Synco 200

3101P03

Universal Controllers

RLU2...

With preprogrammed standard applications Freely programmable controller, for optimum adaptation to the relevant type of plant P-, PI, or PID mode Menu-driven operation Use For use on basic to complex ventilation, air conditioning and chilled water plant. The universal controllers are designed to handle the following controlled variables: Temperature, relative / absolute humidity, pressure / differential pressure, airflow, indoor air quality and enthalpy. Functions Operating modes Setpoints Selection of operating mode via status inputs: Comfort, Economy, Protection Display of current operating mode (Comfort, Economy, Protection) With each sequence controller: Individually adjustable heating and cooling setpoints (or maximum and minimum setpoints) for the Comfort and Economy modes Predefined room temperature setpoint with room unit or setpoint readjuster (passive) With each sequence controller: Predefined setpoint with remote setpoint adjuster (active or passive) Room temperature setpoint with summer and / or winter compensation With each sequence controller: Setpoint shift depending on sensor signal, selectable start and end points Universal inputs for: Passive or active analog input signals of various measured values (C, %, ---) Digital input signals (potential-free contacts)

Universal inputs

CE1N3101en 07.01.2004

Siemens Building Technologies HVAC Products

Control and supervisory functions

Universal controller (sequence controller) for 2 heating sequences (reverse acting) and 2 cooling sequences (direct acting), can be used as a controller providing P-, PI or PID mode, or as a differential controller Controller can be configured as a room / supply air temperature cascade controller with limitation of the supply air temperature Each sequence can be assigned modulating control (modulating output, step switch, mixed air damper / heat recovery equipment) and a pump. 2 sequences can act on the same modulating control (e.g. priority cooling / dehumidification) General limitation (minimum / maximum with PI mode per sequence controller, either as absolute limitation, e.g. for the supply air temperature or supply air humidity), or as relative temperature limitation (e.g. maximum limitation of the room / supply air temperature differential). Limitation acts on all sequences. Minimum limitation can be set to a lower setpoint while cooling is on (e.g cooling with DX cooler battery) Sequence limitation with PI mode per universal controller, can be defined as minimum or maximum limitation. Limitation acts on a single sequence (e.g. heat recovery anti-icing protection or maximum limitation of the heating coils return temperature) Locking of individual sequences Digital input (heating limit switch, from a heating controller) for changing the control strategy (room/supply air cascade/supply air), configurable 2-stage frost protection (modulating / 2-position) or frost protection thermostat (heating sequences delivering 100 % output, fault relay for switching off the fans) (with RLU210 only indication) Control of pumps, constantly ON at low outside temperatures, ON according to load sequence controller (not with RLU210) Control of an analog output. Configurable external presetting (controller used as a pure signal converter). Minimum and maximum position, invertible (only with RLU236) Control of mixed air dampers or heat recovery equipment with maximum economy changeover (not with RLU210) Control of a multistage aggregate with a step switch, with a maximum of 6 steps and a modulating output. The switching on/off points of each step can be adjusted. Adjustable delay times. Configurable external presetting (controller used as a pure step switch). Modulating output with minimum and maximum position, invertible (only with RLU236) Control of a multistage aggregate with a step switch, with a maximum of 2 steps and a modulating output. Functions as described above (not with RLU210) Control of a linear multistage aggregate with a step switch, with a maximum of 6 steps and a modulating output. Fixed assignment of switching on/off points to the load. Adjustable delay times and priority changeover. Configurable external presetting (controller used as a pure step switch). Modulating output for load assignment to the steps, with minimum and maximum position, invertible (only with RLU232 and RLU236) Control of a binary multistage aggregate with a step switch, with a maximum of 4 relays for 15 steps and a modulating output. Fixed switching on/off points with binary switching logic. Adjustable delay times. Configurable external presetting (controller used as a pure step switch). Modulating output for load assignment to the steps, with minimum and maximum position, invertible (only with RLU232 and RLU236)Control of a modulating 3-position actuator. Configurable presetting (controller used as a pure analog/3-position converter) (only with RLU232)Delivery of a passive measuring signal as an active signal for use by other controllers

2/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

Type summary Type reference RLU210 RLU222 RLU232 RLU236 Accessories Universal inputs 3 4 5 5 Digital inputs 1 1 2 2 Positioning outputs 1 2 3 3 Switching outputs 0 2 2 6 Number of control loops 1 1 2 2 Data Sheet N5655 N5243

Name Service tool Digital time switch

Type reference OCI700.1 SEH62.1

Ordering When ordering, please give name and type reference of the controller, e.g.: Universal controller RLU236. The products listed under "Accessories" must be ordered as separate items. Equipment combinations For equipment combinations, refer to the Basic Documentation P3101 or to the document covering the selected application. Product documentation Name Basic Documentation, detailed description of all functions Application Catalog for Synco200 "Ventilation / air conditioning plants" Instructions set (mounting, commissioning, operation) Declaration of Conformity (CE) Environmental Declaration for RLU210 and RLU222 Environmental Declaration for RLU230 and RLU236 Technical design Each controller offers up to 39 ready programmed applications. When commissioning a plant, the relevant basic type must be entered. All associated functions, terminal assignments, settings and displays will then automatically be activated and parameters that are not required will be deactivated. In addition, each type of universal controller has 2 empty applications loaded: 1 for basic type A (ventilation controller) 1 for basic type U (universal controller) With the help of the built-in operation or the OCI700.1 service tool, the controller affords: Activation of a preprogrammed application (refer to "Preprogrammed standard applications") Modification of a preprogrammed application Free configuration of applications Optimization of the controller settings For operating actions of the functions, refer to the Basic Documentation. 74 319 0424 0 CE1T3101xx CE1E3101en01 CE1E3101en02 Ordering number CE1P3101en

3/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

Mechanical design The universal controller consists of terminal base and controller insert with built-in operation. The terminal base can be fitted to a DIN mounting rail or is screwed directly on a flat surface. It consists of a plastic housing with 2 terminal levels. The controller insert engages in the terminal base. It consists of a plastic housing which accommodates the printed circuit boards. Controller operation is fully integrated. Operating, display and connecting elements
3101Z06

1 2 3 4

Legend

1 2 3 4 5 6 7 8 9

OK button for confirming the selected menu line or the value entered Navigation button, upward (+) for selecting the menu line or changing the value Navigation button, downward () for selecting the menu line or changing the value ESC button for returning to the previous menu or rejecting the value entered Connection facility for the service tool (RJ45 connector) Display Catch for fitting the controller to a top hat rail Fixing facility for a cable tie (cable strain relief) Rest for the terminal cover

Engineering notes The controller operates on AC 24 V. Operating voltage must conform to the requirements of SELV / PELV (safety extra low-voltage) The transformers used must be safety isolating transformers featuring double insulation to EN 60 742 or EN 61 558-2-6; they must be suited for 100 % duty Fuses, switches, wiring and earthing must be in compliance with local regulations Sensor wires should not be run parallel to mains carrying wires that power fans, actuators, pumps, etc. It is recommended to use the standard applications provided. Specific plant situations may require certain adaptations however Mounting and installation notes Controllers and extension modules are designed for: Mounting in a standard cabinet to DIN 43 880 Wall mounting on an existing top hat rail (to EN 50 022-35x7.5) Wall mounting with 2 fixing screws Not permitted are wet or damp spaces. The permissible environmental conditions must be observed Disconnected the system from the power supply prior to mounting the controller The controller insert may not be removed from the terminal base! All connection terminals for protective extra low-voltage are located in the upper half of the unit, those for mains voltage at the bottom

