Documente Academic
Documente Profesional
Documente Cultură
POWER ON
ALARMS
TRANSMIT
FAULTS
TRANSMIT STORED
ENTER CLEAR
TPN: 505-003080-001
ii
Notice
This manual and its contents are proprietary to Tiernan Communications, Inc. (Tiernan) and are intended solely for the contractual use of its customers for no other purpose than to install and operate the equipment described herein. This manual and its contents shall not be used or distributed for any other purpose and/or otherwise communicated, disclosed, or reproduced, in any way whatsoever, without prior written consent of Tiernan. Only experienced personnel should install and/or operate this equipment. Prior to installing or operating any of the equipment or parts thereof, personnel must carefully read and understand all of the contents of this manual. To properly install and operate this equipment and/or all parts thereof, personnel must strictly and explicitly follow all of the instructions in this manual. FAILURE TO COMPLETELY READ AND FULLY UNDERSTAND AND FOLLOW ALL OF THE CONTENTS OF THIS MANUAL PRIOR TO INSTALLING AND/OR OPERATING THIS EQUIPMENT, OR PARTS THEREOF, MAY RESULT IN INJURY TO PERSONNEL AND/OR DAMAGE TO THE EQUIPMENT, OR PARTS THEREOF. Tiernan does not assume any liability arising out of the application or use of any products, component parts, circuits, software, or firmware described herein. Tiernan further does not convey any license under its patent, trademark, copyright, or commonlaw rights nor the similar rights of others. Tiernan further reserves the right to make any changes in any products, or parts thereof, described herein without notice. Copyright 1996-1999 Tiernan Communications, Inc.
iii
Restricted Rights
The contents are provided with RESTRICTED RIGHTS. Use, duplication, or disclosure by the government is subject to restrictions as set forth in subparagraph (c) (1) (ii) of the Rights in Technical Data and Computer Software [OCT. 1988] clause at DFARS 252.2277013 and subparagraphs (a) through (d) of the Commercial Computer SoftwareRestricted Rights [JUNE 1987] clause at FAR 52.22719, as applicable. Manufacturer is Tiernan Communications, Inc., 5751 Copley Drive, San Diego, CA 92111 U.S.A.
No Warranty
The contents of this manual are provided as is without warranty of any kind, either expressed or implied, including, but not limited to, the implied warranties of merchantability, fitness for a particular purpose, and noninfringement. The contents of this publication could include technical inaccuracies or typographical errors. Changes are periodically added to the information herein. These changes will be incorporated in new editions of this manual. Tiernan may make improvements and/or changes in the product(s) and/or the program(s) described in this manual at any time without notice.
iv
Limitation of Liability
In no event will Tiernan be liable for direct, indirect, special, incidental, economic, cover, or consequential damages arising out of the use or inability to use the contents even if advised of the possibility of such damages. Some jurisdictions do not allow the exclusion or limitation of implied warranties, or the limitation of liability for incidental or consequential damages, so the above limitation or exclusion may not apply to you. For further information on legal and intellectual property matters, contact Tiernan Communications Corporate Counsel.
DANGER!
The TVRM75 Satellite Modulator contains no userserviceable parts. Do not attempt to service this product yourself. Any attempt to do so will invalidate any and all warranties.
Contents
Introduction...........................................................................vii
About this Manual....................................................................................vii Warning Notices .......................................................................................vii Revision Record ...................................................................................... viii TVRM75 Shipping Cartons and Packing Materials .............................. ix Packing Slip ................................................................................................ ix Shipping Errors .......................................................................................... ix Cartons and Packing Materials................................................................ ix Equipment Repacking Instructions......................................................... ix
Chapter 1
OVERVIEW ............................................................................13
Introduction ............................................................................................... 13 Modulator Assemblies ............................................................................. 15 Modulator Specifications ......................................................................... 15 Fault Tree ................................................................................................... 19
Chapter 2
INSTALLATION .....................................................................21
Unpacking.................................................................................................. 21 Installation ................................................................................................. 22 Remove and Install Data Interfaces ....................................................... 24 External Connections ............................................................................... 25 Remote Connector & Pinout (J1) ............................................................ 26 Fault Connector (J2).................................................................................. 27 Transmit IF Output (CP1)........................................................................ 28 AC Power................................................................................................... 28 Ground (GND) .......................................................................................... 28 Proper Operations for Emissions (CE)................................................... 28
Chapter 3
OPERATION ..........................................................................29
Introduction ............................................................................................... 29 Front Panel................................................................................................. 30 Front Panel Keypad .................................................................................. 32 Menu System ............................................................................................. 33 Main Menu................................................................................................. 34 Configuration Menus ............................................................................... 35 Faults/Alarms Menus.............................................................................. 44 Utility Menus............................................................................................. 51 Defaults after Firmware Upgrade or Hard Reset................................. 63
Contents
vi
Appendix A
DATA INTERFACES..............................................................67
Description................................................................................................. 67 Software Requirement.............................................................................. 68 RS-422 Parallel/Serial Interface .............................................................. 68 Description................................................................................................. 69 Configuration ............................................................................................ 70 User Interfaces ........................................................................................... 72 Serial, J4, DB25 Female (EIA-530 Serial Data Interface) ...................... 75 RS-422 Front Panel Menus....................................................................... 78 RS-422 Remote Commands ..................................................................... 80 ASI & RS-422 Data Interface.................................................................... 82 Description................................................................................................. 83 User Interfaces ........................................................................................... 86 ASI & RS-422 Front Panel Menus ........................................................... 88 ASI & RS-422 Remote Commands.......................................................... 90
Appendix B
Appendix C
vii
Introduction
This section describes the TVRM75 manual conventions.
Warning Notices
HAZARD:
Throughout this manual you will find three types of warning notices that are designed to assist you in identifying important information. An example of each is provided below.
The Hazard symbol identifies the possibility of electric shock when you perform an operation with the TVRM75 or if you do not use the TVRM75 according to instructions.
DANGER!
CAUTION:
The Caution symbol identifies an area that requires special attention to detail or poses the possibility of injury, excluding injury resulting from electric shock.
CAUTION!
Introduction
viii
NOTE:
The Note symbol identifies points of interest or information relevant to a procedure or process.
NOTE...
Revision Record
Revision Record
TPN: 5050030800001 Revision A, 12/20/96
Initial release of the manual.
Revision B, 03/04/98
Technical and editorial revisions. Compatible with firmware v.4.1.1+
Revision C, 12/11/98
Updated manual to reflect 8PSK options, features, and functionality. Compatible with firmware v.5.3.1+
Revision D, 01/11/99
Updated Chapter 3 added the Tx Coding Format command to the Configuration Interface Menu and updated the RS-422 Utility Interface Menu; updated Appendix A corrected the ASI and RS-422 Specifications table and the ASI Loopback J6/J7 BNC Output Connectors description. Compatible with firmware v.5.3.1+
Revision E, 6/21/99
Updated telephone and fax numbers to reflect new area code. Made minor format revisions. Compatible with firmware v.5.3.1+
ix
Shipping Errors
2.
3.
Introduction
x
4.
If you believe the carton or packing materials will not properly protect the equipment during shipping, contact Tiernan Communications Product Support.
If the suspension frames are not packed into the shipping carton as instructed below, the equipment may be severely damaged during shipping and handling.
CAUTION!
2.
xi
3.
4.
Place the second suspension frame into the shipping carton with the plastic film side facing down towards the top of the equipment. The plastic attached to the suspension frame must be placed against the top of the equipment, so that the equipment is fully suspended between the first suspension frame and the second suspension frame. When you place the second suspension frame on top of the equipment, the second suspension frame will extend higher than the top edge of the shipping carton; however, when you close the carton, the second suspension frame will easily fit into the carton. The pressure applied to the second suspension frame will help hold the equipment in place between the two suspension frames. Close the carton, and reseal the carton with adhesive tape. Once the carton is sealed, the packing materials create tension around the equipment that holds the equipment securely between the two plastic sheets and safely away from shocks and vibrations.
Introduction
xii
Introduction
13
Chapter 1
OVERVIEW
This chapter provides a product overview, a list of the internal assemblies, and the specifications for the TVRM75 satellite modulator
Introduction
The TVRM75 is a programmable, variable-rate satellite modulator used for digital video and high-speed data applications. The modulator supports open network modes compliant with the ETSI EN 300 421/prEN 301 210 specification for Digital Video Broadcasting (DVB) by satellite.
POWER ON
ALARMS
TRANSMIT
FAULTS
TRANSMIT STORED
ENTER CLEAR
SYNC H AND R A N D O M IZ E
RS CODER AND IN TE R LE AV E R
V IT E R B I C O D E R AND M A P P IN G
TX IF
S Y N T H E S IZE R
R E M O TE P O R T A N D FA U LTS
The modulator utilizes a plug-in data interface module installed in the rear of the chassis. The data interface module provides flexible adaptation to the various physical and electrical interfaces found in the communications industry. Refer to Appendix A for a detailed description of the data interface module. The data rate of the modulator is programmable from 1.5 to 100 Mbit/s. The maximum symbol rate is 37.5 Msym/s. The minimum symbol rate is limited by the minimum 1.5 Mbit/s data rate.
OVERVIEW
14 Chapter 1
Modulation formats include QPSK, 8PSK, and a future option for 16QAM. Operation is based upon the DVB/DBS standard for QPSK and 8PSK. Table 1-1 lists the minimum and maximum data and symbol rates for each code rate at the Tiernan default framing type 188. See the specifications section for the maximum data rate limits for framing types 187 and 204.
The modulator incorporates concatenated error correction coding for improved signal quality. With concatenated coding, an outer ReedSolomon codec is used in tandem with an inner Viterbi or trellis type codec. The Reed-Solomon coding is DVB (based on 188, 204, 8 type code), while the Viterbi and trellis codes are based upon a constraint length K = 7 convolutional coding. This combination significantly reduces the required operating power of the satellite system. The modulator is a complete, self-contained unit in a standard, oneunit (1U) 19 rack-mountable enclosure. It includes a backlit LCD display and a 6-button keypad for user control. A status and control port (available through a 9-pin D connector at the rear of the chassis) provides either serial RS-232 or RS-485 for remote control applications. A second rear-panel 9-pin D connector provides fault/alarm status. The unit is designed to meet stringent safety and RF emissions standards, including CE Mark certification. See Chapter 2 for information regarding proper operation for CE emissions.
