Users Manual

Sequence CPU Instruction Manual - Function


(For F3SP28-3N/3S, F3SP38-6N/6S, F3SP53-4H/4S, F3SP58-6H/6S, F3SP59-7S)
IM 34M6P13-01E

IM 34M6P13-01E
Yokogawa Electric Corporation
2nd Edition

Applicable Product:
G Range-free-controller FA-M3
Model Name: F3SP28, F3SP38, F3SP53, F3SP58, F3SP59 Name: Sequence CPU Modules

The document number and document model code for this manual are given below. Refer to the document number in all communications; also refer to the document number or the document model code when purchasing additional copies of this manual. Document No. Document Model Code : : IM 34M6P13-01E DOCIM

Media No. IM 34M6P13-01E (CD) 2nd Edition : Oct 1, 2002 (AR) All Rights Reserved Copyright 1992, Yokogawa Electric Corporation

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

ii

Important
About This Manual
This Manual should be passed on to the end user. Before using the controller, read this manual thoroughly to have a clear understanding of the controller. This manual explains the functions of this product, but there is no guarantee that they will suit the particular purpose of the user. Under absolutely no circumstances may the contents of this manual be transcribed or copied, in part or in whole, without permission. The contents of this manual are subject to change without prior notice. Every effort has been made to ensure accuracy in the preparation of this manual. However, should any errors or omissions come to the attention of the user, please contact the nearest Yokogawa Electric representative or sales office.

Safety Precautions when Using/Maintaining the Product


The following safety symbols are used on the product as well as in this manual.

Danger. This symbol on the product indicates that the operator must follow the instructions laid out in this instruction manual to avoid the risk of personnel injuries, fatalities, or damage to the instrument. Where indicated by this symbol, the manual describes what special care the operator must exercise to prevent electrical shock or other dangers that may result in injury or the loss of life.

Protective Ground Terminal. Before using the instrument, be sure to ground this terminal.

Function Ground Terminal. Before using the instrument, be sure to ground this terminal.

Alternating current. Indicates alternating current.

Direct current. Indicates direct current.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

iii
The following symbols are used only in the instruction manual.

WARNING
Indicates a Warning. Draws attention to information essential to prevent hardware damage, software damage or system failure.

CAUTION
Indicates a Caution Draws attention to information essential to the understanding of operation and functions.

TIP
Indicates a TIP Gives information that complements the present topic.

SEE ALSO Indicates a SEE ALSO reference. Identifies a source to which to refer.
For the protection and safe use of the product and the system controlled by it, be sure to follow the instructions and precautions on safety stated in this manual whenever handling the product. Take special note that if you handle the product in a manner other than prescribed in these instructions, the protection feature of the product may be damaged or impaired. In such cases, Yokogawa cannot guarantee the quality, performance, function and safety of the product. When installing protection and/or safety circuits such as lightning protection devices and equipment for the product and control system as well as designing or installing separate protection and/or safety circuits for fool-proof design and fail-safe design of processes and lines using the product and the system controlled by it, the user should implement it using devices and equipment, additional to this product. If component parts or consumable are to be replaced, be sure to use parts specified by the company. This product is not designed or manufactured to be used in critical applications which directly affect or threaten human lives and safety such as nuclear power equipment, devices using radioactivity, railway facilities, aviation equipment, air navigation facilities, aviation facilities or medical equipment. If so used, it is the users responsibility to include in the system additional equipment and devices that ensure personnel safety. Do not attempt to modify the product.

Exemption from Responsibility


Yokogawa Electric Corporation (hereinafter simply referred to as Yokogawa Electric) makes no warranties regarding the product except those stated in the WARRANTY that is provided separately. Yokogawa Electric assumes no liability to any party for any loss or damage, direct or indirect, caused by the use or any unpredictable defect of the product.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

iv Software Supplied by the Company


Yokogawa Electric makes no other warranties expressed or implied except as provided in its warranty clause for software supplied by the company. Use the software with one computer only. You must purchase another copy of the software for use with each additional computer. Copying the software for any purposes other than backup is strictly prohibited. Store the original media, such as floppy disks, that contain the software in a safe place. Reverse engineering, such as decompiling of the software, is strictly prohibited. No portion of the software supplied by Yokogawa Electric may be transferred, exchanged, or sublet or leased for use by any third party without prior permission by Yokogawa Electric.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

v General Requirements for Using the FA-M3 Controller


G Avoid installing the FA-M3 controller in the following locations:
Where the instrument will be exposed to direct sunlight, or where the operating temperature exceeds the range 0C to 55C (0F to 131F). Where the relative humidity is outside the range 10 to 90%, or where sudden temperature changes may occur and cause condensation. Where corrosive or flammable gases are present. Where the instrument will be exposed to direct mechanical vibration or shock. Where the instrument may be exposed to extreme levels of radioactivity.

G Use the correct types of wire for external wiring:


Use copper wire with temperature ratings greater than 75C.

G Securely tighten screws:


Securely tighten module mounting screws and terminal screws to avoid problems such as faulty operation. Tighten terminal block screws with the correct tightening torque as given in this manual.

G Securely lock connecting cables:


Securely lock the connectors of cables, and check them thoroughly before turning on the power.

G Interlock with emergency-stop circuitry using external relays:


Equipment incorporating the FA-M3 controller must be furnished with emergencystop circuitry that uses external relays. This circuitry should be set up to interlock correctly with controller status (stop/run).

G Ground for low impedance:


For safety reasons, connect the [FG] grounding terminal to a Japanese Industrial Standards (JIS) Class D Ground*1 (Japanese Industrial Standards (JIS) Class 3 Ground). For compliance to CE Marking, use cables such as twisted cables which can ensure low impedance even at high frequencies for grounding.
*1 Japanese Industrial Standard (JIS) Class D Ground means grounding registance of 100 max.

G Configure and route cables with noise control considerations:


Perform installation and wiring that segregates system parts that may likely become noise sources and system parts that are susceptible to noise. Segregation can be achieved by measures such as segregating by distance, installing a filter or segregating the grounding system.

G Configure for CE Marking Conformance:


For compliance to CE Marking, perform installation and cable routing according to the description on compliance to CE Marking in the Hardware Manual (IM34M6C11-01E).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

vi
G Keep spare parts on hand:
Stock up on maintenance parts including spare modules, in advance.

G Discharge static electricity before operating the system:


Because static charge can accumulate in dry conditions, first touch grounded metal to discharge any static electricity before touching the system.

G Never use solvents such as paint thinner for cleaning:


Gently clean the surfaces of the FA-M3 controller with a cloth that has been soaked in water or a neutral detergent and wringed. Do not use volatile solvents such as benzine or paint thinner or chemicals for cleaning, as they may cause deformity, discoloration, or malfunctioning.

G Avoid storing the FA-M3 controller in places with high temperature or


humidity:
Since the CPU module has a built-in battery, avoid storage in places with high temperature or humidity. Since the service life of the battery is drastically reduced by exposure to high temperatures, take special care (storage temperature should be from 20C to 75C). There is a built-in lithium battery in a CPU module and temperature control module which serves as backup power supply for programs, device information and configuration information. The service life of this battery is more than 10 years in standby mode at room temperature. Take note that the service life of the battery may be shortened when installed or stored at locations of extreme low or high temperatures. Therefore, we recommend that modules with built-in batteries be stored at room temperature.

G Always turn off the power before installing or removing modules:


Failing to turn off the power supply when installing or removing modules, may result in damage.

G Do not touch components in the module:


In some modules you can remove the right-side cover and install ROM packs or change switch settings. While doing this, do not touch any components on the printed-circuit board, otherwise components may be damaged and modules may fail to work.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

vii

Introduction
I Overview of the Manual
This manual describes the sequencing functions of sequence CPU modules (For F3SP28-3N/3S, F3SP38-6N/6S, F3SP53-4H/4S, F3SP58-6H/6S, F3SP59-7S)designed for use with the Range-free Multi-controller FA-M3.

I How to Read the Manual


If you are a first-time reader, first go through this paragraph, How to Read the Manual, and proceed to Chapter 1, then Chapter 3. For efficiency, read only the relevant remaining chapters according to your flow of work from system design to system operation. The chart below shows the regular workflow, from system design to system operation, as well as chapters you should refer to in each step.

Work Flow from System Design to System Operation, and Relevant Chapters
Design Target machine

Start Determination of system configuration System design Chapter 2, "System Configuration" Assignment of I/Os, registers and relays Basic design Chapter 4, "Devices," and Chapter 5, "Programs"

Start

Wiring

I/O verification

Input: Verification of I/Os with LED lamps Output: Forced SET and RESET instructions Chapter 6, "Functions"

Program downloading Coding Configuration of a ladder diagram Ladder symbols Mnemonic language Chapter 1, "Overview of Instruction Words," Chapter 2, "Basic Instructions," and Chapter 3, "Advanced Instructions," in the Instructions volume of the 3rd or later edition of the Sequence CPUs instruction manual Program input for simulation Performance check Verification of basic logic Program modification Chapter 6, "Functions"

Programming

Debugging Trial operation

Program modification Chapter 6, "Functions"

End of flow?

End

Program storage on floppy/ hard disk or in ROM pack

End of flow?

End

Program storage on floppy/hard disk or in ROM pack

F000001.VSD

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

viii Other Instruction Manuals


Be sure to read each of the following manuals, in addition to this manual.

G For information on the instructions used with sequence CPUs, refer to:
Sequence CPU Instruction Manual - Instructions (IM34M6P12-03E)

G For information on the commands and responses of personal computer link functions
Personal Computer Link Command Instruction Manual (IM34M6P41-01E).

G When creating programs using ladder language, refer to:


- FA-M3 Programming Tool WideField2 Instruction Manual (IM34M6Q15-01E) or FA-M3 Programming Tool WideField Instruction Manual (IM34M6Q14-01E); and FA-M3 Programming Tool WideField Instruction Manual - Application (IM34M6Q14-02E).

G For information on the specifications*, configuration*, installation, wiring, trial operation, maintenance and inspection of the FA-M3, as well as information on the system-wide limitation of module installation, refer to:
*:

Hardware Manual (IM34M6C11-01E).


For information on the specifications of products other than the power supply module, base module, I/O module, cable and terminal block unit, refer to their respective instruction manuals.

Read the following instruction manuals, as required.

G For information on the functions of F3SP21, F3SP25 and F3SP35 sequence CPU modules, refer to:
Sequence CPU Instruction Manual - Functions (for F3SP21, F3SP25 and F3SP35) (IM34M6P12-01E).

G For information on the functions of fiber-optic FA-bus modules, refer to:


Fiber-optic FA-bus Module and Fiber-optic FA-bus Type 2 Module (IM34M6H45-01E).

G For information on the functions of FA link H and fiber-optic FA link H modules, refer to:
FA Link H Module, Fiber-optic FA Link H Module (IM34M6H43-01E).

G For information on the functions of BASIC CPU modules, refer to:


BASIC CPU Modules and YM-BASIC/FA Programming Language (IM34M6Q22-01E).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

ix

Copyrights and Trademarks


Copyrights
Copyrights of the programs and online manual included in this CD-ROM belong to Yokogawa Electric Corporation. This online manual may be printed but PDF security settings have been made to prevent alteration of its contents. This online manual may only be printed and used for the sole purpose of operating this product. When using a printed copy of the online manual, pay attention to possible inconsistencies with the latest version of the online manual. Ensure that the edition agrees with the latest CD-ROM version. Copying, passing, selling or distribution (including transferring over computer networks) of the contents of the online manual, in part or in whole, to any third party, is strictly prohibited. Registering or recording onto videotapes and other media is also prohibited without expressed permission of Yokogawa Electric Corporation.

Trademarks
The trade and company names that are referred to in this document are either trademarks or registered trademarks of their respective companies.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

TOC-1

FA-M3
Sequence CPU Instruction Manual - Function
(For F3SP28-3N/3S, F3SP38-6N/6S, F3SP53-4H/4S, F3SP58-6H/6S, F3SP59-7S)
IM 34M6P13-01E 2nd Edition

CONTENTS
Applicable Product ................................................................................... i Important .................................................................................................. ii Introduction ............................................................................................ vii Copyrights and Trademarks................................................................. Viii 1. Specification and Basic Configuration ....................................... 1-1
1.1 1.2 Overview ................................................................................................... 1-1 Specification............................................................................................. 1-3 1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 1.3 1.3.1 1.3.2 1.3.3 Tables of Performance Data......................................................... 1-3 Device List .................................................................................... 1-7 Configuration ................................................................................ 1-9 Components and Their Functions .............................................. 1-14 External Dimensions .................................................................. 1-15 Unit ............................................................................................. 1-16 Slot Number................................................................................ 1-17 I/O Relay Number....................................................................... 1-19

Basic Configuration............................................................................... 1-16

2.

System Configuration .................................................................. 2-1


2.1 2.2 Basic System Configuration................................................................... 2-1 Multi-CPU System Configuration ........................................................... 2-1 2.2.1 2.2.2 2.3 2.3.1 2.3.2 2.3.3 2.4 2.4.1 Multi-CPU System Configuration.................................................. 2-1 Handling I/O Modules in Multi-CPU System ................................ 2-3 Remote I/O System ...................................................................... 2-4 Personal Computer Link System.................................................. 2-5 FA Link System............................................................................. 2-5 WideField2.................................................................................... 2-6

Extended System Configuration ............................................................ 2-4

Programming Tool ................................................................................... 2-6

3.

Basic Sequence CPU Module Operations .................................. 3-1


3.1 3.2 Operation Modes of Sequence CPU Module......................................... 3-1 Operation at Power-on/off....................................................................... 3-2 3.2.1 3.2.2 3.3 3.3.1 3.3.2 Operation at Power-on ................................................................. 3-2 Operation at Power-off ................................................................. 3-3 Operation in Case of Momentary Power Failure .......................... 3-4 Specifying the Momentary Power Failure Detection Mode .......... 3-5
IM 34M6P13-01E 2nd Edition : Oct 1, 2002

Operation in Case of Momentary or Complete Power Failure............. 3-4

TOC-2
3.3.3 3.3.4 3.4 3.5 3.6 Operation in Case of Complete Power Failure............................. 3-6 Specifying the Range of Devices to Be Latched in Case of Complete Power Failure.............................................. 3-6

Computation Method ............................................................................... 3-7 Method of Executing Peripheral Processes.......................................... 3-9 Method of I/O Processing ..................................................................... 3-11 3.6.1 3.6.2 3.6.3 Method of I/O Processing........................................................... 3-11 Response Delay ......................................................................... 3-12 I/O Processing in Multi-CPU System.......................................... 3-13 Tool Service ................................................................................ 3-14

3.7 3.8

Method of Executing Commands from the WideField2 ..................... 3-14 3.7.1 Method of Executing Commands through Personal Computer Link ....................................................................... 3-15 3.8.1 Personal Computer Link Service................................................ 3-15 Method of Updating Shared Data............................................... 3-16 Setting the Mode of Shared Refreshing ..................................... 3-18 CPU Service ............................................................................... 3-22 Method of CPU-to-CPU Data Communication .................................... 3-16 3.9.1 3.9.2 3.9.3

3.9

3.10

Method of Link Data Updating .............................................................. 3-23 3.10.1 Link Data Updating ..................................................................... 3-23 3.10.2 Link Refreshing........................................................................... 3-24

3.11

Method of Interrupt Processing .......................................................... 3-26 3.11.1 Interrupt Processing ................................................................... 3-26 3.11.2 Interrupt Processing Control....................................................... 3-27 3.11.3 Interrupt Timing........................................................................... 3-28 3.11.4 Interrupt Priority .......................................................................... 3-32

4.

Devices .......................................................................................... 4-1


4.1 I/O Relays (X/Y) ....................................................................................... 4-1 4.1.1 4.1.2 4.1.3 4.1.4 4.2 Input Relays (X)........................................................................... 4-1 Output Relays (Y) ......................................................................... 4-2 Allocation of I/O Addresses .......................................................... 4-2 Configuring DIO Modules ............................................................. 4-3

Internal Relays (I), Shared Relays (E) and Extended Shared Relays (E) ................................................................... 4-6 4.2.1 4.2.2 Internal Relays (I) ......................................................................... 4-6 Shared Relays (E) and Extended Shared Relays (E) .................. 4-7 Link Relays (L)............................................................................ 4-13 Link Registers (W)...................................................................... 4-14 System Numbers ........................................................................ 4-15 Configuring Link Relays (L) and Registers (W).......................... 4-16 Link Refreshing Range............................................................... 4-17 Block Start Status ....................................................................... 4-19 Utility Relays............................................................................... 4-20
IM 34M6P13-01E 2nd Edition : Oct 1, 2002

4.3

Link Relays (L) and Link Registers (W) ............................................... 4-12 4.3.1 4.3.2 4.3.3 4.3.4 4.3.5

4.4

Special Relays (M) ................................................................................. 4-19 4.4.1 4.4.2

TOC-3
4.4.3 4.4.4 4.4.5 4.5 4.5.1 4.5.2 4.5.3 4.6 4.7 4.6.1 Sequence Operation and Mode Status Relays .......................... 4-22 Self-diagnosis Status Relays...................................................... 4-23 FA Link Module Status Relays.................................................... 4-24 100-s, 1-ms, 10-ms, and 100-ms Timers ................................. 4-25 100-ms Continuous Timer .......................................................... 4-27 Selecting Timers ......................................................................... 4-28 Selecting Counters ..................................................................... 4-30

Timers (T)................................................................................................ 4-25

Counters (C) ........................................................................................... 4-29 Data Register (D), Shared Register (R) and Extended Shared Register (R) .............................................................. 4-31 4.7.1 4.7.2 4.7.3 Data Registers (D)...................................................................... 4-31 Shared Registers (R) and Extended Shared Registers (R) ...... 4-32 Setting Initial Data for Data Registers (D) .................................. 4-38 Sequence Operation Status Registers ....................................... 4-39 Self-diagnosis Status Registers.................................................. 4-40 Utility Registers........................................................................... 4-41 FA Link Module Status Registers................................................ 4-42 Sequence CPU Module Status Registers .................................. 4-43

4.8

Special Registers (Z) ............................................................................. 4-39 4.8.1 4.8.2 4.8.3 4.8.4 4.8.5

4.9 4.10

Index Registers (V) ................................................................................ 4-44 File Registers (B) ................................................................................... 4-45 Programming Language ......................................................................... 5-1 5.1.1 5.1.2 Structured Ladder Language........................................................ 5-1 Mnemonic Language .................................................................... 5-2 Blocks and Executable Programs ................................................ 5-3 Programs Composing an Executable Program............................ 5-5

5.

Programs....................................................................................... 5-1
5.1

5.2

Program Types and Configuration......................................................... 5-3 5.2.1 5.2.2

5.3

Program Memory ................................................................................... 5-10 Function List ............................................................................................ 6-1 Operation Setup Function....................................................................... 6-3 Constant Scan 6.3.1 ...................................................................................... 6-5 Setting the Constant Scan Time................................................... 6-5 Executing All Blocks ..................................................................... 6-6 Executing Specified Blocks .......................................................... 6-7 Operation When Specified Blocks Are Enabled ........................... 6-8 Operation When Specified Blocks Are Disabled ........................ 6-10 Operation When Specified Blocks Are Executed ....................... 6-11 Forced SET/RESET ................................................................ 6-13

6.

Functions ...................................................................................... 6-1


6.1 6.2 6.3 6.4

Executing All Blocks/Specified Blocks ................................................. 6-6 6.4.1 6.4.2 6.4.3 6.4.4 6.4.5

6.5

Debugging Functions............................................................................ 6-13 6.5.1 6.5.2 Changing Setpoints, Current Values and Data Values............... 6-13
IM 34M6P13-01E 2nd Edition : Oct 1, 2002

TOC-4
6.5.3 6.6 6.6.1 6.6.2 6.7 6.8 Stopping Refreshing ................................................................. 6-14 Executable Program Protection.................................................. 6-15 Block Protection.......................................................................... 6-16 Protecting Programs ............................................................................. 6-15

Online Editing ...................................................................................... 6-17 Making Programs Resident Using ROM Writer Functions ................ 6-18 6.8.1 6.8.2 6.8.3 Making Programs Resident in ROM........................................... 6-18 Setting Devices Current Values to Be Made Resident in ROM ............................................................. 6-20 ROM Writer Functions and ROM Writer Mode ........................ 6-21

6.9 6.10 6.11

Exclusive Access Control ..................................................................... 6-23 Sampling Trace Function ...................................................................... 6-24 Personal Computer Link Function ....................................................... 6-28 6.11.1 System Configuration ................................................................. 6-29 6.11.2 Differences from Personal Computer Link Module .................... 6-30 6.11.3 Specification of Personal Computer Link Function .................... 6-32 6.11.4 Setting Up the Personal Computer Link Function ...................... 6-33 6.11.5 Communication Procedure......................................................... 6-34 6.11.6 Commands and Responses ....................................................... 6-36

6.12 6.13

Device Management Function .............................................................. 6-45 Macro Instructions................................................................................. 6-46 6.13.1 What Are Macro Instructions? .................................................... 6-46 6.13.2 Specification of Macro Instructions............................................. 6-50 6.13.3 Devices Dedicated to Macro Instructions ................................... 6-51 6.13.4 Nesting Macro Instructions......................................................... 6-54 6.13.5 Handling Macro Instruction Errors.............................................. 6-56 6.13.6 Protecting Macro Instructions..................................................... 6-57 6.13.7 Debugging Operation ................................................................. 6-57 6.13.8 Input Macro Instructions ........................................................... 6-58 6.13.9 Structure Macro Instructions ..................................................... 6-60

6.14 6.15

User Log Management Function .......................................................... 6-62 Sensor Control Function....................................................................... 6-64 6.15.1 Schematic Operation Diagram ................................................... 6-64 6.15.2 Features ..................................................................................... 6-65 6.15.3 Specifications and Restrictions................................................... 6-66 6.15.4 Function Setup Items ................................................................. 6-70 6.15.5 Procedures for Using Sensor Control Function.......................... 6-77 6.15.6 Error Handling ............................................................................ 6-77 6.15.7 Programming Precautions.......................................................... 6-79

6.16 6.17

Partial Download Function ................................................................. 6-81 Function for Storing Comments to CPU ........................................... 6-83 6.17.1 Performing Setup to Download Comments................................ 6-83 6.17.2 Number of Steps Needed for Comments ................................... 6-84 6.17.3 Online Editing of Comments....................................................... 6-85

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

TOC-5
6.18 6.19 Function for Storing Tag Name Definitions to CPU ........................... 6-86 Structures ............................................................................................... 6-87 Information on Scan Time....................................................................... 7-1 Setting Scan Time Monitoring Time....................................................... 7-4 Examples of Calculating the Scan Time................................................ 7-5 Examples of Calculating the I/O Response Time ................................. 7-7 Instruction Execution Time..................................................................... 7-9 Self-diagnosis .......................................................................................... 8-1 8.1.1 8.2 Setting Operation Mode in Case of Failure and External Output Mode in Case of Sequence Stop........................ 8-9

7.

I/O Response Time Based on Scan Time ................................... 7-1


7.1 7.2 7.3 7.4 7.5

8.

RAS Features ................................................................................ 8-1


8.1

Recovering Normal Operation after Correcting Non-fatal/Minor Errors........................................................................... 8-10 Comparison of Performance Data.......................................................... 9-1 Configuration ........................................................................................... 9-3 Special Relays (M) and Special Registers (Z) ....................................... 9-5 CPU Module to CPU Module Communication Method......................... 9-7 High-speed Processing of Application Instructions ............................ 9-7 Instructions .............................................................................................. 9-8

9.

Differences From F3SP25 and F3SP35 Sequence CPUs........... 9-1


9.1 9.2 9.3 9.4 9.5 9.6 10.1 10.2 10.3 10.4

10. Difference between F3SP

- S and F3SP

- N/- H ....... 10-1

Partial Download Function ................................................................... 10-1 Storing Comments or Tag Name Definitions in CPU.......................... 10-1 New Instructions and Instruction Related Functions ........................ 10-2 Changes in Specifications .................................................................... 10-3 Block Start Status ............................................................ App.1-1 Utility Relays .................................................................... App.1-2 Sequence Operation and Mode Status Relays ............. App.1-3 Self-diagnosis Status Relays.......................................... App.1-4 FA Link Module Status Relays ........................................ App.1-5 Sequence Operation Status Registers .......................... App.2-1 Self-diagnosis Status Registers ..................................... App.2-2 Utility Registers................................................................ App.2-3 FA Link Module Status Registers ................................... App.2-4 Sequence CPU Module Status Registers ...................... App.2-5

Appendix 1. Special Relays (M) ................................................. App.1-1


Appendix 1.1 Appendix 1.2 Appendix 1.3 Appendix 1.4 Appendix 1.5 Appendix 2.1 Appendix 2.2 Appendix 2.3 Appendix 2.4 Appendix 2.5

Appendix 2. Special Registers (Z) ............................................. App.2-1

Appendix 3. Forms for System Design ..................................... App.3-1 Index................................................................................................Index-1 Revision Information ................................................................................ i

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

1-1

1.
1.1

Specification and Basic Configuration


This chapter explains the CPU module specifications and the basic configuration of the Range-free Multi-controller FA-M3.

Overview
This section describes the overview, features, main functions of the sequence CPU module.

I Overview
Models F3SP28-3N, F3SP38-6N, F3SP53-4H, F3SP58-6H, F3SP28-3S, F3SP38-6S, F3SP53-4S, F3SP58-6S and F3SP59-7S are CPU modules with built-in memory for use with the FA-M3. In addition to high-speed operation and large memory capacity, these modules have many more features that help increase your development and maintenance efficiency.

I Features G High-speed Operation


20 K steps/ms, with the shortest scan interval of 200 s High-speed I-P-R-S, which means: - High-speed Instruction - High-speed Performance - High-speed Response - High-speed Scan

G Sensor Control Function


In addition to normal scanning, each CPU module has an independent, multiple constant scan function, permitting fast scanning. Fast response is also possible with just a single CPU. You can execute a block of your program at high speed and fixed intervals (200 sminimum), separately from normal scanning. This feature enables you to eliminate the effects of a fault diagnosis program or MMI program, as well as ensures stable control program operation.

G Object Ladder
The FA-M3 Programming Tool WideField2, an object-oriented ladder language development tool, is available with the CPU module. This tool increases your productivity of programs more than structured programming does. In addition, it makes program maintenance easy.

G Function for Storing Comments F3SP

- S

Circuit comments, subcomments, and tag name definitions (including I/O comments) can be stored in the sequence CPU or the ROM pack. This function allows you to debug a program using tag names, even during unscheduled maintenance.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-2
G Other Features
Has a compact body, enabling you to reduce panel enclosure size. Operates large-capacity programs and has large device sizes and, therefore, can cope with advanced, complex control applications. - Uses index modification and structured ladder language for easy program design and maintenance. - Allows the device size and operating method to be flexibly configured according to your application needs. - Provides various functions, e.g., a forced SET/RESET function independent of program computation results, for easy program debugging and maintenance. - Has a carefully designed self-diagnosis function, in addition to a highly reliable design. - Provides macro instruction functions to allow you to create and register new instructions. - Has a sampling trace function capable of acquiring and displaying the states of a maximum of 1024 scans worth of devices. - Can connect to a host computer or a monitor without the need for a personal computer link module, as the programming tool connection port supports a personal computer link function. - Has a logging function capable of recording errors encountered in a program, as well as messages created and registered in advance. - Allows you to mount F3SP28, F3SP38, F3SP53, F3SP58 or F3SP59 modules in slots 2 to 4 of the main unit, for use as add-on CPU modules for sequence processes added to the main CPU module (F3SP21, F3SP25, F3SP28, F3SP35, F3SP38, F3SP53, F3SP58 or F3SP59). - Allows you to attach a ROM pack so that you can perform ROM-based operation and store programs. - Has a program protection function to ensure security. - The partial download function allows the downloading of specified blocks only, which increases debugging efficiency especially in program development by a team. F3SP - S - Indirect designation via devices is available, allowing large volume data handling and creation of efficient programs. F3SP - S - Structure macros simplify passing of data to macros and updating of these data structures. F3SP - S

G Functions
Sensor control Configuration (setup of parameters, including device size, range of devices to be latched in case of power failure, and external output to be retained in case of sequence stop) - Constant scan (at an interval of 1 to 190 ms, in 0.1 ms increments) - Sampling trace - Debugging (forced SET/RESET instructions, online editing, etc.) - Error logging, user logging - Clock (year, month, day, hour, minute, second, and day of the week) - Support for programming tool connection port with the personal computer link function - Program protection - Program/data storage in ROM pack - Circuit/sub-comment, tag name definitions storage in ROM pack. F3SP - S - Circuit/sub-comment storage function and tag name definition storage function. F3SP - S - Partial download function. F3SP - S See Section 1.2, Specification, for more information.
IM 34M6P13-01E 2nd Edition : Oct 1, 2002

1-3

1.2

Specification
This section describes the basic specifications of the FA-M3 sequence CPU module for each CPU type. For performance and specifications, see Section 1.2.1, "Table of Performance Data." For the types and number of devices, see Section 1.2.2, "Device List." For configuration setup ranges, see Section 1.2.3, "Configuration." For the names and functions of the components of the sequence CPU module, see Section 1.2.4, "Components and Their Functions." For the external dimensions of the sequence CPU module, see Section 1.2.5, "External Dimensions."

1.2.1 Tables of Performance Data


Table 1.1 Performance Data (F3SP Item
Control method I/O computation method Programming language Number of I/O points Number of internal relays (I) Number of shared relays (E) Number of extended shared relays (E) Number of link relays (L) Number of special relays (M) Number of timers (T) Number of counters (C) Number of data registers (D) Number of shared registers (R) Number of extended shared registers (R) Number of file registers (B) Number of link registers (W) Number of special registers (Z) Number of labels Number of input interruption processing routines Decimal constant Hexadecimal constant Character-string constant IEEE singleprecision floatingpoint constant Index constant

- S) (1/2) Specifications

F3SP28-3S F3SP53-4S F3SP38-6S F3SP58-6S F3SP59-7S Repetitive computation based on stored programs Refreshing by DIRECT REFRESH instruction Structured ladder language and mnemonic language 4096 max. 8192 max., including remote I/O points 16384 32768 65535 2048 2048 8192 16384 9984 1024 2048 1024 16384 32768 65535 1024 3072 32768 8192 1024 1024 4 16-bit instruction: 32-bit instruction: 16-bit instruction: 32-bit instruction: 16-bit instruction: 32-bit instruction: 262144 16384

Constants

-32768 to 32767 -2147483648 to 2147483647 $0 to $FFFF (hexadecimal number) $0 to $FFFFFFFF (hexadecimal number) e.g. AB, etc e.g. ABCD, etc. 32-bit instruction: e.g. 1.23, -3.21 Approximately -3.41038 to 3.41038 0 to 2047 254K steps 30K steps max. 56K steps max. 120K steps max.
max.

Program size (ROM resident) (Program + Tag Name Definition) size ROM-resident size (Program + Tag Name Definition) Number of program blocks Basic instructions Number of Application instructions instructions Number of macro instructions Basic instruction Application instruction

360K steps
max.

120K steps max. 1024 max. 37 329 256 max. 0.045 to 0.18s per instruction 0.18s min. per instruction 0.0175 to 0.07s per instruction 0.07s min. per instruction

360K steps max.

Instruction execution time

0.045 to 0.18s per instruction 0.18s min. per instruction

0.0175 to 0.07s per instruction 0.07s min. per instruction

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-4
Table 1.2 Performance Data (F3SP Item
Special module High Speed Read Instruction (HRD Instruction)/Special module High Speed Write Instruction (HWR Instruction) Sampling trace function Support for personal computer link function by programming tool connection port User log function Number of personal computer link modules Macro instruction function Scan time monitoring time Startup at power-on or recovery from power failure Sensor control function Constant scan Self-diagnosis Link function Comment storage function F3SP28-3S

- S) (2/2) (Continued) Specifications


F3SP53-4S F3SP38-6S F3SP58-6S F3SP59-7S

64 instructions each Available. This function collects and displays the states of multiple devices for a maximum of 1024 scans. Available. This function allows a personal computer or a monitor to be connected to the programming tool connection port to perform communications equivalent to the personal computer link module. Available. This function allows the user to execute a user log command to log (record the history of) errors in the user system, including information on the state of occurrence and system operation, etc. 6 max. Available. This function allows the user to create and register new user-defined instructions. Variable from 10 to 200 ms. Automatic (Auto-logging of power-on time, power-off time and momentary power failure time) Available. In addition to normal scanning, this function allows one specified block to be scanned at high-speed fixed intervals. 1 to 190 ms, user-definable in 0.1 ms increments. Detection of memory failure, CPU failure and I/O module failure, syntax checking, etc. FA link, FL-net, personal computer link, and remote I/O link (fiber-optic FA-bus, -bus) Available. Circuit comment, sub-comment, tag name definition (including I/O comment). - Online editing - Forced SET/RESET instructions - Clock (year, month, day, hour, minute, second, and day of the week) - Configuration (setup of parameters, including device capacities, range of devices to be latched at power failure, and external outputs to be latched at sequence stop) - Protection - Stop refreshing function

Other functions

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-5
Table 1.3 Performance Data (F3SP Item
Control method I/O computation method Programming language Number of I/O points Number of internal relays (I) Number of shared relays (E) Number of extended shared relays (E) Number of link relays (L) Number of special relays (M) Number of timers (T) Number of counters (C) Number of data registers (D) Number of shared registers (R) Number of extended shared registers (R) Number of file registers (B) Number of link registers (W) Number of special registers (Z) Number of labels Number of input interrupt processing routines Decimal constant Hexadecimal constant Character-string constant Floating-point constant

- N, F3SP

- H) (1/2)

Specifications
F3SP28-3N F3SP53-4H F3SP38-6N F3SP58-6H Repeated computation based on stored programs Refreshing by DIRECT REFRESH instruction Structured ladder language and mnemonic language 4096 max. 8192 max., including remote I/O points 16384 32768 2048 2048 8192 16384 9984 1024 2048 1024 16384 32768 1024 3072 32768 8192 1024 1024 4 262144 16384

Constants

16-bit instruction: -32768 to 32767 32-bit instruction: -2147483648 to 2147483647 16-bit instruction: $0 to $FFFF (hexadecimal number) 32-bit instruction: $0 to $FFFFFFFF (hexadecimal number) 16-bit instruction: e.g. AB, etc 32-bit instruction: e.g. ABCD, etc. 32-bit instruction: e.g. 1.23, -3.21 approximately -3.41038 to +3.41038 30K steps max. 1024 max. 33 312 64 max. 0.045 to 0.18s per instruction 0.18s min. per instruction 64 instructions each 0.0175 to 0.07s per instruction 0.07s min. per instruction 0.045 to 0.18s per instruction 0.18s min. per instruction 0.0175 to 0.07sper instruction 0.07s min. per instruction 56K steps max. 120K steps max.

Program size (that can be ROM resident) Number of program blocks Basic instructions Number of Application instructions instructions Number of program blocks Instruction execution time Basic instruction

Application instruction Special module high speed read instruction (HRD instruction)/special module high speed write instruction (HWR instruction)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-6
Table 1.4 Performance Data (F3SP Item
Sampling trace function Support for personal computer link function by programming tool connection port User logging function Number of personal computer link modules Macro instruction function Scan time monitoring time Startup at power-on or recovery from power failure Sensor control function Constant scan Self-diagnosis Link function

- N, F3SP

- H) (2/2) Specifications

F3SP28-3N F3SP53-4H F3SP38-6N F3SP58-6H Available. This function collects and displays the states of multiple devices for a maximum of 1024 scans. Available. The function allows a personal computer or a monitor to be connected to the programming tool connection port to perform communications equivalent to the personal computer link module. Available. This function allows the user to execute a user log instruction to log (record the history of) errors in the user system, including information on the state of occurrence and system operation, etc. 6 max. Available. This function allows a user to create and register new user-defined instructions.

Variable from 10 to 200 ms


Automatic (Auto-logging of power-on time, power-off time and momentary power failure time) Available. In addition to normal scanning, this function allows one specific block to be scanned at high-speed fixed intervals. 1 to 190 ms, user-definable in 0.1 ms increments Detection of memory failure, CPU failure and I/O module failure, syntax checking, etc. FA link, FL-net, personal computer link, and remote I/O link (fiber-optic FA-bus, -bus) - Online editing Forced SET/RESET instructions Clock (year, month, day, hour, minute, second, and day of the week) Configuration (setup of parameters, including device capacities, range of devices to be latched at power failure, and external outputs to be latched when sequence stops) Protection

Other functions

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-7

1.2.2

Device List
Table 1.5 Device List
Device Code X Y I F3SP28-3N/-3S F3SP53-4H/-4S Range Quantity X00201 to X71664 (discontinuous) 4096 Y00201 to Y71664 (discontinuous) I00001 to 16384 I16384 E0001 to 2048 E2048 E2049 to E4096 L0001 to L72048 (discontinuous) M0001 to M9984 T0001 to T0016 F3SP38-6N/-6S F3SP59-7S F3SP58-6H/-6S Range Quantity Range Quantity X00201 to X00201 to X71664 X71664 (discontinuous) (discontinuous) 8192 8192 Y00201 to Y00201 to Y71664 Y71664 (discontinuous) (discontinuous) I00001 to I00001 to 32768 65535 I32768 I65535 E0001 to E0001 to 2048 2048 E2048 E2048 E2049 to E4096 L0001 to L72048 (discontinuous) M0001 to M9984 T0001 to T0016 E2049 to E4096 L0001 to L72048 (discontinuous) M0001 to M9984 T0001 to T0016 Remarks The range used depends on the module type

Input relay Output relay Internal relay Shared relay Nonlatched Extended type shared relay Nonlatched type 100s Timer 1ms Timer 10ms Timer 100ms Timer 100ms Timer Latched type

2048

2048

2048

Link relay Special relay

L M

8192 9984

16384 9984

16384 9984

These devices default to zero in quantity. Be sure to configure the devices when using the CPU module in a multiCPU configuration. Used in FA link and FL-net communications. Configurable for up to 16 timers Configuration limit correlated to counters (C) (*1).

Timer

T0001 to T2048

T0001 to 2048 in T3072 total

T0001 to 3072 in T3072 total

3072 in total

Continuous timer Counter Data register

C D B W Z V

C0001 to C2048 D00001 to D16384 B000001 to B32768 W00001 to W72048 (discontinuous) Z0001 to Z1024 V001 to V256 R0001 to R1024 16384 32768 8192 1024 256 1024

C0001 to C3072

C0001 to C3072

Configuration limit correlated to Timers (T) (*1)

Latched type Latched File register type NonLink register latched type Special register Index register Shared register Extended shared register

D00001 to D00001 to 32768 65535 D32768 D65535 B000001 to B000001 to 262144 262144 B262144 B262144 W00001 to W00001 to Used in FA link 16384 W72048 16384 and FL-net W72048 (discontinuous) (discontinuous) communications. Z0001 to Z0001 to 1024 1024 Z1024 Z1024 V001 to V256 R0001 to R1024 R1025 to R4096 256 1024 V001 to V256 R0001 to R1024 R1025 to R4096 256 1024 These devices default to zero in quantity. Be sure to configure the devices when using the CPU module in a multiCPU configuration.

Nonlatched type

R R1025 to R4096 3072 3072 3072

*1: See Table 1.6

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-8
Table 1.6 Device Capacities and Setup Restrictions
Device Timer Counter Shared relay Extended Shared relay Shared register Extended shared register Code T C E E R R F3SP28-3N/-3S F3SP53-4H/-4S Default Setup Restrictions value 1024 Total for timers and 1024 0 0 0 0
counters: 2048 max. Initial value for 100-s and 1-ms timers: 0

F3SP38-6N/-6S F3SP58-6H/-6S Default Setup value Restrictions 2048 Total for timers and 1024 0 0 0 0
counters: 3072 max. Initial value for 100-s and 1-ms timers: 0

F3SP59-7S Default Setup Restrictions value 2048 Total for timers and 1024 0 0 0 0
counters: 3072 max. Initial value for 100-s and 1-ms timers: 0

2048 max. 2048 max. 1024 max. 3072 max.

2048 max. 2048 max. 1024 max. 3072 max.

2048 max. 2048 max. 1024 max. 3072 max.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-9

1.2.3

Configuration
This section describes the configuration function. The configuration setup ranges are summarized in the table below.

I Configuration Function
The sequence CPU contains the predefined defaults of device sizes and operation methods. You can use these defaults to run programs. In some applications, however, they may not suit your specific purpose of use. In such a case flexibility allows for defaults to be changed to meet your needs. Changing the defaults is called configuration and can be performed through the FA-M3 programming tool WideField2 (hereinafter simply referred to as WideField2).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-10
I Tables of Configuration Ranges
Table 1.7 Configuration Range (1/5)
F3SP28-3N/-3S F3SP53-4H/-4S Item Shared relay (E) Shared Device (E, R) Extended shared relay (E) Shared register (R) Extended shared register (R) Link relay (L) Device capacities Link Device (L.W) Link register (W) 100s timer 1ms timer 10ms timer 100ms timer 100ms continuous timer Counter Default 0 0 0 0 FA links 1 to 4: 2048 FA links 5 to 8: 0 FA links 1 to 4: 2048 FA links 5 to 8: 0 0 0 512 448 128 1024 Configuration Range

2048 points max. on 32 points basis for all CPUs combined 2048 points max. on 32 points basis for all CPUs combined 1024 points max. on 2 points basis for all CPUs combined 3072 points max. on 2 points basis for all CPUs combined
8192 points max. on 16 points basis (Note) for all links combined. 8192 points max. on 16 points basis (Note) for all links combined. 2048 points on 1 point basis for timers and counters combined; 16 max. for 100s timers; Timer numbers are continuous. 2048 points on 1 point basis for timers and counters combined.