Low-voltage side

Mains-voltage side

4/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

3101Z07en

Each terminal (spring cage terminal) can accommodate only 1 solid wire or 1 stranded wire. For making the connections, the cables must be stripped for 7 to 8 mm. To introduce the cables into the spring cage terminals and to remove them, a screw driver size 1 is required. Cable strain relief can be provided with the help of the fixing facility for cable ties The controller is supplied complete with Installation and Operating Instructions Commissioning notes The configuration and parameters of the standard applications offered by the controller can be changed any time by service staff who have been trained by HVAC Products and who have the required access rights, either locally or online/offline with the service tool During the commissioning process, the application is deactivated and the outputs are in a defined off state On completion of the configuration, the controller automatically makes a new start When leaving the commissioning pages, the peripheral devices connected to the universal inputs (including the extension modules) are automatically tested and identified. If a peripheral device is missing, a fault status message will be delivered If adaptions to specific plants are required, they must be recorded and the documentation kept inside the control panel For the procedure to be followed when starting up the plant for the first time, refer to the Installation Instructions Disposal notes Larger plastic parts carry material identifications conforming to ISO / DIS 11 469 to facilitate environment-compatible disposal. Technical data
Power supply (G, G0) Rated voltage AC 24 V 20 % Safety extra low-voltage (SELV) / protective extra low-voltage (PELV) to HD 384 Requirements for external safety isolating transformer to EN 60 742 / EN 61 558-2-6, min. 10 VA, max. 320 VA Frequency 50 / 60 Hz Power consumption RLU210, RLU222 5 VA RLU232, RLU236 6 VA Supply line fusing max. 10 A Number Sensors Passive Active Signal sources Passive Active Digital inputs (X..., D...) Contact sensing Voltage Current Requirements for status and impulse contacts Signal coupling Type of contact Insulating strength against mains potential Perm. resistance Contacts closed Contacts open refer to "Type summary" LG-Ni 1000, T1, Pt 1000 2x LG-Ni 1000 (averaging) DC 0...10 V 0...2500 DC 0...10 V

Universal inputs Measured value inputs (X...)

DC 15 V 5 mA potential-free maintained or impulse contacts AC 3750 V to EN 60 730 max. 200 min. 50 k

5/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

Outputs Positioning outputs Y...

Number of positioning and switching outputs Output voltage Output current Max. load External supply line fusing Non-renewable fuse (slow) Automatic line cutout Release characteristic Cable length Relay contacts Switching voltage AC current At 250 V At 19 V Switch-on current Contact life at AC 250 V At 0.1 A res. At 0.5 A res. At 4 A res. Red. factor at ind. (cos = 0.6) Insulating strength Between relay contacts and system electronics (reinforced insulation) Between neighboring relay contacts (operational insulation) Q1Q2; Q3Q4; Q5Q6 Between relay groups (reinforced insulation) (Q1, Q2) (Q3, Q4) (Q5, Q6)

refer to "Type summary" DC 0...10 V 1 mA continuous short-circuit

Switching outputs AC 230 V (Q1x...Q6x)

max. 10 A max. 13 A B, C, D to EN 60 898 max. 300 m max. AC 265 V min. AC 19 V max. 4 A ohm., 3 A ind. (cos = 0.6) min. 5 mA min. 20 mA max. 10 A (1 s) guide values: 7 2 x 10 cycles 6 4 x 10 cycles (NO) 6 2 x 10 cycles (changeover) 5 3 x 10 cycles (NO) 5 1 x 10 cycles (changeover) 0.85

AC 3750 V, to EN 60 730-1 AC 1250 V, to EN 60 730-1 AC 3750 V, to EN 60 730-1 AC 24 V max. 4 A RJ45 connector (measuring errors can be corrected) max. 300 m max. 300 m max. 300 m max. 300 m max. 300 m refer to Data Sheet of the signal delivering device spring cage terminals 2 0.6 mm dia....2.5 mm 2 0.25...2.5 mm 2 0.25...1.5 mm IP 20 (when mounted) device suited for use with equipment of safety class II IEC 60 721-3-3 class 3K5 0 ...50 C 5...95 % r.h. (non-condensing) class 3M2 IEC 60 721-3-2 class 2K3 25...+ 70 C < 95 % r.h. class 2M2 type 1B 2 A 4000 V 125 C

Power supply external devices (G1) Interfaces Perm. cable lengths

Voltage Current Service tool connection facility For passive measuring and positioning signals Type of signal LG-Ni 1000, T1 Pt 1000 0...1000 1000...1235 Contact sensing For DC 0...10 V measuring and control signals

Electrical connections

Connection terminals For wires For stranded wires without ferrules For stranded wires with ferrules Degree of protection of housing to IEC 60 529 Safety class to EN 60 730

Degrees of protection

Environmental conditions

Operation to Climatic conditions Temperature (housing and electronics) Humidity Mechanical conditions Transport to Climatic conditions Temperature Humidity Mechanical conditions Mode of operation, automatic controls Degree of contamination, controls environment Software class Rated surge voltage Temperature for ball-pressure test of housing

Classifications to EN 60 730

6/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

Materials and colors

Terminal base Controller insert Packaging Product safety Automatic electrical controls for household and similar use Special requirements for energy controllers Electromagnetic compatibility Immunity industrial sector Emissions domestic sector, light industry conformity EMC directive Low-voltage directive -conformity to Australian EMC Framework Radio Interference Emission Standard

Polycarbonate, RAL 7035 (light-grey) Polycarbonate, RAL 7035 (light-grey) corrugated cardboard

Standards

EN 60 730-1 EN 60 730-2-11 EN 61 000-6-2 EN 61 000-6-3 89 / 336 / EEC 73 / 23 / EEC Radio communication act 1992 AS / NZS 3548 0.292 kg 0.334 kg 0.437 kg 0.481 kg

Weight, excl. packaging

RLU210 RLU222 RLU232 RLU236

Connection diagrams Internal diagrams RLU210

G G0

X1 M

X2 M G1

X3 M

G1 D1 M

G1 Y1 G0

G G0

X1 M

X2 M G1 G0

X3 M X4 M G1 G1 Y2 G0

D1 M N1 Q12

Q11 Q14 N2

Q23 Q24

G1 Y1

G G0

X1 M

X2 M G1 G0

X3 M X4 M G1 G1 Y2 G0

X5 M

D1 M D2 M Q12

Q11 Q14

Q33 Q34

G1 Y1

G1 Y3 G0

G G0

X1 M

X2 M G1 G0

X3 M X4 M G1 G1 Y2 G0

X5 M

D1 M D2 M Q12

Q11 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

G1 Y1

G1 Y3 G0

Legend

G, G0 G1 M G0 X... X..., D... Y... Q... N1, N2

Rated voltage AC 24 V Output voltage AC 24 V for powering external active sensors, signal sources, monitors or setting units Measuring neutral for signal input System neutral for signal output Universal signal inputs for LG-Ni 1000, 2x LG-Ni 1000 (averaging), T1, Pt 1000, DC 0...10 V, 0...2500 Contact sensing (potential-free) Control or status outputs, analog DC 0...10 V Potential-free relay outputs for AC 24...230 V Neutral conductor connection for radio interference suppression elements

Notes

Each terminal (spring cage terminal) can only accommodate 1 solid wire or 1 stranded wire. Double terminals are internally interconnected If a 3-position AC 230 V actuator is used, the radio suppression element must be activated: Connect terminal N1 to neutral conductor and fit a wire link between N1 ans N2 (see connection diagram 5)

7/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

3101G04

RLU236

3101G03

RLU232

3101G02

RLU222

3101G01

Connection diagrams Connections on the measuring side

Examples: Connection diagram 1: Measuring section with passive main and auxiliary sensors and passive signal source
(3) (1)
3101A01

G B M

AC 24 V

B1 B M B5 B2 M R5

G G0

X... M

X... M

X... M

N1

G0

Connection diagram 2: Measuring section with active sensor and active signal source
(1) (2) (3) (4) GL GN out in
3101A02

G B M G

AC 24 V

B3

R2

G G0

X... M G1

G1 M

X...

