load profiling
pulse divisor is 1 (default) to 255.
Instrumentation profiling
In meters with instrumentation profiling (designated with an N suffix), the meter has two
sets of instrumentation profiling. Each set can record up to 16 channels from the sources
listed in Table 2-4. Also, instrumentation profiling can use the sources listed in Table 2-2 for
more extensive load profiling.
Table 2-3. Estimated days of load profiling storage per number of channels
Days of
storage
(max./min.)
Number of channels
1 2 3 4 5 6 7 8
128 KB 199/320 106/171 81/130 60/96 51/81 41/66 37/59 32/51
256 KB 594/714 317/381 242/291 178/214 151/182 124/149 110/133 95/114
1 MB 3177 1696 1294 954 812 664 592 509
Table 2-4. Instrumentation profiling sources
frequency
per phase current
per phase voltage
per phase watts
per phase VA
per phase voltage angle with respect to line 1 voltage
per phase fundamental (1
st
harmonic) current magnitude
per phase fundamental (1
st
harmonic) voltage magnitude
per phase 2
nd
harmonic current magnitude
per phase 2
nd
harmonic voltage magnitude
per phase voltage % total harmonic distortion (THD)
per phase current % THD
per phase harmonic current (sum of 2
nd
through 15
th
)
per phase current angle with respect to line 1 voltage
per phase vars (vectorial)
per phase 2
nd
harmonic voltage %
per phase total demand distortion (TDD)
per phase PF
per phase PF angle
system watts
system VA (arithmetic)
system PF (arithmetic)
system PF angle (arithmetic)
system vars (vectorial)
system VA (vectorial)
system var (arithmetic)
system PF (vectorial)
system PF angle (vectorial)
Technical manual 2-18 Product description
Each channel can be configured to record the instrumentation profiling using any one of
following four algorithms (see Table 2-5):
Each set of instrumentation profiling has its own, separate interval length that is configured
independently from the demand interval length. The length of the instrumentation profiling
interval must adhere to the following rules:
the length must be between 1 and 60 minutes
the time must be evenly divisible into an 60 minutes
TRueQ Log
The A1800 ALPHA meter has a TRueQ log that records TRueQ test failures. Elster meter
support software is used to define and program the number of TRueQ log entries that the
meter will record. Elster meter support software is also used to define which tests can
record failures in the TRueQ log.
The A1800 ALPHA meter can record the following data associated with the TRueQ test:
the date and time when the TRueQ monitor first detects a qualified failure and the
identifier of the TRueQ test (1 TRueQ log entry)
the date and time when the TRueQ monitor no longer detects a failure and the
identifier of the TRueQ test (1 TRueQ log entry)
Note: See TRueQ event counters and timers on page 4-15 for information on
qualification time
For each TRueQ log entry, the meter also records an instrumentation measurement related
to the TRueQ test.
When the maximum number of entries has been stored, the meter will begin overwriting
the oldest entries.
See TRueQ monitoring on page 4-12 for more information.
Voltage sag log
The meter has a voltage sag log. The A1800 ALPHA meter records the date, time, and
phases of any detected voltage sag. The log records a maximum of 1 entry per second.
When the maximum number of entries has been stored, the meter will begin overwriting
the oldest entries.
See Voltage sags on page 4-13 for more information.
User-defined tables
User defined tables offer specific data retrieval options for A1800 ALPHA meters. User
defined table configuration may be requested at the time of purchase, and the specific
configuration may be programmed at the factory. An AMR system can then be configured
to retrieve the user defined table information from the meter instead of individual table
reads. This reduces the total communications time.
Table 2-5. Instrumentation profiling recording algorithms
Item Description
Minimum The meter samples the selected quantity over the instrumentation
interval. The minimum value of all the samples is recorded.
Maximum The meter samples the selected quantity over the instrumentation
interval. The maximum value of all the samples is recorded.
Average The meter samples the selected quantity over the instrumentation
interval. The average value of all the samples is recorded.
End The meter samples the selected quantity over the instrumentation
interval. The last value of all the samples is recorded.
Technical manual 2-19 Product description
Physical dimensions and mass
The approximate dimensions of the meter correspond to DIN 43-857 part 2 (excluding the
meter hanger).
See the following figures for illustrations of the meter and its dimensions.
Figure 2-14. A1800 ALPHA meter, standard terminal cover
Figure 2-15. A1800 ALPHA meter, short terminal cover
204
22
224*
150
170
307
89
5
*This represents hanger
in center position.
Approximate dimensions in millimeters
213*
224*
22*
150
170
89
240
5
*This represents hanger in
center position
Approximate dimensions in millimeters
Technical manual 2-20 Product description
Figure 2-16. A1800 ALPHA meter, back of meter
Figure 2-17. A1800 ALPHA meter, bottom view (direct connect and transformer rated)
Table 2-6. Approximate mass
Elements Direct connect Transformer rated
2-element 1.6 kilograms 1.3 kilograms
3-element 1.7 kilograms 1.3 kilograms
Approximate dimensions in millimeters.
202
150
170
6.2
5.4
170
10
Approximate dimensions in millimeters.
Direct connect meter Transformer rated meter
Technical manual 3-1 Operating instructions
3 Operating instructions
Indicators and controls
LCD
The liquid crystal display (LCD) is used to display meter data and status information.
Figure 3-1 shows the dimensions of the LCD.
Figure 3-1. LCD dimensions
As shown in Figure 3-2, the LCD is divided into different display regions.
Figure 3-2. LCD regions
P - P +
Q
Q
+
-
7
Approximat e dimensions in mil limet ers
9.5
27
32
77
85
5 2
3.5 1.4
Viewing area
P - P +
Q
Q
+
-
L L L 1 2 3
COM 0 1 2
Error/warning indicator
Energy direction
indicator
Display quantity
Tariff indicators 1 to 8
(left to right)
EOI indicator
LC indicator
Cover removed
indicator
Test mode indicator
Power/energy
units identifier
Comm. port indicator
Alternate mode
indicator
Quantity identifier
Low battery indicator
Phase
indicators (3)
Technical manual 3-2 Operating instructions
The A1800 ALPHA meter can be ordered with a backlight option for the LCD. The LCD can
be illuminated by pressing one of the push buttons, making it easier to read the LCD in no-
light or low-light conditions. The backlight option must be specified at the time of ordering.
See Using the backlight on page 3-6 for more information.
Note: LCD backlight is not available in Read without Power mode.
Quantity identifier. This 7-digit region identifies the displayed quantity as defined and
programmed with Elster meter support software. An identifier can be assigned to most
display quantities in the display sequence. See Appendix B, Display table, for more
information.
Display quantity. This 8-digit display on the LCD shows either metered quantities or other
displayable information, depending upon how the A1800 ALPHA meter has been
programmed.
The displayable digits are definable using Elster meter support software for both energy
and demand readings. From 3 to 8 digits with up to 4 decimal places can be used. These
digits are also used to report error codes for the following error conditions:
operational errors (E1, E2, or E3)
system instrumentation and service test errors (SE)
warnings (W1 or W2)
communication codes (COM 0, COM 1, COM 2)
For instrumentation values and tests, numeric values may be replaced by or mixed with
alphabetic characters to better define the value. See Appendix B, Display table, for more
information.
Phase indicators. Each phase indicator (L1, L2, and L3) corresponds to a line voltage (Line
1, Line 2, and Line 3, respectively) present on the A1800 ALPHA meter connections. The
state of the indicators correspond to the following:
If the indicators are on, then all expected line voltages are present.
If an indicator is blinking, then that expected line voltage is either missing or below
the defined threshold for voltage sag detection.
If an indicator is off, the line is not expected for the configured meter type.
See Voltage sags on page 4-13 for more details on momentary voltage sag detection
and the phase indicators.
Energy direction indicators. The energy direction indicators display the quadrant and
direction of the last Wh (active) and varh (reactive) energy flow. Positive energy flow is
energy delivered to the consumer load, while reverse energy flow is energy received from
the consumer load. Figure 3-3 shows the meaning of each energy direction indicator.
The energy direction indicators turn on to display energy flow direction when any of the
meter phases are measuring energy flow (that is, when one of the line currents is above
the meter starting threshold).
Figure 3-3. Energy direction indicators
Positive reactive energy
Reverse reactive energy
Positive active energy Reverse active energy
Technical manual 3-3 Operating instructions
On meters with the Always Positive option, the +P indicator is on continuously whenever
kWh flow of any direction is detected. The P indicator is inoperative for this meter
configuration (see Always Positive on page 2-14 for more information).
Power/energy units identifier. The power/energy units identifier is used to indicate the
unit of measurement for the quantity displayed on the meters LCD. In some cases, it may
not be possible to represent the displayed quantity using the power/energy units identifier.
If this is the case, then the power/energy units identifier will not be used. Instead, the
quantity will be identified either using the quantity identifier or appending the unit to the
display quantity.
Alternate display indicator. This indicator () displays when the A1800 ALPHA meter is
operating in alternate mode. This indicator also displays during the all segment test of the
LCD.
See Operating modes on page 3-7 for more information on the different operating
modes.
Error indicator. The error indicator flashes when any error condition is present or remains
on if a warning condition is present. When the error indicator is on, the LCD will also
display the appropriate error or warning code. See System service error codes on
page 4-10 and Codes and warnings on page 6-2 for details.
Note: This indicator also turns on during the LCD all-segments test.
Low battery indicator. The low battery indicator is turned on when the TOU battery
voltage is low or when the TOU battery is missing. Additionally, the low battery warning
display item (if included in the display list) also is displayed.
Note: This indicator also turns on during the LCD all-segments test.
Active COM port indicator. The active COM port indicator indicates that a
communication session is in progress and which COM port is being used.
See Communication codes on page 6-8 for additional details.
Display indicators. The 12 display indicators () are used to more precisely identify the
information displayed on the meters LCD.
Note: These identifiers may be shown individually or in combination to describe a
particular displayed quantity.
Note: The manufacturers nameplate details the meaning of the display indicators. See
Appendix C, Nameplate and style number information.
Tariff indicators. The tariff indicators (T1, T2, T3, and T4) indicate the current tariff. If the
displayed quantity is a TOU item (for example, tariff 1 total kWh), the corresponding
indicator (T1) turns on. If the quantitys tariff is active at the time, the tariff indicator flashes.
Note: The active tariff indicators also turns on during the LCD all-segments test.
EOI indicator. The end-of-interval (EOI) indicator is used to verify the timing of the demand
interval. Ten seconds before the end of the demand interval, the EOI indicator will be
turned on and remain on until the end of the interval.
Table 3-1. Port codes
Code Port
COM 0 Optical port
COM 1 Remote port 1
COM 2 Remote port 2
Technical manual 3-4 Operating instructions

For rolling demand, the EOI indicator turns on for 10 seconds before the end of
each subinterval.
Transformer and line loss compensation indicator. The loss compensation (LC) indicator
indicates the meter is currently compensating for transformer and line loss.
Cover tamper indicator. The cover tamper (TC) indicator indicates that either the terminal
cover or the meter cover is removed. This may indicate that tampering has occurred on the
meter. The TC indicator turns off when all the covers are in place. See Cover tamper
detection switches on page 2-5 for additional information.
Test mode indicator. The test (TST) mode indicator indicates that the meter is currently
operating in test mode. See Test mode on page 3-8 for details.
Push buttons
The following push buttons are located on the front of the A1800 ALPHA meter:
RESET (sealable)

If sealed, the RESET button is only accessible after breaking the seal; the button is always
accessible.
If the A1800 ALPHA meter is ordered with the backlight display option, then either the RESET
button or the button can be used to illuminate the display. See Using the backlight on
page 3-6 for more information.
Figure 3-4. A1800 ALPHA meter push buttons
RESET button. To activate the RESET button, it may be necessary to break the seal that
locks the RESET button in the inactive position. After the seal is broken, rotate the push
button 90 in either direction and press the push button (see Figure 3-5). Pressing the
RESET button performs a demand reset (see Demand reset on page 3-10 for a description
on what happens during a demand reset). The RESET button performs differently
depending on the A1800 ALPHA operating mode, as shown in Table 3-2.
Note: If the A1800 ALPHA meter is ordered with the backlight display option, then the
RESET button can be used to illuminate the display. See Using the backlight on
page 3-6 for more information.
* (ALT) button
RESET button
(sealable)
Technical manual 3-5 Operating instructions
To seal the RESET button, rotate the RESET button 90 back to the inactive position and
apply the seal.
Figure 3-5. RESET button positions
Using to lock service. Pressing the RESET button will accept and lock the detected service
when the service test lock mode has been set to manual and the system service voltage
test has just been performed by the A1800 ALPHA meter. See Manual lock on page 4-6
for more details.

Using the RESET button to lock the service will not perform a demand reset
unless it is pressed a second time.
button. Pressing the button normally initiates the alternate mode (see Operating
modes on page 3-7 for more information about the A1800 ALPHA operating modes). The
button performs differently depending on the operating mode, as shown in Table 3-3.
Note: If the A1800 ALPHA meter is ordered with the backlight display option, then the
button can be used to illuminate the display. See Using the backlight on page 3-6
for more information.
Table 3-2. RESET button behavior
Mode Description
Normal Performs a demand reset
Alternate Returns to normal mode and performs a demand reset
Test Resets test value and remains in test mode
Read without
Power
Sets the meter to perform a demand reset immediately on power
restoration
Inactive position
RESET button
cannot be pressed
Active position
RESET button can be pressed
Technical manual 3-6 Operating instructions
Using the backlight. The A1800 ALPHA meter can be ordered with an optional backlight
for the LCD. Once the backlight is turned on, the LCD will be illuminated for two minutes.
Note: The backlight option is not available in Read without Power mode.
To illuminate the LCD, use the following process (see Figure 3-6):
1. Press either the button or the RESET button. The backlight turns on for the specified
illumination time.
2. While the LCD is illuminated, the push buttons will operate as follows:
The RESET button operates as specified in Table 3-2.
The button operates as specified in Table 3-3.
3. The backlight will turn off at the end of the illumination time. Pressing either the
button or the RESET button restarts the process, beginning with step 1.
The A1800 ALPHA meter can be ordered with the backlight always turned on. With this
option, the LCD backlight will always be illuminated, and the RESET and buttons will
operate as specified in Table 3-2 and Table 3-3, respectively.
Table 3-3. button function in different operating modes
Mode Press method Description
Normal Less than 1 second Enters alternate mode, LCD displays one cycle of the alternate display list, and returns
to normal mode.
Alternate Continuous Scrolls quickly through the alternate display list while pressed; locks LCD on a display
quantity when released.
Press and release If the LCD is locked on a display quantity, each press steps to the next quantity in the
alternate display list.
Test Continuous Scrolls quickly through the test mode display list while pressed; locks LCD on a display
quantity when released.
Press and release If the LCD is locked on a display quantity, each press steps to the next quantity in the
test display list.
Read without
Power
Less than 1 second LCD displays once cycle of the alternate display list, and returns to normal display list
Continuous Scrolls quickly through the alternate display list while pressed; locks LCD on a display
quantity when released.
Press and release If the LCD is locked on a display quantity, each press steps to the next quantity in the
alternate display list.
Technical manual 3-7 Operating instructions
Figure 3-6. Using the backlight on the A1800 ALPHA meter LCD (default operating mode)
Operating modes
The A1800 ALPHA meter operates in one of the following modes:
normal mode
alternate mode
test mode
Read without Power mode (optional)
As part of its function, the meter performs self tests to make sure it is operating normally.
The self test ensures that the A1800 ALPHA meter is functioning properly and that its
displayed quantities are accurate. If the self test indicates an error, the LCD displays the
error indicator. In addition, the meter can be programmed to lock the error code on the
display. The meter attempts to function normally, however, the meter data may be suspect.
See Meter self test on page 6-1 for more information on self tests and errors.
Normal mode
Normal mode is the default operation mode for the A1800 ALPHA meter. It is generally
used to display billing data on the LCD. The meter is fully operational in this mode, and it
will process and store data while the LCD scrolls through the normal display list quantities.
The LCD test will always appear immediately after power is connected to the A1800 ALPHA
meter or after a power restoration from an outage.
Backlight off
Any button is
pressed
Backlight on
Button pressed
while LCD lit?
Perform
demand reset
Enter alternate
mode
Has time
expired?
Yes, *
Yes,
RESET
Yes
No
No
Technical manual 3-8 Operating instructions
Typically, the normal mode display cycle begins with an LCD test which turns on all of the
display segments. This is recommended because it provides a quick way to determine if
the LCD is functioning properly. The LCD test can be disabled using Elster meter support
software. The normal display cycle will scroll through all programmed display quantities
before beginning the cycle again.
While in normal mode, the LEDs transmit pulses proportional to metered energy. See LED
pulse outputs on page 5-6 for details on the LEDs.
Alternate mode
Alternate mode can be programmed with Elster meter support software to display a
second set of quantities on the LCD. Alternate mode is most often used for displaying non-
billing data, but it can be programmed to display any of the available quantities. This
mode is activated in one of the following ways:
pressing the button on the A1800 ALPHA meter
after power up for one cycle of the alternate display list
Note: This feature can be disabled using Elsters meter support software.
The meter is fully operational while in alternate mode. While in alternate mode, the
alternate display indicator is turned on. Additionally, the LEDs transmit pulses (see LED
pulse outputs on page 5-6).
There are several different ways to exit alternate mode. Whenever exiting the alternate
mode, the meter returns to normal mode.
Test mode
The A1800 ALPHA meter enters test mode by a command through the optical port. While in
test mode, the test mode indicator (TST) will flash on the meters LCD.
Test mode displays test readings without affecting the present energy usage and billing
data values in the A1800 ALPHA meter. Shorter demand intervals may be used in test
mode to reduce demand test time and will not interfere with billing data.
When normal mode is resumed, readings taken during test mode will be discarded and
present energy usage and billing data values will be restored. The status of the meter
(including billing data, profiling data, errors, and warnings) before the meter entered test
mode is restored.
While in test mode, the optical port transmits test pulses proportional to metered energy
(see LED pulse outputs on page 5-6).
Table 3-4. Exiting alternate mode
Method Description
Wait for the end of the
alternate display list
If the meter is scrolling through the alternate display list
automatically, the meter exits alternate mode after the
last item is displayed.
Press the RESET button Exits alternate mode and performs a demand reset.
Wait for the timeout If the LCD remains on a quantity, the meter exits
alternate mode after 2 minutes of inactivity. If the LCD
remains on a pulse line cumulative counter, the meter
will exit the alternate mode at midnight.
Power failure occurs Exits alternate mode; when power is restored, the
meter's display is in normal mode.
At midnight Exits alternate mode at the next midnight crossing.
Technical manual 3-9 Operating instructions
Test mode is entered using Elster meter support software. The meter exits test mode under
any of the following conditions:
Read without Power mode
The A1800 ALPHA meter may be ordered with the Read without Power feature. When the
Read without Power feature is available, the meters registers can be read during an
outage. Auxiliary power is not available in this mode. The Read without Power option must
be specified at the time of ordering. Read without Power is only available as on option for
A1800 ALPHA meters series 150 and later.
To enter Read without Power mode during an outage, press the button for
approximately 5 seconds. The meter will turn on the LCD and will display the following:
LCD test (even if LCD test is disabled in normal mode)
normal display items in sequence; when the cycle is complete, it restarts at the
beginning of the normal display list
Note: Error codes and warning codes are handled in the same manner as they would be
handled under normal mode.
The meter has limited operational capability while in Read without Power mode. While in
read without mode, only the following items can be performed:
manually reading the LCD
performing a billing read or diagnostic using an optical probe over the optical port
1
manually performing a demand reset by pressing the RESET button (see RESET
button on page 3-4)
displaying the alternate display list by pressing the button (see button on
page 3-5)
Other functions, including data altering communication, meter programming, service tests,
and instrumentation, are not available while the meter is in Read without Power mode. If
an unavailable item is programmed in a display list, the LCD will briefly display dashes (-)
in the display quantity area before scrolling to the next item.
The meter exits Read without Power mode when any of the following actions occur:
power is restored to the meter
the maximum lifetime usage of the Read without Power battery is exceeded
the specified timeout expires
The timeout period can be extended by 30 seconds if the user either presses a button or
starts an optical communication session toward the end of the timeout period. The timeout
period is extended by 30-second increments up to a maximum of twice the specified Read
without Power timeout period.
Table 3-5. Exiting test mode
Method Description
Test mode expires Automatically after a programmable timeout has
expired (between 1 and 255 test mode intervals)
Send an exit command Using Elster meter support software, send an exit
command over the optical port.
Automatically after 24
hours
Automatically after a programmable timeout (1-255 test
mode intervals).
Power failure occurs Exits test mode; when power is restored, the meter's
display is in normal mode.
1
Billing data is always available in Read without Power mode. Data stored in shared memory may not be available while in
Read without Power mode (see Logs and data sets on page 2-14 for more information on shared memory).
Technical manual 3-10 Operating instructions
Demand reset
A demand reset can be performed one of three ways:
pressing the RESET button
issuing a command over the optical or remote ports
as a scheduled calendar event
Regardless of how the demand was reset, the meter performs many different functions,
including the following:
the present billing data is copied to the demand reset data area
the billing datas present maximum demand is added to the cumulative demand,
and then the billing datas present maximum demand is reset to zero
the billing datas dates and times of the maximum demands are reset to zero
the billing datas present coincident values are reset to zero
all demand calculations are reset to zero and a new demand interval is started
previous interval demands are reset to zero
present interval demands are reset to zero
all average power factor calculations are restarted
pulse line cumulative counters are cleared
current conditions for certain errors or warnings are cleared
As a security feature, the meter records these values:
the cumulative number of demand resets (rolls over to zero after 255)
the cumulative number of manual demand resets (pressing the RESET button or
issuing a command)
date and time of last demand reset
1
number of days since the last demand reset
the method of the most recent demand reset (for example, button press, procedure,
or calendar)
if configured, the event log records every demand reset
Demand reset lockout
Through Elster meter support software, a demand reset lockout time can be defined. The
demand reset lockout can remain in effect for up to 255 minutes after a demand reset
(regardless of the method of demand reset). During the demand reset lockout, subsequent
demand resets will be ignored by the meter. This prevents subsequent demand resets (for
example, accidental or tamper-related demand reset presses). If a power failure occurs
during the demand reset lockout period, the lockout is released upon power restoration.
Demand reset data area
In all demand reset occurrences, the meter copies the present billing data and stores it in
the demand reset data area. This data is referred to as the previous billing data because
its general purpose is to preserve the data as one billing period ends and the next billing
period begins. The meter stores only one copy of the previous billing data. The next
demand reset overwrites whatever is currently stored as the previous billing data.
Previous billing data is different from self reads, which can store multiple copies of the
billing data. See Self reads on page 2-16 for more information.
1
If demand reset is set during Read without Power mode, the date and time for the demand reset is identical to the start time of
the most recent power outage.
Technical manual 4-1 Meter tools
4 Meter tools
System instrumentation
System instrumentation is a collection of displayable items designed to assist in evaluating
a service by providing real time analysis of the conditions present at the A1800 ALPHA
installation. Instrumentation quantities should not be confused with billing quantities
because they are intended for an entirely different purpose.
System instrumentation quantities are measured instantaneously while billing quantities
are measured and averaged over a number of minutes. Instrumentation quantities are
generally provided on a per phase basis, while billing quantities represent a combination
of all present phases. This can result in discrepancies between similar billing and
instrumentation data, and this is to be expected.
The instrumentation measurements are near instantaneous. Using Elster meter support
software, instrumentation quantities may be placed in normal, alternate, or test mode
display sequences. The alternate mode display sequence is recommended because it is
generally not necessary for these quantities to be displayed at all times.
Most instrumentation quantities are true root mean square (rms) measurements over an
even number of line cycles, but others are compound quantities. Compound quantities
require multiple measurements at slightly different times with the results calculated from
these multiple measurements. Instrumentation quantities can also round or restrict the
quantity to a desirable value under certain system conditions. See Table 4-1 for more
information about how the instrumentation quantities are obtained.The quantities that are
indicated by a footnote are updated about every second; the remaining quantities are
updated about every 5 seconds.
Table 4-1. Description of system instrumentation quantities
Instrumentation quantity Description
Frequency
1
Measured on line 1 voltage.
System kW The signed sum of the kW measurement on each phase taken only moments
apart
System kVA (arithmetic) The signed sum of the kVA measurement on each phase taken only
moments apart
System kvar (arithmetic) Calculated using the following equation:
System power factor (arithmetic) System kW divided by system kVA (arithmetic)
System power factor angle (arithmetic) The arccosine of system power factor (arithmetic)
Phase kW and kVA
1
Measured directly by meter engine
Phase kvar (vectorial)
1
Calculated using the following equation (where kVA and kW are measured
simultaneously):
The result is then signed based on the kvar direction.
System kvar (vectorial) Sum of the per phase kvar (vectorial)
2 2
arith
kW) (system - ) kVA (system kvar =
2 2
kW - kVA kvar =
Technical manual 4-2 Meter tools
System kVA (vectorial) Calculated using the following equation:
System power factor (vectorial) System kW divided by system kVA (vectorial)
System power factor angle (vectorial) The arccosine of system power factor (vectorial)
Phase voltages and currents
1
True rms values measured by meter engine
Phase voltage angle relative to line 1 voltage
1
Each voltage angle is measured relative to line 1 voltage zero crossings and
rounded to 30
Phase current angle relative to line 1 voltage Each current angle is measured relative to line 1 voltage zero crossings
Phase power factor Phase kW divided by phase kVA, both measured simultaneously. Phase
power factor is set to 1.00 if phase current is less than the absolute minimum
current (twice starting amps).
Phase power factor angle
1
The power factor angle is the arccosine of the phase power factor
Phase 1st harmonic (fundamental) voltage
magnitude
The per phase magnitude of the fundamental voltage
Phase 1st harmonic (fundamental) current
magnitude
The per phase magnitude of the fundamental current
Phase 2nd harmonic voltage magnitude The per phase magnitude of the 2nd harmonic voltage
Phase 2nd harmonic current magnitude The per phase magnitude of the 2nd harmonic current
Phase 2nd harmonic voltage percentage Per phase, the 2nd harmonic voltage magnitude divided by the fundamental
voltage magnitude
Phase total harmonic current magnitude Per phase, the square root of the sum of the 2nd - 15th harmonic currents
squared. In other words:
where HC
i
= i
th
harmonic current
Phase total harmonic distortion percentage
(voltage or current)
Calculated by using:
where:
rms represents an unfiltered rms phase voltage or current
fundamental represents the fundamental rms phase voltage or current
Per phase total demand distortion Calculated by using:
where HC
i
represents the i
th
harmonic current.
1
Updated about every 1 second.
Table 4-1. Description of system instrumentation quantities
Instrumentation quantity Description
2
vect
2
vect
) kvar (system kW system kVA + =