Configuration of Timer (T) / Counter (C)

Table 1.8 Configuration Range (2/5)


F3SP38-6N/-6S F3SP58-6H/-6S F3SP59-7S Item Shared relay (E) Shared Device (E, R) Extended shared relay (E) Shared register (R) Extended shared register (R) Device size Link Device (L.W) Link relay (L) Link register (W) 100 s timer 1ms timer 10ms timer 100ms timer 100ms continuous timer Counter 0 0 0 0 2048 for each system 2048 for each system 0 0 1024 896 128 1024 Default Configuration Range 2048 points max. on 32 points basis for all CPUs combined 2048 points max. on 32 points basis for all CPUs combined 1024 points max. on 2 points basis for all CPUs combined 3072 points max. on 2 points basis for all CPUs combined 16384 points max. on 16 points basis(Note) for all links combined 16384 points max. on 16 points basis(Note) for all links combined 3072 points on 1 point basis for timers and counters combined; 16 max. for 100 s timers; timer numbers are continuous. 3072 points on 1 point basis for timers and counters combined.

Configuration of Timers(T)/counters(C)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-11
Table 1.9 Configuration Range (3/5)
F3SP28-3N/-3S F3SP53-4H/-4S F3SP38-6N/-6S F3SP58-6H/-6S F3SP59-7S Item Internal relay (I) Shared and extended shared relay (E) Link relay (L) Extended device configuration Configuration of the range of devices to be latched in case of power failure Timer (T) Counter (C) Data register (D) Shared and extended shared registers (R) Link register (W) Default I0001 to I1024 Non-latched type Non-latched type Non-latched type (except for continuous timers) All latched All latched Non-latched type Non-latched type Configuration Range Configurable on 32 point basis; continuous from the starting number Configurable on 16 points basis
(Note)

Configurable on 1 point basis; continuous from the starting number (Note) Configurable on 2 points basis; continuous from the starting number (Note) Configurable on 16 points basis
(Note)

Note: The configuration range of each of shared and extended shared relays (E) and shared and extended shared registers (R) to be latched in case of power failure is assigned numbers continuous from the starting number. However, if the number of shared relays (E) is smaller than 2048, the last of them is followed by the first extended shared relay (E) numbered E2049. Likewise, if the number of shared registers (R) is smaller than 1024, the last of them is followed by the first extended shared register (R) numbered R1025. Example) In a case where there are 1024 shared relays (E) and 2048 extended shared relays (E): If you define the starting number as 513 and the number of units as 1024 for the range of devices to be latched in case of power failure, then the devices that are latched include: E513 to E1024 shared relays (E); and E2049 to E2560 extended shared relays (E). Note: The configuration range of each of link relays (L) and registers (W) to be latched in case of power failure is assigned numbers continuous from the starting number. However, the following exceptions apply. The number following L/W01024 is L/W11024. The number following L/W11024 is L/W21024. The number following L/W21024 is L/W31024. The number following L/W31024 is L/W41024. The number following L/W41024 is L/W51024. The number following L/W51024 is L/W61024. The number following L/W61024 is L/W71024. (The rules noted above are true when the number of link relays (L) or registers (W) to be used is defined as 1024. If the number is 2048, the number following L/W02048 is L/W10001.) Example) When there are 1024 link relays (L) each for link 1, link 2 and link 3: If you define the starting number as 10513 and the number of units as 1024 for the range of devices to be latched in case of power failure, then the devices included in the latching are: L10513 to L11024 link relays (L) for link 1; and L20001 to L20512 link relays (L) for link 2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-12
Table 1.10 Configuration Range (4/5)
F3SP28-3N/-3S F3SP53-4H/-4S F3SP38-6N/-6S F3SP58-6H/-6S F3SP59-7S Item Initial data for data register (D) Scan time monitoring time Constant scan time I/O module error I/O comparison error Instruction processing error Scan time exceeded Subroutine error Interrupt error Sub-unit communications error Sensor control block scan timeout Data register (D) Default None 200ms Unused Stop Stop Stop Stop Stop Stop Run Stop All Blocks Specified Blocks Run or Stop (user-definable) Configuration Range Configurable for up to 1024 contiguous points from a starting number Configurable from 10 to 200 ms on 10 ms basis Configurable from 1.0 to 190.0 ms on 0.1 ms basis

Operation mode on error Operation control Program execution mode

Enabled only if F3PU10-0N F3PU16-0N Momentary power F3PU20-0N F3PU26-0N or failure detection mode F3PU30-0N Power supply module is used Peripheral management (minimal operation) time Execution span Sensor control block Setup interrupt Input module interrupt handling Timing of interrupt Timing of interrupt

Standard

Standard or Immediate

Not Setup 200s Immediate (during instruction execution) After Instruction Sensor control block interrupt has priority Use BIN 16ms Reset None

100s to 190ms on 100s basis 200s to 25.0ms on 100s basis Immediate or After Instruction Immediate or After Instruction Sensor control block has priority or input module interrupt has priority Use/Do Not Use/Use in sensor control block; configurable on 16 points basis BIN/BCD; configurable on 16 points basis 16ms/1ms/250s/62.5s/constant; configurable on 16 points basis Reset/Hold; configurable on 16 points basis Up to 32768 contiguous points from a starting number

Priorities of sensor control block and input module interrupts Use and non-use of modules Setup DIO module Data code Input sampling interval Reset/Hold of external outputs when sequence stops Device current values Data registers (D) to be resident in ROM File registers (B)

Setup ROM

(Note) Configure on 32 points basis when using the same input module for both sensor control blocks and regular blocks.

SEE ALSO
Instruction manual (IM34M6H45-01E), Fiber-optic FA-bus Module, Fiber-optic FA-bus Type 2 module, for more information on the subunit line failure.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-13
Table 1.11 Configuration Range (5/5)
F3SP28-3N/-3S F3SP53-4H/-4S F3SP38-6N/-6S F3SP58-6H/-6S F3SP59-7S Item Default Configuration Range Mode 0: 9600bps, even parity Mode 1: 9600bps, no parity Mode 2: 19200bps, even parity Mode 3: 19200bps, no parity Mode 4: 38400bps, even parity Mode 5: 38400bps, no parity Mode 6: 57600bps, even parity Mode 7: 57600bps, no parity Mode 8: 115200bps, even parity Mode 9: 115200bps, no parity Unused/Used Yes/No Yes/No Yes/No Yes/No Link number from 1 to 8 Slot numbers from 1 to 16 Run/Stop, configurable for shared relays(E) , shared registers(R) , extended shared relays (E), extended shared registers (R) of each CPU Yes/No Peripheral process /Control process

Connection port for programming tool Setup communications

Mode

Mode 0: 9600bps, even parity

Personal computer link function

Used/Unused Checksum End character Program protection function

Unused None None None None

Setup FA link system (Mapping between FA link and FL-net numbers and slot numbers)

Range for shared refreshing (partial stop) Shared refreshing Simultaneity of shared refreshed data Mode of shared refreshing (control process)

All refreshed Yes Peripheral process

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-14

1.2.4

Components and Their Functions


This section describes the LED indicators, their states, and the programming tool connector on the front side of the sequence CPU module. These features are common to the F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 CPU modules.
F3SP28-3N F3SP38-6N F3SP28-3S F3SP38-6S CPU module operation status LED indicators
SP 8-0N CPU

F3SP53-4H F3SP58-6H F3SP53-4S F3SP58-6S F3SP59-7S


RDY RUN ALM ERR
SP5 S CPU

RDY (= READY, green) --------------------On = Normal Off = Major failure RUN (= RUN, green) ---------------------- On = Program in progress Off = Program at a stop ALM (= ALARM, yellow) ------------------ On = Minor failure Off = Normal ERR (= ERROR, red) --------------------- On = Moderate failure Off = Normal

PROGRAMMER

Major failure --------------- The CPU module is inoperable due to a hardware failure. Moderate failure ----------The CPU module cannot run or continue to run a program. Minor failure --------------- The CPU module still can run or continue to run a program though it has detected a failure. Programming tool connector ------------------------ Connected to a personal computer or handy programming console. A personal computer or a monitor can be connected to this connector when the personal computer link function is in use.

F010201.EPS

Table 1.6 summarizes combinations of the LED indicators as classified by the severity of failure.
Table 1.12 LED Indicator Combinations Based on the Severity of Failure
Status LED Indicator RDY RUN ALM ERR
: ON, : OFF,

Normal

Major Failure

Moderate Failure

Minor Failure

: ON or OFF

Table 1.13 Weight


Model F3SP28, F3SP38 F3SP53, F3SP58, F3SP59

Weight
130g 210g

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-15

1.2.5

External Dimensions
F3SP28 F3SP38 mm Unit: mm

83.2 2

28.9

100

F010202.VSD

F3SP53 F3SP58 F3SP59

113.2 83.2 30.0 2 28.9

100

F010203.VSD

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-16

1.3

Basic Configuration
This section describes units, slot numbers and I/O relay numbers which form the basic configuration of an FA-M3. Units, slots, and input/output relays are identified with unique numbers. These numbers are used in parameters of ladder instructions and configuration setup.

1.3.1

Unit
A unit is a system with the minimum configuration consisting of the following modules. Install these modules on the base module to compose the unit.
Table 1.14 Unit Components (Modules)
Name Base module Power supply module CPU module I/O module Special module Description Five types are available depending on the number of modules to the mounted. One power supply module must always be mounted on the base module. At least one CPU module is required. Several types are available depending on the functionality. Various types are available depending on the type of I/O and the number of I/O points. Various types are available, including analog I/O and communication modules.

The location where you install a module is called a slot.

I Main Unit
Install the power supply module in the leftmost slot of the base module and the CPU module in the slot on the immediate right of the power supply module. Then, install required I/O and special modules in the remaining slots. A system with this configuration is called a main unit.
CPU module

Power supply module I/O and special modules


F010301.EPS

Figure 1.1 Main Unit

I Subunit
A subunit is an I/O expansion unit. It is connected to the main unit through a fiber-optic FA-bus or fiber-optic FA- bus type 2. A maximum of seven subunits can be connected to the main unit and are identified by their unit numbers. With fiber-optic FA-bus type 2, you can separate any single subunit into a maximum of eight stations. For more information on the method of separation, see the instruction manual (IM34M6H45-01E), Fiber-optic FA-bus Module, Fiber-optic FA-bus Type 2 Module.

See Also
For details on unit numbers, see Section 1.3.2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-17

1.3.2

Slot Number
A slot number indicates the position of a slot where a module is installed. The slot number is defined as a three-digit integer, as shown below.

Slot number
Slot positions 01 to 16 are assigned to the slot on the immediate right of the power supply module through to the rightmost slot of a base module. Unit number Main unit = 0 Subunit = 1 to 7
F010302.EPS

Figure 1.2 Slot Numbers (1 of 2)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-18
Fiber-optic FA-bus type 2 module (can be installed in any position) FA-M3 main unit
001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016

Slot numbers 001 to 016

Power supply module Add-on CPUs (three CPUs max.) Subunit 1


101 102 103 104

CPU module
105 106 107 108 109 110 111 112 113 114 115 116

Slot numbers 101 to 116

Power supply module Subunit 2


201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216

Slot numbers 201 to 216

Power supply module Subunit 3


301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316

Slot numbers 301 to 316

Power supply module Subunit 4


401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416

Slot numbers 401 to 416

Power supply module Subunit 5


501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516

Slot numbers 501 to 516

Power supply module Subunit 6


601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616

Slot numbers 601 to 616

Power supply module Subunit 7


701 702 703 704 705 706 707 708 709 710 711 712 713 714 715 716

Slot numbers 701 to 716

Power supply module


F010303.EPS

Figure 1.3 Slot Numbers (2 of 2)

Install fiber-optic FA-bus type 2 modules in both the main unit and a subunit and connect these modules with a fiber-optic cable. You can attach up to seven subunits to the main unit. Subunit numbers are determined by setting the rotary switch on the front panel of each fiber-optic FA-bus type 2 module.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

1-19

1.3.3

I/O Relay Number


Each input relay (X) and output relay (Y) number is defined as a slot number followed by an I/O relay number. The I/O relay number is a number corresponding to each terminal of an I/O module. Example: The output relay number for terminal 6 of an F3YC08-ON module installed in slot 005 is defined as follows.
Y005 06
Terminal number Slot number

001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016

Slot numbers

Power supply module

Y 08-

OUT

Output relay number Y00506

F3YC08-0N
F010304.EPS

Figure 1.4 Output Relay Number

The input and output terminal numbers of a mixed-I/O module or multifunctional module with 32 input and output points each are assigned as 1 to 32 and as 33 to 64, respectively.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

2-1

2.
2.1

System Configuration
This chapter describes the FA-M3 system configuration and programming tools.

Basic System Configuration


The basic system configuration refers to a system consisting of a main unit only. For more information on the main unit, see subsection 1.3.1, Unit.
Sequence CPU module or BASIC CPU module

Power supply module


F020101.EPS

Figure 2.1 Example of Basic System Configuration (when a 13-slot base module is used)

2.2
2.2.1

Multi-CPU System Configuration


This section describes a multi-CPU system configuration and the handling of I/O modules in a multi-CPU system.

Multi-CPU System Configuration


A multi-CPU system configuration refers to a system comprising multiple CPU modules. A maximum of four CPU modules can be installed in the slots (slots 001 to 004) on the main unit. A CPU module installed in slot 001 serves as the main CPU module and CPU modules installed in slots 002 to 004 serve as the add-on CPU modules. A maximum of four sequence CPU modules can be installed at the same time, while only one F3BP BASIC CPU module is allowed in this system configuration. A CPU module installed in the Nth (N = 1 to 4) slot is called the Nth CPU (module) or CPU N.

TIP
A BASIC CPU module refers to a CPU module which is controlled by BASIC programs.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

2-2
Main CPU module

Power supply module


001 002 003 004 005 006 007 008 009 010 011 012 013

Slot numbers
F020201.EPS

Add-on CPU modules

Figure 2.2 Example of Multi-CPU System Configuration

CAUTION
Be careful not to install any CPU module in the 5th or later slot and turn on the power. Otherwise, the memory is cleared and reverts to the factory settings.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

2-3

2.2.2 Handling I/O Modules in Multi-CPU System


I Input Modules
With input modules, you can read input data through multiple CPUs. To do this, configure the CPUs so that they share the same input sampling interval for the input module in question. Be careful, as the sampling interval that you can set varies depending on the type of CPU.

I Output Modules and Multifunctional Modules Containing Y Output Relays (Y)


Combination of F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 Modules
You can send output data separately from multiple CPUs to the same output module on 16 points basis. To do this, configure the output relays (Y) of the unused modules in question as unused on 16 points basis. Also configure all output relays so that they share the same output mode in case of a sequence stop (hold or reset) within the same module.

Combination of CPU Modules Other Than Those Mentioned Above


It is not possible to share the same output module among multiple CPUs. Configure the CPU that does not use the output module so that the output module is set to unused.

SEE ALSO
For details on unused modules, see Section 4.1.4.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

2-4

2.3
2.3.1

Extended System Configuration


The extended system configuration refers to a system configured by adding remote I/O modules, a personal computer link module, and an FA link module to the basic system.

Remote I/O System


The remote I/O system refers to a system configured using fiber-optic FA-bus and FAbus type 2 communication modules. The number of remote I/O points is included in the count of all I/O points.
Fiber-optic FA-bus type 2 module

Main unit

Subunit

Fiber-optic cable

Fiber-optic FA-bus type 2 module

Subunit

Fiber-optic cable, 100-m long

F020302.EPS

Figure 2.5 Example of System Using Fiber-optic FA-bus Type 2 Modules

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

2-5

2.3.2

Personal Computer Link System


The personal computer link system refers to a system configured by connecting a personal computer or a monitor to the main unit through a personal computer link module. The sequence CPU module can be connected directly to a personal computer or a monitor.

Personal computer or monitor with PC interface

Main unit Power supply module

Personal computer link module


F020303.EPS

Figure 2.6 Example of Personal Computer Link System

2.3.3

FA Link System
The FA link system refers to a system that employs FA link communication to build a network system with programmable controllers. The types of communication covered by an FA link system are: - FA link H communication (FA link H module), and - Fiber-optic FA link H communication (fiber-optic FA link H module). Unless otherwise specified, the term FA link in this manual comprehensively refers to these two types of communication. For more information on the FA link, see the instruction manual (IM34M6H43-01E), FA Link H and Fiber-optic FA Link H Modules.

FA link Main unit Main unit Main unit

FA link H module, Fiber-optic FA link H module


F020304.EPS

Figure 2.7 Example of FA Link System

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

2-6

2.4

Programming Tool
The FA-M3 programming tool WideField2, or simply WideField2, is available as a programming tool for the F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 sequence CPU modules.

2.4.1

WideField2
Description Software Model Compatible Sequence CPU Modules F3SP05 F3SP38 F3SP08 F3SP53 F3SP21 F3SP58 F3SP25 F3SP59 F3SP28 F3FP36 F3SP35

FA- M3 Programming Tool WideField2

SF620- JCW

Personal computer

Power supply module

Sequence CPU module

F020401.EPS

Figure 2.8 WideField2

I Object Ladder
WideField2 defines blocks and instruction macros that compose a ladder program as objects, a term commonly used in the computing world. The object-oriented ladder language assumes responsibility for a given function and features a high degree of independence. Consequently, the language offers higher productivity, better maintainability and more effective program reuse, as compared to a structured programming language.

I Features G Change to Components


Blocks can be reused perfectly as components. Devices that are used within a block are defined separately. WideField2 eliminates the chance of using the same device twice and makes it easy to recombine blocks. You can also change macro functions to components.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

2-7
G Index View
You can view the overall range of even a large-size program by hiding its unnecessary part. This makes debugging more efficient.

Material feed
I***** I***** I***** Y*****

Initialization Idling Material feed Preheating Flux coating Finish coat Fixation heating Cleaning Cooling Unloading Fault-diagnosis Power-off sequence

Initialization Idling

I***** CAL I***** = +

I***** MOVE

Material feed Preheating


I***** I***** I***** Y*****

Preheating
I***** I***** I***** Y*****

I***** I*****

Y*****

I***** I***** I***** CAL I***** MOVE = +

I***** I*****

Y*****

I***** I***** I***** CAL I***** MOVE = +

Flux coating
I***** I***** I***** Y*****

Flux coating Finish coat Fixation heating Cleaning Cooling Unloading Fault-diagnosis Power-off sequence

I***** I*****

Y*****

I***** I***** I*****

Y*****

I*****

Y*****

F020402.EPS

G Group Tag Names


You can change the method of naming Tag names from an individual basis to a group basis. This enables you to define a set of data.

SW01 POMP01 OUT01

SW02 POMP02 OUT02

SW03 POMP03 OUT03

Definition of data structure

SWICH POMP OUT

MCN1 MCN1.SWICH MCN1.POMP MCN1.OUT MCN2.SWICH MCN2.POMP MCN3.OUT MCN3.SWICH MCN3.POMP MCN3.OUT MCN2 MCN3
F040403.EPS

Naming of a set of data

G Easy Data Exchange with Windows-based Applications


You can pick such data items on a Microsoft Excel screen as device names and comments to import to WideField2 (drag-and-drop function). In addition, you can copy ladder circuits in WideField2 to such applications as Microsoft Word.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

3-1

3.

Basic Sequence CPU Module Operations


This chapter describes the basic operation modes of the sequence CPU module and add-on CPU modules, as well as their methods of program execution.

3.1

Operation Modes of Sequence CPU Module


The sequence CPU module has three operation modes: Run, Debug and Stop.

I Run Mode
The Run mode is a state in which the sequence CPU module is running a program, and is used for practical system operation. You can monitor the operating status of a sequence CPU module or devices. However, you can use none of the debug functions available from the WideField2 programming tool. In this mode, the RDY and RUN LED indicators come on.

I Debug Mode
The Debug mode is used to debug and tune programs. You can execute programs in the same way as with the Run mode. In the Debug mode, you can use debugging functions, such as forced SET/RESET instructions and online editing, through the WideField2. These functions affect the scan time, however. Disable the functions when debugging and tuning are complete, and set the CPU to the Run mode. In this mode, the RDY and RUN LED indicators turn on. The Debug mode includes a pause state in which the sequence CPU module suspends program execution during such debugging operation as scan operation. In this state, the RUN LED indicator turns off and all external outputs being generated by the program are latched.

I Stop Mode
The Stop mode is a state in which the sequence CPU module stops program execution. In the Stop mode, you can remove programs and clear devices, in addition to using forced SET/RESET instructions, online editing and debug operation. In this mode, the RUN LED indicator turns off. The external outputs being generated by the program are set to ON (hold) or OFF (reset), according to the Output When Stopped setting of the Setup DIO item in the configuration. All of the external outputs are set to OFF if the option has not been set up during configuration.
Figure 3.1 LED Indicator Combinations Based on the Operation Mode
Operation Mode LED Indicator RDY RUN ALM ERR
: ON, : OFF, : ON or OFF

Run

Debug

Stop

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-2

3.2
3.2.1

Operation at Power-on/off
This section describes the operations when power is turned off or turned on.

Operation at Power-on
When the power is turned on, the CPU performs an initialization process to make itself ready for program execution. In the initialization process, the CPU performs I/O collation and instruction analysis in order to check that its hardware and programs are normal. The CPU begins program execution from the first step of a program when no error is found. If equipped with a ROM pack, the CPU reads programs from the pack and begins system operation. If in the ROM Writer mode, however, the CPU does not read programs from the ROM pack. Alternatively, it enters a command-wait state (e.g., waits for a ROM transfer command from the WideField2 ) without executing a program.
Power-on

Self-diagnosis NO The RDY LED indicator turns on.

No error? YES YES

ROM writer mode? NO

NO

Equipped with ROM pack? YES Read programs from ROM pack

Program diagnosis NO

No error? Wait for command YES Start program The RUN LED indicator turns on.

Stop The ERR LED indicator turns on.


F030201.EPS

Figure 3.1 Operation at Power-on

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-3

3.2.2

Operation at Power-off
When the power is turned off, the sequence CPU module records the date and time in its error log file and stops system operation.

TIP
Error log files allow you to save information such as time of occurrence and type of error when a system error occurs or when the power is turned on or turned off.

SEE ALSO
For details on error logs, see Chapter 18 of FA-M3 Programming Tool WideField2 Instruction Manual (IM34M6Q15-01E).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-4

3.3

Operation in Case of Momentary or Complete Power Failure


This chapter describes settings for the following: operation in case of momentary power failure, specifying the momentary power failure detection mode, operation in case of complete power failure and specifying range of devices to be latched in case of complete power failure.

3.3.1

Operation in Case of Momentary Power Failure


There are two types of power failure detection mode for detecting a momentary power failure: the standard mode and the immediate detection mode. The CPU operates differently in case of a momentary power failure, depending on the type of power failure detection mode selected. The immediate detection mode can be selected by configuration only when the F3PU10-0N, F3PU16-ON, F3PU20-0N, F3PU26-0N, or F3PU30-ON power supply module is used.

I Standard Mode
If a momentary power failure occurs, the sequence CPU module records the date and time in its error log file. The sequence CPU module suspends processing until it recovers from the power failure. This causes a delay in the scan time and timer update process. When the power has recovered, the sequence CPU module restarts at the point where it suspended processing. A program can cope with a momentary power failure since its occurrence is reflected on a special relay (M195).
AC voltage Power failure detection level Program execution Interruption

F030301.EPS

Figure 3.2 Operation in Case of Momentary Power Failure

I Immediate Detection Mode


If a momentary power failure occurs, the sequence CPU module records the date and time in its error log file. The sequence CPU module suspends processing until it recovers from the power failure. At this point the CPU sets the external outputs being generated by a program to OFF, and actuates the FAIL contact. When the power has recovered, the sequence CPU module undergoes a reset-and-start sequence and begins executing the program from its start.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-5

3.3.2

Specifying the Momentary Power Failure Detection Mode


This configuration item defines the type of momentary power failure detection mode. You can select either the standard mode or the immediate detection mode. The default is the standard mode. For more information on each of these modes, see Hardware Manual (IM34M6C11-01E, 9th edition or later).

CAUTION
For a multi-CPU configuration, the immediate detection mode must be set for none or all CPU modules.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-6

3.3.3

Operation in Case of Complete Power Failure


If a complete power failure occurs, the CPU operates as it does at power-off. You can configure the types and ranges of devices to be latched in case of this type of power failure. This strategy allows the CPU to restart, when it recovers from the power failure, at the point where it suspended processing. When the power has recovered, the CPU executes the program from its start.

TIP
Latching devices at power failure stores device states immediately before a power failure so that a program can continue execution in the same state after power is restored.

3.3.4

Specifying the Range of Devices to Be Latched in Case of Complete Power Failure


This configuration item sets the range of devices to be latched in case of a complete power failure. Specify the starting number and the number of units for each device type. Figure 3.2 shows the default setting and the configurable range of each device type.
Table 3.2 Configuration of Devices to Be Latched in Case of Complete Power Failure
Item Internal relay (I) Shared and extended shared (E) Link relay (L) F3SP28 F3SP53 I0001 to I1024 Non-latching type Non-latching type Non-latching type (except for continuous timers) All latched (C0001 to C1024) All latched (D00001 to D16384) Non-latching type Non-latching type Default F3SP38 F3SP58 I0001 to I1024 Non-latching type Non-latching type Non-latching type (except for continuous timers) All latched (C0001 to C1024) All latched (D00001 to D32768) Non-latching type Non-latching type F3SP59 I0001 to I1024 Non-latching type Non-latching type Non-latching type (except for continuous timers) All latched (C0001 to C1024) All latched (D00001 to D65535) Non-latching type Non-latching type Configuration Range Configurable on 32 points basis; continuous from the starting number (*1) Configurable on 16 points basis (*2) Configurable on 1 point basis, continuous from the starting number

Extended device Configuration

Setup Data Lock-up Range at Power Failure

Timer (T)

Counter (C) Data register (D) Shared and extended shared registers (R) Link register (W)

Configurable on 2 points basis; continuous from the starting number


(*1) (*2)

Configurable on 16 points basis (*2)

*1:

*2:

If the upper limit of the range of shared relays (E) to be used is smaller than E2049, the last of their numbers is followed by the first of the extended shared relay (E) numbers. Likewise, if the upper limit of shared registers (R) to be used is smaller than R1025, the last of their numbers is followed by the first of the extended shared register (R) numbers. The configuration ranges of link relays and registers to be latched in case of power failure are assigned numbers continuous from their starting numbers. However, the following exceptions apply. The number following L/W01024 is L/W10001. The number following L/W11024 is L/W20001. The number following L/W21024 is L/W30001. The number following L/W31024 is L/W40001. The number following L/W41024 is L/W50001. The number following L/W51024 is L/W60001. The number following L/W61024 is L/W70001. These rules are true when the number of link relays or registers to be used is defined as 1024 (default). If the number is 2048, the number following n2048 is n0001. If the number us 8192, the number following 08192 is 10001.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-7

3.4

Computation Method
This section outlines data computation (scan processing) in the sequence CPU module. Details are explained in subsequent sections. The CPU employs a stored-program iterative computation method. In this method, a created program is pre-stored in the memory of the sequence CPU module. The sequence CPU executes instructions, one at a time, starting from the first step of the program. After executing the last step in the program, the CPU performs required processing, such as self-diagnosis. It then repeats the instructions from the first step. Each of these iterative cycles is called one scan and the time required for one scan is called a scan time. In the case of F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 CPU modules, the CPU executes instructions and peripheral processes concurrently to perform each scan in a shorter time. Common processing, instruction execution, input refreshing, output refreshing, and synchronization processing are classified as a system of control-related processes, while tool service, personal computer link service, CPU service, link refreshing, and shared refreshing are classified as a system of peripheral processes. The CPU performs these two kinds of processes concurrently to speed up the control-related processes.
Peripheral processes Common processing Input refreshing Output refreshing Instruction execution Execution interrupt Peripheral processes are performed within this time range.

Fixed interval

Input refreshing for sensor control block Program execution for sensor control block Output refreshing for sensor control block Input refreshing for sensor control block Program execution for sensor control block Output refreshing for sensor control block

Shared refreshing

Link refreshing Command processing Tool service Link service CPU service

One scan

Synchronization processing If synchronization processing begins, any peripheral process is interrupted temporarily and resumes at the next scan.

Shows a case when the sensor control function is used.

Control-related process Peripheral process


F030401.EPS

Figure 3.3 Computation Method??

SEE ALSO
See Section 6.15, Sensor Control Function, for more information on the sensor control function.

TIP
Common processing includes self-diagnosis, updating of special relays (M) and special registers (Z), as well as updating of timers. The END processing is sometimes known as an END scan.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-8
TIP
The input refreshing process reflects data from input contacts of, say a DI module, to input relays (X). The output refreshing process reflects data from output relays (Y) to output contacts of, say a DO module.

TIP
The synchronization process synchronizes the system of control processes with the system of peripheral processes. In particular, it reflects data to the link refresh and shared refresh (intra-PLC communication) devices.

G System of Control-related Processes


This system performs basic operations of the sequence CPU module, such as instruction execution and I/O refreshing. Execution of the system of control-related processes is called one scan, and the execution time required by the system is usually called a scan time.

G System of Peripheral Processes


This system supports WideField2 programming tools and performs communication between the CPU module and a personal computer or an FA link module. The system of peripheral processes is concurrent with and independent of the system of control-related processes. Therefore, neither the number of modules connected nor the content of each peripheral process affects the way the system of control-related processes works.

G Synchronization between Systems of Control-related Processes and


Peripheral Processes
The system of peripheral processes is concurrent with and independent of the system of control-related processes. For processes related to operation control (e.g., run or stop) or processes requiring the simultaneity of data, however, the CPU synchronizes these two systems using a synchronization process included in the system of control-related processes. The time required for the synchronization process varies depending on its content. It affects the scan time when you use a debugging function, such as online editing.

CAUTION
If the ratio of the instruction execution time to the scan time is too small, you may fail to secure a time long enough to execute the system of peripheral processes. Consequently, the responses of link refreshing, shared refreshing, tool service, personal computer link service and CPU service will become extremely slow. If this happens, use a constant scan with an interval somewhat longer than the normal scan time, or define the peripheral processing time to secure a time long enough to execute the system of peripheral processes.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-9

3.5

Method of Executing Peripheral Processes


Peripheral processes are executed concurrently with the execution of instructions in a program. When the execution of program instructions is completed, any peripheral process is interrupted until the next scan, in order to prevent the process from affecting the scan time. This means the peripheral processing time is affected by the program execution time.
Peripheral processes Common processing Shared refreshing Input refreshing Output refreshing Instruction execution One scan Peripheral processing Link refreshing Command processing Tool service Link service CPU service

Synchronization processing
F030501.EPS

Figure 3.4 Peripheral Processing

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-10
I Peripheral Processing (Minimum Operating) Time
You can configure the peripheral processing (minimum operating) time. Use this configuration item when the instruction execution time is so short that you cannot allocate enough time to peripheral processes. To secure enough time, the scan time is lengthened, or the delays of shared refreshing, link refreshing and command processing included in the peripheral processes are shortened. If at the end of instruction execution, any peripheral process proves to have not run as long as the preset time, the process is prolonged until the expiry of the preset time. In that case, the scan is also prolonged by as much as the extended portion of the preset time. Note that the CPU ignores the peripheral processing (minimum operating) time if a constant scan is predefined.

Common processing Input refreshing Output refreshing Instruction execution Peripheral processing Wait Synchronization processing
F030502.EPS

Peripheral processing (minimum operating) time

Figure 3.5 Peripheral Processing (Minimum Operating) Time

The configurable range is from 0.1 ms to 190 ms, on 0.1 ms basis. If you do not define a peripheral processing (minimum operating) time, the CPU operates with the peripheral processing time of 0.2 ms.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-11

3.6
3.6.1

Method of I/O Processing


This section describes how I/O processing is performed, response delay, as well as I/O processing in a multi-CPU system.

Method of I/O Processing


As the method of I/O processing, the CPU uses batch refreshing. In this method, the sequence CPU module acquires all data changes in the input module into the input-relay (X) area of the CPUs data memory before executing each scan. Thus, the sequence CPU module uses data contained in this area when performing computations. Computation results are output to the output-relay (Y) area of the CPUs data memory each time a computation is performed. The results are sent to the output module, collectively and concurrently with the execution of instructions in the next scan.

External input instrument Input refreshing CPU's data memory Input-relay (X) area

Execution of computations

X00502 X00501 X00503 I0002 X00502 I0001 L0001 I0100

Y00602 Y00601 Y00603 Y00604

CPU's data memory

Computation results External output instrument Output refreshing


F030601.EPS

Output-relay (Y) area

Figure 3.6 Method of I/O Processing

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-12

3.6.2

Response Delay
The maximum response delay of the output module against a change in the input module is two scans. For more information, see Chapter 7, I/O Response Time Based on Scan Time.
External input instrument is turned on

X00502 "ON"

Y00602

"ON"

Instruction execution

Instruction execution

The change is acquired at this moment of input refreshing.

The change is reflected at this moment of output refreshing.

Response delay of two scans One scan One scan

Output External output instrument turns on.


F030602.EPS

Figure 3.7 Response Delay

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-13

3.6.3

I/O Processing in Multi-CPU System


The sequence CPU module performs refreshing when the option Use of Terminals of the I/O Module Setting item is set to Used or when Sensor Control Block is selected in the configuration. For each sequence CPU module, predefine by configuration the terminals to be refreshed. Each sequence CPU module separately refreshes the terminals according to the definition. Be careful not to configure the CPUs so that more than one CPU refreshes the same terminal of the output module. Otherwise, the resulting data of the output module will become uncertain.

SEE ALSO
Subsection 2.2.2, Handling I/O Modules in Multi-CPU System, and subsection 4.1.4, I/O Module Setting, for information on the parameters set for I/O modules and their limitation of use.

Main CPU module (sequence CPU or BASIC CPU module)

Power supply module Slot numbers Add-on CPU modules (sequence CPU or BASIC CPU modules)

F030603.EPS

Figure 3.8 Example of Multi-CPU System

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-14

3.7

Method of Executing Commands from the WideField2


Commands from WideField2 are executed by the tool service. These commands include downloading, uploading, monitoring and debugging programs.

3.7.1

Tool Service
Tool services execute commands sent from the FA-M3 programming tool WideField2. Since the tool service runs concurrently to the execution of instructions, it does not affect the scan time. The CPU does not execute the tool services if there is no command to be processed.
Monitor display X00503 Personal computer X00501 X00502 X00503 Upload Download Y00601 X00504 Y00602

Power supply module Sequence CPU module Sequence CPU Peripheral processes Common processing Input refreshing Output refreshing Instruction execution Shared refreshing

Link refreshing Command processing Tool service Link service CPU service

Synchronization processing

F030701.EPS

Figure 3.9 Execution of Commands Sent from the WideField2

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-15

3.8

Method of Executing Commands through Personal Computer Link


The CPU uses link services to execute commands sent through the personal computer link. These commands include downloading and uploading programs and reading from and writing to devices.

3.8.1

Personal Computer Link Service


Tool services execute commands sent from a personal computer or a monitor connected to the personal computer link module. Since processed concurrently with the execution of instructions, the personal computer link services do not affect the scan time. The CPU does not execute the link services if there is no command to be processed.
Personal computer or monitor

Sequence CPU module

Power supply module Personal computer link module Sequence CPU Peripheral processes Common processing Input refreshing Output refreshing Instruction execution Shared refreshing

Link refreshing Command processing Tool service Link service CPU service

Synchronization processing

F030801.EPS

Figure 3.10 Execution of Commands through Personal Computer Link

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-16

3.9

Method of CPU-to-CPU Data Communication


CPU-to-CPU communication in a multi-CPU system configured using add-on CPUs is carried out using a shared data communication method and CPU services. Communications between sequence CPU modules is carried out using shared data communications; while communications between sequence CPU modules and other types of CPU modules, such as BASIC CPU modules, is carried out using shared data communications or CPU services. This section describes methods for updating shared data, settings for the mode of shared refreshing and the CPU service.

3.9.1

Method of Updating Shared Data


CPU-to-CPU data exchange in a multi-CPU system configured using multiple CPU modules is carried out through shared relays (E), extended shared relays (E), shared registers (R) and extended shared registers (R). Hereafter, shared relays (E), extended shared relays (E), shared registers (R) and extended shared registers (R) are comprehensively referred to as shared devices. You must configure in advance the range of shared devices to be used with the local and remote CPU modules. Then, each CPU module must share the same configuration settings with other CPU modules. You can both read from and write to the shared devices specified for the local CPU modules own area. However, you can only read from the shared devices specified for the areas of other CPU modules.
SLOT1 CPU1 Shared-register area Read/write Read Read Read SLOT2 CPU2 Shared-register area SLOT3 CPU3 Shared-register area SLOT4 CPU4 Shared-register area CPU1 area CPU2 area CPU3 area CPU4 area

Read/write-enabled area Read-only area

F030901.EPS

Figure 3.11 Example of Configuring Shared Registers

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-17
Figure 3.12 shows an example of shared refreshing carried out between a sequence CPU module and an add-on CPU module. In this example, shared relays and registers are allocated as shown below. - Sequence CPU module: Shared relays (E)= E0001 to E0512 (Slot-1 CPU) Shared registers (R) = R0001 to R0256 - Add-on CPU module: Shared relays (E)= E0513 to E1024 (Slot-2 CPU) Shared registers (R) = R0257 to R0512
SLOT1 CPU

Slot-1 shared-relay area

Slot-2 shared-relay area

Slot-1 shared-register area

Slot-2 shared-register area

Shared refreshing

SLOT2 CPU

Slot-1 shared-relay area

Slot-2 shared-relay area

Slot-1 shared-register area

Slot-2 shared-register area

X00604 X00601 X00603

F030902.EPS

Figure 3.12 Shared Refreshing

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-18

3.9.2

Setting the Mode of Shared Refreshing


This section describes the range for shared refreshing (partial stop of refreshing), simultaneity of data of shared devices, and modes of shared refreshing (change to control-related process).

I Range for Shared Refreshing (Partial Stop of Refreshing)


For the shared relays (E), extended shared relays (E), shared registers (R) and extended shared registers (R) of each CPU, you can determine by configuration whether shared refreshing is carried out or not. You can stop shared refreshing from being performed between CPU modules that dont need communicate with each other for data exchange. This reduces the overall interval of shared refreshing.
SLOT1 CPU1 Shared-register area Read/write Read Read Read SLOT2 CPU2 Shared-register area SLOT3 CPU3 Shared-register area SLOT4 CPU4 Shared-register area CPU1 area CPU2 area CPU3 area CPU4 area

Area whose data is used by each CPU

F030903.EPS

Figure 3.13 Example of Setting the Mode of Shared Refreshing

If data need not be shared among add-on CPU modules, the refreshing interval of CPU2, CPU3 or CPU4 is reduced if CPU3 and CPU4, CPU2 and CPU4 or CPU2 and CPU3 are excluded from shared refreshing.

TIP
If you exclude the local CPU module from shared refreshing, the scan time reduces because the local CPU modules data updating done by the synchronization process is disabled. This prohibits data in all areas of other CPU modules from being shared, however.

I Simultaneity of Data of Shared Devices


You can determine by configuration whether or not there is the simultaneity with the data of shared devices. If you select Yes for this configuration item when the sequence CPU modules (F3SP28, F3SP38, F3SP53, F3SP58 or F3SP59 module) is combined with any of the F3SP28, F3SP38, F3SP53, FS3P58 and F3SP59 modules defined as add-on CPU modules, the simultaneity of the data is guaranteed by the unit of shared devices (shared relays (E) and registers (R), or extended shared relays (E) and registers (R)) being refreshed. If the any of the F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 modules is combined with any of the F3SP21, F3SP25, F3SP35 and F3BP modules, the simultaneity of the data is not guaranteed irrespective of the configuration settings. The No option of this configuration item is designed for the interchangeability of the F3SP21, F3SP25 and F3SP35 modules. Select this option when replacing these modules with the F3SP28, F3SP38, F3SP53, F3SP58 or F3SP59 modules.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-19
I Mode of Shared Refreshing (Change to Control-related Process)
You can change by configuration the mode of shared refreshing, which updates the data of relays (E) and registers (R) shared with other CPUs, so that it works as a controlrelated process. Include shared refreshing in peripheral processes if the scan time is important. Alternatively, include it in control-related processes if the speed of exchanging shared data is important.

Common processing Input refreshing Output refreshing Instruction execution One scan Shared refreshing

Link refreshing Command processing Tool service Link service CPU service

Synchronization processing
F030904.EPS

Figure 3.14 Executing Shared Refreshing as Peripheral Process

Executing shared refreshing as a peripheral process reduces effects on scanning.

