Documente Academic
Documente Profesional
Documente Cultură
The protection engineer of today has a wide variety of test sets available at their disposal for their secondary injection testing needs. Much like motorcars they range greatly in performance and functionality. Ranging from the Volkswagen (Sverker and T&R) sets to the higher end Lamborghini (RES-APTS) & Ferrari (Omicron) Priced accordingly! Without question the Omicron & APTS test sets tower above the lower end Sverker and T&Rs in terms of functionality. With their multiple variable current & voltage outputs, customizable test procedures and multiple input/output contacts. They are unparalleled when it comes to testing modern electronic relays, transformer differential & modern distance protection schemes. However, can we rely on these test sets when it comes to testing the humble old Electro-Mechanical (EM) Current Driven Induction Disk Relay? Why should testing EM current driven relays cause issue for concern? Well using a test set out of the box to inject such a relay, especially a high impedance current relay, causes the output waveform of the test set to be distorted. The cause of this distortion is the generation of Harmonics. A Harmonic is a sinusoidal component of a periodic wave having a frequency that is an integral multiple of the fundamental frequency. For example the UK mains frequency of 50Hz would have a 3rd Harmonic of 150Hz a 5th Harmonic of 250Hz etc. These Harmonics superimpose themselves upon the natural sine wave. This imposition summates with the fundamental sinusoidal test set injection signal to produce a distorted waveform (figure 1).
Sometimes the distortion is so severe that the timing tests we carry out on the relay are no longer reliable. We therefore need to consider the magnitude of waveform distortion when performing secondary injection timing tests upon EM protection relays. We are able to quantify & compare the magnitude of the sine wave distortion using a standard known as the Harmonic Distortion Factor (HDF). This factor is an Institute of Electrical & Electronic Engineers (IEEE) Standard - 519-1992, defined as: HDF = Square Roof Of (sum of squares of amplitudes of all harmonics) x 100% (square of amplitude of fundamental) This report will examine the HDF experienced by a variety of test sets & filter configurations. We also see how the distortion impacts upon the secondary injection timing results.
The
Testing
From
practical
protection
testing
experience
it
has
been
observed
that
the
1A
CDG16
Induction
Disk
Earth
Fault
Relay
causes
the
most
severe
secondary
injection
testing
sine
wave
distortions
&
recorded
operation
timing
errors.
It
was
therefore
decided
that
the
CDG16
would
be
an
ideal
relay
to
utilise
in
the
test
set
evaluation
tests.
The
relay
was
set
to
the
minimum
setting,
I.E
0.1A
Minimum
Operation/Creep
Current
with
a
Time
Multiplier
(TM)
of
1.0.
The
relay
was
then
injected
with
a
variety
of
test
sets
currently
employed
within
Electricity
Northwest.
A
variety
of
configurations
were
employed
with
the
injection
procedures,
such
as
no
waveform
filtration,
primary
and
secondary
injection
resistance,
&
secondary
current
filtering
with
the
T&R
100AD
filter
(appendix
A).
The
operating
time
&
waveform
characteristics
we
recorded
over
the
injection
cycle
for
each
configuration
of
a
2x
operation
current
timing
test
(0.2A
Injection).
The
injected
current
level
was
set
using
a
calibrated
external
Fluke
289
multimeter
connected
directly
in
series
with
the
relay
coil
(Not
the
integral
test
set
meters).
The
waveform
was
recorded
on
a
calibrated
Dranetz
PX5
power
monitor
using
a
clip
a
0-10A
2510
clip-on
ammeter
&
direct
voltage
sensing.
