Control Valve Sched

Valve Number Unit or System Served Water Service Steam Service Gallons Close Off Pounds Inlet Super per ft.w.c. per Hour pressure heat F Minute (Note 1) psig

Control Valve Per Outlet Target P, Target Valve Pressure ft.w.c. Cv Note 7 Size, psig (Notes inches 2,3)

#DIV/0! #DIV/0! #DIV/0! #DIV/0!


Notes 1. Minimum close off differential pressure capacity. The control valve must be able to close completely agains this differentail pressure at a minimum. 3. Generally, this will be with the valve fully open, but butterfly valves may be selected for partial disc rotation. See comments and specifications. 4. Basis of scheduled selection for the scheduled valve. Equivalent makes and models as allowed by the specification will also be acceptable. 5. This is the position the valve will go to upon loss of control power. 6. This is the range of input signal that will cause the valve to go from its fully closed position to its fully open position.
For Water Service : Q Cv ! (P Where : Cv ! Flow Coefficien t Q ! Flow in Gallons per Minute (P ! Pressure Drop in psi For Non - critical Steam Flow (Absolute pressure leaving is greater th an 58% of the absolute pressure entering) : ws  K 2.1 v (P P 1 P 2 Where : Cv ! Flow Coefficien t ws ! Steam Flow in pounds per hour Cv ! K !1 .0007  Superheat in rF P 1 ! Absolute Entering Steam Pressure in psia P 2 ! Absolute Leaving Steam Pressure in psia For Critical Steam Flow (Absolute pressure leaving is less than 58% of the absolute pressure entering) : ws Cv ! 1.61  P 1

2. Pressure drop at design flow with the valve fully actuated for the make and model scheduled. +10% variation from this value will be accepted for equivalent makes and modles as allowe

7. The spreadsheet calculates Cv based on the equations that follow. For water valves, if you enter the flow rate and the target pressure drop, the Cv will be calculated. For steam valves, yo

Actuator Data Valve Body Manufacturer/ Action Failure Type Power Range Manufacturer/ Type Model (Note Position (Note 6) Model (Note 4) (Note 5) 4)

Comments

Control Valve Sch


Valve Number Unit or System Served Water Service Steam Service Gallons Close Off Pounds Inlet Super per ft.w.c. per Hour pressure heat F Minute (Note 1) psig

Control V Outlet Target P, Target Valve Pressure ft.w.c. Cv Note 7 Size, psig (Notes inches 2,3)

V-1 V-2 V-3 V-4


Notes

AHU-1 Preheat Coil AHU-1 Humidifier Control AHU-1 Humidifier Shut-down AHU-1 Chilled Water

81

60 409 409 N/A 12 12 N/A 0 0 N/A 0 12 N/A

45

58

39 2" 10 Note 8 Minimize Line size 2" 10 22

10

1. Minimum close off differential pressure capacity. The control valve must be able to close completely agains this differentail pressure at a minimum. 3. Generally, this will be with the valve fully open, but butterfly valves may be selected for partial disc rotation. See comments and specifications. 4. Basis of scheduled selection for the scheduled valve. Equivalent makes and models as allowed by the specification will also be acceptable. 5. This is the position the valve will go to upon loss of control power. 6. This is the range of input signal that will cause the valve to go from its fully closed position to its fully open position. 7. The following equations apply:
For Water Service : Q Cv ! (P Where : Cv ! Flow Coefficien t Q ! Flow in Gallons per Minute (P ! Pressure Drop in psi For Non - critical Steam Flow (Absolute pressure leaving is greater th an 58% of the absolute pressure entering) : ws  K 2.1 v (P P 1 P 2 Where : Cv ! Flow Coefficien t ws ! Steam Flow in pounds per hour Cv ! K !1 .0007  Superheat in rF P 1 ! Absolute Entering Steam Pressure in psia P 2 ! Absolute Leaving Steam Pressure in psia For Critical Steam Flow (Absolute pressure leaving is less than 58% of the absolute pressure entering) : ws Cv ! 1.61  P 1

2. Pressure drop at design flow with the valve fully actuated for the make and model scheduled. +10% variation from this value will be accepted for equivalent makes and modles as allowe

8. As furnished by the humidifiere supplier as a part of their package.

Actuator Data Valve Type Manufacturer/Mod Action Failure Type Power Range Manufacturer/ el (Note 4) Position (Note 6) Model (Note (Note 5) 4)

Comments

Globe Globe Globe Globe

Siemens 284-03179 Note 8 Siemens 278-03143 Siemens 283-03133

N.O. N.C. N.C. N.C.

Open Closed Closed Closed

Pneu. Pneu. Pneu. Pneu.

TC Air TC Air TC Air TC Air

3-8 psi 8-13 psi 3-8 psi 15-20 psi

See valve info. See valve info. See valve info. See valve info.