Modulator Assemblies
15
Modulator Assemblies
TVRM75 QPSK Modulator with an ASI and RS-422 Serial Interface TVRM75 QPSK Modulator with an RS-422 Serial/Parallel Interface TVRM75 Modulator with 8PSK and an ASI and RS-422 Serial Interface
Modulator Specifications
General Specifications Transmission Format Data Rate Symbol Rate Range
OVERVIEW
16 Chapter 1
Data Rate Tolerance Modulation Type & Inner Code Rate Outer Code Rate (Reed-Solomon) Interleaving Spectral Shaping Scrambling Front Panel Interface M&C Interface Fault Interface Input Power Physical: Size Weight Environmental Temperature Humidity Modulator Specifications Transmit IF Output
Depth 12, per EN 300 421 and prEN 301 210 Square-root raised cosine, = 0.35 per EN 300 421 and prEN 301 210 EN 300 421, prEN 301 210, or none Keypad + LCD with backlighting RS-232/RS-485, 9-Pin D female, serial, asynchronous FORM-C, 9-Pin D female 90 to 264 VAC, 47 to 63 Hz Universal Type, 50W Maximum 19 W x 1.75 H x 14 D (1RU) < 10 lbs. 0 to +50C (Operating) -40 to +70C (Storage) < 90%, non-condensing 50 to 180 MHz, 2.5 kHz steps -20 to +5 dBm in 0.1 dB steps ( 0.5 dB accuracy) 18 dB return loss minimum Refer to Table 1 75 50 BNC, female -55 dBc minimum in 4 kHz bandwidth relative to unmodulated carrier -60 dBm minimum when TX carrier = OFF -36 dBc maximum +/- 10 ppm
Modulation and Coding Formats Transmit IF Impedance Optional Transmit IF Impedance IF Output Connector Transmit Spurious Transmit Carrier Isolation AC Line Spurious Reference Stability
Modulator Specifications
17
Amplitude and Phase Imbalance Carrier Null Scrambling Group Delay Fault Specifications Status Relays Remote Control Specifications Asynchronous Serial Interface Baud Rate Serial Format Data Bits Stop Bits Parity Remote Port Addressing Signals Controlled: Data
Modulation, Coding
Carrier
OVERVIEW
18 Chapter 1
General
Status
Faults
Configuration Retention
Fault Tree
19
Fault Tree
FLT LED On On On On On On On On
On On On On
OVERVIEW
20 Chapter 1
Unpacking
21
Chapter 2
INSTALLATION
This chapter provides unpacking and installation instructions, and a description of external connections.
CAUTION
The equipment contains parts and assemblies sensitive to damage by Electrostatic Discharge (ESD). Use ESD precautionary procedures when touching, removing, or inserting PCBs.
Unpacking
The modulator and manual are packaged in pre-formed, reusable, cardboard cartons containing foam spacing for maximum shipping protection.
Do not use any cutting tool that will extend more than 1 into the container. This can cause damage to the modulator.
CAUTION
To remove the modulator: 1. 2. 3. 4. 5. 6. 7. Cut the tape at the top of the carton indicated by OPEN THIS END. Remove the cardboard/foam space covering the modulator. Remove the modulator, manual, and power cord from the carton. Save the packing material for storage or reshipment purposes. Inspect the equipment for any possible damage incurred during shipment. Check the equipment against the packing list to ensure the shipment is correct. Refer to installation section for instructions.
INSTALLATION
22 Chapter 2
Installation
A complete modulator consists of the TVRM75 main unit and an optional plug-in data interface. The modulator is shipped with the data interface installed in the main unit. Changing a data interface is easily accomplished in the field and does not require disassembly of the main unit. For information on removing and installing data interface modules refer to section on removing and installing data interfaces. Install the modulator as follows: 1. Mount the modulator chassis in the assigned position of the equipment rack. Support the modulator by the rack-mounted brackets or a rack-mounted shelf. s If a data interface is to be installed, follow the steps described in the section on Data Interface Installation.
s
For a custom rack installation, refer to the chassis dimensional drawing in Figure 2-1.
2.
3.
4. 5.
Connect the cables to the proper locations on the rear panel. For connector pinouts, placement, and function refer to the section on external connections. The modulator will turn on automatically when the primary power connection is made (plugged in). Before plugging in the modulator, become familiar with the front panel operation in Chapter 3. The modulator will initiate a self-test function. If there is any problem with the installation, contact Tiernans Customer Support Department.
Installation
23
1 .75
1 4.0
IERNAN
1 9.0
1.25
Figure 2-1
Dimensional Drawing
INSTALLATION
24 Chapter 2
The data interface is a removable, plug-in module that provides a terrestrial connection to the modulator. An interface, shown in Figure 2-2, consists of a Printed Circuit Board (PCB) attached to a faceplate. The faceplate contains connectors appropriate for the interface type and two captive, mounting screws.
J 3 PARA LLEL
J4 SERIAL
J5 AU X
Figure 2-2
Note: After a different interface type has been installed, the modulator recognizes the change upon power up, and defaults to valid interface parameters.
To avoid damaging the modulator, always disconnect the power before removing or installing a data interface.
CAUTION
External Connections
25
External Connections
P R IM E PO W ER
The connectors for the main unit are shown in Figure 2-3 and identified in Table 2-1. The connectors for each plug-in data interface are described in Appendix A.
GR OUND
J1 R E M O T E
J2 FA U LT
D ATA IN T E R FA C E C O N N E C TION S
C P 1 TX -IF
Figure 2-3
Rear Panel
INSTALLATION
26 Chapter 2
See Appendix A
The remote control connection is a 9-pin female D connector located on the rear panel of the modulator. Screw locks are provided for mechanical security of the mating connector. The remote connector provides a means for issuing commands and determining the unit status. This connector provides RS-232, RS-485 (2-wire), and RS-485 (4-wire) operation. The communications protocol and the control and status commands are described in Appendix B.
External Connections
27
The fault interface connection is a 9-pin female D connector located on the rear panel of the modulator. Screw locks are provided for mechanical security on the mating connector. The fault connector provides FORM-C contact closures for fault reporting. The two FORM-C summary fault contacts are Modulator and Common Equipment. To obtain a system summary fault, connect all of the FORM-C contacts in parallel. Table 2-3 provides the pinout of the J2 connector. Units with firmware 4.1.4 or later operate as shown in Table 2-3. The last three columns of the table show which pins of the connector have continuity when the status of the TVRM-75 is either OK, Faulted, or Power OFF.
2-3
1-2
2-3
Modulator Fault
5-6
4-5
5-6
INSTALLATION
28 Chapter 2
7-8
8-9
8-9
CP1 is a BNC connector for the transmit IF signal output. The output impedance is 75 (50 optional). The output is a modulated carrier between 50 and 180 MHz. The AC power is supplied to the modulator by a standard, detachable, non-locking, 3-prong power cord. This cord connects to a fused, ESCtype power receptacle. The fuse is a 2A, Slow-blow, metric fuse. Normal input voltage is 90 to 264 VAC, 47 to 63 Hz. The modulator will automatically switch between ranges. Typical power consumption is less than 40W. Refer to Chapter 1 for specifications.
Ground (GND)
A #10-32 stud is available on the rear panel for the purpose of connecting a common chassis ground among all of the equipment. Note: A safety ground is provided through the AC power connector.
Note: The European EMC Directive (EN55022, EN50082-1) requires using properly shielded cables for DATA I/O. These cables must be double shielded from end-to-end, ensuring a continuous ground shield.
Introduction
29
Chapter 3
OPERATION
This chapter describes modulator operation from the front panel, and provides an explanation of command functions. For remote control operation information, refer to Appendix B.
Introduction
The TVRM75 has three general modes of operation controlled by the DVB Framing Type command in the Configuration Interface menu, described in the section on the Configuration Interface Menu. Refer to Table 3-1 for a description of the three modes.
204
None (187)
The different data interfaces with various data formats are all condensed into one of these three formats for operation. Control functions and status readings are accessible through the front panel keypad/LCD display or the rear panel remote port.
OPERATION
30 Chapter 3
Front Panel
The modulator front panel enables the user to control modulator configuration parameters and display the modulator status.
POWER ON
ALARMS
TRANSMIT
FAULTS
TRANSMIT STORED
ENTER CLEAR
Figure 3-1
Front Panel
32-character, 2-line LCD display 6-button keypad for local control 7 LEDs to provide overall status at a glance
All functions are accessible at the front panel by entering one of four pre-defined Function Select categories:
s s s s
Front Panel
31
Alarms
Transmit Yellow A transmit function is in an alarm condition.
Faults
Transmit Stored Red Yellow A fault condition exists in the transmit chain. A fault has been logged and stored. The fault may or may not be active.
Status
Power On Sync Green Green Power is applied to the modulator. The modulator is synchronized to the data in the selected framing mode. The LED is continuously lit when the DVB Framing Type is NONE. Transmitter is currently ON. This indicator reflects the actual condition of the transmitter, as opposed to the programmed condition. Flashes when the modulator is in a test configuration.
Transmitter On
Green
Test Mode
Yellow
At system level, a fault simultaneously activates the modulator fault relay, MF, a TTL-OC fault indication, and turns on the red Transmit Fault LED. This condition is used by redundancy switches to cause a switch-over to replace a failed unit. An alarm condition turns on the yellow Transmit Alarm LED and activates the Modulator alarm relay. Alarms DO NOT activate the fault indications described above.
OPERATION
32 Chapter 3
The front panel keypad permits local operation of the modulator. The keypad consists of six keys. Each key provides one or more logical functions.
E N TE R C LE AR
Figure 3-2
s
Keypad
ENTER key used to select a displayed function or to execute a modem configuration change. CLEAR key used to back out of a selection or to cancel a configuration change which has not been executed using [ENTER]. Pressing [CLEAR] generally returns the display to the previous selection. Left and Right Diamond Keys used to move to the next selection or to move the cursor for certain functions.
Note: Throughout this chapter, [] and [] are used to indicate left and right diamond keys.
Top and Bottom Diamond Keys used primarily to change configuration data (numbers). At times, they are also used to move from one section to another.
Note: Throughout this chapter, [] and [] are used to indicate top and bottom diamond keys.
A single beep indicates a valid entry and the appropriate action was taken. A double beep indicates an invalid entry or a parameter is not available for operation.
Menu System
33
Menu System
To access and execute all functions, refer to Figures 3-3 through 3-13. Use the main menu in Figure 3-3 as a quick reference for accessing the modulator functions. When prime power is applied to the modulator, the base level of the menu system displays the sign-on message:
s
Line 1 of the sign-on message is the modulator model number and type Line 2 is the version number of the firmware
The main level of the menu system is Function Select. To access this base menu level, press either [] or []. From the Function Select menu, use [] or [] to select one of the functional categories:
s s s s
When the desired function is displayed, select that menu by pressing [ENTER]. After entering the appropriate functional menu, press [] or [] to move to the desired function. To return to the previous menu or to exit a function, press [CLEAR].
Notes:
1. 2. Figures 3-3 through 3-15 list the front panel menu selections. Menus that are specific to certain modulator configurations are only accessible after selecting the appropriate modulator configuration. This prevents incompatible parameters from accidentally being selected.
OPERATION
34 Chapter 3
Main Menu
TV R M 75 M O D V E R: 4.1.4
FU N CTIO N S E LE C T C O NFIG UR A T IO N
FU N CTIO N S E LE C T U TILITY
K e y:
A C C ES S T O S U BM E N U C O N D IT IO N AL O R O P T IO N -D EP EN D EN T P arameter Information
Figure 3-3
Main Menu
Menu System
35
Configuration Menus
Modulator configuration may be viewed or changed by entering the Configuration level from the Function Select menu on the front panel. After entering the Configuration menu, press [] or [] to select Modulator, Interface, Save, or Recall. Enter the selected configuration menu by pressing [ENTER]. Press [] or [] to view the selected configuration parameters. To change a configuration parameter, press [ENTER] to begin the change process. Press [] or [] to make the changes. After the changes are made and the display represents the correct parameters, execute the changes by pressing [ENTER]. After [ENTER] is pressed, the necessary programming is initiated by the modulator. To undo a parameter change prior to executing it, simply press [CLEAR]. The modulator configuration functions are described in the following paragraphs.