N1

G0

Connection diagrams 3 and 4: Measuring section with CO2 / VOC sensor with / without ventilation demand processor
3101A03

AC 24 V

G G0

G1 U3

U1 M

U2 D
10

X...

AC 24 V

(CO2) (VOC)

G M

U1 U2

(CO2) (VOC)

B4

U1 U2

B4

G G0

G1 M

X...

U4 S4

G0

N1
G0

N1

G0

Connections on the control and monitoring side


L G

Connection diagram 5:
3101A05

F4
p

S7 F31

L N

M D1 Q12

Q11 Q14

S5
Q11 Q33 Q11 Q23

AC 230 V AC 24 V

M X...

M D1

D2

G0

G0 G1 Y1

Q12

Q14

Q34

N1

N1 Q12

Q14

N2

Q24

G G0 N G0

F31
Y1 Y2 N

Y3

H1

K1

K2

Legend to the connection diagrams 1 through 5

N1 N2 B1 B3 B4 B5 F4 F31 H1 K1

Universal controller RLU2... Universal controller RLU222 Supply air temperature sensor QAM22... Frost sensor QAF63.2/QAF63... CO2 / VOC sensor QPA63... Room temperature sensor QAA24 Differential pressure sensor QBM81... Overcurrent release contact Horn for fault status message from fan Motor contactor "Release of fan"

K2 R5 R2 S4 S5 S7 U4 Y Y3

Motor contactor "Release of circulating pump" Setpoint readjuster BSG21.5 Setpoint adjuster BSG61 On / off switch "Locking signal" Digital time switch SEH62.1 Manual switch "On/ Standby" Ventilation demand processor AQP63.1 Actuating device with 3-position control Actuating device for heating

8/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

3101A04

N2

Preprogrammed standard applications Note The plant diagrams / connection diagrams assigned to the basic types are only examples. Basic type A01 Application no. / description ADA001 LU1 HQ
Extract air (room) temperature control with hot water heating coil. Options: Minimum and maximum limitation of the supply air temperature Remote setpoint readjuster
M N.Y1 T N.X1

Controller type RLU210

Plant diagram / connection diagram


S01

B2

T N.X2

B1

N.X3

R5

Y3

N.D1
S01

S5

RLU210

A02

ADA008 LU1 HQ
Supply air temperature control with hot water heating coil. Options: Room temperature cascade control Remote setpoint readjuster
M T

B5
N.X2 Cascade

R5

B1
N.X1

N.X3

Y3
N.Y1

S5
N.D1
S01

RLU210

A03

ADA002 LU1 HQ
Extract air (room) temperature control with hot water heating coil. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions
T N.X1

B2

T N.X3 M N.Y1

T N.X2

B9

B1

Y3

N.D1
S01

S5

RLU210

A04

ADA009 LU1 HQ
Supply air temperature control with hot water heating coil. Options: Room temperature cascade control Outside temperature-dependent functions
T

N.X2

B5

T N.X3 M N.Y1

T N.X1

B9

B1

Y3

N.D1
S01

S5

RLU210

A05

ACAD01 LU1 HQ
Extract air (room) temperature control with mixed air dampers and outside temperature-dependent functions. Options: External setpoint for maximum selection
Y2 Y1
T N.X3 M M N.Y1 M T N.X1

B2

Y6

B9

N.D1

S5

N.X2
S01

RLU210

A06

ADB001 LU1 HQ
Extract air (room) temperature control with chilled water cooling coil. Options: Minimum and maximum limitation of the supply air temperature Remote setpoint readjuster
M T

B2
N.X1

R5

B1
N.X2

N.X3

Y4
N.Y1

S5
N.D1

9/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

Controller type RLU210

Basic type A07

Application no. / description ADB005 LU1 HQ


Supply air temperature control with chilled water cooling coil. Options: Room temperature cascade control Remote setpoint readjuster

Plant diagram / connection diagram


S01

B5
N.X2 Cascade

R5

B1
N.X1 M N.Y1

N.X3

Y4

S5
N.D1
S01

RLU210

A08

ADB002 LU1 HQ
Extract air (room) temperature control with chilled water cooling coil. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions
T

B2
N.X1

B9
N.X3 M N.Y1

B1
N.X2

Y4

S5
N.D1
S01
S01
S01

RLU210

A09

ADB006 LU1 HQ
Supply air temperature control with chilled water cooling coil. Options: Room temperature cascade control Outside temperature-dependent functions
T

B5
N.X2 Cascade

B9
N.X3 M

B1
N.X1

Y4
N.Y1

S5
N.D1
S01

RLU210

A10

ADC001 LU1 HQ
Extract air (room) temperature control with heating / cooling coil. Options: Outside temperature-dependent functions
T N.X1

B2

T N.X3 M N.Y1 T

B9

Y5

N.X2

F16

RLU210

A11

ABC001 LU1 HQ
Supply air temperature control with heating / cooling coil and frost protection.
F3
N.X3 T

B1
N.X1

Y5
N.Y1

F16
N.X2

S5
N.D1

RLU210

A12

ADA003 LU1 HQ
Extract air (room) temperature control with hot water heating coil and frost protection. Options: Minimum and maximum limitation of the supply air temperature
M N.Y1 T N.X1

B2

N.X3 T T N.X2

F3

B1

Y3

N.D1

S5

RLU210

A13

ADA010 LU1 HQ
Supply air temperature control with hot water heating coil and frost protection. Options: Room temperature cascade control
F3

N.X2

B5

N.X3 T T N.X1 M N.Y1

B1

Y3

N.D1

S5

10/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

Controller type RLU210

Basic type U01

Application no. / description ADKA01 LU1 HQ


Extract air (room) humidity control (r.h.) with spray humidifier. Options: Maximum limitation of the supply air humidity Remote setpoint adjuster

Plant diagram / connection diagram


S01

B12
N.X1 [%]

M N.Y1

R5

B11
N.X2 [%]

N.X3

Y8

N.D1

S5

RLU210

U02

PB0001 LU1 HQ
Differential pressure control of water with speedcontrolled pump. Options: Minimum and maximum pressure limit controller Remote setpoint adjuster
f1 f2

B22

N.X1 [bar]

B23
N.X2

p
S01

G1

N.Y1 T

R5

N.X3

N.D1

S5

RLU210

U03

AZL001 LU1 HQ
Differential pressure control of air with speedcontrolled fan. Options: Minimum and maximum pressure limit controller Remote setpoint adjuster
f1 f2

B24
N.X1 [Pa]

B25

N.X2

p
S01

G1

N.Y1 T

R5

N.X3

N.D1

S5

RLU210

U04

ADI001 LU1 HQ
Extract air (room) humidity control (r.h.) with chilled water cooling coil. Options: External setpoint for maximum selection Remote setpoint adjuster
M N.Y1

B12
N.X1 [%]

R5

N.X3

Y4

N.D1

S5

N .X 2
S01

RLU210

U05

ADI002 LU1 HQ
Extract air (room) humidity control (a.h.) with chilled water cooling coil. Options: External setpoint for maximum selection Remote setpoint adjuster
M x

B12
N.X1 [g/kg]