=
=
=
15 i
2 i
2
i
HC THC
100
l fundamenta
l fundamenta - rms
THD
2 2
=
amps Maximum
HC
TDD
15 i
2 i
2
i
=
=
=
Technical manual 4-3 Meter tools
Voltage, current, kW, kvar, and kVA instrumentation quantities have an error of less than
0.25 %. Accuracy will diminish as the value of the quantity becomes smaller.
The meters LCD can be programmed with Elsters meter support software to display
primary instrumentation values.

If the LCD remains on an instrumentation quantity while in alternate or test
mode, the displayed instrumentation quantity updates once per second. See
button on page 3-5 for more information on locking the LCD on a desired
quantity.
The quantity identifier gives information about the quantity being displayed on the
A1800 ALPHA meter LCD, as indicated in Table 4-2.
The display quantity will show a measurement and a unit of measure on the A1800 ALPHA
meter LCD. See Figure 4-1 and Figure 4-2 for examples showing system instrumentation
quantities. See Appendix B, Display table, for information about displayable items.
Figure 4-1. Instrumentation line 1 voltage
Table 4-2. System instrumentation quantity identifiers
Quantity identifier Description
L123 System instrumentation measurements
L1 Line 1 measurements
L2 Line 2 measurements
L3 Line 3 measurements
L1 H2-15 Line 1 total harmonic distortion
L2 H2-15 Line 2 total harmonic distortion
L3 H2-15 Line 3 total harmonic distortion
L1 H1 Line 1 1st harmonic
L2 H2 Line 2 1st harmonic
L3 H2 Line 3 1st harmonic
L1 H2 Line 1 2nd harmonic
L2 H2 Line 2 2nd harmonic
L3 H2 Line 3 2nd harmonic
L1 TDD Line 1 total demand distortion
L2 TDD Line 2 total demand distortion
L3 TDD Line 3 total demand distortion
P +
L L L 1 2 3
Technical manual 4-4 Meter tools
Figure 4-2. Instrumentation system kVA
Immediately before displaying a system instrumentation quantity, the meter begins to
measure that quantity. If the result of the instrumentation measurement is not immediately
available, dashes (-) will be shown in the display quantity until the measurement is
complete. See Figure 4-3 and Figure 4-4 for examples of system instrumentation display
quantities while the measurement is in progress and when a result is available.
Figure 4-3. Instrumentation line 2 current in progress
Figure 4-4. Instrumentation line 2 current measurement (secondary)
Figure 4-5. Instrumentation line 2 current measurement (primary)
If an A1800 ALPHA meter is programmed to display a system measurement quantity for a
phase that does not exist (for example, Line 2 on a two-element meter), then that display
quantity will be skipped automatically. This allows different meter types to be programmed
with similar configurations using Elster meter support software.
P +
L L L 1 2 3
P +
L L L 1 2 3
P +
L L L 1 2 3
P +
L L L 1 2 3
Technical manual 4-5 Meter tools
System service tests
System service tests can be performed to determine the validity of the electrical service that
the A1800 ALPHA meter is metering. The system service tests consist of a service voltage
test and a service current test.
Service voltage test
The service voltage test is intended to assist in identifying the following:
incorrectly wired or misapplied voltage transformers
open or missing line fuses
The following are validated by this test:
phase voltages
phase voltage angles
phase rotation
The meter measures each phase voltage and phase voltage angle and attempts to match
the measurements to a stored list of valid services.
If the service voltage test is successful, the validated service is shown on the meters
LCD and the meter will continue to the next display quantity in the sequence.
If the test is not successful, a warning is set. Also, the LCD will indicate a service error
by displaying SE plus a code on the LCD. See System service error codes on page 4-
10 for more information about system service error codes.
The following conditions can cause the service voltage test to fail:
phase voltage angles not within 15 of the expected service phase angles
phase voltage magnitudes not within the tolerance of the nominal service voltages
programmed into the meter with Elster meter support software
System service locking. Once a service voltage test has detected a valid service, it can
be locked into the A1800 ALPHA meter memory. A locked valid service is used as a basis
for future system service tests and TRueQ tests. The following information will be stored in
the meter when the service is locked:
service type identification
nominal service voltage
voltage phase rotation
service voltage and current limits
voltage sag detection threshold
The A1800 ALPHA meter can lock a valid service in either of these ways:
smart autolock
manual lock
To indicate that a service voltage test is complete, the LCD displays the following (an
example is shown in Figure 4-6):
phase rotation (for example, L1-2-3 or L3-2-1)
voltage magnitude (for example, 120 or 240)
service type showing the number of wires and the service type, for example:
1L is a single phase service
3 is a 3-wire delta service
4Y is a 4-wire wye service
Technical manual 4-6 Meter tools
Figure 4-6. Sample service voltage test result
The voltage magnitude and service type are surrounded by brackets to indicate that the
service is locked (see Figure 4-7).
Figure 4-7. Sample display of locked service voltage
Smart autolock. When smart autolock is enabled through Elster meter support software,
the A1800 ALPHA meter will attempt to lock the service automatically once it is determined
to be valid. Both the voltage magnitude and phase angle of the service are compared to a
table of valid relationships stored within the meter memory. The meter accepts the service
that most closely matches one of the stored values in the A1800 ALPHA meter.
The A1800 ALPHA meter periodically checks the service. Under certain conditions, the
smart autolocked service may lock on a different service. This is useful because the meter
may have been moved to a new service. The service voltage test will be performed and the
service may be changed in response to the following events:
power up
exit of test mode
after a data-altering communication session
If a new, valid service is detected, the meter locks on the new service. If a valid service
cannot be detected, the meter responds in the following manner:
the meter remains locked on the last known valid service
the LCD displays an error code
Manual lock. When configured through Elster meter support software for manual lock, the
A1800 ALPHA meter will detect and evaluate the service in the same manner as it does
when autolock is enabled. The identified service information will also be shown on the
LCD; however, the RESET button must be pressed in order to lock the detected service (see
Using to lock service on page 3-5).
When the service type has been detected, the phase rotation, voltage magnitude, and the
service type will be displayed on the LCD. If the RESET button is not pressed to accept the
service, the LCD will alternate between L1-2-3 ------ and the detected service
information until the service has been manually locked.

Once manually locked, the service never unlocks automatically. To move the
A1800 ALPHA meter to a new installation with a different type of service, the
service must be unlocked using Elster meter support software. The new service
type can then be detected and manually locked.
P +
L L L 1 2 3
P +
L L L 1 2 3
Technical manual 4-7 Meter tools
Initiating service voltage tests. When enabled, the service voltage test is initiated at any
of the following times:
after power up, a data-altering communications session, or exiting test mode
at midnight
Service voltage tests can also be initiated at any of these times, depending on meter
configuration:
as a display item
as a TRueQ test (for meters with TRueQ capabilities)
The behavior of the service voltage test depends on these factors:
the event that initiates the service voltage test
the state of the service lock
After power up, data-altering communications session, or exiting test mode. The following
table explains meter behavior when the service voltage test is performed after any of the
following:
power is applied to the meter
data-altering communications session
exiting test mode
If the service voltage test is interrupted (for example, the button is pressed or there is a
communications session), the meter restarts the service voltage test after handling the
interruption.
Smart autolock
Manual lock
Current state is locked
Manual lock
Current state is unlocked
1 The meter initiates the service voltage
test.
2 The meter attempts to detect a valid
service.
If a valid service is detected, the
meter automatically locks on the
detected service. The LCD displays
the locked valid service.
If a valid service cannot be found,
the meter displays SE 555000.
The meter restarts the service
voltage test in diagnostic mode
(see Restarting the service voltage
test in diagnostic mode on
page 4-9). However, the meter
remains locked on the last valid
service until a new valid service is
detected.
1 The meter initiates the service voltage
test.
2 The phase indicator voltage threshold
levels are based on the currently
locked service.
3 The meter attempts to match the
service.
If the service matches the presently
locked service, then the LCD
displays the locked valid service.
If the service does not match the
presently locked service, then the
LCD displays the service test error.
The meter restarts the service
voltage test in diagnostic mode
(see Restarting the service voltage
test in diagnostic mode on
page 4-9).
1 The meter initiates the service voltage
test.
2 The phase indicator voltage
thresholds are set at the default
values.
3 The meter attempts to detect a valid
service.
If a valid service is found, the LCD
displays the data for the service it
detected.
If a valid service is not found, the
LCD displays SE 555000. The
meter restarts the service voltage
test until a valid service is found.
4 While a valid service is displayed, the
user can manually lock the service.
The user presses the RESET button
to lock the service. The LCD displays
the locked service.
If the user does not lock the service,
the meter returns to the service test
until a valid service is found and
locked.
Technical manual 4-8 Meter tools
At midnight. If the service is locked, the meter checks the service at midnight. The meter
always does the following when the service voltage test is run at midnight:
If the service test is interrupted (for example, the button is pressed or there is a
communications session), the meter restarts the service test after handling the interruption.
If the service has not been locked, the test is not performed and the LCD displays
SE 555000.
As a display item in a display sequence. Using Elster meter support software, the service
voltage test can be programmed as a displayable quantity in any display sequence. The
service test is initiated when the service test quantity is displayed on the LCD.
As a TRueQ test. When the service voltage test is programmed as a TRueQ test, the service
test is performed only if the service is locked. TRueQ tests are available only on meters with
TRueQ capabilities. See Service voltage test on page 4-5 for more information.
Smart autolock
Manual lock
Current state is locked
1 The meter initiates the service test.
2 The phase indicator voltage threshold
levels are based on the currently locked
service.
3 The meter attempts to match the service.
If the service matches the presently
locked service, then the LCD displays
the locked valid service.
If the service does not match the
presently locked service, then the LCD
displays SE 555000. The meter
restarts the service voltage test in
diagnostic mode (see Restarting the
service voltage test in diagnostic
mode on page 4-9). However, the
lock remains on the last valid service
until a new valid service is detected.
1 The meter initiates the service test.
2 The phase indicator voltage threshold
levels are based on the currently locked
service.
3 The meter attempts to match the service.
If the service matches the presently
locked service, then the LCD displays
the locked valid service.
If the service does not match the
presently locked service, then the LCD
displays a service test error. The meter
restarts the service voltage test in
diagnostic mode (see Restarting the
service voltage test in diagnostic
mode on page 4-9). However, the
lock remains on the last valid service
until a new valid service is detected.
Smart autolock
Manual lock
Current state is locked
Service locking disabled
1 The meter initiates the service test.
2 The meter attempts to match the
service.
If the service detected matches the
presently locked service, then the
LCD displays the locked valid
service.
If the service does not match the
presently locked service, then the
LCD displays a service test error.
3 After the LCD displays the locked valid
service or the service test error, the
LCD continues to the next item in the
display sequence.
The service test is performed as the
autolock.
1 The meter initiates the service test.
If a valid service is detected, the
LCD displays the valid service.
If a valid service cannot be found,
the meter displays SE 555000.
2 After the LCD displays the valid service
or the service test error, the LCD
continues to the next item in the
display sequence.
Technical manual 4-9 Meter tools
Restarting the service voltage test in diagnostic mode. Depending on how the
service voltage test was started, the test restarts in diagnostic mode if the test fails. The
A1800 ALPHA meter uses the diagnostic mode if the service voltage test was started in
these ways:
after power up, data-altering communications session, or exiting test mode
at midnight
The diagnostic mode cycles through performing the service voltage test and displaying
information about the service that may be useful in determining why the test failed, as
listed below:
1. Perform the service voltage test.
2. Display line 1 voltage.
3. Perform the service voltage test.
4. Display line 2 voltage.
5. Perform service voltage test.
6. Display line 3 voltage.
7. Perform service voltage test.
8. Display line 2 voltage angle.
9. Perform service voltage test.
10. Display line 3 voltage angle.
If at any point a valid service is found and locked, the meter displays the locked service on
the LCD and continues to the next item in the display sequence. Otherwise, the cycle
restarts at step 1.
Service current test
The service current test validates system currents and is intended to assist in identifying the
following:
incorrectly wired or misapplied current transformers
open or missing load-side fuses
If the service current test is successful, L1-2-3 OK is shown on the A1800 ALPHA meter
LCD. The meter will continue to the next item in the display sequence. See Figure 4-8 for an
example of a successful service current test.
Figure 4-8. Service current test successful completion
If the test is not successful, a warning is set. Also, the LCD will indicate a service error by
displaying SE and a code, an example of which is shown in Figure 4-9. See System service
error codes on page 4-10 for more information. The following conditions can cause the
service current test to fail:
current remains on one phase while no current is on any other phase
current on any single phase is below the programmed low current limit
current on any phase is greater than the programmed absolute maximum
current is negative on any phase (reverse power)
power factor on any phase is less than the limit set for leading or lagging power
factor
P +
L L L 1 2 3
Technical manual 4-10 Meter tools
If all phases are below the absolute minimum current threshold, the low and missing
current failure will not be reported. It is assumed that this is a valid, no-load condition. In
this case, the low and zero current warnings will display if the condition exists.
Figure 4-9. Service current test error
Initiating the service current test. The service current test can be initiated in any of the
following ways:
the service current test may be placed in any display sequence. The service current
test will be performed when the quantity is displayed in the display sequence.
the service current test may be included in the TRueQ tests if the A1800 ALPHA meter
is equipped with this feature. The results of the TRueQ test will not be seen on the
LCD. See TRueQ monitoring on page 4-12 for more details on TRueQ.
the service current test may be programmed to be performed after successful
service voltage tests that perform automatically (but not as part of a display list)
If the A1800 ALPHA meter does not have a locked service, then the system service current
test will be skipped regardless of how the test is initiated.
Parameters regarding the system service current tests can be changed without requiring
the meter to be unlocked and then relocked or requiring the meter to be reset. These
parameters (configurable with Elster meter support software) include the following:
enable or disable per phase reverse power tests
absolute minimum current
per phase low currents
absolute maximum current
per phase leading and lagging power factor limits
System service error codes
When SE is shown on the LCD, the displayed quantity is a numeric code representing a
system service error. This indicates that there is a service problem detected by the
A1800 ALPHA meter. Table 4-3 and Table 4-4 show all possible system service error codes.
Table 4-3. System service voltage test error codes
Service error condition (SE)
Error code
Voltage phase
L1 L2 L3
Low nominal voltage on line 1 1 0 0 0 0 0
Low nominal voltage on line 2 0 1 0 0 0 0
Low nominal voltage on line 3 0 0 1 0 0 0
High nominal voltage on line 1 2 0 0 0 0 0
High nominal voltage on line 2 0 2 0 0 0 0
High nominal voltage on line 3 0 0 2 0 0 0
Unrecognized service 5 5 5 0 0 0
P +
L L L 1 2 3
Technical manual 4-11 Meter tools
Bad phase angle on line 1 8 0 0 0 0 0
Bad phase angle on line 2 0 8 0 0 0 0
Bad phase angle on line 3 0 0 8 0 0 0
Low voltage & bad phase angle on line 1 9 0 0 0 0 0
Low voltage & bad phase angle on line 2 0 9 0 0 0 0
Low voltage & bad phase angle on line 3 0 0 9 0 0 0
High voltage & bad phase angle on line 1 A 0 0 0 0 0
High voltage & bad phase angle on line 2 0 A 0 0 0 0
High voltage & bad phase angle on line 3 0 0 A 0 0 0
Table 4-4. System service current test error codes
Service error condition (SE)
Error code
Current phase
L1 L2 L3
Missing line 1 current 0 0 0 1 0 0
Missing line 2 current 0 0 0 0 1 0
Missing line 3 current 0 0 0 0 0 1
Low line 1 current 0 0 0 2 0 0
Low line 2 current 0 0 0 0 2 0
Low line 3 current 0 0 0 0 0 2
Missing and low current on line 1 0 0 0 3 0 0
Missing and low current on line 2 0 0 0 0 3 0
Missing and low current on line 3 0 0 0 0 0 3
Low PF on line 1 0 0 0 4 0 0
Low PF on line 2 0 0 0 0 4 0
Low PF on line 3 0 0 0 0 0 4
Reverse power on line 1 0 0 0 5 0 0
Reverse power on line 2 0 0 0 0 5 0
Reverse power on line 3 0 0 0 0 0 5
Low PF & low current on line 1 0 0 0 6 0 0
Low PF & low current on line 2 0 0 0 0 6 0
Low PF & low current on line 3 0 0 0 0 0 6
Reverse power & low current on line 1 0 0 0 7 0 0
Reverse power & low current on line 2 0 0 0 0 7 0
Reverse power & low current on line 3 0 0 0 0 0 7
Excess current on line 1 current 0 0 0 8 0 0
Table 4-3. System service voltage test error codes
Service error condition (SE)
Error code
Voltage phase
L1 L2 L3
Technical manual 4-12 Meter tools
If service current errors are present on more than one phase, a single error code is
displayed to represent all detected errors. For example, SE 000308 indicates missing
current on line 1 and excess current on line 3.
TRueQ monitoring
All A1800 ALPHA meters are equipped with the tamper restraint and quality (TRueQ)
monitoring features that can monitor circuit parameters on a cyclic basis, 24 hours a day
throughout the billing period. TRueQ tests may be turned on or off through Elster meter
support software.
TRueQ tests will recognize any deviation beyond the thresholds. When shipped, the meter
is stored with default values for the thresholds. Using Elster meter support software, these
thresholds can be edited.
Most TRueQ tests are performed individually so that circuit parameters are not being
monitored continuously. Each subsequent test will begin immediately after the previous
one has ended. The momentary voltage sag test, however, uses the per phase rms
voltage calculation which is part of the voltage sensing process within the meter engine.
The rms voltages are calculated once every 2 line cycles, so the momentary voltage sag
test is capable of recognizing any phase voltage deviation that remains below a specified
threshold for as few as 2 line cycles.
TRueQ timing
In addition to defining thresholds for each test, a minimum time may also be defined. Once
the monitored parameter falls outside the threshold and remains there longer than the
minimum time, the failure will be stored and the cumulative count will increment by one. A
cumulative timer will also be activated and will run for as long as the event is detected. The
cumulative count and timer for each test can be retrieved through Elster meter support
software.
TRueQ display items
The meter can be programmed to display a warning code on the LCD when a TRueQ test
fails. Warning codes can be enabled or disabled on a test-by-test basis using Elster meter
support software.
TRueQ and relays
If one or more relays are installed in the A1800 ALPHA meter, the relay can be
programmed to close when the failure occurs. When a failure condition is no long present,
the warning code will automatically clear; and any relays will open.
Excess current on line 2 current 0 0 0 0 8 0
Excess current on line 3 current 0 0 0 0 0 8
Excess current & low PF on line 1 0 0 0 C 0 0
Excess current & low PF on line 2 0 0 0 0 C 0
Excess current & low PF on line 3 0 0 0 0 0 C
Excess current & reverse power on line 1 0 0 0 d 0 0
Excess current & reverse power on line 2 0 0 0 0 d 0
Excess current & reverse power on line 3 0 0 0 0 0 d
Table 4-4. System service current test error codes
Service error condition (SE)
Error code
Current phase
L1 L2 L3
Technical manual 4-13 Meter tools
TRueQ log
All A1800 ALPHA meters record TRueQ events in the TRueQ log. Meters with TOU capability
will also record the date and time of any TRueQ failure in the TRueQ log. See TRueQ Log
on page 2-18 for more information about the TRueQ log.

