SECTION P15007 SPLIT AIR CONDITIONI CONDITIONING UNITS


1.0
1.1

GENERAL
DESCRIPTION a) The following specifications are the Particular Requirements for the Split Air Conditioning Units, which supplement the Requirements contained in the Units, other Sections of ADSSC General Specifications. Extent of air conditioning work required by this Section is shown on drawings and schedules and is indicated by the requirements of this Section. Regulatory Requirements ory i. ARI Compliance. Provide capacity ratings for air conditioning equipment in accordance with Air Conditioning and Refrigeration Institute ARI 210 "Standard for Unitary Air Conditioning Equipment". ASHRAE Compliance. Construct refrigerating system of condensing units in accordance with American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) Standard ANSI/ASHRAE 15 "Safety Code for Mechanical Refrigeration". UL Compliance. Provide condensing units which are listed by Underwriters Laboratories (UL) and have UL label affixed.

b) c)

ii.

iii. 1.2

QUALITY ASSURANCE a) b) All products shall be new. Products shall be of an experienced manufacturer. i. ii. iii. iv. Manufacturer must have similar equipment installed and successfully operating in a desert climate for a minimum of five years. for Must demonstrate equal or larger capacity operating installations using similar equipment. Provide names and phone numbers of contacts at referenced installation to verify performance. Demonstrate to satisfaction of Engineer that equipment to be that provided is equal to that specified.

2.0
2.1

PRODUCTS
GENERAL a) Provide factory factory-assembled and tested air-cooled condensing units as cooled indicated. Include the following: i. ii. Compressors Condensers

Page 1 of 5 Addendum 4

Abu Dhabi Sewerage Services Company (ADSSC) Supply Department

Tender No. O-11008 11008 Asset Enhancement Scheme, Stage in Abu Dhabi, Stage-1 Area 2 Construction of Deep Trunk Sewer from MPS 14 to MPS 8 including Interception of Sewers and Abandonment of Existing Pump Stations

iii. iv. v. vi. vii. b) c)

Evaporator Coil Condenser and Evaporator Fans Refrigeration and Temperature controls Filters Dryers

Provide capacity as scheduled. Provide necessary compressor oil, refrigerant, refrigerant and condensate pipes, filter drier, moisture indicator sight glass, high pressure switch (manual reset) low pressure switch (automatic reset), pressure relief device, liquid line ssure shut off valve, suction and discharge shutoff valves and line service gauge ports, suction line accumulator, check valve, and room thermostat assembly as a complete package. Factory wire all controls and place in a readily accessible location. all Testing i. ii. iii. Test and rate units according to ARI standard 240 conditions and certified under the ARI certification programme. Units to carry ARI certification seal. Ground units to meet UL and NEC standards for servicing. standards

d) e)

2.2

CASING a) Provide 18 gauge galvanized steel casing, bonderized and finished with baked enamel. i. ii. iii. iv. b) c) d) Insulate with minimum 12mm insulation te Provide knockout for electrical and piping connections. electrical Provide condensate drain connection. de Include lift lifting provisions to facilitate rigging.

Provide removable panel for inspection and access to internal parts and controls Provide base with mounting holes. Provide brass service valves, fittings and gauge ports on exterior of casing. Design to withstand U.S. Federal Test Method Standard No. 141 (Method 6061) 500 hour salt spray test.

2.3

COMPRESSOR a) b) Provide welded hermetically sealed compressors with built overloads and built-in vibration isolation and crankcase heater. Provide for compressor motor, thermal and current sensitive overload device, current-sensitive internal high-pressure protection, high and low pressure cutout switches, pressure

Page 2 of 5 Addendum 4

Abu Dhabi Sewerage Services Company (ADSSC) Supply Department

Tender No. O-11008 11008 Asset Enhancement Scheme, Stage in Abu Dhabi, Stage-1 Area 2 Construction of Deep Trunk Sewer from MPS 14 to MPS 8 including Interception of Sewers and Abandonment of Existing Pump Stations

start capacitor and relay, contractor, and temperature actuated switch and timer to prevent compressor rapid cycle. c) 2.4 Provide vibration isolation as specified within these specification documents. specified

CONDENSER a) Construct coil of seamless copper or aluminium tubes with mechanically bonded aluminium plate fins. Coat all coils to prevent corrosion, Technicoat 10-1 phenolic coating, ACRA - CLAD, or approved equal. 1 i. ii. iii. iv. b) Use brazed tubing joints. Provide with liquid accumulator and liquid sub cooler. Provide weatherproof fused disconnect at the unit. Leak test coils at 1034 kPa and pressure test unit at 3310 kPa.