Common processing Input refreshing (including shared refreshing) Output refreshing Instruction execution One scan

Link refreshing Command processing Tool service Link service CPU service

Synchronization processing
F030905.EPS

Figure 3.15 Executing Shared Refreshing as Control-related Process

If you execute shared refreshing as a control-related process, the scan time lengthens. This however enables you to execute shared refreshing without being affected by link refreshing or the command processing time.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-20
TIP
- Sequence of Shared Refreshing For a main CPU, shared refreshing is executed in the order of CPU2s shared relays(E) /registers(R), CPU2s extended shared relays(E) /registers(R), CPU3s shared relays(E)/registers(R), CPU3s extended shared relays(E) /registers(R), CPU4s shared relays(E) /registers(R), and CPU4s extended shared relays(E) /registers(R). - When the configuration item Mode of Shared Refreshing is set to Peripheral Process Each single scan of peripheral processing refreshes the CPUns shared relays(E) /registers(R) or extended shared relays(E) /registers(R). The data that has been read is reflected in device areas during the synchronization process occurring after the completion of shared refreshing. Note however that in a case where the configuration item Simultaneity of Shared Refreshed Data is set to Yes, refreshing may be delayed by as much as three scans of peripheral processing due to the need for synchronization with the CPUn. - When the configuration item Mode of Shared Refreshing is set to Control-related Process Each single scan of control-related processing refreshes the CPUns shared relays(E) /registers(R) or extended shared relays(E) /registers(R). Note however that when the configuration item Simultaneity of Shared Refreshed Data is set to Yes, refreshing may be delayed by as much as three scans due to the need for synchronization with the CPUn. - Reference to Local CPUs Write Area You can read data in the local CPUs write area from other CPUs. That is, you can read the data alternately from shared relays(E) /registers(R) and from extended shared relays(E) /registers(R) in that area during the synchronization process of each scan. Note however that when the configuration item Simultaneity of Shared Refreshed Data is set to Yes for any of the other CPUs, refreshing may be delayed by as much as the slowest of those CPUs scans due to the need for synchronization with that CPU.
CPU2 Shared refreshing of shared relays/registers CPU2 Shared refreshing of extended shared relays/registers CPU3 Shared refreshing of shared relays/registers Refreshing may be delayed by three scans of peripheral processing due to the simultaneity of data

Data updates are reflected by this common processing

Instruction execution

Instruction execution

Instruction execution

Instruction execution

With this common processing, it becomes possible to alternately refer to the shared relays/registers and extended shared relays/registers of the local CPU from other CPUs. (Refreshing may be delayed by as much as the slowest of these CPUs' scans due to the simultaneity of data.) One scan One scan One scan One scan
F030906.EPS

Figure 3.16 Shared Refreshing as a Peripheral Process


CPU2 Shared refreshing of sharedrelays/registers CPU2 Shared refreshing of extended shared relays/registers Refreshing may be delayed by as much as three scans due to the simultaneity of data CPU3 Shared refreshing of shared relays/registers

Data updates are reflected by this common processing Instruction execution Instruction execution

Instruction execution

Instruction execution

One scan

With this common processing, it becomes possible to alternately refer to the shared relays/registers and extended shared relays/registers of the local CPU from other CPUs. (Refreshing may be delayed by as much as the slowest of these CPUs' scans due to the simultaneity of data.) One scan One scan One scan
F030907.EPS

Figure 3.17 Shared Refreshing as a Control-related Process

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-21
SEE ALSO Tables 3.3 and 3.4 show examples of how shared refreshing affects the scan time. For more information, see Section 7.1, Information on Scan Time.
These examples assume that both CPU1 and CPU2 have 512 shared relays and 512 shared registers. Table 3.3 Durations of Interference by Shared Refreshing as a Peripheral Process with the Scan Time
Duration of Duration of Interference with Scan Synchronization Time (= Duration of Processing Synchronization Processing) 1.138ms 1.138ms 1.138ms 1.138ms Duration of Interference with Scan Time of Peripheral Processing (=Duration of Shared Refreshing) 0.916ms 3.908ms

Remote CPU

Duration of Shared Refreshing 0.916ms 3.908ms

F3SP28/38/53/58/59 F3SP21/25/35

Table 3.4 Durations of Interference by Shared Refreshing as a Control-related Process with the Scan Time
Duration of Interference with Scan Time (= Duration of Extended Shared Refreshing plus Duration of Shared Refreshing) 1.782ms 4.774ms Duration of Interference with Scan Time of Peripheral Processing 0ms 0ms

Remote CPU

Duration of Shared Refreshing

Duration of Synchronization Processing

F3SP28/38/53/58/59 F3SP21/25/35

0.916ms 3.908ms

0.866ms 0.866ms

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-22

3.9.3

CPU Service
CPU services exchange data and process commands between the sequence CPU and a BASIC CPU. Since processed concurrently with the execution of instructions, the CPU services do not affect the scan time. The sequence CPU does not execute the CPU services unless it receives commands to be processed, such as ENTER or OUTPUT, from the BASIC CPU.

Power supply module

BASIC CPU module

Sequence CPU Peripheral processes Common processing Input refreshing Output refreshing Instruction execution Shared refreshing

Link refreshing Command processing Tool service Link service CPU service

Synchronization processing

F030908.EPS

Figure 3.18 CPU Service

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-23

3.10 Method of Link Data Updating


This section describes methods of data updating and link refreshing for the FA link system.

3.10.1 Link Data Updating


Link data updating is a process of updating data by exchanging data with sequence CPU modules in remote stations through link relays (L) and registers (W). You must configure in advance the ranges of link relays (L) and registers (W) to which data is written in the local and remote stations.
Power supply module Power supply module Power supply module

F3LP

F3LP

F3LP

Link relays

Link registers

FA link module in local station

FA link module in remote station

FA link module in remote station

Data allocated to each FA link module

F031001.EPS

Figure 3.19 Link Data Updating

SEE ALSO
See FA Link H Module F3LP02-0N, Fiber-optic FA Link H Modules F3LP12-0N (IM34M6H43-01E) for more information on link data updating and link refreshing.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-24

3.10.2 Link Refreshing


Link refreshing reads data from or writes data to devices of the sequence CPU module, such as link relays (L) and registers (W), through the FA link module installed in the local unit. Thus, the link refresh process matches the link data in the storage area of the sequence CPU module to those of the FA link module. In this process, the sequence CPU module automatically reads the link data of the FA link module. This means data communication can be achieved without having to be conscious of it. As link refreshing is performed concurrently with the execution of instructions, it does not affect the scan time.
Station 1

W00001 L00033 L00001

Station-1 link-relay area

Station-n link-relay area

Station-1 link-register area

Station-n link-register area

Link refreshing

Link refreshing Station n

Station 1

Link refreshing

Link refreshing

Station n

Station-1 link-relay area

Station-n link-relay area

Station-1 link-register area

Station-n link-register area

L00003

X00604 W00001 L00033

X00601 L00001 X00603

F031002.EPS

Figure 3.20 Link Refreshing

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-25 Setting the Mode of FA Link Refreshing


FA link refreshing is performed in peripheral processing. Link refreshing runs concurrently with instruction execution so it does not affect the scan time.

Common processing Input refreshing Output refreshing Instruction execution


One scan

Shared refreshing

Link refreshing

Command processing Tool service Link service CPU service

Synchronization processing
F031003.EPS

Figure 3.21 FA Link Refreshing Carried Out in Peripheral Processing

Link refreshing updates the link relays(L) /registers(W) of FA link 1 to FA link 8 in each cycle of peripheral processing.
Link relays/registers of FA link 1 Link relays/registers of FA link 2 Link relays/registers of FA link 3

Results of link refreshing are reflected by this common processing. Instruction execution Instruction execution Instruction execution Instruction execution

One scan

One scan

One scan

One scan
F031004.EPS

Figure 3.22 FA Link Refreshing Sequence

TIP
Tables 3.5 shows an example of how link refreshing affects the scan time. For more information, see Section 7.1, Information on Scan Time.

Table 3.5 Durations of Interference by Link Refreshing with the Scan Time
Number of Link Devices Example 1 Example 2 Link relay = 1024 units Link register = 1024 units Link relay = 2048 units Link register = 2048 units Duration of Interference with Scan Time 3.314ms 6.578ms Duration of Interference with Scan Time of Peripheral Processing 16.38ms 32.7ms

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-26

3.11
3.11.1

Method of Interrupt Processing


This section describes interrupt processing, interrupt processing control, interrupt timing, and interrupt priority.

Interrupt Processing
The sequence CPU module detects the rising edge of an interrupt input from an input module and executes an input interrupt program. You can register a maximum of four interrupt programs with the sequence CPU module using an interrupt instruction (INTP instruction.) The module can accept a maximum of eight interrupts at the same time. Interrupt programs are executed in the order in which their interrupt factors occur. If any interrupt factor occurs during execution of an interrupt program, the factor is processed when the interrupt program finishes.

Interrupt factor 1

Interrupt factor 2

Interrupt program 1 Executed when interrupt program 1 finishes. Interrupt program 2

Interval of waiting for completion of interrupt program 1.

F031101.EPS

Figure 3.28 Interrupt Processing

CAUTION
Do not register any interrupt program intended for a particular input module with two or more CPU modules. This is because the modules may fail to execute interrupt processing. Do not use a TIMER instruction in any interrupt program because the instruction may not work correctly.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-27

3.11.2 Interrupt Processing Control


You can control the execution of interrupt programs by means of programming. Use EI and (Enable Interrupt) DI (Disable Interrupt) instructions to determine whether the interrupt program in question is executed (cancellation of interrupt prohibition) or not executed (prohibition of interrupt). The default is the Executed option. Although the sequence CPU recognizes any interrupt occurring in a case where you have selected the Not executed option with a DI instruction, it does not execute the relevant interrupt program. Such interrupts are processed in order of their occurrence after you have selected the Executed option with an EI instruction. A maximum of eight interrupts are accepted at the same time. Simultaneous input of nine or more interrupts results in an interrupt error.
I0001 Y00602

Occurrence of interrupt X00503 X00501 No interrupt pro grams are executed in this interval. I0002 X00502 I0003

DI Y00603 I0004

EI

INTP

X00301

IRET
F031102.EPS

Figure 3.29 Interrupt Processing Control

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-28

3.11.3 Interrupt Timing


Using the configuration function of the WideField2, set the timing of interruption by an interrupt program that takes place during program execution. The configuration item Interrupt Timing has the following two options.
Table 3.7 Timing Options of Interrupt Processing
Interrupt Timing After completion of instruction execution (default) Immediately during instruction execution Description The sequence CPU switches to an interrupt program (part between INTP and IRET instructions) at the end of a ladder instruction. This switching does not take place, however, during synchronization processing, common processing or refreshing. The sequence CPU switches to an interrupt program (part between INTP and IRET instructions) during execution of a ladder instruction. This switching also takes place during synchronization processing, common processing or input refreshing.
Execution of input interrupt programs

Execution of normal programs LD

OUT LD

BMOV

Execution of input interrupt program (Part between INTP and IRET instructions) Next instruction
F031103.EPS

Figure 3.30 Execution of Interrupt Program after the Completion of Instruction Execution

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-29
Execution of normal programs LD OUT LD BMOV Execution on input interrupt programs

Interruption of program execution Continuation of BMOV instruction Next instruction

Execution of input program (Part between INTP and IRET instructions)

F031104.VSD

Figure 3.31 Immediate Execution of Interrupt Program during Instruction Execution

The features of these two interrupt timing options are as follows.


Table 3.8 Features of Interrupt Timing Options
Item Execution of Interrupt Program after the Completion of Instruction Execution Processing time of instruction under execution (*2) + switching time (*3), or duration of synchronization processing (*4) + duration of common processing (*4) + duration of input refreshing + switching time (*3) Guaranteed on an instruction basis Immediate Execution of Interrupt Program during Instruction Execution Switching time only (*3)

Execution delay (*1) Simultaneity of data


*1: *2: *3: *4:

None for multiple devices

Does not include the response time of an input module. For information on the response time of each input module, see the instruction manual (IM34M6C11-01E), Range-free Multi-controller FA-M3 - Hardware. For information on the instruction processing time, see the explanation of the instruction processing time given in the appendix of the instruction manual (IM34M6P12-03E), Sequence CPU Modules - Instructions. 120 s for F3SP28 and F3SP38 modules and 100 s for F3SP53, F3SP58 and F3SP59 modules. See Section 7.1, Information on Scan Time.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-30
CAUTION
G

Output of Data by Interrupt Programs, Which Are Executed Immediately during Instruction Execution, to Relays Be careful when outputting data to relays using such an instruction as OUT, SET or RST in a case where interrupt processing is applied along with the timing option Immediately during instruction execution. That is, do not output data in a normalscan program to any of the relays numbered 1 to 16 if you have already output data in an interrupt program to any of these relays (there is no limitation on inputting data, however). See the programming example given below. Example) Interrupt program: OUT I2 Normal-scan program: OUT I1 - Not allowed. OUT I17 - Allowed. The same rule applies to relays numbered 17 to 32, 33 to 48, 49 to 64, and so on. If you have included such an output instruction in both the interrupt program and normal-scan program, the CPU may not output data to the relay in question.

CAUTION
G

Simultaneity of Multiple Devices in Interrupt Programs Executed Immediately during Instruction Execution There is no simultaneity of data for multiple devices in the case of executing an interrupt program whose timing option is Immediately during instruction execution. The time the simultaneity of data is required is when multiple devices data is exchanged between a normal-scan program and an interrupt program using a block transfer instruction (BMOV), a long-word instruction containing a IEEE singleprecision floating point instruction, or two or more instructions. For example, consider the case shown in Figure 3.30 where an interrupt program is executed when a block transfer instruction (BMOV) in a normal-scan program is in progress; in which case, there is a risk that data under block transfer is rewritten before and after the execution of the interrupt program. If the simultaneity of data is required when executing an interrupt program whose timing option is Immediately during instruction execution, follow either of the two instructions given below. 1. Use DI (prohibition of interrupt) and EI (cancellation of interrupt prohibition) instructions to prevent any interrupt program from being executed when exchanging data of multiple devices. 2. Use an application program to carry out flag control using relays between a normal-scan program and an interrupt program.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-31
CAUTION
G

Simultaneity of Refresh Data in Interrupt Programs Executed Immediately during Instruction Execution If you select the timing option Immediately during instruction execution for an interrupt program, the program is executed even during synchronization processing, input refreshing or common processing. If the program is executed during synchronization processing or input refreshing, it is possible for you to read devices (I/O relays (X/Y), shared and extended shared relays (E), shared and extended shared registers(R), and link relays and registers (L/W)) which are being refreshed. If you rewrite these devices by the interrupt program, the simultaneity of data is lost before and after the execution of the program. To prevent any interrupt program from being executed during synchronization processing, input refreshing and common processing, execute a DI instruction at the end of a normal-scan program. In combination with this instruction, execute an EI instruction at the start of the normal-scan program.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

3-32

3.11.4 Interrupt Priority


Define the sub-item Interrupt Priority of the configuration item Interrupt Setting of the WideField2, in order to determine priority when the timing of interrupt processing coincides with the interrupt timing of a sensor control block. Table 3.9 shows the two options of the Interrupt Priority sub-item, along with the way they work.
Table 3.9 Options of Interrupt Priority Sub-item and Their Functionality
Interrupt Priority Sensor control block interrupt has priority (first) Input module interrupt has priority Functionality When an interrupt from an input When the time of executing a module occurs during execution sensor control block arrives of a sensor control block during interrupt processing Aborts the interrupt once and Executes the interrupt process after resumes the process after executing executing the sensor control block. the sensor control block. Aborts the execution of the sensor control block once and resumes the Executes the sensor control block execution after executing the after executing the interrupt process. interrupt process.

CAUTION
The sequence CPU follows the rules of execution timing (after completion of instruction execution or immediately during instruction execution) discussed above, even when the execution of the sensor control block or interrupt process is aborted due to the interrupt priority.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-1

4.

Devices
This chapter describes the types and functions of devices available with the sequence CPU modules. Relay devices are accessed on a one-bit basis. Thus a relay device number corresponds to a bit. Register devices are accessed on a 16-bit basis. Thus a register device number corresponds to 16 bits.

4.1

I/O Relays (X/Y)


I/O relays (X/Y) are devices used to exchange data with external devices. I/O-relay (X/Y) numbers are determined by the position of the slot where an I/O module is installed. They are fixed, discontinuous numbers and are assigned in increments of 64 relays for each slot. The input-relay (X) numbers never coincide with any of the outputrelay (Y) numbers. Data held in the I/O relays is not retained when the power is turned off. For more information on I/O-relay (X/Y) number definitions, refer to Section 1.3, Basic Configuration.

4.1.1

Input Relays (X)


Input relays are used to input the ON and OFF states of external devices, such as pushbuttons and limit switches. In programs, you can use these relays for contacts a and b and Application Instructions. Input-relay numbers are coded as X mmnn, where: mm mm nn
Input from external devices

= Slot number = Unit number (0 to 7) = Slot position (01 to 16) =Terminal number (1 to 64)
X00502 X00501 X00503 X00501 X00502 X00504 X00502 X00503
F040101.VSD

Y00602 Y00601 Y00603 Y00604

Figure 4.1 Input Relays (X)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-2

4.1.2

Output Relays (Y)


Output relays are used to output the results of program-based control to external devices, such as actuators. In programs, you can use these relays, for example, for contacts a and b, coils and Application Instructions. Output-relay numbers are represented as Y mmnn, where: mm = Slot number = Unit number (0 to 7) mm = Slot position (01 to 16) nn = Terminal number (1 to 64)
X00502 X00501 X00503 X00501 X00502 X00504 X00502 X00503
F040102.VSD

Y00602 Y00601 Y00603 Y00604 Output to external devices

Figure 4.2 Output Relays (Y)

4.1.3

Allocation of I/O Addresses


There is no need to allocate I/O address through the WideField2. I/O-relay numbers are determined by the position of the slot where an I/O module is installed. They are fixed, discontinuous numbers and assigned in increments of 64 relays for each slot. An empty slot is regarded as being equivalent to 64 relays.
1 2 3 4 1 2 3 4
Empty Empty Empty slot slot slot Empty slot 32 32 32 32 32 32 64 relays relays relays relays relays relays relays

CPU X32 X32 Y32

Relay numbers

X00201 to X00232 1
Empty slot 64 relays

X00301 to X00332 2 3
Empty

Y00401 to Y00432 4 5
Empty

5 Y32

CPU X64

X32 Empty slot

64 relays

slot Empty slot slot 32 32 32 32 64 relays relays relays relays relays

Relay numbers

X00201 to X00264

X00301 to X00332

Y00501 to Y00532
F040103.EPS

Figure 4.3 Allocation of I/O Addresses

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-3

4.1.4

Configuring DIO Modules


This section describes settings for terminal usage (use/non-use/sensor control block), data code (BIN/BCD), input sampling interval (16 ms/1.0 ms/250s/62.5s/constant), and holding/resetting output relays when the program stops.

I Specifying Terminal Usage


With the configuration function, select one of the three options, Use, Use in Sensor CB, and Do Not Use, in order to determine whether the I/O module is used in programs, or in the sensor control block (CB), or not used at all. In this selection, configure the I/O module on 16 points basis (see the second caution below, when the selected option is Use in Sensor CB). Also configure multifunctional modules containing I/O relays (X/Y) in the same way as discussed here. I/O relays that are included in the option Do not Use are not refreshed at all. By default, all I/O modules are set to the option Use.

SEE ALSO
For details on Sensor Control CB (senor control block), see Section 6.15.

CAUTION
When using output modules or advanced modules with output modules or Y output relays(Y) in multi-CPU system configuration Cases where F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 CPU modules are combined You can output data from multiple sequence CPU modules separately to the output relays (Y) of the same output module in increments of 16 relays. To do this, set the unused output terminals to the option Do not Use in increments of 16 terminals. Cases where CPU modules other than those noted above are combined It is not possible to use the same output module with multiple CPUs. Configure the CPU that does not use the output module so that the output module is set to Do not Use.

CAUTION
- When using the sensor control block (CB) When using an input or output module in the sensor control block, configure: - the input module in units of long words (i.e., 32 relays and 32 terminals - terminals 1 to 32 or 33 to 64); and - the output module in units of words (i.e., 16 relays and 16 terminals). Now, lets consider a case where you have made a mistake configuring the input module in units of words (for example, you have set terminals 1 to 16 to the option Used [for normal scans] and terminals 17 to 32 to the option Use in Sensor CB). Since input refreshing is performed in units of long words, input (X) relays used under a normal scan are refreshed by the Refresh instruction of the sensor control block when the normal scan is in progress. Consequently, the simultaneity of data is not guaranteed before and after the refreshing. The simultaneity of data is also not guaranteed for input (X) relays used in the sensor control block.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-4
CAUTION
When using a Direct Refresh (DREF) instruction

Set the output relays (Y) to be refreshed in a DREF instruction of a program to the option Do not Use. If you set them to the option Use or Use in Sensor CB, the values one scan earlier may be overwritten with the values output by the DREF instruction because of the timing of output refreshing that is executed concurrently with the instruction.

I Specifying Data Code Type


Determine whether data held in I/O relays (X/Y) should be handled as BIN data or handled as BCD data when you use them for a Compare, Arithmetic or Move instruction. All internal computations are based on BIN data. For this reason, if you set the I/O relays to the option Handled as BCD Data, the type of data code (format) of the input relays is automatically converted from BCD to BIN, while the data format of the output relays is automatically converted from BIN to BCD. This option enables you to handle data easily, without having to be conscious of the data format during programming, in cases where data handled by external devices are in BCD format. By default, all I/O modules are set to the option Handled as BIN Data. You can specify the data code type in increments of 16 relays.

I Specifying Input Sampling Interval


Set the input sampling interval of input modules. This setting is not effective for some input modules, however. Refer to the data item response time in the specifications section of each individual input module discussed in Hardware Manual (IM34M6C1101E). You can select from the five options, 16 ms, 1.0 ms, 62.5 s, 250 s and Constant. By default, all input modules are set to 16 ms. You can specify the sampling interval in increments of 16 relays.

CAUTION
If a single input module (or advanced module with input relays X ) is used with two or more CPU modules in multi-CPU system configuration, configure the CPUs so that they share the same sampling interval for that input module. (Also re-configure any CPU whose input relays (X) were set to the option Do not Use, so that their settings become equal to those of other CPUs.) Otherwise, system operation may become unstable.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-5
I Holding/Resetting Output Relays When a Program Stops
Determine whether the output relays (Y) of an output module (or multifunctional module with output relays Y ) should be placed in a Hold state or Reset state when a program stops (due to a moderate or major failure or a change to stop mode). The setting of this configuration for a stop of programs due to a major failure is not effective for some output modules, however. Refer to the data item output in case of stop of programs in the specifications section of each individual output module discussed in Hardware Manual (IM34M6C11-01E). For a multifunctional module, the setting for a stop of programs due to a major failure is always ineffective. By default, all output modules are set to the option Reset. You can perform this configuration in increments of 16 relays.

CAUTION
When using output modules or advanced modules with Y relays in multi-CPU system configuration output

Cases where F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 CPU modules are combined You can output data from multiple sequence CPU modules separately to the output relays of the same output module in increments of 16 relays. To do this, configure the sequence CPU modules so that all of them share the same output mode, either the Hold or Reset option. (Also re-configure any sequence CPU modules whose output relays were set to the option Do not Use, so that their settings become equal to those of local sequence CPU modules.) Cases where CPU modules other than those noted above are combined It is not possible to share the same output module with multiple CPUs.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-6

4.2

Internal Relays (I), Shared Relays (E) and Extended Shared Relays (E)
This section describes internal relays (I), shared relays (E), and extended shared relays (E). Internal relays (I) are 1-bit variables that can be used without restriction in a program. Shared relays (E) and Extended Shared relays (E) are 1-bit variables that can be used to perform data communications between CPUs in a multi-CPU system.

4.2.1

Internal Relays (I)


Internal relays are auxiliary relays available for programs. In programs, you can use these relays, for example, for contacts a and b, coils and Application Instructions. Unlike I/O relays (X/Y) however, these relays cannot directly exchange signals with an external device. There is no limitation on the number of contacts a and b that can be used in a program.
I0001 X00501 X00503 X00501 X00502 I0002 X00502 I0003
F040201.VSD

Y00602 I0003 Y00603 I0004

Figure 4.4 Internal Relays

With the configuration function, you can configure a range of internal relays to determine whether or not they retain computation results when the power is turned off. If you set the internal relays so as not to retain computation results, they are cleared to OFF (0) when you: - turn off the power once and turn it on again; - change the operation mode to Run or Debug with the WideField2; or - send a Clear Device command from WideField2. If you set the internal relays so as to retain computation results, they retain those until power-off. In this case, the relays are cleared to OFF (0) when you send a Clear Device command from the programming tool. - send a Clear Device command from WideField2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-7

4.2.2

Shared Relays (E) and Extended Shared Relays (E)


Shared and extended shared relays are used to perform communications between CPU modules in cases where a sequence CPU module and add-on CPU modules are installed. Shared relays (E) are available with the F3SP21, F3SP25, F3SP28, F3SP35, F3SP38, F3SP53, F3SP58 and F3SP59 sequence CPU modules, as well as with an add-on sequence CPU module that is combined with one of those sequence CPUs. Extended shared relays (E) are only available if one of the F3SP25, F3SP28, F3SP35, F3SP38, F3SP53, F3SP58 and F3SP59 sequence CPU modules is combined with any one or more of the CPUs installed as add-on CPU modules. In programs, you can use these relays, for example, for contacts a and b, coils and Application Instructions. In addition, you can exchange ON/OFF data between CPUs by using shared relays (E) of the local CPU as coils and those of the remote CPUs as contacts.

CAUTION
If you write data to a device area other than that of the local CPU, information held by shared and extended shared relays (E) of remote CPUs are overwritten. This results in a failure for these shared relays to reflect the correct results of computation. By default, no shared relays are assigned as devices. When using add-on CPU modules, set the range of shared relays to be used. Assign the same range for all of the CPU modules. Otherwise, the shared relays (E) are not correctly refreshed.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-8
Figure 4.5 shows an example of how specific shared relays are shared if you allocate shared relays E0001-0512 to CPU1 and E0513-1024 to CPU2.
CPU1 I0001 E0513 X00502 E0010 I0003

CPU2 X00503 X00501 E0010 X00502 I0003


F040202.VSD

Y00603 E0513

Figure 4.5 Shared Relays

With the configuration function, you can configure a range of shared relays (E) to determine whether or not they retain computation results when the power is turned off. By default, all shared relays are set so as not to retain computation results. If you set the internal relays to this option, they are cleared to OFF (0) when you: - turn off the power and turn it on again; - change the operation mode to Run or Debug with the WideField2; or - send a Clear Device command from WideField2. If you set the internal relays so as to retain computation results, the latest results are retained after power-off. In this case, the relays are cleared to OFF (0) when you send a Clear Device command from the programming tool. - send a Clear Device command from WideField2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-9
CAUTION
When using shared or extended shared relays (E), follow the precautions given below. (1) Index modification of shared or extended shared relays (E) When applying index modification to shared or extended shared relays (E) of the local CPU, be careful that a relay number resulting from index modification does not exceed the range specified by configuration for the local CPU. Otherwise, information held by shared or extended shared relays (E) of the sequence CPU modules is overwritten. This results in a failure for these shared relays to reflect the correct results of computation.
X00503 X00601 E0010 V01 X00602 I0003 Y00703 Y00702 Make sure the relay number does not exceed the range set for the local CPU. F040203.VSD

Figure 4.6 Precautions when Using Shared or Extended Shared Relays (E) (1 of 2)

(2) Block move and computation of multiple devices When using shared or extended shared relays (E) in an instruction for transferring or computing multiple devices, be careful that the specified range of these relays does not exceed the range specified by configuration for the local CPU. Otherwise, information held by shared or extended shared relays (E) of the sequence CPU modules is overwritten. This results in a failure for these shared relays (E) to reflect the correct results of computation.
X00601 X00604 BMOV D0001 E0001 D0100

X00601

X00602 BMOV D0001 E0001 10


F040204.VSD

Make sure the range does not exceed the range set for the local CPU.

Figure 4.7 Precautions when Using Shared or Extended Shared Relays (E) (2 of 2)

(3) Simultaneity of data With the configuration function, you can select either Yes or No for the simultaneity of data of shared devices. If you select the Yes option, the simultaneity of the data is guaranteed in units of devices (shared relays(E) /registers or extended shared relays(E) /registers) to be refreshed when one of the F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 sequence CPU modules is combined with add-on CPU modules. (The simultaneity of data held by the shared relays (E) /registers or extended shared relays(E) /registers is not guaranteed, however.) If any of the F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 CPUs is combined with any of the F3SP21, F3SP25, and F3SP35 sequence CPU modules, the simultaneity of the data is not guaranteed irrespective of the configuration settings. The No option of this configuration item is designed for the interchangeability with the F3SP21, F3SP25 and F3SP35 CPUs. Select this option when replacing these CPUs with the F3SP28, F3SP38, F3SP53, F3SP58 or F3SP59 sequence CPU modules.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-10
I Configuring Shared and Extended Shared Relays (E) in Multi-CPU System
Set the range of shared and extended shared relays (E) to be used by each CPU when add-on CPU modules are installed. You can allocate a desired number of relays on 32 points basis. Extended shared relays (E) are only available if one of the F3SP25, F3SP28, F3SP35, F3SP38, F3SP53, F3SP58 and F3SP59 sequence CPU modules is combined with any one or more of the CPUs installed as add-on CPUs.
Table 4.1 Configuration of Shared Relays
F3SP28 F3SP38 F3SP53 F3SP58 F3SP59 Configuration Range 2048 points max. on 32 points basis for all CPUs combined (E0001 to E2048) 2048 points max. on 32 points basis for all CPUs combined (E2049 to E4096)

Item Default Shared relay (E) Extended shared relay (E) 0 0

CAUTION
The starting number of extended shared relays (E) is always E2049 even if the range of shared relays (E) to be used is less than 2048.

CAUTION
Apply the same allocation of shared/extended shared relays (E) to all CPUs. If the allocation differs from CPU to CPU, shared refreshing is not performed correctly. This results in a failure for these relays (E) to reflect the correct results of computation.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-11
Shared relays E0001 E0257 1024 points 1024 points 1024 points CPU 1 256 points CPU 2 256 points CPU 4 256 points CPU-1 shared relays CPU-2 shared relays CPU-3 shared relays CPU-4 shared relays

E1281 512 points E1793 256 points 256 points 256 points 512 points 512 points

Extended shared relays CPU 1 E2079 1024 points E3073 256 points

CPU 2 1024 points

CPU 4 1024 points CPU-1 extended shared relays CPU-2 extended shared relays CPU-3 extended shared relays CPU-4 extended shared relays
F040205.EPS

256 points

256 points

E3329 512 points E3841 256 points 256 points 256 points 512 points 512 points

Figure 4.8 Example of Allocating Shared/Extended Shared Relays (E) when Four Sequence CPU Modules Are Installed

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-12

4.3

Link Relays (L) and Link Registers (W)


This section describes link relays (L), link registers (W), their settings, system numbers, as well as the link refreshing range. Link relays (L) are 1-bit parameters used for data communications with FA link systems. Link registers (W) are 16-bit parameters used for data communications with FA link systems. Link relays (L) and link registers (W) are devices used to exchange data with other programmable controllers through FA link modules. Before using the link relays, specify the range of links for both the local and the remote stations. You can use configuration to specify which computation results will be held when power is turned off. By default, all link relays (L) and link registers (W) are set to not hold their data when the power is turned off. A link relay or register that is set to not hold its value will reset to 0 when you: - Turn on the power. - Switch to Run or Debug mode from WideField2. - Execute the Clear Device command from WideField2. If set to be held, the last computation result is retained even when the power is turned off. If you want to clear the a value to 0: - Send the device clear command from WideField2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-13

4.3.1

Link Relays (L)


Link relays are used to exchange data with other programmable controllers through FA link modules. In programs, you can use these relays, for example, for contacts a and b, coils, and Application Instructions. In addition, you can exchange ON/OFF data between CPUs by using link relays (L) of the local station as coils and those of remote stations as contacts. Before using the link relays, specify the range of links for both the local station and remote stations.
Station 1 I0001 L0513 X00502 L0010 I0003

Station 2 X00603 X00601 L0010 X00602 I0003


F040301.VSD

Y00703 L0513

Figure 4.9 Link Relays (L)

The relay number is coded as Lmnnnn, where: m = FA link module number 1 (0 to 7) nnnn = Link relay number
Table 4.2 Range of Link Relay Number
Module (Optic) FA Link H Module High Speed Normal Speed Configuration Range 1 to 1024 1 to 2048

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-14

4.3.2

Link Registers (W)


Link registers are used to exchange data with other programmable controllers through FA link modules. In programs, you can read from or write to link registers in 16-bit or 32bit increments using Application Instructions. When you use a long word, the lower-order 16 bits are stored in the link register with the number specified in the instruction and the higher-order 16 bits are stored in the link register (W) with that number incremented by 1. Data exchange can be performed between the local station and remote stations by writing data to link registers of the local station and reading it from the remote stations. Before using the link registers, specify the range of links for both the local station and remote stations.
Station 1 X00502 MOV X00501 X00502 $100 W0001 Y00601

Station n X00503 X00501 X00504 T001 X00503


F040302.VSD

MOV

W0001

D0001 Y00602

Figure 4.10 Link Registers (W)

The register number is coded as Wmnnnn, where: m = FA link module number 1 (0 to 7) nnnn =Link register number
Table 4.3 Range of Link Register Number
Module (Optic) FA Link H module High speed configuration Normal configuration Configuration Range 1 to 1024 1 to 2048

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-15

4.3.3

System Numbers
In a FA link system, modules are automatically assigned system numbers based on their slot positions, where the module with the smallest slot number will be named system 1.
System 1 L (W) 10001 System 2 L (W) 10001 System 3 L (W) 20001 System 4 L (W) 30001 System 5 L (W) 40001 System 6 L (W) 50001 System 7 L (W) 50001 System 8 L (W) 70001 F040303.VSD

System numbers 1 2 3 4 5 6 7 8

Figure 4.11 Assignment of System Numbers

To manually assign system numbers to modules independent of their slot positions, use configuration setup to assign fixed system numbers to slot positions.
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8 Slot 9 Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8 Slot 9

Allocation change

System numbers 1 2 3 4 5 6 7 8

System numbers 8 7 6 5 4 3 2 1

F040304.VSD

Figure 4.12 Changing System Number Assignment

F040305.VSD

Figure 4.13 WideField2 Configuration Setup

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-16

4.3.4

Configuring Link Relays (L) and Registers (W)


Set the range of link relays and registers to be included in each link. More specifically, specify the number of link relays and registers used for each FA link module number, as well as the range of link relays and registers to which data is written at the local station or from remote stations.
Table 4.4 Configuration of Device Sizes
F3SP28 F3SP53 Default Link relays (L) for each FA link system Device Size Link registers (W) for each FA link system FA systems 1 to 4: 2048 points FA systems 5 to 8:0 FA systems 1 to 4: 2048 points FA systems 5 to 8:0 points Configuration Range 18192 max. for all systems combined, 16 points basis 8192 max. for all systems combined, 16 points basis F3SP38 F3SP58 F3SP59 Default Configuration Range 2048 points for each system 2048 points for each system 16384 max. on 16 points basis for all systems combined 16384 max. on 16 points basis for all systems combined

Item

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-17

4.3.5

Link Refreshing Range


This section describes the link refreshing range for an FA link.

Setting Link Refreshing Range in for an FA Link


Link refreshing of a FA link module is performed only for link relays (L) and link registers (W) that are used by instructions coded in a program.

Link Relay (L)


If link relays (L) are directly coded in a program, each word containing such a link relay is refreshed. If link relays (L) are specified by index modification, each word including the link relay (L) pointed by the index register with a value of 0 is refreshed.
Y00035 V02 L00001 to L00016 (including L00003) are refreshed L00033 to L00048 (including L00035) are refreshed

L00003

F040306.VSD

Figure 4.14 Link Relay (L) Link Refreshing Range

Link Register (W)


For an instruction that handles word data, the link register (W) specified in the instruction is refreshed. For an instruction that handles long-word data or IEEE single-precision floatingpoint data, the link register (W) specified in the instruction and the data in link register (W) +1 are refreshed. For an instruction that handles two or more words of data, the specified range of words is refreshed if the range is specified by a constant, or only first word is refreshed if the range is specified by a register.
M035 M035 M035 M035 L MOV BMOV W00051 W00030 D00034 D00051 5 V03 MOV D00001 W00061
W00061 is refreshed.
F040307.VSD

MOV

D00001

W00012

W00012 is refreshed. W00030 and W00031 are refreshed.


W00051 to W00055 are refreshed.

Figure 4.15 Link Refreshing Range for Link Registers (W)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-18
TIP
Link relays (L) and link registers (W) specified in a program are link-refreshed irrespective of whether or not the relevant instructions are executed. If you want to link-refresh all link relays (L) and link registers (W), include the following codes in the program:

M034 M034

BSET BSET

0 0

L00001 W00001

64 1024
F040308.VSD

Figure 4.16 Link-refreshing L00001 to L01024, and W00001 to W01024 If link relays (L) and link registers (W) are specified by index modification, define the index modification range as shown below so that they will be link-refreshed.

M034

BSET

W00021

10
F040309.VSD

Figure 4.17 Link-refreshing W00011 to W00020 (index modified)

CAUTION
(1) Index modification/indirect designation - Index modification/indirect designation must not be made across different systems. Refer to TIP to link-refresh link relays and registers with index modification or indirect designation. (2) Block move and computation involving multiple devices - Block move or computation for multiple devices must not be made across different systems. Be careful especially when specifying the number of bytes of data to be moved or the number of computations using devices. If you specify the number of bytes of data to be moved or the number of computations using devices, refer to TIP so that all relevant devices are linkrefreshed. (3) Multi-CPU configuration - Multiple CPU modules cannot share the same FA link module. Ensure that only one CPU module is accessing a FA link module.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-19

4.4

Special Relays (M)


Special relays have specific functions, such as indicating the internal state of the sequence CPU module or detecting errors. In programs, these relays are used mainly for contacts a and b.

4.4.1

Block Start Status


Block start status relays indicate which block is running when the selected blocks are being executed. These relays are numbered in ascending order as M001, M002, . . ., to correlate with block 1, block 2, ...
Table 4.5 Block Start Status
Item Relay Number M0001 to M0032 M2001 to M3024 Description Block n start status relay Block Start Status Functionality Explanation Indicate whether or block ON : Run n is in progress or at a OFF : Stop stop when blocks are selected and executed.

Note: The start status relays assigned to blocks 1 to 32 are M0001 to M0032 and M2001 to M2032, where the values of M0001 to M0032 are the same as those of M2001 to M2032. Similarly, start status relays M2033 to M3024 are assigned to blocks 33 to 1024.

CAUTION
Do not write to a special relay (M), including those not listed in the table above (e.g., M067 to M128), unless otherwise stated. This is because they are used by the sequence CPU module for the system side. If you inadvertently write to these relays, a failure, such as a system shutdown, may result. (It is also prohibited to use a forced set/reset instruction in debug mode.)

CAUTION
You are not allowed to apply index modification to a special relay (M) in an attempt to specify them as the destination of data output. If you do so, an instruction processing error will result.

CAUTION
In a ladder instruction for continuous data transfer or table-format data output (see examples below), you are not allowed to specify a special relay as the output estination. If you do so, an instruction processing error will result. - Instructions for continuous data transfer: Block Move Instruction (BMOV Instruction), BSET, String Move Instruction (SMOV), etc. - Read User Log instruction (ULOGR), FIFO Write Instruction (FIFWR instruction), etc.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-20

4.4.2

Utility Relays
Utility relays are used to provide timing in a program or give instructions to the sequence CPU module.
Table 4.6 Utility Relays (1 of 2)
Item No. M033 M034 M035 M036* M037* M038* M039* M040* M041* M042* M047* M048* Name Always ON Always OFF Turns on for one scan at the start of operation. 0.01-sec clock 0.02-sec clock 0.1-sec clock 0.2-sec clock 1-sec clock 2-sec clock 1-min clock 1-msec clock 2-msec clock Utility Relays Function Description Used for an initialization process or as a dummy contact in a program. Turns on for one scan only after the start of a program Generates a clock pulse with a 0.01-sec period. Generates a clock pulse with a 0.02-sec period. Generates a clock pulse with a 0.1-sec period. Generates a clock pulse with a 0.2-sec period. Generates a clock pulse with a 0.2-sec period. Generates a clock pulse with a 2sec period. Generates a clock pulse with a 1msec period. Generates a clock pulse with a 1msec period. Generates a clock pulse with a 2msec period.

ON OFF ON OFF
1 scan 0.005 s 0.01 s 0.005 s 0.01 s

0.05 s 0.1 s 0.5 s 1s 30 s 0.5 ms 1 ms

0.05 s 0.1 s 0.5 s 1s 30 s 0.5 ms 1 ms

*: The rising and falling clock timings are synchronized among M036 to M048. Updates are done at the end of a scan.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-21
Table 4.6 Utility Relays (2 of 2)
Item No. M049 M050 M051 M052 M053 M054 M055 M056 M057 M058 M059 M060 M061 M062 M063 M064 M066 M067 Name 0 key-in from hand-held programming console 1 key-in from hand-held programming console 2 key-in from hand-held programming console 3 key-in from hand-held programming console 4 key-in from hand-held programming console 5 key-in from hand-held programming console 6 key-in from hand-held programming console 7 key-in from hand-held programming console 8 key-in from hand-held programming console 9 key-in from hand-held programming console A key-in from hand-held programming console B key-in from hand-held programming console C key-in from hand-held programming console D key-in from hand-held programming console E key-in from hand-held programming console F key-in from hand-held programming console Normal subunit transmission line On for one scan at CB startup Utility Relays Function Description

Turns on for one scan only at key-in from the hand-held programming console.

ON: Normal transmission line OFF: Unspecified or abnormal transmission line ON: When the block starts Turns on for one scan when OFF: In all other cases the sensor control block starts (at the first execution of the sensor control block).