A qualified TRueQ failure causes the W2 020000 warning code to be shown on
the LCD. See W2 020000: TRueQ test failure warning on page 6-7 for more
details.
Voltage sags
A momentary sag in voltage can reset process control equipment and computer systems.
The momentary voltage sag monitor watches for decreases in voltage that last for a
measured number of cycles. This monitor can detect any voltage decrease that falls below
a programmed threshold for as few as 2 line cycles. Threshold and duration are defined
using Elster meter support software.
The voltage sag threshold is defined as a percentage of the lowest nominal per phase
voltage and recommended to be in the range of 60 % to 99.9 %.
A sag is defined as a drop in phase voltage below the threshold for a duration greater
than the sag minimum time and less than the sag maximum time. If the condition exceeds
the maximum sag time, it will not be considered a sag event. The sag times can be
configured to a resolution of 8 milliseconds. The minimum time range can be from 32
milliseconds to 2.04 seconds. The maximum time range can be a time up to 546 seconds.
The potential indicators on the A1800 ALPHA meter LCD will indicate when voltage is below
the sag level threshold. When a phase voltage drops below the voltage sag threshold, the
corresponding potential indicator will blink.
Voltage sag counter and timer. Each phase voltage has a voltage sag counter and
timer associated with it. Each counter can accumulate up to 65,535 before rolling over to
zero. Each cumulative timer can record time for 414 days.
A voltage sag event is only counted if the voltage remains below the voltage sag threshold
for more than the minimum time and less than the maximum time. A voltage that remains
below the voltage sag threshold for longer than the maximum time is considered to be a
low voltage condition, and it is not counted by the momentary voltage sag monitor.
The counter and timer for each phase are maintained within the A1800 ALPHA meter
memory. These values can be reported and can be reset through Elster meter support
software.
See Voltage sag log on page 2-18 for more information about the log of momentary
voltage sag events.
TRueQ tests
TRueQ tests do not interfere with any meter functions related to energy measurement.
These tests run separately from the metering functions. Table 4-5 shows the available tests
for TRueQ, along with their description.
Table 4-5. TRueQ tests
TRueQ Test name Configuration based upon
Test 1 Service voltage test System service voltage test thresholds
Test 2 Low voltage test A specified low voltage threshold
Test 3 High voltage test A specified high voltage threshold
Technical manual 4-14 Meter tools
The following TRueQ tests are available on all A1800 ALPHA meters programmed with
Metercat release 2.3 or later:
Test 4 Reverse power test & PF Service current test thresholds
Test 5 Low current test Service current test thresholds
Test 6 Power factor (PF) A specified threshold for leading and
lagging
Test 7 Second harmonic current test A specified current threshold
Test 8 % Total harmonic distortion
(THD) current
Specified THD percentage
Test 9 % Total harmonic distortion
voltage
Specified THD percentage
Test 10 Voltage imbalance Minimum high voltage threshold and
imbalance threshold
Test 11 Current imbalance Minimum high current threshold and
imbalance threshold
Test 12 % total demand distortion
(TDD)
Specified TDD percentage
Table 4-6. Enhanced TRueQ tests
TRueQ Test name Configuration based upon
Test 13 Low voltage (Line 1) Specified low voltage threshold
Test 14 Low voltage (Line 2) Specified low voltage threshold
Test 15 Low voltage (Line 3) Specified low voltage threshold
Test 16 High voltage (Line 1) Specified high voltage threshold
Test 17 High voltage (Line 2) Specified high voltage threshold
Test 18 High voltage (Line 3) Specified high voltage threshold
Test 19 Low voltage and current
present (Line 1)
Specified thresholds for low voltage and
high current
Test 20 Low voltage and current
present (Line 2)
Specified thresholds for low voltage and
high current
Test 21 Low voltage and current
present (Line 3)
Specified thresholds for low voltage and
high current
Test 22 Current missing (Line 1) Specified thresholds for voltage and
current
Test 23 Current missing (Line 2) Specified thresholds for voltage and
current
Test 24 Current missing (Line 3) Specified thresholds for voltage and
current
Table 4-5. TRueQ tests
TRueQ Test name Configuration based upon
Technical manual 4-15 Meter tools

During the low current and reverse power and power factor tests, there will be
no event detected if all measured line currents drop below the absolute
minimum current threshold. An event will be detected if any single phase or two
phases drop below the programmed threshold for the qualification time. This
eliminates false detection when the load is dramatically reduced or turned off.
TRueQ event counters and timers. Each TRueQ test has its own event counter
associated with it. Each counter can accumulate to a maximum of 65,535 before rolling
over to zero. For each TRueQ test, an event occurring on one phase or across multiple
phases is counted as a single event. The momentary voltage sag monitor, however,
records counters and timers for each phase. See Voltage sag counter and timer on
page 4-13 for details.
The cumulative timer for each monitor can record time over 20 years. To increase the
cumulative counter or timer, the TRueQ test must fail for a period greater than the
qualification time. The cumulative timer includes the qualification time for the test (see
Figure 4-10). The qualification time is defined as zero to 60 minutes where zero causes the
event to be recognized immediately as it is detected.
Figure 4-10. Total TRueQ test failure time
An event ends when the condition is no longer present. If an event occurs but does not last
for the qualification time, then neither the counter nor timer will reflect the event having
occurred.
The counter and timer for each monitor are maintained within the A1800 ALPHA meter
memory. These values can be reported and can be reset through Elster meter support
software.
Time recorded by
meter
TRueQ
failure
Qualification
time
Remaining
time
Technical manual 4-16 Meter tools
Test 1 Name Service voltage test
Formula
Variable Based on service test thresholds
Default value Based on service test thresholds
Configuration based on System service voltage test thresholds
Description This test continually monitors service voltage. Voltage fluctuations outside the programmed limits are detected
and can indicate one of the following:
improper voltage transformer operation
inappropriate transformer tap settings
equipment failure
All voltage magnitudes and phase angles must fall within the thresholds for the locked service. The thresholds
are defined by the service voltage configuration. Programming the service voltage as a TRueQ test allows it to
continually run and create a log of the results.
Stored value None
Test 2 Name Low voltage test
Formula
Variable 0 % to 99.9 %
Default value 94.0 %
Configuration based on A specified low voltage threshold
Description This test checks the per phase voltages for values that fall below a specified limit. Each phase threshold can be
set individually and can be set at a value higher or lower than the limits selected for the service voltage test.
This allows a more thorough study of the voltage changes.
The threshold is defined as a percentage of the expected per phase nominal voltage (recommended to be in
the range of 60 % to 99.9 %). The percentage for each phase can be individually defined. The test fails if any
phase voltage exceeds the threshold.
Stored value Line 1 voltage (even if line 2 or line 3 causes the test to fail)
Test 3 Name High voltage test
Formula
Variable 100.1 % to 200.0 %
Default value 106.0 %
Configuration based on A specified high voltage threshold
Description This test checks the per phase voltages for values that exceed a specific limit. The threshold values can be set
at a value higher or lower than the limits selected for the service voltage test. This allows a more thorough
study of the voltage changes.
The threshold is defined as a percentage of the expected per phase nominal value. The percentage for each
phase can be individually defined. the test fails if any phase voltage exceeds the threshold.
Stored value Line 1 voltage (even if line 2 or line 3 causes the test to fail)
threshold voltage low Specified ) V or V or (V
L3 L2 L1

threshold voltage low Specified ) V or V or (V
L3 L2 L1

threshold voltage high Specified ) V or V or (V
L3 L2 L1

Technical manual 4-17 Meter tools
Test 4 Name Reverse power test and power factor test
Formula
Variable Based on service test thresholds
Default value Based on service test thresholds
Configuration based on Service current test thresholds
Description This test recognizes any condition where the current transformer may be wired incorrectly or where may
tampering may have occurred. The power factor (PF) threshold in this test is typically set to a very low value to
detect only abnormal conditions.
The PF thresholds are defined with the system service current test definition. Using the service current test
definition permits independent PF settings to be set for each service type. Each service type can have
individual leading and lagging thresholds.
Testing for reverse power can only be enabled or disabled for all phases simultaneously.
Stored value None
Test 5 Name Low current test
Formula
Variable Based on service test thresholds
Default value Based on service test thresholds
Configuration based on Service current test thresholds
Description This test checks the service current for values that fall below a specified limit. This test will check for erroneous
operation or failure of a current transformer and can detect signs of meter tampering. If all phase currents fall
below the limit on an initial no-load or test condition, then no warning or indication will be provided. A warning
will be issued when one or more phase currents fall below the threshold value for the qualification time while
the remaining phase currents stay above the limits.
This threshold is defined as a percentage of the A1800 ALPHA meter Class ampere rating from the system
service test definition. This percentage is applied on a per phase basis. The thresholds are defined by the
service current configuration.
Stored value None
Test 6 Name Power factor test
Formula
Variable 0.00 to 1.00 for minimum leading power factor (per phase)
0.00 to 1.00 for minimum lagging power factor (per phase)
Default value 0.20 for minimum leading power factor (per phase)
0.20 for minimum lagging power factor (per phase)
Configuration based on Specified thresholds for leading and lagging power factors
Description This test checks the power factor for any deviation beyond the programmed threshold. This monitor may be
used alone to monitor rate-based conditions or in conjunction with the reverse power test and PF monitor to
provide a more thorough analysis of power factor fluctuations.
The leading and lagging thresholds are individually defined for each phase. These settings may be different
than those defined in the service current configuration.
Stored value None
threshold current low Specified ) I or I or (I
L3 L2 L1

Technical manual 4-18 Meter tools
Test 7 Name Second harmonic current test
Formula
Variable 0.00 % to 100.00 %
Default value Transformer-rated: 2.50 % of Class amps (per phase)
Self-contained: 1.25 % of Class amps (per phase)
Configuration based on A specified current threshold
Description This test checks for the presence of second harmonic current. The second harmonic current may be created by
equipment on the line or may indicate the presence of DC on the system. The threshold is defined as values in
AC amperes according to the meter class. The test fails if any phase exceeds the threshold.
To prevent the monitor from creating a false alarm from legitimate second harmonic current sources, the
recommended qualification time is 15 minutes.
Stored value Line 1 second harmonic magnitude (even if line 2 or line 3 causes the test to fail)
Test 8 Name % total harmonic distortion current test
Formula
Variable 0.0 % to 99.9 % of the fundamental current
Default value 30.0 % of the fundamental current (per phase)
Configuration based on A specified THD percentage
Description As the load on electrical systems becomes more saturated with electronic control devices (such as computers
and communications systems), there is a growing concern with the harmonics that these devices can
contribute to the electrical system. Total harmonic distortion, expressed as a percentage of the fundamental, is
measurement of the power quality of the circuit under these conditions.
The total harmonic distortion current test measures the per phase THD current and can alert the utility to
conditions that may be harmful or dangerous to the system or other equipment. The threshold is defined as a
percentage of the fundamental. The thresholds are defined by the service voltage configuration. The test
phases if any phase exceeds the threshold.
Stored value Line 1 THD (even if line 2 or line 3 causes the test to fail)
Test 9 Name % total harmonic distortion voltage test
Formula
Variable 00.0% to 99.9 % of the fundamental voltage
Default value 30.0 % of the fundamental voltage (per phase)
Configuration based on A specified THD percentage
Description As the load on electrical systems becomes more saturated with electronic control devices (such as computers
and communications systems), there is a growing concern with the harmonics that these devices can
contribute to the electrical system. Total harmonic distortion, expressed as a percentage of the fundamental, is
a measurement of the power quality of the circuit under these conditions.
The total harmonic distortion voltage test measures per phase THD voltage and can alert the utility to
conditions that may be harmful or dangerous to the system or other equipment. The threshold is defined as a
percentage of the fundamental. The thresholds are defined by the service voltage configuration. The test fails if
any phase exceeds the threshold.
Stored value Line 1 THD voltage (even if line 2 or line 3 causes the test to fail)
threshold magnitue current harmonic 2 current harmonic 2
nd nd

Technical manual 4-19 Meter tools


Test 10 Name Voltage imbalance test
Formula
Variable Minimum voltage threshold: 0.00 % to 100.00 % of the nominal
Imbalance threshold: 0.00 % to 100.00 %
Default value Minimum voltage threshold: 80.00 % of the nominal
Imbalance threshold: 90.00 %
Configuration based on Minimum high voltage threshold and imbalance threshold
Description This test checks for an imbalance between phase voltages. The test first measures and normalizes each per
phase voltage. The voltages are normalized to account for different per phase nominal voltages as specified
by the locked service. To qualify as a failure, both the following conditions must exist:
The highest normalized per phase voltage must be greater than the minimum voltage threshold
The ratio of the lowest normalized per phase voltage to the highest (low/high) must be less than the
imbalance threshold
Using Elster meter support software, the minimum voltage threshold is defined as a percentage of the
nominal voltage, and the imbalance threshold is a fraction (0 to 1).
Stored value None
Test 11 Name Current imbalance test
Formula
Variable Minimum current threshold: 0.00 % to 100.00 % of Class amperes
Imbalance threshold: 0.00 % to 100.00 %
Default value Minimum current threshold: 1.25 % of the Class amperes
Imbalance threshold: 5.00 %
Configuration based on Minimum high current threshold and imbalance threshold
Description This test checks for an imbalance between phase currents. To qualify as a failure, both the following must
exist:
The highest per phase current must be greater than the minimum current threshold
The ratio between the lowest per phase current to the highest (low/high) must be less than the imbalance
threshold
Using Elster meter support software, the minimum current threshold is defined as a percentage of Class
amperes, and the imbalance threshold is a fraction (0 to 1).
Stored value None
threshold imbalance
voltage phase per highest
voltage phase per lowest
and threshold voltage minimum ) V or V or (V
L3 L2 L1
<
>
threshold imbalance
current phase per highest
current phase per lowest
and threshold current minimum ) I or I or (I
L3 L2 L1
<
<
Technical manual 4-20 Meter tools
Test 12 Name Total demand distortion
Formula
Variable 0.00 % to 100.00 % of the class amperes (per phase)
Default value 10.00 % of the Class amperes
Configuration based on Specified TDD threshold
Description This test checks the per phase total demand distortion (TDD) and makes sure that the TDD is less than the
threshold. TDD measures the harmonic current distortion on each phase in percentage of the maximum
demand load current (Class amperes).
Stored value Line 1 % TDD (even if it is line 2 or line 3 that causes the test to fail)
Test 13 Name Low voltage (Line 1)
Formula
Variable 0.0 % to 99.9 % of nominal
Default value 60.0 %
Configuration based on A specified voltage threshold
Description This test checks Line 1 voltage for values that fall below a specified limit. The threshold is defined as a
percentage of the expected Line 1 nominal voltage. The test fails if Line 1 voltage falls below the voltage
threshold.
Stored value Line 1 voltage
Test 14 Name Low voltage (Line 2)
Formula
Variable 0.0 % to 99.9 % of nominal
Default value 60.0 %
Configuration based on A specified voltage threshold
Description This test checks Line 2 voltage for values that fall below a specified limit. The threshold is defined as a
percentage of the expected Line 2 nominal voltage. The test fails if Line 2 voltage falls below the voltage
threshold.
Stored value Line 2 voltage
threshold TDD >
threshold voltage Specified V
1 L
<
threshold voltage Specified V
2 L
<
Technical manual 4-21 Meter tools
Test 15 Name Low voltage (Line 3)
Formula
Variable 0.0 % to 99.9 % of nominal
Default value 60.0 %
Configuration based on A specified voltage threshold
Description This test checks Line 3 voltage for values that fall below a specified limit. The threshold is defined as a
percentage of the expected Line 3 nominal voltage. The test fails if Line 3 voltage falls below the voltage
threshold.
Stored value Line 3 voltage
Test 16 Name High voltage (Line 1)
Formula
Variable 100.1 % to 200.0 % of nominal
Default value 115.0 %
Configuration based on A specified voltage threshold
Description This test checks Line 1 voltage for values that exceed a specified limit. The threshold is defined as a percentage
of the expected Line 1 nominal voltage. The test fails if Line 1 voltage exceeds the voltage threshold.
Stored value Line 1 voltage
Test 17 Name High voltage (Line 2)
Formula
Variable 100.1 % to 200.0 % of nominal
Default value 115.0 %
Configuration based on A specified voltage threshold
Description This test checks Line 2 voltage for values that exceed a specified limit. The threshold is defined as a
percentage of the expected Line 2 nominal voltage. The test fails if Line 2 voltage exceeds the voltage
threshold.
Stored value Line 2 voltage
threshold voltage Specified V
3 L
<
threshold voltage Specified V
1 L

threshold voltage Specified V
2 L

Technical manual 4-22 Meter tools
Test 18 Name High voltage (Line 3)
Formula
Variable 100.1 % to 200.0 % of nominal
Default value 115.0 %
Configuration based on A specified voltage threshold
Description This test checks Line 3 voltage for values that exceed a specified limit. The threshold is defined as a
percentage of the expected Line 3 nominal voltage. The test fails if Line 3 voltage exceeds the voltage
threshold.
Stored value Line 3 voltage
Test 19 Name Low voltage and current present (Line 1)
Formula
Variable 0.0 % to 99.9 % of nominal for Line 1 voltage
0.0003 to 1000.0000 amperes for Line 1 current
Default value 78.0 % for voltage threshold
0.0015 amps for current threshold
Configuration based on Specified thresholds for voltage and current
Description This test checks voltage and current on Line 1 to detect possible theft or VT problems on Line 1. This test fails if
the following conditions are present:
Current on Line 1 is greater than a specified current threshold, and
Voltage on Line 1 is less than a specified voltage threshold
Stored value Line 1 voltage
Test 20 Name Low voltage and current present (Line 2)
Formula
Variable 0.0 % to 99.9 % of nominal for Line 2 voltage
0.0003 to 1000.0000 amperes for Line 2 current
Default value 78.0 % for voltage threshold
0.0015 amps for current threshold
Configuration based on Specified thresholds for voltage and current
Description This test checks voltage and current on Line 2 to detect possible theft or VT problems on Line 2. This test fails if
the following conditions are present:
Current on Line 2 is greater than a specified current threshold, and
Voltage on Line 2 is less than a specified voltage threshold
Stored value Line 2 voltage
threshold voltage Specified V
3 L

threshold voltage high Specified I
and threshold voltage Specified V
L1
L1

<
threshold voltage high Specified I
and threshold voltage Specified V
L2
L2

<
Technical manual 4-23 Meter tools
Test 21 Name Low voltage and current present (Line 3)
Formula
Variable 0.0 % to 99.9 % of nominal for Line 3 voltage
0.0003 to 1000.0000 amperes for Line 3 current
Default value 78.0 % for voltage threshold
0.0015 amps for current threshold
Configuration based on Specified thresholds for voltage and current
Description This test checks voltage and current on Line 3 to detect possible theft or VT problems on Line 3. This test fails if
the following conditions are present:
Current on Line 3 is greater than a specified current threshold, and
Voltage on Line 3 is less than a specified voltage threshold
Stored value Line 3 voltage
Test 22 Name Current missing (Line 1)
Formula
Variable 5.0 % to 100.0 % of nominal for Line 1 voltage threshold
5.0 % to 100.0 % of nominal for Line 2 voltage threshold
5.0 % to 100.0 % of nominal for Line 3 voltage threshold
0.0003 A to 1000.0000 A for Line 1 current threshold
0.0010 A to 1000.0000 A for Line 2 current threshold
0.0010 A to 1000.000 A for Line 3 current threshold
Default value 60.0 % of nominal for Line 1 voltage threshold
60.0 % of nominal for Line 2 voltage threshold
60.0 % of nominal for Line 3 voltage threshold
0.0015 A for Line 1 current threshold
0.0750 A for Line 2 current threshold
0.0750 A for Line 3 current threshold
Configuration based on Specified thresholds for voltage and current
Description This test checks voltage and current on all phases to help detect possible theft or CT problems on Line 1. This
test fails if the following conditions are present:
Voltage is present on any phase, and
Current is at or above a specified threshold on Line 2 or Line 3, and
Current is below a specified threshold on LIne 1
Stored value Line 1 current
threshold current high Specified I
and threshold voltage Specified V
L3
L3

<
threshold current specified ) I or (I
and threshold current specified I
and threshold voltage specified ) V or V or (V
L3 L2
L1
L3 L2 L1

<

Technical manual 4-24 Meter tools


Test 23 Name Current missing (Line 2)
Formula
Variable 5.0 % to 100.0 % of nominal for Line 1 voltage threshold
5.0 % to 100.0 % of nominal for Line 2 voltage threshold
5.0 % to 100.0 % of nominal for Line 3 voltage threshold
0.0010 A to 1000.0000 A for Line 1 current threshold
0.0003 A to 1000.0000 A for Line 2 current threshold
0.0010 A to 1000.000 A for Line 3 current threshold
Default value 60.0 % of nominal for Line 1 voltage threshold
60.0 % of nominal for Line 2 voltage threshold
60.0 % of nominal for Line 3 voltage threshold
0.0750 A for Line 1 current threshold
0.0015 A for Line 2 current threshold
0.0750 A for Line 3 current threshold
Configuration based on Specified thresholds for voltage and current
Description This test checks voltage and current on all phases to help detect possible theft or CT problems on Line 2. This
test fails if the following conditions are present:
Voltage is present on any phase, and
Current is at or above a specified threshold on Line 1 or Line 3, and
Current is below a specified threshold on LIne 2
Stored value Line 2 current
threshold current specified ) I or (I
and threshold current specified I
and threshold voltage specified ) V or V or (V
L3 L1
L2
L3 L2 L1

<

Technical manual 4-25 Meter tools


Security
All A1800 ALPHA meters include features that help prevent unauthorized access to meter
data and record events that may indicate meter tampering.
Meter passwords
Access to the A1800 ALPHA meter is protected through the use of passwords. When
establishing communication with the meter, the meter will request a password. If the
correct password is not supplied, the meter will not communicate or perform the
commands that it is issued. Passwords help ensure that the meter data is protected and
that the programming cannot be altered without proper authorization.
The A1800 ALPHA meter uses three passwords to control access to the meter. As shown in
Table 4-7, each password allows different activities that can be performed on the meter.
For more information regarding passwords, see the documentation that comes with the
Elster meter support software.
Test 24 Name Current missing (Line 3)
Formula
Variable 5.0 % to 100.0 % of nominal for Line 1 voltage threshold
5.0 % to 100.0 % of nominal for Line 2 voltage threshold
5.0 % to 100.0 % of nominal for Line 3 voltage threshold
0.0010 A to 1000.0000 A for Line 1 current threshold
0.0010 A to 1000.0000 A for Line 2 current threshold
0.0003 A to 1000.000 A for Line 3 current threshold
Default value 60.0 % of nominal for Line 1 voltage threshold
60.0 % of nominal for Line 2 voltage threshold
60.0 % of nominal for Line 3 voltage threshold
0.0750 A for Line 1 current threshold
0.0750 A for Line 2 current threshold
0.0015 A for Line 3 current threshold
Configuration based on Specified thresholds for voltage and current
Description This test checks voltage and current on all phases to help detect possible theft or CT problems on Line 3. This
test fails if the following conditions are present:
Voltage is present on any phase, and
Current is at or above a specified threshold on Line 1 or Line 3, and
Current is below a specified threshold on LIne 3
Stored value Line 3 current
Table 4-7. A1800 ALPHA meter passwords
Password Allowed activity
Read only The meter can be read. No alteration of data or programming is
allowed.
Billing read The meter can be read. Some basic data-altering activity relating to
billing functions is allowed.
Unrestricted The meter can be read. Full programming of the meter is allowed.
threshold current specified ) I or (I
and threshold current specified I
and threshold voltage specified ) V or V or (V
L2 L1
L3
L3 L2 L1

