Sunteți pe pagina 1din 46

For continual product development, LG reserves the right to change specifications without notice. LG Electronics Inc.

Printed in Korea December. 2008 Designed by crimad.

LG MULTI V Air Conditioning System

Enjoy a clean & comfortable life with MULTI V.

Outdoor Unit

10

16 20 28 34

MULTI V MINI MULTI V PLUS II MULTI V SYNC II MULTI V SPACE II

2009
Air Conditioning System

Indoor Unit

38

49 50 52 56 60 61 62

Wall Mounted ARTCOOL Ceiling Cassette Ceiling Concealed Duct Ceiling & Floor Ceiling Suspended Floor Standing

2009
Air Conditioning System

64

Heat Recovery Ventilator


66 67 68 70
Features Installation & Maintenance Line-up Specifications

& Accessory

Network Solution & Accessory


Remote Controller Central Controller Accessory Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. Phone : +82-2-3777 -7998 Fax : +82-2-3777- 5136

Distributed by

http://www.lgeaircon.com

EU-MV091

http://www.lgeaircon.com

72

74 76 84

2009

LG runs 30 global air conditioning academies, providing training for air conditioning professionals around the world.

Lifes Good!

From installation to maintenance and repair,

B r i e f
Establishment
1947 1958 1962

H i sto r y

Establishment of the LG Group Establishment of LG Electronics Inc. Establishment of Digital Appliance Company

Growth
1968 1985 1986 Manufactured Koreas first air conditioners Introduced Koreas first Inverter air conditioners Exported Koreas first window type air conditioner

Expansion
1995 1997 1999 1999 2001 2002 2002 2004 2008 2008 Establishment of LGE TA in China Establishment of LG E I L in India Establishment of LG E AT in Turkey Establishment of LG E V N in Vietnam Establishment of LG E A Z in Brazil Establishment of LG E T H in Thailand Establishment of LG E I N in Indonesia Turnover of US$1 . 4 Billion dollars Establishment of LGELF in Levant Countries Establishment of LGETK in Turkey

Global Air Conditioning Academies

Changwon in Korea

Pyeongtaek in Korea

Thailand

England

France

Australia

Moscow

Singapore

Spain

Italy

Dubai

China

Saudi Arabia

Mexico

Panama

Indonesia

Iran

Turkey

Vietnam

Multi V Series
Environment

Your life comes more quiet, economical and powerful with LG air conditioning high technology.

Outdoor Unit

10

16 20 28 34

MULTI V MINI MULTI V PLUS II MULTI V SYNC II MULTI V SPACE II

Economic Engineering Support Easy Design & Installation


Indoor Unit

38

49 50 52 56 60 61 62

Wall Mounted ARTCOOL Ceiling Cassette Ceiling Concealed Duct Ceiling & Floor Ceiling Suspended Floor Standing

eco V
(Heat Recovery Ventilator)

64

66 67 68 70

Features Installation & Maintenance Line-up Specifications

V-net & Accessory

72

74 76 84

Remote Controller Central Controller Accessory

Outdoor unit line up


MODEL HP 4 5 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64

*1, 220V *3, 380V

MULTI V_Outdoor unit Line up


LG Air Conditioners System

06_07

Indoor unit line up


kW Btu / h SRAC 1.5 5k 2.2 7k 2.8 9k 3.6 12k 4.5 15k 5.6 18k 7.1 24k 8.2 28k 10.6 36k 12.3 42k 14.1 48k 22.4 76k 28.0 96k

Wall Mounted

Series

Mirror 4way Cassette


(570*570)

MULTI V_Indoor unit Line up

4way Cassette
Ceiling Cassette
(840*840)

2way Cassette 1way Cassette

LG Air Conditioners System

Low Static
Ceiling Concealed Duct

Built-in High Static

08_09

Ceiling & Floor Ceiling Suspended

Floor Standing

With Case Without Case

Outdoor unit
MULTI V Inverter units composed of serially arranged refrigerant pipes connected to a single outdoor unit are an efficient system that offers outstanding energy saving, simple and easy installation, and connection to different types of indoor units, making it easy to design and install.

Outdoor Unit_MULTI V series


LG Air Conditioners System

10_11

M U LT I V outdoor
16 20 28 34
MULTI V MINI MULTI V PLUS II MULTI V SYNC II MULTI V SPACE II

Outdoor unit
Pursuing the market needs of high energy efficiency and environmental friendliness.

2009 New Features


MULTI V MINI / MULTI V PLUS II MULTI V SYNC II / MULTI V SPACE II

World Highest COP!


