General overview fire & smoke protection Summary: Actuators for fire & smoke protection Technical characteristics, Type 229, 5 Nm Technical characteristics, Type 239, 20 Nm Your way to Gruner
GR
UNER he frie t
alte dly n
rnative
Fire Protection
= Standard = Optional
Type
Spring Return Torque (Actuator) Torque (Spring) Angle of Rotation
229
5 Nm (ca. 1 m )
2
239
20 Nm (ca. 4 m2) 15 Nm 100
4 Nm 100
Control
On/Off
Power Supply
24 VAC/DC 230 VAC
Options
Auxiliary switch(es) Thermal Tripping Device (72C) Thermal Tripping Device for Duct Mounting (72C)
Applications
Motorised control of fire and smoke dampers in HVAC systems. All actuators correspond to the DIN-VDE standards and CE guidelines.
= Standard = Optional
Type
Torque (Actuator) Torque (Spring) On/Off Control Angle of Rotation
5 Nm 4 Nm 100
Power Supply
24 VAC/DC 230 VAC
Options
Thernal Tripping Device (72C) Thernal Tripping Device for Duct Mounting (72C) Auxiliary switch(es) Page 4 4 6 6 8 8 8 10 10 10
Actuators typ 239 dispose of the manual override option by crank. Actuators according to US standard available upon demand.
Important Note
The modification and mounting of the actuator to the fire damper is made by the manufacturer of the damper. For this reason the spring-return actuator is only supplied directly to manufacturers of fire dampers. The manufacturer then bears overall responsibility for proper functioning of the damper.
22 902 405 22 -S 9T 2 A02 422 05 9-S 23 2 005 22 -S 9T 2 A23 005 -S 2 23 902 420 23 -S 9T 2 -0 24 -2 23 09T S2 A02 423 20 9-S 23 2 020 23 -S 9T 2 -2 30 -2 23 09T S2 A23 020 -S 2
5 Nm 4 Nm 100 5 Nm 4 Nm 100 5 Nm 4 Nm 100 20 Nm 20 Nm 20 Nm 20 Nm 20 Nm 20 Nm 15 Nm 15 Nm 15 Nm 15 Nm 15 Nm 15 Nm 100 100 100 100 100 100
229-024-05-S2, 229TA-024-05-S2
Applications
To regulate fire and smoke dampers in HVAC systems: Form-locking steel drive Torque 5 Nm / 4 Nm Angle of rotation 100 Hold safe position in case of high temperature no manual operation and position fixing reliable safe postion Electromagnetic compatibility controlled
Technical Characteristics
Control Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90) Torque Auxiliary switches Switching power Auxiliary switches Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On/Off 24 VAC (50/60 Hz) / DC 20% Motion: 5.0 W / Power safe mode: 3.0 W 6.5 VA 100 (-5...+95) can be selected by mounting back to front Actuator: < 40...75 s / Spring: < 20 s Actuator: 5 Nm / Spring: 4 Nm 2, position fixed to 5 and 80 250 VAC / 5.0 (2.5) A, change-over switch Cable 900 mm / 0.75 mm2 III IP54 (Cable downwards) 158 x 66 x 61 mm -30C...+50C maintenance-free 73/23/EWG, 89/336/EWG 1,100 g
229-024-05-S2
Connection scheme S1 S2
1 2 3 4 5 6
229TA-024-05-S2
Connection scheme S1 S2 1 2 3 4 5 6 TA
TF1 TF2
BU BN
BU BN
229-024-05-S2, 229TA-024-05-S2
1 Fixing of the shaft
Concentric form locking shaft: 8...12 mm
Auxiliary switches
The actuator has two position fixed auxiliary switches for indicating the damper postion. The position of the damper can be read on the scale on front of the actuator.
If 72C are reached the actuator turns the damper back to its safe position.
2
2.00
2.8...3 9.5...10
27.60
107.002.00
50.00 40.00
2.8...3
66.001.00
9.00
Technical drawing
229-024-05-S2
R2
157.001.00
.0
2.00
12.00
0 ,2
13.00
1,2,3,4,5,6 11.00
N ,B BU
66.001.00
,4
12.20
52.00
TA
61.001.00
,6 ,8
6.00
12.20
13.00
1
R65 .00
R1 1
.00
66.00
2.00
229-230-05-S2, 229TA-230-05-S2
Applications
To regulate fire and smoke dampers in HVAC systems: Form-locking steel drive Torque 5 Nm / 4 Nm Angle of rotation 100 Hold safe position in case of high temperature no manual operation and position fixing reliable safe postion Electromagnetic compatibility controlled
Technical Characteristics
Control Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90) Torque Auxiliary switches Switching power Auxiliary switches Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On/Off 230 VAC (50/60 Hz) 15% Motion: 5.0 W / Power safe mode: 2.5 W 5.5 VA 100 (-5...+95) can be selected by mounting back to front Actuator: < 40...75 s / Spring: < 20 s Actuator: 5 Nm / Spring: 4 Nm 2, position fixed to 5 and 80 250 VAC / 5.0 (2.5) A, change-over switch Cable 900 mm / 0.75 mm2 II IP54 (Cable downwards) 158 x 66 x 61 mm -30C...+50C maintenance-free 73/23/EWG, 89/336/EWG 1,100 g
229-230-05-S2
Connection scheme S1 S2 1 2 3 4 5 6
229TA-230-05-S2
Connection scheme S1 S2 1 2 3 4 5 6 TA
TF1 TF2
BU BN
BU BN
N L
N L
229-230-05-S2, 229TA-230-05-S2
1 Fixing of the shaft
Concentric form locking shaft: 8...12 mm
Auxiliary switches
The actuator has two position fixed auxiliary switches for indicating the damper postion. The position of the damper can be read on the scale on front of the actuator.