<

Technical manual 4-26 Meter tools


When communicating with the A1800 ALPHA meter remotely, the A1800 ALPHA meter
supports the password encryption standards in accordance with ANSI C12.21. In
accordance with ANSI C12.18, the password is not encrypted when communicating using
the optical port.
The meter records the number of failed password attempts that were used in trying to
access the meter. An internal warning will be generated if 10 failed password attempts
occur since the last demand reset. This warning can be used to control a relay output or to
trigger an alarm call.
Antitampering
All A1800 ALPHA meters provide auditing capabilities that can be used to indicate potential
meter tampering. These capabilities can record such items as the following:
programming changes
power outages
number of days since last pulse
number of manually-initiated demand resets
number of days since last demand reset
reverse energy flow
history log
cover removal detection
Program protection
As a security feature, the A1800 ALPHA meter can be ordered with program protection.
Program protection prevents metrological parameters from being altered. Some data and
configuration parameters can be altered while in program protection.
1
These alterable
items must be specified at ordering and can include the following:
communication parameters
TRueQ parameters
time of day (TOU or load profiling configurations)
switch times (TOU configurations)
special dates list (TOU or load profiling configurations)
All other parameter changes require the meter to exit program protect mode.
To temporarily disable program protection:
1. Break the terminal cover seals and remove terminal cover. The TC indicator will turn
on.
2. Break the meter cover seals and lift the meter cover.
3. At this point, you can perform any of the data or program altering operations
available using the Elster meter support software.
4. Close the meter cover and install the seals.
5. Install the terminal cover and seals. The TC indicator will turn off.
If programmed to do so, changes in the state of the terminal cover and the meter cover are
logged in the event log. See Event log on page 2-15 for details.
1
On meters with a history log, it may be possible to change certain metrological parameters while in program protection. For
more information, see History log on page 2-15.
Technical manual 5-1 Outputs
5 Outputs
Relay outputs
The A1810 ALPHA meter does not include relay outputs. The A1830 ALPHA meter and
higher supports up to 4 relays.
1
Figure 5-1. A1800 ALPHA meter with RS-232 as second communication port
1
Support for up to 6 relays on the A1830 ALPHA meter and higher is a future option. Contact Elster for availability.
Pulse output relay
(optional)
RS-232
connector
RS-485 terminals
RS-232 connector
(optional)*
*Present when optional second communication port is installed
Pulse output relay default values
1 2 3 4 5
6 7 8 9
RS-232 connector
1 = NC
2 = Rx
3 = Tx
4 = DTR
5 = GND
6 = DSR
7 = RTS
8 = NC
9 = NC
Tx+ Rx-
Tx- Rx+
RS-485 connections
A B C D
A = Wh del
B = varh del
C = Wh rec
D = varh rec
4-wire
2-wire
+
-
-bias
+bias
Technical manual 5-2 Outputs
Figure 5-2. A1800 ALPHA meter with RS-485 as second communication port
For more information about relay outputs and communications, see the instructional leaflet
(IL) that comes with the option board.
The output relays on the main circuit board can switch up to 125 VAC or 180 VDC at up to
70 mA. See Appendix D, Wiring diagrams.
With the A1800 ALPHA meter, all relay outputs are fully programmable using Elster meter
support software. Sources for relay outputs are listed in Table 5-1.
Table 5-1. Source for relay operation and output specifications
Relay source Relay output specification
Energy pulse For each pulse of the selected basic metered
quantity (see Metered energy and demand
quantities on page 2-10), the relay will do either of
the following:
toggle (that is, turn on and off)
pulse for a specified length of time
Load control The relay closes when the demand exceeds the
specified demand threshold, and it remains closed
for the duration of the interval. The relay will open
after the demand remains below the threshold for
one full interval.
EOI indication The relay closes for 5 seconds after the end of each
interval or subinterval.
Pulse output relay
(optional)
RS-232
connector
RS-485 terminals
RS-485 connector
(optional)*
*Present when optional second communication port is installed
Pulse output relay default values
A B C D
A = Wh del
B = varh del
C = Wh rec
D = varh rec
1 2 3 4 5
6 7 8 9
RS-232 connector
1 = NC
2 = Rx
3 = Tx
4 = DTR
5 = GND
6 = DSR
7 = RTS
8 = NC
9 = NC
Tx+ Rx-
Tx- Rx+
RS-485 connections
4-wire
2-wire
+
-
-bias
+bias
Technical manual 5-3 Outputs
Figure 5-3. Toggle relay output
In toggle mode, a relay changes state for each energy pulse received from the meter
engine.
Figure 5-4. Pulse relay output (default pulse width)
In pulse mode, a default pulse width of 10 milliseconds is generated for each energy pulse
received from the meter engine. Using Elster meter support, the width can be
programmed with a value from 1 millisecond to 255 milliseconds.
Energy pulse outputs
When a relay is used to echo energy pulses for a basic metered quantity, each pulse is
equal to a specified amount of energy.
Using Elster meter support software, there are two methods for specifying the weight of
each pulse.
Using pulse divisor. Program the energy pulse divisor with an integer value between 1
and 999.
Demand forgiveness
(cold load pickup)
The relay closes while demand forgiveness is in
effect. The relay will open after the demand
forgiveness time has expired.
TRueQ tests failure Relay closes as long as the specified TRueQ tests
continue to fail (see TRueQ monitoring on page 4-
12).
Specified errors, warnings, and
meter events
The relay closes for as long as the specified errors,
warnings, or events persist (see Relay-related
alarms on page 5-4).
TOU switches to a specific tariff The relay closes for the duration of the specified
tariffs.
Table 5-1. Source for relay operation and output specifications
Relay source Relay output specification

Pulse
On
Off

Pulse period Pulse period Pulse period
Pulse
On
Off
10 msec. 10 msec.
10 msec.
Pulse period Pulse period Pulse period
constant Relay
constant Pulse
divisor pulse Energy =
Technical manual 5-4 Outputs
The pulse constant (also known as the meter constant) for the A1800 ALPHA meter is as
follows:
For transformer rated meters: 40,000 pulses per kWh
For example, the desired relay constant is 1000 pulses per 1 kWh and the pulse
constant is 40,000 pulses per 1 kWh:
Using Elster meter support software, program the energy pulse divisor of 40 into the
meter.
Note: If the energy pulse divisor is not an integer, then the exact desired output is not
possible.
For direct connect-rated meters: 4000 pulses per kWh
For example, the desired relay constant is 1000 pulses per 1 kWh and the pulse
constant is 4000 pulses per 1 kWh:
Note: If the energy pulse divisor is not an integer, then the exact desired output is not
possible.
Using pulse value. Program the energy pulse value with a value between 0.000001 kWh
and 100 kWh to represent the amount of energy per pulse (in kilo units). For example, to
have one energy pulse represent 2 Wh (0.002 kWh), you would use an energy pulse value
of 0.002.
Note: The pulse value method is available from the Tools > System Preferences >
Programming Options command in Metercat.
Note: Elster recommends that the pulse value should not be used when verifying meter
accuracy. Use the pulse divisor method when verifying meter accuracy.
Relay-related alarms
The A1800 ALPHA meter periodically performs a self test to determine if it is operating
properly. If any errors are detected, the meter can respond in any or all of the following
ways:
display an error or a warning (see Codes and warnings on page 6-2)
initiate a telephone call using a modem
trigger a relay
See Table 5-2 for errors, warnings, and events that can trigger a relay.
Table 5-2. Errors, warnings, and events that can trigger a relay
Condition Description
Carryover error See E1 000001: Carryover error on page 6-3.
Clock error See E3 030000: Clock error on page 6-5.
Crystal oscillator error See E1 000010: Crystal oscillator error on page 6-4.
Demand overload warning See W1 100000: Demand overload warning on
page 6-7
EEPROM access error See E1 010000: EEPROM access error on page 6-4.
End of calendar warning See W2 200000: End of calendar warning on
page 6-8.
40
1000
40000
divisor pulse Energy = =
4
1000
4000
divisor pulse Energy = =
Technical manual 5-5 Outputs
Event log wrap event The event log has exceeded the maximum number of
entries, and the oldest records will be overwritten.
General configuration error See E1 100000: General configuration error on
page 6-4.
History log wrap warning The history log has exceeded the maximum number
of entries. Depending on programming, the meter will
either lock the history log or start overwriting the
oldest records. If the history log is locked, no further
changes to the meter are allowed until the history log
has been read.
Improper meter engine
operation warning
See W1 000010: Improper meter engine operation
warning on page 6-6
Instrumentation profiling set 1
wrap imminent event
Set 1 of the instrumentation profiling log is within 2
days of overflowing. Data will be lost if the
instrumentation profiling log is not read within 2 days.
Instrumentation profiling set 2
wrap imminent event
Set 2 of the instrumentation profiling log is within 2
days of overflowing. Data will be lost if the
instrumentation profiling log is not read within 2 days.
Internal communication error See E1 001000: Internal communication error on
page 6-4.
Low battery warning See W1 000001: Low battery warning on page 6-6.
Possible tamper warning This condition indicates possible tampering of the
meter because a specified number of invalid
passwords used to access the meter has been used
(called tamper detect warning in this manual). This
condition does not generate an error or warning code
on the LCD.
Potential indicator warning See W1 010000: Potential indicator warning on
page 6-7.
Power fail data save error See E2 200000: Power fail data save error on
page 6-5.
Pulse profiling wrap imminent
event
The pulse profiling log is within 2 days of overflowing.
Data will be lost if the pulse profiling log is not read
within 2 days.
Rate override warning The current TOU rate is being overridden by the
alternate TOU rate schedule.
Reverse energy flow warning See W1 000100: Reverse energy flow warning on
page 6-7.
Service current test failure
warning
See W2 000002: Service current test failure warning
on page 6-7.
Service voltage test failure
warning
The service voltage test was unable to find a valid
service or the measured service does not match the
locked service.
Table 5-2. Errors, warnings, and events that can trigger a relay
Condition Description
Technical manual 5-6 Outputs
LED pulse outputs
The A1800 ALPHA meter has two energy light emitting diodes (LEDs), which are
permanently configured as follows:
active LED - indicates active (Wh) energy import or export
alternate LED - indicates alternate (varh/VAh) energy import or export
The LEDs emit pulse outputs that can be used to test the A1800 ALPHA meter in the field
without removing the meter from service or breaking the seal.
Figure 5-5. LEDs
Output specifications
The LEDs support up to 120 pulses per second.The pulse width is fixed at 8 msec.
Depending on the operating mode of the meter, the LEDs are programmed at the factory to
emit a pulse as follows:
For alternate pulse rates, contact your Elster representative.
Table 5-3. Transformer rated meter LED output specifications
Operating mode Pulse rate Pulse divisor
Normal 5000 pulses/kWh or 5000 pulses/kvarh 8
Alternate 5000 pulses/kWh or 5000 pulses/kvar 8
Test 40,000 pulses/kWh or 40,000 pulses/kvarh 1
Table 5-4. Direct connect-rated meter LED output specification
Operating mode Pulse rate Pulse divisor
Normal 500 pulses/kWh or 1000 pulses/kvarh 8
Alternate 500 pulses/kWh or 1000 pulses/kvarh 8
Test 4000 pulses/kWh or 4000 pulses/kvarh 1
Active energy LED
Alternate energy LED
Technical manual 6-1 Testing
6 Testing
A1800 ALPHA meters are factory calibrated and tested to provide years of trouble-free
service. No field calibrations or adjustments are required to ensure accurate operation of
the meter. It is normal, however, to test installed A1800 ALPHA meters periodically to
ensure accurate billing.
The A1800 ALPHA meter performs its own self tests. Additionally, the system
instrumentation and TRueQ features provide valuable information about the meter service.
See Chapter 4, Meter tools, for more information about the instrumentation and power
quality features of the meter.
Testing procedures are the same regardless of the type of meter being tested.
Meter self test
The A1800 ALPHA meter periodically performs a self test to determine if it is operating
properly. The self test ensures that the A1800 ALPHA meter is functioning properly and its
displayed quantities are accurate. Any errors encountered will be displayed on the LCD.
Certain errors may also initiate a telephone call via a modem or trigger a relay.
For LCD errors and warnings, see Codes and warnings on page 6-2.
For relay alarms, see Relay-related alarms on page 5-4.
The meter self test will be performed automatically under the following conditions:
when the meter is initially installed and after any power restoration
at midnight
immediately after a data-altering communication session
The self test incorporates a series of electronic analyses verifying many aspects of the
A1800 ALPHA meter. Continuity checks and communications checks are made between
various key circuits of the electronics, and parity checks are made of memory and data
locations. After the meter passes its self test upon power restoration, all of the LCD
segments will be turned on briefly before beginning the normal display sequence. The
following is a list of the specific tests performed during a self test:
verification of the configuration data and checksums
confirmation of the crystal oscillator accuracy
detection of low battery voltage
detection of low Read without Power battery voltage
maximum lifetime usage of the Read without Power battery
verification of normal microcontroller function
detection of unexpected meter engine resets (for multiple tariff configurations)
detection and identification of user-defined warning conditions
Technical manual 6-2 Testing
Codes and warnings
There are 3 types of codes:
error codes
warning codes
communication codes
The A1800 ALPHA meter displays error codes and warnings as an indication of a problem
that may be adversely affecting its operation. The meter will continue to function as
normally as possible when displaying an error or warning. The and RESET buttons
operate differently if an error or warning is displayed. See Push buttons on page 3-4 for
information on how the push buttons operate when an error or warning is displayed.
Error codes indicate conditions that may be affecting billing data. It is not recommended to
operate the A1800 ALPHA meter for an extended time when it is displaying an error code.
Warning codes indicate conditions that may be of concern but do not affect the integrity of
billing data.
Communication codes generally indicate a condition affecting communications with the
meter through the optical port or remote port. Not all communication codes indicate
potential problems; some codes provide an indication of the present communication
process.
Error codes. Error codes override any other item that is being displayed on the LCD. Using
Elster support software, error codes can be configured to lock the display, preventing
other items from being displayed, and the error indicator turns on. There are exceptions to
errors locking the display:
The normal and alternate display sequence can be viewed even when an error code
locks the display. See button on page 3-5 for more information.
Warning codes can be programmed to display an error code. When the condition
causing the warning code is clear, the error code is no longer displayed. See E3
300000: Display locked by warning on page 6-5 for more information.
Communication codes are temporarily displayed on the LCD even when the LCD is locked
by an error code. After the communication code clears, LCD returns to showing the error
code.
Error codes are indicated on the LCD by a group code and a numerical code. The group
code makes it easier to identify the error on the LCD. The numerical code indicates the
specific condition that has occurred. See Figure 6-1 for a sample error code displayed on
the meter LCD. Table 6-1 through Table 6-3 describe the different error conditions and their
codes.
Figure 6-1. Sample error code displayed on the LCD
P +
L L L 1 2 3
Technical manual 6-3 Testing
Error codes of the same group are displayed in combination (E1 001010, for example),
indicating that more than one error condition has been detected. If errors exist in more
than one group, the meter will continually cycle through the different groups. Any
problems must be corrected before normal operation can continue. In some cases, the
meter may need to be reprogrammed or returned to the factory for repair or replacement.
E1 000001: Carryover error. This code indicates a failure of a RAM checksum test on data
stored in the meters volatile RAM during a power outage. When a loss of line voltage
occurs, the meters RAM is maintained by the super capacitor and the TOU battery. If both
of these fail, the data stored in RAM is lost. Billing data is stored in nonvolatile EEPROM and
will still be available.
1
The push buttons and communications ports will function normally.

Since shipping can take several days, this error will likely be seen on meters
shipped without a connected battery.
The meter battery may need to be replaced, and the error will need to be reset through
Elster meter support software. If the error code is still shown after using Elster meter
support software, the meter must be returned to the factory for repair or replacement.
Table 6-1. Group E1 error conditions and codes
Condition Code
Carryover error 0 0 0 0 0 1
Crystal oscillator error 0 0 0 0 1 0
Table CRC error 0 0 0 1 0 0
Internal communication error 0 0 1 0 0 0
EEPROM access error 0 1 0 0 0 0
General configuration error 1 0 0 0 0 0
Table 6-2. Group E2 error conditions and codes
Condition Code
Security configuration error 0 0 0 0 0 2
Password table CRC error 0 0 0 0 2 0
Encryption key table CRC error 0 0 0 2 0 0
ROM fail error 0 2 0 0 0 0
Power fail data save error 2 0 0 0 0 0
Table 6-3. Group E3 error conditions and codes
Condition Code
Clock error 0 3 0 0 0 0
Display locked by warning 3 0 0 0 0 0
1
Billing data is always stored in nonvolatile memory. Depending on meter configuration, other data may be stored in RAM,
which uses a battery to preserve memory. If the battery fails, this data would be lost.
Technical manual 6-4 Testing
E1 000010: Crystal oscillator error. This codes indicates a problem with the crystal oscillator.
The A1800 ALPHA meter must be returned to the factory for repair or replacement.
E1 000100: Table CRC error. This code indicates a possible error in the A1800 ALPHA
meters programming. This code might appear if a communications interruption occurs
during meter programming. Depending on which area of the meter is affected, billing data
may not be reliably accumulated while this error condition exists. The push buttons and
optical port will continue to function normally.
Reprogramming the meter with Elster meter support software may correct the problem. If
the error code is displayed after reprogramming, the A1800 ALPHA meter should be
returned to the factory for repair or replacement.
E1 001000: Internal communication error. This code indicates the meter had an internal
communication error. The A1800 ALPHA meter must be returned to the factory for repair or
replacement.
E1 010000: EEPROM access error. This code indicates the meter had a problem accessing
its nonvolatile EEPROM. The A1800 ALPHA meter should be returned to the factory for
repair or replacement.
E1 100000: General configuration error. This code indicates a problem with the meters
configuration or program. The meter can usually be reprogrammed using Elster meter
support software to correct the errors.
E2 000002: Security configuration error. This code indicates an error is present in the
meters security configuration. Contact Elster if this error is displayed on the LCD.

If this error occurs, the meter is vulnerable to tampering. Prompt correction of the
error will maximize the A1800 ALPHA meters security protection.
E2 000020: Password table CRC error. This code indicates a CRC error is present in the
meters ANSI C12.21 password configuration table. Contact Elster if this error is displayed
on the LCD.

If this error occurs, the meter is vulnerable to tampering. Prompt correction of the
error will maximize the A1800 ALPHA meters security protection.
E2 000200: Encryption key table CRC error. This code indicates a CRC error is present in the
meters ANSI C12.19 encryption key configuration table. Encryption keys are used for secure
access to the meters data and configuration through the remote communication port.
Contact Elster if this error is displayed on the LCD.