DC Inverter compressor Inverter combination High efficient DC Inverter fan Wide louver heat exchanger

Inverter

Inverter

Inverter

Inverter Combination
Increased performance & high COP Faster response for partial load Optimized combination with space saving Competitive price for customers Reduced total base model units

Outdoor Unit_MULTI V series

A Company
* Based on 10HP model

- Simple line-up (16 models > 5 models) - Easy stock & logistics management

Extended Piping Length


MULTI V PLUS II / SYNC II
Level difference 100m 1st branch to farthest Indoor 40m[90m**]
* Using Y branch

DC Inverter Compressor
* 25~105Hz

Constant Speed Compressor

Total piping length Longest piping length Longest piping length after 1st branch Level difference between ODU~IDU Level difference between IDU~IDU Level difference between ODU~ODU

1000m 150m(200m**) 40m[90m**] 100m 15m 5m 02 01

15m

Other Features
01 DC Inverter fan motor - Max RPM increased from 850 to 920 rpm - Power consumption decreased by 30~40% 02 Wide louver heat exchanger - Improved heat exchange rate by 14% - Anti-corrosion treatment (Gold fin) 03 Black box function - Save the last 3 minutes operating data - Precise analysis & fast trouble-shooting 04 Upgraded Main PCB - 3-Digit 7 segment

Longest piping length 150m(200m**)

LG Air Conditioners System

Refer to the specifications for more information Total piping length 1000m
MULTI V PLUS II, MULTI V SYNC II
** Conditional Application To make 40~90m of pipe length after first branch, refer to the part of installation of outdoor units in PDB

DC Inverter Compressor
01 02
01 Optimized scroll shape 02 Oil injection mechanism - High reliability in low rpm operation - High efficiency in partial load operation

03

04

12_13

03 04 05 06

Wide Louver heat exchanger

3 INV controller

- Double DIP switch


Main PCB

03 Oil discharge reduction - High reliability in high rpm operation - Enhanced oil circulation 04 DC Inverter motor - High efficiency - Low noise

Corrugate fin

05 Teflon coated bearing 06 High performance oil pump

Wide louver fin

Outdoor unit
Pursuing the market needs of high energy efficiency and environmental friendliness.

2009 New Features


MULTI V MINI / MULTI V PLUS II MULTI V SYNC II / MULTI V SPACE II

Enhanced comfort for end-user!

Night Silent Operation


Night silent operation will be on for X hours starting from the peak temperature during daytime, and then after Y hours, itll be back to normal operation.
- Mode 1 > X : 8.0 hours, Y : 9.0 hours - Mode 2 > X : 6.5 hours, Y : 10.5 hours - Mode 3 > X : 5.0 hours, Y : 12.0 hours Command Sensor reading

LG MV
Easy start-up, easy trouble shooting Monitoring the normality of all parts such as compressor, fan, valve, etc

Outdoor Unit_MULTI V series

Each mode can be selected as 3 steps of sound level.


* Based on MULTI V PLUS II, 10HP model

Operation state

Central Controller Cycle view

Unit : dBA

MINI Step 1 Step 2 Step 3


46 43 40

PLUS II
47 44 41

SYNC II
47 44 41

* Fault detect & diagnosis Manifold

Automatic Refrigerant Charging


Refrigerant charging without any scales or quantity calculation This function is recommended during service. Guaranteed temperature range : IDU(20~32C), ODU(0~43C) FDD function (Fault detect & diagnosis)

Model selection

Auto check

LATS MULTI V
Convenient model selection program Highly user-friendly design (Autocad version) Automatic piping design & check
Download from sales supporting system > http://www.lgeaircon.com

LG Air Conditioners System

Refrigerant charging kit

CAD application

Making quotation

14_15

Refrigerant

* Fault detect & diagnosis


Leakage! Leakage! Leakage!

Automatic Refrigerant Check-Up


It can be checked refrigerant status during start-up whether it is undercharged or overcharged It can be decided appropriate amount of refrigerant automatically through cycle operation. FDD function (Fault detect & diagnosis)

Leakage!

MULTI V MINI can be easily installed in small offices and shops. Designed for low-noise operation, it ensures a pleasant air conditioned environment.

EFFICIENCY
MULTI V MINI uses the cutting-edge, artificial intelligence control to obtain efficient operation and reduced noise.