OPERATION
36 Chapter 3
T X-D R Q P S K 1 /2 (D a ta R a te )
T X-S R Q P S K 1 /2 (S ym b o l rate)
T X-IF F R E Q U E N C Y
T X-IF O U T P U T
O N , O F F, M O R E
P R E S S E N T E R TO T U R N O N TX-IF
T X-IF O U T P U T = O N ON OFF
P R E S S E N T E R TO T U R N O N TX-IF
P R E S S E N T E R TO T U R N O N TX-IF
T X P O W E R LE V E L
C A R R IE R M O D E
+ 5 .0 to -20 .0 d B m
ON OFF
N O R M A L-M O D U LA T E D D U A L -C W O F FS E T-C W C E N T E R -C W
Key:
AC C ESS TO SU BM EN U C O N D IT IO N A L O R O P T IO N -D E P E N D E N T P a ra m e te r In fo rm a tio n
P R E S S E N T E R TO T U R N O N TX-IF
Figure 3-4
Note: The Scrambler function is related to Energy Dispersal and has no association with conditional access scrambling. To avoid any confusion, Scrambler is referred to as Energy Dispersal on newer versions of the TVRM75.
Menu System
37
Programs the modulator symbol rate (SR) from 1 to 37.5, in 1 sym/s steps, limited by code rate and data interface. On entry, the current symbol rate is displayed with the flashing cursor on the first character. Press [] or [] to move the flashing cursor. Press [] or [] to increment or decrement the digit at the flashing cursor. Press [ENTER] to execute the change. Notes: 1. When [ENTER] is pressed to change the symbol rate, the transmitter is automatically turned off to prevent the possible swamping of other channels. Another menu is displayed that allows the operator to turn the transmitter on again, simply by pressing [ENTER]. 2. 3. 4. Programming is done by either data rate or symbol rate. Data rate refers to the equivalent serial data rate at the data interface connector. Symbol rate refers to the modulation rate after framing, trellis (Viterbi) coding, and Reed-Solomon coding are applied. The framing type (see Section 3.2.5.2) selection affects the symbol rate (if programming from the data rate [TX-DR] menu), or the data rate (if programming from the symbol rate [TX-SR] menu). If data rate is programmed, the symbol rate menu is updated to reflect the code rate and framing selections. If symbol rate is programmed, the data rate display is similarly updated.
OPERATION
38 Chapter 3
TX-IF Output
TX Power Level
Scrambler
Menu System
39
OPERATION
40 Chapter 3
TX CLO CK PHASE
TX DATA PHASE
2 04 7 P A T T E R N
TX SYNC SELECT
NORMAL IN V E R T
NORMAL IN V E R T
OFF ON
E XT S Y N C CORR ON DAT A U TO D E T E C T
TX DATA FAULT
T X C L K A C T IV IT Y
D V B FR A M IN G T Y P E
In te rfac e Lo o p ba ck
NONE A IS D A TA S T A B L E
A LA R M FAULT
Key:
AC C ESS TO SU BM EN U C O N D IT IO N A L O R O P T IO N -D E P E N D E N T P a ra m e te r In fo rm a tio n
P R E S S E N TE R T O T U R N O N T X-IF
Figure 3-5
Menu System
41
TX Data Phase
2047 Pattern
TX Sync Select
TX Data Fault
OPERATION
42 Chapter 3
Interface Loopback
TX Coding Format
Menu System
43
C O N FIG U R AT IO N xx S AV E
xx = 1 to 10
T VR M 75 M O D V ER : 4.1.4
C O N FIG U R AT IO N R E C A LL M E N U
C O N FIG U R AT IO N xx R E C A LL
K ey:
xx = 1 to 10
ACCESS TO SUBM ENU C O N D IT IO N A L O R O P T IO N -D E P E N D E N T P a ra m e te r In fo rm a tio n
Figure 3-6
The Configuration Save menu allows you to program configuration parameters into memory on the M&C. There are 10 memory locations that may be used to store frequently used configuration setups. After changing the configuration parameters to the desired settings, enter the Configuration Save menu, select memory location 1 through 10 by pressing [] or [], and press [ENTER] to execute the save.
The Configuration Recall menu allows the user to recall a previously saved configuration setup. Upon entry, select memory location 1 through 10 by pressing [] or []. Press [ENTER] to execute the recall.
OPERATION
44 Chapter 3
Faults/Alarms Menus
The Faults/Alarms level is accessible from the Function Select menu. These are similar to monitor functions, as the current status is displayed. Press [] or [] to move between the Fault/Alarm groups:
s s s
The current Faults/Alarms status is displayed on line 2 of the display in real time. Fault status is displayed as a + (plus) or - (minus) for each parameter monitored:
s s
- indicates that no fault or alarm exists. + indicates that a fault exists, and will cause switching in a redundant system. A reversed-contrast + sign appearing on the display indicates an alarm is active.
Note: Alarms do not cause switching to occur. To display labels for individual faults or alarms, press [ENTER]. Press [] or [] to move the flashing cursor to the fault or alarm to be identified. The label for that fault/alarm is immediately displayed on line 1 of the display. To exit this level of operation and return to the previous level, press [CLEAR]. The following paragraphs list the faults and alarms monitored and displayed in each group.
Faults/Alarms Menus
45
Faults/Alarms Menu
T V R M 75 M O D V E R : 4.1.4
F U N C T IO N S E LE C T F A U LT S /A LA R M S
M O D U LA T O R
T X IN T E R F A C E
COMMON
IF S Y N T H E S IZ E R D A T A C LO C K S Y N I CHANNEL Q CHANNEL A G C LE V E L M O D U LE IF M O D U LE C O N F IG U R A T IO N
N otes: 1. A - indicates that no fault or alarm exists. 2. A + indicates that a fault exists, and will cause switching in a redundant system . 3. A reversed contrast + indicates an active alarm .
Key:
ACCESS TO SUBMENU C O N D IT IO N A L O R O P T IO N -D E P E N D E N T P a ra m e te r In fo rm a tio n
Figure 3-7
Faults/Alarms Menu
OPERATION
46 Chapter 3
I Channel
Q Channel
AGC Level
Faults/Alarms Menus
47
IF Module Configuration
Clock PLL
Clock Activity
Data Format
OPERATION
48 Chapter 3
+5 Volt Supply
Controller
Faults/Alarms Menus
49
T V R M 75 M O D V E R : 4.1.4
F U N C T IO N S E LE C T STORED F LT S /A LM S
M O D U LA T O R x
T X IN T E R F A C E x
COMMON x
C LE A R ??
S T O R E D T IM E /D A T E H H :M M :S S /M M -D D -Y Y (F A U LT LA B E L) IF S Y N T H E S IZ E R D A T A C LO C K S Y N I CHANNEL Q CHANNEL A G C LE V E L M O D U LE IF M O D U LE C O N F IG U R A T IO N
S T O R E D T IM E /D A T E H H :M M :S S /M M -D D -Y Y (F A U LT LA B E L) FRAME SYNC D A T A S T A B LE /A IS C LO C K P LL C LO C K A C T IV IT Y F IF O IN T E R FA C E M O D U LE
S T O R E D F A U LT S
C LE A R ?? YES
Figure 3-8
The modulator stores the first 10 (Flt0 through Flt9) occurrences of fault status changes in each of the three major fault categories. Each fault status change is stored with the time and date of the occurrence. Stored faults may be viewed by entering the Stored Faults level from the Function Select menu. All stored faults may be cleared by executing the CLEAR Stored Faults? command from the Stored Faults level.
OPERATION
50 Chapter 3
Stored faults are not maintained through a controller power-on reset cycle. However, the last known time is maintained in non-volatile RAM, and upon power-down, a common equipment fault is logged (Flt0) with that time and date. On power-up, an additional common equipment fault is also logged (Flt1) to indicate the power-up time and date. On power-up, the power-down and power-up times are logged as common equipment fault 0 and common equipment fault 1. Upon entering the Stored Faults level, press [] or [] to move between the fault groups and the CLEAR Stored Faults?? selections. The time and date of the first stored fault status (Flt0) for the selected group will be displayed alternately on line 2 of the display. Press [] or [] to cycle through the selected groups stored fault status (Flt0 through Flt9). To display the fault status associated with the displayed time and date, press [ENTER]. At this time, press [] or [] to move the flashing cursor to the fault to be identified. To clear the stored faults currently logged, simply press [ENTER] when the CLEAR Stored Faults/YES?? selection is displayed, press [ENTER] again to clear. Note: Faults are stored in time sequence, with the oldest fault status change stored in Flt0, and the most recent in Flt9. Only the first 10 fault status changes are stored, additional faults are ignored until the log is cleared. All stored faults which have not been used indicate No Fault on the display.
Faults/Alarms Menus
51
Utility Menus
The utility functions are divided into four user categories, and provide access to the following Utility menus:
s s s s
Set the time and date of the modulator real time clock. Test the front panel optical indicators. Choose filtering types, code rates, decoder types, TX fault enables, modulator type, and overhead type.
After entering the Utility functions level, press [] or [] to select the Utility menu desired, and press [ENTER]. Press [] or [] to select the utility function of interest. Notes: 1. The Utility Factory Setup menu is for Tiernan service personnel only. Unauthorized access may cause the modulator to operate incorrectly. Changes in the Utility menu may cause changes in other front panel menus.
2.
OPERATION
52 Chapter 3
M O D S P E C TR U M
MOD POW ER O F FS E T
P O W E R U P TX-IF
M O D U LA TO R TY P E
NO RMAL IN V E R T
-4 0.0 to + 40.0 dB - U S E R p ow er o ffset in 0 .1 d B step s. A n ythin g e xce pt 0.0 dB will caus e A D J to b e d ispla yed in th e TX P O W E R L E V E L scre en.
LA S T K N O W N OFF
D V B -1 D V B -2
N o te: P ressing E nter in this m e nu tu rns off TX-IF O U TP U T.
K e y:
AC C ESS TO SU BM EN U C O N D IT IO N A L O R O P T IO N -D E P E N D E N T P a ram e te r In fo rm ation
Figure 3-9
Faults/Alarms Menus
53
Power Up TX-IF
Modulator Type
OPERATION
54 Chapter 3
T V R M 75 M O D V E R : 4.1.4
F U N C T IO N S ELE C T U T ILIT Y
U T ILIT Y IN T E R F A C E
IN T E R F A C E TY P E
R S -422 A IS /R S -422 UNKNOW N S ee A ppendix A for m enus specific to the available interface m odules.
K ey:
ACCESS TO SUBMENU C O N D IT IO N A L O R O P T IO N -D E P E N D EN T P a ra m e te r In fo rm a tio n
Figure 3-10
.
Faults/Alarms Menus
55
UTILITY INTERFACE
INTERFACE TYPE
RS422
SERIAL PARALLEL
ON OFF
RTS STATE
DM STATE
NORMAL INVERT
NORMAL INVERT
NORMAL
Key:
ACCESS TO SUBMENU CONDITIONAL OR OPTION-DEPENDENT Parameter Information
Figure 3-11
OPERATION
56 Chapter 3
RTS STATE
CTS STATE
DM STATE
Faults/Alarms Menus
57
UTILITY INTERFACE
INTERFACE TYPE
INTERFACE SELECT
TX INTERFACE FIRMWARE
ASI/RS422
ASI RS422
RTS STATE
CTS STATE
DM STATE
ST STATE
Key:
ACCESS TO SUBMENU CONDITIONAL OR OPTION-DEPENDENT Parameter Information
Figure 3-12
OPERATION
58 Chapter 3
INTERFACE SELECT Displays the mode type ASI or RS422 interface. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. TX INTF FIRMWARE Press [ENTER] will show the FW Release date. ASI LINK SELECT (ASI Mode Only) INTERFACE LOOP THRU (ASI Mode Only) Displays the A-LINK (J4) or B-LINK (J3). Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the Interface Loop thru selection of either ON or OFF. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. When On is selected, input data is looped to the output of the terrestrial interface; data also continues into the modulator. This mode is identical to the Interface Loopback function found on the Configuration Interface menu, except that the front panel yellow Test Mode LED is not illuminated. Note: This option available only with VER 5.3.1 and later. Displays the RTS selection of either ON or OFF. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the RTS selection of either NORMAL or INVERT. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the CTS selection of either NORMAL or INVERT. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the DM selection of either NORMAL or INVERT. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the ST selection of either NORMAL or INVERT. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change.