If this error occurs, the meter is vulnerable to tampering. Prompt correction of the
error will maximize the A1800 ALPHA meters security protection.
E2 020000: ROM fail error. This code indicates an incomplete attempt to flash the meter
firmware. This code will exist on the meter if Elster firmware flash software did not
complete the upgrade process. All meter functionality is halted until this error is resolved.
Use Elster firmware flash software to attempt repair. If this fails, the meter must be returned
to the factory for repair or replacement.
Technical manual 6-5 Testing
E2 200000: Power fail data save error. This code indicates that the data saved in the
nonvolatile EEPROM during a power fail may be invalid. This error will be displayed when
power is restored to the meter, and a self check has discovered an error with the EEPROM
data. The A1800 ALPHA meter must be returned to the factory for repair or replacement.
E3 030000: Clock error. This code indicates an error with the meters timekeeping ability.
When a carryover error occurs (see E1 000001: Carryover error on page 6-3), reference to
real time is lost. The meter battery may need to be replaced, and the error will need to be
reset through Elster meter support software. If the error code is still present, the meter must
be returned to the factory for repair or replacement.
TOU features cannot be performed when time is lost. Previously accumulated data is
stored in nonvolatile EEPROM and will still be available.
E3 300000: Display locked by warning. This code indicates that one or more warning
codes (see Warning codes on page 6-5) has locked the display. The A1800 ALPHA meter
can be programmed to lock the display if a warning condition is present. Elster meter
support software is used to select the individual warnings that will cause this error code to
display. If the condition causing the warning clears, the error code will also clear.
Warning codes. Warning codes indicate conditions of concern that do not yet affect the
integrity of billing data. When the condition is present, a warning code is automatically
inserted as the last item in the normal and alternate display sequences. When the
condition clears, the warning code, is removed from the display sequence. Elster meter
support software can be used to select individual warnings that will lock the display as an
error. See Error codes on page 6-2 for more information.
Warning codes are indicated on the LCD by a group code and a numerical code. The
group code makes it easier to identify the error on the LCD. The numeric code indicates the
specific condition that has occurred. See Figure 6-2 for a sample warning code displayed
on the LCD. Table 6-4 and Table 6-5 describe the different warning conditions and their
codes.
Figure 6-2. Sample warning code
Table 6-4. Group W1 warning codes
Condition Code
Low battery warning 0 0 0 0 0 1
Improper meter engine operation
warning
0 0 0 0 1 0
Reverse energy flow warning 0 0 0 1 0 0
Potential indicator warning 0 1 0 0 0 0
Demand overload warning 1 0 0 0 0 0
P +
L L L 1 2 3
Technical manual 6-6 Testing
Warning codes of the same group are displayed in combination (for example,
W2 202000), indicating that one or more warning conditions are present. If warnings
exist in more than one group, the meter displays each group at the end of the display
sequence before returning to the first item in the display sequence.
W1 000001: Low battery warning. This warning code indicates a low battery voltage or
missing battery. A1800 ALPHA meters having realtime TOU functionality require a battery to
maintain date and time over an extended power outage.
For timekeeping configurations, the meter should be de-energized and the battery should
be replaced. Once the new battery has been installed and the meter is energized, the
code is automatically cleared. See Removing the battery on page 7-6 and Installing a
TOU battery on page 7-3 for instructions on replacing batteries.
Note: In addition, the low battery indicator will display on the LCD (see Low battery
indicator on page 3-3).
W1 000010: Improper meter engine operation warning. This code indicates that the meter
engine program may be corrupt or is not executing correctly. This warning condition is
typically triggered when the microcontroller reinitializes the meter engine. An unstable or
noisy electrical environment at the A1800 ALPHA meter installation can interfere with this
operation.
If the meter engine is successfully reinitialized, then the warning code will be automatically
cleared from the LCD. If the code continues to be displayed on the LCD, the A1800 ALPHA
meter should be returned to the factory for repair or replacement.
Table 6-5. Group W2 warning codes
Condition Code
Service current test failure
warning
0 0 0 0 0 2
Demand threshold exceeded
warning
0 0 0 2 0 0
Line frequency warning 0 0 2 0 0 0
TRueQ test failure warning 0 2 0 0 0 0
End of calendar warning 2 0 0 0 0 0
Table 6-6. Group W3 warning codes
Condition Code
Read without Power battery
discharged
0 0 0 0 0 3
Read without Power mode active 0 0 0 0 3 0
Technical manual 6-7 Testing
W1 000100: Reverse energy flow warning. This warning code indicates that reverse energy
flow has been detected equivalent to twice the K
h
since the last reset. It may be an
indication of tampering with the A1800 ALPHA meter installation. If reverse energy flow is
expected, then this warning code can be disabled through Elster meter support software. If
the service being metered is not expected to return energy to the utility, further
investigation is required. In some cases, it may be necessary to return the A1800 ALPHA
meter to the factory for repair or replacement.
The code is cleared by these methods:
performing a demand reset
issuing the clear values and status command through Elster meter support software
W1 010000: Potential indicator warning. This code indicates that one or more of the phase
potentials are missing or below the defined threshold for voltage sag detection. This code
will display at the same time as one or more of the potential indicators blink. See Phase
indicators on page 3-2 and Voltage sags on page 4-13 for more details on potential
indicators and voltage sags.
The code is automatically cleared when the phase potential returns a value within the
programmed thresholds.
W1 100000: Demand overload warning. This code indicates that the demand value
exceeded the programmed overload value. It is generally intended to inform a utility when
the installation is requiring more power than the service equipment was originally
designed to handle.
If the demand overload value has been set lower than appropriate for the installation, the
A1800 ALPHA meter may be reprogrammed with a higher threshold value.
The code is cleared by these methods:
performing a demand reset
issuing the clear values and status command through Elster meter support software
W2 000002: Service current test failure warning. This code indicates that the most recently
performed service current test has failed. See Service current test on page 4-9 for more
information.
The code is cleared by these methods:
the service current test is performed again and the test does not fail
issuing the clear values and status command through Elster meter support software
W2 000200: Demand threshold exceeded warning. This code indicates that the demand
has exceeded one of the programmed demand thresholds. This warning follows the state
of any relay programmed for demand threshold operation. It is set once the demand
threshold has been exceeded and only cleared after one complete demand interval
during which the threshold is not exceeded.
W2 002000: Line frequency warning. If a meter is configured to use the line frequency
instead of the crystal oscillator as the time base, this code indicates that the line frequency
is off by 5 % of its programmed setting. When this condition occurs, the meter switches
timekeeping to the crystal oscillator.
The code will be automatically cleared once the line frequency returns to within 5 % of the
nominal frequency. This warning will never appear on meters configured for constant
timekeeping operation from the internal crystal.
W2 020000: TRueQ test failure warning. This code indicates that one or more TRueQ tests
have detected a value outside the programmed thresholds. Use the meter system
instrumentation displays or Elster meter support software to gain additional information on
the specific TRueQ test causing the problem.
The code will be automatically cleared once TRueQ conditions return to a value within the
programmed thresholds.
Technical manual 6-8 Testing
W2 200000: End of calendar warning. This code indicates that the meter calendar has
expired or is about to expire. The date at which this code appears is configurable using
Elster meter support software. Program a new calendar using Elster meter support
software.
The code is cleared by these methods:
performing a demand reset
issuing the clear values and status command through Elster meter support software
W3 000003: Read without Power battery discharged. This code indicates that the Read
without Power battery, which is used only to enable the Read without Power mode during
an outage, failed the meters most recent self test. The Read without Power battery fails if
the meter self test detects that the batterys voltage is below the minimum threshold or the
battery has exceeded its maximum lifetime usage time. The meter will not enter Read
without Power mode if this warning is displayed. Contact Elster if this warning appears on
the display.
W3 000030: Read without Power mode active. This code indicates that the meter is
operating in the Read without Power mode. The meter has limited functionality while in this
mode (see Read without Power mode on page 3-9 for more information). This code is
cleared automatically when the meter exits the Read without Power mode.
Communication codes. Communication codes temporarily override any other item that
is being displayed on the LCD (including error codes). Communication codes are indicated
on the LCD by a port code and a numerical code. The port code identifies the affected port.
The numerical code indicates the status of the communication session. See Figure 6-3 for
a sample communication code displayed on the meters LCD. See Table 6-7 for the
communication codes that can be displayed.
Figure 6-3. Sample communication code
For most communication errors, Elster recommends you attempt the communication
again. You may need to cycle power to the A1800 ALPHA meter or to reattempt the Elster
meter support software function. If communication errors persist, return the meter to the
factory for repair or replacement.
Table 6-7. Communication codes
Condition Code
CRC error C 0 0 1 0 1
Syntax error C 0 0 1 0 3
Framing error C 0 0 1 0 4
Timeout error C 0 0 1 0 5
P +
L L L 1 2 3
Technical manual 6-9 Testing
Meter shop testing
Test equipment
Typically, meter shops develop testing procedures specific to their own needs and have the
test equipment needed. Below is a list of standard test equipment required for testing the
A1800 ALPHA meter:
a stable mounting fixture for the meter and a means to temporarily make the proper
power connections to the meter
a reliable power supply that should be able to do the following:
provide a voltage source for energizing the meter at its rated voltage (if desired,
the meter can be tested using a lower source voltage if that voltage is within the
wide operating voltage range of the A1800 ALPHA meter)
provide a variable load current at unity power factor (PF)
provide a variable load current at a lagging power factor for varh testing; the
power supply should be capable of delivering load current at PF = 0.0 (90
lagging) or PF = 0.5 (60 lagging)
a precision Wh reference standard with 0.002 % accuracy
a precision varh reference standard with 0.002 % accuracy
a phantom load device or other loading circuit capable of handling the test
current
one of the following:
a photoelectric pickup to sense test pulses from the LED and a device capable of
counting pulses
a low voltage (12 VDC to 24 VDC), low-power pulse sensor to capture and count
pulses from the meter output relay (the pulse sensor should provide a low voltage
source to the pulsing relay as well as detect and count contact closures of the
output relay)
test equipment for measuring, counting, and timing pulse outputs
control equipment that can provide switching between the meter source voltage and
precision reference standard
precision voltage and current transformers
voltmeters, ammeters, phase angle meters, power factor meters, and any other
measuring equipment that might be required
Test setup
Before testing the A1800 ALPHA meter, check the nameplate for the following:
Meter class for expected accuracy
Test amperes (I
n
or I
b
)
The specific test ampere value is not critical as long as the applied current does not
exceed the I
max
current rating of the meter. Normally, a value of approximately 20 %
to 25 % of I
max
is used for basic tests, with additional test points at 5 %, 10 %, and
100 % of I
max
also required by most legal authorities.
Note: The A1800 ALPHA meter has a flat, linear load curve accuracy response. Therefore,
when allowed by local legislation, meter accuracy testing can be accomplished by
checking the meter accuracy at two typical points. For example, test the meter with
In equal to 10 % of I
max
, at both 100 % and 20 % PF. Historical data from testing the
A1800 ALPHA meter confirms that if these test points are within the required
accuracy, the entire range of loads is within the required accuracy.
Operating voltage range
Any other important specifications for the meter being tested
Technical manual 6-10 Testing

Risk of personal injury or death!
Use only authorized personnel and proper test procedures to test metering
equipment. Dangerous voltages are present. Personal injury, death, or
equipment damage can result if safety precautions are not followed.
To set up the A1800 ALPHA meter for testing:
1. Install the meter in the stable mounting fixture.
2. Place the precision Wh or varh reference standard and precision voltage and current
transformers (as required) in series with the meter being tested.
If voltage transformers are not required, then the meter source voltage should be
placed in parallel with the Wh or VARh reference standards. See Appendix D, Wiring
diagrams, for appropriate wiring diagrams for the A1800 ALPHA meter.
3. Connect the control equipment for switching the source voltage to the precision
reference standard.
4. Connect the measuring equipment for counting the standards output pulses.
5. Apply the rated test current and voltage to the terminals of the meter.
Meter testing
Since no adjustments are required for the A1800 ALPHA meter in the field, meter testing is
done primarily to verify that the meter is operating within its specifications. Typically, meter
specifications are verified by checking the meter calibration. The accuracy of the
A1800 ALPHA meter remains consistent over a wide range of ambient temperatures.
Nevertheless, for precise test results, meters should be tested in an environment where the
meter and test equipment are at the same ambient temperature, ideally 22 C (72 F).
The test voltage should be applied to the meter for at least ten seconds prior to making test
measurements. This allows the power supply circuitry to stabilize. When testing meters for
Class 0.2 accuracy, a test cycle time of at least one minute is recommended at I
n
and with
PF = 1.0. When using current values lower than I
n
for testing, test errors may occur because
not enough time is allowed for the test. When using a lower test I
n
, increase the test time
proportionally.
The preferred test method is to apply full 3-phase voltage and current to both the meter
and the precision reference standard. Nevertheless, if required, polyphase meters can be
tested with single phase loading. Single phase loading is done by connecting the voltage
inputs in parallel and the current sensors in series to combine element operation. The
accuracy test results for single phase and polyphase loading will be virtually identical and
well within A1800 ALPHA meter specifications.
Using relay outputs for testing. The relay outputs can be used instead of the LED to test
meter calibration. To do so, the relay outputs need to be configured for pulse output. When
using the relay outputs for testing, testing time should exceed 20 seconds for accurate
results at normal test current values of I
b
or I
n
. If more accurate testing is required, use
longer testing times. If precision testing is required, testing times should be as long as it
takes to attain a stable accuracy level when comparing the meter under test to the
precision standard. The testing time may vary because of the characteristics of the
precision reference standard and the amount of power flowing through the test circuits.
Some experimentation may be required to determine the testing time needed to reach a
stable accuracy level.
Using LCD pulse count for testing. For test shops that do not have photoelectric pulse
sensors and related counters and do not want to use relay outputs for testing, the LCD can
provide a pulse count that reflects the energy measured during a test. Use the LCD pulse
count to determine the energy measured during the test cycle and compare it with the
energy delivered by precision reference standard.
Technical manual 6-11 Testing

Wiring a portable device into an energized metering circuit must be done with
extreme care, using only authorized procedures. If high voltage connected
current transformers are accidentally open circuited, the voltages at the
secondary open terminals can rise to the primary voltage level, creating an
extremely hazardous condition, leading to possible property damage, personnel
injury or death.
To test the meter using the LCD pulse count, the meter display must be configured to
display a test pulse count. Use the Elster meter support software to communicate to the
meter through the optical port and place it in test mode. In test mode, the LCD display can
be cycled to display the pulse count accumulated during a test cycle. After meter testing is
complete, use the meter software to restore the meter to normal mode.
If a meter is programmed to display energy pulse counts when it is in the alternate display
mode, a similar procedure also can be used to test a meter while it is in service at a
customer site. When testing a meter in service, follow the safety procedures specified by
the utility. Wire a portable precision reference standard into the circuit in series with the
billing meter. After the portable precision reference standard is in the circuit, the energy
value determined from the pulse count displayed on the LCD over the test interval can be
compared with the energy value displayed on the portable reference standard. If this test
method is used while the meter is in alternate mode, any energy consumed by the
customer during the test is registered in the normal manner.
Technical manual 6-12 Testing
Technical manual 7-1 Installation and removal
7 Installation and removal
Preliminary inspection

Circuit-closing devices must be used on current transformer secondaries.
Dangerous currents and voltages are present if secondaries are open-circuited.
Equipment damage, personal injury, or death can result if circuit-closing devices
are not used.
The A1800 ALPHA meter is calibrated and tested at the factory, and it is ready for
installation. Follow proper installation and removal procedures for personal safety and
protection of the meter.
Before installing and applying power to the A1800 ALPHA meter, a quick inspection of the
meter itself is recommended. Check for some of the following items:
no broken or missing parts
no missing or broken wiring
no bent or cracked components
no evidence of overheating
check the nameplate to make sure it is appropriate for the service
Physical damage to the outside of the A1800 ALPHA meter could indicate potential
electronic damage in the inside of the meter. Do not connect power to a meter that is
suspected to have unknown internal damage. Contact your local Elster representative if
you suspect your meter may be damaged.
Placing the meter into service
See Appendix D, Wiring diagrams, for illustrations of both internal and connection wiring
diagrams.

Circuit-closing devices must be used on current transformer secondaries.
Dangerous currents and voltages are present if secondaries are open-circuited.
Personal injury, death, or equipment damage can result if circuit-closing devices
are not used.
Technical manual 7-2 Installation and removal

Make sure to install the correct meter for the service type, maximum current, and
capacity required. Always verify that the maximum meter voltage and current
ratings are equal to or greater than the maximum service voltage and current.
Installing inappropriate meters can damage equipment.
To use the A1800 ALPHA meter effectively and safely, follow this procedure:
1. Make sure that the meter hanger, located on the base of the A1800 ALPHA meter, is
in the desired position. Sliding the hanger down to the hidden position will hide the
top supporting screw.
2. Use at least an M6 screw for the top supporting position and hang the meter on it,
making sure it is level. The meter will operate correctly in any position, but failing to
mount the meter in a proper vertical position will place the other mounting holes at
the wrong place on the mounting panel.
3. Use at least an M6 screw in each of the bottom supporting screws to secure the
A1800 ALPHA meter enclosure; the mounting holes are 7.1 mm (0.28 inches) in
diameter.

Before wiring the meter into the power circuit, use authorized utility procedures
to install proper ground connections on all appropriate VT and CT circuits and on
the meter ground terminals. Also, be certain that CTs on energized lines are
securely short-circuited either with circuit-closing test switches or with properly
installed conductors. Dangerous voltages can be present. Personal injury, death,
or equipment damage can result from wiring an ungrounded meter or
mishandling improperly grounded metering transformer circuits.
4. Install the ground connections.

A1800 ALPHA meter terminals are designed for optimum use with copper wiring.
For direct connect-rated meters, aluminum wiring can be used but if so, it is
extremely important to use proper aluminum wiring practices. Aluminum wiring
compound or wiring paste (grease) should be used when attaching the bottom-
connected terminals. Tighten the connections, allow them to relax for a few
minutes, then tighten them again. This will minimize the cold-flow effects of
aluminum cable. Failure to observe correct practices for installing aluminum
wiring could lead to overheating of the terminals, equipment failures, or
damaging fires. Where possible, Elster recommends copper-compatible meter
terminals and aluminum wire. Such adapters also can provide for use or larger
aluminum conductors that can be otherwise used in the terminals of the
A1800 ALPHA meter.
5. Ensure that primary or system voltages are either disconnected from a power source
or that utility safety practices for handling live circuits are strictly followed.
6. If applicable, ensure that any current transformers are de-energized with no high-
voltage primary voltage connected to their primaries and no primary current
circulating through them. If primary current and voltage are present in the current
transformers, it is extremely important to verify that safety shorting connections are in
Technical manual 7-3 Installation and removal
place on all secondary winding connections prior to handling CT connections to the
meter.
7. Wire the meter using color-coded wire according to locally applicable specifications.
The terminal block dimensions on the A1800 ALPHA meter support cable sizes of
approximately 5 mm in diameter for transformer rated connections (10 mm in
diameter for direct connect).
Standard wiring diagrams are shown in Appendix D, Wiring diagrams.
8. After wiring the meter and making any communication and relay connections,
assemble the terminal cover and apply power.
For information on communication and relay connections, see Chapter 5, Outputs.
Figure 7-1. A1800 ALPHA meter mounting screw locations
Installing a TOU battery
The TOU battery is replaceable without breaking the meter seal. Use only Elster-
recommended TOU batteries. See your Elster representative for details.

The meter should be de-energized before installing the battery. Dangerous
voltages are present; and equipment damage, personal injury, or death can
result if safety precautions are not followed. Use authorized procedures to install
the battery while power is removed from the meter.
Before installing the battery, the A1800 ALPHA meter must have been energized for at least
1 minute within the preceding 60 minutes. This ensures that the supercapacitor is properly
charged and that the battery is not immediately drained upon installation. If this is not
done, then the battery may be damaged and the meter may not function correctly. While
the meter is powered, verify that the LCD is active and functioning.
Hanger screw mount
Screw mounts
Technical manual 7-4 Installation and removal
To install the battery:
1. If the meter has not been energized for at least 1 minute during the previous 60
minutes, energize the meter for 1 minute.
If the meter has been energized for at least 1 minute during the previous 60 minutes,
proceed to step 2.
2. De-energize the meter.
3. Remove the terminal cover screws and seals.
4. Remove the terminal cover to expose the battery well.
Figure 7-2. Battery well and connector
5. Slide the battery leads into the connector to the right of the battery well.
6. Place the battery firmly in the battery well.
7. Replace the terminal cover.
8. Energize the meter and verify that the LCD becomes active and functioning properly.
Verify that the low battery symbol on the meter LCD is not displayed. See Indicators
and controls on page 3-1 for details.
9. Replace the terminal cover screws and seals.
10. Reprogram the meter or clear the errors (as necessary).
Troubleshooting.

Not following this procedure can cause the meter to function improperly. In case
a battery has been installed correctly and the meter is not functioning properly (for
example, display is blank but the meter is powered), use the following procedure.
1. De-energize the meter and let it sit without power for 48 to 72 hours. This provides
sufficient time for the supercapacitor to discharge and for the microcontroller to shut
down.
1
2. Energize the meter for at least 1 minute. The microcontroller should power up
correctly and the supercapacitor will charge. Verify that the LCD becomes active and
functioning correctly.
3. De-energize the meter and insert the battery, following the instructions earlier in this
section.
If the meter still does not function properly, then it should be returned to the factory.
1
If the battery was installed with the polarity reversed, the battery should not be damaged. If the battery was installed without
having the meter properly energized, then the battery will lose approximately 8.5 % of its service life each day.
TOU battery
Technical manual 7-5 Installation and removal
Initial setup
After installing and powering the A1800 ALPHA meter, verify the following:
The system service voltage test (if enabled) shows the valid service for this
installation. The phase rotation, service voltage, and service type should be indicated
on the LCD. Other validation information can be obtained using the system
instrumentation display quantities.
All potential indicators (from L1 to L3 depending on the wiring) are present and are
not blinking. A blinking indicator means that the phase is missing the required
voltage or is below the programmed minimum voltage threshold value.
The LEDs are blinking and the energy direction indicators on the LCD show the correct
energy flow direction.
Required meter seals are in place.
Any information (such as registration and location of the meter) has been recorded.

If the meter is not working correctly after it has been installed, then check for
improper installation or wiring. If the installation and wiring are correct, then verify
these other areas:
the meter installation matches the meter nameplate
the correct type of A1800 ALPHA meter is installed in the existing service
no evidence of mechanical or electrical damage to either the meter or the installation
location
the service voltage falls within the operating range as indicated on the nameplate
the optical port is free of dirt or other obstructions
Marking the utility information card
The utility information card can be removed without breaking seals and removing the
meter cover screws. Note that the direct connect meter uses a blank card.
To remove the utility information:
1. Remove the terminal cover as described above.
2. Grasp the protruding utility information card tab firmly and pull the card out slowly
from under the meter cover.
3. Mark the card as needed.
Figure 7-3. Removing the utility information card
Technical manual 7-6 Installation and removal
Removing the meter from service
Use the appropriate procedure when removing an A1800 ALPHA meter from service.

Use authorized utility procedures to remove metering equipment. Dangerous
voltages are present, and equipment damage, personal injury, or death can
result if safety procedures are not followed.