Noise level (dBA)

Enhanced Comfort
Night silent operation High COP
1, 220V Cooling 4HP 5HP 6HP 3.9 3.7 3.6 Heating 4.0 4.0 3.8 3, 380V Cooling 3.7 3.6 3.5 Heating 3.9 3.9 3.8

Outdoor Unit_MULTI V MINI

50
4HP

51
5HP

52
6HP

46

43

40

Longest Piping Length


Total piping length Longest piping length (Equivalent) Longest piping length after 1st branch Level difference between ODU~IDU Level difference between IDU~IDU Level difference between ODU~ODU
*Outdoor unit is lower than indoor unit.

STEP 1 STEP 2 STEP 3


(Based on 4HP)

300m 150m(175m) 40m 50m(40m*) 15m 5m

Day time

Night time

Conventional
5, 6 HP 4, 5, 6 HP

Slim & Compact Size


Easy & efficient installation of MULTI V MINI will provide the best solution for small offices and shops.

LG Air Conditioners System

Foot print area

46%
Reduction
950mm 806mm

Volume

730mm

330 mm

16_17

52%
Reduction

WxHxD : 8061607730 Enjoy a clean & comfortable life with MULTI V MINI.

WxHxD : 950x1380x330

09 New Feature
MULTI V MINI can be easily installed in small offices and shops. Designed for low-noise operation, it ensures a pleasant air conditioned environment.
DC Inverter Compressor & Fan motor Black Box Function Night Silent Operation Fault Detect & Diagnosis Pump Down

Max. 9 Indoor Units Connectable


Maximum 9 indoor units can be connected to one single outdoor unit with 130% indoor unit combination.
- 9 indoor units for 6HP - 8 indoor units for 5HP - 6 indoor units for 4HP
6 7 8

Outdoor Unit_MULTI V MINI

units

*Based on 6 HP model

Easy to Service
01
01 Inner SVC valve - 4 Way piping is possible (Front, Rear, Right, Down) - Excellent exterior

* Specifications
HP Model Capacity Power Input COP Independent Unit Cooling Heating Cooling Heating Cooling Heating kW kW kW kW

*1, 220V 4 ARUN40GS2


11.2 12.5 2.9 3.1 3.86 4.03 950 x 1380 x 330 118 50 52 110 1

*3, 380V 5 ARUN50GS2


14.0 16.0 3.8 4.0 3.68 4.00 1, 220 ~ 240, 50 950 x 1380 x 330 118 Warm Gray 51 53 BLDC 110 DC INVERTER 1 Gold Fin R410A 3.7 EEV FV50S[PVE] 1.7 9.52(3/8) 15.88(5/8) 1 8 50~130% 150m/50m

6 ARUN60GS2
15.5 18.0 4.3 4.7 3.60 3.83 950 x 1380 x 330 118 52 54 110 1

4 ARUN40LS2
11.2 12.5 3.0 3.2 3.73 3.91 950 x 1380 x 330 112 50 52 110 1

5 ARUN50LS2
14.0 16.0 3.9 4.1 3.59 3.90 3, 380 ~ 415, 50 950 x 1380 x 330 112 Warm Gray 51 53 BLDC 110 DC INVERTER 1 Gold Fin R410A 3.7 EEV FV50S[PVE] 1.3 9.52(3/8) 15.88(5/8) 1 8 50~130% 150m/50m

6 ARUN60LS2
15.5 18.0 4.4 4.8 3.52 3.75 950 x 1380 x 330 112 52 54 110 1

LG Air Conditioners System

02

03

1 Way

4 Way

02 Convenient moving handle 03 Compact design & Easy service - Remove 3 pieces of screw for SVC - Front panel removal system

3 pieces of screw Easy service

Power Supply , V, Hz Dimensions(WxHxD) mm Weight kg Color Noise level Cooling dBA3 Heating dBA3 Fan Type Air flow rate [CMM] Compressor Type Number of compressors Heat Exchanger Refrigerant Type Charge kg Control Refrigerant Type Oil Charge l Piping Liquid Pipes mm(inch) Connections Gas Pipes mm(inch) Number of outdoor unit Number of maximum connectable indoor units Ratio of the connectable indoor units Longest piping length / Level difference Note :

18_19

3.7 FV50S[PVE] 1.7 9.52(3/8) 15.88(5/8) 1 6

3.7 FV50S[PVE] 1.7 9.52(3/8) 19.05(3/4) 1 9

3.7 FV50S[PVE] 1.3 9.52(3/8) 15.88(5/8) 1 6

3.7 FV50S[PVE] 1.3 9.52(3/8) 19.05(3/4) 1 9

1. Capacities are based on the following conditions Cooling-Indoor temp. 27C[80.6F]DB / 19C[66.2F]WB Outdoor temp. 35C[95F]DB / 24C[75.2F]WB Interconnecting piping length 7.5m Level difference of zero

Heating-Indoor temp. 20C[68F]DB / 15C[59F]WB Outdoor temp. 7C[44.6F]DB / 6C[42.8F]WB Interconnecting piping length 7.5m Level difference of zero

2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV : Electronic Expansion Valve

MULTI V Inverter system offers one of the worlds largest capacity units, essential for high-rise buildings. We are proud to say the system will ensure the highest level of customer satisfaction.