Provide aluminium alloy propeller fan, direct driven, with p permanently lubricated totally enclosed fan motor with thermal overload protection. Motor to be class F insulation, lP lP-55 protection rated for continuous operation at maximum conditions. Include suitable safety guards.

2.5

EVAPORATOR FANS a) b) Use forward curved c centrifugal evaporator fans Provide either belt driven fans with adjustable sheaves or direct driven fans. Motors shall be to class F insulation, IP55 protection. Use permanently lubricated motor bearings. Include fused disconnect.

c) 2.6

FILTERS a) b) Provide cleanab filters, washable or vacuum cleanable. cleanable Polyurethane construction or approved equal.

2.7

REFRIGERANT PIPING a) Use seamless refrigeration copper tubing. i. ii. b) Sized by equipment manufacturer. Match unit connection sizes.

Provide continuous thermal insulation. i. ii. iii. iv. Closed cell type. Minimum 15 mm thickness. Design temperature range: -20 to +100 C C. Meet NFPA 90 requirements for flame spread and smoke generation.

c)

Coating.

Page 3 of 5 Addendum 4

Abu Dhabi Sewerage Services Company (ADSSC) Supply Department

Tender No. O-11008 11008 Asset Enhancement Scheme, Stage in Abu Dhabi, Stage-1 Area 2 Construction of Deep Trunk Sewer from MPS 14 to MPS 8 including Interception of Sewers and Abandonment of Existing Pump Stations

i. ii. iii.

Surfaces to be cleaned and degreased. Smooth surfaces etched with wire wool and all oxidation removed using suitable abrasives. Apply a two component polyamide epoxy primer with brush or airless spray to a thickness of 50 micron minimum. Apply two coats of a two component high build acrylic - urethane two-component finish over properly cured primer. Each coat shall pr provide a minimum thickness of 50 microns. Apply by brush or airless spray.

2.8

CONDENSATE DRAIN PIP PIPING a) Use PVC piping as specified within these specification documents.

3.0
3.1

EXECUTION
INSPECTION a) b) Examine areas and conditions under which the air conditioning equipment is to be installed. Do not proceed with work until unsatisfactory conditions have been corrected in a manner acceptable to Installer.

3.2

INSTALLATION OF SPLI COOLING UNITS SPLIT a) Install split cooling air conditioning equipment in accordance with manufacturers installation instructions Install units plumb and level, firmly urers anchored in locations indicated, and maintain manufacturers recommended clearances. Electrical i. ii. Install electrical devices furnished by manufacturer but not factory mounted. Furnish elec electrical field-wiring diagrams to Electrical Installer for power wiring wiring to air conditioning equipment, and control wiring for field fieldmounted controls. Provide positive equipment ground for components. Verify that electrical wiring installation is in accordanc with accordance manufacturer's submittal and the installation requirements.

b)

iii. iv. c)

Condensing and Fan Coil Units. i. Connect pre charged refrigerant tubing to unit's quick pre-charged quick-connect fitting.

d)

Run tubing so as not to interfere with access to unit. i. Collect condensate and pipe to nearest plant drain or the location shown on the drawings.

e) 3.3

Install furnished accessories.

START UP OF SPLIT CO COOLING UNITS

Page 4 of 5 Addendum 4

Abu Dhabi Sewerage Services Company (ADSSC) Supply Department

Tender No. O-11008 11008 Asset Enhancement Scheme, Stage in Abu Dhabi, Stage-1 Area 2 Construction of Deep Trunk Sewer from MPS 14 to MPS 8 including Interception of Sewers and Abandonment of Existing Pump Stations

a) b)

Start-up air conditioning equipment, in accordance with manufacturers startup up instructions, and in the presence of manufacturer's representative. representative. Test controls and demonstrate compliance with requirements. Replace demonstrate damaged or malfunctioning controls and equipment.

END OF SECTION