R5

N.X3

Y4
N.Y1

S5
N.D1

N .X2
S01

RLU210

U06

AAZD01 LU1 HQ
Indoor air quality control with mixed air dampers. Options: External setpoint for maximum selection Remote setpoint adjuster
AQ

Y2 Y1

M M

N.X1 [ppm]

B4

N.Y1 M

Y6
T

R5

N.X3

N.D1

S5

N .X 2
S01

RLU222

A01

ADA006 LU2 HQ
Extract air (room) temperature control with electric air heater battery. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster 2-stage electric air heater battery
T

B2
N.X1

R5

B9
N.X3

E1
N.Q1 N.Q2 N.Y1

B1
N.X2

N.X4

S5
N.D1

11/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

Controller type RLU222

Basic type A02

Application no. / description ADA012 LU2 HQ


Supply air temperature control with electric air heater battery. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 2-stage electric air heater battery

Plant diagram / connection diagram


S01

B5
N.X2 Cascade

R5

B9
N.X3

E1
N.Q1 N.Q2 N.Y1

B1
N.X1

N.X4

S5
N.D1
S01

RLU222

A03

ADA014 LU2 HQ
Supply air temperature control with hot water heating coil. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster
T

B5
N.X2 Cascade

R5

B9
N.X3

B1
N.X1

N.X4

Y3
N.Q1 N.Q2

S5
N.D1
N.Q1 1 T N.X1

Extract air (room) temperature control with hot water heating coil, frost protection and fan release. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions

B2

N.X3 1 T N.X4 M N.Y1 T T N.X2

F3

B9

N.Q2

M3

B1

Y3

N.D1
S01

S5

RLU222

A05

ADA005 LU2 HQ
Extract air (room) temperature control with hot water heating coil, frost protection and fan release. Options: Minimum and maximum limitation of the supply air temperature Remote setpoint readjuster
M

N.Q1 1 T

B2
N.X3 1 T T T

F3

N.X1

R5

M3
N.Q2

B1
N.X2

N.X4

Y3
N.Y1

S5
N.D1 N.Q1 1 T

RLU222

A06

ADA0011 LU2 HQ
Supply air temperature control with hot water heating coil, frost protection and fan release. Options: Room temperature cascade control Outside temperature-dependent functions

B5
N.X2 Cascade

N.X3 1 T T T

F3

B9
N.X4 M

M3
N.Q2

B1
N.X1

Y3
N.Y1

S5
N.D1
S01

RLU222

A07

ADB003 LU2 HQ
Extract air (room) temperature control with DX cooler battery. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster 2-stage DX cooler battery
T

B2
N.X1

R5

B9
N.X3

M7
N.Q1 N.Q2 N.Y1

B1
N.X2

N.X4

S5
N.D1
S01

RLU222

A08

ADB007 LU2 HQ
Supply air temperature control with DX cooler battery. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 2-stage DX cooler battery
T

B5
N.X2 Cascade

R5

B9
N.X3

M7
N.Q1 N.Q2 N.Y1

B1
N.X1

N.X4

S5
N.D1

12/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

S01

RLU222

A04

ADA004 LU2 HQ

Controller type RLU222

Basic type A09

Application no. / description ADC002 LU2 HQ


Extract air (room) temperature control with hot water heating coil and chilled water cooling coil. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster

Plant diagram / connection diagram


S01

T N.X1

B2

T N.X3 M N.Y1

R5

B9

N.Q1 M N.Y2

M3

N.Q2

M4

N.X2

B1

N.X4

Y3

Y4

N.D1
S01

S5

RLU222

A10

ADC010 LU2 HQ
Supply air temperature control with hot water heating coil and chilled water cooling coil. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster
T

B5
N.X2 Cascade

R5

B9
N.X3 M

M3
N.Q1 M

M4
N.Q2

B1
N.X1

N.X4

Y3
N.Y1

Y4
N.Y2

S5
N.D1
S01

RLU222

A11

ADC004 LU2 HQ
Extract air (room) temperature control with electric air heater battery and chilled water cooling coil. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster 2-stage electric air heater battery
T N.X1

B2

T N.X3

T N.Q1 N.Q2 N.Y1

R5

B9

E1

N.X2 M N.Y2

B1

N.X4

Y4

N.D1
S01

S5

RLU222

A12

ADC012 LU2 HQ
Supply air temperature control with electric air heater battery and chilled water cooling coil. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 2-stage electric air heater battery
T

B5
N.X2 Cascade

R5

B9
N.X3

E1
N.Q1 N.Q2 N.Y1 M

B1
N.X1

N.X4

Y4
N.Y2

S5
N.D1
S01

RLU222

A13

ADC003 LU2 HQ
Extract air (room) temperature control with hot water heating coil and DX cooler battery. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster 2-stage DX cooler battery
T

B2
N.X1

R5

B9
N.X3 M

M7 Y3
N.Y1

B1
N.X2

N.X4

N.Q1 N.Q2 N.Y2

S5
N.D1
S01

RLU222

A14

ADC011 LU2 HQ
Supply air temperature control with hot water heating coil and DX cooler battery. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 2-stage DX cooler battery
T

B5
N.X2 Cascade

R5

B9
N.X3 M

M7 Y3
N.Y1 N.Q1 N.Q2 N.Y2

B1
N.X1

N.X4

N.D1
S01

S5

RLU222

A15

ADC006 LU2 HQ
Extract air (room) temperature control with hot water heating coil, frost protection, chilled water cooling coil and fan release. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions

N.Q1 1 T N.X1

B2

N.X3 1 T N.X4 M N.Y1 T T N.X2 M N.Y2

F3

B9

N.Q2

M3

B1

Y3

Y4

N.D1

S5

13/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

Controller type RLU222

Basic type A16

Application no. / description ADC014 LU2 HQ


Supply air temperature control with hot water heating coil, frost protection, chilled water cooling coil and fan release. Options: Room temperature cascade control Outside temperature-dependent functions

Plant diagram / connection diagram


N.Q1 1 T

B5
N.X2 Cascade

N.X3 1 T T T

F3

B9
N.X4 M

M3
N.Q2 M

B1
N.X1

Y3
N.Y1

Y4
N.Y2 N.Q1 1 T N.X1

S5
N.D1

Extract air (room) temperature control with hot water heating coil, frost protection, DX cooler battery and fan release. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions

B2

N.X3 1 T N.X4 M N.Y1 T N.Y2 T N.X2

F3

B9

Y7

B1

Y3

N.Q2
N.Q1 1

M7

N.D1

S5

Supply air temperature control with hot water heating coil, frost protection, DX cooler battery and fan release. Options: Room temperature cascade control Outside temperature-dependent functions

B5
N.X2 Cascade

N.X3 1 T T N.Y2 M T

F3

B9
N.X4

Y7

B1
N.X1

Y3
N.Y1

N.Q2

M7

S5
N.D1
S01

RLU222

A19

AEAG01 LU2 HQ
Extract air (room) temperature control with closedcircuit heat recovery system and hot water heating coil. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster
T

M6
M

N.Q2

N.X1

B2

Y6
T N.X3

N.Y2 T T

R5

B9

N.Q1 M N.Y1

M3

N.X2

B1

N.X4

Y3

N.D1
S01

S5

RLU222

A20

AEAG02 LU2 HQ
Supply air temperature control with closed-circuit heat recovery system and hot water heating coil. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster
T

B5
N.X2 Cascade

M6
M

N.Q2

Y6
T

N.Y2 T T

R5

N.X4

B9
N.X3 M

M3
N.Q1

B1
N.X1

Y3
N.Y1

S5
N.D1

Extract air (room) temperature control with mixed air dampers, hot water heating coil, frost protection and fan release. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions

Y2 Y1
T N.X4

M M

T N.X1

B2

N.Y2 M

Y6

N.X3 1 T T N.X2

F3

B9

N.Q2 M N.Y1

M3

B1

Y3

N.D1
N.Q1 1 T

S5

Supply air temperature control with mixed air dampers, hot water heating coil, frost protection and fan release. Options: Room temperature cascade control Outside temperature-dependent functions

B5
N.X2 Cascade

Y2 Y1
T

M M

N.Y2 M

Y6

F3
N.X3 1 T T

B9
N.X4 M

M3
N.Q2

B1
N.X1

Y3
N.Y1

N.D1

S5

14/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

RLU222

A22

AEAD02 LU2 HQ

S01

RLU222

A21

AEAD01 LU2 HQ

N.Q1

S01

RLU222

A18

ADC016 LU2 HQ

S01

RLU222

A17

ADC007 LU2 HQ

S01

Controller type RLU222

Basic type A23

Application no. / description ADB009 LU2 HQ


Extract air (room) temperature control with chilled water cooling coil and 2 cooling towers. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster

Plant diagram / connection diagram


S01

T N.X1

B2

T N.X3

N.Q1
f1 f2

N.Q2
f1 f2

T N.X2

R5

N.X4

B9

G1

N.Y1

G2

N.Y2

B1

N.D1

S5

RLU222

A24

AECD01 LU2 HQ
Extract air (room) temperature control with mixed air dampers, hot water heating coil and DX cooler battery. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster
Y2 Y1
T N.X3 M N.Y1 M M N.Y2 M T N.X1

B2

Y6

R5

B9

N.X4

N.Q1

M3

M7

N.Q2

N.X2

B1

Y3

N.D1
S01

S5

RLU222

A25

AECD04 LU2 HQ
Supply air temperature control with mixed air dampers, hot water heating coil and DX cooler battery. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster
T

B5
N.X2 Cascade

Y2 Y1
T

M M

N.Y2 M

Y6
T T

R5

B9
N.X3 M

M3
N.Q1

M7
N.Q2

B1
N.X1

N.X4

Y3
N.Y1

S5
N.D1
S01

RLU222

A26

AECD02 LU2 HQ
Extract air (room) temperature control with mixed air dampers, hot water heating coil and DX cooler battery. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster 2-stage DX cooler battery
Y2 Y1
T N.X3 M N.Y1 M M T N.X1

B2

N.Y2 M

Y6

R5

B9

N.Q1 N.Q2

M7

N.X2

B1

N.X4

Y3

N.D1

S5

RLU222

A27

AECD05 LU2 HQ
Supply air temperature control with mixed air dampers, hot water heating coil and dx cooler battery. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 2-stage DX cooler battery
T

B5
N.X2 Cascade

Y2 Y1
T

M M

N.Y2 M

Y6
T T

R5

B9
N.X3 M

M7
N.Q1 N.Q2

B1
N.X1

N.X4

Y3
N.Y1

S5
N.D1
S01

RLU222

A28

AECD03 LU2 HQ
Extract air (room) temperature control with mixed air dampers, electric air heater battery and chilled water cooling coil. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster 2-stage electric air heater battery
Y2 Y1
T N.X3 M M T N.X1

B2

N.Y1 M

Y6

T N.Q1 N.Q2 M N.Y2

R5

B9

E1

N.X4

N.X2

B1

Y4

N.D1

S5

RLU222

A29

AECD06 LU2 HQ
Supply air temperature control with mixed air dampers, electric air heater battery and chilled water cooling coil. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 2-stage electric air heater battery
T

B5
N.X2 Cascade

Y2 Y1

M M

N.Y1 M T

Y6
T T

R5

B9
N.X3

E1
N.Q1 N.Q2 M

B1
N.X1

N.X4

Y4
N.Y2

S5
N.D1

15/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

S01

S01

Controller type RLU222

Basic type U01

Application no. / description ADKA02 LU2 HQ


Extract air (room) humidity control (r.h.) with spray humidifier. Options: Maximum limitation of the air humidity Remote setpoint adjuster 2-stage spray humidifier

Plant diagram / connection diagram


S01

B12
N.X1 [%]

R5

N.Q1 N.Q2 N.Y1

Y8

B11
N.X2 [%]

N.X3

N.D1

S5

RLU222

U02

PB0002 LU2 HQ
Differential pressure control of water with speedcontrolled pumps. Options: Minimum and maximum pressure limit controller Outside temperature-dependent functions Remote setpoint adjuster
N.Q1
f1 f2

B22
N.Q2
f1 f2

N.X1 [bar]

B23
N.X2

N.Y1

G1

N.Y2 T

G2

R5

N.X4

T N.X3

B9

N.D1

S5

RLU222

U03

AZL002 LU2 HQ
Differential pressure control of air with speedcontrolled fans. Options: Minimum and maximum pressure limit controller Outside temperature-dependent functions Remote setpoint adjuster
N.Q1
f1 f2

B24
N.Q2
f1 f2

N.X1 [Pa]

B25
N.X2

G1

N.Y1

N.Y2 T

G2

R5

N.X4

T N.X3

B9

N.D1
S01

S5

RLU222

U04

ADI003 LU2 HQ
Extract air (room) humidity control (r.h.) with DX cooler battery. Options: External setpoint for maximum selection Room temperature-dependent shifting of humidity setpoint Remote setpoint adjuster 2-stage DX cooler battery
T

S01

S01

B5

N.X3

B12
N.X1 [%]

T N.Q1 N.Q2 N.Y1

R5

N.X4

M7

N.D1

S5

N .X2
S01

RLU222

U05

ADI005 LU2 HQ
Extract air (room) humidity control (a.h.) with DX cooler battery. Options: External setpoint for maximum selection Room temperature-dependent shifting of humidity setpoint Remote setpoint adjuster 2-stage DX cooler battery
x N.X1 [g/kg] T

B5

N.X3

B12

T N.Q1 N.Q2 N.Y1

R5

N.X4

M7

N.D1

S5

N .X2
S01

RLU222

U06

AAZD02 LU2 HQ
Indoor air quality control with mixed air dampers and fan control. Options: External setpoint for maximum selection Outside temperature-dependent functions Remote setpoint adjuster 2-speed fan
AQ

Y2 Y1
T N.X3

M M

N.X1 [ppm]

B4

N.Y1 M

Y6
T

B9

M1

R5

N.X4

N.Q1 N.Q2

N.D1

S5

N .X 2
S01

RLU222

U07

ADZA01 LU2 HQ
Extract air (room) humidity control (r.h.) with spray humidifier and DX cooler battery. Options: Maximum limitation of the supply air humidity External setpoint for maximum selection Remote setpoint adjuster

B12
N.X1 [%]

R5

N.Q1 N.Y1

Y8

M7

N.Q2 N.Y2

N.X2 [%]

B11

N.X4

N.D1

S5

N .X3

16/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

Controller type RLU222

Basic type U08

Application no. / description CZC001 LU2 HQ


Temperature control of chilled ceilings. Options: Setpoint compensation depending on humidity Deviation alarm

Plant diagram / connection diagram


S01

T M N.Y1 N.X1

B1

N.X2

B16

Y4

H1

N.Q1

N.D1

S5

Temperature control of mixing heating circuit. Options: Minimum limitation of the return temperature Outside temperature-dependent functions Remote setpoint adjuster

N.X3

N.X1

B1

Y3

N.Q1 N.Q2 M T

S01

RLU222

U09

HZC001 LU2 HQ

B9

R5

N.X4

N.X2 N.D1

B7

S5

RLU222

U10

ZZZ001 LU2 HQ
3-position actuator
G G0

DC 0 ... 10 V

X1 M

G1

D1 M N1 Q12

Q11 Q14
3P

Q23 N2 Q24

RLU222

RLU222

U11

ZZZ002 LU2 HQ
Variable 2-step switch
G G0

DC 0 ... 10 V

X1 M

G1

D1 M N1 Q12

Q11 Q14 N2

Q23 Q24

RLU222

2Q VAR.