If 72C are reached the actuator turns the damper back to its safe position.
2
2.00
2.8...3 9.5...10
27.60
107.002.00
50.00 40.00
2.8...3
66.001.00
9.00
Technical drawing
229-230-05-S2
R2
157.001.00
.0
2.00
12.00
0 ,2
13.00
1,2,3,4,5,6 11.00
N ,B BU
66.001.00
,4
12.20
52.00
TA
61.001.00
,6 ,8
6.00
12.20
13.00
1
R65 .00
R1 1
.00
66.00
2.00
Technical Characteristics
Control Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90) Torque Auxiliary switches Switching power Auxiliary switches Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On/Off 24 VAC (50/60 Hz) / DC 20% Motion: 6.5 W / Power safe mode: 4,0 W 10 VA 100 (-5...+95) can be selected by mounting back to front Actuator: 150 s / Spring: < 20 s Actuator: 20 Nm / Spring: 15 Nm 2, position fixed to 5 and 80 250 VAC / 5.0 (2.5) A, change-over switch Cable 900 mm / 0.75 mm2 III IP54 (Cable downwards) 250 x 98 x 58 mm -30C...+50C maintenance-free 73/23/EWG, 89/336/EWG 2,500 g
239-024-20-S2
Connection scheme S1 S2
1 2 3 4 5 6
239T-024-20-S2
Connection scheme S1 S2 1 2 3 4 5 6 T
TF1
239TA-024-20-S2
Connection scheme S1 S2 1 2 3 4 5 6 TA
TF1 TF2
BU BN
BU BN
BU BN
Auxiliary switches
The actuator has two position fixed auxiliary switches for indicating the damper postion. The position of the damper can be read on the scale on front of the actuator.
If 72C are reached the actuator turns the damper back to its safe position.
2
2.00
2.8...3 9.5...10
27.60
107.002.00
50.00 40.00
2.8...3
66.001.00
9.00
Technical drawing
6(6x) 10
239-024-20-S2
R1
Motor bl, br
S1, S2 80 1, 2, 3, 4, 5, 6
80
36
98
58 2
24
43
27 149 250 67
15
10
Technical Characteristics
Control Connecting voltage Power consumption Transformer sizing Angle of rotation Direction of rotation Running time (90) Torque Auxiliary switches Switching power Auxiliary switches Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On/Off 230 VAC (50/60 Hz) 15% Motion: 9.0 W / Power safe mode: 7,0 W 10.0 VA 100 (-5...+95) can be selected by mounting back to front Actuator: 150 s / Spring: < 20 s Actuator: 20 Nm / Spring: 15 Nm 2, position fixed to 5 and 80 250 VAC / 5.0 (2.5) A, change-over switch Cable 900 mm / 0.75 mm2 II IP54 (Cable downwards) 250 x 98 x 58 mm -30C...+50C maintenance-free 73/23/EWG, 89/336/EWG 2,500 g
239-230-20-S2
Connection scheme S1 S2 1 2 3 4 5 6
239T-230-20-S2
Connection scheme S1 S2
1 2 3 4 5 6 T
TF1
239TA-230-20-S2
Connection scheme S1 S2 1 2 3 4 5 6 TA
TF1 TF2
BU BN
BU BN
BU BN
N L
N L
N L
11
Auxiliary switches
The actuator has two position fixed auxiliary switches for indicating the damper postion. The position of the damper can be read on the scale on front of the actuator.
If 72C are reached the actuator turns the damper back to its safe position.
2
2.00
2.8...3 9.5...10
27.60
107.002.00
50.00 40.00
2.8...3
66.001.00
9.00
Technical drawing
6(6x) 10
239-230-20-S2
R1
Motor bl, br
S1, S2 80 1, 2, 3, 4, 5, 6
80
36
98
58 2
24
43
27 149 250 67
15
Stuttgart
A8
Mnchen
Balingen Karlsruhe
Schmberg
Freudenstadt
A81
Wehingen
B27
Gosheim Frittlingen Denkingen
Tuttlingen
Strasbourg
Rottweil B14
Schramberg Aldingen
Spaichingen
34
B27
Donaueschingen
Singen Zrich
Basel N1 N3