RTS TX-IF CNTRL (RS422 Mode Only) RTS STATE (RS422 Mode Only) CTS STATE (RS422 Mode Only) DM STATE (RS422 Mode Only) ST STATE (RS422 Mode Only)
Faults/Alarms Menus
59
UTILITY SYSTEM
REMOTE ADDRESS
REMOTE TYPE
X= 300 4800 600 9600 1200 19200 2400 X = bit/s Parity: EVEN, ODD, or NONE
1 to 255
YEAR DISPLAY
LAMP TEST ??
DISPLAY CONTRAST
2- DIGIT 4-DIGIT
RF OUTPUT CARRIER MODE MOD FAULTS INTF FAULTS 2047 PATTERN IMPULSE TEST INTF LOOPBACK
0 to 100
MASTER RESET
ALARM RELAY
Key:
ACCESS TO SUBMENU CONDITIONAL OR OPTION-DEPENDENT Parameter Information
HARD SOFT
NORMAL INVERT
Figure 3-13
OPERATION
60 Chapter 3
Remote Address The current modulator address is displayed (1 to 255). To set the remote address, press [ENTER]. Press [] or [] to change the parameter to the desired value. Press [ENTER] to execute the change. Note: Address 0 is reserved as a global address. Remote Type Remote interface type selection, choices include: RS-485 (4-wire) RS-485 (2-wire) RS-232 Press an arrow key to make the selection. Press [ENTER] to execute the change. Displays the year in either 2-digits or 4-digits. Press an arrow key to make the selection. Press [ENTER] to execute the change.
Year Display
Faults/Alarms Menus
61
Display Contrast
M&C FIRMWARE Displays M&C module firmware version. Note: Pressing [CLEAR] will exit from this menu. Upon entry, the date of release of this firmware will be displayed. This is a status window only. BOOT FIRMWARE ENCODER FIRMWARE Displays the Boot module firmware version. The display includes the month, day, and year. Displays Encoder firmware version. Note: Pressing [CLEAR] will exit from this menu. Upon entry, the date of release of this firmware will be displayed. This is a status window only. Displays R/S module firmware version. Note: Pressing [CLEAR] will exit from this menu. Upon entry, the date of release of this firmware will be displayed. This is a status window only.
R/S FIRMWARE
OPERATION
62 Chapter 3
CAUTION
When a hard reset is initiated, the modulator hardware is reset, and all default configuration settings will be installed. When a soft reset is initialized, the modulator hardware will be reset, but the initial firmware configuration settings will be saved. Press [ENTER] once to access Soft. Press [] or [] to alternate between Hard and Soft until the desired type is visible. Press [ENTER]. If Soft has been selected, press [ENTER] again to reset the modulator. If Hard is selected, press [] until the cursor is on YES, and press [ENTER].
ALARM RELAY Displays Alarm selection at NORMAL or INVERT> Upon entry, the date of release of this firmware will be displayed. This is a status window only.
Faults/Alarms Menus
63
Note: See Appendix C for instructions on restoring the factory default configuration after a firmware upgrade or a hard reset.
OPERATION
64 Chapter 3
R E V E M U LA T IO N
M O D O P T IO N S
M O D S E R IA L #
C O N F IG U R A T IO N CODE - MOD
F U N C T IO N A L x C U R R E N T V E R S IO N x = 1 to x 16Q A M 8P S K O E M LC D
(S tatus O nly) (- or +) (- or +) (- or +)
(S tatus O nly)
K ey:
A C C ES S T O S U BM E N U C O N D IT IO N A L O R O P T IO N -D E PE N D E N T P a ra m e te r In fo rm a tio n
Figure 3-14
Faults/Alarms Menus
65
MOD Options
MOD Serial#
Configuration CodeMOD
OPERATION
66 Chapter 3
T V R M 75 M O D V E R : 4.1.4
F U N C T IO N S E LE C T U T ILIT Y
U T ILIT Y F A C T O R Y S E T -U P
K ey:
ACCESS TO SUBMENU C O N D IT IO N A L O R O P T IO N -D E P E N D E N T P a ra m e te r In fo rm a tio n
Figure 3-15
CAUTION
This configuration is used for factory alignment and filter setup parameters. To avoid modulator failure, Factory Setup should not be changed by unauthorized personnel.
Description
67
Appendix A
DATA INTERFACES
This chapter describes the plug-in data interface modules used with the TVRM75.
Description
The data interface is a plug-in module that provides a specific terrestrial connection to the modulator unit. Where practicable, both the transmit (modulator) and receive (demodulator) paths are incorporated into the data interface. Each data interface has its own specification. Some general requirements are described in the main body of the specification. The requirements for each interface includes:
s
Reference to any other interface specification, such as: G.703, RS-422. Voltage levels (where applicable) for clarity, or when not covered adequately by the referenced standard. Signal/timing characteristics under special conditions. Timing, if not covered by the applicable specification, or if special. Pinout and signal description for all connectors. Description of each connector. Limitations: data rate range. Where needed, any other application information.
s s
s s s s
Different interfaces are described in the following sections of this appendix. As additional interfaces are developed, the appendix will be revised to include the new interfaces. Contact Tiernan Customer Support for the latest offering.
DATA INTERFACES
68 Appendix A
Software Requirement
As additional data interfaces are introduced, the software is revised to support the operation of each interface. Table A-1 summarizes the minimum software version necessary to operate each interface type.
To avoid damaging the modulator, always disconnect the power before removing or installing a data interface.
CAUTION
The following paragraphs describe the RS-422 parallel and serial interface. The interface operates at RS-422 signal levels. It accommodates a variety of MPEG2 framing formats and EIA-530 serial data. Applicable specifications referenced within this manual include:
s
TM1449 Interfaces for CATV/SMATV Headends and Similar Professional Equipment TIA/EIA-644 Telecommunications Industry Standard, Electrical Characteristics Of Low Voltage Differential Signaling (LVDS) Interface Circuits (originally Standards Proposal SP-3357) EIA-422 Electrical Characteristics of Balanced Voltage Digital Interface Circuits EIA-530 High Speed 25-Position Interface for Data Circuit-Terminating Equipment
69
Description
The RS-422 interface has two data connectors and an auxiliary connector supporting various operating modes.
s
Parallel modeIn this mode, the interface behaves like a DVB parallel synchronous interface, but with RS-422 levels. The input is at the byte rate. Serial modeAn alternate form of operation is possible, where the MSB is used for serial input at the bit rate. Serial mode onlyEIA-422 levels with pinout and operation per EIA-530 at a serial clock rate. Provides an additional ST Clock (output), plus open collector fault signals.
The appropriate interface control is automatically enabled when the interface module is installed in the modulator. The plug-in data interface is programmable for serial or parallel operation from either the front panel keypad or the remote port on the rear panel. The following cables, or an equivalent computer-grade cable incorporating twisted, shielded pairs, are recommended:
s s
The Belden 8175 has a lower capacitance, however it has a larger diameter and requires the selection of an appropriate connector shell. The maximum cable length for the serial and parallel interfaces is unknown. Typical lengths are less than 5 meters. The interface operates to the specifications described in Table A-2.
DATA INTERFACES
70 Appendix A
Configuration
Note: The jumper location on the interface card and the optional positions are shown in Figure A-1. A single jumper provides the option for a transmit or receive reference clock on connector J3 (pins 2 and 15). The pins are configured at the factory as signal ground per TM 1449. For modulator applications where an SCT output is required in conjunction with using the DVB Data port (J3), SCT may be jumpered to pins 2 and 15, thus providing all signals on a single connector. The same jumper configuration in demodulator applications provides for a Master clock input. Alternatively, SCT and Master clock interconnects are available on the Auxiliary port (J5).
71
X U A 5 J
L A I R E S 4 J
L E L L A R A P 3 J
J3 - 2 & 15
GND
CLOCK CONFIGURATION
J3 - 2 & 15 J3 - 2 & 15
Figure A-1
DATA INTERFACES
72 Appendix A
User Interfaces
Parallel, J3, DB25 Female (DVB Parallel/Serial Data Interface) This data port supports DVB and DBS parallel and serial
packetised data. The following standard frame formats are supported:
s
None, no framing byte format continuous serial or parallel payload data with no framing information. 188 byte format serial or parallel data, (1 sync byte + 187 payload bytes). 204 byte format serial or parallel data, (1 sync byte + 187 payload bytes + 16 bytes for Reed-Solomon coding).
Figure A-2 and Figure A-3 depict the 204 byte packetization for byte parallel and byte serial formats, showing all possible data fields and timing signal relationships. The 188 byte and no framing formats are subsets of the 204 byte format.
1 Byte Sync 187 Bytes Payload 16 RS Bytes 1 Byte Sync
SYNC
187
16
SYNC
Figure A-2
8 Bits Sync 0 1 0 0 0 1 1 1
128 Bits RS 0 1
8 Bits Sync 0 0 0 1 1 1
Figure A-3
73
For proper operation, data and timing must be continuous and meet the criteria shown in Table A-3.
CLOCK SYNC
NONE
For the 188 or 204 byte framing modes, either a sync pulse or sync byte of value 47h is required, dependent on the modulator configuration. Both may be applied, with only one having effect, dependent upon configuration. When used, the sync pulse is active high centered over the sync word. In parallel operation, it is one byte clock wide. In serial operation, the modulator recognizes the sync pulse centered on the entire sync byte (8 clocks wide), or centered on the most significant bit of the byte (1 clock wide). DVALID Although this signal is identified by both DVB and DBS formats, it is not used by the modulator.
Connector Pinout, J3 The connector is a sub-miniature, 25-pin, female D connector, with threaded jack nuts (refer to Table A-4 for pinout). All signals on this connector are inputs to the modulator, except the signal pair on pins 2 and 15 when the jumper is selected for SCT output.
When used as a serial data port, Data 7 (pins 3 and 16) are the active data pins. Signal assignments for pins 2 and 15 are jumper-selectable. They are defined as signal ground in the DVB definition of TM1449, but may be configured to provide SCT out. Refer to the section on Configuration for jumper specifics. Signal levels are as defined in EIA-422.
DATA INTERFACES
74 Appendix A
Per TM1449, the differential sense of all signal pairs is a logic 1 when A is positive with respect to B. This is the normal selection in the Configuration Interface menu (refer to Chapter 3).
3 4 5 6 7 8 9 10 11 12 13 14 15
Data 7 A(MSB/Serial) Data 6 A Data 5 A Data 4 A Data 3 A Data 2 A Data 1 A Data 0 A DVALID A SYNC A Cable Shield Clock B System GND/REFCLKA
I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O O/GND
16 17 18 19 20 21 22 23 24 25
Data 7 B (MSB/Serial) Data 6 B Data 5 B Data 4 B Data 3 B Data 2 B Data 1 B Data 0 B DVALID B SYNC B
I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O
75
This interface has no provision for SYNC or DVALID signals. If framing is desired, a sync byte(47 hex) is imbedded into the data stream every 188 or 204 bytes, as selected in the modulator configuration. The modulator detects the sync byte and formats the serial interface data into a standard, error-protected 204 byte packet.