Note:
The
ideal/theoretical
operating
time
@
2x
(1.0TM)
should
be
10.03
sec
Results
The
following
secondary
injection
configuration
waveforms
&
timings
were
evaluated:
Test
00
T&R
100ADM
No
Filter
Op
Time
@
2x
=
14.78sec
Test
01
T&R
100ADM
+
100ADM
Filter
Op
Time
@
2x
=
10.35sec
Test
02
Sverker
760
No
Filter
Op
Time
@
2x
=
15.32sec
Test
03
Sverker
760
+
Secondary
Resistors
(126.5
OHM)
Op
Time
@
2x
=
13.69sec
Test
04
Sverker
760
+
Primary
Resistor
(100
OHM)
Op
Time
@
2x
=
15.27sec
Test
05
Sverker
760
+
Primary
(100
OHM)
+
Secondary
R
(126.5
OHM)
Op
Time
@
2x
=
13.44sec
Test
06
Omicron
256
(280VA
@7.5A
40V
RMS
Output
/
No
Filter)
Op
Time
@
2x
=
10.67sec
Test
07
Sverker
760
+
T&R
100ADM
Filter
Op
Time
@
2x
=
10.31sec
Test
08
Sverker
650
No
Filter
Op
Time
@
2x
=
15.28sec
Test
09
Sverker
650
+
T&R
100ADM
Filter
Op
Time
@
2x
=
10.50sec
Test
10
APTS
3
Phase
(No
Filter)
Op
Time
@
2x
=
11.80sec
Test
11
APTS
1
Phase
Parallel
(No
Filter)
Op
Time
@
2x
=
15.08sec
Test
12
APTS
1
Phase
Series
(No
Filter)
Op
Time
@
2x
=
9.85sec
Note:
The
sampled
waveforms
for
each
of
these
configurations
(including
voltage
&
current
harmonic
content)
may
be
observed
over
the
following
pages.
Date
21/3/11
Issued by
D Rothwell
Report No.:
CDG00
Amps
13:00:25.00
Waveform harmonics
% 25
20
15
10
H02 H03
H04 H05
H06 H07
H08 H09
H10 H11
H16 H17
H18 H19
H20 H21
H22 H23
H24 H25
Date
21/3/11
Issued by
D Rothwell
Report No.:
CDG01
13:38:25.00
Waveform harmonics
% 35 30 25 20 15 10 5 0
H02 H03
H04 H05
H06 H07
H08 H09
H10 H11
H16 H17
H18 H19
H20 H21
H22 H23
H24 H25
Date
21/3/11
Issued by
D Rothwell
Report No.:
CDG02
Amps
14:11:32.00
Waveform harmonics
% 25
20
15
10
H02 H03
H04 H05
H06 H07
H08 H09
H10 H11
H16 H17
H18 H19
H20 H21
H22 H23
H24 H25
Date
21/3/11
Issued by
D Rothwell
Report No.:
CDG03
Amps
14:35:59.00
Waveform harmonics
% 20
15
10
H02 H03
H04 H05
H06 H07
H08 H09
H10 H11
H16 H17
H18 H19
H20 H21
H22 H23
H24 H25
Date
21/3/11
Issued by
D Rothwell
Report No.:
CDG04
Amps
08:34:18.00
Waveform harmonics
% 25
20
15
10
H02 H03
H04 H05
H06 H07
H08 H09
H10 H11
H16 H17
H18 H19
H20 H21
H22 H23
H24 H25
Date
22/3/11
Issued by
D Rothwell
Report No.:
CDG05
Amps
Waveform harmonics
% 20
15
10
HG02 HG03
HG04 HG05
HG06 HG07
HG08 HG09
HG10 HG11
HG16 HG17
HG18 HG19
HG20 HG21
HG22 HG23
HG24 HG25
Date
22/3/11
Issued by
D Rothwell
Report No.:
CDG06
09:35:48.00
Waveform harmonics
% 150 125 100 75 50 25 0
H05 H10
H15 H20
Date
22/3/11
Issued by
D Rothwell
Report No.:
CDG07
10:51:09.00
Waveform harmonics
% 40 35 30 25 20 15 10 5 0
H02 H03
H04 H05
H06 H07
H08 H09
H10 H11
H16 H17
H18 H19
H20 H21
H22 H23
H24 H25
Date
22/3/11
Issued by
D Rothwell
Report No.:
CDG08
Amps
13:39:10.04
Waveform harmonics
% 25
20
15
10
H02 H03
H04 H05
H06 H07
H08 H09
H10 H11
H16 H17
H18 H19
H20 H21
H22 H23
H24 H25
Date
22/3/11
Issued by
D Rothwell
Report No.:
CDG09
14:10:36.00
Waveform harmonics
% 35 30 25 20 15 10 5 0
HG02 HG03
HG04 HG05
HG06 HG07
HG08 HG09
HG10 HG11
HG16 HG17