TECHNOLOGY
Your life will be upgraded through the state-of-the-art technology of MULTI V PLUS II.

Low Noise
Latest technology and features are applied to the new outdoor units to reduce noise level.
*Based on 10HP model

Outdoor Unit_MULTI V PLUS II

57dB

Rear

52dB

Side

58dB

Front

ODU Noise Comparison


dBA
70

LG Air Conditioners System

65

60

Gernerally lower noise!!


55

50

10

20

30
LG

40
Competitor

HP

20_21

Alternate-Cycling Function
To extend compressors life span by operating them alternately Inverter A <> Inverter B <> Inverter C
ON ON ON ON ON

Constant A <> Constant B <> Constant C To meet diverse load in operation

Enjoy a clean & comfortable life with MULTI V.

Inverter Constant Inverter Constant A A B B

Inverter Constant C C

MULTI V Inverter system offers one of the worlds largest capacity units, essential for high-rise buildings. We are proud to say the system will ensure the highest level of customer satisfaction.

CONVENIENCE
From installation and transportation to maintenance and service, MULTI V PLUS II adds convenience to cutting-edge technology.

Automatic Back-Up
For emergency, it makes back-up operation possible before trouble-shooting Inverter A, B + Constant B > Inverter B + Constant A, B Error notice in indoor unit : 4 times per day (every 6 hour)
Outdoor unit Indoor unit 1 Outdoor unit
E F A

Outdoor unit control box


Indoor unit
B

Central controller
C D

Dry contact
Dry1 Dry2

Central controller
GND 12V

Non-Polarity Transmission Connection


Easy installation and no errors for transmission line connections
3 4

ON

ON

ON

Failed

ON

ON

ON

3 4

3 4

3 4

Outdoor Unit_MULTI V PLUS II

Inverter Constant Inverter Constant A A B B

Inverter Constant Inverter Constant A A B B * Combination possible model only

Indoor unit 1 Indoor unit 2

Indoor unit 2

A > 3 or 4 > 3 or 4 B > 3 or 4 > 3 or 4

Pump down Refrigerant flow

Pump Down & Pump Out


Pump down
Repair!

Plate Type SC HEX


Increased sub-cooling by highperformance heat exchanger
Double tube

Repair!

Repair!

When indoor units need to replace, refrigerant can be collected to the outdoor unit.
- MULTI V MINI / PLUS II / SYNC II / SPACE II

Enable to be long piping length and level difference More powerful cooling operation

Pump out Refrigerant flow


Reftigerant flow

Pump out
If left outdoor unit breakdown, refrigerant can be sent to another outdoor and indoor unit during service. - MULTI V PLUS II / SYNC II

LG Air Conditioners System

Plate SC

Failed!

22_23

Auto addressing
Indoor unit Indoor unit Indoor unit

Cool / Heat Selector


Fan mode Cooling Mode change Heating

Addressing outdoor units and indoor units are automatically done just by pressing the button.

Control all units without any central controller installed Select operation mode (Air circulation, cooling, heating) Mode lock for heating & cooling mixing error-proof during the change of season

Wired remote Wired remote control control

Wired remote control

09 New Feature
MULTI V Inverter system offers one of the worlds largest capacity units, essential for high-rise buildings. We are proud to say the system will ensure the highest level of customer satisfaction.
DC Inverter Compressor & Fan motor Black Box Function Night Silent Operation Fault Detect & Diagnosis Pump Down & Pump Out

Separate Front Panel


Easy access to main PCB (DIP switch) Convenient during service and start-up Benefits for technician, installer

Outdoor Unit_MULTI V PLUS II

Close

Open

Safety chassis

Swing control box

Other Features
Resistant to dust, rain, corrosion and others Convenient maintenance due to swing door type control box Easy to handle through fork lift slot Strong base-pan support