Connector Pinouts, J4
The connector is a subminiature, 25-pin, female D connector, with threaded jack nuts (refer to Table A-5 for pinout). Signal functions are as defined in EIA-530. Notes: 1. 2. The differential sense of all signals is a logic 1 when B is positive with respect to A as defined in EIA-530. Only those pins indicated as modulator in the table are applicable.
DATA INTERFACES
76 Appendix A
Auxiliary, J5
This port provides for other modem-specific signals not otherwise defined for either or both of the two data connectors.
Connector Pinout, J5 The connector is a sub-miniature, 9-pin, female D connector, with threaded jack nuts (refer to Table A-6 for connector pinout).
Differential pairs are RS-422 compatible. Note: The sense of differential signal pairs is a logic 1 when B is positive with respect to A. Single ended signals (MF and DF fault signals) are open collector where:
77
DATA INTERFACES
78 Appendix A
If the RS-422 interface module is installed, the Utility Interface menu displays commands specific to that interface, as shown in Figure A-4 and described in Table A-7.
UTILITY INTERFACE
INTERFACE TYPE
RTS STATE
RS422
ON OFF
NORMAL INVERT
CTS STATE
DM STATE
NORMAL INVERT
NORMAL INVERT
Key:
ACCESS TO SUBMENU CONDITIONAL OR OPTION-DEPENDENT Parameter Information
Figure A-4
79
INTF MODE Select Programs the modulator to use either SERIAL or PARALLEL interface mode. Note: INTF MODE SELECT appears only when the DVB interface type is selected. Upon entry, the current status is displayed. Press an arrow key to make the selection. Press [ENTER] to execute the change. RTS TX-IF CNTRL Programs the modulator to use a Request To Send (RTS) logic high signal to enable the output when data is ready for transmission. ON uses the RTS signal OFF does not use the RTS signal Upon entry, the current status is displayed. Press an arrow key to make the selection. Press [ENTER] to execute the change. RTS State Selects the logic sense, which can be either: NORMAL INVERT Upon entry, the current status is displayed. Press an arrow key to make the selection. Press [ENTER] to execute the change. Selects the logic sense, which can be either: NORMAL INVERT Upon entry, the current status of the RTS TX-IF CNTRL is displayed. Press an arrow key to make the selection. Press [ENTER] to execute the change. Selects the logic sense, which can be either: NORMAL INVERT Upon entry, the current status is displayed. Press an arrow key to make the selection. Press [ENTER] to execute the change.
CTS State
DM State
DATA INTERFACES
80 Appendix A
RS-422 Defaults
listed in Table A-8.
The control commands listed in Table A-9 are displayed only when the RS-422 interface module is installed.
81
Interface Select Interface Mode DVB Framing Type Modulator Frequency Modulator Rate Modulator Power Offset Modulator Output Power Scrambler Enable (ON/OFF) Transmit Clock Phase Transmit Data Phase Transmit Data Fault Transmit 2047 Pattern Generator Transmit Sync Select Modulator Spectrum Rotation Modulator Type Transmit IF Output Power-up Configuration Carrier Only Mode RTS Mode Control RTS State Control CTS State Control DMS State Control TX Clock Activity Action RF Output (ON/OFF)
Command: Response:
Transmit Clock Phase Transmit Data Phase Transmit 2047 Pattern Generator Transmit Sync Select Transmit Data Fault DVB Framing Type Interface Identification Interface Select Interface Mode RTS Mode Control RTS State Control CTS State Control DM State Control TX Clock Activity Action
DATA INTERFACES
82 Appendix A
1 - Parameters 23 through 27 of the BCS command are displayed only when the RS-422 interface module is installed. 2 - The use of this command is dependent upon the type of interface module installed in the modulator. This command is used by the Tiernan M:N protection switch to collect information that is necessary to configure back-up modulators. Because this command (content and/or order) can be changed at any time by Tiernan, it is advisable that other commands ('MCS_' and 'ICS_', or 'BCS_') be used for M&C systems.
This section describes the Asynchronous Serial Interface (ASI) and RS-422 Data Interface. Applicable specifications referenced in this manual include:
s
TM1449 Interfaces for CATV/SMATV Headends and Similar Professional Equipment EIA-422 Electrical Characteristics of Balanced Voltage Digital Interface Circuits EIA-530 High Speed 25-Position Interface for Data Circuit Terminating Equipment ETS 300 421 Digital Broadcasting Systems For Television, Sound And Data Services; Framing Structure, Channels Coding And Modulation For 11/12 GHz Services
83
Description
This data interface is a plug-in module, shown in Figure A-5, that inserts into the rear of the TVRM75 Modulator. It provides physical and electrical connection between the external terrestrial circuit and the internal circuitry of the modulator.
ASI IN PU TS
J3
J4
EIA-422/530ASI O U TPUTS
J6 J5
J7
Figure A-5
The ASI and RS-422 interface combines two electrical and physical interfaces into a single assembly. The ASI section provides DVB-compliant interface with BNC connectors, while the RS-422 section supports serial communications through a standard 25-pin D connector per EIA-530. Operation for either ASI or RS-422 is selected by programming the unit from the front panel keypad/LCD or from the remote port. Only one of the interface types is active at a time. Figure A-6 is a block diagram of the interface.
DATA INTERFACES
84 Appendix A
J3 TX ASI J4
TT SD ST RS TERRESTRIAL INTERFACE CS RR RD RT DM RS-422 RECOVERY, PROCESSING AND ASI/RS-422 SELECTION LOOPBACK LEVEL TRANSLATORS MODULATOR/ DEMODULATOR INTERFACE
Figure A-6
A 75 coaxial cable (Belden 8281 or equivalent) is recommended for all ASI connectors. Typical coaxial cable length is up to 140 meters with good quality coaxial cable. Typical alternation of up to 18 dB at 270 MHz is permitted. The following cables, or an equivalent computer grade cable incorporating twisted, shielded pairs, are recommended for the RS-422 interface:
s s
The Belden 8175 has a lower capacitance, however it has a larger diameter and requires the selection of an appropriate connector shell. The maximum cable length for the serial and parallel interfaces is unknown. Typical lengths are less than 2 meters. The interface operates to the specifications described in Table A-10.
85
Voltage Level
1.5 to 18 Mbit/s, serial RS-422 Programmed data rate 100 ppm 25-Pin D female per EIA-530 per EIA-422 SD, TT, ST, RD, RT, RS, RR, CS, DM, and MC Data synchronization is detected by correlating the data stream for the MPEG2 sync pattern per ETS 300 421. 4 2 V differential into 100
Notes: 1 In loopback TX, data is routed through as much of the interface card as practicable before being returned to the RX interface. In a modulator chassis, TX data continues to enter the modulator and is TX during loopback. 2 Rev. A or later assemblies
DATA INTERFACES
86 Appendix A
User Interfaces
The following paragraphs describe the electrical and physical properties of the ASI and RS-422 data interface module.
Transmit Input Connectors, J3/J4, BNC, Female These two connectors accept TX data from the terrestrial interface. By default, J3 is enabled and J4 is disabled. The active input is user programmable and maintained in non-volatile memory of the modulator chassis. Both connectors are terminated into 75 whether selected or not. ASI Loopback Output Connectors, J6/J7, BNC, Female
Duplicate signals exit both of these connectors on the modulator when Loopback mode is enabled. The input data is looped back to the output data connectors and data continues into the modulator.
Single ended signals (MF and DF fault signals) are open collector where: Voh=12V max. and Vol=0.5V max. @ Iol=8 ma. A pull-up resistor external to the equipment is required. The fault signals, MF and DF, operate as follows: A fault is indicated by an OFF collector (high) and OK status is indicated by an ON collector (low).
87
DATA INTERFACES
88 Appendix A
When the ASI/RS-422 interface is selected only the commands that apply to that specific interface (ASI or RS-422) are displayed.
UTILITY INTERFACE
INTERFACE TYPE
INTERFACE SELECT
TX INTERFACE FIRMWARE
ASI/RS422
ASI RS422
RTS STATE
CTS STATE
DM STATE
ST STATE
Key:
ACCESS TO SUBMENU CONDITIONAL OR OPTION-DEPENDENT Parameter Information
Figure A-7
89
Table A-12 ASI and RS-422 Interface Menu (refer to Figure A-7)
INTERFACE TYPE INTERFACE SELECT Displays ASI/RS422 or UNKNOWN. This is a status window only, and no changes can be made from this menu. Displays the mode type ASI or RS422 interface. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Press [ENTER] will show the FW Release date. Displays the A-LINK (J4) or B-LINK (J3). Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the Interface Loop thru selection of either ON or OFF. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. When On is selected, input data is looped to the output of the terrestrial interface; data also continues into the modulator. This mode is identical to the Interface Loopback function found on the Configuration Interface menu, except that the front panel yellow Test Mode LED is not illuminated. Note: This option available only with VER 5.3.1 and later. Displays the RTS selection of either ON or OFF. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the RTS selection of either NORMAL or INVERT. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the CTS selection of either NORMAL or INVERT. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the DM selection of either NORMAL or INVERT. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change. Displays the ST selection of either NORMAL or INVERT. Upon entry, the current status of the mode type is displayed. Press [] or [] to make the selection. Press [ENTER] to execute the change.
TX INTF FIRMWARE ASI LINK SELECT (ASI Mode Only) INTERFACE LOOP THRU (ASI Mode Only)
DATA INTERFACES
90 Appendix A
ASI and RS-422 Defaults Default settings for the ASI/RS-422 interface are listed in Table A-13.
The remote control commands listed in Table A-14 are displayed only when the ASI/RS-422 interface module is installed.
ASI Link Command: <add/ASI_x'cr' (Input) Select Response: >add/ASI_x'cr'lf'] Command Status: <add/ASI_'cr' Response: >add/ASI_x'cr'lf'] RTS TX-IF Command: <add/RTSM_xxx'cr' Control Mode Response: >add/RTSM_xxx'cr''lf'] Status: <add/RTSM_'cr' Response: >add/RTSM_xxx'cr''lf']
Where: xxx = ON or OFF. This command configures the modem for the RTS TX-IF control mode. If "ON" is selected, the TX-IF output will only be turned on if the incoming RTS signal is asserted (also the TX-IF output has to be programmed ON and no major modulator faults are present). If "OFF" is selected, the TX-IF output will operate normal ignoring the RTS signal. Where: xxx = NRM (normal sense) or INV (inverted sense). This command controls the logic sense of the RTS signal.
91
DATA INTERFACES
92 Appendix A
93
Interface Select Interface Mode DVB Framing Type Modulator Frequency Modulator Rate Modulator Power Offset Modulator Output Power Scrambler Enable (ON/OFF) Transmit Clock Phase Transmit Data Phase Transmit Data Fault Transmit 2047 Pattern Generator Transmit Sync Select Modulator Spectrum Rotation Modulator Type Transmit IF Output Power-up Configuration Carrier Only Mode ASI Input RTS Mode Control RTS State Control CTS State Control DM State Control ST State Control TX Clock Activity Action RF Output (ON/OFF)
The use of this command is dependent upon the type of interface module installed in the modulator. This command is used by the Tiernan M:N protection switch to collect information that is necessary to configure back-up modulators. Because this command (content and/or order) can be changed at any time by Tiernan, it is advisable that other commands ('MCS_' and 'ICS_', or 'BCS_') be used for M&C systems. Note: Only displayed when RS-422 interface is installed.