Circuit-closing devices must be used on current transformer secondaries. This
applies to CT-connected meters. Dangerous currents and voltages are present if
secondaries are open-circuited. Equipment damage, personal injury, or death
can result if circuit-closing devices are not used.
If it becomes necessary to remove an A1800 ALPHA meter from service, use the following
procedure:
1. Before disconnecting the meter, make sure that the existing meter data has been
copied, either manually or electronically using Elster meter support software.
2. Remove the voltage and disconnect the current circuits.
3. Break the seal holding the A1800 ALPHA meter terminal cover in place.
4. Remove the terminal cover screws and take off the terminal cover.
5. Disconnect the wiring.
6. Remove the lower supporting screws.
7. Lift the meter off the top supporting screw.
Removing the battery

The meter should be de-energized before removing the battery. Dangerous
voltages are present; and equipment damage, personal injury, or death can
result if safety precautions are not followed. Use authorized procedures to
remove the battery while power is removed from the meter.
Use the following procedure to remove a battery from an A1800 ALPHA meter:
1. De-energize the meter.
2. Remove the terminal cover to expose the battery well.
3. Firmly grasp the battery and lift it from the well.
4. Disconnect the battery leads from the connector.
5. Replace the terminal cover and ensure the seals are in place.
If the removed battery is still in working condition, it can be stored safely for future use.
Non-functioning batteries should be disposed of according to local laws, regulations, or
electric utility policies.
Technical manual 8-1 Loss compensation
8 Loss compensation
Introduction
What is Loss Compensation?
The Handbook for Electricity Metering defines loss compensation as follows:
A means for correcting the reading of a meter when the metering point and the point
of service are physically separated resulting in measurable losses including I
2
R
losses in conductors and transformers, and iron-core losses. These losses may be
added to, or subtracted from the meter registration.
1
For example, it may be desirable to measure the energy usage on the low voltage side of
a distribution transformer that serves an industrial customer even though the end-point
customer actually owns the transformer and is responsible for any transformer losses. In
this case, the utility billing point is actually the high voltage side of the transformer. Using
loss compensation, the meter on the low voltage side of the transformer can actively adjust
the energy registration to account for the losses in the transformer.
Availability
The loss compensation functionality is available only on the following CT-connected
A1800 ALPHA meter configurations:
2-element
3-element
Software support
A meter with loss compensation must first be programmed with the proper utility rate
configuration using Elster meter support software just as you would with any other
A1800 ALPHA meter. Next, a special programming step is performed to load the proper
loss constants into the meter. This is done with special Windows-based software titled
A1800 ALPHA Meter Loss Compensation Tool.
Calculating the correction values
To configure the loss compensation feature of an A1800 ALPHA meter you must input the
following values into the loss compensation software. These values are site specific and
must be uniquely determined for each loss compensation application.
1
Edison Electric Institute, Handbook for Electricity Metering, 10th edition, Washington, DC: Edison Electric Institute, 2002, p. 16.
Parameter Description
%LWFe Iron watts correction percentage
%LWCu Copper watts correction percentage
%LVFe Iron vars correction percentage
%LVCu Copper vars correction percentage
Technical manual 8-2 Loss compensation
These values must be calculated on the basis of the power transformer test report and, if
line losses are to be included, the characteristics of the primary/secondary conductors at
the specific site in question. The following sections describe these calculations.
Calculation of loss compensation parameters is dependent on the location of the meter
with respect to the power transformer. The rated voltage and rated current used in the
calculations must represent the values on the same side of the power transformer as the
meter is located.
If the meter is located on the secondary side of the power transformer, then the rated
voltage and rated current used in the calculations must be secondary values.
If the meter is located on the primary side of the power transformer, then the rated
voltage and rated current used in the calculations must be primary values.
Gather necessary data
The following information is necessary to calculate the loss compensation configuration
parameters.
Note: There may be one 3-phase transformer or a bank of three single phase
transformers. If there are three single phase transformers then test data is needed
for all three.
Calculate the meter configuration parameters
Step 1. Calculate the following quantities.
Meter current Meter current when power transformer is operating at
maximum rating
Meter voltage Meter voltage when power transformer is operating at rated
voltage
Parameter Description
KVA
rated
Rated kVA of power transformer
V
pri L-L
Primary line-to-line voltage of power transformer
V
sec L-L
Secondary line-to-line voltage of power transformer
LWCu Full load watts loss of power transformer (copper or winding
losses)
LWFe No load watts loss of power transformer (iron or core losses)
%EXC Percent excitation current of the power transformer
%Z Percent impedance of the power transformer
CTR Current transformer ratio for instrument transformers supplying
current to the meter
VTR Voltage transformer ratio for instrument transformers supplying
voltage to the meter
Elements Number of meter elements (use 3- for all 2 -element meters)
Parameter Description
VA
phase
Per phase VA rating of power transformer
V
sec rated
Rated secondary voltage of power transformer
I
sec rated
Rated secondary current of power transformer
V
pri rated
Rated primary voltage of power transformer
Parameter Description
Technical manual 8-3 Loss compensation
I
pri rated
Rated primary current of power transformer
LWFe No load watt loss of power transformer (loss watt iron)
LWCu Full load watt loss of power transformer (loss watt copper)
LVAFe No load VA loss of power transformer (loss VA iron)
LVACu Full load VA loss of power transformer (loss VA copper)
LVFe No load var loss of power transformer (loss var iron)
LVCu Full load var loss of power transformer (loss var copper)
Parameter Equation
VA
phase
If bank of 3 transformers
If one 3-phase transformer
V
sec rated
For 2 element, 3-wire delta
applications
For 3 element, 4-wire wye
applications
V
pri rated
For 2 element, 3-wire delta
applications
For 3 element, 4-wire wye
applications
I
sec rated
All applications
I
pri rated
All applications
Note: For a bank of three single phase transformers the below calculations should be
performed independently for each transformer and then summed to obtain the
total losses.
LWFe Take directly from power transformer test report.
LWCu Take directly from power transformer test report.
Parameter Description
1000 KVA VA
rated phase
=
3
) 1000 kVA (
VA
rated
phase

=
L - L sec rated sec
V V =
3
V
V
L - L sec
rated sec
=
L - L pri rated pri
V V =
3
V
V
L - L pri
rated pri
=
L - L sec
phase
rated sec
V
VA 3
I

=
L - L pri
phase
rated pri
V
VA 3
I

=
Technical manual 8-4 Loss compensation
Step 2. If it is desired to compensate for line losses then calculate the full load watt line
loss and the full load var line loss values (see next section for details on line loss
calculation).
Step 3. Calculate the per element % correction factors, the meter voltage, and the meter
current. These are the values that must be entered into the loss compensation software to
configure the meter properly.
If the meter is on the primary side of the power transformer, then V
rated
= V
pri rated

and I
rated
= I
pri rated
.
If the meter is on the secondary side of the power transformer, then V
rated
= V
sec rated

and I
rated
= I
sec rated
.
LVAFe
LVACu
LVFe
LVCu
Parameter Description
LiW
TOT
Total full load watt line loss (line loss watt)
LiV
TOT
Total full load var line loss (line loss var)
Parameter Equation
%LWFe
%LWCu
%LVFe
Parameter Equation


100
%EXC
1000 kVA
rated


100
%Z
1000 kVArated
2 2
LWFe - LVAFe
2 2
LWCu - LVCu
Elements I V
100 LWFe
rated rated

( )
Elements I V
100 LiW LWCu
rated rated
TOT

+
Elements I V
100 LVFe
rated rated

Technical manual 8-5 Loss compensation


Calculating line loss
Compensation for line losses may include primary losses, secondary losses, or both
depending on the application.
Gather necessary data
The following information is necessary to calculate the line losses.
Step 1. Calculate line resistance and line reactance
The equations below should be applied individually to the primary and the secondary
conductors.
%LVCu
Meter current
Meter voltage
Parameter Description
f Frequency
n Number of conductors
L Line length (units compatible with conductor resistance)
R
a
Conductor resistance (/meter or /kilometer)
GMR
1
1
Either GMR or X
a
is required, but not both. The available information determines which
is used in the calculations.
Geometric mean radius of the phase conductors (in meters)
X
a
1
Inductive reactance of the conductor at 1ft. spacing (/meter or
/kilometer)
Parameter Description
R
L
Line resistance ()
X
L
Line reactance ()
D
eq
Geometric mean distance between phase conductors (in
meters)
D
L1,L2
Distance between Line 1 and Line 2 (in meters)
D
L2,L3
Distance between Line 2 and Line 3 (in meters)
D
L3,L1
Distance between Line 3 and Line 1 (in meters)
Parameter Equation
( )
Elements I V
100 LiV LVCu
rated rated
TOT

+
CTR
I
rated
VTR
V
rated
Technical manual 8-6 Loss compensation
Calculating the reactive component of the impedance is not as straight forward as the
resistance calculation, and the calculation depends on the wiring configuration. The most
common configuration is one where the wires are unbundled and the spacing between
wires is uniform. Other types of wiring, such as bundled conductors, will not be discussed
in this document. Two equations can be used to calculate line reactance. The choice of
which equation to use is based on the whether GMR or X
a
is available.
where:
Step 2. Calculate the line losses.
Note: V
pri L-L
, V
sec L-L
, I
pri rated
, and I
sec rated
are the same values as used in calculation
of transformer losses (see previous section).
When compensating for both transformer and line losses:
Parameter Equation
R
L
Item Equation
X
L
If using GMR
If using X
a
Item Description
LiW
TOT
Total full load watt line loss (line loss watt)
LiV
TOT
Total full load var line loss (line loss var)
V
pri L-L
Primary line-to-line voltage of power transformer
V
sec L-L
Secondary line-to-line voltage of power transformer
I
pri rated
Rated primary current of power transformer
I
sec rated
Rated secondary current of power transformer
Item Equation
LiW
sec
LiV
sec
LiW
pri
a
R L


GMR
D
Log
60
f
0.2794 L
eq

+
eq a
LogD
60
f
2794 . 0 X L
3
1 L , 3 L 3 L , 2 L 2 L , 1 L
D D D Deq =
n R I
sec L
2
rated sec

n X I
sec L
2
rated sec

n R I
pri L
2
rated pri

Technical manual 8-7 Loss compensation
Note: In the special case that you are compensating only for line loss (no transformer
losses), then the values for I
pri rated
and I
sec rated
must be directly specified by the
user. Typically, these two values will be inversely proportional to the rated
secondary and primary voltages of the power transformer. That is,
Step 3. If compensating for both transformer and line losses, return to Step 3 of the
previous section using the above calculated line losses to help calculate the %LWCu and
%LVCu values.
If compensating only for line losses use the following equations to calculate the per
element % correction factors, the meter voltage and the meter current for entry in the loss
compensation software.
If the meter is on the primary side of the power transformer,
I
rated
= I
pri rated
.
If the meter is on the secondary side of the power transformer,
I
rated
= I
sec rated
.
V
rated
is the nominal voltage seen on the high side of the instrument transformer supplying
voltage to the meter.
LiV
pri
LiW
TOT
LiV
TOT
Parameter Equation
%LWFe 0
%LWCu
%LVFe 0
%LVCu
Meter current
Meter voltage
Item Equation
n X I
pri L
2
rated pri

pri sec
LiW LiW +
pri sec
LiV LiV +
rated pri
rated sec
rated sec
rated pri
V
V
I
I
=
Elements I V
100 LiW
rated rated
TOT

Elements I V
100 LiV
rated rated
TOT

CTR
I
rated
VTR
V
rated
Technical manual 8-8 Loss compensation
Calculation example
The following example can be used as a guideline. This is based on the sample
transformer data for loss compensation shown in chapter 10 of the Handbook for Electricity
Metering (10th edition).
2
Application notes:
The application is a bank of three single-phase power transformers.
The metering occurs on the low (secondary) side of a power transformer, and losses
will be added to the measured energy.
There is a delta connection on the secondary of the power transformer and thus a 2-
element meter will be used to measure the service.
Losses are being compensated for the power transformer only (no line losses).
Gather necessary data
Power transformer data (from transformer manufacturer)
Instrument transformer data:
Meter data:
Step 1. Calculate the quantities
2
Edison Electric Institute, Handbook for Electricity Metering, tenth edition, Washington, DC: Edison Electric Institute, 2002, Chapter
10, Special Metering, pp. 249-88.
Parameter Value
Line 1 Line 2 Line 3
KVA
rated
3333 3333 3333
V
pri L-L
115000 115000 115000
V
sec L-L
2520 2520 2520
LWCu 18935 18400 18692
LWFe 9650 9690 9340
%EXC 1.00 1.06 0.91
%Z 8.16 8.03 8.12
Parameter Value
CTR
VTR
Parameter Value
Elements 2
600
5
3000
=
20
120
2400
=
Technical manual 8-9 Loss compensation
Because the metering is on the secondary side of the power transformer, all references to
rated voltage and rated current refer to the secondary rated values.
Phase 1. Calculations
Phase 2. Calculations
Parameter Description
VA
phase
bank of three transformers:
V
rated
secondary side, 2-element delta application:
I
rated
secondary side application:
Parameter Value
LWFe 9650
LWCu 18935
LVAFe
LVACu
LVFe
LVCu
Parameter Value
LWFe 9690
LWCu 18400
3,333,000 1000 3333 1000 kVA
rated
= =
2520 V
L - L sec
=
84 . 2290
2520
000 , 333 , 3
3
V
VA
3
L - L sec
phase
= =
330 , 33
100
00 . 1
1000 3333
100
%EXC
1000 kVA
rated
=


973 , 271
100
16 . 8
1000 3333
100
%Z
1000 kVA
rated
=


975 , 33 9690 330 , 35
LWFe - LVFe
2 2
2 2
=
313 , 271 935 , 18 923 , 271
LWCu - LVACu
2 2
2 2
=
Technical manual 8-10 Loss compensation
Phase 3. Calculations
LVAFe
LVACu
LVFe
LVCu
Parameter Value
LWFe 9340
LWCu 18,692
LVAFe
LVACu
LVFe
Parameter Value
330 , 35
100
06 . 1
1000 3333
100
EXC %
1000 kVA
rated
=


640 , 267
100
03 . 8
1000 3333
100
Z %
1000 kVA
rated
=


975 , 33 9690 330 , 35
LWFe - LVAFe
2 2
2 2
=
007 , 267 400 , 18 640 , 267
LWCu - LVACu
2 2
2 2
=
330 , 30
100
91 . 0
1000 3333
100
EXC %
1000 kVA
rated
=


640 , 270
100
8.12
1000 3333
100
%Z
1000 kVA
rated
=


856 , 28 9340 330 , 33
LWFe - LVAFe
2 2
2 2
=
Technical manual 8-11 Loss compensation
From the above:
Step 2. Compensate for line loss (if needed).
Per the stated assumptions, there is no compensating for line losses:
Step 3. Now the per element % correction factors may be calculated:
LVCu
Parameter Value
LWFe 9650 + 9690 + 9340 = 28,680
LWCu 18,935 + 18,400 + 18,692 = 56,027
LVAFe 33,330 + 35,330 + 30,330 = 98,990
LVACu 271,973 + 267,640 + 270,640 = 810,253
LVFe 31,902 + 33,975 + 28,856 = 94,734
LVCu 271,313 + 267,007 + 269,993 = 808,313
Parameter Value
LiW
TOT
0
LiV
TOT
0
Parameter Value
%LWFe
%LWCu
%LVFe
Parameter Value
993 , 269 692 , 18 640 , 270
LWCu - LVACu
2 2
2 2
=
2484 . 0
2 229084 2520
100 680 , 28
Elements I V
100 LWFe
rated rated
=

( )
4853 . 0
2 84 . 2290 2520
100 027 , 56
Elements I V
100 LiW LWCu
rated rated
TOT
=


+
8205 . 0
2 84 . 2290 2520
100 734 , 94
Elements I V
100 LVFe
rated rated
=

Technical manual 8-12 Loss compensation


Enter Data
Summary of calculated values to enter in A1800 ALPHA Meter Loss Compensation Tool
Internal meter calculations
To understand the loss compensation calculations, it is first necessary to understand a little
bit about how the A1800 ALPHA meter engine operates. Internal to the meter engine, V
rms

and I
rms
are measured independently on each phase every two line cycles. These values
are used to perform the normal energy calculations on each phase every two line cycles.
The individual phase measurements are then summed. This drives an internal
accumulator in the meter engine that generates a pulse to the microcontroller when a
threshold level is reached. The threshold level at which a pulse is generated is known as
the meter K
e
(energy per pulse). There are separate calculations, separate accumulators
and separate K
e
pulses generated for each measured energy quantity (for example, kWh-
delivered, kvarh-delivered).
When loss compensation is turned on, additional calculations are performed. Every two
line cycles on each phase, the V
rms
and I
rms
values used in the normal energy calculations
are also used to calculate a watt compensation value and a var compensation value. The
following equations indicate the compensation terms that are calculated and applied to
the normal energy measurements every two line cycles.
%LVCu
Meter current
Meter voltage
Parameter Value
Registration Add losses
Iron watts correction % (%LWFe) 0.2484
Copper watts correction % (%LWCu) 0.4853
Iron vars correction % (%LVFe) 0.8205
Copper vars correction % (%LVCu) 7.0009
Meter current 3.82
Meter voltage 126
Parameter Value
( )
0009 . 7
2 84 . 2290 2520
100 313 , 808
Elements I V
LiV LVCu
rated rated
TOT
=


+
A 3.82
600
84 . 2290
CTR
I
rated
= =
V 26 1
20
2520
VTR
V
rated
= =
Technical manual 8-13 Loss compensation
For a 3-element meter, watts and vars are compensated every two line cycles according to
the following equations:
For a 2-element meter, watts and vars are compensated every two line cycles according to
the following equations:
Where:
The A1800 ALPHA Meter Loss Compensation Tool calculates R, G, X, and B using the
following formulas and then programs these values into the meter.
Compensation Equation
W
var
Compensation Equation
W
var
Term Description
R Per element resistance
G Per element conductance
X Per element reactance
B Per element susceptance
I
xmeas
Per phase rms current
V
xmeas
Per phase rms voltage
Item Equation
R
( )
( )
2
meas c
2
meas L2
2
meas L1
2
meas L3
2
meas L2
2
meas L1
V V V G
I I I R
+ +
+ + +
( )
( )
4
meas c
4
meas L2
4
meas L1
2
meas L3
2
meas L2
2
meas L1
V V V B
I I I X
+ +
+ + +
( )
( )
2
meas c
2
meas L1
2
meas L3
2
meas L1
V V G
I I R
+
+ +
( )
( )
4
meas c
4
meas L1
2
meas L3
2
meas L1
V V B
I I X
+
+ +
100 current Meter
voltage Meter %LWCu

Technical manual 8-14 Loss compensation


The compensation terms will be either positive or negative depending on whether losses
are configured to be added or subtracted from the energy measurements. So, the key
difference on meters with loss compensation is that every two line cycles on each phase,
the calculated W compensation value is summed with the normal Wh energy calculations.
Similarly, the var compensation term is summed per phase every two line cycles with the
normal varh energy calculations. From that point everything is essentially the same
(individual phases are then summed to drive an accumulator).
Note regarding two-element meters: Two-element ALPHA meters are unique in that they
create an artificial internal reference that is used to measure the phase voltages. For
example, line 3 experiences a loss of voltage while the meter remains powered (either
from line 1 or from an auxiliary supply) the internal meter engine will still measure a line 3
voltage equal to one-half of the line 1 voltage. In applications where loss compensation is
not applied this has no impact on the measurement of energy because no power will be
drawn by the load on line 3. That is, line 3 current equals zero and so the net energy
measured on line 3 is accurately calculated as zero. However, in the special case of a
meter that is compensating for transformer losses, the no-load compensation terms are
based solely on the measured voltage on each phase (see above formulas). Therefore, on
2-element ALPHA meters with loss compensation enabled, if line 3 voltage is lost while the
meter remains powered, the no load compensation terms for line 3 will be in error
because they will be calculated based on one-half the line 1 voltage.
The same situation would result if line 1 experiences a loss of voltage.
G
X
B
Item Equation
100 voltage Meter
current Meter %LWFe

100 current Meter


voltage Meter %LVCu

( ) 100 voltage Meter


current Meter %LVFe
3

Technical manual 8-15 Loss compensation


Meter outputs affected by compensation
When loss compensation is enabled on an A1800 ALPHA meter, all of the following
collected data use the compensated values:
all register billing data
all pulse profile data
all KYZ pulse outputs
all test pulses (both in the LCD and on the LED)
Compensation does not affect instrumentation values or the meter features that use
instrumentation values. Regardless of the status of loss compensation, all instrumentation
values reflect the actual measured values as seen at the meter terminals. For example, per
phase voltage values are not affected (whether displayed on the LCD or reported in meter
support software). Likewise TRueQ functions and instrumentation profiling values are not
affected when compensation is active.
Testing a meter with compensation
The LEDs on A1800 ALPHA meters always reflect the current measurement algorithm in the
meter engine. That is, if compensation is turned on then the LEDs will indicate
compensated energy. If compensation is turned off then the LEDs will indicate
uncompensated energy. Because the LED always reflects the state of the compensation it
reduces the chance that a meter with active compensation is accidentally installed
unknowingly.
Using the A1800 ALPHA Meter Loss Compensation Tool, it is possible to configure the
meter to automatically turn off compensation whenever the meter enters test mode. This
may or may not be desired depending on utility testing practices.
The loss compensation software also permits the A1800 ALPHA meter loss compensation
function to be manually turned off and turned on without altering the loss compensation
parameters configured in the meter.
Utilities may desire to calculate the expected test results of a compensated meter and then
test the meter with active compensation to verify that the expected results are obtained.
Technical manual 8-16 Loss compensation
Technical manual A-1 Glossary
A Glossary
button. The push button that activates the alternate mode. It also can be used to control
the scrolling of display quantities in the different operating modes.
Alpha Keys. A system combining hardware and software to upgrade existing
A1800 ALPHA meters. Keys allow addition of new functionality to an existing meter for an
additional fee.
alternate mode. The operating mode in A1800 ALPHA meters used to display a second
set of display quantities on the LCD. It is generally activated by pressing the Q button on the
meter. A typical use of the alternate mode is to display non-billing data as programmed by
Elster meter support software.
AvgPF. see average power factor.
average power factor. Calculated once every second, when the meter is not in test mode,
using the following formula:
billing data. The measured quantities recorded and stored by the meter for use in billing
the consumer. May also be referred to as tariff data.
bit. Short for binary digit. It is the smallest information unit used in data communications
and storage.
coincident. Information regarding one parameter occurring at the same time as another.
For example, coincident kvar demand is the kvar demand occurring during the interval of
peak kW demand.
communication session count. The number of data-altering communications occurring
since the A1800 ALPHA meter was last programmed or a clear of the values and status.
complete LCD test. A display showing 8 in all the display areas and all identifiers on the
LCD turned on. This confirms that all segments are operating properly.
continuous cumulative. A display technique used with demand calculations and similar
to cumulative demand except continuous cumulative demand is updated constantly.
CTR. see current transformer ratio.
cumulative. A display technique used with demand calculations. Upon a demand reset,
the present maximum demand is added to the sum of the previous maximum billing
period demand values.
current transformer ratio. The ratio of the primary current to the secondary current of a
current transformer. For example, 400 A to 5 A would have a current transformer ratio of
400:5 or 80:1.
2 2
kWh kvarh
kWh
AvgPF
+
=
Technical manual A-2 Glossary
data-altering communication. Any communication that performs any of the following
actions:
writes to a meter table
clears data
resets log pointers or data set pointers
resets the demand
performs a self read
performs a season change
del. see delivered.
delivered. Used to specify the energy delivered (provided) to an electric service.
demand. The average power computed over a specific time.
demand forgiveness. The number of minutes that demand will not be calculated
following a recognized power outage. This provides a time period immediately following
the restoration of power during which startup power requirements will not be included in
the calculated demand.
demand interval. The time period over which demand is calculated. Demand interval
must be evenly divisible into 60 minutes.
demand reset. The act of resetting the present maximum demand to zero.
demand reset count. The total number of demand resets since the meter was last
programmed.
demand reset date. The date of the last demand reset.
demand threshold. The present value of demand which when reached initiates a relay
closure or other programmed action.
display quantity. Any value available for display on the LCD.
EEPROM. Acronym for electrically erasable programmable read only memory. This
memory retains all information even when electric power is removed from the circuit.
EOI. see end of interval.
end of interval. The indication that the end of the time interval used to calculate demand
has occurred. An EOI indicator is on the LCD and an optional relay can be supplied to
provide an EOI indication.
energy. Power measured over time.
error display. The method by which the meter displays an error message which consists of
E and numeric codes. The code indicates a condition or conditions that can adversely
affect the proper operation of the meter.
event log. The event log provides a record of entries that date and time stamp specific
events such as:
power outages
demand resets
entering test mode
time changes
external display multiplier. Used when the transformer factor is larger than can be stored
within the A1800 ALPHA meter. When programmed with Elster Metering meter support
software for an external display multiplier, display quantities read from the meter LCD must
be manually multiplied by this value to yield proper readings.
Technical manual A-3 Glossary
factory default. Operating parameters that are programmed into the meter at the factory
and assure that the meter is ready for correct energy measurement when installed.
four quadrant metering. See Figure A-1 for an illustration of energy relationships for
delivered and received real power (kW), apparent power (kVA), and reactive power (kVAR).
Figure A-1. Four quadrant metering quantity relationships
IC. see integrated circuit.
instrument transformer. A transformer used to reduce current and voltage to a level
which does not damage the meter. Meter readings will need to be increased by the
transformer ratios to reflect the energy and demand values on the primary side of the
instrument transformer.
integrated circuit. Generally used to reference the custom meter circuit used in the
A1800 ALPHA meter for per phase voltage and current sampling plus energy
measurements.
K
e
. The smallest discrete amount of energy available within the meter. It is the value of a
single pulse used between the meter IC and the microcontroller.
kW overload value. The kW threshold which, when exceeded, will cause the display of the
kW overload warning message.
LC. see load control.
LCD. see liquid crystal display.
LP. see load profile.
line frequency. The frequency of the AC current on the transmission line, often used in
timekeeping applications in lieu of the internal oscillator. Depending upon the country or
region, the line frequency is either 50Hz or 60Hz.
liquid crystal display. The LCD allows metered quantities and other information about the
A1800 ALPHA meter and installed service to be viewed. Display quantities are
programmable through Elster meter support software.
load control. Used to describe a relay dedicated to operate based upon entering a
specific TOU rate period or when a demand threshold is reached.
kvar Delivered
kvar Received
k
W