SEE ALSO
See "Fiber-optic FA-bus Module F3LP02-0N Fiber-optic FA-bus Type 2 Module F3LP12-0N" (IM34M6H45-01E) for more information on the M066 utility relay (Normal Subunit Transmission Line).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-22

4.4.3

Sequence Operation and Mode Status Relays


Sequence operation and mode status relays indicate the status of sequence operation or each mode.
Table 4.7 Sequence Operation and Mode Status Relays
Item No. M129 M130 M131 M132 M133 M135 M136 M137 M172 (write-enabled) M173 M174 M175 M176 M177 to M187 M188 M189 to M192 Sequence Operation and Mode Status Relays Function Description Indicates the status of the ON: Run mode Run mode flag sequence CPU module OFF Other modes operation. Indicates the status of the ON: Debug mode Debug mode flag sequence CPU module OFF: Other modes operation. Indicates the status of the ON: Stop mode Stop mode flag sequence CPU module OFF: Other modes operation. Indicates the status of program ON: Pause Pause flag execution during debug mode OFF: Program execution operation. Execution flag Indicates whether specified ON: Specified blocks (All blocks/specified blocks or all blocks are OFF: All blocks blocks) executed. ROM/RAM-based ON: ROM-based operation Indicates whether operation is operation flag OFF: RAM-based operation based on the ROM or RAM. ON: Power-on operation Indicates whether the system Power-on operation OFF: Other modes of has been put in run mode at flag operation power-on or by resetting. ON: Start Indicates the status of sensor CB execution status OFF: Stop control block execution. ON: Time being set Time setting Requests to set clock data. OFF: ON: Offline Indicates that input refreshing Input-off line flag OFF: Online has stopped. ON: Offline Indicates that shared refreshing Output-off line flag OFF: Online has stopped. Shared-I/O off line ON: Offline Indicates that shared refreshing flag OFF: Online has stopped. ON: Offline Indicates that link refreshing has Link-I/O-off line flage OFF: Online stopped. Devices reserved for extended functions ON: Carry-enabled A carry flag used for shift or Carry flag OFF: Carry-disabled rotation operation. Devices reserved for extended functions Name

SEE ALSO
Specifications of Z49 to Z54 special registers for clock data for more information on time setting.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-23

4.4.4

Self-diagnosis Status Relays


Self-diagnosis status relays indicate the results of self-diagnostics by the sequence CPU.
Table 4.8 Self-diagnosis Status Relays
Item No. M193 M194 M195 Name Self-diagnosis error Battery failure Momentary power failure
Communication failure between Sequence CPU modules

Self-diagnosis Status Relays Function Description Error information is stored in special registers ON: An error is found. Z17 to Z19 for updating the results of OFF: No error is found. self-diagnosis. ON: Abnormal. Indicates a failure in backup batteries. OFF: Normal. ON: A momentary power failure is found. Indicates that a momentary failure has OFF: No momentary occurred. power failure is found. ON: Abnormal. OFF: Normal. ON: Exists. OFF: Does not exist. ON: Exists. OFF: Does not exist. ON: Exists. OFF: Does not exist. ON: Exists. OFF: Does not exist. ON: An error is found. OFF: No error is found. ON: Abnormal. OFF: Normal. ON: Abnormal. OFF: Normal. ON: Abnormal. OFF: Normal. ON: Abnormal transmission line. OFF: Unspecified or normal transmission line. ON: Abnormal transmission line. OFF: Unspecified or normal transmission line. ON: Abnormal. OFF: Normal. ON: Executes the program. OFF: Stops the program. ON: Executes the program. OFF: Stops the program. ON: Executes the program. OFF: Stops the program. ON: Executes the program. OFF: Stops the program. Indicates that a communication failure has occurred in shared relays/registers. Indicates whether or not a CPU module exists in slot 1. Indicates whether or not a CPU module exists in slot 2. Indicates whether or not a CPU module exists in slot 3. Indicates whether or not a CPU module exists in slot 4. Information on an error that may occur during instruction processing is stored in special registers Z22 to Z24. Indicates that the state of module installation is not consistent with the program. Indicates that no access is possible to I/O modules. The slot number of the module in question is stored in special registers Z33 to Z40. Indicates that the scan has exceeded the scan time monitoring time.

M196 M197 M198 M199 M200 M201 M202 M203 M204 M210

Existence of CPU1 Existence of CPU2 Existence of CPU3 Existence of CPU4 Instruction processing error I/O collation error I/O module failure Scan time-out Failure in subunit transmission line Switchover in subunit transmission line CB scan timeout CPU-1 sequence program execution CPU-2 sequence program execution CPU-3 sequence program execution CPU-14 sequence program execution

The slot number of the fiber-optic FA-bus module in question is stored in special registers Z89 to Z96 if a failure occurs in the module.

M211 M212 M225 M226 M227 M228

Indicates that it is not possible to maintain the execution interval of the sensor control block. Indicates whether the sequence program for the sequence CPU module in slot 1 is running or not running. Indicates whether the sequence program for the sequence CPU module in slot 2 is running or not running. Indicates whether the sequence program for the sequence CPU module in slot 3 is running or not running. Indicates whether the sequence program for the sequence CPU module in slot 4 is running or not running.

SEE ALSO
Fiber-optic FA-bus Module and Fiber-optic FA-bus Type 2 Module (IM34M6H45-01E) for more information on the M210 (Failure in Subunit Transmission Line) and M211 (Changeover in Subunit Transmission Line) self-diagnosis relays.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-24

4.4.5

FA Link Module Status Relays


FA Link module status relays indicate the status of FA link
Table 4.9 FA Link Module Status Relays
Item No. M257 to M480 M8321 to M8992 Name FA link failure FA Link Module Status Relay Function Description ON: Abnormal. Indicate the status of FA link OFF: Normal.

SEE ALSO
Special relays/registers sections of FA Link H Module F3LP02-0N Fiber-optic FA Link H Module (IM34M5H43-01E) F3LP12-0N for more information on these FA link module status relays.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-25

4.5

Timers (T)
There are five types of timer (T): 100-s, 1-ms, 10-ms and 100-ms timers and a 100-ms continuous timer. For each type of timer (T), you can assign the number of timers using the configuration function. However, you are not allowed to assign more than 16 points of 100-s timers.

CAUTION
Do not use a timer instruction in the sensor control block or an interrupt program. The timer used will not operate correctly.

4.5.1

100-s, 1-ms, 10-ms, and 100-ms Timers


100-s, 1-ms, 10-ms, and 100-ms timers are synchronized-scan, decremental timers (T) which update their current values and turn on/off their time-out relays using an END process. Setpoints: 100-s timer 1-ms timer 10-ms timer 100-ms timer 0.0001 to 3.2767 s 0.001 to 32.767 s 0.01 to 327.67 s 0.1 to 3276.7 s

Each timer starts counting at the rising edge of the timer input, and expires when the current value reaches 0. When the timer (T) expires, its time-out relay turns on. The time-out relay is used for a contact a or b. The timer (T) is reset at the falling edge of the timer input and the current value returns to the timers setpoint.
Timer input X00502 X00501 I0001 X00301 T001 I0002

TIM

T001

1s Y00601 Y00603

Timer input X00502

ON OFF Setpoint

Current value T001

0 ON OFF 1s
F040501.EPS

Time-out relay T001

Figure 4.18 Timer (T)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-26
TIP
The preset value of a timer refers to the duration from the time the timer starts running (starting time) until the timer stops. The preset value can be specified using the Timer instruction.

TIP
When a timer is running, its current value decrements as time passes. The current value is set to the preset value when the timer starts running, and becomes 0 when the timer timeouts.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-27

4.5.2

100-ms Continuous Timer


A 100-ms continuous timer is a synchronized-scan, decremental timer which updates its (T) current value and turns on/off its time-out relay using a scan end process. Setpoint: 0.1 to 3276.7 s

The 100-ms continuous timer retains its current value and the state of its time-out relay even when the timer input is set to OFF. When the timer input is set to ON again, the timer starts counting from the value it retains. When the timer input is set to OFF after the continuous timer expires, the timer (T) is reset, the current value returns to the setpoint, and the time-out relay is set to OFF. If you want to reset the continuous timer before it expires, write 0 to the time using a MOV instruction (MOV 0 Tnnn) when the timer input is in an OFF state.
Timer input X00502 X00501 I0001 X00301 T241 I0002

TIM

T241

10s Y00601 Y00603

Timer input X00502

ON OFF Setpoint

Current value T241

0 ON OFF
1 1 2

Time-out relay T241

=10 s
F040502.EPS

Figure 4.19 100-ms Continuous Timers

With the configuration function, you can configure a range of timers to determine whether or not they retain their current values when the power is turned off. By default, all timers are set so as not to retain their current values. If you set the timers to this option, their current values are reset to their setpoints when you: - turn off the power and turn it on again; - change the operation mode to Run or Debug with the WideField2; or - send a Clear Device command from WideField2. If you set the timers so as to retain their current values, the latest results are retained after power-off. In this case, the timers are reset to their setpoints when you send a Clear Device command from the programming tool. - send a Clear Device command from WideField2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-28

4.5.3

Selecting Timers
Select the range of 100-s, 1-ms, 10-ms, and 100-ms timers and 100-ms continuous timers to be used. To select the range, specify the number of timers you will use for each timer (T). The magnitudes of starting numbers assigned to these timers (T) are in the following relationship, as classified by the timer type. 100-s timer < 1-ms timer < 10-ms timer < 100-ms timer < 100-ms continuous timer Allocate 100-s, 1-ms, 10-ms and 100-ms timers and 100-ms continuous timers to the sequence CPU, in that order.
Table 4.11 Configuration of Timers
Item Configurat ion of Timer (T) and Counter 100-s timer 1-ms timer 10-ms timer 100-ms timer 100-ms continuous timer Default 0 0 512 448 64 F3SP28 F3SP53 Configuration Range 2048 on 1 point basis for timers and counters combined; 16 max. for 100-s timers; Timer numbers are continuous. Default 0 0 1024 896 128 F3SP38 F3SP58 F3SP59 Configuration Range 3072 on 1 point basis for timers and counters combined; 16 max. for 100-s timers; Timer numbers are continuous.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-29

4.6

Counters (C)
This section describes the function and operation of counters, as well as selection of counters in the configuration. The counters are decremental counters (C) and have two types of input: count input and reset input. A counter detects the rising edge of a count input and updates the current value when a counter instruction is executed. The counter terminates when its current value reaches 0. When the counter (C) terminates, its end-of-count relay turns on. The count-up relay is used for a contact a or b. The counter (C) is reset at the rising edge of the reset input and the current value returns to the counters setpoint. Count input is not accepted when the reset input is on.
Count input X00502 X00501 Reset input C001 X00504 Y00602

CNT

C001

100

Reset input X00502 Count input X00502

ON OFF ON OFF T241 99 98 1

100 Current value C001

Count-up relay C001

ON OFF
F040601.EPS

Setpoint: 1 to 32767
Figure 4.20 Counter (C)

With the configuration function, you can configure a range of counters to determine whether or not they retain their current values when the power is turned off. By default, all counters are set so as to retain their current values. If you set the counters otherwise, their current values are reset to their setpoints when you: - turn off the power and turn it on again; - change the operation mode to Run or Debug with the WideField2; or - send a Clear Device command from WideField2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-30
If you set the counters so as to retain their current values, the latest results are retained after power-off. In this case, the counters are reset to their setpoints when you send a Clear Device command from the programming tool. - send a Clear Device command from WideField2

TIP
A counter preset value refers to the value of the counter when it starts counting. The counter value can be set using a Counter (CNT) instruction.

TIP
When a counter is running, its current value decrements until it reaches 0.

4.6.1

Selecting Counters
Select the range of counters (C) to be used.
Table 4.12 Configuration of Counters
F3SP28 F3SP53 Default Timer (T) Device size T0001 to T1024
C0001 to C1024

Item

Counter (C)

Configuration Range Sum of timers and counters: 2048 points max., on 1 point basis Timer numbers: T0001 to T2048 Counter numbers: C0001 to C2048

Default T0001 to T2048


C0001 to C1024

F3SP38 F3SP58 F3SP59 Configuration Range Sum of timers and counters: 3072 points max., on 1 point basis Timer numbers: T0001 to T3072 Counter numbers: C0001 to C3072

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-31

4.7

Data Register (D), Shared Register (R) and Extended Shared Register (R)
This section describes data registers (D), shared registers (R), extended shared register (R), and how to set the initial data. Data registers (D) are 16-bit variables that can be used without restrictions in a program. Shared registers (R) are 16-bit variables that can be used for communications between CPUs in a multi-CPU system.

4.7.1

Data Registers (D)


Data registers serve as memory for storing the results of program-based computation. Each data register has 16 bits. In programs, you can read from or write to data registers in word unit or long word unit using application instructions. When you use link registers on a string of words basis, the lower-order 16 bits are stored in the data register with the number specified in the instruction and the higherorder 16 bits are stored in the data register with that number incremented by 1.
X00502 MOV X00501 X00503 X00501 X00502 X00504 MOV T001 X00503 D0001 D0002 D0003 $100 $5678 $1234
F040701.VSD

$100 $1234 $5678

D0001 Y00601

D0002 Y00602

Figure 4.21 Data Registers (D)

With the configuration function, you can configure a range of data registers to determine whether or not they retain computation results when the power is turned off. By default, all data registers are set so as to retain the results. If you set the registers otherwise, they are set to OFF (0) when you: - turn off the power and turn it on again; - change the operation mode to Run or Debug with the WideField2; or - send a Clear Device command from the Widefield2. If you set the registers so as to retain the computation results, the latest results are retained after power-off. In this case, the registers are set to OFF (0) when you send a Clear Device command from the programming tool. - send a Clear Device command from the Widefield2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-32

4.7.2

Shared Registers (R) and Extended Shared Registers (R)


Shared and extended shared registers are used to exchange data between CPUs in multi-CPU system configuration. The shared registers (R) can be used regardless of how CPUs are combined. The extended shared registers (R) can only be used with the sequence CPU modules (F3SP25, F3SP28, F3SP35, F3SP38, F3SP53, F3SP58 and F3SP59). In programs, you can read from or write to data registers in word unit and a long word string basis using Application Instructions. When you use a long word string, the lower-order 16 bits are stored in the data register with the number specified in the instruction and the higher-order 16 bits are stored in the data register with that number incremented by 1. Data can be exchanged between the local CPU module and a remote CPU module by writing the data to shared registers in the local CPU module and reading it from the remote CPU module. If you write data to a device area other than that of the local CPU module, information held by shared registers (R) of the remote CPU module is overwritten. This results in a failure for these shared registers to reflect the correct results of computation. By default, no shared registers are assigned as devices. When using add-on sequence CPUs, set the range of shared registers to be used. Assign the same range for all of the CPUs. Otherwise, the shared registers (R) are not correctly refreshed. SEE ALSO
Shared and extended shared registers (R) are used to exchange data (data sharing) between CPUs in multi-CPU system configuration where sequence CPU module BASIC CPU module are installed. For more information on the functions of BASIC CPU modules, refer to: BASIC CPU Modules and YMBASIC/FA Programming Language Instruction manual (IM34M6Q22-01E).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-33
Figure 4.22 shows an example of how specific shared registers are shared if you allocate shared registers R0001 to R0256 for CPU 1 and shared registers R0257 to R0512 for CPU 2.
CPU1 X00502 MOV X00501 X00502 $100 R0001 Y00601

CPU2 X00503 X00501 X00504 MOV T001 X00503


F040702.VSD

R0001

D0001 Y00702

Figure 4.22 Shared Register (R)

With the configuration function, you can configure a range of shared registers to determine whether or not they retain computation results when the power is turned off. By default, all shared registers are set so as not to retain the results. If you set the registers otherwise, they are cleared when you: - turn off the power and turn it on again; - change the operation mode to Run or Debug with the WideField2; or - send a Clear Device command from WideField2. If you set the registers so as to retain the computation results, the latest results are retained after power-off. In this case, the registers are cleared when you send a Clear Device command from the programming tool. - send a Clear Device command from WideField2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-34
CAUTION
When using shared or extended shared registers (R), follow the precautions given below. (1) Index modification of shared or extended shared registers (R) - When applying index modification to shared or extended shared registers (R) of the local sequence CPU module, be careful that any register number, which is directly specified in an instruction and to which the content of an index register has been added, does not exceed the range specified by configuration for the local CPU. Otherwise, information held by shared or extended shared registers (R) of remote CPU modules is overwritten. This results in a failure for these shared registers (R) to reflect the correct results of computation.
X00501 MOV X00501 T001 I0003 V1 R0001 B0001 Y00602

Make sure the register number does not exceed the range set for the local CPU

F040703.VSD

Figure 4.23

Precautions when Using Shared or Extended Shared Registers (R) (1 of 2)

(2) Block move and computation of multiple devices - When using shared or extended shared registers (R) in an instruction for transferring or computing data held by multiple devices, be careful that the range of registers, which is defined by the register number directly specified in the instruction and the number of registers included in the transfer and computation, does not exceed the range specified by configuration for the local CPU. Otherwise, information held by shared or extended shared registers (R) of remote CPUs is overwritten. This results in a failure for these shared registers (R) to reflect the correct results of computation.
X00501 X00504 BMOV R0001 D0001 D0100

X00501

X00504 BMOV R0001 D0001 10


F040704.VSD

Make sure the range does not exceed the range set for the local CPU.

Figure 4.24 Precautions when Using Shared or Extended Shared Registers (R) (2 of 2)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-35
(3) Simultaneity of data - With the configuration function, you can select either Yes or No for the simultaneity of data of shared devices. If you select the Yes option, the simultaneity of the data is guaranteed in units of devices (shared relays/registers or extended shared relays/registers) to be refreshed when one of the F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 sequence CPUs is combined with add-on sequence CPUs. (The simultaneity of data held by the shared relays/registers or extended shared relays/registers is not guaranteed, however.) If any of the F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 CPUs is combined with any of the F3SP21, F3SP25, F3SP35 and F3BP CPUs, the simultaneity of the data is not guaranteed irrespective of the configuration settings. The No option of this configuration item is designed for the interchangeability of the F3SP21, F3SP25 and F3SP35 CPUs. Select this option when replacing these CPUs with the F3SP28, F3SP38, F3SP53, F3SP58 or F3SP59 CPUs.

SEE ALSO
For details on index modification, see Section 1.8 in Sequence CPU Instruction Manual Instructions (IM34M6P12-03E).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-36
I Configuring Shared and Extended Shared Registers (R) for Multiple CPUs
Set the range of shared and extended shared registers (R) to be used by each CPU in multi-CPU system configuration where add-on CPU modules are installed. You can allocate a desired number of registers to each CPU in 2 unit increments.
Table 4.13 Configuration of Shared Registers (R)
Item Default
Device size

Shared register (R) Extended shared register (R)

0 0

F3SP28/F3SP53 F3SP38/F3SP58/F3SP59 Configuration Range 1024 points max. on 2 points basis for all CPUs combined 3072 points max. on 2 points basis for all CPUs combined

The extended shared registers can only be used with the sequence CPU modules (F3SP25, F3SP28, F3SP35, F3SP38, F3SP53, F3SP58 and F3SP59).

CAUTION
Assign the same range of shared/ extended shared registers (R) for all CPU modules. No error will result, however, even if the range is not the same among the CPU modules. Rather, data in a remote CPU module may appear wrongly assigned to register numbers or data in the local CPU module may appear that way when referenced from the remote CPU.

- Shared registers
R0001 R0129 512 points 512 points 512 points CPU-2 shared registers CPU-3 shared registers CPU-4 shared registers CPU 1 128 points CPU 2 128 points CPU 4 128 points CPU-1 shared registers

R0641 256 points R0897 128 points 128 points 128 points 256 points 256 points

- Extended shared registers


R1025 R2561 512 points 512 points 512 points CPU 1 1536 points CPU 2 1536 points CPU 4 1536 points CPU-1 extended shared registers CPU-2 extended shared registers CPU-3 extended shared registers CPU-4 extended shared registers
F040705.EPS

R2945 768 points R3713 384 points 384 points 384 points 768 points 768 points

Figure 4.25 Example of Allocating Shared/Extended Shared Registers (R) when Four Sequence CPU Modules are Installed

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-37
CAUTION
Even if the specified range includes less than 1024 shared registers (R), the extended shared registers (R) always begin with the number R1025.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-38

4.7.3

Setting Initial Data for Data Registers (D)


Using the configuration function, set the initial values of data registers (D) to be used at the start of program execution. The data items to be configured are the data registers starting number and their quantity and initial data values. After this configuration, the preset initial data values are stored in the specified data registers when the program starts. This configuration is useful when a large volume of initial data needs to be set by a program or when the initial data needs to be saved. You can set initial data in a maximum of 1024 data registers.
The initial data is transferred at the start of program execution. Starting number =1 Quantity = 1024 D0001

D1024

D4096

F040706.EPS

Figure 4.26 Setting Initial Data for Data Registers (D)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-39

4.8
4.8.1

Special Registers (Z)


Special registers have specific functions, such as indicating the internal state of a programmable controller or detecting errors.

Sequence Operation Status Registers


Sequence operation status registers indicate the status of sequence operation.
Table 4.14 Sequence Operation Status Registers
Type No. Z001 Z002 Z003 Z004 Z005 Z006 Name Scan time (Run mode) Minimum scan time (Run mode) Maximum scan time (Run mode) Scan time (Debug mode) Minimum scan time (Debug mode) Maximum scan time (Debug mode) Peripheral-process scan time Sequence Operation Status Registers Stored Data Description Stores the latest scan time in 100-s Latest scan time increments. Allows the latest scan time to be read in Minimum scan time 100-s increments if it is shorter than the minimum scan time. Allows the latest scan time to be read in Maximum scan time 100-s increments if it is longer than the maximum scan time. Stores the latest scan time in 100-s Latest scan time increments. Allows the latest scan time to be read in Minimum scan time 100-s increments if it is shorter than the minimum scan time. Allows the latest scan time to be read in Maximum scan time 100-s increments if it is longer than the maximum scan time. Stores the latest scan time in100-s increments. Latest scan time (Tolerance: Scan time of one control process) Allows the latest scan time to be read in 100-s increments if it is shorter than the Minimum scan time minimum scan time. (Tolerance: Scan time of one control process) Allows the latest scan time to be read in 100-s increments if it is longer than the Maximum scan time maximum scan time. (Tolerance: Scan time of one control process)

Z007

Z008

Minimum peripheralprocess scan time

Z009

Maximum peripheralprocess scan time

CAUTION
Do not write to a special register (Z), including those not listed in the table above (e.g., Z010 to Z016), unless otherwise stated. This is because they are used by the CPU module for the system. If you inadvertently write to these registers, a failure, such as a system shutdown, may result. You are not allowed to apply index modification to special registers (Z) in an attempt to specify them as the destination of data output. If you do so, an instruction processing error will result. In a ladder instruction for continuous data transfer or table-format data output (see examples below), you are not allowed to specify a special register (Z) as the output destination. If you do so, an instruction processing error will result. - Instructions for continuous data transfer: Block Move Instruction (BMOV Instruction), Block Set Instruction (BSET Instruction), String Move Instruction (SMOV Instruction), etc. - Instructions for table-format data output: User Log Read Instruction (ULOGR Instruction), FIFO Write Instruction (FIFWR Instruction), etc.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-40

4.8.2

Self-diagnosis Status Registers


Self-diagnosis status registers indicate the results of self-diagnostics by the sequence CPU.
Table 4.15 Self-diagnosis Status Registers
Type No. Z017 Z018 Z019 Z022 Z023 Z024 Z027 Z028 Z029 I/O collation error Instruction processing Self-diagnosis error Name Self-diagnosis Status Registers Stored Date Self-diagnosis error number Self-diagnosis error block number Self-diagnosis error instruction number Instruction processing error number Instruction processing error block number Instruction processing error instruction number I/O collation error number Instruction processing error block number Instruction processing error instruction number Store, as a bit pattern, the slot number for which an I/O failure has occurred. Z033: Main unit Z034: Subunit 1 Z035: Subunit 2 Z036: Subunit 3 Z037: Subunit 4 Z038: Subunit 5 Z039: Subunit 6 Z040: Subunit 7 Descriptions Store the results of self-diagnosis.*

Store errors occurring during instruction processing.*

Store detailed information on I/O collation errors.*

Z033 to Z040

I/O failure

I/O failure 16 2 1 0 ..... 1 0

Z041 Z042 Z043 Z044 Z045 Z046 Z047 Z048 Z089 Z090 Z091 Z092 Z093 Z094 Z095 Z096 Abnormal slot in subunit transmission line Module recognition

Main unit Subunit 1 Subunit 2 Subunit 3 Subunit 4 Subunit 5 Subunit 6 Subunit 7 Main unit Subunit 1 Subunit 2 Subunit 3 Subunit 4 Subunit 5 Subunit 6 Subunit 7

Slot number 16 2 1 0 ..... 1 0 0: No modules are recognized. - Unable to read/write. 1: Modules are recognized.

Slot number 16 2 1 0 ..... 1 0 Fiber-optic FA-bus module 0: Normal transmission line; Unspecified transmission line; or Loaded with a wrong module 1: Abnormal transmission line (Failure or changeover in transmission line)

* For information on error numbers (codes) to be saved in these special registers, see Table 8.2, Details of Self-diagnosis.

SEE ALSO

Fiber-optic FA-bus Module, Fiber-optic FA-bus Type 2 Module (IM34M6H45-01E), for more information on the Z089 to Z096 special registers (Abnormal Slot in Subunit Transmission Line).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-41

4.8.3

Utility Registers
Table 4.16 Utility Registers
Type No. Z049 (write-enabled) Z050 (write-enabled) Z051 (write-enabled) Z052 (write-enabled) Z053 (write-enabled) Z054 (write-enabled) Z055 Z056 Z057 Z058 Constant scan time Constant scan time Scan time monitoring time Clock data Name Utility Registers Stored Data Description Lower-order two digits Stores "year" as a BCD-coded value. of calendar year Example: 1999 as $0099 2000 as $0000 Stores "month" as a BCD-coded Month value. Example: January as $0001 Stores "day of month" as a Day BCD-coded value. Example: 28th as $0028 Stores "hour" as a BCD-coded value. Hour Example: 10 o'clock as $0010 Stores "minute" as a BCD-coded Minute value. Example: 15 minutes as $0015 Stores "second" as a BCD-coded Second value. Example: 30 seconds as $0030 Stores "day of week" as a Day of week BCD-coded value. ($0 to $6) Example: Wednesday as $0003 Value of constant scan 0.1 ms increments time Example: 10 ms = 100 Value of constant scan 1 ms increments time Example: 10 ms = 10 Value of scan time 1 ms increments Example: 200 ms = 200

- For CPU module F3SP - S, you can set clock data using the Set Date instruction (DATE), Set Time instruction (DATE), Set Date String instruction (SDATE), and Set Time String instruction (STIME). - For CPU module F3SP - N/- H, use the following procedure to set time data. (1) Write the clock data to special registers Z049 to Z054 (use a MOV P instruction). (2) Set special relay M172 to ON within the same scan as that in step 1 (use a DIFU instruction, for example). (3) Set special relay M172 to OFF in the scan subsequent to that in step 2. Also stop writing the clock data to special registers Z049 to Z054 in that scan. Note that no change is made to the clock data and the data reverts to its original values if the values being set are incorrect. - The accuracy of clock data is as follows. Maximum monthly error: 8 s (2 s, when actually measured) The clock accuracy is reset to the maximum daily error of -1.2 s/+2 s, however, when the power is turned off and on again. In addition, it is possible to input a corrective value from the programming tool. If you input a precise corrective value, the clock data is corrected during the power-off-and-on sequence, thus offsetting the cumulative amount of error.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-42

4.8.4

FA Link Module Status Registers


FA Link module status registers indicate the status of FA link.
Table 4.17 FA Link Module Status Registers
Type No. Z065 Z066 Z070 Z071 Z257 Z258 Z262 Z263 Z267 Z268 Z272 Z273 Z277 Z278 Z282 Z283 Name FA Link Module Status Registers Stored Data Description

Local station status Cyclic transmission time Local station status Cyclic transmission time Local station status Cyclic transmission time Local station status Cyclic transmission time Local station status Cyclic transmission time Local station status Cyclic transmission time Local station status Cyclic transmission time Local station status Cyclic transmission time

0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online

FA link 1 FA link 1 1ms increments FA link 2 FA link 2 1ms increments FA link 3 FA link 3 1ms increments FA link 4 FA link 4 1ms increments FA link 5 FA link 5 1ms increments FA link 6 FA link 6 1ms increments FA link 7 FA link 7 1ms increments FA link 8 FA link 8 1ms increments

SEE ALSO
For more details on the FA link module status registers (Z), see the Special relays (M)/registers (Z) sections in the instruction manual (IM34M5H43-01E), FA Link H Module, Fiber-optic FA Link H Module.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-43

4.8.5

Sequence CPU Module Status Registers


CPU module status registers indicate the status of a CPU.
Table 4.18 Sequence CPU Module Status Registers
Type No. Z105 Name Number of stored user logs Refers to the length of time from when input refreshing is started for the sensor control block to when the program is executed and output refreshing is completed. (Unit: 10 s) Refers to the maximum time taken to execute the sensor control block. (Unit: 10 s) Module name and firmware revision number. CPU Module Status Registers Contents Description See Section 6.14, "User Log Management Function," for information on user logs.

Z109

CB execution time

Z111

Maximum CB execution time

Z121~Z128 Module details (*)

*:For example, the values for moduleF3SP58-6S, firmware Rev1 are as follows. Z121 F3 Z122 SP Z123 58 Z124 6S Z125 /R Z126 01 Z127 / Z128

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-44

4.9

Index Registers (V)


Index registers are used to apply index modification to devices. You can use these registers for both basic instructions and Application Instructions to make index modifications. Use these registers when specifying a device number by adding the content of an index register to a device whose number is directly specified in an instruction.

SEE ALSO
Section 1.8.1, Index Modification, in the 3rd or later edition of the instruction manual (IM34M6P12-03E), Sequence CPU - Instructions, for more information on index registers.
X00502 MOV I0001 V01 X00502 X00504 MOV X00501 T001 X00503 I(0001+100)=I0101 D(0001+100)=D0101
F040901.VSD

100

V01 Y00601

X00503

V01 D0001

V02 D0100 Y00602

Figure 4.27 Index Registers

CAUTION
Examination of whether or not the device number specified using an index register exceeds the given configuration range, is not performed on the system side of the sequence CPU module. The configuration range may be exceeded depending on the content of the index register used, resulting in the selection of a wrong device. Be careful when specifying the device number.

CAUTION
You can set a value from -32768 to 32767 in index registers. For such devices as file registers (B) whose size is larger than 32768, however, it is not possible to specify any of them by index modification.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

4-45

4.10 File Registers (B)


File registers (B) are used as extensions of data registers (D). Each file register has 1 word point Like data registers (D), you can read from or write to file registers in a word basis or 32-bit basis using Application Instructions.
X00502 MOV MOV X00501 X00503 X00502 X00504 MOV B00002 = B00002 B00003 + D0003 1
F041001.VSD

B00001 1

D0001 B00002 Y00601

Figure 4.28 File Registers (B)

Unlike data registers (D), all file registers (B) retain computation results when the power is turned off. The file registers are cleared to OFF (0) when you write the data value OFF (0) to the file registers from the programming tool. Unlike data registers, the file registers are not cleared to OFF (0) even if you: - send a Clear Device command from WideField2; or - send a memory clearance command from the Widefield2.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

5-1

5.
5.1

Programs
This chapter describes languages used for programming, program types and program memory.

Programming Language
Two types of programming language are available: structured ladder language and mnemonic language. In either case, the written program is read sequentially by the sequence CPU to perform computations according to the programs process details.

5.1.1

Structured Ladder Language


The structured ladder language is based on relay symbol representation and allows the programmer to do structured programming by breaking a program into functional parts.
The programmer can perform programming on a function-by-function basis. Function 1 X00501 I0001 I0001 TIM I0001 T001 T010 10ms I0002 T001 I0001

Function n X00502 CNT X00501 C001 X00501 I0016 X00504 T001 X00503
F050101.VSD

C001

100

Y00602 Y00601

Figure 5.1 Structured Ladder Language

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

5-2

5.1.2

Mnemonic Language
The mnemonic language is designed to describe a program by breaking its process details into instruction, input parameter, and output parameter. Like the structuredladder language, the mnemonic language allows the programmer to perform programming on a function-by-function basis.
Instruct6ion section LD OUT LD AND MOV Instruction section I0001 Y00602 X00501 X00502 D0001 D0002 Output parameter section

Input parameter section

F050102.VSD

Figure 5.2 Mnemonic Language

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

5-3

5.2
5.2.1

Program Types and Configuration


There are two types of programs: blocks and executable programs.

Blocks and Executable Programs

I Blocks
A block refers to a set of circuits entered through the WideField2. Parts of each program written on a function-by-function basis using the structured ladder language or mnemonic language are managed as blocks. Since the program can be maintained or reused block by block, program development becomes extremely easy. A single block can contain steps up to 10 K. For CPU modules F3SP - N and F3SP - H, one block has a maximum step of 10K steps. For CPU module F3SP - S, one block has a maximum step of 56K steps. (Module F3SP28-3S has a maximum step of 30K steps.)

CAUTION
It is not possible for the CPU to execute a separate block.
Block 1
X00503 X00504

Circuit

Y00602

X00501

X00502 X00503

Y00601

Block n
I0001 X00501 X00502 Y00602 I0003

F050201.VSD

Figure 5.3 Blocks

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

5-4
I Executable Program
An executable program refers to a program with a format which can be executed by the CPU. The executable program is composed by combining multiple blocks created with the Widefield2. Each executable program can contain a maximum of 1024 blocks. Since you can execute only specific blocks of an executable program, it becomes easy for you to control and manage your programs.
Block 1
X00503 X00501 X00504 X00502 X00503

Circuit
Y00602 Y00601

Executable program Block 1 Block 2

Block 16
I0001 X00501 X00502 Y00602

Block 16
F050202.VSD

Figure 5.4 Example of an Executable Program

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

5-5

5.2.2

Programs Composing an Executable Program


An executable program contains a maximum of 1024 blocks. The sensor control block is regarded as a single, separate block. Programs that compose an executable program are classified into main routine programs, subroutine programs, interrupt programs and sensor control block programs, according to their functions.
Main routine program

Block 1 Subroutine program

Main routine program Block 2

Subroutine program Executable program

Main routine program

Block n Subroutine program

Interrupt program Sensor control block program Sensor control block


F050203.VSD

Figure 5.5 Programs Composing an Executable Program

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

5-6
I Main Routine Programs
A main routine program is always executed in each scan. Since the main routine program is written in the structured ladder language, it is composed of multiple blocks. You can execute a main routine program by either executing all blocks of the program or executing only specific blocks.

Program execution Block 1 SUB This subroutine program is excluded from the execution.

RET

Block n-1

Block n

F050204.VSD

Figure 5.6 The Way a Main Routine Program Is Executed

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

5-7
I Subroutine Programs
A subroutine program is executed when a CALL instruction is given by a main routine program. Use this program when you want to run a specific process two or more times within one scan. A subroutine program can be placed in any location in a block. In a case where the operation mode in which only specific blocks are executed is selected, a subroutine program is executed even if it is located in a yet-to-be-executed block and called from a block being executed. Subroutine programs can be nested to a maximum depth of eight layers (nesting means to call a subroutine from within another subroutine).
Program execution CALL Block 1 Program execution

Block n-1

SUB

Block n RET Subroutine program

F050205.VSD

Figure 5.7 The Way a Subroutine Program Is Executed

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

5-8
I Interrupt Programs
An interrupt program is executed when any cause of interrupt occurs. A maximum of four interrupt programs can be included in a block. The relationship between a cause of interrupt and an interrupt program is described as a parameter of the Interrupt (INTP) Instruction.
INTP X00301
F050206.VSD

Figure 5.8 INTP Instruction

Program execution

Program execution

Block 1

Interrupt processing

Block n-1

INTP

Block n IRET Interrupt program

F050207.VSD

Figure 5.9 The Way an Interrupt Program Is Executed

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

5-9
I Sensor Control Block
The sensor control block (CB) is a bock that is executed separately from those for a normal scan, both at high speeds and at fixed intervals.

CBACT

Block 1

Fixed-interval timing

Block n-1

Block n

F050208.VSD

Figure 5.10 The Way the Sensor Control Block Is Executed

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

5-10

5.3

Program Memory
Program memory contains programs as well as information required for their operation and management. This section describes the configuration of the program memory and its initial condition when there are no programs in it.
Table 5.1 Configuration of Program Memory and Its Initial Condition

Memory Component Program management table Program Configuration table*

I/O configuration table*

Program control instructions table Timer/counter settings table Utility

Description An area for storing information required to manage the entire range of programs, such as program names, the number of steps, and information on block management. An area for storing programs. An area for storing configuration information, such as device sizes and operation methods. An area for storing configuration information such as output settings, in case the sequence stops and for I/O module settings. An area for storing the information required to control the execution of program instructions, such as a JMP instruction and a subroutine instruction. An area for storing timer and counter setpoints. An area for storing such information as circuit comments and sub-comments.

Initial Condition Stays in the default state of program management, where the program name is "PROGRAM," block name is "PROGRAM," and the number of steps is "0". Contains a NOP instruction. Contains the defaults discussed in subsection 1.2.3, "Configuration." Contains the defaults discussed in subsection 1.2.3, "Configuration." Contains "0," indicating there are no such program control instructions as a JMP instruction or a subroutine instruction. Contains "0," indicating there are neither timers nor counters. Contains "0".

* See subsection 1.2.3, Configuration, for more information.

CAUTION
No programs can be executed when the program memory is in its initial condition.

Configuration of program memory Program management table Program Programs F3SP28: F3SP53: F3SP38/F3SP58: F3SP59:

30 K 56 K 120 K 254K

(30720) steps (57346) steps (122880) steps (260096) steps

Configuration table RAM I/O configuration table Program control instructions table Timer/counter settings table Utility

Range of devices Error-mode operation Range of devices latched at power failure Setting as to whether or not data is retained Setting of sampling interval Setting of data codes Jump Interrupt definition Subroutine Label

Circuit comments, sub-comments, registration tables, etc.


F050301.VSD

Figure 5.11 Configuration of Program Memory

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-1

6.
6.1

Functions
This chapter describes functions which can be executed by the sequence CPU module, such as the execution of specified blocks and debugging operation.

Function List
The following tables summarize the functions provided by the sequence CPU module and add-on CPU modules.
Table 6.1 Functions Provided by Sequence/Add-on Sequence CPUs
Function of Sequence CPU Module Function Overview Specifies the operation mode of the sequence CPU module and its actions. Executes a sequence program at certain time intervals. Specifies how an executable program is processed. Specified blocks are executed using ACT and INACT instructions. Supports debugging operations, such as forced set/reset. Protects programs by means of password. This function has two modes: executable program protection and block protection. Makes on-line modifications or changes to a program in the program memory of the sequence CPU module. Acquires and displays states of multiple devices for up to 1024 scans. Performs the same level of communication as that of a personal computer link module, when a personal computer or a monitor is connected to the programming tool connector. Allows the user to create and register new, customized instructions. Allows the user to keep a log, or record of, errors in the user's system, the way they occurred, the system's operating condition, and so on. Executes a single block separately from those for a normal scan, both at high speeds and at fixed intervals. Downloads only specified blocks/macros. Stores circuit comments and subcomments to a sequence CPU module. Stores tag name definitions to a sequence CPU module. Represents a group of data items under a unified name. Page 6-3 6-5 6-6 6-13 6-15 6-17 6-24 6-28 6-46 6-62 6-64 6-81 6-83 6-86 6-87

Operation setup function


Constant scan Execution all blocks/specified blocks Debugging function Program protection function Online edit function Sampling trace function Personal computer link function Macro instruction function User log management function Sensor control function Partial download function Function for storing comments to CPU Function for storing tag name Definitions to CPU Structures

Table 6.2 ROM Management (Writer) Function


ROM Management (Writer) Function File-to-ROM transfer function CPU-to-ROM transfer (ROM copy) function Compare file and ROM pack function ROM pack clearing function Function Overview Writes programs or data to the ROM pack Writes a program or data to the ROM pack Compares the contents in the ROM to the program in WideField2. Erases the ROM pack data. Page 6-22 6-22 6-22 6-22

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-2
Table 6.3 Device Management Functions
Device Management Function Device upload function Device download function Device edit function Device comparison function Function Overview Reads device information (data) from the sequence CPU module and saves it to a WideField2 file. Reads device information (data) from a WideField2 file and writes it to the sequence CPU module. Edits device information saved in a file in the WideField2. Compares device information saved in the sequence CPU module with that saved in a WideField2 file. Page 6-45 6-45 6-45 6-45

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-3

6.2

Operation Setup Function


The operation setup function sets up the sequence CPU module operation mode and initializes programs and devices. This function can be used by entering a command from the WideField2, personal computer link module, or an add-on CPU module.

I Run Mode
The CPU begins running a program from its first instruction, similar to when the power is turned on. When the power is turned on or the mode is changed from stop to run, the CPU sets all devices to 0, except for latching-type devices, before executing the program. When the CPU enters the Run mode, functions available only in the Debug or Stop mode are disabled.

I Debug Mode
The CPU begins running a program from its first instruction, similar to when the power is turned on. When the Stop mode is changed to the Debug mode, the CPU sets all devices to 0, except for latching-type devices, before executing the program. Be sure to disable the Debug mode and enter the Run mode when you have completed your debugging and tuning tasks.

I Stop Mode
The CPU stops running the program. External output data is retained (ON) or not retained (OFF), depending on the settings of the configuration item external output to be retained in case of sequence stop. This mode does not work when the CPU has already stopped running the program.

I Clear Memory

Stop

This function deletes a program or programs and sets all devices to 0. Stop running the program before using this function.

I Clear Devices

Stop

This function sets all latching-type devices, excluding file registers (B), to 0. Stop running the program before using this function. To clear file registers (B), use the device edit function of the device management function to set all the file register (B) data to 0 and write the data to the sequence CPU module using the device write function.