DATA INTERFACES
94 Appendix A
Transmit Clock Phase Transmit Data Phase Transmit 2047 Pattern Generator Transmit Sync Select Transmit Data Fault DVB Framing Type Interface Identification Interface Select Interface Mode ASI Input RTS Mode Control RTS State Control CTS State Control DM State Control ST State Control TX Clock Activity Action p23 = n, where n = '0' (ASI), '1' (RS422).
24
25
26
27
28
29
30 to 32
Parameters 23 through 27 of the BCS command are displayed only when the ASI interface module is installed.
General
95
Appendix B
General
Remote controls and status information are transferred via an RS-485 (optional RS-232) serial communications link. Commands and data are transferred on the remote control communications link as US ASCII-encoded character strings. The remote communications link is operated in a half-duplex mode. Communications on the remote link are initiated by a remote controller or terminal. The modem never transmits data on the link unless it is commanded to do so. Some commands and status information are interface-type dependent. Refer to Appendix A.
Message Structure
Messages on the remote link fall into the categories of commands and responses. Commands are messages which are transmitted to a satellite modem, while responses are messages returned by a satellite modem in response to a command. The general message structure is as follows:
s s s s
Start Character
A single character precedes all messages transmitted on the remote link which flags the start of a message. This character is:
s s
Device Address
The device address is the address of the one satellite modulator which is designated to receive a transmitted command, or which is responding to a command. Valid device addresses are 1 to 3 characters long, and in the range of 1 to 255. Address 0 is reserved as a global address which simultaneously addresses all devices on a given communications link. Devices do not acknowledge global commands. Each satellite modulator which is connected to a common remote communications link must be assigned its own unique address. Addresses are software selectable at the modulator, and must be in the range of 1 to 255.
Command/ Response
The command/response portion of a message contains a variablelength character sequence of command and response data. If a satellite modulator receives a message addressed to it which does not match the established protocol or cannot be implemented, a negative acknowledgment message is sent in response. This message is:
s
>add/?ER1_parity error'cr''lf'] (Error message for received parity errors.) >add/?ER2_invalid parameter'cr''lf'] (Error message for a recognized command which cannot be implemented or has parameters which are out of range.) >add/?ER3_unrecognizable command'cr''lf'] (Error message for a recognized command which cannot be implemented or has parameters which are out of range.) >add/?ER4_modem in local mode'cr''lf'] (Modem in local error; send the REM command to go to remote mode.) >add/?ER5_hard coded parameter'cr''lf'] (Error message indicating that the parameter is hardware dependent and may not be changed remotely.)
Note: add is used to indicate a valid 1 to 3 character device address in the range between 1 and 255.
Configuration Commands/Responses
97
End Character
Each message is ended with a single character which signals the end of the message:
s s s
cr
lf
Carriage return character for commands Line feed End bracket for responses
RF Output (IF Command: <add/RF_xxx'cr' Output) Response: >add/RF_xxx'cr''lf'] Status: Response: Command: Response:
<add/RF_'cr' >add/RF_xxx'cr''lf'] <add/AMRV_nnnnn_mmm.mmmmmm'cr' Where: >add/AMRV_nnnnn_mmm.mmmmmm'cr''lf'] nnnnn = 1/2 (QPSK 1/2) [Code rate] 3/4 (QPSK 3/4) Status: <add/AMRV_'cr' 7/8 (QPSK 7/8) Response: >add/AMRV_nnnnn_mmm.mmmmmm'cr''lf'] 5/6 (QPSK 5/6) 2/3 (QPSK 2/3) 8P23 (8PSK 2/3) 8P56 (8PSK 5/6) 8P89 (8PSK 8/9) mmm.mmmmmm = Data rate in Mbps. Command: <add/ASR_nnnnn_mm.mmmmmm'cr' Where: Response: >add/ASR_nnnnn_mm.mmmmmm'cr''lf'] nnnnn = 1/2 (QPSK 1/2) [Code rate] 3/4 (QPSK 3/4) Status: <add/ASR_'cr' 7/8 (QPSK 7/8) Response: >add/ASR_nnnnn_mm.mmmmmm'cr''lf'] 5/6 (QPSK 5/6) 2/3 (QPSK 2/3) 8P23 (8PSK 2/3) 8P56 (8PSK 5/6) 8P89 (8PSK 8/9) mm.mmmmmm = Symbol rate in MS/s.
Where: xxxx = LAST (last known state) or OFF (OFF). This command selects the state that the TX-IF Output will be at power up. Where: snn.n = +40.0 to -40.0 in 0.1dB increments. Note: The modulator power offset is added to the nominal power level. Where: xxxx = DVB1 or DVB2.
Modulator Type
Note: The Scrambler function is related to Energy Dispersal and has no association with conditional access scrambling. To avoid any confusion, Scrambler is referred to as Energy Dispersal on newer versions of the TVRM75.
Configuration Commands/Responses
99
Interface Mode Command: Config Response: Status: Response: TX Clock Command: Activity Action Response: Status: Response:
Command: <add/DATE_mm/dd/yyyy'cr' Where: Response: >add/DATE_mm/dd/yyyy'cr''lf'] mm = 1 to 12 (month). dd = 1 to 31 (day). Status: <add/DATE_'cr' yy = 00 to 99 (year) in two-digit mode Response: >add/DATE_mm/dd/yyyy'cr''lf'] yyyy = 1975 to 1999, and 2000 to 2075 in four-digit mode. Command: <add/REM_'cr' Response: >add/REM_'cr''lf'] Configures the Modem for remote operation. The modulator will respond to any status request at any time. However, the modulator must be in 'Remote Mode' to change configuration parameters.
Remote
This command is used to clear all stored faults logged by the modulator. Where: n = 1, 2, 3, ..., 10 (stored configuration number). This command saves the current mod configuration for recall at a later time using the 'RMC_' command. Up to ten different mod configurations can be saved.
Where: n = 1, 2, 3, ..., 10 (stored configuration number). This command causes the mod to be reprogrammed with configuration parameters previously saved using the 'SMC_' command. One of ten saved configurations can be specified.
Alarm Command: <add/ARLY_xxx'cr' Relay State Response: >add/ARLY_xxx'cr''lf'] <add/ARLY_'cr' Status: Response: >add/ARLY_xxx'cr''lf']
Where: xxx = NRM (normal sense) or INV (inverted sense). This command controls the logic sense of the Mod alarm relay (NC and NO contacts).
Configuration Commands/Responses
101
Modulator Command: <add/MCS_'cr' Config Status Response: >add/MCS_'cr' RF_xxx'cr' MF_nnn.nnnn'cr' MR_nnnn_mmm.mmmmmm'cr' AMRA_nnnn_mmm.mmmmmm'cr' AMRV_nnnn_mmm.mmmmmm'cr' MPO_snn.n'cr' MOP_snn.n'cr' SE_xxx'cr' COM_xxxxxx'cr' MSR_xxx'cr' MT_xxxxcr TXPU_xxxxx'cr''lf']
RF Output (ON/OFF) Modulator Frequency Modulator Rate Modulator Rate Modulator Rate Modulator Power Offset Modulator Output Power Scrambler Enable (ON/OFF) Carrier Only Mode Modulator Spectrum Rotation Modulator Type Transmit IF Output Power-up Configuration
The Modulator configuration status command causes a block of data to be returned by the addressed mod. The block of data reflects the current configuration status of the modulator module. Additional configuration status of new options and features will always be appended to the end.
This command is used by the Tiernan M:N protection switch to collect information that is necessary to configure back-up mods. Because this command (content and/or order) can be changed at any time by Tiernan, it is advisable that other commands ('MCS_' and 'ICS_', or 'BCS_') be used for M&C systems. Note: Only displayed when RS-422 interface is installed.
Configuration Commands/Responses
103
RF Output (ON/OFF) Actual Status Not Config Module (OK/FLT) IF Synthesizer (OK/FLT) Data Clock Synthesizer (OK/FLT) I Channel (OK/FLT) Q Channel (OK/FLT) AGC Level (OK/FLT) IF Module fault (OK/FLT) Configuration Fault (OK/FLT) Number of Stored Faults Logged (0 to 10)
Monitor & Control Module (OK/FLT) Battery/Clock (OK/FLT) +5V Power Supply (OK/FLT) +12V Power Supply (OK/FLT) -12V Power Supply (OK/FLT) Mode (LOCAL or REMOTE) Number of Stored Faults Logged (0 to 10)
The common equipment status command causes a block of data to be returned which indicates the status of the common equipment. Bulk Consol Status Command: <add/BCS_'cr' Response: >add/BCS_p1,p2,p3, . . . pn'cr''lf'] This bulk consol status command causes bulk mod status to be returned. To reduce the length of the response, message parameter data are returned without identifiers. However, parameter identification can be determined by order of return. Each status parameter is terminated with a ',' (comma) except for the last parameter which has the standard message termination sequence ('cr''lf']). Most of the data returned is formatted the same way as the single command status request (refer to the appropriate portions of this document in preceding sections). Additional configuration status of new options and features will always be appended to the end. Parameter Parameter Name (Command Reference) Number 1 Description
MODEM REMOTE/LOCAL mode. p1 = n, where 'n' is '0' (LOCAL) or '1' (REMOTE). Modulator RF output (ref. 'RF_' command). Modulator IF frequency (ref. 'MF_' command). Modulator rate (ref. 'MR_' command). Modulator rate (ref. 'ASR_' command). p2 = n, where 'n' is '0' (off) or '1' (on).
p4 = nnnn_mmm.mmmmmm, code rate/data rate in Mbps. p5 = nnnn_mm.mmmmmm, code rate/ symbol rate in Msps.
Configuration Commands/Responses
105
10
p10 = n, where 'n' is '0' (Off), '1' (Dual),' 2' (Offset), or '3' (Center). p11 = n, where n = 0 (DVB-1) or 1 (DVB-2) p12 = n, where 'n' is '0' (NRM), '1' (INV), or '2'. p13 = n, where 'n' is '0' (NRM) or '1' (INV).
11
12
13
14
p14 = n, where 'n' is '0' (None), '1' (Data stable), or '2' (AIS).
15
Transmit 2047 pattern generator p15 = n, where 'n' is '0' (off) or '1' (on). (ref. 'ISP_' command). Transmit clock phase (ref. 'SYNC_' command). DVB Framing Type (ref. 'TDVB_' command). Modulator Spectrum Rotation (ref. 'MSR_' command). Reserved. Reserved. p16 = n, where 'n' is '0' (EXT), '1' (DATA), or '2' (AUTO). p17 = n, where n = '1' (188), '2' (187), or '3' (NONE). p18 = n, where 'n' is '0' (NRM) or '1' (INV).
16
17
18
19 20
22
23 to 32 33
Note: Parameters 23 through 27 of the BCS command are displayed for a specific installed interface card such as an RS-422 or ASI/RS-422. Bulk Consol. Status Faults Command: <add/BCSF_'cr' Response: >add/ BCSF_abcdefghijklmnop'cr''lf'] This command causes all mod fault status to be returned. To reduce the length of the response, fault status is embedded into the bit structure of the characters that are returned. Faults are indicated by a binary 1 in the designated bit position. Additional fault status of new options and features will be appended to the end or use existing reserved bits. Character 'a': Modulator fault status character 1. Bit 6 = 1 always. Bit 5 = Modulator module fault. Bit 4 = RF output status, actual not programmed status (1 = on, 0 = off). Bit 3 through Bit 0 = Binary representation (0 to 10) of the number of modulator stored faults. Character 'b': Modulator fault status character 2. Bit 6 = 1 always. Bit 5 = IF Synthesizer. Bit 4 = Data Clock Synthesizer. Bit 3 = I Channel. Bit 2 = Q Channel. Bit 1 = AGC Level. Bit 0 = Configuration. Character 'c': Modulator fault status character 3. Bit 6 = 1 always. Bit 5 = IF module. Bit 4 through Bit 0 reserved.