Extract air (room) temperature control with heat recovery, hot water heating coil, frost protection and fan release. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Anti-icing protection for heat recovery Comfort / Economy changeover

1 T N.X4 T N.X1

B10
N.X3 1 T T

B2

F3

T N.X2

N.X5

B9

Y11

N.Y2

N.Q3 M N.Y1

M3

B1

S5 S6

Y3

N.D1 N.D2

Supply air temperature control with heat recovery, hot water heating coil, frost protection and fan release Options: Room temperature cascade control Outside temperature-dependent functions Anti-icing protection for heat recovery Comfort / Economy changeover

1 T

B5
N.X2 Cascade

B10
N.X4 N.X3 1 T T T

F3

B9
N.X5

Y11
N.Y2 M

M3
N.Q3

B1
N.X1

S5
N.D1

Y3
N.Y1
N.Q1 1 T

S6

N.D2

Supply air temperature control with hot water heating coil, frost protection, chilled water cooling coil and fan release Options: Room temperature cascade control Outside temperature-dependent functions Comfort / Economy changeover

B5
N.X2 Cascade

F3
N.X3 1 T T T

B9
N.X4 M

M3
N.Q3 M

B1
N.X1

S5
N.D1

Y3
N.Y1

Y4
N.Y2

S6

N.D2

17/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

RLU232

A03

ADC015 LU3 HQ

S01

RLU232

A02

AEAF02 LU3 HQ

N.Q1

S01

RLU232

A01

AEAF01 LU3 HQ

N.Q1

A01

A01

Controller type RLU232

Basic type A04

Application no. / description AECG01 LU3 HQ


Extract air (room) temperature control with closedcircuit heat recovery system, hot water heating coil and chilled water cooling coil. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Anti-icing protection for heat recovery Remote setpoint readjuster Comfort / Economy changeover

Plant diagram / connection diagram


S01

T T

B21
N.X4

M6
M

N.Q3

B2
N.X1

Y6
T

N.Y2 T T

R5

N.X5

B9
N.X3 M

M3
N.Q1 M

B1
N.X2

S5
N.D1

Y3
N.Y1

Y4
N.Y3

S6

N.D2

RLU232

A05

AECG02 LU3 HQ
Supply air temperature control with closed-circuit heat recovery system, hot water heating coil and chilled water cooling coil. Options: Room temperature cascade control Outside temperature-dependent functions Anti-icing protection for heat recovery Remote setpoint readjuster Comfort / Economy changeover
T T

B5
N.X2 Cascade

B21
N.X4

M6
M

N.Q3

Y6
T

N.Y2 T T

R5

N.X5

B9
N.X3 M

N.Q1 M

M3

B2
N.X1

S5
N.D1

Y3
N.Y1

Y4
N.Y3

S6

N.D2

RLU232

A06

AECF01 LU3 HQ
Extract air (room) temperature control with heat recovery, hot water heating coil and chilled water cooling coil. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Anti-icing protection for heat recovery Remote setpoint readjuster Comfort / Economy changeover
T T

B10
N.X4

B2
N.X1

B9
N.X3

Y11
N.Y2 M

M3
N.Q1 M

M4
N.Q3

B1
N.X2

R5

N.X5

S5
N.D1

Y3
N.Y1

Y4
N.Y3

S6

N.D2

RLU232

A07

AECF03 LU3 HQ
Supply air temperature control with heat recovery, hot water heating coil and chilled water cooling coil. Options: Room temperature cascade control Outside temperature-dependent functions Anti-icing protection for heat recovery Remote setpoint readjuster Comfort / Economy changeover
T T

B5
N.X2 Cascade

B10
N.X4

B9
N.X3

Y11
N.Y2 M

M3
N.Q1 M

M4
N.Q3

B1
N.X1

R5

N.X5

S5
N.D1

Y3
N.Y1

Y4
N.Y3

S6
N.Q1 1

N.D2

Extract air (room) temperature control with heat recovery, hot water heating coil, frost protection, chilled water cooling coil and fan release. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Anti-icing protection for heat recovery Comfort / Economy changeover

T N.X5

T N.X1

B10
N.X3 1 T T

B2

F3

T N.X2 M N.Y3

N.X4

B9

Y11

N.Y2

M N.Y1

N.Q3

M3

B1

S5 S6

Y3

Y4

N.D1 N.D2

Supply air temperature control with heat recovery, hot water heating coil, frost protection, chilled water cooling coil and fan release. Options: Room temperature cascade control Outside temperature-dependent functions Anti-icing protection for heat recovery Comfort / Economy changeover

1 T

B5
N.X2 Cascade

B10
N.X5 N.X3 1 T T T

F3

B9
N.X4

Y11
N.Y2 M

M3
N.Q3 M

B1
N.X1

S5 S6
N.D1 N.D2

Y3
N.Y1

Y4
N.Y3

18/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

RLU232

A09

AECF04 LU3 HQ

N.Q1

S01

RLU232

A08

AECF02 LU3 HQ

S01

S01

S01

Controller type RLU232

Basic type A10

Application no. / description ADC009 LU3 HQ


Extract air (room) temperature control with hot water heating coil and 2 chilled water cooling coils. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster Comfort / Economy changeover

Plant diagram / connection diagram


1S01

T N.X1

B2

T N.X3 M N.Y1

T N.Q1 M N.Y2

B9

M3

N.Q3 M

M4

N.X2

B1

R5

N.X4

S5 S6

Y3

Y4

Y15

N.D1 N.D2
S01

N.Y3

RLU232

A11

ADC018 LU3 HQ
Supply air temperature control with hot water heating coil and 2 chilled water cooling coils. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster Comfort / Economy changeover
T

B5
N.X2 Cascade

B9
N.X3 M

M3
N.Q1 M

M4
N.Q3 M

B1
N.X1

R5

N.X4

S5
N.D1

Y3
N.Y1

Y4
N.Y2

Y15
N.Y3

S6

N.D2
S01

RLU232

A12

AEDK01 LU3 HQ
Supply air temperature control and room humidity control (r.h.) with heat recovery, hot water heating coil and spray humidifier. Options: Room temperature cascade control Maximum limitation of the supply air humidity Outside temperature-dependent functions Comfort / Economy changeover
T T

B15 B5
N.X3 N.X2 Cascade

B9
N.X5

Y11
N.Y2 M

M3
N.Q1

M N.Q3 N.Y3

B1 B11
N.X1 N.X4

Y8

S5
N.D1

Y3
N.Y1

S6

N.D2

Extract air (room) temperature control and dewpoint control with hot water preheating coil, frost protection, chilled water cooling coil, hot water reheating coil and fan release. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Comfort / Economy changeover

1 T N.X1

B2

N.X4 1 T N.X5 M N.Y2 M N.Y3 T T N.X3 T N.X2 M

F3

B9

B27

B1

S5 S6

Y3

Y4

Y10

N.D1 N.D2

N.Y1

RLU232

A14

ADFA01 LU3 HQ
Supply air temperature and extract air (room) humidity control (r.h.) with hot water heating coil, frost protection, spray humidifier, chilled water cooling coil and fan release. Options: Maximum limitation of the supply air humidity Outside temperature-dependent functions Comfort / Economy changeover