SEE ALSO
For details on the device management function, see Section 6.12, Device Management Function.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-4
CAUTION
The following are precautions you should follow when using the functions described in this chapter: - Some functions are not available in all the operation modes. - Note that the following marks are used when explaining each function, in order to indicate that the function in question is available in the cited mode or modes.
Run Debug Stop

Unless otherwise specified, the function can be used in any operation mode. The scan time may become longer for some functions. When you finish using such a function, be sure to disable it before running the system. Be especially careful when using any function that works in Debug mode. When your debugging and tuning tasks are complete, always disable the function and enter Run mode. Be sure to use the ROM writer functions when you operate the ROM pack. Note that the following mark is used when explaining each ROM writer function to indicate that the function is available in ROM Writer mode.
ROM writer

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-5

6.3

Constant Scan
END instruction END instruction END instruction

Run

Debug

The constant scan function executes a program repeatedly at certain time intervals. You can set the constant scan time, i.e., constant-scan time interval, to a value from 1 ms to 190 ms in 0.1 ms increments. To do this, use the configuration function.
0 step 0 step 0 step

3ms 10ms

5ms 10ms

2ms 10ms

F060301.VSD

Figure 6.1 Operation Based on 10-ms Constant Scan

If the scan time of a sequence program is longer than the preset constant scan time, any constant scan is ignored and the program is executed with its own scan time.
0 step END instruction 0 step END instruction END 0 step instruction 0 step

1ms 2ms

3ms 3ms Program's scan time

1ms 2ms
F060302.VSD

Figure 6.2 Operation Based on 2-ms Constant Scan

6.3.1

Setting the Constant Scan Time


Set the constant scan time using the configuration item operation control of the WideField2. You can set the constant scan time to a value from 1 ms and 190 ms in 0.1-ms increments. If you will not use the constant scan time, set the constant scan function to the option Not used (default).

CAUTION
The constant scan time must be shorter than the scan time monitoring time. If the constant scan time is longer than the scan time monitoring time, a scan timeout error occurs.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-6

6.4

Executing All Blocks/Specified Blocks


Run Debug

Select the method of program execution: executing all blocks or executing specified blocks. using the configuration item operation control of the WideField2.

6.4.1

Executing All Blocks


This method always executes all blocks of an executable program sequentially from block 1. The default of the program execution method is all blocks are executed.
All blocks are executed. Executable program Block 1 I0001 X00501 X00502 Y00602 I0003

Block n X00503 I0002 X00501 X00502 I0003 Y00603 I0004

F060401.VSD

Figure 6.3 Execution of All Blocks

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-7

6.4.2

Executing Specified Blocks


This method uses ACT/INACT instructions to control blocks of an executable program so that only the specified blocks are executed. This allows you to control blocks which are programmed for each function. Thus, you can easily know how the blocks are controlled. Enabled blocks are referred to as blocks in an ACTIVE state, while disabled blocks are called blocks in an INACTIVE state. Use an ACT instruction to set a block in an ACTIVE state and an INACT instruction to set the block in an INACTIVE state. Whether a block is in an ACTIVE or INACTIVE state is indicated by a special relay. Special relays M2001 to M3024 support blocks 1 to 1024 in indicating their states. (Note that special relays M0001 to M0032 contain the same values as special relays M2001 to M2032.) A special relay is set to 1 when the corresponding block is in an ACTIVE state, and 0 when the block is in an INACTIVE state. This means the two states can be handled in a program. ACTIVE-state blocks are executed in ascending order of their block numbers. By default, only block 1 is in an ACTIVE state.
Executable program Block 1 (Function 1) Block 2 (Function 2) ACTIVE -state special relay M2001=1 INACTIVE -state special relay M2002=2 Block m Block m (Function m) Block n (Function n) ACTIVE -state special relay M200m=1 INACTIVE -state special relay M200n=0 X00503 X00501 X00502 I0003 Y00603 I0004 Block 1 I0001 X00501 X00502 Y00602 I0003

F060402.VSD

Figure 6.4 Execution of Specified Blocks-Executing block 1 and block m only

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-8

6.4.3

Operation When Specified Blocks Are Enabled


Blocks that have been enabled with an ACT instruction are initialized at the end of the scan in which they were enabled. It is from the next scan that the blocks enabled with an ACT instruction actually start.
nth scan Executable program Block 1 Function 1 Block 2 Function 2 Block m Function m Block n Function n ACT Block 1 Function 1 Special relay M2001=1

ACT: Block 2 Next scan (n+1)th scan Block 1 Function 1 Next scan Block 2 Function 2 Special relay M2002=1 Special relay M2001=1

Executable program Block 1 Function 1 Block 2 Function 2 Block m Function m Block n Function n ACT

ACT: Block m Next scan (n+2)th scan Block 1 Function 1

Special relay M2001=1

Block 2 Function 2

Special relay M2002=1

Block m Function m

Special relay M200m=1

F060403.VSD

Figure 6.5 Operation When Specified Blocks are Enabled

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-9
Devices that are specified in the blocks enabled with an ACT instruction are placed in the following conditions by block initialization.
Table 6.4 Conditions when Blocks Are Enabled
Device Timer (T) Continuous timer Counter (C) Destination of OUT instruction All other devices Condition when Blocks Are Enabled Resets. Retains the value it held before the blocks are enabled. Retains the value it held before the blocks are enabled. Goes into an OFF state. Retain the states they held before the blocks are enabled.

Use a SET instruction for devices whose output values need to be retained when blocks are enabled.
This device is set to OFF. X00503 I0002 X00501 X00502 I0003 X00301 I0005 I0004 SET Y00601 Y00603 I0004

Use a SET instruction to retain the output value of this device.


F060404.VSD

Figure 6.6 Example of Devices Initialized When Blocks Are Enabled

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-10

6.4.4

Operation When Specified Blocks Are Disabled


Blocks that have been disabled with an INACT instruction are initialized at the end of the scan in which they were disabled. It is in the next scan that the blocks disabled with an INACT instruction actually stop.
nth scan Executable program Block 1 Function 1 Block 2 Function 2 Block m Function m Block n Function n INACT Block 1 Function 1 Special relay M2001=1

INACT: Block 2 Block 2 Function 2 Special relay M2002=1

Block m Function m

Special relay M200m=1

Initialization of block 2 Block 2 Function 2 Special relay M2002=0

Executable program Block 1 Function 1 Block 2 Function 2 Block m Function m Block n Function n Block 1 Function 1 Special relay M2001=1 INACT Next scan (n+1)th scan

INACT: Block m Block n Function n Special relay M200m=1

Initialization of block m Block m Function m Special relay M200m=0

Next scan (n+2)th scan Block 1 Function 1 Special relay M2001=1

F060405.VSD

Figure 6.7 Operation When Specified Blocks Are Disabled

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-11
Devices that are specified in the blocks disabled with an INACT instruction are placed in the following conditions by block initialization.
Table 6.5 Conditions when Blocks Are Disabled
Device Timer (T) Continuous timer Counter (C) Destination of OUT instruction All other devices Condition when Blocks Are Disabled Resets. Retains the value it held before the blocks are enabled. Retains the value it held before the blocks are enabled. Goes into an OFF state. Retain the states they held before the blocks are enabled.

Use a SET instruction for devices whose output values need to be retained when blocks are disabled.
This device is set to OFF. X00503 I0002 X00501 X00502 I0003 X00301 I0005 I0004 SET Y00601 Y00603 I0004

Use a SET instruction to retain the output value of this device.


F060404.VSD

Figure 6.8 Example of Devices Initialized When Blocks Are Disabled

6.4.5

Operation When Specified Blocks Are Executed


G Example Where Each Block Controls the Block to Be Enabled Next
Time
Block 1
Condition

ACT

Block 2

INACT Block 1
Condition

Block 1

Block 2
Condition

ACT

Block m

Block 2
Condition

INACT

Block 2

Block m

Block m
Condition

ACT

Block 1

INACT

Block m
F060407.VSD

Figure 6.9 Example Where Each Block Controls the Block to Be Enabled Next Time

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-12
G Example Where Blocks to Be Enabled Are Controlled by Creating
Scheduler
Block 1
Condition

ACT INACT Block 1


Condition

Block 2 Block n Block 3 Block 2 Block 1 Block m Block 3 Block n Block 1 Block m

ACT INACT
Condition

ACT ACT INACT


Condition

ACT INACT INACT

Block 2 Condition Block 3 Condition

Block 1 Condition

Block m Condition

Block n Condition
F060408.VSD

Figure 6.10 Example Where Blocks to Be Enabled Are Controlled by Creating Scheduler

Create a scheduler for block 1 which is initially in an ACTIVE state.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-13

6.5

Debugging Functions
This section describes the following functions: forced set/reset function that forcibly changes the status of a relay, function that changes setpoints, current values and data values specified in a register, as well as the Stop Refreshing function that stops I/O refreshing, link refreshing, and shared refreshing.

6.5.1

Forced SET/RESET

Debug

Stop

A forced SET/RESET instruction forcibly sets a specified bit device to ON/OFF, regardless of program execution. You can use the instruction to a maximum of 32 bit devices at one time. The device type supported is bit devices only, i.e., X, Y, I, E, L, T and C devices. If a forced SET instruction is applied to a timer (T) or a counter (C), the timer expires or the counter terminates. A forced SET/RESET instruction remains valid until you: - Disable the instruction, - Change the operation mode to RUN, or - Turn off the power.

6.5.2

Changing Setpoints, Current Values and Data Values


Debug Stop

Changing Setpoints You can change the setpoints of timers (T) and counters (C). Changing Current Values You can change the current values of timers (T) and counters (C). If you set a current value of 0, a timer expires and a counter terminates. Changing Word or Long-word Data Values You can change the data values of word devices other than timers (T) and counters (C), such as data registers (D). If you select bit devices such as internal relays (I) instead, data values included in the change are those of 16 or 32 bits worth of devices, beginning with the first device address.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-14

6.5.3

Stopping Refreshing

Stop

You can prevent relays (input relays (X) and output relays (Y)) for external devices, link relays/registers for FA links, and shared relays/registers for add-on CPU modules, from being refreshed by the results of program execution. This allows you to visually check I/O data on the monitor. In the case of relays (input relays (X) and output relays (Y)) for external devices, you can stop refreshing X input relays and Y output relays separately.
X00502 X00501 X00503 X00501 X00502 X00504 X00502 X00503 Y00602 Y00601 Y00603 Y00604

CPU data memory

Arithmetic results

Area of Y output relays

External devices

The output is not refreshed.

F060504.VSD

Figure 6.13 Stop of Output Refreshing

CAUTION
It is not possible to stop input relays (X) and output relays (Y) for external devices, specified in the sensor control block, from refreshing.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-15

6.6

Protecting Programs
For security reasons, you can protect your programs from being referenced. There are two modes of protection: executable program protection and block protection. Protection is achieved by entering a password with the WideField2. A password must consist of eight alphanumeric characters, beginning with a letter. The protection information is saved in an executable program or block by the WideField2.

CAUTION
Program protection is designed to prevent unauthorized references only. It is not effective against deleting programs or changing CPU operations due to erroneous operations or writing.

6.6.1

Executable Program Protection


Executable program protection protects the entire executable program. When this protection mode is selected, all functions that act upon an executable program (e.g., downloading, uploading, monitoring and online editing) are disabled.
Personal computer X00503 X00501 X00504 X00502 X00503 Monitoring, debugging operation and printing Y00602 Y00601

Uploading

Downloading

F060601.VSD

Figure 6.14 Executable Program Protection

When executable program protection is selected, the following functions are disabled. Downloading, uploading, monitoring (circuit diagram monitoring, debugging operation, changing timer (T)/ counter (C) setpoints, online editing), ROM writer functions, and printing.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-16

6.6.2

Block Protection
Block protection protects programs on a block-by-block basis. This protection mode is designed to prevent unauthorized references only. In addition, only specified blocks are included in the protection. When block protection is selected for a block, its circuit diagrams and instructions are not displayed on the WideField2.
Block n Personal computer X00503 X00504 Y00602

Block m X00501 X00502 X00503 Y00601

Only the protected bolock is excluded from viewing.

F060602.VSD

Figure 6.15 Block Protection

When block protection is selected, the following functions are disabled. Monitoring (circuit diagram monitoring, debugging operation, changing timer (T) /counter (C) setpoints, and online edit) and printing

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-17

6.7

Online Editing

Debug

Stop

Online editing allows you to make modifications or additions to your program when the program is being executed. This function is useful when you make minor changes to the program during a debugging or tuning task. Modifications/changes made to the program are reflected in the program memory of the sequence CPU module at the end of a given scan.
Addition I0001 X00501 X00503 X00501 X00502 I0002 X00502 I0003 Y00602 I0003 Y00603 I0004

CPU program memory The addition is reflected at the end of a given scan.
F060701.VSD

Figure 6.16 Online Editing

WARNING
Do not perform online editing when machinery under control is in operation. The scan time may become excessively longer than when carried out under normal conditions, while data edited online is written to the sequence CPU module. The scan time lengthens by as much as 10 ms for every 10 K step increase in the program size. During scan time, it is not possible to perform external refreshing or communicate with any external device. If modifications/additions span two or more circuits, several scans will be required until the overall range of these modifications/additions is reflected in the sequence CPU module. Be careful with sequence CPU module operation during this process.

CAUTION
(1) You are not allowed to modify the following instructions and circuits. - Subroutine Entry instruction (SUB instruction) and Subroutine Return instruction (RET instruction) as well as circuits that contain any of these instructions. - Input module Interrupt instruction (INTP instruction) and Interrupt Return instruction (IRET instruction), as well as circuits that contain any of these instructions. - Structure Macro Call Instruction (SCALL), Structure Move instruction (STMOV), as well as circuits that contain any of these instructions. (2) Online editing affects peripheral processing. The peripheral processing time may lengthen by approximately 200 ms, though this depends on the program size or the location in the program where modifications are made. During the peripheral processing time, the CPU does not perform shared refreshing, link refreshing and command processing.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-18

6.8

Making Programs Resident Using ROM Writer Functions


This section describes how to make programs resident in ROM, setting initial values of devices to be resident in ROM, as well as ROM management (writer) function and ROM writer mode.

6.8.1 Making Programs Resident in ROM


Programs that have been debugged and tuned can be made resident in the ROM pack. To make a program resident in the ROM pack, transfer the program to the ROM pack using the ROM writer functions of the sequence CPU module. The items to be made resident in the ROM pack are programs themselves, as well as program management information, configuration information, control tables, timer (T)/counter(C) setpoint tables, and comment management information. All required by the CPU to start program execution at power-on are made resident in the ROM pack. The maximum limits on program steps that can be stored on various ROM packs depend on whether only programs are stored in the ROM pack, or tag name definitions are stored along with programs, as shown in the table below.
Table 6.6 Limitations on Selection of ROM pack
Sequence CPU Module F3SP28-3N F3SP53-4H F3SP38-6N F3SP58-6H F3SP28-3S F3SP53-4S F3SP38-6S F3SP58-6S F3SP59-7S Destination RK33-0N RK73-0N RK33-0N RK73-0N RK33-0N RK73-0N RK33-0N RK73-0N RK33-0N RK73-0N RK33-0N RK73-0N RK93-0N RK33-0N RK73-0N RK93-0N Program 30K steps 56K steps 56K steps 120K steps 30K steps 56K steps 56K steps 120K steps 254K steps 56K steps 120K steps 254K steps No tag name definition can be stored. Program + Tag Name Definition

56K steps 120K steps 56K steps 120K steps 56K steps 120K steps 360K steps 56K steps 120K steps 360K steps

With the configuration function, you can make the following two types of data resident in ROM. These types of data are used to set initial values to be used by a program. - Setpoints of 1,024 data registers (D) worth of default data - Either 32768 data registers (D) or file registers (B) worth of current values within the sequence CPU module. See Section 6.8.2, Setting Devices Current Values to Be Made Resident in ROM. At power-on, data read from the ROM pack is stored in data registers (D) or file registers (B) specified with the configuration function. Data registers (D) and file registers (B) included in the data retention in case of power failure revert to their respective default values. If you edit both of the configuration items mentioned above for the same data register (D), only the setpoint of the second configuration item Setting Devices Current Values is effective.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-19
TIP
Data retention in case of power failure is effective for devices not included in the configuration discussed above.

Program RAM configuration Program management table

ROM pack configuration Program management table

Program

Program

Configuration table RAM I/O configuration table Program control instruction table Timer/counter setpoint table Utility

Tag name definition table Configuration table I/O configuration table Program control instruction table Timer/counter setpoint table Utility
F060801.VSD

ROM area

Figure 6.17 Contents of Program to Be Made Resident in ROM

CAUTION
Limitations on writing to the ROM pack - Debug and tune programs before making them resident in the ROM. There is a limit to the number of write operations that can be performed on a ROM pack. Furthermore, program and data resident in the ROM pack cannot be edited. Writing to the ROM pack of an installed CPU module - A resident program in a ROM pack can only be executed by the CPU module whose model name has been transferred to the ROM pack. Example: A program written in the ROM pack by a F3SP28-3S CPU module can only be executed by a F3SP28-3S CPU module. A program written in the ROM pack by a F3SP28-3N CPU module cannot be executed by a F3SP28-3S CPU module. Compatibility between the ROM pack and the CPU module - If a sequence CPU module is installed with an incompatible ROM pack, WideField2 may return an error message of "ROM cassette is not installed."

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-20

6.8.2

Setting Devices Current Values to Be Made Resident in ROM


Define initial values to be made resident in data registers (D) or file registers (B) when program execution begins. The data items to be defined are the type of device, starting number, and quantity of devices. This configuration enables the current values of the specified devices to be stored in the ROM pack when the file-to-ROM transfer or CPU-to-ROM transfer (ROM copy) function of the ROM writer functions is executed. You can determine whether or not to update the device data to be made resident in ROM with the current values when executing the file-to-ROM transfer or CPU-to-ROM transfer function. When program execution begins, the device data in the ROM pack is read and stored in the specified devices. This configuration is useful when you want to set a large volume of initial data or save initial data for a program. You can set initial values in a maximum of 32768 devices.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-21

6.8.3

ROM Writer Functions and ROM Writer Mode

ROM writer

The sequence CPU module or an add-on CPU module can be operated by reading a program stored in the ROM pack. In the FA-M3 R series, you can achieve the same functions as those of a commercially available ROM writer, such as writing a program to the ROM pack, by using the sequence CPU module or add-on CPU module. These functions are called the ROM writer functions and include file-to-ROM transfer, CPU-toROM transfer, and file and ROM pack comparison. The ROM writer functions work in a dedicated mode different from the normal operation mode of the sequence CPU module. This dedicated mode is called the ROM Writer mode. The ROM Writer mode is maintained even when you turn on or off the power. At power-on, no programs are read from the ROM pack.
Sequence CPU

Program memory ROM pack Transfer Write Read ROM Writer mode
F060802.VSD

Figure 618 ROM Writer Functions and ROM Writer Mode

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-22
Using the ROM writer functions, you can save a debugged and/or tuned program to the ROM pack. To transfer the program to the ROM pack, use the ROM management function of the WideField2. The following details the ROM writer functions.

File-to-ROM Transfer Function


This function writes programs, data, and a tag name definitions to a ROM pack. It first transfers a program to the CPU memory, and then writes the program to the ROM pack. You can specify whether to make the current values of devices resident in ROM and whether to write tag name definitions to the ROM pack. Tag name definitions, if to be written, are written directly to the ROM pack without first being transferred to the CPU memory.

I CPU-to-ROM Transfer (ROM Copy) Function


This function writes a program or data in the CPU directly to the ROM without transferring it using the ROM management function of the WideField2. You can specify whether to make the current values of devices resident in ROM and whether to write tag name definitions to the ROM pack. A debugged and/or tuned program or data in the CPU is not initialized when the CPU is changed to the ROM Writer mode. It is therefore possible to write the program or data directly to ROM. If tag name definitions are downloaded in the CPU, they are also written directly the ROM pack. This function is also used to write the same program to multiple ROM packs. You can write the program to multiple ROM packs by simply changing the ROM packs one after another. There is no need to transfer the program repeatedly.

I Compare File and ROM Function


This function compares the content of the ROM pack with the program in WideField2. If the contents do not match, the function shows the mismatches.

I ROM Clearance Function


This function erases the content of a ROM.

CAUTION
Change the CPU to the ROM Writer mode before using the ROM writer functions. You cannot use the ROM writer functions in other modes. Be sure to disable the ROM Writer mode when you finish using the ROM writer functions. The CPU does not execute any sequencing functions if the ROM Writer mode remains active.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-23

6.9

Exclusive Access Control


This section describes exclusive access control, a function that prohibits program, operation mode, or device data from being changed or downloaded during operation or debugging. An excusive access right is used to prevent a program, operation mode, or device data from being changed or prohibit the program or device data from being downloaded by other users when the program is being executed or debugged. Once you acquire the exclusive access right, all alteration- and control-related commands entered from other tools, sequence CPU modules or personal computer links are rejected until you release the right. If you withhold the exclusive access right, all alteration- and control-related commands from other users remain disabled. Release the access right as soon as you have completed the required process. If another user has already acquired the exclusive access right, it is not available to you. The exclusive access right is handled in the following three modes:

G Get
This mode acquires the exclusive access right.

G Release
This mode releases the exclusive access right.

G Forced Release
This mode permits you to forcibly acquire the exclusive access right from the CPU holding the right through access from a tool or module having no access right.
Personal computer

Prohibition of access Acquisition of exclusive access right Personal computer link

Sequence CPU module

F060901.VSD

Figure 6.19 Exclusive Access Right

Once the exclusive access control is acquired, the system prohibits the following acts from being performed by a tool or module having no access right. CPU operation, CPU stop, debugging, downloading, debugging operation, use of debugging functions, writing to devices, and change in timer (T)/counter (C) setpoints.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-24

6.10 Sampling Trace Function


This section describes the sampling trace function that records state transitions of specified devices. The sampling trace function sequentially stores the states and contents of devices selected to be sampled, in the sampling trace memory of the sequence CPU module. The sampling trace function has three sampling modes: - Sampling trace instruction (TRC) - End-of-scan sampling - Fixed-interval sampling As the condition for triggering sampling, you can define the rising or falling edge of a selected relay signal or a match with the data of a selected word device. The CPU monitors the trigger condition during scan end processing. If the trigger condition becomes true, the CPU is allowed to perform 1024 rounds of sampling from a point of time as much as the number of delays before (negative delay) or after (positive delay) the condition becomes true. Configure the sampling trace function using the WideField2. The results of sampling trace operation can be viewed on the WideField2 in timing-chart format, as shown below.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-25

M00040

/C00001

Start of sampling trace Trigger condition Sampling method Sampling frequency Number of delays Devices to be sampled

: Instructed from the programming tool : Set from the programming tool - Rising/falling edge of signal at selected relay - Match between data values : TRC-instruction sampling End-of-scan sampling (every 1 to 1000 scans) Fixed-interval sampling (10 to 2000 ms) : 1024 cycles : Selection of a positive or negative number from (-1023 to +1023) : 16 points of X, Y, I, E, L, T, C or M relay devices 4 or 16 points of D, B, R, W, V, Z, T or C word devices or X, Y, I, E, L, T, C or M relay devices, beginning with the one with the specified first address

F061007.VSD

Figure 6.20

View of Results of Sampling Trace Operation

You can perform the sampling trace function in either the Run or Debug mode. The sampling trace function, if performed, deletes previous data. If you define sampling trace function settings using the configuration function, the CPU begins sampling at the moment of power-on. If you define sampling trace function settings using the configuration function and then permanently store them in ROM, the CPU reverts to the ROM data during a power-on-and-off sequence even if you redefine the settings later using the programming tool.

SEE ALSO
For details on how to define sampling trace function settings, see, "FA-M3 Programming Tool WideField2 Instruction Manual" (IM34M6Q15-01E).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-26
Sampling is carried out as explained below.

G Sampling Using the Sampling Trace (TRC) Instruction


By using the Sampling Trace (TRC) instruction in a program, you can sample the states and data of specified contacts at any point of a scan. The CPU collects data when the input-condition relay of the Sampling Trace (TRC) instruction is set to ON. The CPU stores results of up to four cycles of sampling if it has executed multiple TRC instructions during the same scan. The subsequent Sampling Trace (TRC) instructions are ignored. It is at the end of a given scan when the CPU actually stores the results.
END TRC END TRC TRC END TRC END

Sampling

Sampling

Sampling

Sampling
F061002.VSD

Figure 6.21 Sampling Using the Sampling Trace (TRC) Instruction

G End-of-scan Sampling
The CPU samples the states and data of specified contacts at the end of a scan. It collects and stores the data each time the specified number of scans are completed.
END END END END

Sampling

Sampling
F061003.VSD

Figure 6.22 End-of-scan Sampling at Two-scan Intervals

G Fixed-interval Sampling
The CPU samples the states and data of specified contacts at fixed time intervals. It collects and stores the data when the specified period expires and before the next scan begins.
Specified period END END END END

Sampling

Sampling
F061004.VSD

Figure 6.23 End-of-scan Sampling at Two-scan Intervals

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-27
CAUTION
The sampling trace function monitors the trigger condition when an END instruction in a program is being processed. The function therefore cannot judge the condition as established if it is established once during program execution but becomes false again by the time the processing of the END instruction begins.

G Sampling when Negative Delay Is Defined


Negative number of delays Trigger condition being established Start of tracing End of tracing

Results of 1024 cycles of tracing are stored in the sampling trace memory
F061005.VSD

Figure 6.24 Sampling when Negative Delay Is Defined

G Sampling when Positive Delay Is Defined


Start of tracing Trigger condition being established Positive number of delays End of tracing

Results of 1024 cycles of tracing are stored in the sampling trace memory
F061006.VSD

Figure 6.25 Sampling when Positive Delay Is Defined

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-28

6.11 Personal Computer Link Function


This section describes the personal computer link function that allows a personal computer or a display device to be connected to a sequence CPU module. The programming tool connector on the front of the CPU module functions in the same way as the RS232-C communication port on the F3LC11-1N personal computer link module. This means you can connect a host computer, such as a personal computer or FA computer, or a monitor to the CPU module to perform one-to-one communication as you do with the personal computer link module. This feature is called the personal computer link function. You can monitor and configure devices and start, stop, load and save programs by entering commands from the host computer.
Personal computer or monitor with PC interface Personal computer running WideField2 Personal computer

X00503

X00504

Y00602

Perosnal computer link function Capability of programming tool connection

X00501

X00502 X00503

Y00601

Sequence CPU module

F061101.VSD

Figure 6.26 Personal Computer Link Function

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-29

6.11.1 System Configuration


Figure 6.27 shows examples of system configuration using the personal computer link function. External equipment, such as a personal computer or monitor, is connected to the sequence CPU module of the FA-M3 by using the programming tool connector on the front of the FA-M3 and a dedicated programming tool cable.
Personal computer Monitor

Programming tool cable FA-M3 FA-M3

Programming tool cable

Sequence CPU module

Sequence CPU module

F061102.VSD

Figure 6.27 Examples of Connection between a Sequence CPU Module and External Equipment

Provide the programming tool cable with a ferrite core if you want to have the connected device compatible with the CE marking.
Kitagawa Industries K.K. Examples of ferrite cores TDK Corporation NEC TOKIN Corporation RFC series ZCAT series ESD-SR series

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-30

6.11.2 Differences from Personal Computer Link Module


This section describes the differences between the F3LC1 -1F personal computer link module and the personal computer link function of the CPU.

I Function
The transmission rate and data format of the CPUs personal computer link function differ from those of the personal computer link module. For more information, see subsection 6.11.4, Setting Up the Personal Computer Link Function.
Table 6.7 Transmission Rate and Data Format of CPUs Personal Computer Link Function
Transmission Rate (bps) 9600 9600 19200 19200 38400 38400 57600 57600 115200 115200 Data Length 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits Parity Even None Even None Even None Even None Even None No. of Stop Bits 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit

The dedicated programming tool cable is required to connect a personal computer or monitor to the CPU module. To set the transmission rate, data format, checksum, terminating character, and protection function, use the configuration item communication setting, or switches in the case of the personal computer link module. The event transfer function is not supported. An MDR module reset command resets only the communication port. The maximum number of personal computer link modules that can be installed remains the same even if the CPUs personal computer link function is used.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-31
I Protocol
This section briefly describes the communications protocol of the personal computer link function of CPU.
Sending station Receiving station Communication protocol of personal computer link function STX Station No. CPU No. Response wait time Command Parameters Checksum ETX CR STX Station No. CPU No. OK Command response Checksum ETX CR

F061103.VSD

Figure 6.28 Communication Protocol of Personal Computer Link Function

In personal computer link communication, the maximum size of text that can be transferred at the same time is 512 bytes.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-32

6.11.3 Specification of Personal Computer Link Function


Table 6.8 Specifications of Personal Computer Link Function
Item Interface Transmission mode Synchronization Transmission rate (bps) Half-duplex Start-stop 9600/19200/38400/57600/115200 Start bit: 1 Data format Data length: Fixed at 8 bits Parity bit: None/Even Stop bit: Fixed at 1 bit Error checking RS-232-C control line Xon/Xoff Configurable item Protocol Terminal character Protection function *2 Range of access operations Transmission distance External connection
*1 *2

Description Compliant with EIA RS-232C

Setup *1

Parity check Checksum: Yes/No Not used. Not used. Transmission rate, data format, checksum, terminal character, and protection function Dedicated protocol Yes/No Yes/No Access to all control data, uploading/downloading ladder programs, CPU operation (Run mode)/stop (Stop mode), and reading error logs 8m max. Dedicated cable

The check mark indicates that the user can configure the item by using the configuration function. However, there are restrictions on the way the transmission rate and parity check are combined. See subsection 6.11.4, Setting Up the Personal Computer Link Function, for more information. You can set the protection function to the Yes option to prevent inadvertent writing to the FA-M3.

CAUTION
The personal computer link function uses neither a control line nor Xon/Xoff characters. Be careful when using the function because a communication failure may occur at the higher-order equipment side, depending on the transmission rate.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-33

6.11.4 Setting Up the Personal Computer Link Function


This subsection describes the items you should define when using the personal computer link function.

I Transmission Rate and Data Format


You cannot set up the transmission rate and data format separately because they are shared by WideField2 and personal computer link function. To define these items, use the ladder programming tool or the program configuration function. You can define the transmission rate and data format only by selecting one of the combinations listed in Table 6.9.
Table 6.9 Combinations of Transmission Rate and Data Format
Mode Communication mode 0 Communication mode 1 Communication mode 2 Communication mode 3 Communication mode 4 Communication mode 5 Communication mode 6 Communication mode 7 Communication mode 8 Communication mode 9 Transmission Rate and Data Format Transmission Data No. of Parity Rate (bps) Length Stop Bits 9600 9600 19200 19200 38400 38400 57600 57600 115200 115200 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits Even None Even None Even None Even None Even None 1 bits 1 bits 1 bits 1 bits 1 bits 1 bits 1 bits 1 bits 1 bits 1 bits Use of Hand-held Programming Tool Yes No No No No No No No No No

The personal computer link function is set to communication mode 0 when the sequence CPU module is shipped from the factory, the CPU memory is cleared, or the function has not yet been configured.

CAUTION
Be careful when setting the transmission rate. The WideField2 supports all of the communication modes listed above. However, first refer to the instruction manual of the personal computer that runs the WideField2 to check available transmission rates and data formats. Then, temporarily change the transmission rate of the personal computer link function using WideField2 to make sure the Sequence CPU module can communicate with the personal computer in the communication mode you want to use. Finally, configure the personal computer link function according to that communication mode. Note that the personal computer link function automatically reverts to the previous transmission rate if communication is not established after a temporary change in the transmission rate. If you select a communication mode in which the personal computer cannot communicate, it is impossible to communicate with the Sequence CPU module through the computer. If this happens, first install the sequence CPU module in the fifth or later slot of the main unit. Next, turn on the power and make sure the RDY indicator has come on. Then, turn off the power to clear the sequence CPU module memory completely and allow the CPU module to revert to its factory-set defaults.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-34
CAUTION
To use the personal computer link function, set the configuration item personal computer link function to the option Used. If you do not select this option, communications with higher-order instruments may fail.

I Checksum, Terminating Character and Write Protection Function


Define these items using the program configuration item communication setting. By default, all these items are set to the option Not used.

SEE ALSO
For details on the configuration function, see, "FA-M3 Programming Tool WideField2 Instruction Manual" (IM34M6Q15-01E).

6.11.5 Communication Procedure


To be able to perform communication, the transmission specifications, e.g., the transmission rate and data format, must be consistent between the CPU module and a personal computer, FA computer or monitor. Use the program configuration function to set up the transmission specifications of the sequence CPU module. To set the transmission specifications of a personal computer or FA computer, use a communication software program. In the case of the transmission specifications of a monitor, use its own configuration tool.

I Communication Procedure
The following outlines the procedure of communication using a BASIC program on a personal computer. For details on the statements and functions used in the program, refer to the BASIC reference manual that came with your personal computer. 1. Open the RS-232-C communication file. Enter a command in the following format: OPEN COM : AS# : Enter communication parameters, such as the parity, data length, and the number of stop bits. : File number. This number is used for subsequent inputs to and outputs from the file. 2. Send a command to the FA-M3 in the following format. PRINT#n, String variable name (or string) 3. Enter a command in the following format to receive a response from the FA-M3. LINE INPUT#n, String variable name INPUT#n, String variable name

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-35
I Overview of Communication
Communication control performed by the CPU module is based on the processing of commands and responses using a dedicated protocol. At first, the host computer (or monitor) has the transmission right. When the computer sends out a command, the transmission right transfers to the CPU module. The CPU module then sends a response to the host computer. If the configuration item personal computer link function is set to the option Used, the CPU module does not send any command to the host computer.
Personal computer (when running BASIC programs) Program Print# Line Input# or Input$ Command xxxxxx (ASCII string)

Response xxxxxx (ASCII string) FA-M3

Power supply

CPU

F061104.VSD

Figure 6.29 Interaction between Command and Response


Host computer Command STX code Station No. CPU No. Response wait time Command Parameters Checksum ETX code Terminating character

To FA-M3 (FA-M3) Response STX code Station No. CPU No. Response wait time Command response Parameter Checksum ETX code Terminating character
F061105.VSD

To host computer or monitor

Figure 6.30 Brief Description of Command and Response Formats

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-36

6.11.6 Commands and Responses


SEE ALSO
For details on commands and responses, see "Personal Computer Link Commands Instruction Manual" (IM34M6P41-01E).

Command Format and Elements


Figure 6.31 shows the format of a command to be sent from the host computer or monitor to the FA-M3.
No. of Bytes 1 2 2 1 3 Variable-length 2 1 1 Element STX code Station No. CPU No. Response wait time Command Parameters Checksum ETX code CR code
Required only if the configuration item "checksum" is set to the "Yes" option Required only if the configuration item "terminating character" is set to the "Yes" option F061106.VSD

Figure 6.31 Command Format and Elements

For commands and responses, use the upper-case alphabetic letters of A to Z, which are the ASCII codes of $41 to $5A (hexadecimal numbers). The individual elements are detailed below.

G STX (Start of Text) Code


A control code indicating the start of text. The corresponding character code is $2.

G Station Number
The station number is fixed at 01 when the personal computer link function of the sequence CPU module is used.

G CPU Number
Use a number from 01 to 04 to define which of the sequence CPU module and add-on CPU modules is the one to communicate with. 01: Sequence CPU module 02: Add-on CPU module 1 03: Add-on CPU module 2 04: Add-on CPU module 3

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-37
G Response Wait Time
You can set a wait time, i.e., delay, which is an interval from when a command is sent to when a response is received. The wait time can be as long as 600 ms. Set a relatively long wait time if the communication software running on the host computer is such a program as a BASIC interpreter. To set a wait time, use characters 0 to F, as shown below.
Table 6.10 Setpoints of Response Wait Time
Character 0 1 2 3 4 5 6 7 Response Wait Time (ms) 0 10 20 30 40 50 60 70 Character 8 9 A B C D E F Response Wait Time (ma) 80 90 100 200 300 400 500 600

Note: Even if the response wait time is set at 0, there is a delay of as much as the internal processing time*.

Host computer or monitor

Command

Response wait time Internal processing time*

CPU module

Preprocessing Processing

Postprocessing

Response

One scan

Pause between scans

One scan
F061107.VSD

Figure 6.32 CPU Operation during Response Wait Time

G Command
Using three letters, specify the type of access, such as reading or writing, from the host computer or monitor to the sequence CPU module.

G Parameters
Set such data items as a device name, the number of devices and their data values. Available parameter types vary depending on the command you use. No parameter is required for some commands.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-38
G Checksum
A checksum can be added to the transmission text to check data. Using the program configuration function, you can determine whether or not to add a checksum. If you set the item Checksum to Yes, you must add a checksum to a command which is sent from the host computer or monitor to the FA-M3. In this case, a checksum is automatically added to each response. If the item Checksum is set to No, this code is unnecessary. The calculation of the checksum is explained below. The ASCII codes of characters from the one following the STX code to the one immediately preceding the checksum code in the text are added together on a byte-bybyte basis. The lower-order one byte of the result of performing addition is taken and represented as a hexadecimal number. The 2-character, 2-byte string thus obtained is used as the checksum.
Transmission text (character string) Range of check-sum calculation STX 0 1 0 1 A B R D X 0 0 2 0 1 , 1 6 B 9 ETX CR

Checksum

02 30 31 30 31 41 42 52 44 58 30 30 32 30 31 2C 31 36 42 39 03 0D Hexadecimal ASII code The ASCII codes are added together as "30+31+30+31+41+42+52+44+58+30+30+32+30+31+30+31+2C+31+36=3B9 (hexadecimal)." The checksum is a hexadecimal representation of the lower-order one byte of the result of performing addition. In this case, it is B9.
F061108.VSD

Figure 6.33 Method of Check-sum Calculation

G EXT (End of Text) Code


A control code indicating the end of text. The corresponding character code is $3.

G CR (Carriage Return) Code


A control code indicating the termination of text. The corresponding character code is $0D, which is the ASCII-code decimal numeral of 13. This code is required only if the configuration item Terminal character is set to Yes.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-39 Response Format and Elements


The following shows the format of a response to be sent from the FA-M3 to the host computer or monitor. For details on the individual elements and characters used, see paragraph (1), Command Format and Elements.

G When Communication is Normal


No. of Bytes 1 2 2 2 Variable-length 2 1 1 Element STX code Station No. CPU No. OK Command response Checksum ETX code CR code Also added to the response only if specified accordingly using the configuration Figure 6.32 Response Format when Communication Is Normal
F061109.VSD

Figure 6.34 Response Format when Communication is Normal

When communication ends successfully, the string OK is returned along with a command response.

G When Communication is Abnormal


No. of Bytes 1 2 2 2 2 2 3 2 1 1 Element STX code Station No. CPU No. ER EC 1 EC 2 Command Checksum ETX code CR code

Also added to the response only if specified accordingly using the configuration.
F061110.VSD

Figure 6.35 Response Format when Communication Is Abnormal

When communication results in an abnormal end, the string ER is returned along with the codes EC1 and EC2, where: EC1 = Error code EC2 = Detailed error code If the communication failure is due to an error in the CPU number, the received 2-byte CPU number is returned. If the failure is due to an error in the station number, no response is returned. If an ETX code in a command is not received, no response may be returned. If this happens, be sure to perform a timeout process on the host computer or monitor.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-40 Error Code in a Response


A communication failure may occur when the sequence CPU module receives a command. In that case, the module returns the string ER and an error code as a response to the command. The following error codes are reserved.
Table 6.11 Error Codes
Error Code (EC1) 01 02 03 Meaning CPU number Probable Cause

04

05 06 08 41 42 43 51 52 F1

- The CPU number is outside the range of 1 to 4. - The command does not exist. Command error - The command is not executable. - The device name does not exist.* Device specification - Incorrectly specified the bit devices in an attempt to read/write error them in units of words. - Attempted to use characters other than 0 and 1 when setting bits.* - Attempted to use values other than 0000 to FFFF when setting w Value outside the ords. range - The starting point in the command, such as Load or Save, is outside the range of addresses. Number of data - The number of bits or words is outside the specified range.* items outside the - The specified number of data items does not match the number range of parameters including device names. - Attempted to execute monitoring without having specified a monitor Monitor error command (BRS or WRS). Parameter error - The parameter is incorrect for a reason other than noted above.* Communication error - An error has occurred during communication.* Checksum error - The check sum is wrong due to missing bits, garbled character, etc. Internal buffer - The amount of data received is larger than the specified. overflow - No end-of-process response is returned from the CPU for reasons Timeout such as a CPU power failure. CPU processing - The CPU has detected an error when processing the command. failure - A Cancel command (PLC) has been issued while neither a Load Internal error command (PLD) nor a Save command (PSV) is in process. - An internal error is found.

See Table 6.12, "Detailed Error Codes," for more information.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-41
If a parameter error occurs, the detailed error code field indicates the number of the faulty parameter. If a communication error occurs, the detailed error code field indicates details on the error.
Table 6.12 Detailed Error Codes
Error Code (EC1) 03 04 05 Meaning Device specification error Value outside the range Number of data items outside the range Detailed Error Code (EC2) *
The EC2 field provides a hexadecimal representation of the number assigned to the faulty parameter. (The number is one, among the ordinal parameter numbers, at which an error has occurred first.) (Example:) 6 Parameter 1 2 4 5 3 S numbers T 0101ABRW 03 Y00501, 1, I0002, 0, A1234567 X Erroneous device number In this example, the respective error codes take the values shown below. - EC1 = 08 - EC2 = 06

08

Parameter error

b
7

b
6

b
5

b
4

b
3

b
2

b
1

b
0

MSB

LSB

41

Communication error

Each bit has the following meaning. b7: Reserved b6: Reserved b5: Framing error b4: Overrun error b3: Parity error b2: Reserved b1: Reserved b0: Reserved
1 2 4 8 9 A B C F : Self-diagnostic error : Program error (including parameter error) : CPU-to-CPU communication error : Device access error : Protocol error : Parameter error : Operation mode error, or state of protection or exclusive access : Device/block specification error : System's internal error

52

CPU processing failure

* The EC2 error code has no meaning for any value of EC1 other than those listed above.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-42 Devices which can specified


Table 6.13 lists devices that you can select by typing their names. Use commas (,) or spaces to separate parameters. A device name should be represented in six or seven characters (or bytes). Their abbreviations can be also used, however. For example, X00201 can be abbreviated as X201 and V00002 as V02 or V2. The following example shows a case when you read the data of CPU1s five input relays, beginning with input relay X00201. The response wait time is assumed to be 100 ms.
S T X 0 1 0 1 A B R D X 0 0 2 0 1 , 0 0 5

Command Response wait time CPU number Station number, which is fixed at 01.