Configuration Commands/Responses
107
This command indicates that a change has or has not occurred on either the BCS_ or the BCSF_ response since the last BCS_ or BCSF_ poll.
Boot Firmware Command: <add/BFI_cr Information Response: >add/BFI_cr Ver:_xxx_yyy.zzzcr FW/nnnnnn-ddr'cr' mm/dd/yyyy'cr''lf'] Interface Firmware Information Command: <add/IFI_cr Response: >add/IFI_cr Ver:_xxx_yyy.zzzcr FW/nnnnnn-ddr'cr' mm/dd/yyyy'cr''lf'] Command: <add/EFI_cr Response: >add/EFI_cr FW/nnnnn-drrcr Mm/dd/yyyycrlf]
Reed-Solomon Command: <add/RSFI_cr Firmware Response: >add/RSFI_cr Information FW/nnnnn-drrcr (RSFI) Mm/dd/yyyycrlf] Interface Command: <add/IFI_cr Firmware Response: >add/IFI_cr Information FW/nnnnn-drrcr (As Required)) mm/dd/yyyycrlf] Modem Options/ Misc. Information Command: <add/MOI_'cr' Response: >add/MOI_'cr' s,OEM_LCD'cr' s,16QAM'cr' s,8PSK'cr'lf]
Stored Faults
109
Stored Faults
Information on stored faults is returned when requested. If no stored fault exists for a given fault number, the words NO Fault will be returned instead of the normal time/date status information. The following symbols are commonly used to define the stored faults status commands:
s s s s s s s
# hh mm ss MM DD
Fault number (0 to 9). 0 is the first fault stored Hours in 24-hr. format Minutes Seconds Month Day
YY or YYYY Year
Frame Sync Lock (OK/FLT) Transmit Data (OK/FLT) Transmit Synthesizer PLL Lock (OK/FLT) Transmit Clock Activity (OK/FL) Transmit FIFO (OK/FLT) Interface Module (OK/FLT) Data Format (OK/FLT) Video Sync (OK/FLT)
Monitor & Control Module (OK/FLT) Battery/Clock (OK/FLT) +5V Power Supply (OK/FLT) +12V Power Supply (OK/FLT) -12V Power Supply (OK/FLT)
Purpose
111
Appendix C
Purpose
Due to the numerous transport stream output formats available on the Tiernan DVB Encoders, there are several default configurations for the TVRM-75 DVB Modulator. When the Encoder is configured with the default configuration, the Modulator must be configured with the appropriate default configuration so that the Modulator will operate properly with the Encoder. The default configuration is designed to optimize the Modulators performance and minimize configuration conflicts between the Encoder and the Modulator. When the operator initiates a hard reset or when the firmware has been upgraded, the Modulator will reload its internal hardware defaults upon power-up. The Modulator must then be reconfigured with the appropriate Factory Default Configuration.
Table C-1 presents the Factory Default Configuration for the TVRM-75 when used in an application where a Tiernan Encoder is sending an ASI transport stream to the Modulators ASI input. For this application, configure the modulator with the default parameters shown in bold.
113
INTERFACE
SYSTEM
TIME/DATE
REMOTE BAUD RATE REMOTE ADDRESS REMOTE TYPE TEST MODE STATUS LAMP TEST DISPLAY CONTRAST
1 - Menu not available prior to firmware version 4.1.4 Note: a no fault condition is indicated by a - sign and a fault condition is indicated by a + sign.
Save the factory default configuration, cycle power to the unit, and verify that the factory default settings are displayed after power-up.
115
Table C-2 presents the Factory Default Configuration for the TVRM-75 when used in an application where a Tiernan Encoder is sending a serial RS422 transport stream to the Modulators serial RS422 Data input. For this application, configure the modulator with the default parameters shown in bold.
Table C-2 Factory Default Configuration for Serial RS422 Data Input
TOP MENU CONFIGURATION SUB MENU MODULATOR PARAMETER TX-DR QPSK 5/6 TX-SR QPSK 5/6 TX-IF FREQUENCY TX-OUTPUT TX-POWER LEVEL SCRAMBLER CARRIER MODE INTERFACE TX CLOCK PHASE TX DATA PHASE 2047 PATTERN TX SYNC SELECT TX DATA FAULT TX CLK ACTIVITY DVB FRAMING TYPE SAVE RECALL FAULTS/ALARMS MODULATOR CONFIGURATION CONFIGURATION ----------------------------` VALUE 8.448000Mbps 5.500187Msps 70.000000MHz ON -10dBm ON NORMAL NORMAL1, 2 NORMAL OFF CORR ON DATA NONE ALARM 188 1 - 10 1 - 10
Table C-2 Factory Default Configuration for Serial RS422 Data Input
TX INTERFACE COMMON STORED FAULTS/ALARMS MODULATOR NO FAULT -------------------------------------------------------
TX INTERFACE
NO FAULT
COMMON
NO FAULT
CLEAR??? UTILITY MODULATOR MOD POWER OFFSET MOD SPECTRUM POWER UP TX-IF INTERFACE INTERFACE TYPE RS422 INT SELECT RTS TX-IF CNTRL RTS STATE CTS STATE DM STATE ST STATE TT STATE SYSTEM TIME/DATE 0.0dB NORMAL LAST KNOWN ASI/RS422 RS422 OFF NORMAL NORMAL NORMAL NORMAL NORMAL SET CURRENT TIME SET CURRENT DATE
117
Table C-2 Factory Default Configuration for Serial RS422 Data Input
REMOTE BAUD RATE 19200 NONE 1 RS-232 -------------------------PRESS ENTER TO TEST 64 FW/5613-1H HARD/SOFT NORMAL CURRENT VERSION -------------------------XXXXXXX CODE - MOD NOT APPLICABLE
REMOTE ADDRESS REMOTE TYPE TEST MODE STATUS LAMP TEST DISPLAY CONTRAST M&C MODULE FW MASTER RESET ALARM RELAY 3 MOD OPTIONS REV EMULATION MOD OPTIONS MOD SERIAL # CONFIGURATION FACTORY SETUP
1 - TX CLOCK PHASE is set to INVERT for Revision 01 Serial RS422 Data Cable. 2 - TX CLOCK PHASE is set to NORMAL for Revision 02 Serial RS422 Data Cable. 3 - Menu not available prior to firmware version 4.1.4 Note - a no fault condition is indicated by a - sign and a fault condition is indicated by a + sign.
Save the factory default configuration, cycle power to the unit, and verify that the factory default settings are displayed after power-up.
119
Glossary
A
AC switching power supply A pulsewidth modulation, AC to DC converter. The TUI10 can receive and convert from 100 to 240 V inputs at 50 to 60 Hz. Amp or Ampere The standard unit of measure for electrical strength defined as the amount of current that would be produced by an electromotive force of one volt acting through a resistance of one ohm. ASI Asynchronous serial interface.
Autodetecting The capability of a unit to automatically sense and set its configuration to match the operational parameters of an incoming signal. Autoranging The capability of a power supply unit to accept variable voltage rates. Autosensing The capability of a power supply unit to detect variable voltage rates.
Builtinselftest.
Bit rate Refers to the number of bits of data transmitted over a given time period. See also bps. BNC British Naval ConnectorA type of connector featuring a locking pin on the female end and a cutout groove for the pin on the male end. bps A ratio of the number of bits of data transmitted to the number of seconds elapsed, expressed as bits per second.
Glossary
120
Buffer In data transmission, a buffer is a temporary storage location for information being sent or received. A buffer is usually located between two different devices that have different abilities or speeds for handling the data. Buffer overflow Within a data buffering system, the condition occurring whenever the number of data bits entering the buffer exceeds the data capacity of the buffer. Buffer underflow Within a data buffering system, the condition occurring whenever the number of data bits entering the buffer is not sufficient to maintain the buffer minimum output rate. Builtinselftest Evaluative procedures residing in the TUI10 microcontroller which are used to provide diagnostic information regarding its operational state.
Cband A portion of the electromagnetic spectrum used heavily for satellite transmissions. The uplink frequency is at 6GHz, and the downlink is at 4GHz. Traditional applications include voice communications, video conferencing, and broadcast TV and radio. Cable Loss Loss of signal quality within cable, typically due to impedance as a result of excessive cable length or material construction. Carrier Offset The frequency difference in Hertz measured between the programmed receive frequency and the actual frequency received. Channel signals. A single path for transmitting electric or electromagnetic
CSA Canadian Standards AssociationThe Canadian counterpart of the U.S. Underwriters Laboratories.
Data Typically refers to the information content of a signal including video, audio, graphic, or characterbased information. Data Bits Within a data packet, the bits which represent the information content of a packet. See also Data.
121
dB DecibelA unit of measure of signal strength, usually the relation between a transmitted signal and a standard signal source. An increase of 3 dB results in a doubling of the signal strength. An increase of 6 dB results in a quadrupling of the signal strength. Conversely, a decrease of 3 dB and 6 dB results in a reduction in signal strength by one half and three quarters, respectively. Decode To convert a coded signal into its original form. Demod Demodulation. See Demodulate. To retrieve an electrical signal from a carrier signal or
Demodulate wave.
DS3 A commercial leased line that has the capacity to handle up to 44.763 Mbps of digital information, as defined in ITU-T Rec. G.703. dsec DecisecondsA measurement of time that is equal to 0.1 seconds. For example, 15 dsec is equal to 1.5 seconds. DTE Data Termination EquipmentA generic name for any device that generates information to be transmitted to another device or over a transmission system. For example, visual display units, computers, and office workstations. DVB Digital Video BroadcastA set of standards providing the specifications for transmission and reception of digitally processed broadcasting signals.
E2 A commercial leased line that has the capacity to handle up to 8.448 Mbps of digital information, as defined in ITU-T Rec. G.703. E3 A commercial leased line that has the capacity to handle up to 34.368 Mbps of digital information, as defined in ITU-T Rec. G.703. Eb/No Eb =Energy per information bit; No =Noise energy per HertzSignal energy with respect to noise, expressed in energy per bit/noise in 1 Hz bandwidth.
Glossary
122
Fault FIFO
A disturbance that impairs or disrupts normal operations. First In, First OutA type of data buffer.
FPGA Field Programmable Gate Array A chip that can be reprogrammed for various uses. Functional Block A component that performs a specific process within a unit. For example, an input controller is a functional block within the TUI10.
G.703 ITUT Recommendation G.703, Physical/Electrical Characteristics of Hierarchical Digital Interfaces.An interface protocol used for terrestrial transmissions that operates at multiples of 64 Kbps PCM. Hz HertzA measurement of frequency in cycles of a waveform occurring in one second. One hertz is one cycle per second. HPA High power amplifier A device which provides the high power necessary to transmit radio signals from an earth terminal to a satellite.