D
e
l
i
v
e
r
e
d
k
V
A

D
e
l
i
v
e
r
e
d
k
V
A

R
e
c
e
i
v
e
d
k
W

R
e
c
e
i
v
e
d
Q1
Q4
Q2
Q3
Q1
Q4
Q2
Q3
Lag Lag Lag Lag
Lead Lead Lead Lead
Technical manual A-4 Glossary
load profiling. Load profiling records energy usage per a specific time interval while the
meter is energized. Load profiling data provides a 24 hour record of energy usage for
each day of the billing period.
maximum demand. The highest demand calculated during any demand interval over a
billing period.
microcontroller. A single chip that contains the following components:
main processor
RAM
ROM
clock
I/O control unit
nonrecurring dates. Holidays or other specific dates that are not based upon a
predictable, repeated pattern.
normal mode. The default operating mode for the A1800 ALPHA meter. Typically, normal
mode displays billing data on the LCD following a programmed sequence.
optical port. A photo-transistor and an LED on the face of the meter that is used to transfer
data between a computer and the meter via pulses of light.
outage log. Display quantity that shows the cumulative total outage time in minutes.
P/R. see pulse ratio.
previous billing data. Used to describe the billing data recorded at the demand reset. See
also self read.
previous season data. Used to describe the billing data for the season preceding the
present billing season.
primary rated. A condition where the energy and demand as measured by the meter are
increased by the current and voltage transformer ratios. Meter data will reflect the energy
and demand actually transferred on the primary side of the instrument transformers.
program change date. The date when the meter program was last changed.
program mode. The operating mode of the meter in which full reprogramming of
metrological parameters is permitted.
pulse ratio. Pulses per equivalent disk revolution. On ALPHA meters, 1 revolution is equal
to 1 K
h
period.
pulse relay. A relay used with the meter to provide output pulses from the meter to an
external pulse collector. Each pulse represents a specific amount of energy consumption.
rec. see received.
received. Used to specify the energy received by the utility at an electric service.
recurring dates. Holidays or other special dates that occur on a predictable basis.
self read. The capturing of current billing data and storing it in memory. Self reads are
scheduled events that can be triggered by the specific day of month, every set number of
days, or command by Elster meter support software. See also previous billing data.
tariff data. See billing data.
TOU. see time-of-use.
TOU meter. A meter that records energy usage and demand data on a time-of-use basis.
Technical manual A-5 Glossary
test mode. The test mode stores billing data in a secure memory location while the meter
measures and displays energy and demand data for testing purposes. The TEST identifier
will flash while the test mode is active. When test mode is exited, the accumulated test
data is discarded and the original billing data is restored.
timekeeping. The ability of the meter to keep a real time clock, including date and time.
time-of-use. A billing rate that records energy usage and demand data related to specific
times during the day. See also timekeeping.
transformer-rated. A meter designed to work with current or voltage transformers. The
maximum current of a transformer-rated A1800 ALPHA meter is typically 20 A.
voltage transformer ratio. The ratio of primary voltage to secondary voltage of a
transformer. For example, 12,000 V to 120 V would have a voltage transformer ratio of
100:1.
VTR. see voltage transformer ratio.
watthour constant. A meter constant representing the watthours per output pulse on the
LED. Historically, the constant represents the energy equivalent to one revolution of an
electromechanical meter.
Technical manual A-6 Glossary
Technical manual B-1 Display table
B Display table
Display format
Displayable items are described in Display list items on page B-2. The A1800 ALPHA
meter supports up to 64 quantities for display on the LCD. The LCD can be divided into
different regions, as described in Table B-1. See Indicators and controls on page 3-1 for
more detailed information on the LCD regions.
Figure B-1. A1800 ALPHA meter LCD
Table B-1. LCD regions
Item Description
quantity identifier identifies the displayed quantity. Using Elster meter support
software, an identifier can be assigned to most quantities.
For instrumentation quantities, the identifiers are fixed.
alternate display
indicator
indicates that the meter is currently displaying items in the
alternate display list (see button on page 3-5)
active COM port
indicators
indicates that a communication session is in progress and
the communication port that is being used: either COM 0,
COM 1, or COM 2
power/energy units
identifier
indicates the unit of measurement for the quantity currently
displayed on the LCD.
display indicators indicates whether the meter is currently doing the following:
accumulating in tariff (T1 - T4)
has reached the end of an interval (EOI)
compensating for transformer line loss (LC)
indicating that either the terminal cover or the meter cover
has been removed
is operating in test mode (see Test mode on page 3-8)
Energy direction
indicators
Error/warning indicator
Low battery indicator
Phase
indicators (3)
Quantity identifier
Alternate mode
indicator
Comm. port
indicator
Power/energy
units identifier
Tariff indicators 1 to 4
(left to right)
EOI indicator
LC indicator
Cover removed
indicator
Test mode
indicator
Reserved
Display
quantity
Technical manual B-2 Display table
Display list items
The display list items for the normal mode, alternate mode, and test mode are
programmed from the 64 available items.
The display format for all displayable items can be programmed using Elster meter
support software. The A1800 ALPHA meter LCD is capable of supporting the following
characters and symbols:
all numbers (0 to 9)
all Latin-based alphabetical characters
symbols such as (degree), * (asterisk), [ (left bracket), and ] (right bracket)
Additional display items may also be available depending upon the version of Elster meter
support software. See the software documentation for a list of the displayable items.
Displayable items can be grouped into the following categories:
LCD test
general meter information
meter configuration
status
metered quantities
average power factor
coincident demand and power factor
display quantity Shows metered quantities or other displayable information.
From 3 to 8 total digits with up to 9 decimal places can be
used. These digits are also used to report the following:
operational errors
system instrumentation and service test errors
warnings
communication codes
display identifiers more precisely identifies the information presented on the
LCD.
energy direction
indicators
indicates the directions of active (P) and reactive (Q) energy
flow (positive energy flow is energy delivered to the
consumer load, while reverse energy flow is energy received
from the consumer load)
error indicator indicates either of the following:
flashes when any error flag is set
remains on if a displayable warning flag is set and no
error exists
low battery indicator if the indicator is turned on, the battery warning flag has
been set.
phase indicators L1, L2, and L3 (Line 1, Line 2, and Line 3, respectively)
correspond to a phase voltage present on the A1800 ALPHA
meter connections.
If the indicators are on, then all phase voltages are
present.
If an indicator is blinking, then that phase voltage is either
missing or below the defined threshold for voltage sag
detection.
Table B-1. LCD regions
Item Description
Technical manual B-3 Display table
system instrumentation
system service test
errors and warnings
communication codes
Default display formats
The display areas on the LCD (such as the display quantity and display identifier) are
programmable through Elster meter support software. See Display format on page B-1
for more information.
The following sections describe the default behavior of the A1800 ALPHA meter display.
See Table B-2 for a description of some of the special characters that have been used in
the display quantity examples.
LCD test
The A1800 ALPHA meter tests the LCD by displaying all the identifiers, as shown in
Figure B-2. The meter tests the LCD for 3 seconds after power up.
Figure B-2. LCD all segment test
Table B-2. Characters in display quantity examples
Character Represents
Blank (space)
. Decimal
- hyphen; represents testing in progress
* asterisk; represents all 16 character segments on
: colon; separates time units (hh:mm), etc.
a Any alphanumeric character displayable on the LCD.
dd Numeric character; represents day (01 to 31)
H Indicates the day type is holiday
hh Numeric character; represents time in hours (01 to 24)
mm Numeric character; represents time in minutes (00 to 59)
MM Numeric character; represents month (01 to 12)
x Any numeric character.
ss Numeric character; represents time in seconds (00 to 59)
YY Numeric character; represents two digit year (00 to 99)
P - P +
Q
Q
+
-
L L L 1 2 3
COM 0 1 2
Technical manual B-4 Display table
General meter information
General meter information quantities are items that are not associated with any particular
pulse or instrumentation source.
Meter configuration
Display description Display quantity Quantity ID Units ID
LCD test [all segment test] ******* ******** [all segments]
Display description Display quantity Quantity ID Units ID
Identifier String 1 [Account:1] aaaaaaaa ID 1-1 of 4
Identifier String 1 [Account:2] aaaaaaaa ID 1-2 of 4
Identifier String 1 [Account:3] aaaa ID 1-3 of 4
Identifier String 1 [Account:4] ID 1-4 of 4
Identifier String 2 [Meter ID:1] aaaaaaaa ID 2-1 of 4
Identifier String 2 [Meter ID:2] aaaaaaaa ID 2-2 of 4
Identifier String 2 [Meter ID:3] aaaa ID 2-3 of 4
Identifier String 2 [Meter ID:4] ID 2-4 of 4
Meter type A1800 TYPE
Firmware product xxx FW
Firmware version xxx FWV
Firmware revision xxx FWR
Hardware version xxx HDWV
Hardware revision xxx HDWR
DSP code xxx DSP
DSP code revision xxx DSPR
Meter Programmer ID xxxxxxxx
LCD test [all segment test] ******* ******** [all segments]
Display description Display quantity Quantity ID Units ID
Program ID xxxxxxxx PRG ID
Pulse ratio (P/R) x.xxxxxxx P/R
Pulse output ratio [imp/kWh] xxxxx.xxx imp/kWh
Current transformer (CT) ratio xxxxxxxx CT
Voltage transformer (VT) ratio xxxxxxxx VT
Demand interval - normal mode xxxxxxxx INTERV
Demand interval - test mode xxxxxxxx INTERVT
Watthours per pulse (K
e
) xxxxxxxx Wh/Imp
Meter K
h
xxxxxxxx Kh
Transformer factor (CT VT) xxxxxxxx CTxVT
External multiplier xxx.xxxxx ExtMult
Technical manual B-5 Display table
Status
Demand overload value xxxxx.xxx DmdOvld
Display description Display quantity Quantity ID Units ID
Communication session count (port 1) xxxxxxxx Com1No
Communication session count (port 2/optical) xxxxxxxx Com2No
Days since demand reset xxxxxxxx ResDays
Days since input pulse xxxxxxxx ImpDays
Number of manual demand resets xxxxxxxx RstPress
Number of all demand resets xxxxxxxx DmdRes
Power outage count xxxxxxxx Outages
Initial remote baud (port 1) xxxxxxxx COM1bps
Initial remote baud (port 2) xxxxxxxx COM2bps
Transformer Loss Comp Status xxxxxxxx
TRueQ Status (On/Off) On
Off
Outage Log
Program Change Date (port 1) MM:dd:YY
Program Change Date (port 2/optical) MM:dd:YY
Last Elster configuration change date MM:dd:YY CnfDate
Demand reset date MM:dd:YY DmdRes
Last power outage start date MM:dd:YY Outage
Last power outage start time hh:mm Outage
Last power outage end date MM:dd:YY Restore
Last power outage end time hh:mm Restore
Present date MM:dd:YY Date
Present time hh:mm Time
Present day of week aaaaaaaa Day
Present season aaaaaaaa Season
Date of last pending table activation MM:dd:YY TblActv
Time Left in interval hh:mm Sub Int
Pulse count for quantity (Wh-delivered) xxxxxxxx ImpWhD
Pulse count for quantity (alternate-delivered) xxxxxxxx ImpE2D
Pulse count for quantity (Wh-received) xxxxxxxx ImpWhR
Pulse count for quantity (alternate-received) xxxxxxxx ImpE2R
Self Read Date MM:dd:YY
Effective Date for Rates/Special Dates MM:dd:YY
Number of Write Sessions (port 1) xxxxxxxx
Number of Write Sessions (port 2/optical) xxxxxxxx
Display description Display quantity Quantity ID Units ID
Technical manual B-6 Display table
Metered quantities
A1800 ALPHA meters can measure two quantities. Meters with the optional 4-quadrant
metering can measure eight quantities. The A1800 ALPHA meter can display the available
metered quantities for each meter type.
To indicate a self read quantity, the LCD will use the last two characters of the quantity
identifier to indicate the last self read number (01 to 35).
Display description Display ID Display quantity Quantity ID Units ID
Current billing, Previous billing, Previous season, Last self read
Total energy xxxxxxxx Deliver
Receive
Q1
Q2
Q3
Q4
kWh/kVAh/kvarh
Maximum demand xxxxxxxx Del MD
Rec MD
Q1 MD
Q2 MD
Q3 MD
Q4 MD
kW/kVA/kvar
Date of maximum demand MM:dd:YY MD Date
Time of maximum demand hh:mm MD Time
Cumulative demand xxxxxxxx Del CMD
Rec CMD
Q1 CMD
Q2 CMD
Q3 CMD
Q4 CMD
kW/kVA/kvar
Tariff 1 energy T1 xxxxxxxx Deliver
Receive
Q1
Q2
Q3
Q4
kWh/kVAh/kvarh
Tariff 1 maximum demand T1 xxxxxxxx Del MD
Rec MD
Q1 MD
Q2 MD
Q3 MD
Q4 MD
kW/kVA/kvar
Tariff 1 date of maximum demand T1 MM:dd:YY MD Date
Tariff 1 time of maximum demand T1 hh:mm MD Time
Tariff 1 cumulative demand T1 xxxxxxxx Del CMD
Rec CMD
Q1 CMD
Q2 CMD
Q3 CMD
Q4 CMD
kW/kVA/kvar
Technical manual B-7 Display table
Tariff 2 energy T2 xxxxxxxx Deliver
Receive
Q1
Q2
Q3
Q4
kWh/kVAh/kvarh
Tariff 2 maximum demand T2 xxxxxxxx Del MD
Rec MD
Q1 MD
Q2 MD
Q3 MD
Q4 MD
kW/kVA/kvar
Tariff 2 date of maximum demand T2 MM:dd:YY MD Date
Tariff 2 time of maximum demand T2 hh:mm MD Time
Tariff 2 cumulative demand T2 xxxxxxxx Del CMD
Rec CMD
Q1 CMD
Q2 CMD
Q3 CMD
Q4 CMD
kW/kVA/kvar
Tariff 3 energy T3 xxxxxxxx Deliver
Receive
Q1
Q2
Q3
Q4
kWh/kVAh/kvarh
Tariff 3 maximum demand T3 xxxxxxxx Del MD
Rec MD
Q1 MD
Q2 MD
Q3 MD
Q4 MD
kW/kVA/kvar
Tariff 3 date of maximum demand T3 MM:dd:YY MD Date
Tariff 3 time of maximum demand T3 hh:mm MD Time
Tariff 3 cumulative demand T3 xxxxxxxx Del CMD
Rec CMD
Q1 CMD
Q2 CMD
Q3 CMD
Q4 CMD
kW/kVA/kvar
Tariff 4 energy T4 xxxxxxxx Deliver
Receive
Q1
Q2
Q3
Q4
kWh/kVAh/kvarh
Tariff 4 maximum demand T4 xxxxxxxx Del MD
Rec MD
Q1 MD
Q2 MD
Q3 MD
Q4 MD
kW/kVA/kvar
Display description Display ID Display quantity Quantity ID Units ID
Current billing, Previous billing, Previous season, Last self read
Technical manual B-8 Display table
Average power factor
For each average power factor, the following items are available for display.
Coincident demand and power factor
The A1800 ALPHA meters can measure two coincident quantities. Additionally, meters with
the 4-quadrant metering option can measure four coincident quantities. Coincident
quantities are configurable with Elster Metering meter support software to be any demand
or average power factor value captured at the time of a maximum demand value. For
each coincident value, the following items is available for display:
Cumulative demand
The A1800 ALPHA meter records either the cumulative or continuous cumulative demand.
Tariff 4 date of maximum demand T4 MM:dd:YY MD Date
Tariff 4 time of maximum demand T4 hh:mm MD Time
Tariff 4 cumulative demand T4 xxxxxxxx Del CMD
Rec CMD
Q1 CMD
Q2 CMD
Q3 CMD
Q4 CMD
kW/kVA/kvar
Present Interval (current billing only)
Previous Interval (current billing only)
Display description Display ID Display quantity Quantity ID Units ID
Average power factor xxxxxxxx AvgPF
Tariff 1 average power factor T1 xxxxxxxx AvgPF
Tariff 2 average power factor T2 xxxxxxxx AvgPF
Tariff 3 average power factor T3 xxxxxxxx AvgPF
Tariff 4 average power factor T4 xxxxxxxx AvgPF
Display description Display ID Display quantity Quantity ID Units ID
Coincident demand xxxxxxxx CoinDmd kW/kVA/kvar
Tariff 1 coincident demand T1 xxxxxxxx CoinDmd kW/kVA/kvar
Tariff 2 coincident demand T2 xxxxxxxx CoinDmd kW/kVA/kvar
Tariff 3 coincident demand T3 xxxxxxxx CoinDmd kW/kVA/kvar
Tariff 4 coincident demand T4 xxxxxxxx CoinDmd kW/kVA/kvar
Coincident power factor x.xxx CoinPF kW/kVA/kvar
Tariff 1 coincident power factor T1 x.xxx CoinPF kW/kVA/kvar
Tariff 2 coincident power factor T2 x.xxx CoinPF kW/kVA/kvar
Tariff 3 coincident power factor T3 x.xxx CoinPF kW/kVA/kvar
Tariff 4 coincident power factor T4 x.xxx CoinPF kW/kVA/kvar
Display description Display ID Display quantity Quantity ID Units ID
Cumulative demand xxxxxxxx CumDmd kW/kVA/kvar
Display description Display ID Display quantity Quantity ID Units ID
Current billing, Previous billing, Previous season, Last self read
Technical manual B-9 Display table
System instrumentation
The A1800 ALPHA meter can display system instrumentation quantities. See System
instrumentation on page 4-1 for a listing of the instrumentation quantities that can be
displayed.
Tariff 1 cumulative demand T1 xxxxxxxx CumDmd kW/kVA/kvar
Tariff 2 cumulative demand T2 xxxxxxxx CumDmd kW/kVA/kvar
Tariff 3 cumulative demand T3 xxxxxxxx CumDmd kW/kVA/kvar
Tariff 4 cumulative demand T4 xxxxxxxx CumDmd kW/kVA/kvar
Display description Display quantity Quantity ID Units ID
Line frequency xx.xxHz L123
Line 1 voltage (secondary)
Line 1 voltage (primary)
xxx.xxx V
xxx.xxxkV
L1
Line 2 voltage (secondary)
Line 2 voltage (primary)
xxx.xxx V
xxx.xxxkV
L2
Line 3 voltage (secondary)
Line 3 voltage (primary)
xxx.xxx V
xxx.xxxkV
L3
Line 1 current (secondary)
Line 1 current (primary)
xxx.xxx A
xxx.xxxkA
L1
Line 2 current (secondary)
Line 2 current (primary)
xxx.xxx A
xxx.xxxkA
L2
Line 3 current (secondary)
Line 3 current (primary)
xxx.xxx A
xxx.xxxkA
L3
Line 1 power factor xx.xx L1 COS
Line 2 power factor xx.xx L2 COS
Line 3 power factor xx.xx L3 COS
Line 1 power factor angle xxx.xx L1
Line 2 power factor angle xxx.xx L2
Line 3 power factor angle xxx.xx L3
Line 1 voltage phase angle xxx.xxV L1
Line 2 voltage phase angle xxx.xxV L2
Line 3 voltage phase angle xxxx.xV L3
Line 1 current phase angle xxx.xA L1
Line 2 current phase angle xxx.xA L2
Line 3 current phase angle xxx.xA L3
Line 1 kW (primary)
Line 1 kW (secondary)
xxxx.xxxx
xxx.xxx
L1 kW
MW
Line 2 kW (primary)
Line 2 kW (secondary)
xxxx.xxxx
xxx.xxx
L2 kW
MW
Line 3 kW (primary)
Line 3 kW (secondary)
xxxx.xxxx
xxx.xxx
L3 kW
MW
Line 1 kvar (primary)
Line 1 kvar (secondary)
xxxx.xxxx
xxx.xxx
L1 kvar
Mvar
Display description Display ID Display quantity Quantity ID Units ID
Technical manual B-10 Display table
Line 2 kvar (primary)
Line 2 kvar (secondary)
xxxx.xxxx
xxx.xxx
L2 kvar
Mvar
Line 3 kvar (primary)
Line 3 kvar (secondary)
xxxx.xxxx
xxx.xxx
L3 kvar
Mvar
Line 1 kVA (primary)
Line 1 kA (secondary)
xxxx.xxxx
xxx.xxx
L1 kVA
MVA
Line 2 kVA (primary)
Line 2 kA (secondary)
xxxx.xxxx
xxx.xxx
L2 kVA
MVA
Line 3 kVA (primary)
Line 3 kA (secondary)
xxxx.xxxx
xxx.xxx
L3 kVA
MVA
System kW (primary)
System kW (secondary)
xxxx.xxxx
xxx.xxx
L123 kW
MW
System kvar (primary) (arithmetic)
System kvar (secondary) (arithmetic)
xxxx.xxxx
xxx.xxx
L123 kvar
Mvar
System kVA (primary) (arithmetic)
System kVA (secondary) (arithmetic)
xxxx.xxxx
xxx.xxx
L123 kVA
MVA
System power factor (arithmetic) xx.xx L123.COS
System power factor angle (arithmetic) xx.xx L123
System kvar (primary) (vectorial)
System kvar (secondary) (vectorial)
xxxx.xxxx
xxx.xxx
L123 kvar
Mvar
System kVA (primary) (vectorial)
System kVA (secondary) (vectorial)
xxxx.xxxx
xxx.xxx
L123 kVA
MVA
System power factor (vectorial) xx.xx L123.COS
System power factor angle (vectorial) xx.xx L123
Line 1 voltage % total harmonic distortion (THD) xx.xx%V L1.H2-15
Line 2 voltage % total harmonic distortion (THD) xx.xx%V L2.H2-15
Line 3 voltage % total harmonic distortion (THD) xx.xx%V L3.H2-15
Line 1 current % total harmonic distortion (THD) xx.xx%A L1.H2-15
Line 2 current % total harmonic distortion (THD) xx.xx%A L2.H2-15
Line 3 current % total harmonic distortion (THD) xx.xx%A L3.H2-15
Line 1 total demand distortion (TDD) xx.xx A L1 TDD
Line 2 total demand distortion (TDD) xx.xx A L2 TDD
Line 3 total demand distortion (TDD) xx.xx A L3 TDD
Line 1 fundamental voltage magnitude (secondary)
Line 1 fundamental voltage magnitude (primary)
xxx.xxx V
xxx.xkV
L1 H1
Line 2 fundamental voltage magnitude (primary)
Line 2 fundamental voltage magnitude (secondary)
xxx.xxxkV
xxx.x V
L2 H1
Line 3 fundamental voltage magnitude (primary)
Line 3 fundamental voltage magnitude (secondary)
xxx.xxxkV
xxx.x V
L3 H1
Line 1 fundamental current magnitude (primary)
Line 1 fundamental current magnitude (secondary)
xxx.xxxkA
xxx.x A
L1 H1
Line 2 fundamental current magnitude (primary)
Line 2 fundamental current magnitude (secondary)
xxx.xxxkA
xxx.x A
L2 H1
Line 3 fundamental current magnitude (primary)
Line 3 fundamental current magnitude (secondary)
xxx.xxxkA
xxx.x A
L3 H1
Display description Display quantity Quantity ID Units ID
Technical manual B-11 Display table
System service tests
The A1800 ALPHA meter can display the validity of the electricity service where it is
installed. See System service tests on page 4-5 for more information.
Line 1 2nd harmonic voltage magnitude (primary)
Line 1 2nd harmonic voltage magnitude (secondary)
xxx.xxxkV
xxx.x V
L1 H2
Line 2 2nd harmonic voltage magnitude (primary)
Line 2 2nd harmonic voltage magnitude (secondary)
xxx.xxxkV
xxx.x V
L2 H2
Line 3 2nd harmonic voltage magnitude (primary)
Line 3 2nd harmonic voltage magnitude (secondary)
xxx.xxxkV
xxx.x V
L3 H2
Line 1 2nd harmonic current magnitude (primary)
Line 1 2nd harmonic current magnitude (secondary)
xxx.xxxkA
xxx.x A
L1 H2
Line 2 2nd harmonic current magnitude (primary)
Line 2 2nd harmonic current magnitude (secondary)
xxx.xxxkA
xxx.x A
L2 H2
Line 3 2nd harmonic current magnitude (primary)
Line 3 2nd harmonic current magnitude (secondary)
xxx.xxxkA
xxx.x A
L3 H2
Line 1 2nd harmonic voltage % distortion xx.xx%V L1 H2
Line 2 2nd harmonic voltage % distortion xx.xx%V L2 H2
Line 3 2nd harmonic voltage % distortion xx.xx%V L3 H2
Line 1 harmonic current distortion
(2nd - 15th) (primary)
Line 1 harmonic current distortion
(2nd - 15th) (secondary)
xxx.xxxkA
xxx.x A
L1 H2-15
Line 2 harmonic current distortion
(2nd - 15th) (primary)
Line 2 harmonic current distortion
(2nd - 15th) (secondary)
xxx.xxxkA
xxx.x A
L2 H2-15
Line 3 harmonic current distortion
(2nd - 15th) (primary)
Line 3 harmonic current distortion
(2nd - 15th) (secondary)
xxx.xxxkA
xxx.x A
L3 H2-15
Display description Display quantity Quantity ID Units ID
Service Voltage Test -------- TEST V
System Test Error xxxxxxxx SE
Service Current Test OK
--------
TEST I
System Service Type xxx 4Y
xxx 3
xxx 1L
L1-2-3
L3-2-1
Currently locked service [xxx 4Y]
[xxx 3]
[xxx 1L]
L1-2-3
L3-2-1
Display description Display quantity Quantity ID Units ID
Technical manual B-12 Display table
Errors and warnings
The A1800 ALPHA meter displays error codes and warning codes as an indication of a
problem that may be affecting its operation. See Error codes on page 6-2 and Warning
codes on page 6-5 for more information.
Communication codes
The A1800 ALPHA meter indicates the status of a communication session by displaying it
on the LCD. See Communication codes on page 6-8.
Technical manual C-1 Nameplate and style number information
C Nameplate and style number
information
Nameplate
The nameplate provides important information about the meter. The nameplate can be
configured to meet the needs of the utility company; however, Figure C-1 is an illustration of
a A1800 ALPHA nameplate for transformer rated meters.
Figure C-1. Sample nameplate
See Table C-1 for a description of the firmware version information.
Table C-1. Firmware version information
Code Description
R Meter release
A1800 ALPHA meter
01 Firmware version number
00 Firmware revision number
YYWW Manufacturing date code (year and week)
DD Meter engine code set version
XX Slot 1 option board firmware version, if installed (numbers are omitted
from the nameplate if no option board is installed)
ZZ Slot 2 option board firmware version, if installed (numbers are omitted
from the nameplate if no option board is installed)
AAAAAA Manufacturer order number
ELSTER SAMPLE
SERIAL #
01234567
UUf11
*01234567*
STYLE
ZE3JF4R00LM-01
R1.2-06210102AG-000000
3 x 58/100...240/415V, 60 Hz
1(10)A
0.2S
Made in USA 2006
5,000 imp/kWh
5,000 imp/kVarh
TYPE A1800
MODEL 1830RALN s150
T1 T2 T3 T4 T5 T6 T7 T8 EOI LC TC TST
Meter type
Voltage rating
and frequency
Nominal (max)
current
Isolation Class 2
symbol
Meter serial number
and barcode
Elster style number
Utility symbol
LCD indcator labels
Accuracy Class 0.2
Number of elements
LED pulse
settings
Year and place
of manufacture
Firmware version
Meter model
Technical manual C-2 Nameplate and style number information
Utility information card
The removable utility information card provides a place for the utility to enter meter site-
specific information (for example, CT, VT, etc.). Figure C-2 is an example of a utility
information card.
Figure C-2. Utility information card (transformer rated)
Figure C-3. Utility information card (direct connect rated)
CT
VT
A
V
imp/kW (kVARh
Style number information
Meter style numbers for the A1800 ALPHA meter
Field numbers 1 2 3 4 5 6 7 8 9 10 11
Z E 3 K F 4 R 0 0 L P
A1800 ALPHA meter
Service
3-phase, 3-wire, delta or network 2
3-phase, 4-wire, wye 3
Test amps & wiring
1 A or 5 A (10 A max), transformer rated
Symmetrical writing J
Sequential wiring K
5 A (120 A max), direct connect-rated
Sequential wiring N
Main board & voltage link options
All meters are 57.7 V to 480 V*
No main board options (128 KB memory) F
Auxiliary power supply only (128 KB memory) G
Backlight only (128 KB memory) J
Auxiliary power supply with backlight (128 KB memory) K
No main board options (256 KB memory) L
Auxiliary power supply only (256 KB memory) M
Backlight only (256 KB memory) N
Auxiliary power supply with backlight (256 KB memory) P
Internal voltage links (256 KB memory) Q
External voltage links (256 KB memory) R
Internal voltage links with backlight (256 KB memory) S
External voltage links with backlight (256 KB
memory)
T
Relays and extended memory
No relays and no extended memory 0
2 relays with no extended memory (A1805 only) 2
4 relays with no extended memory 4
Extended memory with no relays A
4 relays with extended memory E
Communication options ANSI DLMS
Optical port only A1810 00 C0
1 port: Internal telephone modem (ITM3) A1810 D0 CA
2 ports: RS-232/485 and ITM3 A1830 RD CD
2 ports: RS-232/485 and RS-232 A1860 RE CE
2 ports: RS-232/485 and RS-485 A1860 RF CF
1 port: RS-232/485 A1830 R0 CR
2 ports (ACB): RS-232/485 and DLT645 over RS-485 A1880 R1 C1
1 port: RS-232/485 A1830 R2
2 ports (ACB): RS-232/485 and Modbus over RS-485 A1882 R3
2 ports (ACB): RS-232/485 and DNP over RS-485 A1884 R4
2 ports (ACB): RS-232/485 and Modbus over RS-232 A1882 R5
2 ports (ACB): RS-232/485 and DNP over RS-232 A1884 R6


