DATA SHEET FOR DISTRIBUTION TRANSFORMER PART - I ( TO BE FURNISHED BY PURCHASER ) 1.0 SITE CONDITIONS 1.

1 Maximum ambient temp 1.2 Minimum ambient temp 1.3 Design Ambient temp. 1.4 Relative humidity 1.5 Altitude 1.6 Environment 2.0 OPERATING CONDITIONS 2.1 Primary voltage/fault level 2.2 Earthing system Primary Secondary 3.0 GENERAL DATA 3.1 Duty 3.2 Type of cooling 3.3 Installation 3.4 Oil type 3.5 Temperature rise oil/winding at extreme tap having maximum losses 3.6 Painting Colour : Continuous : ONAN : Outdoor : Mineral (as per IS:335) : 50C/55C : Solidly earthed : Solidly earthed : 11KV/ @ : 45.6C : 1.1C : 40C : 86% : <1000mm from MSL : Dusty and corrosive

: Epoxy : Shade 632 as per IS-5

4.0 ELECTRICAL DATA 4.1 No. of windings 4.2 Phase 4.3 Frequency : Two :3 : 50 Hz+3%

* To be decided by Contractor in line with specification / bid document @ As per specification / bid document / SLD. 4.4 Insulation class 4.5 Winding insulation 4.6 Neutral earthing 4.7 H.V. phase sequence 4.8 LV phase sequence 5.0 SPECIFIC REQUIREMENTS 5.1 Transformer Tag no. 5.2 Rated KVA 5.3 Voltage ratio 5.4 Vector group 5.5 % Impedance 5.6 Off circuit tap changer 5.7 Neutral C.T. E/F (Secondary) REF 5.8 Terminal details Terminal location HV LV to HV terminals) : On small side of transformer : On Top/Side (At right angle :@ :* : 11/0.433KV : Dyn 11 :@ : +5%, each step of 2.5% :@ :@ :A : Uniform : Solidly earthed : UVW : To suit switchgear/As per IS:8623

5.9 Primary Cable size/Type Secondary Cable size/Type 6.0 Accessories (in addition to IS:2026) 6.1 Sampling valve 6.2 Explosion vent with double diaphragm & equaliser pipe 6.3 Conservator drain valve 6.4 Rollers (Distance between rollers 1000 mm) 6.5 Dial type thermometer with contacts 6.6 Drain cum bottom filter valve 6.7 Marshalling box(IP-55) 6.8 Double float Buchholz relay 6.9 Cross channels with towing lugs 6.10 Separate neutral bushing outside terminal box with connector assembly 6.11 Top oil filter valve 6.12 Inspection cover 6.13 Disconnecting chamber 6.14 Winding temperature indicator (for transformers rated 500 KVA and above)

: Cable box : */@ : Busduct : */@ : INCLUDED

: YES : YES

: YES : YES

: YES

: YES : YES : YES : YES : YES

: YES : YES : YES : YES

6.15 Busduct flange on LV side 6.16 Lugs and cable glands

: NO : YES

7.0 LOSS CAPITALISATION : NOT APPLICABLE; However, minimum guaranteed efficiency inclusive of all tolerances, at 50% & 100% of transformer rating at 0.8 pf shall be:98.75% and 98.19% respectively. 9.0 TESTS REQUIRED 9.1 Heat Run Test : YES (on one transformer of each rating) 9.2 Vacuum and pressure test : YES (on one transformer of each rating)on tank All other tests as specified in the specification.

NOTE : 1. For make of Equipments/components refer elsewhere in bid document. PART-II ( TO BE FILLED BY VENDOR ALONG WITH BID QUOTATION) 1.0 Rating of transformer : 2.0 PERFORMANCE Losses shall be inclusive of positive tolerance and shall be at nominal tap 2.1 No load loss At 100%V At 110%V 2.2 F.L. Copper losses at 75C 2.3 No load current At 100%V At 110%V 2.4 Efficiency at full load at 75C At 0.8 p.f At 1.0 p.f : : : : : : :

2.5 Efficiency at 1/2 load at 75C At 0.8 p.f At 1.0 p.f 2.6 Load at which max. efficiency occurs 2.7 Maximum efficiency 2.8 Percentage regulation at 75 C At 1.0 PF At 0.8 PF 3.0 CONSTRUCTIONAL FEATURES 3.1 Location of terminals 3.1.1 Primary 3.1.2 Secondary 3.2 Location of Neutral CT 3.3 Explosion Protection 4.0 MECHANICAL DATA 4.1 Core & Winding wt. 4.2 Tank & Fittings wt. 4.3 Radiator without oil wt. 4.4 Total wt 4.5 Total quantity of Oil 4.6 Quantity of oil in Radiators 4.7 Overall dimensions LxBxH : : : : : ltrs. : ltrs. : : : : : : Explosion vent/ PRV : : : : :