Parameters

F061111.VSD

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-43
Table 6.13 Specifiable Devices
Device Name Xnnnnn Input relay Ynnnnn Output relay Innnnn Internal relay Bit device Ennnnn Shared/extended shared relay Lnnnnn Link relay Mnnnnn Special relay Tnnnnn Timer Cnnnnn Counter Dnnnnn Data register Rnnnnn Shared register Word device Vnnnnn Index register Bnnnnnn File register *3 Wnnnnn Link register Znnnnn Speical Read Length 6 bytes 6 bytes 6 bytes 6 bytes 6 bytes 6 bytes 6 bytes 6 bytes 6 bytes 6 bytes 6 bytes 7 bytes 6 bytes 6 bytes Bit Yes Yes Yes Yes Yes Yes Yes*1 Yes*1 No No No No No No Word Yes Yes Yes Yes Yes Yes Yes*2 Yes*2 Yes Yes Yes Yes Yes Yes Bit No Yes Yes Yes Yes Yes*6 No No No No No No No No Write Word No Yes Yes Yes Yes Yes*6 Yes*2 Yes*2 Yes Yes Yes Yes Yes Yes*6

*1 Specify: a time-out relay as TUnnnn, and an end-of-count relay as CUnnnn, *2 Specify: - the current value of a countdown timer as TPnnnn, - the current value of a countdown counter as CPnnnn, - the current value of a count-up timer*4 as TInnnn, - the current value of a count-up counter*4 as CInnnn, - the setpoint of a timer*5 as TSnnnn, and - the setpoint of a counter*5 as CSnnnn. *3 Only available with the F3SP25, F3SP28, F3SP35, F3SP38, F3SP53, F3SP58, and F3SP59 sequence CPU modules. *4 The countdown type of timers and counters has been made available with the FA-M3 controller for such reasons as viewing them on a host computer. Current value of count-up type timer/counter =Setpoint-Current value of countdown type timer/counter *5 The timer setpoint TSnnnn and counter setpoint CSnnnn are not available for a word writing command. *6 In the case of F3SP28, F3SP38, F3SP53, F3SP58, and F3SP59 sequence CPU modules, writing to this device is not possible with any of BWR, BFL, WWR and WFL commands. Alternatively, use a BRW or WRW command.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-44 Cautionary Notes on Communication Process


No response may be returned if for example, you specify a wrong station number in a command. In such a case, perform a time-out process on the host computer. When downloading a program using the personal computer link function, you are not allowed to download the program at the same time using a personal computer link module or Ethernet interface module. If you do, normal operation is not guaranteed. If you write a value to the shared device that is being used by another sequence CPU module, the written value may soon be updated. If you are using a monitoring-purpose command, you must renew it in the event of a power failure. In personal computer link communication, the maximum size of text that can be sent or received by the CPU module at one time is 512 bytes. The maximum size that can be received by the host computer may be limited to 256 bytes if there is such a limitation on the computer. If this is the case, pay special regard to the length of response text. Take such corrective measures as reducing the number of devices to be read, so that the text length will not exceed 256 bytes.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-45

6.12 Device Management Function


The device management function enables you to upload/download device information/data of the CPU module to/from the WideField2, edit the data, and crosscheck it between the CPU module and the WideField2. You can specify the range of devices whose data are uploaded or downloaded. You can also use this function to set defaults in devices when, for example, replacing the CPU module. The devices that you can configure using the device management function are: Internal relays (I), shared relays (E), time-out relays for timers current values (T), countup relays for counters current values (C), data registers (D), shared registers (R), link registers (W), index registers (V) and file registers (B) You cannot configure the following devices. I/O relays (X/Y), timers and counters, special relays (M), and special registers (Z). The device management function serves the following four purposes.

I Device Data Uploading


The device management function allows you to read device information/data from the sequence CPU module and saves it to a WideField2file. You can specify the range of devices to be saved.

I Device Data Downloading


The device management function allows you to read device information/data from a WideField2 file and writes it to the sequence CPU module. You can either download all the device data from the file or download part of the data by specifying the range of devices.

I Device Data Editing


The device management function allows you to edit device information/data in a WideField2 file. You can view and change the current value of each device.

I Device Data Comparison


The device management function allows you to compare device information/data in the sequence CPU module with that in a WideField2 file. You can make a comparison of all device data in the file or part of the data by specifying the range of devices. If there is any mismatch, the function shows the name of the device having the mismatch as well as the mismatch itself.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-46

6.13 Macro Instructions


This section describes macro instructions. Using the macro instruction function allows multiple reuse of a created program, increasing programming efficiency. A program using macro instructions contain compact program codes for each function, thus improving program readability and maintainability.

6.13.1 What Are Macro Instructions?


I Overview
A macro instruction enables you to perform a process requiring multiple instructions/steps as a single-instruction/step process. Figure 6.36 presents an overview of the macro instructions. How to write a macro instruction in ladder diagram editing
X00502 MOV M ABC D0001 D0002 0 (Mnemonic: MCALL ABC D0001 D0002 0) M V01 EFG123 W0001 Y00301 D0002 (Mnemonic: MCALL EFG123 D0002 W0001 Y00301) 1 D0001 Macro instruction call (calling side)

F061301.VSD

How to write macro instruction entity "ABC" in ladder macro editing


"ABC" macro instruction entity (called side) M033 MOV MOV P02 = U01 P01 1 2 + A0001 U01 A001 MRET
F061302.VSD

Figure 6.36 Examples of Macro Instructions

In Figure 6.36, the ABC and EFG123 instructions are macro instructions. When the CPU encounters the ABC instruction, it executes the called-side ABC macro instruction entity like a subroutine, using operands D0001 and D0002 as its parameters. Macro instructions are created by ladder-macro editing separately from regular instructions created in ladder-diagram editing. The MRET (macro return) instruction represents the end of the macro instruction. For details on operands P01, P02, and U01 in the figure, see subsection 6.13.3, "Devices Dedicated to Macro Instructions.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-47
SEE ALSO
For details on the Macro Return (MRET) instruction, see Section 3.13.4, "Macro Call (MCALL), Parameter (PARA), Macro Return (MRET), of "Sequence CPU Instruction Manual - Instructions" (IM34M6P12-03E, 3rd Edition).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-48
I Purpose
Using macro instructions offers the following two advantages.

G Enhancing Programming Efficiency


Like subroutines, macro instructions allow you to group processes of the same type into one. Macro instructions differ from subroutines, however, in the following two points. Parameters can be passed to macro instructions. Subroutines require that an instruction for passing parameters, such as MOV, must precede a CALL instruction. Macros can be handled as instructions. You need not be aware of internal processing at all except for inputting/outputting parameters.
Reuse of subroutines Use of macro instructions

Reuse subroutines? Yes Search for subroutines Find I/O data Mention the devices used internally Copy subroutines (Note) Match I/O data with data of devices used internally End

No

Presence/absence of instructions

Absent

Present Create subroutines newly Check specifications Input of instructions End Create new instructions

Note: 1. Copy a block containing subroutines under a different name. 2. Delete components other than subroutines from a circuit diagram. 3. In ladder-diagram editing, read the copying-destination block.

F061303.VSD

Figure 6.37 Difference between Subroutines and Macro Instructions

G Accumulating Expertise
You can accumulate your control expertise in the form of macro instructions to customize your FA-M3 controller.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-49 Types of Macro Instructions


There are three types of macro instructions, the availability of which depends on CPU types as follows:
Table 6.14 Macro Instructions and their Availability
Types Macro Call (MCALL) Input Macro Instruction Call (NCALL) Structure Macro Instruction Call (SCALL) Available Not available Not available F3SP28-3N F3SP38-6N F3SP53-4H F3SP58-6H Available Available Available F3SP28-3S F3SP38-6S F3SP53-4S F3SP58-6S F3SP59-7S

G Macro Call
The Macro Call instruction can pass up to 16 parameters.

G Input Macro Instruction Call


The Input Macro Instruction Call instruction can be used as an input condition, just like the Load or Compare instruction. It can be used to represent complex or reusable input conditions in a single instruction. Using an Output of Input Macro (NMOUT) instruction in an Input Macro Instruction allows you to output the result of logical operations to the next instruction.

INLET1 = =
F061304.VSD

Macro instruction

Increased reusability and visibility

Figure 6.38 Benefits of Input Macro Instruction Call

G Structure Macro Instruction Call


The Structure Macro Instruction Call instruction passes multiple data items collectively in a structure to a macro instruction, and is especially useful in reducing the number of items to be passed to a macro and providing better representation of a group of related data items.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-50

6.13.2 Specification of Macro Instructions


I Number of Macro Instructions
Called-side macro instruction entities are downloaded, along with user ladder programs, from a personal computer to the sequence CPU module using the WideField2. The table below lists the maximum number of called-side macro instruction entities allowed in one executable program during downloading. In addition, you can use each callingside macro instruction in your user ladder program any number of times.
Table 6.15 Maximum Number of Macro Instructions Allowed by CPU Type
F3SP28-3N F3SP38-6N F3SP53-4H F3SP58-6H 64 0 (not available) 0 (not available) Total of 256 F3SP28-3S F3SP38-6S F3SP53-4S F3SP58-6S F3SP59-7S

Types Macro Call (MCALL) Input Macro Instruction Call (NCALL) Structure Macro Instruction Call (SCALL)

I Size of Macro-instruction Program


The size of a program of called-side macro instruction entities is limited by the total size of that program and user programs combined.

I Macro Instruction Execution Time


Table 6.16 Macro Instruction Execution Time
F3SP28 F3SP38 When Executed (s) 10.0 6.0 5.0 10.0 2.4 34.0 When Not Executed (s) 0.45 0.27 0.45 0.18 3.17 F3SP53 F3SP58 F3SP59 When When Not Executed Executed (s) (s) 4.0 0.175 2.5 0.105 2.0 4.0 1.0 15.7 0.175 0.070 1.265

FUN NO. 996 995 998 981 309 980

Instruction

Mnemonic

Macro Call Parameter Macro Return Input Macro Instruction Call Output of Input Macro Structure Macro Instruction Call

MCALL PARA MRET NCALL NMOUT SCALL

I Online Macro Instruction Editing


You can use the online edit function of the WideField2 for user-created ladder programs containing calling-side macro instructions. In that case however, you can use only already download macro instructions. You cannot create any new macro instruction. You can also edit online already downloaded called-side macro instruction entities. It is not possible, however, to edit online any circuit diagram that follows the Macro Return (MRET) instruction.

I Making Macro Instructions Resident in ROM


Like programs, you can make macro instructions resident in a ROM pack. This is automatically done when you transfer a program to the ROM pack using the ROM writer function of the CPU module.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-51

6.13.3 Devices Dedicated to Macro Instructions


Table 6.17 Devices Dedicated to Macro Instructions
Device Pointer register (P) Macro relay (H) Macro register (A) Macro index register (U) Structure pointer register (Q) Symbol P H A U Q Range P01 to P16 H0001 to H0512 A0001 to A0512 U01 to U16 Q01, Q02 Number of devices 16 512 512 16 2

I Pointer (P) Registers


Pointer registers are dedicated to macro instructions and used to pass parameters to macro instructions. You can use these registers for called-side macro instruction entities. Structure macro instructions use structure pointer registers instead of pointer registers. The relationship between the pointer register (P) and macro instruction parameters is shown in the following figure.
M EFG123 D0001 I0001 Y00301 Operand 3 Operand 2 Operand 1
F061305.VSD

Table 6.18 Relationship between Pointer Registers and Macro Instruction Operands
Operand No. Pointer Register No.

1 2 3 4

P01 P02 P03 P04


Parameters that can be passed using a parameter instruction Parameters that can be directly passed using a macro instruction call

16

P16

F061306.VSD

Using a basic or Application Instruction, you can read from and write to pointer registers in a macro instruction just like devices passed as parameters. You can also apply a word/long word process, index modification process, and automatic BIN-to-BCD or BCD-to-BIN conversion process to these pointer registers. High speed processing of Application Instructions is not performed, however. More specifically, high speed processing does not apply to MOV, CAL, CMP, or logical operation instructions that use pointer registers as operands in a macro instruction.

TIP
When executing two or more instructions that use pointer registers(P), it is recommended that you first transfer the values of the pointer registers(P) to macro relays(H)/registers(A). Then, execute two or more instructions that use these macro relays(H)/registers(A). This strategy reduces the instruction execution time.

SEE ALSO
For details on basic and application instructions, see Sections 2.1 and 3.1 of the "Sequence CPU Instruction Manual - Instructions" instruction manual (IM34M6P12-03E).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-52
X00502 MOV PARA 1 4 V01 V01 R0001 P04=R0002

M P01=D0001 D0001 EFG123 I0001 Y00301 P02=I0001 (Mnemonic: MCALLEFG123 D0001 I0001 Y00301) P03=Y00301 "EFG123" macro instruction entity (called side) M033 MOV MOV P04 = U01 P01 1 2 + A0001 U01 A0001

Pointer registers in a called-side macro instruction entity (Note) R0002 = U01 D0001

A0001 MRET
F061307.VSD

Note: This register can be used in the called-side macro instruction entity.

Figure 6.39 Example of Using Pointer Registers (P)

CAUTION
If you pass a device accompanied by an index modification device to a macro instruction as a parameter, the instruction receives an already index-modified device. In the example of Figure 6.39, the parameter R0001;V01 equals the device R0002 because V01 = 1. Any index modification in a pointer register (P) applies to a parameter that is passed. In the example of Figure 6.39, the parameter P01;U01 equals the device D0003 because P01 = D0001 and U01 = 2

I Macro Relays (H), Macro Registers (A) and Macro Index Registers (U)
These devices are dedicated to macro instructions. Using a basic or Application Instruction, you can read from and write to a macro relay, macro register and macro index register in a called-side macro instruction entity just like an internal relay (I), data register (D) and index register (V). These devices can be used for called-side macro instruction entities. You can use these devices in your macro instruction without having to be aware which devices are used in the instruction when applying the instruction. Needless to say, the values of these devices are retained.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-53 Structure Pointer Register (Q)


F3SP - S

The Structure Pointer Register is a special register used to pass structure data to structure macro instructions. It is used by structure macro instruction entities (called side). The relationship between the structure pointer register (Q) and structure macro instruction parameters is shown in the figure below.
S ROAD STR1 STR2 Parameter 2 Parameter 1
F061308.VSD

Table 6.19 Relationship between a Structure Pointer Register (Q) and Structure Macro Instruction Parameters
Operand 1 (parameter 1) 2 (parameter 2) Structure pointer register number Q01 Q02

Structure data In a structure macro instruction body (called side) can be read or written using basic and application instructions with the "<structure pointer register number>.<structure member name>" format. Word processing, long-word processing and automatic binary-BCD conversion can be used with structure pointer registers, index modification is not allowed. In addition, high-speed processing of application instructions is also not available. Thus, Move (MOV), Arithmetic Computation (CAL), or logical operation instructions that operates on parameters specified by a structure pointer register (Q) in a structure macro instruction are not processed at high-speed.

TIP
Instead of coding several instructions that use a structure pointer register (Q), you can first transfer the member data to macro relays (H) and macro registers (A) and then code instructions to use these relays and registers instead. In this way, you can shorten the execution time.

SEE ALSO
For details on basic and application instructions, see Sections 2.1 and 3.1 of the "Sequence CPU Instruction Manual - Instructions" instruction manual (IM34M6P12-03E).

SEE ALSO
For details on structures, see "FA-M3 Programming Tool WideField2 Instruction Manual" (IM 34M6Q15-01E).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-54

6.13.4

Nesting Macro Instructions


Nesting macro instructions is to call another macro instruction or an input macro instruction when executing a macro instruction. Calling a structure macro instruction from a structure macro instruction body is not allowed. Calling another macro instruction or an input macro instruction from a structure macro instruction body is allowed but the PARA instruction cannot be used. Nesting macro instruction calls beyond seven levels will cause an instruction processing error. The nesting depth is stored in special register Z106. A value of 0 is stored in the special register Z106 during non-nested execution of a macro instruction.
Table 6.20 Calls between Macros, Input Macros, and Structure Macros
Calling Side Block Block Block Macro Macro Macro Input macro Input macro Input macro Structure macro Structure macro Structure macro
: : :

Called Side Macro Input macro Structure macro Macro Input macro Structure macro Macro Input macro Structure macro Macro Input macro Structure macro

Availability

Call is allowed (PARA instruction can be used) Parameters passed using the PARA instruction are overwritten. Call is not allowed.

CAUTION
Parameters 1 to 3 passed to macro instructions are saved when macro instructions are nested. However, parameters 4 to 16 passed using PARA (parameter) instructions are not saved. If a Parameter (PARA) instruction is executed in a called macro instruction, the relevant parameters are overwritten.

CAUTION
Errors generated in nested macro instructions are reported as errors of the first macro instruction.

SEE ALSO
For details on the Parameter instruction, see Section 3.13.4, "Macro Call (MCALL), Parameter (PARA), Macro Return (MRET), of "Sequence CPU Instruction Manual - Instructions" (IM34M6P12-03E, 3rd Edition).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-55
When nesting macro instructions, you may mistakenly overwrite macro devices, such as relays, registers and index registers, in a called macro instruction and thereby destroy their data. To avoid this problem, check the depth of macro instruction nesting stored in special register Z106 and use macro devices separately for each level of nesting depth (see the example below).
X00501 M NEST1 NEST1 macro instruction entity X00502 U01 0 U01 A01 = = Z106 0 P1 + 1 * 64 D0001 D0002 0

A01 (A001 to A064 can be used) M NEST2 U01 = U01 A01 Z106 P2 * 0 6 4

Data of U01 in NEST2 instruction is destroyed. MRET

NEST2 macro instyruction entity X00503 U01 64 U01 A01 = = Z106 1 P1 + 1 * 64

A65 (A065 to A128 can be used) M NEST3 U01 = U01 A01 Z106 P2 * 0 64

Data of U01 in NEST3 instruction is destroyed. MRET


F0613081.VSD

Figure 6.40 Example of Using Macro Devices Separately when Nesting Macro Instructions

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-56

6.13.5

Handling Macro Instruction Errors


An error occurs when creating a program using a macro instruction tool if: - there are two or more macro instructions of the same name, - a macro instruction specified in an MCALL macro instruction call is not found, or a single macro instruction contains two or more MRET macro return instructions.

An error also occurs and the special relay M201 for instruction processing errors is set to ON if: - an MRET ladder macro instruction return is executed before an MCALL macro instruction call (special register Z022 contains the error code $2501), or - the depth of macro instruction call nesting exceeds 7 levels (special register Z022 contains the error code $2502). An error encountered in a called-side macro instruction entity is viewed by the user as an error in a calling-side macro instruction. Thus, the user can know which parameters were passed to the macro instruction.

CAUTION
An error, except a check-sum memory error, found by self-diagnosis in a called-side macro instruction entity is also viewed by the user as an error that has occurred as the result of executing a calling-side a macro instruction.

It is not possible to determine in which downloaded-type macro instruction a check-sum memory error is found. Therefore, the error is recognized when it is detected, rather than when the macro instruction is executed.
Table 6.21 Error Codes for Macro Instructions
Error Type Instruction processing Error Name Macro instruction error Error Code $2502 $2501 Description Three is o return destination The upper limit of nesting depth, i.e., seven levels, has been exceeded.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-57

6.13.6

Protecting Macro Instructions


You can protect macro instructions from being referenced by someone else to ensure the security of called-side macro instruction entities. This protection is achieved for each macro instruction by entering a password with the WideField2. A password must consist of eight alphanumeric characters, beginning with a letter. The protection information is saved in the management information area of a macro instruction file. You are not allowed to perform macro instruction editing, printing and monitoring for macro instructions under protection unless your password matches.

Tip
Executable program protection and block protection are effective for user-created ladder programs that contain macro instructions. If for example, executable program protection is enabled, any act of working with executable programs, such as downloading, uploading, monitoring or online-editing, becomes impracticable.

6.13.7

Debugging Operation

I Forced-Set/Reset
You can also turn on and off bit devices forcibly in calling-side and called-side macro instructions.

I Partial Operation
Partial operation is not possible with called-side macro instructions.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-58

6.13.8

Input Macro Instructions

F3SP

- S

An Input Macro Instruction is a type of macro instruction that can be used as an input condition, just like the Load or Compare instruction. It can represent complex, reusable input conditions as a single instruction. By calling the Output of Input Macro (NMOUT) instruction internally, an input macro instruction can also output the result of logical operation to its subsequent instruction.

INLET1 = =
F061309.VSD

Macro instruction

Increased reusability and readability

Figure 6.41 Benefit of Input Macro Instructions

How to Use
Creating an Input Macro Instruction
Input macro instructions can be created like ordinary macro instructions. Macro instructions called by the Input Macro Instruction Call (NCALL) instruction are called input macro instructions. Therefore, the same macro instruction entity can be either an input macro instruction (if called by NCALL) or a macro instruction (if called by MCALL).

Calling an Input Macro Instruction


Use the Input Macro Instruction Call (NCALL) instruction.

SEE ALSO
For details on the NCALL instruction, see "Sequence CPU Instruction Manual - Instructions" (IM34M6P12-03E, 3rd Edition).

Where to Code the Input Macro Instruction Call (NCALL) Instruction


You can code the NCALL instruction along with the Load, And, or Or logical operator. You cannot use it in place of an output instruction (at the right end of a ladder rung). To call a macro instruction at the position of an output instruction, use the MCALL instruction instead.

Passing Parameters to an Input Macro Instruction


Use the pointer register (P) to pass parameters, just like with the ordinary macro instructions. The NCALL instruction can contain up to three parameters. To pass more than three parameters, use the Parameter (PARA) instruction. Be careful when using the PARA instruction, because it can be used by both macro and input macro instructions.

SEE ALSO
For details on the pointer register (P), see Section 6.13.3, "Devices Dedicated to Macro Instructions."

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-59
Output of Logical Operation Result to the Power Rail
Specifies the logical operation result of an input macro instruction. The logical operation result to be output to the step following the Input Macro Instruction Call instruction depends on the status of the input parameter of the input macro instruction.
Input Parameter Constant Relay device Register device Logical Operation Output of Input Macro (device status = output) OFF if 0, ON if otherwise OFF if 0, ON If 1 OFF if 0, ON if otherwise

If NMOUT is executed more than once, the last instruction takes precedence. If no NMOUT instruction is executed, the logical operation result of an input macro is OFF.

SEE ALSO
For details on the NMOUT instruction, see "Sequence CPU Instruction Manual - Instructions" (IM34M6P12-03E, 3rd Edition).

CAUTION
NMOUT takes effect only if executed in a macro (input macro) instruction that has been called by NCALL. It is ignored if executed in a macro instruction that has been called by MCALL.

Nesting Input Macros


The macro and input macro instructions when combined may be nested up to 8 levels.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-60

6.13.9 Structure Macro Instructions

F3SP

- S

The Structure Macro Instruction passes a number of parameters collectively in a structure to a macro instruction. By using a structure, it simplifies data passing and improves representation when there are many related parameters.

Passing all data in a structure called MITAKA Ladder block S ROAD S ROAD MITAKA 0 Macro instruction (ROAD) STRCT Q1.Road_Val MOV FUCHUU 0
Q1.Road_Frm D0001 Q1 CITY

I00200 if MITAKA is passed, and I00205 if FUCHUU is passed

Structure object definition MITAKA.Road_Frm MITAKA.Road_To MITAKA.Road_Val


D00100 D00101 I00200 D00102 D00103 I00205

Structure type definition (CITY) Road_Frm Road_To Road_Val


FUCHUU.Road_Frm FUCHUU.Road_To FUCHUU.Road_Val


WORD WORD RELAY


F061310.VSD

Figure 6.42 Benefits of Structure Macro Instructions

SEE ALSO
For details on structures, see "FA-M3 Programming Tool WideField2 Instruction Manual" (IM 34M6Q15-01E).

CAUTION
A structure macro instruction may not call another structure macro instruction. A structure macro instruction may be called only by a block.

CAUTION
If the type of a structure passed using a structure macro instruction is different from the structure type declared by a structure pointer declaration instruction in the called structure macro instruction, the latter structure type is used during execution with no error generated.

CAUTION
Structure macros use P4 to P8.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-61 How to Use


Structure Type Definition
Defines the name and members of a structure type.

Structure Object Definition


Allocates actual registers to the structure data.

Creating Structure Macro Instructions


Structure macro instructions can be created just like ordinary macro instructions. Macro instructions called by the structure Macro Instruction Call (NCALL) instruction are called structure macro instructions.

Structure Type Declaration (STRCT) for Structure Macro Instructions


At the very beginning of a structure macro instruction, you must declare the type of the structure to be passed. One structure type declaration is required if one structure is to be passed. Two structure type declarations are required if two structures are to be passed.

Calling a Structure Macro Instruction


Use the structure Macro Instruction Call (SCALL) instruction.

SEE ALSO
For details on the SCALL instruction, see "Sequence CPU Instruction Manual - Instructions" (IM34M6P12-03E, 3rd Edition).

Passing Structure Data to a Structure Macro Instruction


When passing structure data, refer to the name of the structure on the calling side, and use the structure pointer register (Q) on the called side.

SEE ALSO
For details on the structure pointer registers (Q), see Section 6.13.3, "Devices Dedicated to Macro Instructions."

Nesting structure Macros


A structure macro instruction cannot call another structure macro instruction. A structure macro instruction can call macro and input macro instructions, but cannot use the PARA instruction.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-62

6.14 User Log Management Function


User log management is a function that logs, or keeps record of, errors in a user system, information on the way they occurred, and the condition of system operation, by executing a user log instruction. This function is useful for analyzing faults and understanding the operating conditions of machinery. You can read saved user logs using instructions or WideField2.

I Handling User Logs


For each CPU, you can save a maximum of 64 user logs as 32-character messages classified by their main codes, by executing a user log instruction in a program. As user log information, four data items-the date, time, one-word main code and one-word subcode-are recorded. The user log information storage area is used cyclically. If the maximum recordable number of logs is exceeded, the extra logs are overwritten in chronological order. Use WideField2 or a user log reading instruction to read stored user log information. You can refer to the special register Z105 to find out the number of user logs stored.
Ladder program ULOG D0001 D1000

Stored during instruction execution

User log information storage area Stored by means of overwriting in the order of occurrence Rotarybuffer format

95/09/26 95/09/26

14:10:52 14:21:12

12-05 17-04

F061401.VSD

Figure 6.43 Handling User Logs

CAUTION
In some cases, WideField2 may show two identical logs. This happens when you execute a user log instruction to store a new user log while reading a stored use log using WideField2. To prevent this from occurring, view user logs when you are not executing a user log instruction.

SEE ALSO
For details on the instructions related to user log, see "Sequence CPU Instruction Manual Instructions" (IM34M6P12-03E, 3rd Edition).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-63
TIP
You may assign values in the range -32768 to +32767 to user log main codes. Messages for main codes 1 to 64 can be stored in a CPU module.

TIP
You may also assign values in the range -32768 to +32767 to user log sub codes.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-64

6.15

Sensor Control Function


To enable response requests to be dealt with at speeds of a several hundred microseconds, a small PLC or sensor controller is installed separate from the main PLC. The sensor control function serves as a separately installed small PLC or sensor controller. This function is not affected by the main scan time that tends to lengthen because of the systems advanced functionality or higher performance. Thus, you can scan a program at high speeds and fixed intervals, independent of the main scan time. With the sensor control function, it is possible to run a block of a program at high speeds and fixed intervals (200 s minimum), independent of a regular scan. This function is effective for types of control that require higher machining accuracy.

6.15.1

Schematic Operation Diagram


The sensor control block behaves as shown in Figure 6.44.
Normal scan Input refreshing Sensor control block

Input refreshing Program execution Output refreshing


Wait time before the next fixed-interval scan 200-s minimum fixed interval

Normal program execution

Input refreshing Interruption of execution Program execution Output refreshing


200-s minimum fixed interval

Input refreshing Interruption of execution Program execution Output refreshing Common processing
200-s minimum fixed interval

Input refreshing Program execution Output refreshing


200-s minimum fixed interval

Output refreshing

F061501.VSD

Figure 6.44 Schematic Diagram of Sensor Control Block Operation

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-65

6.15.2 Features
I Features
The sensor control function has the following features.

G High Speed
The minimum interval of block execution is as short as 200 s. The sequence CPU module operates as if it contains another sequence CPU module with the minimum scan time of 200 s. The maximum I/O response delay is only 400 s, i.e., twice the minimum interval of block execution. It is possible to use a process requiring fast I/O responses by isolating it from a regular program. It is possible to use a wide choice of modules, including multifunctional modules, for the input/output of the function.

G Fixed Intervals
The sensor control block is executed at fixed intervals. The sensor control block function works even while instructions in a normal scan are being executed or refreshed, or common processing is in progress.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-66

6.15.3

Specifications and Restrictions

I Specifications
Table 6.23 Specifications of Sensor Control Block
Item Number of sensor control blocks Interval of execution Applicable module Unit of I/O-refreshed devices Maximum number of I/O-refreshed words Applicable instructions Applicable device Maximum program execution time Initial condition at the moment of normal program execution Interrupt timing Interrupt priority Others 1 200 s to 25.0 ms, in 100 s increments Specifications

All types of modules. See the cautionary notes on the next page.
One-word basis, i.e., in units of 16 relays or terminals. 4 to 512. See below. All instructions, except for the Timer, Special Module Highspeed Read (HRD), and Special Module High-speed Write (HWR) instructions

All types of device; common to normal scans


50 s to 24.95 ms (see below) Sensor control block at a stop

For details on writing to relay devices, see Section 6.15.7, "Programming Precautions."

Can be defined as "after completion of instruction execution" or "immediate, during instruction execution"-default Sensor control block has priority (default) or input interrupt has priority. See below. Start, stop or interrupt prohibition by means of instruction or tool.

I Applicable Modules
There is no restriction on the types of applicable module, however, observe the cautionary notes given on the next page.

CAUTION
Cautionary notes on setting the Terminal Usage in the in DIO setup Using the configuration function in WideField2, edit this item to determine whether I/O modules are refreshed by means of the sensor control block or a normal scan. The settings of all devices, including X input relays and Y output relays, are common to normal scans. Configure an input module on a long-word basis in units of 32 relays or terminals, from terminals 1 to 32 or 33 to 64, and an output module on a word basis in units of 16 relays or terminals. Avoid inadvertently configuring the input module on a word basis, such as using terminals 1 to 16 for a normal scan and terminals 17 to 32 for the sensor control block. Otherwise, refreshing based on the sensor control block takes place during the normal scan since input refreshing is performed on a long-word basis. This means X input relays used for the normal scan are refreshed and, therefore, the simultaneity of data before and after this refreshing is not guaranteed. The simultaneity of data is also not guaranteed for X input relays used in the sensor control block.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-67
CAUTION
Relationship between shared refreshing and link refreshing In I/O refreshing based on the sensor control block, shared and extended shared relays (E), shared and extended shared registers (R), link relays (L) and link registers (W) are not refreshed. Instead, these devices are refreshed during common (synchronization) processing in a normal scan.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-68
I Maximum Number of I/O-refreshed Words
The number of words defined using the configuration function as those to be refreshed, is limited by the type of unit-either main unit or subunit-where the module in question is installed, by the time interval of block execution, or by the number of CPU modules including a BASIC CPU module. See Table 6.24 below for details. Calculate the number of words according to the following equation. Number of I/O-refreshed words = (Number of words of I/O modules in main unit to be refreshed) + (Number of F3XH04 modules in main unit to be refreshed that use pulse catch function) + (Number of words of I/O modules in subunit to be refreshed) x 4 (Number of F3XH04 modules in subunit to be refreshed that use pulse catch function) x 4
Table 6.24 Maximum Number of I/O-refreshed Words Handled by Sensor Control Block for each CPU
Execution Interval 200s 300s 400s 500s 1 ms 2 ms 3 ms 4 ms 5 ms 10 ms 20 ms 25 ms Maximum Number of I/O-refreshed Words One CPUs Two CPUs Three CPUs Four CPUs 4 0 0 0 8 4 0 0 12 4 4 0 16 8 4 4 36 16 12 8 76 36 24 16 116 56 36 28 156 76 52 36 196 96 64 48 396 196 132 96 512 396 264 196 512 496 332 248

Example 1: Number of CPU modules installed: 2 Execution interval of sensor control block at CPU 1: 1 ms Sum of CPU-1 input-refreshed and output-refreshed words : Should be kept below 16. Execution interval of sensor control block at CPU 2: 500 s Sum of CPU-2 input-refreshed and output-refreshed words : Should be kept below 8. The maximum number of I/O-refreshed words is proportional to the execution interval. Calculate the maximum number for any execution interval not found in Table 6.24 by referring to the numbers for the execution intervals immediately above and below that maximum number. Example 2: Number of CPU modules installed:1 Execution interval of sensor control block: 600 s Maximum number of I/O-refreshed words: 20 It is not possible to sustain the execution interval of the sensor control block if the maximum number of I/O-refreshed words is exceeded. This may result in a sensor control block scan time-out error. See subsection 6.15.6, Error Handling, for details on operation in the case of this error.
IM 34M6P13-01E 2nd Edition : Oct 1, 2002

6-69
I Maximum Program Execution Time
In the case of the sensor control block, keep the program execution time as short as possible. Otherwise, a program being executed under a normal scan will be interrupted for a longer period of time. Consequently, the time interval of the normal scan becomes longer. Calculate the maximum time of this program execution according to the equation given below. If this maximum time is exceeded, a sensor control block scan time-out error may result because the CPU fails to sustain the execution time of the sensor control block. See subsection 6.15.6, Error Handling, for details on operation in case of this error. Maximum program execution time (s) = (Maximum number of I/O-refreshed words discussed earlier - Number of actually refreshed words) x Number of CPU modules installed x 25 s + 50 s Example 1: Execution interval: 200 s Number of CPU modules installed:1 Execution interval of sensor control block: 600 s Maximum number of I/O-refreshed words: 4 (from Table 6.19) Number of actually refreshed words: 2 Maximum program execution time = (4 - 2) x 1 x 25 + 50 = 100 s The sensor control block, if composed of basic instructions only, is equivalent to a program with the following number of steps. 100/0.09 = 1111 steps = Approximately 1.1 K steps (for F3SP28 and F3SP38 CPU modules) 100/0.035 = 2856 steps = Approximately 2.8 K steps (for F3SP53, F3SP58 and F3SP59 CPU modules) Example 2: Execution interval: 1 ms Number of CPU modules installed:1 Maximum number of I/O-refreshed words: 36 (from Table 6.19) Number of actually refreshed words: 6 Maximum program execution time = (36 - 6) x 1 x 25 + 50 = 800 s The sensor control block, if composed of basic instructions only, is equivalent to a program with the following number of steps. 800/0.09 = 8888 steps = Approximately 8.7 K steps (for F3SP28 and F3SP38 CPU modules) 800/0.035 = 42865 steps = Approximately 41.8 K steps (for F3SP53, F3SP58 and F3SP59 CPU modules)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-70

6.15.4

Function Setup Items


The sensor control function has the following function setup items.
Table 6.25 Function Setup Items of Sensor Control Function
Function Setup Item Execution interval setting Interrupt timing Interrupt priority Activate/Deactivate Disable/Enable On-for-one-scan-at-CB-startup function Execution status Execution time monitor Description Allows the execution interval of the sensor control block to be set by WideField2. Allows the interrupt timing of the sensor control block to be set, by WideField2, to either of the following options. - After completion of instruction execution - Immediate, during instruction execution Allows the order of interrupt priority to be set, by WideField2, between the sensor control block and the input interrupt process. Allows the sensor control block to be activated or deactivated by a dedicated instruction. Prohibits the sensor control block from being executed or cancels the prohibition by a dedicated instruction. Refers to a special relay (M) that remains turned on for one scan when the sensor control block is activated. Reflects the Start or Stop status of the sensor control block in a special relay (M). Stores the processing time of the sensor control block in a special register (Z).

I Execution Interval Setting and Accuracy


Using the configuration function of WideField2, set the execution interval of the sensor control block.
Table 6.26 Execution Interval Setpoints of Sensor Control Block
Item Setting range Configuration Range 200s to 25.0 ms. The setting range from 200s to 900s is only effective for the interrupt timing option of immediate, during instruction execution.

Unit of setpoint 100s

The accuracy of an execution interval is 100 ppm.

I Interrupt Timing
Using the configuration function of WideField2, set the interrupt timing of the sensor control block for a case when a program is being executed. There are two options for the interrupt timing, as shown in Table 6.27.
Table 6.27 Interrupt Timings of Sensor Control Block
Interrupt Timing After completion of instruction execution Immediate, during ladder instruction execution (default) Description The CPU switches to the sensor control block after the completion of instruction execution. It does not, however, switch to the sensor control block during common processing or refreshing. The CPU switches to the sensor control block during ladder instruction execution. It also switches to the sensor control block during common processing or refreshing.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-71
Program execution in normal scan LD OUT LD BMOV Input refreshing Sensor control block

Program execution Next instruction Output refreshing


F061503.VSD

Figure 6.45 Interrupt by Sensor Control Block after Completion of Instruction Execution

Program execution in normal scan LD OUT LD BMOV

Sensor control block

Input refreshing Interrupt of execution Continuation of BMOV instruction Next instruction


F061504.VSD

Program execution Output refreshing

Figure 6.46 Immediate Interrupt by Sensor Control Block during Instruction Execution

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-72
Table 6.28 summarizes differences between these two interrupt timings.
Table 6.28 Differences between Two Interrupt Timings
Item Interrupt by Sensor Control Block after Completion of Instruction Execution Processing time of instruction being executed (Note 1) + Switchover processing time (Note 2), or Synchronization processing time (Note 3) + Common processing time (Note 3) + Input refreshing time (Note 3) + Switchover processing time (Note 2) Guaranteed for each instruction Immediate interrupt by Sensor Control Block during Instruction Execution

Execution delay Simultaneity of data

Switchover processing only (Note 2)

No simultaneity of multiple devices' data

Note 1: See the table of commands in Appendix of the 2nd or later edition of, Sequence CPU Instruction Manual Instructions (IM34M6P12-03E), for details on the instruction processing time. Note 2: 9 to 30 s for F3SP28 and F3SP38 CPU modules and 3 to 10 s for F3SP53, F3SP58 and F3SP59 CPU modules Note 3: See Section 7.1, "Information on Scan Time."

CAUTION
Execution interval setting when the interrupt timing is after completion of instruction execution For interruption by the sensor control block after completion of instruction execution, set the execution interval at 1 ms or longer. In this type of interruption, the CPU does not switch to the sensor control block during common processing or refreshing. Although the common processing time or refreshing time varies depending on the time interval of synchronization processing, such as shared refreshing or link refreshing, it must be at least 1 ms. Otherwise, It is not possible to sustain the execution interval of the sensor control block. This may result in a sensor control block scan time-out error. Debug operation when interrupt is set to occur after completion of instruction execution: If the timing of interrupts is set to "After Instruction," the sensor scan time exceeded error may occur when switching from Run to Debug mode or from Debug to Run mode, or when canceling a forced set/reset in Debug mode.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-73
CAUTION
Simultaneity of data when the interrupt timing is immediate, during instruction execution When interruption by the sensor control block is immediate, during instruction execution, there is no simultaneity of multiple devices data. For example, consider the case in Figure 6.46 where the sensor control block is executed when a BMOV block transfer instruction is being executed in a normal scan. The data in the source of block transfer is rewritten before and after the execution of the sensor control block or data being blocktransferred may be read in the sensor control block. The time the simultaneity of data is required is when multiple devices data is exchanged between a normal-scan program and an input interrupt program by using a BMOV block transfer instruction, a long-word instruction containing a floating point, or two or more instructions. If the simultaneity of data is required in the case of immediate interruption by the sensor control block during instruction execution, follow either of the two instructions given below. 1. Use CBD (Sensor Block Disable) and CBE (Sensor Block Enable) instructions to prevent the sensor control block from being executed when exchanging data of multiple devices. 2. Use an application program to carry out flag control using relays between a normal-scan program and the sensor control block.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-74
I Interrupt Priority
Using the configuration function of WideField2, determine priority when the timing of interrupt from an input module coincides with the interrupt timing of the sensor control block. Table 6.29 shows the two options of interrupt priority.
Table 6.29 Options of Interrupt Priority and Their Functionality
Interrupt Priority Functionality When an interrupt from an input When the time of executing the module occurs during execution of sensor control block arrives during the sensor control block input interrupt processing Aborts the interrupt once and resumes Executes the interrupt process after the process after executing the sensor executing the sensor control block. control block. Aborts the execution of the sensor control block once and resumes the Executes the sensor control block after execution after executing the input executing the input interrupt process. interrupt process.

Sensor control block first Input interrupt process first

TIP
The sequence CPU follows the rules of execution timing (after completion of instruction execution or immediate, during instruction execution) discussed above, even when the execution of the sensor control block or input interrupt process is aborted due to the interrupt priority.

I Activating/Deactivating Sensor Control Block


You can activate the sensor control block using a CBACT (Control Block Activate) instruction, or stop the block using a CBINA (Control Block Deactivate) instruction. At the start of operation, the sensor control block defaults to the Stop status. To activate the sensor control block, execute a CBACT (Sensor Block Activate) instruction in a normal-scan program. An initial startup of the sensor control block takes place within 100 _s after the execution of a CBACT enable instruction.
Table 6.30 Instructions to Enable/Disable Sensor Control Block
Instruction CBACT instruction CBINA instruction Description Enables the sensor control block. Disables the sensor control block.