B12
N.X2 1 T N.X5 M N.Y1 T N.Y3 N.Q3 T

F3

N.X3

B9

Y8

M M N.Y2
N.Q1

N.X1 N.X4

B1 B11 S5 S6
N.D1 N.D2

M8

Y3

Y4

Extract air (room) temperature control and dewpoint control with hot water preheating coil, frost protection, spray humidifier, chilled water cooling coil, hot water reheating coil and fan release. Options: Minimum and maximum limitation of the supply air temperature External setpoint for maximum selection Comfort / Economy changeover

1 T N.X1

B2

N.X5 1 T T N.X4 M N.Y3 M N.Y2 T N.X2 M N .X3 ( 0...1 0 V ) N.D1 N.D2

F3

B27

B1

S5 S6

Y3

Y4

Y10

N.Y1

Supply air temperature and room humidity control (r.h.) with mixed air dampers, hot water heating coil, frost protection, chilled water cooling coil, spray humidifier and fan release. Options: Room temperature cascade control Outside temperature-dependent functions Comfort / Economy changeover

Y2 Y1
T

M M

B15 B5 F3
N.X3 1 T T N.X4 N.X2 Cascade

N.Y2 M

Y6

B9
N.X5 M

B1
N.X1

M8
N.Q1

S5
N.D1

Y3
N.Y1

Y4
N.Y3

S6

N.D2

19/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

RLU232

A16

AEFH01 LU3 HQ

N.Q3

S01

RLU232

A15

ADFA02 LU3 HQ

S01

N.Q1

S01

RLU232

A13

ADE001 LU3 HQ

N.Q1

Controller type RLU232

Basic type U01

Application no. / description ABA001 LU3 HQ


2 independent supply air temperature control systems with hot water heating coils. Options: 2 independent remote setpoint adjusters Outside temperature-dependent functions

Plant diagram / connection diagram

M3.1
N.Q1 T N.X5

B1.1
N.X1 T

M3.2 R5.1
N.X2 N.Q3

B1.2
N.X3 T

R5.2
N.X4

B9

N.Y1

Y3.1

N.Y2

Y3.2

S5

N.D1

RLU232

U02

ADL001 LU3 HQ
Supply and extract air volume control with fan control. Options: 2 independent remote setpoint adjusters Outside temperature-dependent functions
p

N.Q2 N.Y2

G2

f1

f2

N.X3

B8

T N.X5

B9

N.Q1 N.Y1

G1

f1

f2

N.X1

B7

R5.1
N.X4

R5.2
N.X2

S5

N.D1

RLU232

U03

ZZZ003 LU3 HQ
Linear 2-step switch
G G0

DC 0 ... 10 V

X1 M

G1

D1 M Q12

Q11 Q14

Q33 Q34

RLU232

2Q LIN.

RLU232

U04

ZZZ004 LU3 HQ
Binary 2-step switch
G G0

DC 0 ... 10 V

X1 M

G1

D1 M Q12

Q11 Q14

Q33 Q34

RLU232

Q1 Q1 Q2

2Q BIN.

RLU232

U05

ZZZ005 LU3 HQ
Variable 2-step switch
G G0

DC 0 ... 10 V

X1 M

G1

D1 M Q12

Q11 Q14

Q33 Q34

RLU232

2Q VAR.

RLU236

A01

ADA007 LU3 HQ
Extract air (room) temperature control with electric air heater battery. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster 6-stage electric air heater battery Comfort / Economy changeover
T N.X1

A01
S01 S01

B2

T N.X3

R5

B9

E1

N.Q4 N.Q1 N.Q5 N.Q2 N.Q6 N.Q3 N.Y1

N.X2

B1

N.X4

S5 S6

N.D1 N.D2

RLU236

A02

ADA013 LU3 HQ
Supply air temperature control with electric air heater battery. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 6-stage electric air heater battery Comfort / Economy changeover
T

B5
N.X2 Cascade

R5

B9
N.X3

E1

N.Q4 N.Q1 N.Q5 N.Q2 N.Q6 N.Q3 N.Y1

B1
N.X1

N.X4

S5
N.D1

S6

N.D2

20/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

A01

A01

S01

S01

Controller type RLU236

Basic type A03

Application no. / description ADB004 LU3 HQ


Extract air (room) temperature control with DX cooler battery. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster 6-stage dx cooler battery Comfort / Economy changeover

Plant diagram / connection diagram


S01

B2
N.X1

R5

B9
N.X3

M7

N.Q4 N.Q1 N.Q5 N.Q2 N.Q6 N.Q3 N.Y1

B1
N.X2

N.X4

S5
N.D1

S6

N.D2

RLU236

A04

ADB008 LU3 HQ
Supply air temperature control with DX cooler battery. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 6-stage DX cooler battery Comfort / Economy changeover
T

B5
N.X2 Cascade

R5

B9
N.X3

M7

N.Q4 N.Q1 N.Q5 N.Q2 N.Q6 N.Q3 N.Y1

B1
N.X1

N.X4

S5
N.D1

S6

N.D2
S01

RLU236

A05

ADC005 LU3 HQ
Extract air (room) temperature control with electric air heater battery and DX cooler battery. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions Remote setpoint readjuster 4-stage electric air heater battery 2-stage DX cooler battery Comfort / Economy changeover
T N.X1

B2

T N.X3

R5

B9

E1

N.Q1 N.Q2 N.Q3 N.Q4 N.Y1

M7

N.Q5 N.Q6 N.Y2

N.X2

B1

N.X4

S5 S6

N.D1 N.D2

RLU236

A06

ADC013 LU3 HQ
Supply air temperature control with electric air heater battery and DX cooler battery. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 4-stage electric air heater battery 2-stage DX cooler battery Comfort / Economy changeover
T

B5
N.X2 Cascade

R5

B9
N.X3

E1
N.Q1 N.Q2 N.Q3 N.Q4 N.Y1

M7

B1
N.X1

N.X5

N.Q5 N.Q6 N.Y2

S5
N.D1

S6

N.D2

Extract air (room) temperature control with hot water air heating coil, frost protection, DX cooler battery and fan release. Options: Minimum and maximum limitation of the supply air temperature Outside temperature-dependent functions External absolute remote setpoint adjuster 4-stage DX cooler battery Comfort / Economy changeover

1 T N.X1

B2

N.X3 1 T N.X4 M N.Y1 T T T

F3

R5

B9

N.Q2

M3

M7

Y3

N.Q3 N.Q4 N.Q5 N.Q6 N.Y2

N.X2

B1

N.X5

S5 S6

N.D1 N.D2

Supply air temperature control with hot water heating coil, frost protection, DX cooler battery and fan release. Options: Room temperature cascade control Outside temperature-dependent functions Remote setpoint readjuster 4-stage DX cooler battery Comfort / Economy changeover

B5
N.X2 Cascade

F3
N.X3 1 T T T T

R5

B9
N.X4 M N.Y1

M3
N.Q2

M7

B1
N.X1

N.X5

Y3

N.Q3 N.Q4 N.Q5 N.Q6 N.Y2

S5
N.D1

S6

N.D2

21/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

RLU236

A08

ADC017 LU3 HQ

N.Q1

S01

RLU236

A07

ADC008 LU3 HQ

N.Q1

S01

S01

Controller type RLU236

Basic type A09

Application no. / description AEDL01 LU3 HQ


Supply air temperature and supply air humidity control (r.h.) with closed-circuit heat recovery system, hot water heating coil, frost protection, spray humidifier and fan release. Options: Room temperature cascade control Outside temperature-dependent functions Comfort / Economy changeover