1 port (NIC): EA_NIC nA1810 PE
1 port (NIC): EA_NIC with last gasp nA1810 PF
2 ports (NIC): RS-232/485 and EA_NIC nA1830 PB
2 ports (NIC): RS-232/485 and EA_NIC with last gasp nA1830 PD


Miscellaneous options
Read without power Not enabled Enabled
Long terminal cover, IEC optical port, TOU battery 0 A
Long terminal cover, ANSI optical port, TOU battery 1 B
Long transparent terminal cover, IEC optical port, TOU battery 2 C
Long transparent terminal cover, ANSI optical port, TOU battery 3 D
Short terminal cover, IEC optical port, TOU battery 4 E
Short terminal cover, ANSI optical port, TOU battery 5 F
Metering options
Watt, var, TRueQ (A1805 when combined with A1810 options) L1
Watt, var, loss compensation, TRueQ L3
Watt, var, load profiling, TRueQ L5
Watt, var, loss compensation, load profiling, TRueQ L7
Watt, var, load profiling, instrumentation profiling, TRueQ L9
Watt, var, loss compensation, load profiling, instrumentation profiling, TRueQ LB
Watt, var, 4-quadrant metering, TRueQ LD
Watt, var, 4-quadrant metering, loss compensation, TRueQ LF
Watt, var, 4-quadrant metering, load profiling, TRueQ LH
Watt, var, 4-quadrant metering, loss compensation, load profiling, TRueQ LK
Watt, var, 4-quadrant metering, load profiling, instrumentation profiling, TRueQ LM
Watt, var, 4-quadrant metering, loss compensation, load profiling, instrumentation profiling, TRueQ LP
*Voltage link options available for direct connect-rated meters only.
Select this option for direct connect meters without voltage links
Contact Elster for availability
4-wire RS-485 implementation
2-wire RS-485 implementation

Technical manual C-4 Nameplate and style number information
Technical manual D-1 Wiring diagrams
D Wiring diagrams
Refer to the wiring diagram on the nameplate of each meter for specific terminal
assignments. All connections are equipped with combination-head screws that accept
either a slotted or Phillips screwdriver.
Direct connected
Figure D-1. 3-element, 4-wire wye or 4-wire delta
Figure D-2. 2-element, 3-wire delta or 3-wire network
1 3 7 9 4 6 10 12
L1
L2
L3
N
L2
N
L1 L3
1 3 7 9 4 6
L2 or N
L1
L3
or
N
L1 L3
L1
L2
L3
Technical manual D-2 Wiring diagrams
CT-connected meters
Figure D-3. 2-element, 3-wire delta, transformer connected
Figure D-4. 3-element, 4-wire current transformer, sequential connection
1 2 3 5 7 8 9
3
2
1 L
I
N
E
L
O
A
D
2
1 3
1 2 3 4 5 6 7 8 9 11
N
3
2
1
L
I
N
E
L
O
A
D
2
1 3
N
Technical manual D-3 Wiring diagrams
Figure D-5. 3-element, 4-wire current transformer, symmetrical connection
Figure D-6. 3-element, 4-wire instrument transformer, sequential connection
1 2 3 4 5 6 7 8 9 11
N
3
2
1
L
I
N
E
L
O
A
D
2
1 3
N
1 2 3 4 5 6 7 8 9 11
N
L
I
N
E
2
1 3
N
3
2
1
L
O
A
D
Technical manual D-4 Wiring diagrams
Figure D-7. 3-element, 4-wire instrumentation transformer, symmetrical connection
1 2 3 4 5 6 7 8 9 11
N
3
2
1
2
1 3
N
L
I
N
E
L
O
A
D
Technical manual E-1 Technical specifications
E Technical specifications
Absolute maximums
Operating ranges
Operating characteristics
Voltage Continuous 528 VAC
Surge voltage withstand Test performed
Oscillatory (IEC 61000-4-12)
Fast transient (IEC 61000-4-4)
Impulse voltage test (IEC 60060-1)
AC voltage (insulation) test
Results
2.5 kV, 60 seconds
4 kV
12 kV @ 1.2/50 s 450 (8 kV with option
boards)
4 kV, 50 Hz for 1 minute
Current Continuous at I
max
Temporary (0.5 seconds) at 2000 % of I
max
(transformer rated)
cycle at 30 Imax (direct connect-rated)
Voltage
Nameplate nominal range 58 V to 415 V
Operating range 49 V to 528 V
Auxiliary power supply range For AC power: 57 V rms to 240 V rms (nominal)
For DC power: 80 V to 340 V (nominal)
Current 0 A to 10 A (transformer rated)
0 A to 120 A (direct connect rated)
Frequency Nominal 50 Hz or 60 Hz 5 %
Temperature range -40 C to +85 C inside meter cover
-40 C to +60 C outside
Humidity range 0 % to 100 % noncondensing
Power supply burden Less than 3 W
Per phase current burden Less than 0.01 VA (transformer rated and direct connect-rated)
Per phase voltage burden
1
1
Conforms to IEC 62053-61 (Electricity Metering Equipment, Power Consumption and Voltage Requirements)
0.008 W at 120 V 0.03 W at 240 V 0.04 W at 480 V
Accuracy
Active energy 0.2 % (IEC 62053-22) 0.5 % (IEC 62053-22) 1.0 % (IEC 62053-21)
Reactive energy 2.0 % (IEC 62053-23)
Actual accuracy is better than 0.5 % for 0.2 % accuracy
meters
Technical manual E-2 Technical specifications
General performance characteristics
Dimensions and mass
For the dimensions and mass of the A1800 ALPHA meter, see Physical dimensions and
mass on page 2-19.
Starting current
CT-connected 1 mA
Direct-connected < 20 mA (I
b
= 5 A)
Creep 0.000 A (no current) No more than 1 pulse per quantity, conforming to IEC 62053 requirements
Internal clock accuracy Better than 0.5 seconds/day (while powered), while conforming to IEC 62054-21
Outage carryover capacity LiSOCl2 battery rated 800 mAhr, 3.6 V and shelf life of 15+ years.
5 years continuous duty at 25 C.
Supercapacitor is expected to provide carryover power for all normal power outages for a
period of at least 6 hours at +25 C. The battery is not under load except when
supercapacitor is discharged or when a programmed meter is stored for an extended
period without line power. Based on this low duty cycle, the projected life of the battery in
normal service is expected to be greater than 20 years.
Read without power battery 20 years based on 6 uses per year and 3-minute operation each use.
Communications rate
Optical port 1200 to 28,800 bps Physical components meet IEC 62056-21 or ANSI C12.18
Optical port protocol ANSI C12.18 and C12.19; DLMS/COSEM (optional)
Serial ports 1200 bps to 19,200 bps
Serial port protocol ANSI C12.21 and C12.19; DLMS/COSEM (optional)
Technical manual X-1 Index
Index
A
A1800 ALPHA meter
accuracy 1-4
adaptability 1-4
dimensions 2-19
economy 1-4
meter types 1-5
physical components 2-1
reliability 1-3
security 1-4
active COM port indicator 3-3
alternate mode 3-8
entering 3-8
exiting 3-8
LED pulse output and 3-8
Always Positive
theft-resistant option 2-14
ANSI standards. See standards:IEEE/ANSI
auditing
tampering 4-26
autolock. See system service locking:smart
autolock
auxiliary power supply. See power supply,
auxiliary
average power factor. See power factor
average
B
backlight. See liquid crystal display:back-
light
basic metered quantities 2-10
pulse output and 5-2
battery 1-3, 2-5, 6-1, 6-3, 6-5
and cover removal detection 2-15
disposal 7-6
indication of low power 3-3, 5-5, 6-5,
6-6, B-2
installing 7-3
removing 7-6
reversed polarity 7-4
block diagram. See system architecture
C
calibration constants. See EEPROM
clock precision E-2
coincident power factor. See power factor
coincident
communication
ANSI standards 1-4
RS-232/RS-485 1-4, 2-6, 5-1
serial 1-4, 2-8
communication codes 6-8
communications
optical port. See optical port
cover assembly 2-1
long terminal cover 2-1
meter cover 2-1
partially-transparent terminal cover 2-1
sealing of 2-2
short terminal cover 2-1
cover tamper 3-4
crystal oscillator 1-3, 2-6, 5-4, 6-1, 6-3, 6-
4, 6-7
current sensors. See sensors:current
current test, errors 4-11
D
delivered, energy 3-2
demand
and primary metering 2-13
and secondary metering 2-13
coincident 2-13
continuous cumulative maximum 2-12
cumulative maximum 2-12
metered quantities 2-10
demand forgiveness 2-13
demand interval 2-10
block 2-11
rolling 2-11
thermal time constant 2-12
demand reset
data area 3-10
lockout 3-10
performing 3-4, 3-10
results of 3-10
dimensions. see A1800 ALPHA meter:di-
mensions
DIN standards. See standards:DIN
display indicator 3-3
display quantity 4-3
system instrumentation 4-3
DLMS standards. See standards:DLMS
DSP. See meter engine
E
EEPROM 1-3, 6-3
access error 5-4, 6-4
and microcontroller 2-8
and power failure 2-9, 6-5
calibration constants 2-8
stored values 2-9
theory of operation 2-9
end-of-interval 3-3
relay outputs and 5-2
energy delivered 3-2
energy direction indicator 3-2
energy pulse divisor 5-3
energy pulse value 5-4
energy received 3-2
EOI. See endofinterval.
error codes 6-2
error indicator 3-3
event log. See logs:event
extended memory 2-15
H
history log. See logs:history.
I
IEC standards. See standards:IEC
IEEE standards. See standards:IEEE/ANSI
installation
calibration 7-1
preliminary inspection 7-1
verifying 7-5
instrumentation accuracy 4-3
and primary metering 2-13
instrumentation profiling. See logs:instru-
mentation profiling
L
LCD. See liquid crystal display
LED
output specifications 5-6
pulse outputs 5-6
LED pulse output
alternate mode and 3-8
normal mode and 3-8
test mode and 3-8
line frequency 6-6
and timekeeping 1-3, 6-7
line loss compensation
availability 8-1
calculations 8-5
liquid crystal display
backlight 3-2, 3-6
cover tamper (TC) indicator 3-4
endofinterval indicator 3-3
energy direction indicator 3-2
error indicator 3-3
loss compensation indicator 3-4
low battery indicator 3-3
phase indicator 3-2
power/energy units identifier 3-3
tariff indicator 3-3
test mode indicator 3-4
load control
relay outputs and 5-2
load profiling. See logs:load profiling

Technical manual X-2 Index
logs 2-14
event 2-15
history 2-15
instrumentation profiling 2-17
load profiling 2-16
self reads 2-16
TRueQ 2-18
voltage sag 2-18
loss compensation 3-4
software support 8-1
M
Memory. See EEPROM, extended memory,
shared memory
meter cover. See cover assembly
meter cover
meter engine
pulse 2-10
theory of operation 2-8
metered quantities 2-10
microcontroller
and meter engine pulses 2-10
detecting power failure 2-9
theory of operation 2-8
N
nameplate 6-9
in verifying installation 7-5
nonvolatile memory. See EEPROM
normal mode
LED pulse output and 3-8
O
optical port 2-3
and communication codes 6-2
and microcontroller 2-8
and operation during errors 6-4
and password 4-26
and test mode 3-8, 6-11
ANSI 1-4
IEC 1-4
output relays
voltage 5-2
P
password
encryption 4-26
levels 4-25
meter 4-25
phase indicator 3-2
physical components. See A3 ALPHA me-
ter:physical components
power factor
average 2-10
concident 2-13
power fail 2-9
and event log 2-14
power supply 1-3, 2-6
theory of operation 2-8
power supply, auxiliary 1-3, 2-8
power supply, main
theory of operation 2-8
power/energy units identifier. See liquid
crystal display:power/energy units iden-
tifier
primary metering 2-13
programmable relays 5-2
push buttons 3-4
R
received, energy 3-2
relay
demand forgiveness 5-3
energy pulse 5-2
EOI 5-2
error, warning, event 5-3
load control 5-2
pulse outputs 5-3
tariff 5-3
triggering alarms 5-4
TRueQ test failure 5-3
relay outputs 5-1
pulse mode 5-3
specifications 5-2
toggle mode 5-3
removal
Abase procedure 7-6
RESET button
system service locking and 3-5
resistive dividers. See sensors:voltage
RS-232/RS-485. See communication:RS-
232/RS-485
S
safety
notices 1-v
procedures 1-v
seals 2-2
secondary metering 2-13
security
anti-tampering 4-26
program protection 4-26
use of passwords 4-25
self reads. See logs:self reads
self test 6-1
sensors
current 2-8
theory of operation 2-8
voltage 2-8
service current test 4-9
initiation of 4-10
service voltage test 4-5
shared memory 2-14
allocation 2-15
signal conversion 2-8
standards
ANSI 4-26, 6-4
DIN 1-3, 2-19
DLMS 1-3
IEC 1-2, 1-4, 2-1
IEEE/ANSI 1-2
style numbers C-3
support software
loss compensation 8-1
system architecture 2-6
System instrumentation 4-1
system instrumentation
calculations used in 4-1
how obtained 4-1
measurement in progress 4-4
system service locking 4-5
manual lock 4-5, 4-6
RESET button and 3-5
smart autolock 4-5, 4-6
system service tests. See service current
test or service voltage test
T
tamper detection switches 2-5
Tamper restraint and quality. See TRueQ
tariff indicator 3-3
test
diagnostic mode 4-9
test LED 5-6
test mode 3-8
indicator 3-8
LED pulse output and 3-8
test mode indicator 3-4
testing
meter 6-10
setup 6-9, 6-10
theft-resistant measurement 2-14
theft-resistant option
poor power factor 2-14
theory of operation 2-72-9
auxiliary power supply 2-8
EEPROM 2-9
main power supply 2-8
meter engine 2-8
microcontroller 2-8
time-of-use 2-13
TOU. See time-of-use
TRueQ 4-12
counters 4-15
LCD and 4-12
log 2-18
notification of event 4-12
relay outputs and 4-12
timers 4-15
voltage sag 4-13
TRueQ log. See logs:TRueQ
TRueQ test
no event 4-15
TRueQ test sets 4-13
U
user defined tables 2-18
utility information card 2-4, C-2
V
voltage sensors. See sensors:voltage
voltage test, errors 4-10
W
warning codes 6-5
warranty v
ALPHA, ALPHA Plus, REX, and EnergyAxis are registered
trademarks. Metercat, AlphaPlus, REX2, REX2-EA, and gREX are
trademarks of Elster. Other products and company names
mentioned herein may be the trademarks and/or registered
trademarks of their respective owners.
About Elster Group
A world leader in advanced metering
infrastructure, integrated metering, and
utilisation solutions to the gas, electricity and
water industries, Elsters systems and solutions
reflect over 170 years of knowledge and
experience in measuring precious resources
and energy. Elster provides solutions and
advanced technologies to help utilities more
easily, efficiently and reliably obtain and use
advanced metering intelligence to improve
customer service, enhance operational
efficiency, and increase customer benefits.
Elsters AMI solutions enable utilities to cost-
effectively deliver, manage, and conserve the
life-essential resources of gas, electricity, and
water. Elster has over 7500 staff and operations
in 38 countries in North and South America,
Europe, and Asia.
Elster
208 S Rogers Lane
Raleigh, NC 27610-2144
United States
T +1 800 338 5251 (US toll free)
T +1 905 634 4895 (Canada)
F +1 919 212 4801
www.elster.com
2009 by Elster. All rights reserved.
No part of this software or documentation may be reproduced,
transmitted, processed or recorded by any means or form,
electronic, mechanical, photographic or otherwise, translated
to another language, or be released to any third party without
the express written consent of the Elster.
Printed in the United States of America.

S-ar putea să vă placă și