SEE ALSO
For details on the instructions, see "Sequence CPU Instruction Manual - Instructions" (IM34M6P12-03E), edition 3 or later.

TIP
When the sensor control block stops, the CPU holds or resets the data of Y output relays used or refreshed by the sensor control block, according to the setting of the configuration item Hold/reset output in case of program stop. When the sensor control block is enabled, the relays are always set to the Hold option.

TIP
The initialization processing of timers, counters and the destinations of OUT instructions does not apply to the sensor control block enabled or disabled by ACT/INACT instructions.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-75
I Enabling/Disabling Sensor Control Block
You can temporarily disable the sensor control block using a CBD (Control Block Disable) instruction or enable the sensor control block using a CBE (Control Block Enable) instruction. The CPU does not execute the sensor control block if disabled, until it is enabled. The CPU immediately begins executing the block as soon as it is enabled.
Table 6.31 Instructions to Disable and Enable Execution of the Sensor Control Block
Instruction CBD Instruction CBE Instruction Description Disables execution of the sensor control block. Enables execution of the sensor control block.

SEE ALSO
For details on the instructions, see "Sequence CPU Instruction Manual - Instructions" (IM34M6P1203E, 3rd Edition).

CAUTION
If the interval of execution disable is too long for the CPU to be able to execute the sensor control block at fixed intervals, a sensor control block scan time-out error will result. Consequently, the CPU stops executing the sensor control block. See subsection 6.15.6, Error Handling, for more information.

I On-for-one-scan-at-CB-startup Function
This function causes a special relay (M) to remain turned on for one scan-during the first execution of the sensor control block, when the sensor control block is activated.
Table 6.32 Special Relay for One Scan at the Startup of Sensor Control Block
No. M097 Name Status Description Remains turned on for one scan during the first execution of the sensor control block when the sensor control block is activated. ON: When the sensor On-for-one-scancontrol block is at-CB-startup relay activated OFF: Other cases

TIP
The on-for-one-scan-at-CB-startup relay turns on when a CBACT (Control Block Activate) instruction is executed. It then turns off at the end of the first execution of the sensor control block.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-76
I Execution Status
The CPU stores in a special relay (M), the status of whether the sensor control block is enabled or disabled.
Table 6.33 Special Relay for Execution Status of Sensor Control Block
No. M137 Name CB-execution-status relay Status ON: Enabled OFF: Disabled Description Indicates the operating status of the sensor control block.

TIP
The status of the sensor control block is updated when a CBACT (control block activate) instruction is executed, or during normal-scan input refreshing after error detection when a CBINA (control block deactivate) instruction is executed.

I Execution Time Monitoring


This function stores the time taken from when input refreshing for the sensor control block is started, followed by program execution, to when output refreshing is completed in a special register (Z). The time indicates how many times the CPU has executed the sensor control block during the preset execution interval.
Input refreshing for sensor control block Execution interval Program execution for sensor control block Output refreshing for sensor control block Wait time before the next fixed-interval scan Input refreshing for sensor control block Program execution for sensor control block Output refreshing for sensor control block Execution time

F061505.VSD

Figure 6.47 Schematic Diagram Showing Execution Time of Sensor Control Block

Table 6.34 Special Registers (Z) for Execution Time of Sensor Control Block
No. Z109 Z111 Name CB-execution-time register Maximum-CB-execution-time register Description Indicates the time (in units of 10 s) taken from when input refreshing for the sensor control block is started, followed by program execution, to when output refreshing is completed. Indicates the maximum time (in units of 10 s) taken to execute the sensor control block.

TIP
The execution time of the sensor control block is updated at each normal-scan input refreshing process.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-77

6.15.5 Procedures for Using Sensor Control Function


Table 6.35 summarizes procedures for using the sensor control function.
Table 6.35 Procedures for Using Sensor Control Function
Procedure Setup/Edit Item Setting of I/O-refreshed words of sensor control block Execution interval setting 1 Interrupt timing setting Execution priority setting Creation of normal-scan programs Creation of sensor control programs 2 Registration of sensor control block Reference to Setup Items Discussed Earlier Maximum number of I/O-refreshed words WideField2 configuration Execution interval DIO setup and interrupt setting setup Switchover timing Execution priority Enabling/disabling sensor control block WideField2 block editing Creation/WideField2 WideField2 configuration definition

TIP
You can use the sensor control block, irrespective of whether the setting of the option of the configuration item method of program execution, is Execution of all blocks or Execution of specified blocks.

6.15.6 Error Handling


Table 6.36 summarizes the modes of errors found when the sensor control function is in use.
Table 6.36 Errors Found during Use of Sensor Control Function
Type of Error Description The CPU fails to sustain the execution interval because it is Sensor control block scan timeexceeded by the sum of the fixed-interval I/O refreshing time and out error the execution time of sensor control programs. The CPU falls short of time to execute a regular program because Scan timeout the execution time of sensor control programs is too long. Thus, the normal scan time exceeds the scan time monitoring time. An I/O module has failed during fixed-interval I/O refreshing in the I/O module failure sensor control block.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-78
CAUTION
If I/O module failures are found during I/O refreshing in the sensor control block, the CPU only informs the first-found failure by means of an alarm indicator.

Table 6.37 Sensor-control-block-scan-timeout-error Special Relay


Item No. M212 Name CB-scan-timeout Self-diagnosis Status Description Status Indicates that the CPU cannot ON: Abnormal sustain the execution interval of OFF: Normal the sensor control block.

Table 6.38 Actions When Error Is Encountered in Sensor Control Block


Type of Error Encountered Action in Case of Error Sensor Control Block Effect on Normal Scans

Sensor control block scan timeout (Special relay M212 turns on.)

Other errors

Run or Stop status depending on the option of the configuration item "Operation Stops in case of sensor control block scan timeout error" For errors with a configuration item defining operation when there is an error, the sensor control block either runs or stops depending on the item's option. The block stops if there is no such configuration item.

TIP
If an error is encountered in the sensor control block, the block number for which the error is found and which is stored in a special register is the last block number of a regular program with an increment of 1. Table 6.39 Action of Sensor Control Block when an Error Is Found in Normal Scan
Type of Error All types of error Action For errors with a configuration item defining operation when there is an error, the sensor control block either runs or stops depending on the item's option. The block stops if there is no such configuration item.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-79

6.15.7

Programming Precautions
Instruction TIM Corrective Actions Enable/disable timers in a regular block. Reference to timer relays is possible, however.

I Instructions Not Applicable to Sensor Control Block

Special Module High-speed Use the Special Module Read (READ) instruction instead. Read (HRD) Special Module High-speed Use the Special Module Write (WRITE) instruction instead. Write (HWR)

I Precautions when the interrupt timing is immediate, during instruction execution


G Precautions when outputting data to relays
If in the sensor control block you have already output data to any of the relays numbered 1 to 16 using an OUT, SET RST, DIFU or DIFD instruction, do not output data to any of these relays in a normal-scan program as well. Otherwise, the output instruction may not be processed correctly. This precaution is also true with other groups of 16 relays numbered 17 to 32, 33 to 48, 49 to 64, and so on. Do not output data to any relay in each of these groups both in the sensor control block and in a normal-scan program.
16n+16 16n+1

Sensor control block

Normal program steps

Example: If a sensor control block controls I00032, the normal program steps may not control I00017 to I00031. Figure 6.48 When Outputting to Relays

F061506.VSD

G Simultaneity of multiple devices data


There is no simultaneity of data if multiple devices are handled as a group. For example, consider the case in Figure 6.46 where the sensor control block is executed when a BMOV block transfer instruction is being executed in a normal scan. The data in the source of block transfer is rewritten before and after the execution of the sensor control block or data being block-transferred may be read in the sensor control block. The time the simultaneity of data is required is when multiple devices data is exchanged between a normal-scan program and an input interrupt program by using a BMOV block transfer instruction, a long-word instruction containing a floating point, or two or more instructions. If the simultaneity of data is required, follow either of the two instructions given below. 1. Use CBD (Control Block Disable) and CBE (Control Block Enable) instructions to prevent the sensor control block from being executed when exchanging data of multiple devices. 2. Use an application program to carry out flag control using relays between a regular block and the sensor control block.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-80
G Data simultaneity of devices to be refreshed
It becomes impossible to sustain the simultaneity of data if, in the sensor control block, an access is made to I/O relays refreshed in a regular block among other I/O relays, or to shared/extended shared relays (E), shared/extended shared registers (R), link relays (L), or link registers (W). The sensor control block is executed during a normal-scan input and output refreshing even when the CPU is performing common processing. If you read any of the abovementioned devices in the sensor control block, a data value being refreshed may be read. Likewise, if you write to the device, the data value being refreshed may be rewritten. Consequently, the CPU may fail to sustain the simultaneity of data. To prevent the sensor control block from being executed during normal-scan input refreshing, output refreshing or common processing, execute a CBD instruction for disabling the block at the end of a regular program and execute a CBE instruction for enabling the block at the beginning of the program.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

6-81

6.16 Partial Download Function

F3SP

- S

The partial download function allows only specified blocks/macros to be downloaded to a CPU overwriting the corresponding blocks/macros of a program that has been downloaded earlier. This reduces downloading time and improves debugging efficiency, especially in largescale program development by a group of developers. This function is available only in STOP mode. It allows multiple blocks or macro instructions to be specified. Addition or deletion of block/macro instructions that are downloaded using the partial download function are not allowed.

Personal computer Downloading only blocks 2 and 4 from personal computer to CPU and hence replacing only blocks 2 and 4 in the CPU. Block 1 Function 1 Block 2 Function 2' Block 3 Function 3 Block 4 Function 4'
F061601.VSD

Executable program Block 1 Function 1 Block 2 Function 2 Block 3 Function 3 Block 4 Function 4

Figure 6.49 Partial Download Function

Programmer A Programmer B

Programmer A partially downloads block 4 and debugs them. Programmer B partially downloads block 2 and debugs them. Block 1 Function 1 Block 2 Function 2 Block 3 Function 3 Block 4 Function 4

Executable program Block 1 Function 1 Block 2 Function 2 Block 3 Function 3 Block 4 Function 4

F061602.VSD

Figure 6.50 Partial Download Function Used by Multiple Programmers

IM 34M6P13-01E

2nd Edition : Oct. 1, 2002

6-82
CAUTION
If an error occurs at the time of partial downloading, the step count of the error block becomes 0. If you then upload this defective program to a personal computer, the step count for the corresponding block on the personal computer will also be 0. If you have to upload such a program, save it under a different project name.

CAUTION
At the completion of partial downloading, program checking and optimization are performed and this may take some time.

IM 34M6P13-01E

2nd Edition : Oct. 1, 2002

6-83

6.17 Function for Storing Comments to CPU

F3SP

- S

You can store circuit comments and subcomments to the CPU module. Storing comments in the CPU module allows you to display them during circuit monitoring even if there is no project.

TIP
This function can only store circuit comments and subcomments. To store I/O comments, use the function for storing tag name definitions to CPU.

6.17.1 Performing Setup to Download Comments


You can select whether to store (download) circuit comments and subcomments to a CPU module but you cannot select to store only circuit comments, or only subcomments. In WideField2, setup for downloading comments has to be performed in two places: in the block properties setup and when you execute the download function. Firstly, specify to download comments in the block properties setup for each relevant block (macro instruction). Then, turn on the download comments checkbox when you execute the download program function. Turning on this checkbox downloads comments to the CPU module according to the block properties setup. Turning off the download comments checkbox when you execute the download program function will not download comments irrespective of the block properties setup.

SEE ALSO
For details on block properties and program downloading, see "FA-M3 Programming Tool WideField2 Instruction Manual" (IM 34M6Q15-01E).

CAUTION
Note that if you turn off the checkbox for storing comments to the CPU when you execute the download program function, comments will not be downloaded to the CPU module regardless of the block properties setup.

IM 34M6P13-01E

2nd Edition : Oct. 1, 2002

6-84

6.17.2 Number of Steps Needed for Comments


Like program steps, circuit comments/subcomments also takes up program area. Thus, how much of the program area is consumed in terms of step count also depends on whether comments are downloaded to a CPU module.

Calculating the Step Count of Comments


G If comments are downloaded:
The step count of a circuit comment or a circuit subcomment is the sum of one comment offset and step count of the character string, as given below. Step count of a comment = comment offset (1 step) + step count of the character string The step count of the character string is calculated as follows: Sum the step counts of all characters in a character string, using 0.25 steps for each single-byte character and 0.5 steps for each double-byte character, and round up to the nearest integer.

TIP
- Example: Assume that a comment is a character string consisting of four single-byte character and five double-byte characters. Summing the step counts of individual characters yields: 4 0.25 (for single-byte characters) 5 0.5 (for double-byte characters) = 3.5 (steps) Rounding up to the nearest integer yields: Step count of the character string = 4 (steps) Adding 1 step for comment offset: Step count of the comment = 4 1 = 5 (steps)

G If no comments are downloaded:


One step of program area is consumed for each comment (as comment offset).

CAUTION
One step of comment offset is added for each comment to the step count for a program even if the comments are not downloaded.

Checking the Program Step Count (including Comments)


The step count of a block (or macro instruction) containing comments is displayed on the status bar when the block is opened. The displayed step count includes the step counts of comments and tag names specified to be downloaded to the CPU module in the block properties window. If you select to only download the program, the displayed step count includes only the step count of the program.

IM 34M6P13-01E

2nd Edition : Oct. 1, 2002

6-85

6.17.3 Online Editing of Comments


If circuit comments/subcomments are stored in a CPU module, you can edit or delete them online but you cannot add new comments online.

CAUTION
If you have added circuit comments or subcomments using offline program editing, you should download the circuit comments and subcomments to the CPU module again.

IM 34M6P13-01E

2nd Edition : Oct. 1, 2002

6-86

6.18 Function for Storing Tag Name Definitions to CPU

F3SP

- S

This function stores common, block, and macro tag name definitions along with a program to either the program memory of a sequence CPU module or the ROM pack. If tag name definitions are to be stored in the program memory of a sequence CPU module, the sum of the program and tag name definition step counts must be within the capacity of the program. If tag name definitions are to be stored in the ROM pack, the sum of the program and tag name definition step counts must be within the capacity of the ROM pack.
Table 6.40 Program Capacity for Storing Tag Name Definitions
CPU Module F3SP28-3S F3SP53-4S F3SP38-6S F3SP58-6S F3SP59-7S Where to Store CPU memory RK33-0N RK73-0N CPU memory RK33-0N RK73-0N CPU memory RK33-0N RK73-0N RK93-0N CPU memory RK33-0N RK73-0N RK93-0N Program Only 30K steps 56K steps 120K steps 56K steps 120K steps 120K steps 254K steps 56K steps 120K steps 254K steps Program plus Tag Name Definitions 30K steps 56K steps 120K steps 56K steps 56K steps 120K steps 120K steps 56K steps 120K steps 360K steps 360K steps 56K steps 120K steps 360K steps

For the step count of tag name definitions, check the project properties, the block tag name definition properties for each block, or the macro tag name definition properties for each macro instruction. You can separately specify whether to download common, block, and macro tag name definitions using the project properties, the block tag name definition properties for each block, or the macro tag name definition properties for each macro instruction. In addition, at the time you execute the download program function, you can choose to disable the downloading of tag name definitions, regardless of the properties setup. If you specify not to download tag name definitions when you execute the downloading program function, any tag name definitions previously downloaded will be erased after the download. If you edit tag name definitions online, the tag name definition files on the personal computer will be updated but not those in the program memory of the CPU module. If changes are made to the tag name definitions, download them to the CPU module again.

TIP
For better programming efficiency, we recommend that you maintain the tag name definitions on the personal computer without storing them in the CPU module during debugging and program development, and download the tag name definitions to the CPU module after the programs are debugged.

IM 34M6P13-01E

2nd Edition : Oct. 1, 2002

6-87

6.19 Structures

F3SP

- S

A structure represents a group of data under a unified name. It improves device representation and program readability. The instructions related to structures are:
- Structure Move (STMOV) - Structure Pointer Declaration (STRCT) - Structure Macro Instruction Call (SCALL)

SEE ALSO
For details on structures, see "FA-M3 Programming Tool WideField2 Instruction Manual" (IM 34M6Q15-01E).

SEE ALSO
For details on the instructions, see "Sequence CPU Instruction Manual - Instructions" (IM34M6P12-03E, 3rd Edition or later).

IM 34M6P13-01E

2nd Edition : Oct. 1, 2002

Blank Page

7-1

7.

I/O Response Time Based on Scan Time


This chapter discusses examples of calculating the scan time and I/O response time. It also explains such parameters as instruction execution time.

7.1

Information on Scan Time


As discussed earlier in Chapter 3, the sequence CPU module is designed so that two systems of processes, i.e., a system of control-related processes and a system of peripheral processes, run concurrently and independently. For this reason, the system of control-related processes whose main purpose is to execute programs and controlrelated processes is not affected by the system of peripheral processes whose purpose is to support communication and WideField2. Thus, the system of control-related processes can run at extremely high speeds. Under normal conditions, the scan time of the sequence CPU module is equivalent to the time taken by the system of controlrelated processes. The following paragraphs explain the processing tasks and time of each of these systems.

G System of Control-related Processes


The latest, minimum and maximum of scan times taken by the system of control-related processes are stored in special registers Z001 to Z003 in that order.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

7-2
Table 7.1 Scan Time of System of Control-related Processes
Item
Common processing Program execution Output refreshing

Processing Task
Self-diagnosis Executes ladder programs. The scan time is calculated sing the program execution time or output refreshing time, whichever is greater. Writes the contents of Y output relays to an output module. Updates the contents of shared/extended shared relays (E) and shared/extended shared registers (R) when an add-on CPU is installed and shared refreshing is set as a controlrelated process. In a single refreshing cycle, this task updates the contents of shared/extended shared relays (E) or shared/extended shared registers (R) included in the configuration setting, for each CPU. Not performed if no add-on CPU module is installed or shared refreshing is set as a peripheral process. Write the contents of input modules to a CPU input relays (X). Fixed at 0.2 ms

Processing Time

The scan time is the sum of the execution times of basic and advanced instructions. It varies depending on the execution time of each instruction word. See Section 7.5, "Instruction Execution Time," for more information. 12 s number of modules calculated on a 16-points basis*

Shared refreshing

When an add-on CPU module is installed and shared refreshing is set as a controlrelated process: 0.003T(number of relays set in the sequence CPU module for refreshing /32+number of registers set in the sequence CPU module for refreshing/2)+0.10 ms, if the sequence CPU module for which the devices are refreshed is F3SP28, F3SP38, F3SP53, F3SP58 or F3SP59. 0.014T(number of relays set in the sequence CPU module for refreshing/32+number of registers set in the sequence CPU module for refreshing/2)+0.10 ms, if the sequence CPU for which the devices are refreshed is other than F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59.

0.00ms

Input refreshing

6 s number of modules calculated on a 16- points basis* - When output relays (Y) are used: 8 s number of modules calculated on a 16-points basis* - When FA link modules are used: 0.003T(number of relays used in FA link for refreshing/16+number of registers used in FA link for refreshing)+0.05 ms. - When an add-on CPU module is installed and shared refreshing is set as a control-related process: 0.002x (number of relays set in local CPU/32+number of registers set in local CPU/20)+0.05 ms. - When an add-on CPU module is installed and shared refreshing is set as a peripheral process: 0.002x (number of relays set in CPU for refreshing/32+number of relays set in local CPU/32+number of registers set in CPU for refreshing/2+number of registers set in local CPU/20)+0.05 ms. Minimum peripheral processing time (0.2 ms if not yet configured) or sum of program execution time + output refreshing time, whichever is greater.

Ensures synchronization and the simultaneity of data for operation- and control-related Synchronization processes between the processing system of control-related processes and the system of peripheral processes.

Peripheral processing

Performs peripheral processes.

* Relationship between Types of I/O Module and Number of Modules Calculated on a 16-points Basis
Type of I/O Module 4-point I/O relay 8-point I/O relay 14-point I/O relay 16-point I/O relay 32-point I/O relay 64-point I/O relay Number of Modules Calculated on a 16-device Basis 1 1 1 1 2 4

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

7-3
G System of Peripheral Processes
The latest, maximum and minimum of scan times taken by the system of peripheral processes are stored in special registers Z007 to Z009 in that order.
Table 7.2 Scan Time of System of Peripheral Processes
Item Processing Task Processing Time
Updates the contents of shared/extended shared relays (E) and shared/extended shared registers (R) when an add-on CPU module is installed and shared refreshing is set as a peripheral process. In a single refreshing cycle, this task Shared updates the contents of refreshing shared/extended shared relays (E) or shared/extended shared registers (R) included in the configuration setting, for each CPU. Not performed if no add-on CPU module is installed or shared refreshing is set as a peripheral process. Updates the contents of link relays and registers when an FA link FA link module is installed. Link refreshing Not performed if no FA link module is installed. Processes commands input from the WideField2 connected Tool service to the sequence CPU module. Executes one command per service. Processes commands input from a personal computer link Link service module. Executes one command per service. Processes commands input from a remote CPU module. CPU service Executes one command per service.

When an add-on CPU module is installed and shared refreshing is set as a peripheral process: 0.003x (number of relays set in CPU for refreshing/32+number of registers set in CPU for refreshing/2)+0.10 ms, if the CPU modules for which the devices are refreshed is F3SP28, F3SP38, F3SP53, F3SP58 or F3SP59. 0.014x (number of relays set in CPU for refreshing/32+number of registers set in CPU for refreshing/2)+0.10 ms, if the CPU modules for which the devices are refreshed is other than F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59..

0.00ms When an FA link module is installed: 0.015x (number of relays used in FA link for refreshing/16+number of registers used in FA link for refreshing)+0.06 ms 0.00ms

Varies with the type command.

Varies with the type command.

Varies with the type command.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

7-4

7.2

Setting Scan Time Monitoring Time


This configuration item sets the scan time monitoring time. You can set the time within the range from 10 ms to 200 ms, in 10 ms increments. By default, the time is set at 200 ms.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

7-5

7.3

Examples of Calculating the Scan Time


G When the CPU is F3SP28 or F3SP38
Module configuration User program : Four 32-point input modules : Four 32-point output modules : 5K steps consisting of LD and OUT instructions only, where the average execution time of these instructions is assumed to be 0.09 s

F 3 P U 2 0

F 3 S P 2 8
32-point input modules 32-point output modules F070301.VSD

Figure 7.1 Module Configuration of F3SP28 or F3SP38 Sequence CPU Table 7.3 Scan Time of F3SP28 or F3SP38 Sequence CPU
Item Common processing Program execution Calculation Fixed 0.2ms Processing Time 0.2ms 0.5ms 0.1ms* 0.00ms 0.05ms 0.06ms 0.2ms* 0.8ms

0.09s5120 = 461s Number of modules calculated on a Output refreshing 16-points basis: 24 = 8 12s8 = 96s When no add-on CPU module is Shared refreshing installed: 0.00 ms Number of modules calculated on a Input refreshing 16-points basis: 24 = 8 8s8 = 64s Number of modules calculated on a Synchronization 16-points basis: 24 = 8 Processing 8s8 = 64s Minimum peripheral processing Peripheral processing time, if not yet defined: 0.2 ms Scan time, which is the sum of all time spans listed above

* The output refreshing time and the minimum peripheral processing time are excluded from scan time calculation because the sum of these time spans is smaller than the program execution time.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

7-6
G When the CPU Is F3SP53, F3SP58 or F3SP59
Module configuration User program : Four 32-point input modules : Four 32-point output modules : 20K steps consisting of LD and OUT instructions only, where the average execution time of these instructions is assumed to be 0.035 s

F 3 P U 2 0

F 3 S P 5 8
32-point input modules 32-point output modules F070302.VSD

Figure 7.2 Module Configuration of F3SP53, F3SP58 or F3SP59 Sequence CPUs Table 7.4 Scan Time of F3SP53, F3SP58 or F3SP59 Sequence CPU
Item Common processing Program execution Calculation Fixed at 0.2ms. Processing Time 0.2ms 0.5ms 0.1ms* 0.00ms 0.05ms 0.06ms 0.2ms* 1.0ms

0.035s20480 = 717s Number of modules calculated on a Output refreshing 16-points basis: 24 = 8 12s8 = 96s When no add-on CPU module is Shared refreshing installed: 0.00ms Number of modules calculated on a Input refreshing 16-points basis: 24 = 8 6s8 = 48s Number of modules calculated on a Synchronization 16-points basis: 24 = 8 processing 8s8 = 64s Minimum peripheral processing Peripheral processing time, if not yet defined: 0.2ms Scan time, which is the sum of all time spans listed above

* The output refreshing time and the minimum peripheral processing time are excluded from scan time calculation because the sum of these time spans is smaller than the program execution time.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

7-7

7.4

Examples of Calculating the I/O Response Time


G Calculation of the minimum I/O response time
Input response time: Output response time: 16 ms 1 ms

Scan time: 2 ms Minimum I/O response time = Input response time + Scan time + Output response time = 16 ms + 2 ms + 1 ms = 19 ms
X00502 Y00602

Input refreshing Instruction execution Instruction execution

Output refreshing Input X00502 One scan

Output

Y00602
F070401.VSD

Figure 7.3 Minimum I/O Response Time

G Calculation of the maximum I/O response time


Input response time: 16 ms Output response time: 1 ms Scan time: 2 ms Maximum I/O response time = Input response time + (Scan time x 2) + Output response time = 16 ms + (2 x 2) ms + 1 ms = 21 ms
X00502 Y00602

Input refreshing Instruction execution Instruction execution

Input X00502 One scan

Output refreshing One scan Y00602

Output

F070402.VSD

Figure 7.4 Maximum I/O Response Time

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

7-8
TIP
The I/O response time refers to the total time taken to execute instructions from the external input device and the time taken to turn on the eternal output equipment.

TIP
Input response time refers to the time taken to load external input tag name using the input refreshing process.

TIP
Output response time refers to the time taken to reflect the result of instruction execution in the external output device using the output refreshing process.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

7-9

7.5

Instruction Execution Time


SEE ALSO
Table of instruction words in the appendix of the 3rd or later edition of Sequence CPU Instruction Manual - Instructions (IM34M6P12-03E), for details on the execution time of each instruction.

The instruction execution time varies slightly depending on the contents of the input parameter or output parameter devices or the number of devices included in data transfer. The execution time lengths listed in the Table of Instruction Words are typical. Use these values of the instruction execution time just for reference purposes only when calculating the scan time. The instruction execution time decreases or increases in length, as shown in Table 7.5 below, depending on the conditions under which an instruction is executed. Use values of T in the Table of Instruction Words to figure out guidelines of the scan time according to the formulas given in Table 7.5.
Table 7.5 Calculation of Instruction Execution Time
Instruction Execution Time (s) F3SP53 F3SP28 F3SP58 F3SP38 F3SP59 T+0.18 T+0.07 T+2.5N1 T+3.5N1 T+3.5N2 T+4.5N2 T+1.0N3 T+2.0N4 T+1.0N1 T+1.4N1 T+1.4N2 T+1.8N2 T+0.4N3 T+0.8N4

Execution Conditions

Differential type instruction Relay (BIN format) X and Y I/O relays defined in BCD format Index modification
T N1 N2 N3

When executed When not executed 16 bits 32 bits 16 bits 32 bits Basic instruction Advance instruction

: Instruction execution time in Table of Instruction Words. : Number of relay devices : Number of relay devices defined in BCD format : Number of index-modified relay devices

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

7-10
I Examples of Calculation
The following paragraphs give examples of calculating the instruction execution time. For information on the execution time of an MOV instruction, see Table of Instruction Words in Appendix of the 3rd or later editions of the Sequence CPU Instruction Manual Instructions (IM34M6P12-03E). (1) Differential Type Instructions

MOV

D0001

D0002

0.18+0.18=0.36 s (for F3SP28 and F3SP38 sequence CPUs) 0.07+0.07=0.146 ms (for F3SP53, F3SP58 and F3SP59 sequence CPUs)
F070501.VSD

(2) Relays (BIN Format) Use any execution time from the Table of Instruction Words in parentheses ( ).

MOV

I0002

D0001

Number of relay devices: N1 = 1

3.2+2.5=5.7 s (for F3SP28 and F3SP38 sequence CPUs) 1.2+1.0=2.2 s (for F3SP53, F3SP58 and F3SP59 sequence CPUs)

F070502.VSD

(3) X and Y I/O Relays Defined in BCD Format Use any execution time from the Table of Instruction Words in parentheses ( ).
Number of relay device defined in BCD format: N2 = 1 3.2+3.5=6.7s (F3SP28 and F3SP38 sequence CPUs) 1.2+1.4=2.6s (F3SP53, F3SP58 and F3SP59 sequence CPUs)
MOV D0001 Y00301

F070503.VSD

(4) Index Modification 1. Basic Instructions


I0001 Number of relay devices defined in BCD format: N3 = 1

0.09+1.0=1.09ms (F3SP28 and F3SP38 sequence CPUs) 0.035+0.4=0.435ms (F3SP53, F3SP58 and F3SP59 sequence CPUs)

F070504.VSD

2.

Application Instructions Use any execution time from the Table of Instruction Words in parentheses ( ).
V01 MOV D0001 V02 D0002

Number of index-modified relay devices:N4 = 2

3.2+2.0 X 2=7.2s (F3SP28, F3SP38 sequence CPUs) 1.2+0.8 X 2=2.8s (F3SP53, F3SP58 and F3SP59 sequence CPUs)

F070505.VSD

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-1

8.
8.1

RAS Features
This chapter describes the RAS features of the sequence CPU module, such as the self-diagnosis and error logging functions that work if the module fails.

Self-diagnosis
The sequence CPU performs self-diagnosis on its device memory, instruction codes, and so on when the power is turned on or a program is being executed. The results of self-diagnosis are reflected in predetermined special relays (M) and registers (Z). If any failure is found during self-diagnosis, the CPU module updates the mode statuses of LED indicators and stops executing programs depending on the failure mode.
Table 8.1 Shows how the severity of failure is classified by type and mode.
Action of Output Module Output *2 F3YD64-1F modules and with 64 F3WD64- F Between Between output output FAIL1 points, FAIL2 modules and COM and COM except with 32 or F3YD64-1F less output and points F3WD64- F Default: Nullified RESET setpoint Shorted Open Can be set in The status is 16 points always increments. HOLD. FAIL Signal Contact Output

Severity of Failure

LED Indicator Status

Failure Condition

Failure Mode

Major failure

The green RDY lamp goes out.

The key hardware is disabled.

CPU failure Memory crash

The red Moderate ERR lamp failure comes on.

Minor failure

The yellow ALM lamp comes on.

- Program error - I/O collation failure*1 - I/O module failure*1 Memory failure - PU failure Instruction error*1 - Scan time-out*1 Startup failure The user - Detection of invalid program cannot Instruction be started or - Excess number of I/O run any further. points - ROM pack failure - Subroutine error*1 - Interrupt error*1 - Failure in subunit transmission line*1 - Sensor control scan time-out error*1 - Momentary power failure The program is - CPU-to-CPU abnormal, communication failure though it can - Switchover in subunit still be run. transmission line

Shorted

Open

Default: RESET Can be set in 16 points increments.

Default: RESET Can be set in 16 points increments.

Open

Shorted

Continued operation

Continued operation

* 1: Either the minor or moderate failure can be selected as the failure level for this item using the configuration function * 2: Include the F3WD64 module and advanced modules that contain output relays.

For some of the failure modes, you can select the Stop or Run option to determine whether to stop or continue program execution if any of these failures occur. This selection can be made using the configuration function. This configuration item defaults to the Stop option for a moderate failure and to the Continue option for a minor failure. Moderate failure modes set to the Continue option are treated as minor failure modes, while minor failure modes set to the Stop option are treated as moderate failure modes.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-2
SEE ALSO
The fail signal contact indicates the error state to the external environment when an error occurs.

CAUTION
If you want the contacts of an output module to be held in case of a major or moderate failure in the sequence CPU module, set the Output to be latched in case of CPU stop option of the configuration function to HOLD. Note that there is no difference in the module action due to a difference in the type of output module.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-3
Table 8.2 Details on Self-diagnosis (1 of 6)
Stored Error Code Special Special Registers Relay that Store that Error Turns ON Codes, Etc. Nonfatal Startup error M193 Z017 to Z019

Failure Mode

Failure Description

Corrective Actions

Severe

CPU error $10nn

The CPU Hardware malfunctions due to failure noise or for other reasons. Hardware failure A failure has occurred during CPU initialization.

SPU error

$11nn

The CPU for sequence computing has failed. A program checksum error has occurred. Transient memory failure or hardware failure (See CAUTION at the end of tables for information on how to discriminate between these failures). Application

Memory error

$1201

1. Check the installation environment for possible problems, such as noise sources. If the failure recurs, replace the module. 1. It is likely that restrictions on module installation have been violated. Check the modules according to Section 1.2, "Restrictions on Installing Modules," in the instruction manual. Sequence CPUs-Hardware. 2. Check the installation environment for possible problems, such as noise sources. If the failure recurs, replace the module. 1. Check the installation environment for possible problems, such as noise sources. If the failure recurs, replace the module. 1. It is likely that the error is due to a transient memory failure caused by effects of noise. Check the installation environment. Clear the memory by referring to CAUTION at the end of tables and download the program once again. If the failure recurs, replace the module. (Note) 1.Check if there is any error in the values of index registers or in the parameters defining the number of devices in an instruction for globally rewriting multiple devices, such as a BMOV block transfer instruction. 1. It is likely that the error is due to a transient memory failure caused by effects of noise. Check the installation environment. Clear the memory by referring to CAUTION at the end of tables and download the program once again. If the failure recurs, replace the module. 1. Verify compatibility among the JMP, SUB and RET instructions. 2. It is likely that the error is due to a transient memory failure caused by effects of noise. Check the installation environment. Clear the memory by referring to CAUTION at the end of tables and download the program once again. If the failure recurs, replace the module.

$1202

Inadvertent writing has been done to the M129 to M131 special relays for handling Run, Debug and Stop mode flags. A device memory read/write check error has occurred. A system memory read/write check error has occurred. An invalid instruction has been encountered. There is no END instruction in the program. The JMP, SUB and RET instructions are not compatible with one another

Hardware failure

$1203 Detection of invalid instruction Program error $1701 $1702 $2001

Hardware failure

Note: You may recover from this error by turning the power off and then on again.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-4
Table 8.2 Details on Self-diagnosis (2 of 6)
Special Relay that Turns ON M193 Special Registers Stored that Store Error Failure Description Code Error Codes, Etc. $2002 The number of I/O Z017 to points has been Z019 exceeded.

Failure Mode

Corrective Actions

Nonfatal

Excess number of I/O points

ROM pack error

$8203

The ROM pack is incompatible with the CPU

Mismatch between ROM pack and CPU Hardware failure

$8204

It is not possible to Hardware read from or write to failure the ROM pack.

Battery error

M194

$1801

The backup batteries have failed. Application The subroutine error return (RET) instruction was not executed or there is no return destination. The maximum nesting depth of eight levels has been exceeded. The interrupt return (IRET) instruction was not executed or there is no return destination. There are more than eight interrupts waiting for execution.

Subroutine M201 error (Note)

Z022 to Z024

$2201

1. It is likely that restrictions on module installation have been violated. Check the modules according to Section 1.2, "Restrictions on Installing Modules," in the instruction manual Sequence CPUs-Hardware. 1. A ROM pack whose data has been erased is in no way defective. Use it as is. 2. It is likely that data has been written to the ROM pack under a wrong sequence CPU module name. Rewrite to the ROM pack and try using it again. The ROM pack or sequence CPU module may be defective if the same failure recurs. Replace the ROM pack or the sequence CPU module. 1. Rewrite to the ROM pack and try using it again. The ROM pack or CPU module may be defective if the same failure recurs. Replace the ROM pack or CPU module. 1. The power supply module may be defective if the same failure recurs. Replace the module. 1. Check if there is a jump out of or into the subroutine. 2. Check if a scan timeout has been detected within the subroutine. 1.Check the depth of nesting when calling another subroutine in a given subroutine. 1. Check if there is a jump out of or into the input module interrupt program. 2. Check if a scan timeout was detected within the input module interrupt program. 1. There are more than eight interrupts waiting for execution. Check the detailed process of each interrupt, the number of interrupts, their frequency, etc. When the power is turned on and before the program is executed, check if there is a possibility that more than eight interrupts will occur.

$2202

Moderate failure

$2301

$2302

Note: For this failure mode, you can determine whether to stop or continue program execution.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-5
Table 8.2 Details on Self-diagnosis (3 of 6)
Special Special Registers Stored Relay that Store Error that Error Code Turns ON Codes, Etc. M201 Z022 to $2101 Z024 $2102

Failure Mode

Failure Description

Corrective Actions

Non-fatal

Instruction error (Note)

The parameters are erroneous.

The data is erroneous.

$2103

There is an error in BIN-to BCD or BCD to-BIN conversion.

$2104

There is an error in the pointers of the FIFO table.

$2105

The value defining a boundary between devices has been exceeded

$2106

The FOR-NEXT loop is not consistent.

1. Check if any abnormal value is set in the instruction parameter in question. 1. Check if any abnormal value, such as one based on division by 0, is set in the instruction parameter. 1. It is likely that an impossible value has been set in BINto-BCD or BCD-to-BIN conversion. Check the parameter where the error has occurred. 1. Check if more data values have been written to the FIFO table than can be accepted by the table. 2. Check if an attempt has been made to read data values from the FIFO table when there is none. 3. Check if the default settings of the FIFO table are correct. Also check if the table has been destroyed in any other part of the program. 1. Check if there is any error in the values of index registers or in the parameters defining the number of devices in an instruction for globally rewriting multiple devices, such as a BMOV block transfer instruction. 1. Check if there is such an error as a jump out of the FOR-NEXT loop or a jump into the loop from outside it. 2. Check if a scan timeout has been detected within the FOR-NEXT loop.

Note: For this failure mode, you can determine whether to stop or continue program execution.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-6
Table 8.2 Details on Self-diagnosis (4 of 6)
Special Relay that Turns ON M202 Special Registers Stored that Store Error Error Code Codes, Etc. Z027 to $2401 Z029

Failure Mode

Failure Description

Corrective Actions

Nonfatal error

I/O collation error (Note)

I/O error (Note)

M203

Z033 to Z040

- The condition of Application 1. It is likely that there is a module installation is failure mismatch between the X not consistent with and Y I/O relay devices the program. specified in the program and those contained in the - The number of installed I/O module. Special Module Check if the instruction High-Speed Read parameter in question is (HRD) instructions or consistent with the Special Module installed I/O module. High-Speed-Write 2. Check if the number of (HWR) instructions exceeded the limit Special Module High(error code: $2401). Speed-Read (HRD) instructions or the number of Special Module HighSpeed-Write (HWR) instructions exceeded 64. $2402 $2402 1. It is likely that there is a mismatch between the slot (READ/W (READ/WRITE) number in READ/WRITE RITE) instructions used in the program and that of the installed I/O module. Check if the instruction parameter in question is consistent with the installed I/O module. $2403 $2403 1. It is likely that there is a mismatch between the slot (READ/W Special module highnumber in a Special RITE) speed-read Module High Speed Read instruction (HRD (HDR) Instruction or a Instruction)/ special Special Module High module-high-SpeedSpeed Write (HWR) write instruction Instruction used in the (HWR Instruction) program and that of the installed I/O module. Check if the instruction parameter in question is consistent with the installed I/O module. -It is not possible to 1. Check if the subunit is read from or write turned off. to the I/O module. 2. Check if there is any -There is a problem with the cable of communication the fiber-optic FA-bus failure in the fibermodule. optic FA-bus 3. Do not reset the CPU module. modules individually. -An attempt has Rather, reset them all at been made to reset once from the main CPU. a remote sequence 4. The I/O module may be CPU module in a defective. multi-CPU system. Replace it.

Note: For this failure mode, you can determine whether to stop or continue program execution.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-7
Table 8.2 Details on Self-diagnosis (5 of 6)
Special Special Registers Relay that Store that Error Turns ON Codes, Etc. M204 Stored Error Code

Failure Mode

Failure Description

Corrective Actions

Nonfatal error

Scan timeout (Note)

Failure in subunit transmission line (Note)

M210

Z089 to Z096

Sensor M212 control scan timeout (Note)

Momentary power failure

M195

1. Check if the repetitioncounter values of the FORNEXT loop are correct. 2. Check if the FOR-NEXT loop has been mistakenly turned into an endless loop by JMP instructions. 3. Adjust the scan time monitoring time according to the execution time of the application program. It is not possible to Open1. Check if the subunit is read from or write to circuited turned off. the subunit. cable Loss of 2. Check if there is any power to problem with the cable of subunit the fiber-optic FA-bus Hardware module. failure 3. The fiber-optic FA-bus module may be defective. Replace it. The CPU fails to Application 1. For interruption by the sustain the failure sensor control block after execution interval completion of instruction because it is execution, set the exceeded by the execution interval at 1 ms or sum of the I/O longer, preferably at the refreshing time of largest possible value. the sensor control 2. Check the number of words and the execution in the sensor control block time of the block. and the block's execution time to reduce both of them as much as possible. 3. Check the CBD-CBE instruction section where executing the sensor control block is prohibited to shorten the section as much as possible. The CPU indicates 1. If this failure mode occurs that a momentary too frequently, check the power failure has power supply for possible occurred. problems. If a UPS is in use, check that it has captured peak values of its supply voltage waveform. If the failure still occurs frequently while there is no problem with the waveform, it is likely that the power supply module and/or sequence CPU module is defective. Replace it.

The scan time Application monitoring time has failure been exceeded.