* Specifications
HP Model Combination unit Independent unit

5 ARUN50LT2 ARUN50LT2
14.0 15.8 3.75 4.00 3.73 3.95 3, 380~415, 50 8061607730 175 56 105 1

6 ARUN60LT2 ARUN60LT2
16.0 18.0 4.25 4.55 3.76 3.96 3, 380~415, 50 8061607730 175 56 105 DC Inverter Scroll 1

8 10 12 14 16 ARUN80LT2 ARUN100LT2 ARUN120LT2 ARUN140LT2 ARUN160LT2 ARUN80LT2 ARUN100LT2 ARUN120LT2 ARUN140LT2 ARUN160LT2
22.4 25.2 5.28 5.73 4.24 4.40 3, 380~415, 50 12801607730 240 58 190 1 28.0 31.5 7.16 7.33 3.91 4.30 3, 380~415, 50 12801607730 285 Warm Gray 58 33.6 37.8 9.08 9.05 3.70 4.18 3, 380~415, 50 12801607730 285 58 39.2 44.1 11.85 10.60 3.31 4.16 3, 380~415, 50 12801607730 285 58 44.8 50.4 14.00 12.40 3.20 4.06 3, 380~415, 50 12801607730 285 58 190 2

LG Air Conditioners System

Easy to handle

Strong base-pan

Capacity Cooling kW Heating kW Power Cooling kW Input Heating kW COP Cooling Heating Power Supply , V, Hz Dimensions(WxHxD) mm Weight kg Color Noise level dBA3 Fan Type Air flow rate [CMM] Compressor Type Number of compressors Heat Exchanger Refrigerant Type Charge kg Control Refrigerant Type Oil Charge l Piping Liquid Pipes mm(inch) Connections Gas Pipes mm(inch) Number of outdoor unit Number of maximum connectable indoor units * Ratio of the connectable indoor units Longest piping length / Level difference **

24_25

Propeller Fan (DC INV) 190 190 190 DC Inverter Scroll / Constant speed Scroll 2 Gold fin R410A 2 2

4.5

4.5

8 EEV FVC68D(PVE) 5.6 9.52(3/8) 22.2(7/8) 1 16(25) 50~200% 200m/100m

2.3 9.52(3/8) 15.88(5/8) 1 8(12)

2.3 9.52(3/8) 19.05(3/4) 1 9(14)

3.3 9.52(3/8) 19.05(3/4) 1 13(20)

5.6 12.7(1/2) 28.58(1 1/8) 1 19(30)

5.6 12.7(1/2) 28.58(1 1/8) 1 23(35)

5.6 12.7(1/2) 28.58(1 1/8) 1 26(40)

Check up the note, refer to on the 27 page.

MULTI V PLUS II ensures economic life with high energy efficiency!!


* Specifications
HP Model Combination unit Independent unit

* Specifications
18 20 22 24 26 28 30 32 ARUN180LT2 ARUN200LT2 ARUN220LT2 ARUN240LT2 ARUN260LT2 ARUN280LT2 ARUN300LT2 ARUN320LT2 ARUN120LT2 ARUN140LT2 ARUN160LT2 ARUN160LT2 ARUN140LT2 ARUN140LT2 ARUN160LT2 ARUN160LT2 ARUN60LT2 ARUN60LT2 ARUN60LT2 ARUN80LT2 ARUN120LT2 ARUN140LT2 ARUN140LT2 ARUN160LT2
50.4 56.7 13.33 13.60 3.78 4.17 56.0 63.0 16.10 15.15 3.48 4.16 (12801607730) +(8061607730) 285+175 60 295 3 61.6 69.3 18.25 16.95 3.38 4.09 67.2 75.6 19.28 18.13 3.49 4.17 72.8 81.9 20.93 19.65 3.48 4.17 78.4 88.2 23.70 21.20 3.31 4.16 84.0 94.5 25.85 23.00 3.25 4.11 89.6 100.8 28.00 24.80 3.20 4.06