HG18 HG19
HG20 HG21
HG22 HG23
HG24 HG25
Date
22/3/11
Issued by
APTS - 3 Phase
Event Details/Waveforms
50 Volts 25 0 -25 -50 AV 0.4 0.2 Amps 0.0 -0.2 -0.4 AI 14:24:24.10 22/03/2011 Tuesday 14:24:24.15 14:24:24.20 14:24:24.25
D Rothwell
Report No.:
CDG10
14:24:24.29
Waveform harmonics
% 35 30 25 20 15 10 5 0
H02 H03
H04 H05
H06 H07
H08 H09
H10 H11
H16 H17
H18 H19
H20 H21
H22 H23
H24 H25
Date
22/3/11
Issued by
D Rothwell
Report No.:
CDG11
Amps
14:30:07.00
Waveform harmonics
%
25
20
15
10
H02 H03
H04 H05
H06 H07
H08 H09
H10 H11
H16 H17
H18 H19
H20 H21
H22 H23
H24 H25
Date
22/3/11
Issued by
D Rothwell
Report No.:
CDG12
Amps
Volts
14:33:28.00
Waveform harmonics
% 40
30
20
10
H02 H03
H04 H05
H06 H07
H08 H09
H14 H15
H16 H17
H18 H19
H20 H21
H22 H23
H24
Conclusions
The
most
significant
relationship
to
note
from
these
tests
is
that
of
operation
time
Vs.
Current
HDF.
Generally
speaking
the
greater
the
distortion
of
the
test
set
current
waveform,
the
greater
the
inaccuracy
of
the
current
driven
relay
timing
will
be.
The
Voltage
HDF
also
has
some
impact,
but
it
is
marginal
compared
to
the
current
waveform.
The
two
exceptions
to
this
general
rule
are
the
APTS
and
Omicron
sets.
Even
with
large
waveform
distortion
factors,
both
of
these
test
sets
if
selected
to
the
appropriate
output
mode,
were
capable
of
providing
accurate
operation
times
on
the
CDG16
relay.
Due
to
the
severe
distortion
of
the
waveforms,
there
is
either
an
ingenious
software
algorithm
manipulating
the
output
amplifiers
in
place,
producing
an
accurate
RMS
sine
waveform
value,
or
both
tests
were
a
fluke.
To
determine
accuracy
of
operational
timing
for
these
electronically
controlled
test
sets,
both
should
be
examined
separately
at
a
variety
of
values
(I.E.
plotting
the
full
IDMT
curve).
Utilising
the
primary
and
secondary
resistors
available
to
the
Sverker
range
of
test
sets
only
marginally
reduced
harmonics
&
improved
timing
results
on
the
CDG16
relay.
It
was
noted
however
that
these
resistors
did
greatly
increase
the
current
resolution/sensitivity
of
the
sets.
We
can
unequivocally
identify
from
these
results
is
that
all
non-electronically
controlled
test
sets
should
be
used
with
the
addition
of
a
filter
such
as
the
T&R
100ADM
employed
in
these
tests.
All
of
the
test
sets
coupled
with
the
filter
produced
results
within
5%
of
the
ideal/theoretical
timing
value.
Excluding
the
filter
their
timing
deviations
ranged
from
34.0-52.3%.
The conclusions of this report have been derived from the worst-case secondary injection scenario using the CDG16 EF relay. Although this was a great starting point for investigating a range of test sets, test findings may prove more fruitful using EM relays of a lesser impedance. The next series of test aims to examine the functionality of the same test set configurations with a commonly placed 5A distribution EM IDMT relay. Following these tests, self-powered protection relays such as the VIP300 shall be examined.