IEC International Electrotechnical CommissionA Genevabased organization that sets international electrical and electronics standards and includes national committees from over 40 countries. IF Intermediate Frequency1. A frequency to which a signal wave is shifted locally as an intermediate step in transmission or reception. 2. The fixed frequency resulting from heterodyning the incoming signal with a signal from a local oscillator. IFL Interfacility linkTypically refers to an interfacility link cable used to connect a lownoise block (LNB) to an IRD. Often this IFL carries power from the IRD to the LNB. IF Looptest A diagnostic, troubleshooting, or operational test procedure designed to test operate satellite equipment by passing video and audio test signals through an encoder and satellite modulator, looping the output of the modulator to the input of the IRD, and monitoring the video and audio output of the IRD.
123
Impedance The total opposition of a device offers to the flow of alternating current. Measured in ohms and varies at different frequencies. Integrated Receiver/Decoder Within a satellite downlink system, a piece of equipment used to demodulate and decode a transport stream. IRD See Integrated Receiver/Decoder.
Kuband A portion of the electromagnetic spectrum in the 12GHz to 14GHz range. Used for satellites, employing 14GHz on the uplink and 11GHz on the downlink in support of such applications as broadcast TV for manonthestreet interviews and other situations requiring a small, portable dish. Ku is also used in Direct Broadcast Satellite (DBS) systems, or Direct Satellite System (DSS). Kbps Kilobits per second A ratio of 1000 bits transmitted per second. For example, 10Kbps is equal to 10,000 bits transmitted per second. KSps Kilosample or kilosymbol per secondA ratio of 1000 samples or symbols transmitted per second. For example, 10KSps is equal to 10,000 samples or symbols transmitted per second.
Lband 1. Portion of the electromagnetic spectrum commonly used in satellite applications, with frequencies in the 390 MHz to 1550 MHz range. 2. For an IRD, the frequency received from the LNB, existing in a range of 950 MHz to 2050 MHz. LCD Liquid crystal displayA display technology that uses liquid crystals to form displayed characters. LED Light emitting diodeA display technology that uses a light emitting diode to form displayed characters.
Glossary
124
Line Resolution The degree of sharpness of a displayed video image. LNB Low Noise Block A combination low noise amplifier and local oscillator used in some satellite downconverters. LO Local OscillatorA device within a frequency converter that is used to reduce or increase the frequency of the signal passed from the device input to output.
Mbps Megabits per secondA ratio of 1,000,000 bits transmitted per second. For example, 15Mbps is equal to 15,000,000 bits transmitted per second. MCPC See Multichannelpercarrier. Referring to one audio output not contained in a
MPEG Moving Picture Experts GroupA joint committee of the International Standards Organization (ISO) and the International Electrotechnical Commission (IEC). 2. A series of hardware and software standards designed to reduce the storage requirements of digital video. 3. A compression scheme for full motion video. MPEG1 Refers to ISO/IEC standards developed in 1991 by the ISO/IEC JTC1/SC29 WG11, Moving Picture Experts Group. MPEG2 Refers to ISO/IEC standards 13818 1 (Systems), 138182 (Video), 138183 (Audio), 138184 (Compliance). MTBF Mean time between failuresThe length of time a user may reasonably expect a device or system to work before an incapacitating fault occurs. Multichannelpercarrier Two or more video programs transmitted per digital transport stream.
125
Network Management System A system designed to keep a network operating near maximum efficiency and to provide operator interface to the managed system for configuring, isolating and correcting faults, and monitoring operational performance. Nonvolatile, fieldprogrammable memory A type of Flash ROM used to store configuration parameters. The ROM memory is configurable by the user but will not clear if the unit loses power. NTSC 1. National Television Standards Committee of the Electronic Industries Association (EIA) A committee which determines the video standards for broadcast in the U.S. 2. The U.S. standard for video broadcast which uses a 3.57945 MHz subcarrier whose phase varies with the instantaneous hue of the televised color, and whose amplitude varies with the instantaneous saturation of the color. A single frame (picture) in the standard consists of 525 horizontal scanning lines. Frames are scanned at the rate of 30 frames per second. 3. Used to describe the standard method of television transmission in the U.S., Canada, japan, Central America, and parts of South America.
Ohm A unit of measure for resistance symbolized by the Greek letter omega . Defined as the electrical resistance between two points of a conductor when a constant difference of potential of 1 volt, applied between these points produces in this conductor a current of 1 ampere, the conductor not being the source of any electromotive force. Overhead A number of data bits used for errorchecking, control, timing, and other communications functions that are inserted in the data stream as an additional to the individual data rates of the transport stream components. Overhead must be included when calculating the aggregate transport stream output data rate.
PAL Phase Alteration Line1. A broadcast television standard that uses a subcarrier which is alternated 90 degrees in phase from one line to the next to minimize hue errors in color transmission. 2. The color television transmission standard used in Europe and other parts of the world.
Glossary
126
PALI A European color television transmission standard that uses a 4.43361875 MHz subcarrier. A single frame in this standard consists of 625 scanning line, and frames are scanned at a rate of 25 frames per second. PALM A European color television transmission standard that uses a 3.57561149 MHz subcarrier. A single frame is this standard consists of 525 scanning lines, and frames are scanned at a rate of 30 frames per second. PGCA A proprietary conditional access method used by Tiernan equipment. PID Packet IdentifierWithin a data packet, the bits used for its identification. Pixel Picture Element1. The smallest unit of area of a video screen image that can be turned on or off, or varied in intensity. 2. The smallest division that makes up the raster scan line for a video display. PSI Program Specific Information.
QPSK Quadrature Phase Shift KeyingThe transmission of 2 bits per symbol, with each symbol being a phase range of the sine wave. In this fashion, a 2:1 compression ratio is achieved, resulting in a doubling of the efficiency with which a circuit is employed. RCD Remote Control DeviceA computer terminal used to configure and monitor an encoder or an IRD without using the units control front panel. RF Input The user configured receive frequency parameter.
Sample Rate The number of times per second that an analog signal is measured and converted to a binary number in order to convert the analog signal to a digital signal. Satellite downlink frequency Within a satellite system, the frequency, either Cband or Kuband, of the signal transmitted to the receiving dish.
127
SCPC
SMPT Society of Motion Picture and Television Engineers. A standard for video connections. The TUI10 has a SMPTE-310 port that handles data rates of 19.39 Mbps and 38.78 Mbps. SNMP Simple Network Management ProtocolA widely used network monitoring and control protocol. Data is passed from SNMP agents, which are hardware and/or software processes reporting activity in each network device (hub, router, bridge, etc.) to the workstation console used to oversee the network. The agents return information contained in a Management Information Base, which is a data structure that defines what is obtainable from the device and what can be controlled. sps 1. Samples per secondA ratio of the number of times that an analog signal is measured and converted to a binary number to seconds elapsed, expressed as samples per second. 2. Symbols per secondA ratio of symbols transmitted to seconds elapsed expressed as symbols per second. Commonly used to express the speed at which QPSK symbols are transmitted. Stereo Pair Two audio signals consisting of sound reproduction of the same audio source. Symbol In digital transmission, a recognizable electrical state that is associated with a signal element, which is an electrical signal within a defined period of time.
TAD1006 A Tiernan Communication, Inc. option module that allows an encoder to convert a composite analog video input into a serial digital video stream for inclusion in the transport stream output. The TAD1006 provides this functionality automatically without need for special setup or configuration. TDR600 A DVBcompliant, standalone MPEG2 integrated receiver/decoder produced by Tiernan Communications, Inc. that can decode both 4:2:2 and 4:2:0 video formatting.
Glossary
128
TDR7 A DVBcompliant, standalone MPEG2 integrated receiver/decoder produced by Tiernan Communications, Inc. TDR777 A DVBcompliant, standalone MPEG1 and MPEG2 integrated receiver/decoder produced by Tiernan Communications, Inc. TE6 A 4:2:2 MPEG2 encoder produced by Tiernan Communications, Inc. that is backwards compatible with existing 4:2:0 integrated receiver decoders.
TTM A Tiernan Communications, Inc. internal multiplexer that allows an encoder to multiplex various inputs into a single MPEG2 transport stream output.
TTM2070/RA A Tiernan Communications, Inc. option module that allows an encoder to multiplex video, audio, and user data inputs into an MPEG2 transport stream output with an ASI aggregate bit rate up to 53 Mbps and an RS422 aggregate bit rate up to 18 Mbps.
U V
UL VAC
VDC Volts DC. VDE Verband Deutscher ElektrotechnikerThe German counterpart of the U.S. Underwriters Laboratories. Viterbi Code Rate Forward error correction scheme.
129
Index
A
AC power 28 ASCII character format 95 ASI block diagram 84 data interface 82 defaults 90 description 83 factory defaults 112 front panel menus 88 receive output connectors, J6/J7 remote commands 90 RS-422 connector, J5 86 specifications 85 transmit input connectors, J3/J4 user interfaces 86 assemblies, modulator 15 commands interface 99 modulator 97 stored faults 109 system 100 connectors external 25 rear panel 26 transmit IF output, CP1
86
86
28
data interfaces ASI 82 description 67 installation 25 removal 25 RS-422 parallel/serial 68 software requirement 68 data rates 14 default settings 63 defaults factory 111 modulator settings 63
Index
130
25
factory defaults 111 ASI 112 RS-422 115 faults command tree 19 commands/responses 109 stored 109 firmware upgrade, default settings 63 front panel configuration interface menu 40 configuration menu 36 configuration menu, overview 35 configuration save & recall menus 43 faults & alarms menu 45 faults & alarms menus, overview 44 features 30 keypad 32 LEDs 30 main menu tree 34 menu structure, overview 33 operation, introduction 29 stored faults & alarms menu 49 utility factory setup menu 66 utility interface menu 54 utility interface menu, ASI/RS-422 57 utility interface menu, RS-422 55 utility menus overview 51 utility mod options menu 64 utility modulator menu 52 utility system menu 59 ground hard reset 28 63
G H
131
installation data interfaces 24 process 22 interface commands/responses keypad, front panel LEDs description front panel 32
99
K L
31 30
menus ASI 88 front panel, see front panel Utility Interface RS-422 Options message structure 95 command/response 96 device address 96 end character 97 start character 96 modulator commands/responses 97 default settings 63 fault tree 19 pinout ASI, RS-422 connector, J5 87 auxiliary connector, J5 77 DVB Interface, J3 74 EIA530 serial interface, J4 75 fault connector, J2 27 remote, J1 26 power, AC 28 rear panel connectors 26 remote commands ASI summary 90 RS-422 summary 80 remote operation message structure 95
78
Index
132
RS-422 configuration 70 data/timing criteria 73 defaults 80 factory defaults 115 front panel menus 78 overview 68 remote commands 80 specifications 70 user interfaces 72
software requirements data interfaces 68 specifications ASI 85 modulator 15 symbol rates 14 system commands/responses
100
Tiernan Communications Product Support department contact information TVRM75 assemblies 15 data rates 14 emissions, CE 28 external connections 25 fault tree 19 ground 28 installation process 22 overview 13 specifications 15 symbol rates 14 unpacking 21 unpacking the unit 21 user interfaces 72 ASI 86 DVB parallel/serial EIA-530 serial 75 serial, J4 75
ix
72
183
Before you call Product Support, please photocopy and complete the following Return Materials Authorization (RMA) Request form. This information enables the Product Support Engineer to understand, diagnose, and correct your product problems.
System Configuration
Format: PAL t
480P t 704 t
NTSC t 544 t
Frame Rate: __________________ Mux: Ouput Rate________________ Mod: Code Rate _______
IRD Configuration
Manual t
If Manual: ________________
ASI t
RS-422 t
Audio: Digital t
184