Positioner, high temp. High temp, stainless trim Positioner

Control Valve Schedule - Engineering Data


Valve Number Unit or System Served Water Service Steam Service Super heat F Gallons Close Off Pounds Inlet per ft.w.c. per Hour pressure Minute (Note 2) psig

Control Valve Schedule - Valve Data


Control Valve Data Outlet Target P, Target Cv Pressure ft.w.c. Note 8 psig (Notes 3, 4) Valve Size, inches Valve Type Manufacturer/ Model Action

Control Valve Schedule - Actuator Data


Actuator Data Failure Position (Note 7) Type Power Range Manufacturer/ (Note 6) Model Comments

V-1 V-2 V-3 V-4


Notes

AHU-1 Preheat Coil AHU-1 Humidifier Control AHU-1 Humidifier Shut-down AHU-1 Chilled Water

81

60 409 409 N/A 12 12 N/A 0 0 N/A 0 12 N/A

10 Minimize 10

45

60

39 10 Line size 22

Note 6 Note 6 Note 6 Note 6

Note 6 Note 6 Note 6 Note 6

Note 6 Note 6 Note 6 Note 6

Notes 5, 6 Notes 5, 6 Notes 5, 6 Notes 5, 6

Open Closed Closed Closed

Note 6 Note 6 Note 6 Note 6

Note 6 Note 6 Note 6 Note 6

Notes 5,6 Notes 5,6 Notes 5,6 Notes 5,6

Note 6 Note 6 Note 6 Note 6

Note 9

1. Final valve sizing and selection to be by the control contractor based on the indicated parameters. As a part of the control submital, include a copy of this valve schedule with specifics for all applicable parameters based on the final selections. 2. Minimum close off differential pressure capacity. The control valve must be able to close completely agains this differentail pressure at a minimum. 3. Pressure drop at design flow with the valve fully actuated for the make and model scheduled.+10% variation from this value will be accepted for equivalent makes and modles as allowed by the specification. 4. Generally, this will be with the valve fully open, but butterfly valves may be selected for partial disc rotation. See comments and specifications. 5. As required by the final control sequence developed by the contractor based on the parameters specified in the contract documents. 6. Contractor determined by sizing the valve based on the indicated parameters. 7. This is the position the valve will go to upon loss of control power. 8. This is a preliminary specification based on the indicated flows and pressure drops based on the following equations. Final selection to be based on sizing performed by the contractor. Include the sizing equations used in the selection process if they differ from those listed below.

For Water Service : Cv ! Q (P Where :

Cv ! Flow Coefficien t Q ! Flow in Gallons per Minute (P ! Pressure Drop in psi For Non - critical Steam Flow (Absolute pressure leaving is greater th an 58% of the absolute pressure entering) : Cv ! ws  K 2.1 v (P P 1 P 2 Where : Cv ! Flow Coefficien t ws ! Steam Flow in pounds per hour K ! 1  .0007  Superheat in r F P1 ! Absolute Entering Steam Pressure in psia P 2 ! Absolute Leaving Steam Pressure in psia For Critical Steam Flow (Absolute pressure leaving is less than 58% of the absolute pressure entering) : ws 1.61  P 1 9. Coordinate with the humidifier supplier as required for proper sizing and control signal compatiblity for humidifiers that include this valve as a part of the humidifier assembly. Cv !

Control Valve Schedule - Engineering Data


Valve Number Unit or System Served Water Service Steam Service Gallons Close Off Pounds Inlet Super per ft.w.c. per Hour pressure heat F Minute (Note 1) psig

Control Valve Sch

Control V Outlet Target P, Target Valve Pressure ft.w.c. Cv Note 7 Size, psig (Notes inches 2,3)

V-1 V-2 V-3 V-4


Notes

AHU-1 Preheat Coil AHU-1 Humidifier Control AHU-1 Humidifier Shut-down AHU-1 Chilled Water

81

60 409 409 N/A 12 12 N/A 0 0 N/A 0 12 N/A

45

58

39 2" 10 Note 8 Minimize Line size 2" 10 22

10

1. Minimum close off differential pressure capacity. The control valve must be able to close completely agains this differentail pressure at a minimum. 3. Generally, this will be with the valve fully open, but butterfly valves may be selected for partial disc rotation. See comments and specifications. 4. Basis of scheduled selection for the scheduled valve. Equivalent makes and models as allowed by the specification will also be acceptable. 5. This is the position the valve will go to upon loss of control power. 6. This is the range of input signal that will cause the valve to go from its fully closed position to its fully open position. 7. The following equations apply:
For Water Service : Q Cv ! (P Where : Cv ! Flow Coefficien t Q ! Flow in Gallons per Minute (P ! Pressure Drop in psi For Non - critical Steam Flow (Absolute pressure leaving is greater th an 58% of the absolute pressure entering) : ws  K 2.1 v (P P 1 P 2 Where : Cv ! Flow Coefficien t ws ! Steam Flow in pounds per hour Cv ! K !1 .0007  Superheat in rF P 1 ! Absolute Entering Steam Pressure in psia P 2 ! Absolute Leaving Steam Pressure in psia For Critical Steam Flow (Absolute pressure leaving is less than 58% of the absolute pressure entering) : ws Cv ! 1.61  P 1

2. Pressure drop at design flow with the valve fully actuated for the make and model scheduled. +10% variation from this value will be accepted for equivalent makes and modles as allowe

8. As furnished by the humidifiere supplier as a part of their package.

Control Valve Schedule - Actuator Data


Actuator Data Valve Type Manufacturer/Mod Action Failure Type Power Range Manufacturer/ el (Note 4) Position (Note 6) Model (Note (Note 5) 4) Comments

Globe Globe Globe Globe

Siemens 284-03179 Note 8 Siemens 278-03143 Siemens 283-03133

N.O. N.C. N.C. N.C.

Open Closed Closed Closed

Pneu. Pneu. Pneu. Pneu.

TC Air TC Air TC Air TC Air

3-8 psi 8-13 psi 3-8 psi 15-20 psi

See valve info. See valve info. See valve info. See valve info.

Positioner, high temp. High temp, stainless trim Positioner