Appendices
100ADM-F
Resistor Box
RB10
Filtered
Features Forces test current to a sinusoid Improves timing accuracy when testing electromechanical relays 0.25A-100A ranges High overload capability 50/60Hz operating frequency High efficiency
The 100ADM-F filter unit reduces the level of current harmonics when testing electro-mechanical protection relays. It is designed for use with our range of secondary injection test sets. All electromechanical protection relays have iron cores that saturate and distort the test current under high overload test conditions. This distortion causes significant errors in the measured trip time of these relays during testing. Distortion of the waveform can be a particular problem with disc induction type over-current and sensitive earth fault relays. For example, testing a CDG11 disc induction over-current relay without a filter causes significant timing errors. The results below show the errors for a 1.3s 1A CDG11 overcurrent relay on its 0.5A plug setting, tested at 5A. Current No Filter With Filter 5A 5A THD 34.5% 6.12% Trip time 1.54s 1.30s Error 18.5% 0%
Features Improves current control into low impedance loads Particularly suitable for solid state relays 0.51666.5 in 8 steps Maximum current 0.210A Thermal cutout Compact & lightweight
The RB10 resistor box is used in conjunction with a current injection unit when testing low impedance relays and trips, allowing finer control of the current. The unit is designed for use with the 100ADM and 200ADM, but may be used with any suitable current source. The unit has eight resistance ranges with a maximum power dissipation of 50W for any one resistor.
Range Continuous current 0.5 5A 1.5 3.5A 6.5 1.5A 16.5 1A 66.5 0.5A 166.5 0.35A 666.5 0.15A 1666.5 0.1A *3 minutes on/8 minutes off Intermittent current* 10A 7A 3A 2A 1A 0.7A 0.3A 0.2A Maximum voltage 5V 10V 25V 50V 100V 150V 250V 250V
The RB10 is supplied in a robust aluminium case, and all connections are made by industry standard 4mm safety sockets. The RB10 has fuse and over-temperature protection.
The 100ADM-F has nine current ranges covering 0.25A to 100A and is supplied in an insulated case complete with protective cover and carrying strap.
100ADM-F Specification
Current Waveforms
The waveforms below show the current and voltage for a disc induction type relay supplied from a 100ADM.
RB10 Specification
Resistance Ranges and Ratings The RB10 has eight resistance ranges.
Range 0.5 1.5 6.5 16.5 66.5 166.5 666.5 1666.5 Continuous current 5A 3.5A 1.5A 1A 0.5A 0.35A 0.15A 0.1A Intermittent current* 10A 7A 3A 2A 1A 0.7A 0.3A 0.2A Maximum voltage 5V 10V 25V 50V 100V 150V 250V 250V
Voltage
Current Disc induction relay without filter unit Disc induction relay with filter unit
Range Selection
The appropriate range is selected by 4mm safety sockets on the front panel of the unit.
Temperature Range
Storage Operating -20C to 60C 0C to 45C
Protection
The unit has over-temperature protection and the common terminal is fused with a T10A fuse.
Dimensions
220mm x 163mm x 72mm including earth teminal
Frequency
The unit may be used at either 50Hz or 60Hz, selectable by a switch on the front panel.
Range Selection
The lower ranges (0.25A-50A) are selected by a switch, and the highest current range (100A) is selected by a terminal.
Current Monitor
A current monitoring output is provided that gives an output of 0100mA corresponding to the rated current for the range.
Temperature Range
-20C to 60C 0C to 45C
Dimensions
340mm x 230mm x 330mm
Weight
15.6kg
Accessories
Current monitor plug and lead
Optional Accessories
100AL lead set
Note: Due to the companys continuous research programme, the information above may change at any time without prior notificatio n. Please check that you have the most recent data on the product.
T&R Test Equipment Ltd, 15-16 Woodbridge Meadows, Guildford, Surrey, GU1 1BJ, UK Tel: +44 (0)1483 207428 Fax: +44 (0)1483 511229 email: sales@trtest.com
10
www.trtest.com