Note: For this failure mode, you can determine whether to stop or continue program execution.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-8
Table 8.2 Details on Self-diagnosis (6 of 6)
Special Special Registers Relay that Store that Error Turns ON Codes, Etc. M196 Stored Error Code

Failure Mode

Failure Description

Corrective Actions

Nonfatal error

CPU-to-CPU communication failure

There is a Hardware communication failure failure in the shared devices.

Switchover in subunit transmission line

M211

Z89 to Z96

There is a problem Openwith the twisted-pair circuited cables attached to cable remote I/O modules in a loop configuration.

1. It is likely that there is a failure in remote CPUs in a multi-CPU system. Do not reset the CPU modules individually. Rather, reset them all at once from the main CPU. If this failure mode recurs, replace the CPU modules. 1.Check if there is any problem with the cable of the fiber-optic FA-bus module 2.The fiber-optic FA-bus module may be defective. Replace it

CAUTION
You can clear the CPU memory and revert it back to the factory settings by installing the sequence CPU module in the 5th or later slot of the main unit and turning it on. If the failure is a transient memory failure due to effects of noise, download an application program once again so that you can reuse the memory. If the failure recurs, there may be a hardware failure. Replace the sequence CPU module.

SEE ALSO
Fiber-optic FA-bus Module and Fiber-optic FA-bus Type 2 Module (IM34M6H45-01E), for more information on the failure modes failure in subunit transmission line and switchover in subunit transmission line.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-9

8.1.1

Setting Operation Mode in Case of Failure and External Output Mode in Case of Sequence Stop

I Setting Operation Mode in Case of Failure


Using the configuration function, determine whether to stop (for moderate failures) or Run (for minor failures) executing sequence programs in case of such a fault as an instruction processing failure. The table below summarizes the configuration items and their defaults. If a failure for which you have selected the Run option actually occurs, the CPU fails to correctly perform such tasks as accessing the I/O module that caused the failure or processing instructions.
Configuration Item I/O module failure I/O collation failure Instruction processing error Scan time-out Subroutine error Interrupt error Sensor control scan time-out error Failure in subunit transmission line Continue execution (for minor failures) Stop (for moderate failures) Default

See Also
Fiber-optic FA-bus Module and Fiber-optic FA-bus Type 2 Module (IM34M6H45-01E), for more information on the failure mode failure in subunit transmission line.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

8-10

8.2

Recovering Normal Operation after Correcting Non-fatal/Minor Errors


After eliminating the cause of a moderate or minor failure, initialize the states of special relays (M), special registers (Z) and LED indicators as instructed below.

I Recovery after Correcting Non-fatal Errors


Reset special relay (M) and special Registers (Z), as well as turn off the ERR indicator lamp by: turning on the power once again, and setting the sequence CPU in the Run or Debug mode using the WideField2.

I Recovery after Correcting Minor Errors


After correcting any minor failure, reset the special relays (M) and special registers (Z) and turn off the ALM indicator lamp by: - turning on the power once again, - setting the sequence CPU in the Run or Debug mode using the WideField2, and - performing an alarm acknowledgement.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

9-1

9.

Differences From F3SP25 and F3SP35 Sequence CPUs


This chapter describes the differences between F3SP25 and F3SP35 sequence CPUs. You must read this chapter before replacing sequence CPU module F3SP25 or F3SP35 to sequence CPU module F3SP28, F3SP38, F3SP53, or F3SP58 N/ H.

9.1

Comparison of Performance Data


Item F3SP25 4096 max. 8192 8192 1024 32768 8192 F3SP35 Specification F3SP28-3N F3SP28-3S F3SP38-6N F3SP38-6S F3SP53-4H F3SP53-4S F3SP58-6H F3SP58-6S 8192 max., including remote I/O points 32768 16384 2048 32768 262144 16384 120K steps max. 1024 max. 64 max. 33 328 312 328 256 max. F3SP59-7S 8192 max., including remote I/O points 65535 16384 2048 65535 262144 16384 254K steps max. 1024 max. 256 max 33 328 Sensor control function 8192 max., including 4096 max., including remote I/O remote I/O points points 16384 16384 8192 2048 8192 32768 8192 8192 1024 16384 32768

Number of I/O points Number of internal relays (I) Number of link relays (L) Number of timers (T) Number of file registers (B) Number of link registers (W) Program size Number of program blocks Number of program macros Number of basis instructions Number of advanced instructions Other functions

Number of data registers (D) 8192

8192 30K steps max 20K steps 100K steps (F3SP28) max. max. 56K steps max. (F3SP53) 128 max. 1024 max. 1024 max. 1024 max. 25 307 64 max. 33 312 256 max.

128 max. 25 307

Sensor control function

Sensor control function

Specification Item Instruction execution time Basic instruction Advanced instruction F3SP25 0.12 to 0.24s/ instruction From 0.24s/ instruction F3SP35 0.0 9 to0.18s/ instruction From 0.18s/ instruction F3SP28 F3SP53 0.0 45 to 0.18s /instruction From 0.18 s / instruction F3SP38 F3SP58 F3SP59 0.0175 to 0.07s/ instruction From 0.07s /instruction

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

9-2
TIP
- To gain access to file register (B) using a personal computer link command, refer to the conventions given below.
Module Personal computer link (F3LC11-1N, F3LC11-2N) Personal computer link (F3LC11-1F, F3LC12-1F) Ethernet interface CPU (personal computer link function) Restriction Yes Convention Accessible file registers are B1 to B99999.

No

The device name of file registers (B) must be seven bytes long.

- To gain access to the sensor control block using personal computer link module, refer to the conventions given below.
Module Personal computer link Ethernet interface CPU (personal computer function) No A sensor control block number is determined by adding 1 to the end of a number assigned to regular blocks. Restriction Convention

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

9-3

9.2

Configuration
Specification Item F3SP28 F3SP38 F3SP53 F3SP58 F3SP59 No configuration is required for these types of relays. No configuration is required for these types of registers. 16 max F3SP28 and F3SP53: 2048 max. (for all timers combined) F3SP38, F3SP58, F3SP59: 3072 max. (for all timers combined) . Yes F3SP25 8912 units for both types of relays combined F3SP35 16384 units for both types of relays combined

Internal relay (I) Shared Relay (E) Data register (D) Device size Shared register(R) 100-s timer 1-ms timer Operation mode in case of failure Sensor control scan timeout Use /Do not Use

8912 units for both types of registers combined. No 16 max.

No Use/ Do not Use Configurable on a module basis.

Configurable on 16 points basis, including Use/Do not Use/Use as Sensor CB (Note) . I/O module setting 16ms/1ms/250s/62.5s/ 16ms/1ms; configurable on a module Input sampling interval constant; configurable on 16 basis. points basis. Output mode in case Configurable on a module basis. Configurable on 16 points. of sequence stop Configurable from 200s to Execution interval No 25.0ms in 100s increment. Sensor control After completion of instruction block Interrupt timing No execution/Immediate, during instruction execution. Input module After completion of instruction No (always after completion of interrupt Interrupt timing execution/Immediate, during instruction execution) ) instruction execution processing Sensor control block has Priorities of sensor control block and input No priority module interrupt processes / input interrupt has priority Peripheral processing (minimum operating) Configurable from 100s to No time 190ms in 100s increments. Run/Stop; configurable for shared relays (E) , shared Range of shared registers (R) , extended refreshing (partial No shared relays (E) , and stop) extended shared registers (R) Shared refreshing of each CPU module. (inter-CPU-module communications Simultaneity of shared No Yes/No method) refreshing data Mode of shared refreshing (definition Peripheral process/ No (No simultaneity in all cases) Control-related process as control-related process)
Note: Denotes CB (Sensor control block)

CAUTION
For F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59, you can determine by configuration (Yes/No options) whether there is simultaneity with the data of shared devices. The No option of this configuration item is designed for the interchangeability of the F3SP21, F3SP25 and F3SP35 modules. Select this option when replacing these modules with the F3SP28, F3SP38, F3SP53, F3SP58 or F3SP59 modules.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

9-4
CAUTION
If your sequence CPU is F3SP28, F3SP38, F3SP53, F3SP58, or F3SP59, set the CPUs output relays (Y) to be refreshed to the option Unused, by a direct Refresh (DREF) instruction in a program. If you set them to the option Used or Used in CB (sensor control block) , the values one scan earlier may be overwritten with the values output by the DREF instruction because of the timing of output refreshing that is executed concurrently with the instruction.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

9-5

9.3

Special Relays (M) and Special Registers (Z)


The following special relays (M) have been added to the list of utility relays.
Item No. M047 M048 M097 Name 1-ms clock 2-ms clock On for one scan at CB startup Function Utility Description Generates a clock pulse with a period. Generates a clock pulse with a 2-ms period. Turns on for one scan when the sensor control block is enabled (at the first execution of the sensor control block) .

0.5ms 1ms

0.5ms 1ms

ON: When the block is enabled. OFF: In all other cases

Item No. M137 Name CB execution status

Utility Function ON: Enabled OFF: Disabled Utility Name CB scan timeout Function ON: Abnormal OFF: Normal Description The CPU fails to sustain the execution interval of the sensor control block Description Indicates the status of a sensor control block

Item No M212

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

9-6
The following special registers (Z) have been added to the list of utility registers.
Item No. Z109 Z111 Name CB execution time Maximum CB execution time Utility Description Refers to the length of time from when input refreshing is started for the sensor control block to when the program is executed and output refreshing is completed. (Unit: 10s) Refers to the maximum time taken to execute the sensor control block.(Unit:10s)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

9-7

9.4

CPU Module to CPU Module Communication Method


Data Sharing
The availability of the simultaneity of data in CPU-to-CPU communication between shared relays (E) and shared registers (R) and between extended shared relays (E) and extended shared registers (R) is as shown in the following table.
CPU B F3SP28 F3SP38 F3SP25 F3SP53 F3SP35 F3SP58 F3SP59

Availability of Simultaneity of Data among CPU Modules F3SP25 F3SP35 F3SP28 F3SP38 F3SP53 F3SP58 F3SP59

C P U A

There is no simultaneity of data in CPU module to CPU module communication between shared relays (E) /registers and extended shared relays (E) /registers.

Stopping Shared Refreshing Partially


You can exclude a particular CPU or CPUs from shared refreshing.

Defining Shared Refreshing as a Control-related Process


You can determine whether shared refreshing is performed as a control-related process or a peripheral process.

9.5

High-speed Processing of Application Instructions


The F3SP25 and F3SP35 sequence CPUs do not support high -speed processing for Application Instructions that use any of the devices listed below. In contrast, the F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 sequence CPUs support the high-speed processing of Application Instructions where these devices are used. Extended shared relays (E) Extended shared registers (R) Link registers for FA link system 3 or later (W) File registers (B)

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

9-8

9.6

Instructions
The following instructions have been added to the list of instructions available with the F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 sequence CPU modules.
Instruction Name LDU LDD UP DWN UPX DWNX INV FF CBACT CBINA CBD CBE FTIMR Description Rising-edge differential load Rising-edge differential load Rising-edge differential computation Rising-edge differential computation Rising-edge differential computation with device specification Rising-edge differential computation with device specification Inverter Flip-flop Enablement of sensor control block Disablement of sensor control block Prohibition of sensor control block execution Cancellation of prohibition of sensor control block execution Reading of free-running timers

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

10-1

10. Difference between F3SP F3SP - N/- H

- S and

This chapter describes the difference in function and specifications between the F3SP28/38/53/58/59- N/ H (old models) and the F3SP28/38/53/58-S (new models) CPU modules.

10.1 Partial Download Function


The new models are provided with a partial download function, which allows only specified blocks or macros to be downloaded to a CPU, overwriting corresponding blocks or macros of a program that has been downloaded earlier.

SEE ALSO
For details on the partial download function, see Section 6.16, "Partial Download Function."

10.2 Storing Comments or Tag Name Definitions in CPU


The new models allow circuit comments/subcomments or tag name definitions to be stored in the memory of a CPU module or the ROM pack.

SEE ALSO
- For details on the download comments function, see Section 6.17, "Function for Storing Comments to CPU." - For details on the download tag name definitions function, see Section 6.18, "Function for Storing Tag Name Definitions to CPU." - For details on the ROM pack function, see Section 6.8.3, "ROM Writer Functions and ROM Writer Mode."

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

10-2

10.3 New Instructions and Instruction Related Functions


Structures The new models introduce a new concept of structures to handle device addresses. Some instructions are added to handle structures.

SEE ALSO
For details on structures, see "FA-M3 Programming Tool WideField2 Instruction Manual" (IM 34M6Q15-01E).

Indirect designation With the new models, indirect designation is available to address devices. Thus some instructions are added to handle this new function. Using indirect designation allows you to address all file registers (B), including those which cannot be accessed using index modification. You can also use indirect designation to address devices other than the file registers (B).

SEE ALSO
For details on indirect designation, see Section 1.8.2, "Indirect Designation," of "Sequence CPU Instruction Manual - Instructions" (IM 34M6P12-03E, 3rd Edition or later).

Index modification by constant With the new models, index modification by constant is available.

SEE ALSO
For details on index modification by constant, see Section 1.8.1, "Index Modification," of "Sequence CPU Instruction Manual - Instructions" (IM 34M6P12-03E, 3rd Edition or later).

Nesting of interlock areas (program steps between IL and ILC) Interlock areas may be nested up to 8 levels.

SEE ALSO
For details on interlock, see Section 2.18, "Interlock, Interlock Clear," of "Sequence CPU Instruction Manual - Instructions" (IM 34M6P12-03E, 3rd Edition or later).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

10-3
New instructions The following instructions are added in the new models.

Table 10.1 List of Added Instructions


Mnemonic SET ADD MOV LDW OUTW SETW RSTW NCALL NMOUT SCALL STMOV STRCT DATE TIME SDATE STIME Instruction Indirect Address Set Indirect Address Add Indirect Address Move Load Specified Bit Out Specified Bit Set Specified Bit Reset Specified Bit Input Macro Instruction Call Output of Input Macro Structure Macro Instruction Call Structure Move Structure pointer Declaration Set Date Set Time Set Date String Set Time String

SEE ALSO
For details on these new instructions, see "Sequence CPU Instruction Manual - Instructions" (IM 34M6P12-03E, 3rd Edition or later).

10.4 Changes in Specifications


Table 10.2 List of Changes in Specifications
CPU Types Items F3SP28-3N F3SP38-6N F3SP53-4H F3SP58-6H 10K steps 64 3000 per program 2 RK33/RK73 F3SP28-3S F3SP38-6S F3SP53-4S F3SP58-6S F3SP59-7S 56K steps 256 30000 per block 4 RK33/RK73/RK93*1

Number of steps per block Number of macro instructions Number of circuits/subcomments Number of timer steps Compatible ROM pack

*1: RK93E is not compatible with the F3SP28-3S and F3SP53-6S.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

App.1

FA-M3
Sequence CPU Instruction Manual - Function
(For F3SP28-3N/3S, F3SP38-6N/6S, F3SP53-4H/4S, F3SP58-6H/6S, F3SP59-7S)
IM 34M6P13-01E 2nd Edition

These appendices provide lists of special devices, as well as formats of documentation which can be used when designing your system. These formatted sheets can be conveniently copied for use as standard forms in your system design. Four forms are provided, as shown below.

Contents
Appendix 1 Special Relays (M) ............................................................... App.1-1 Appendix 2 Special Registers (Z) .......................................................... App. 2-1 Appendix 3 Forms for system Design................................................... App. 3-1
Program Coding Sheet ............................................................ App 3-1 Relay Devices Assignment Table ............................................ App 3-2 Register Devices Assignment Table ........................................ App 3-3 Timer/Counter Setpoints Table ................................................ App 3-4

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

App.1-1

Appendix 1. Special Relays (M)


Special relays have specific functions, such as indicating the internal state of a CPU or detecting errors. In programs, these relays are used mainly for contacts a and b.

Appendix 1.1 Block Start Status


Block start status relays indicate which block is running when the selected blocks are being executed. These relays are numbered in ascending order as M001, M002, . . ., to correlate with block 1, block 2, ...
Table Appendix 1.1 Block Start Status
Item Sequence CPU Module F3SP05, F3SP08, F3SP21 F3SP25, F3SP35 F3SP28, F3SP38 F3SP53, F3SP58, F3SP59
Note:

Block Start Status Module M0001 to M0032 M0001 to M0032 M2001 to M3024 Relay Block n start status relay Number ON: Run OFF: Stop Name Indicate whether block n is in progress or at a stop when blocks are selected and executed.

The start status relays assigned to blocks 1 to 32 are M0001 to M0032 and M2001 to M2032, where the values of M0001 to M0032 are the same as those of M2001 to M2032. Similarly, start status relays M2033 to M3024 are assigned to blocks 33 to 1024.

CAUTION
Do not write to a special relay, including those not listed in the table above (e.g., M067 to M96), unless otherwise stated. This is because they are used by the sequence CPU module for the system side. If you inadvertently write to these relays, a failure, such as a system shutdown, may result. (It is also prohibited to use a forced set/reset instruction in debug mode.)

CAUTION
You are not allowed to apply index modification to a special relay in an attempt to specify them as the destination of data output. If you do so, an instruction processing error will result.

CAUTION
In a ladder instruction for continuous data transfer or table-format data output (see examples below), you are not allowed to specify a special relay as the output destination. If you do so, an instruction processing error will result. - Instructions for continuous data transfer: BMOV, BSET, SMOV, etc. - Instructions for table-format data output: ULOGR, FIFWR, etc.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.1-2

Appendix 1.2 Utility Relays


Utility relays are used to provide timing in a program or give instructions to the CPU module.
Table Appendix 1.2
Item No. M033 M034 M035 M036** M037** M038** M039** M040** M041** M042* M047** M048* M066 M097 Name Always ON Always OFF 1 scan ON after the start of a program 0.01 s clock 0.02 s clock 0.1 s clock 0.2 s clock 1 s clock 2 s clock 1 min clock 1 ms clock 2 ms clock Normal subunit transmission line On for one scan at CB startup

Utility Relays
Function Description Used for an initialization process or as a dummy contact in a program.

Utility Relays

ON OFF ON OFF
1 Scan

Turns on for one scan only after the start of a program Generates a clock pulse with a 0.010.005s 0.005s sec period. Generates a clock pulse with a 0.020.01s 0.01s sec period. Generates a clock pulse with a 0.1-sec 0.05s 0.05s period. Generates a clock pulse with a 0.2-sec 0.1s 0.1s period. Generates a clock pulse with a 1-sec 0.5s 0.5s period. Generates a clock pulse with a 2-sec 1s 1s period. Generates a clock pulse with a 1-min 30s 30s period. Generates a clock pulse with a 1-msec 0.5ms 0.5ms period. Generates a clock pulse with a 2-msec 1ms 1ms period. ON: Normal transmission line or no fiber-optic FA-bus installed OFF: Unspecified or abnormal transmission line ON: When the block Turns on for one scan when the sensor starts. control block starts (at the first OFF: In all other execution of the sensor control block). cases.

*: Blocks M036 to M048 have their rising and falling clock timing synchronized.

SEE ALSO
For details on the M066 Utility relay (Normal Subunit Transmission Line), see "Fiber-optic FA-bus Module and Fiber-optic FA-bus Type 2 Module" (IM34M6H45-01E).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.1-3

Appendix 1.3 Sequence Operation and Mode Status Relays


Sequence operation and mode status relays indicate the status of sequence operation or each mode.
Table Appendix 1.3 Sequence Operation and Mode Status Relays
Item No. M129 M130 M131 M132 M133 M135 M136 M137 M172 (write-enabled) M173 M174 M175 M176 M177 to M178 M188 M189 to M192 Name Run mode flag Debug mode flag Stop mode flag Pause flag Execution flag (All blocks/Specified blocks) RAM/ROM-based operation flag Power-on operation flag CB execution status Time setting Input-off-line flag Output-off-line flag Shared-I/O-off-line flag Link-I/O-off-line flag Devices reserved for extended functions Carry flag Devices reserved for extended functions ON: Carry-enabled OFF: Carry-disabled A carry flag used for shift or rotation operation. Sequence Operation and Mode Status Relays Function ON: Run mode OFF: Other modes ON: Debug mode OFF: Other modes ON: Stop mode OFF: Other modes ON: Pause OFF: Program execution ON: Specified blocks OFF: All blocks ON: ROM-based operation OFF:RAM-based operation ON: Power-on operation OFF: Other modes of operation ON: Start OFF: Stop ON: Time being set OFF: ON: Off-line OFF: On-line ON: Off-line OFF: On-line ON: Off-line OFF: On-line ON: Off-line OFF: On-line Description Indicates the status of CPU operation. Indicates the status of CPU operation. Indicates the status of CPU operation. Indicates the status of program execution during debug mode operation. Indicates whether all blocks or specified blocks are executed. Indicates whether operation is based on the ROM or RAM. Indicates the status of sensor control block execution. Indicates the status of sensor control block execution. Requests to set clock data. Indicates that input refreshing has stopped. Indicates that shared refreshing has stopped. Indicates that shared refreshing has stopped. Indicates that link refreshing has stopped.

SEE ALSO
Specifications of special registers (Z) for clock data, for more information on time setting.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.1-4

Appendix 1.4 Self-diagnosis Status Relays


Self-diagnosis status relays indicate the results of self-diagnostics by the sequence CPU.
Table Appendix 1.4 Self-diagnosis Status Relays
Item No. M193 M194 M195 Name Self-diagnosis error Battery failure Momentary power failure CPU-to-CPU communication failure Existence of CPU1 Existence of CPU2 Existence of CPU3 Existence of CPU4 Instruction processing error I/O collation error Self-diagnosis Status Relays Function ON: An error is found. OFF: No error is found. ON: Abnormal. OFF: Normal. ON: A momentary power failure is found. OFF: No momentary power failure is found. ON: Abnormal. OFF: Normal. ON: Exists. OFF: Does not exist. ON: Exists. OFF: Does not exist. ON: Exists. OFF: Does not exist. ON: Exists. OFF: Does not exist. ON: An error is found. OFF: No error is found. ON: Abnormal. OFF: Normal. ON: Abnormal. OFF: Normal. Description Error information is stored in special registers Z17 to Z19 for updating the results of self-diagnosis. Indicates a failure in backup batteries. Indicates that a momentary failure has occurred. Indicates that a communication failure has occurred in shared relays/registers. Indicates whether or not a CPU exists in slot 1. Indicates whether or not a CPU exists in slot 2. Indicates whether or not a CPU exists in slot 3. Indicates whether or not a CPU exists in slot 4. Information on an error that may occur during instruction processing is stored in special registers Z22 to Z24. Indicates that the state of module installation is not consistent with the program. Indicates that no access is possible to I/O modules. The slot number of the module in question is stored in special registers Z33 to Z40. Indicates that the scan has exceeded the scan time monitoring time. The slot number of the fiber-optic FA-bus module in question is stored in special registers Z89 to Z96 if a failure occurs in the module. Indicates that it is not possible to sustain the execution interval of the sensor control block. Indicates whether a sequence program for a CPU in slot 1 is running or at a stop. Indicates whether a sequence program for a CPU in slot 2 is running or at a stop. Indicates whether a sequence program for a CPU in slot 3 is running or at a stop. Indicates whether a sequence program for a CPU in slot 4 is running or at a stop.

M196 M197 M198 M199 M200 M201 M202

M203 M204 M210

I/O module failure Scan time-out

M211

ON: Abnormal. OFF: Normal. ON: Abnormal transmission Subunit transmission line. line failure OFF: Unspecified or normal transmission line. ON: Abnormal transmission Switchover in line. subunit transmission OFF: Unspecified or normal line transmission line. ON: Abnormal. OFF: Normal. ON: Executes the program. OFF: Stops the program. ON: Executes the program. OFF: Stops the program. ON: Executes the program. OFF: Stops the program. ON: Executes the program. OFF: Stops the program.

M212 M225 M226 M227 M228

CB scan timeout CPU-1 sequence program execution CPU-2 sequence program execution CPU-3 sequence program execution CPU-4 sequence program execution

SEE ALSO
Fiber-optic FA-bus Module and Fiber-optic FA-bus Type 2 Module (IM34M6H45-01E), for more information on the M210 (Subunit Transmission Line Failure) and M211 (Switchover in Subunit Transmission Line) self-diagnosis relays.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.1-5

Appendix 1.5 FA Link Module Status Relays


FA Link module status relays indicate the status of FA link.

SEE ALSO
Special relays/registers sections of instruction manual (IM34M5H43-01E), FA Link H Module, Fiberoptic FA Link H Module, for more information on these FA link module status relays.

Table Appendix 1.5


Item No. M257 to M480 M8321 to M8992

FA Link Module Status Relays


FA Link Module Status Relays Name Function ON: Abnormal. OFF: Normal. Description Indicate the status of FA link.

FA link error

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

App.2-1

Appendix 2. Special Registers (Z)


Special registers have specific functions, such as indicating the internal state of a programmable controller or detecting errors.

Appendix 2.1 Sequence Operation Status Registers


Sequence operation status registers indicate the status of sequence operation.
Table Appendix 2.1 Sequence Operation Status Registers
Item No. Z001 Z002 Z003 Z004 Z005 Z006 Z007 Name Sequence Operation Status Registers Function Description Stores the latest scan time in 100 s increments. Allows the latest scan time to be read in 100 s increments if it is shorter than the minimum scan time. Allows the latest scan time to be read in 100 s increments if it is longer than the maximum scan time. Stores the latest scan time in 100 s increments. Allows the latest scan time to be read in 100 s increments if it is shorter than the minimum scan time. Allows the latest scan time to be read in 100 s increments if it is longer than the maximum scan time. Stores the latest scan time in 100 s increments. (Tolerance: Scan time of one control process) Allows the latest scan time to be read in 100 s increments if it is shorter than the minimum scan time. (Tolerance: Scan time of one control process) Allows the latest scan time to be read in 100 s increments if it is longer than the maximum scan time. (Tolerance: Scan time of one control process)

Scan time (Run mode) Latest scan time Minimum scan time (Run mode) Maximum scan time (Run mode) Scan time (Debug mode) Minimum scan time (Debug mode) Maximum scan time (Debug mode) Peripheral-process scan time Minimum peripheralprocess scan time Maximum peripheralprocess scan time Minimum scan time Maximum scan time. Latest scan time Minimum scan time Maximum scan time. Latest scan time

Z008

Minimum scan time

Z009

Maximum scan time.

CAUTION
Do not write to a special register (Z), including those not listed in the table above (e.g., Z010 to Z016), unless otherwise stated. This is because they are used by the sequence CPU module for the system. If you inadvertently write to these registers, a failure, such as a system shutdown, may result. You are not allowed to apply index modification to special registers (Z) in an attempt to specify them as the destination of data output. If you do so, an instruction processing error will result. In a ladder instruction for continuous data transfer or table-format data output (see examples below), you are not allowed to specify a special register (Z) as the output destination. If you do so, an instruction processing error will result. Instructions for continuous data transfer: Block Move instruction (BMOV instruction), Block Set instruction (BSET instruction), String Move instruction (SMOV instruction), etc. Instructions for table-format data output: User Log Read instruction (ULOGR instruction), FIFO Write instruction (FIFWR instruction), etc.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.2-2

Appendix 2.2 Self-diagnosis Status Registers


Self-diagnosis status registers indicate the results of self-diagnostics by the sequence CPU.
Table Appendix 2.2 Self-diagnosis Status Registers
Type No. Z017 Z018 Z019 Z022 Z023 Z024 Z027 Z028 Z029 I/O collation error Instruction processing error block number Instruction processing error block number Self-diagnosis error Name

Self-diagnosis Status Registers


Function Self-diagnosis error number Self-diagnosis error block number Self-diagnosis error instruction number Instruction processing error block number Instruction processing error block number Instruction processing error instruction number I/O collation error number Instruction processing error block number block number Instruction processing error instruction number Store, as a bit pattern, the slot number for which an I/O failure has occurred. Z033: Main unit Z034: Subunit 1 Z035: Subunit 2 Z036: Subunit 3 Z037: Subunit 4 Z038: Subunit 5 Z039: Subunit 6 Z040: Subunit 7
Slot number 16 0 1

Description Store the results of self-diagnosis.*

Store errors occurring during instruction processing.*

Store detailed information on I/O collation errors.*

Z033 to 040

I/O error

I/O error 16 0

2 1

1 0

Z041 Z042 Z043 Z044 Z045 Z046 Z047 Z048 Z089 Z090 Z091 Z092 Z093 Z094 Z095 Z096 Abnormal slot in subunit transmission line Module recognition

Main unit Subunit 1 Subunit 2 Subunit 3 Subunit 4 Subunit 5 Subunit 6 Subunit 7 Main unit Subunit 1 Subunit 2 Subunit 3 Subunit 4 Subunit 5 Subunit 6 Subunit 7
Slot number 16 0 1 1 0
1 0

0: No modules are recognized. Unable to read/write. 1: Modules are recognized.

Fiber-optic FA-bus module 0: Normal transmission line; Unspecified transmission line; or Loaded with a wrong module 1: Abnormal transmission line (Failure or changeover in transmission line)

* For information on error numbers (codes) to be saved in these special registers, see Table 8.2, "Details of Self-diagnosis."

SEE ALSO
Fiber-optic FA-bus Module and Fiber-optic FA-bus Type 2 Module (IM34M6H45-01E), for more information on the Z089 to Z096 special registers (Abnormal Slot in Subunit Transmission Line).

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.2-3

Appendix 2.3 Utility Registers


Table Appendix 2.3 Utility Registers
Type No. Z049 (write-enabled) Z050 (write-enabled) Z051 (write-enabled) Z052 (write-enabled) Z053 (write-enabled) Z054 (write-enabled) Z055 Z056 (Note) Z057 (Note) Z058 Constant scan time Constant scan time Scan time monitoring time Clock data Name Utility Registers Function Description Stores "year" as a BCD-coded value. Lower-order two digits of Example: 1999 as $0099 calendar year 2000 as $0000 Stores "month" as a BCD-coded value. Month Example: January as $0001 Stores "day of month" as a BCD-coded Day of month value. Example: 28th as $0028 Stores "hour" as a BCD-coded value. Hour Example: 10 o'clock as $0010 Stores "minute" as a BCD-coded value. Minute Example: 15 minutes as $0015 Stores "second" as a BCD-coded value. Second Example: 30 seconds as $0030 Stores "day of week" Day of week ($0000 to as a BCD-coded value. $0006) Example: Wednesday as $0003 Value of constant scan 0.1 ms increments time Example: 10 ms as 100 Value of constant scan 1 ms increments time Example: 10 ms as 10 Value of scan time 1 ms increments monitoring time Example: 200 ms as 200

Note: Available with the F3SP28, F3SP38, F3SP58 and F3SP59 only.

Setting Clock Data


For CPU module F3SP - S, use Set Date instruction (DATE), Set Time instruction (DATE), Set Date String instruction (SDATE), and Set Time String instruction (STIME) to set clock data. For CPU module F3SP - N/- H, follow the procedure given below to set clock data. (1) Write the clock data to special registers Z049 to Z054 (use a MOV P instruction). (2) Set special relay M172 to ON within the same scan as that in step (1) (use a DIFU instruction, for example). (3) Set special relay M172 to OFF in the scan subsequent to that in step (2). Also stop writing the clock data to special registers Z049 to Z054 in that scan. Note that no change is made to the clock data and the data reverts to its original values if the values being set are incorrect.

Clock Data Accuracy


- The accuracy of clock data is specified as: - Maximum monthly error = 8 s (2 s, when actually measured) The clock accuracy is reset to the maximum daily error of -1.2 s/+2 s, however, when the power is turned off and on again. In addition, it is possible to input a corrective value from the programming tool. If you input a precise corrective value, the clock data is corrected during the power-off-and-on sequence, thus offsetting the cumulative amount of error.
IM 34M6P13-01E 2nd Edition : Oct 1, 2002

App.2-4

Appendix 2.4 FA Link Module Status Registers


FA Link module status registers indicate the status of FA link.

SEE ALSO
Special relays/registers sections in, FA Link H Module F3LP02-0N Fiber-optic FA Link H Module F3LP12-0N (IM34M5H43-01E), for more information on the FA link module status registers.

Table Appendix 2.4 FA Link Module Status Registers


Type No. Z065 Z066 Z070 Z071 Name Local station status Cyclic transmission time Local station status Cyclic transmission time 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online 0: Under initialization 1: Offline 2: Online FA Link Module Status Registers Function 0: Under initialization 1: Offline 2: Online Description FA link 1 FA link 1 1 ms increments FA link 2 FA link 2 1 ms increments FA link 3 FA link 3 1 ms increments FA link 4 FA link 4 1 ms increments FA link 5 FA link 5 1 ms increments FA link 6 FA link 6 1 ms increments FA link 7 FA link 7 1 ms increments FA link 8 FA link 8 1 ms increments

Z257 (Note) Local station status Z258 (Note) Cyclic transmission time

Z262 (Note) Local station status Z263 (Note) Cyclic transmission time

Z267 (Note) Local station status Z268 (Note) Cyclic transmission time

Z272 (Note) Local station status Z273 (Note) Cyclic transmission time

Z277 (Note) Local station status Z278 (Note) Cyclic transmission time

Z282 (Note) Local station status Z283 (Note) Cyclic transmission time

Note: Available with the F3SP25, F3SP28, F3SP35, F3SP38, F3SP53, F3SP58 and F3SP59 only.

TIP
Units that make up a system are known as stations.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.2-5

Appendix 2.5 Sequence CPU Module Status Registers


CPU module status registers indicate the status of a CPU.
Table Appendix 2.5 Sequence CPU Module Status Registers
Item No. Z105 Name Number of stored user logs Refers to the length of time from when input refreshing is started for the sensor control block to when the program is executed and output refreshing is completed. (Unit: 10 s) Refers to the maximum time taken to execute the sensor control block. (Unit: 10 s) Model name and revision number of firmware. CPU Module Status Registers Function Description See Section 6.14, "User Log Management Function, " for information on user logs.

Z109 (Note 1)

CB execution time

Z111 (Note 1)

Maximum CB execution time

Z121 to Z128 Model details (Note 2)

Note 1: Only for F3SP28, F3SP38, F3SP53, F3SP58, and F3SP59 Note 2: F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59 For example, module F3SP58-6S with firmware Rev1, Z121 F3 Z122 SP Z123 58 Z124 6S Z125 /R Z126 01 Z127 / Z128 F3SP05, F3SP08, F3SP21, F3SP25, F3SP35 For example, module F3SP21-0N with firmware Rev 14 Z121 F3 Z122 SP Z123 21 Z124 -0 Z125 *A Z126 14 Z127 Z128

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

App.3-1

Appendix 3. Forms for System Design


Program Coding Sheet
System Name Model Drawing No.
Approved Checked Prepared Sheet No. by by by

Instruction No. Instruction 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

Operand

Remarks

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.3-2
I Relay Devices Assignment Table
System Name Model Drawing No.
Approved Checked Prepared Sheet No. by by by

Device No. 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2

Signal Name

Description

Device No. 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4

Signal Name

Description

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.3-3
I Register Devices Assignment Table
System Name Model Drawing No.
Approved Checked Prepared Sheet No. by by by

Device No. 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

Signal Name

Description

Device No. 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

Signal Name

Description

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

App.3-4
I Timer/Counter Setpoints Table
System Name Model Drawing No.
Approved Checked Prepared Sheet No. by by by

Device No 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2

Setpoint

Signal Name

Description

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Index-1

FA-M3
Sequence CPU Instruction Manual - Function
(For F3SP28-3N/3S, F3SP38-6N/6S, F3SP53-4H/4S, F3SP58-6H/6S, F3SP59-7S)
IM 34M6P13-01E 2nd Edition

Index
Number
100ms Continuous Timer ................................... 4-27 100ms Timer ...................................................... 4-25 100ms Timer ...................................................... 4-25 10ms Timer ........................................................ 4-25 1ms Timer .......................................................... 4-25

F
FA Link Module Status.........................4-24, App. 1-5 FA Link System .................................................... 2-5 File Registers (B) ............................................... 4-45 Forced Reset...................................................... 6-13 Forced Set.......................................................... 6-13

A
ACTIVE State ....................................................... 6-7 Allocation of I/O Addresses .................................. 4-2

H
High-speed Processing of Application Instructions9-7

B
Basic System Configuration................................. 2-1 Block Protection ................................................. 6-16 Block Start Status ............................................... 4-19 Blocks................................................................... 5-3

I
I/O Relay Number .............................................. 1-19 Immediate Detection Mode .................................. 3-4 INACTIVE Status.................................................. 6-7 Index Registers V) ........................................... 4-44 Input Relays (X) ................................................... 4-1 Internal Relays (I)................................................. 4-6 Interrupt Processing Control .............................. 3-27 Interrupt Processing ........................................... 3-26 Interrupt Programs ............................................... 5-8

C
Changing Data Values ....................................... 6-13 Clear Device......................................................... 6-3 Clear Memory....................................................... 6-3 Commands......................................................... 6-36 Communication Procedure ................................ 6-34 Computation Method............................................ 3-7 Configuration................................................. 1-9, 9-3 Configuring Link Relays (L) and Registers (W) Constant Scan...................................................... 6-5 Counter (C) ........................................................ 4-29 CPU Service....................................................... 3-22 Current Values ................................................... 6-13

L
Link Data Updating............................................. 3-23 Link Refreshing .................................................. 3-24 Link Registers (W)............................4-12, 4-14, 4-16 Link Relay (L) ...................................4-12, 4-13, 4-16

M
Macro Instructions.............................................. 6-46 Main Routine Programs ....................................... 5-6 Main Unit ............................................................ 1-16 Making Programs Resident in ROM .................. 6-18 Making Programs Resident................................ 6-18 Method of I/O Processing................................... 3-11 Minor Errors ....................................................... 8-10 Mnemonic Language............................................ 5-2 Mode Status ................................................ 4-22, 1-4 Multi-CPU System Configuration ......................... 2-1

D
Data Registers (D) ............................................. 4-31 Debug Mode......................................................... 6-3 Debugging Operation ......................................... 6-57 Device List............................................................ 1-7 Device Management Function ........................... 6-45 Differences from F3SP25 and F3SP35................ 9-1 Differences from Personal Computer Link Module............................. 6-30

N
Non-fatal Errors .................................................. 8-10

E
Exclusive Access Control ................................... 6-23 Executable Program Protection ......................... 6-15 Executable Program............................................. 5-4 Executing All Blocks ............................................. 6-6 Executing Specified Blocks .................................. 6-7 Extended Shared Registers (R) ......................... 4-32 Extended Shared Relays (E) ............................... 4-7 Extended System Configuration .......................... 2-4

O
Online Editing..................................................... 6-17 Operation in case of Complete Power Failure ..... 3-6 Operation in case of Momentary Power Failure... 3-6 Output Relays (Y)................................................. 4-2

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Index-2
P
Peripheral Processes ........................................... 3-9 Personal Computer Link Function...................... 6-28 Personal Computer Link Service ....................... 3-15 Personal Computer Link System ......................... 2-5 Power Failure ...................................................... 3-6 Program Memory ............................................... 5-10 Programming Language ...................................... 5-1 Protecting Programs .......................................... 6-15 Ranges of Devices To Be Latched in case of Complete Power Failure............ 3-6

U
Unit ..................................................................... 1-16 User Log Management Function........................ 6-62 Utility ............................ 4-20, 4-41, App.1-2, App.2-3

W
WideField2 ........................................................... 2-6

R
Remote I/O System.............................................. 2-4 Response Delay................................................. 3-12 Responses ......................................................... 6-36 ROM Clear Function .......................................... 6-22 ROM Compare Function .................................... 6-22 ROM Copy Function........................................... 6-22 ROM Transfer function ....................................... 6-22 ROM Write Functions......................................... 6-21 Run Mode............................................................. 6-3

S
Sampling Trace .................................................. 6-24 Selecting Timers................................................. 4-28 Self-diagnosis .............. 4-23, 4-40, App.1-4, App.2-2 Self-diagnosis Status Registers ...........4-40, App.2-2 Self-diagnosis Status...................4-23, 4-40, App.1-5 Sensor Control Block ........................................... 5-9 Sensor Control Function .................................... 6-64 Sequence CPU Module Operation Modes........... 3-1 Sequence CPU Module Status .......................... 4-43 Sequence Operation Status .................4-39, App.2-1 Sequence Operation ............................4-22, App.1-3 Setpoints ............................................................ 6-15 Setting Scan Time Monitoring Time ..................... 7-4 Shared Refreshing ............................................. 3-18 Shared Registers (R) ......................................... 4-32 Shared Relays (E)................................................ 4-7 Slot Number ....................................................... 1-17 Special Registers (Z)............................................ 9-5 Special Relays (M) ............................................... 9-5 Specifying Input Sampling Interval....................... 4-4 Specifying Input Sampling Interval....................... 4-4 Standard Mode..................................................... 3-4 Stop Mode ............................................................ 6-3 Stop Refreshing.................................................. 6-14 Structured Ladder Language ............................... 5-1 Subroutine Programs ........................................... 5-7 Subunit ............................................................... 1-16

T
Timer (T)............................................................. 4-25 Tool Service........................................................ 3-14

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Revision Information
Document Name : Sequence CPU Instruction Manual - Function (For F3SP28-3N/3S, F3SP38-6N/6S, F3SP53-4H/4S, F3SP58-6H/6S, F3SP59-7S) Document No.
Edition 1st 2nd

: IM 34M6P13-01E
Revised Item New publication Included F3SP59, for - S Incorporated addendum, errata

Date Jul. 2000 Oct. 2002

Written by

Product Marketing Department, IT Controller Center. Yokogawa Electric Corporation Published by Yokogawa Electric Corporation 2-9-32 Nakacho, Musashino-shi, Tokyo, 180-8750, JAPAN Printed by Yokogawa Graphic Arts Co., Ltd.

IM 34M6P13-01E

2nd Edition : Oct 1, 2002

Blank Page

S-ar putea să vă placă și