Sunteți pe pagina 1din 3

SMARTSPOT INDICATOR AMP-TRAP 2000

AJT

TIME DELAY / CLASS J


SMARTSPOT WITH MAXIMUM CIRCUIT PROTECTION Amp-trap 2000 SmartSpot AJT fuses now provide a visual open fuse indicator. With advanced material technology added to the existing product line the AJT fuse provides IEC Type 2 (No Damage) protection to main, feeder, and branch circuits, for all types of loads yet, they require only half the mounting space needed for 600VAC Class RK fuses. AJTs time delay characteristics for handling harmless in-rush currents, its current limiting ability (the most current limiting UL fuse class!), and wide range of ratings (from 1 to 600 Amperes) give excellent protection for all your applications.
Features/Benefits Solid State SmartSpot Indicator Time delay for motor starting and transformer inrush 300kA interrupting rating - self-certified, UL witnessed tests Extremely current limiting for low peak let-thru current Most current limiting UL class fuse Small footprint requires less mounting space and allows smaller, more economical fuse blocks Easy 2-to-1 selectivity for prevention of nuisance shutdowns Unique Class J dimensions prevent replacement errors High-visibility orange label gives instant recognition Metal-embossed date and catalog number for traceability and lasting identification Fiberglass body provides dimensional stability in harsh industrial settings High-grade silica filler ensures fast arc quenching Optional EI Indicator/Switch mount for AJT70 to 600 open fuse indication Ratings AC: 1 to 600A 600VAC, 200kA I.R. (self certified for 600VAC, 300kA I.R., UL witnessed) DC: 1 to 600A 500VDC, 100kA I.R. Approvals AJT (1-600): UL Listed to Standard 248-8 DC Listed to UL Standard 198L CSA Certified to Standard C22.2 No. 248.8 IEC 269-2-1 AJT (70-600) EI: UL Component Recognized DC Tested to UL Standard 198L A2

HIGHLIGHTS:

APPLICATIONS:

Smart Spot Indicator Time Delay Highly Current Limiting DC Ratings Optional Mechanical Indicator (70 to 600A fuses)

Motor Circuits Mains Feeders Branch Circuits Lighting, Heating & General Loads Transformers Control Panels Circuit Breaker Back-up Bus Duct Load Centers

SMARTSPOT INDICATOR AMP-TRAP 2000

TIME DELAY / CLASS J FUSES


Standard Fuse Ampere Ratings, Catalog Numbers
AMPERE RATING 1 1-1/4 1-1/2 1-6/10 1-8/10 2 2-1/4 2-1/2 2-8/10 3 3-2/10 3-1/2 4 CATALOG NUMBER AJT1 AJT1-1/4 AJT1-1/2 AJT1-6/10 AJT1-8/10 AJT2 AJT2-1/4 AJT2-1/2 AJT2-8/10 AJT3 AJT3-2/10 AJT3-1/2 AJT4 AMPERE RATING 4-1/2 5 5-6/10 6 6-1/4 7 8 9 10 12 15 17-1/2 20 CATALOG NUMBER AJT4-1/2 AJT5 AJT5-6/10 AJT6 AJT6-1/4 AJT7 AJT8 AJT9 AJT10 AJT12 AJT15 AJT17-1/2 AJT20 AMPERE RATING 25 30 35 40 45 50 60 70 80 90 100 110 CATALOG NUMBER AJT25 AJT30 AJT35 AJT40 AJT45 AJT50 AJT60 AJT70 AJT80 AJT90 AJT100 AJT110 AMPERE RATING 125 150 175 200 225 250 300 350 400 450 500 600 CATALOG NUMBER AJT125 AJT150 AJT175 AJT200 AJT225 AJT250 AJT300 AJT350 AJT400 AJT450 AJT500 AJT600

AJT
Recommended Fuse Blocks With Box Connectors for Amp-trap Class J Fuses
Fuse Ampere Rating 0-30 31-60 61-100 101-200 201-400 401-600 Catalog Number 600V OR LESS 1 Pole 3 pole US3J1I US6J1I 61036J 62001J 64031J 6631J US3J3I US6J3I 61038J 62003J 64033J 6633J

A variety of pole configurations and termination provisions is available.

Note: Indicator Not availible (1-7a)

1-60A 70-600A

Dimensions
AMPERE RATING 1-30 31-60 61-100 101-200 201-400 401-600 A In. 2-1/4 2-3/8 4-5/8 5-3/4 7-1/8 8 mm 57 60 117 146 181 203 In. 13/16 1-1/16 1-1/16 1-5/8 2-1/8 2-1/2 B mm 21 27 27 41 54 64 In. 1/8 3/16 1/4 3/8 C mm 3.2 4.8 6.3 9.5 In. 3/4 1-1/8 1-5/8 2 D mm 19 29 41 51 In. 1 1-3/8 1-7/8 2-1/8 E mm 25 35 48 54 In. 3-5/8 4-3/8 5-1/4 6 F mm 92 111 133 152 In. 3/8 3/8 17/32 11/16 G mm 10 10 14 18 In. 9/32 9/32 13/32 17/32 H mm 7 7 10 13

Optional Indicator/Microswitch Mount (EI) dimensions:


Note: Fuses with the EI option will receive the AOS-S or AOS-Q Add-On-Switch

CATALOG NUMBER AJT(70-100)-EI AJT(110-200)-EI AJT(225-400)-EI AJT(450-600)-EI

A 2.80 (71.0) 3.22 (81.8) 3.24 (82.2) 3.61 (91.8)

A3

SMARTSPOT INDICATOR AMP-TRAP 2000

TIME DELAY / CLASS J FUSES


AJT1 to 600

AJT

Melting Time Current Data, 600V Fuses

Time in Seconds

Peak Let-Thru Current Data AJT30 to 600, 600 Volts AC


Maximum Instantaneous Peak Let-Thru Amperes

Note: See Application Tables page L9 for Three Phase Class J AJT Fuses.

Available Current in RMS Symmetrical Amperes

A4

Current in Amperes