Plant diagram / connection diagram


N.Q1 1 T

B5
N.X2 Cascade

M6
M

N.Q3

Y6
T

F3
N.X3 1 T T M

N.Y2

B9
N.X5 M

M3
N.Q2

B1 B11
N.X1 N.X4

Y8
N.Q4 N.Y3

S5
N.D1

Y3
N.Y1

S6

N.D2

Supply air temperature and supply air humidity control (r.h.) with closed-circuit heat recovery system, DX cooler battery, hot water heating coil, frost protection, spray humidifier and fan release. Options: Room temperature cascade control Outside temperature-dependent functions 2-stage DX cooler battery Comfort / Economy changeover

B5
N.X2 Cascade

M6
M

N.Q3

Y6

N.Y2

F3
N.X3 1 T M

B9
N.X5

M7
N.Q4 N.Q5 M

M3
N.Q2

B1 B11
N.X1 N.X4

Y8
N.Q6 N.Y3

S5
N.D1

Y3
N.Y1

S6

N.D2

RLU236

U01

ADKA03 LU3 HQ
Extract air (room) humidity control (r.h.) with spray humidifier. Options: Maximum limitation of the supply air humidity Outside temperature-dependent functions Remote setpoint adjuster 6-stage spray humidifier Comfort / Economy changeover

B12
N.X1 [%]

T N.X3

R5

B9

Y8 M N.Q4 N.Q5 N.Q1 N.Q6 N.Q2 N.Y1 N.Q3

B11
N.X2 [%]

N.X4

S5 S6

N.D1 N.D2

RLU236

U02

PB0003 LU3 HQ
Differential pressure control of water with speedcontrolled pumps. Options: Minimum and maximum pressure limit controller Outside temperature-dependent functions Remote setpoint adjuster Comfort / Economy changeover

B22
N.X1 [bar]

B23
N.X2

p
S01

N.Q1

N.Q2

N.Q3

N.Q4

N.Q5

N.Q6 T

R5

N.X4

T N.X3

B9

S5 S6

N.D1 N.D2

RLU236

U03

AZL003 LU3 HQ
Differential pressure control of air with speedcontrolled fans. Options: Minimum and maximum pressure limit controller Outside temperature-dependent functions Remote setpoint adjuster Comfort / Economy changeover

B24
N.X1 [Pa]

B25
N.X2

p
S01

N.Q1

N.Q2

N.Q3

N.Q4

N.Q5

N.Q6 T

R5

N.X4

T N.X3

B9

S5 S6

N.D1 N.D2

RLU236

U04

ADI004 LU3 HQ
Extract air (room) humidity control (r.h.) with DX cooler battery. Options: External setpoint for maximum selection Room temperature-dependent shifting of humidity setpoint Remote setpoint adjuster 6-stage DX cooler battery Comfort / Economy changeover
T

B5

N.X3

B12
N.X1 [%]

T N.Q2 N.Q3 N.Q4 N.Q5 N.Q6 N.Y1

R5

N.X4

M7

N.Q1

N .X 2

S5 S6

N.D1 N.D2

22/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

S01

S01

S01

RLU236

A10

AEFL01 LU3 HQ

N.Q1

S01

Controller type RLU236

Basic type U05

Application no. / description ADI006 LU3 HQa


Extract air (room) humidity control (a.h.) with DX cooler battery. Options: External setpoint for maximum selection Room temperature-dependent shifting of humidity setpoint Remote setpoint adjuster 6-stage DX cooler battery Comfort / Economy changeover

Plant diagram / connection diagram


S01

x N.X1 [g/kg]

B5

N.X3

B12

T N.Q2 N.Q3 N.Q4 N.Q5 N.Q6 N.Y1

R5

N.X4

M7

N.Q1 N .X 2

S5 S6

N.D1 N.D2

RLU236

U06

AAZD03 LU3 HQ
Indoor air quality control with mixed air dampers and fan control. Options: External setpoint for maximum selection Outside temperature-dependent functions Remote setpoint adjuster 6-speed fan Economy
AQ

Y2 Y1
T N.X3

M M

N.X1 [ppm]

B4

N.Y1 M

Y6
T

B9

N.Q2 M1 N.Q3 N.Q1 N.Q4 N.Q5 N.Q6

R5

N.X4

N .X 2

S5 S6

N.D1 N.D2
S01

RLU236

U07

ADZA02 LU3 HQ
Extract air (room) humidity control (r.h.) with spray humidifier and DX cooler battery. Options: Maximum limitation of supply air humidity External setpoint for maximum selection Remote setpoint readjuster 2-stage spray humidifier 4-stage DX cooler battery Comfort / Economy changeover

B12
N.X1 [%]

R5

N.Q1 N.Q2 N.Y1

Y8

M N.Q4 N.Q5 N.Q6 N.Y2

B11
N.X2 [%] N .X 3

N.X4

S5 S6

M7

N.D1 N.D2

N.Q3

RLU236

U08

ZZZ006 LU3 HQ
Linear 3-step switch
G G0

DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

3Q LIN.

RLU236

U09

ZZZ007 LU3 HQ
Linear 4-step switch
G G0

DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

4Q LIN.

RLU236

U10

ZZZ008 LU3 HQ
Linear 5-step switch
G G0

DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

5Q LIN.

23/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

A01

A01

A01

S01

Controller type RLU236

Basic type U11

Application no. / description ZZZ009 LU3 HQ


Linear 6-step switch
G G0

Plant diagram / connection diagram


DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

6Q LIN.

RLU236

U12

ZZZ010 LU3 HQ
Variable 3-step switch
G G0

DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

3Q VAR.

RLU236

U13

ZZZ011 LU3 HQ
Variable 4-step switch
G G0

DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

4Q VAR.

RLU236

U14

ZZZ012 LU3 HQ
Variable 5-step switch
G G0

DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

5Q VAR.

RLU236

U15

ZZZ013 LU3 HQ
Variable 6-step switch
G G0

DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

6Q VAR.

24/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

A01

A01

A01

A01

A01

Controller type RLU236

Basic type U16

Application no. / description ZZZ014 LU3 HQ


Binary step switch with 7 steps (3 relays)
G G0

Plant diagram / connection diagram


DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

3Q BIN.
Q1 Q1 Q1 Q2

Q1 Q2

Q3

RLU236

U17

ZZZ015 LU3 HQ
Binary step switch with 15 steps (4 relays)
G G0

DC 0 ... 10 V

X1 M G1

Q11 Q12 Q14

Q23 Q24

Q33 Q34 Q42

Q41 Q44

Q53 Q54

Q63 Q64

RLU236

Q1

4Q BIN.
Q1 Q1 Q1 Q1 Q1 Q1 Q2 Q2 Q4 Q2

Q1

Q2

Q3

Q3

25/26 Siemens Building Technologies HVAC Products Universal controllers RLU2... CE1N3101en 07.01.2004

A01

A01

Dimensions RLU210, RLU222


86 5 3 10,5 5 3 123 3 2 50 44,5 = 66,4 97 35 44 EN 60 715-TH 35-7.5

RLU232, RLU236
86 5 3 10,5 5 176 3 2

3101M02

50 44,5

= 66,4 153
3101M01

35

44 EN 60 715-TH 35-7.5
Dimensions in mm

26/26 Siemens Building Technologies HVAC Products

2003 Siemens Building Technologies AG Universal controllers RLU2... CE1N3101en 07.01.2004