HP Model

Combination unit Independent unit

Capacity Cooling Heating Power Cooling Input Heating COP Cooling Heating Power Supply Dimensions(WxHxD)

kW kW kW kW

50 ARUN500LT2 ARUN140LT2 ARUN140LT2 ARUN140LT2 ARUN80LT2


140 157.5 40.83 37.53 3.43 4.20

52 ARUN520LT2 ARUN160LT2 ARUN140LT2 ARUN140LT2 ARUN80LT2


145.6 163.8 42.98 39.33 3.39 4.16

54 ARUN540LT2 ARUN160LT2 ARUN160LT2 ARUN140LT2 ARUN80LT2


151.2 170.1 45.13 41.13 3.35 4.14

56 ARUN560LT2 ARUN160LT2 ARUN160LT2 ARUN160LT2 ARUN80LT2


156.8 176.4 47.28 42.93 3.32 4.11

58 ARUN580LT2 ARUN160LT2 ARUN160LT2 ARUN160LT2 ARUN100LT2


162.4 182.7 49.16 44.53 3.30 4.10

60 ARUN600LT2 ARUN160LT2 ARUN160LT2 ARUN160LT2 ARUN120LT2


168 189 51.08 46.25 3.29 4.09

62 ARUN620LT2 ARUN160LT2 ARUN160LT2 ARUN160LT2 ARUN140LT2


173.6 195.3 53.85 47.80 3.22 4.09

64 ARUN640LT2 ARUN160LT2 ARUN160LT2 ARUN160LT2 ARUN160LT2


179.2 201.6 56.00 49.60 3.20 4.06

, V, Hz mm

3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 (12801607730) +(8061607730) 285+175 60 295 3 (12801607730) (12801607730)2 (12801607730)2 (12801607730)2 (12801607730)2 (12801607730)2 +(8061607730) 285+175 60 295 3 285+240 61 380 285x2 61 380 285x2 61 380 4 285x2 61 380 4 285x2 61 380 4 Warm Gray Propeller Fan(DC INV) DC Inverter Scroll / Constant speed Scroll 3 4 Gold fin R410A 4.5+8 4.5+8 4.5+8 8+8 EEV FVC68D(PVE) 5.6+2.3 15.88(5/8) 28.58(1 1/8) 2 29(36) 5.6+2.3 15.88(5/8) 28.58(1 1/8) 2 32(40) 5.6+2.3 15.88(5/8) 28.58(1 1/8) 2 35(44) 5.6+3.3 15.88(5/8) 34.9(1 3/8) 2 39(48) 50~160% 200m/100m 5.6x2 19.05(3/4) 34.9(1 3/8) 2 42(52) 5.6x2 19.05(3/4) 34.9(1 3/8) 2 45(56) 5.6x2 19.05(3/4) 34.9(1 3/8) 2 49(60) 5.6x2 19.05(3/4) 34.9(1 3/8) 2 52(64) 8+8 8+8 8+8 8+8

Weight kg Color Noise level dBA3 Fan Type Air flow rate [CMM] Compressor Type Number of compressors Heat Exchanger Refrigerant Type Charge kg Control Refrigerant Type Oil Charge l Piping Liquid Pipes mm(inch) Connections Gas Pipes mm(inch) Number of outdoor unit Number of maximum connectable indoor units * Ratio of the connectable indoor units Longest piping length / Level difference **

Capacity Cooling kW Heating kW Power Cooling kW Input Heating kW COP Cooling Heating Power Supply , V, Hz Dimensions(WxHxD) mm Weight kg Color Noise level dBA3 Fan Type Air flow rate [CMM] Compressor Type Number of compressors Heat Exchanger Refrigerant Type Charge kg Control Refrigerant Type Oil Charge l Piping Liquid Pipes mm(inch) Connections Gas Pipes mm(inch) Number of outdoor unit Number of maximum connectable indoor units Ratio of the connectable indoor units Longest piping length / Level difference **

3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 (1280x1607x730)x4 (1280x1607x730)x4 (1280x1607x730)x4 (1280x1607x730)x4 285X3+240 64 760 7 285X3+240 64 760 7 285X3+240 64 760 7 285X3+240 (1280x1607x730)x4 (1280x1607x730)x4 (1280x1607x730)x4 (1280x1607x730)x4 285x4 285x4 64 285x4 64 760 8 285x4 64 760 8

Warm Gray 64 64 Propeller Fan(DC INV)

760 760 760 DC Inverter Scroll / Constant speed Scroll 7 Gold fin R410A 8 8

Outdoor Unit_MULTI V PLUS II

8+8+8+8

8+8+8+8

8+8+8+8

8+8+8+8

8+8+8+8 EEV FVC68D(PVE) 5.6x4 19.05(3/4) 41.3(1 5/8) 4 64 50~130% 200m/100m

8+8+8+8

8+8+8+8

8+8+8+8

5.6X3+3.3 19.05(3/4) 41.3(1 5/8) 4 64

5.6X3+3.3 19.05(3/4) 41.3(1 5/8) 4 64

5.6X3+3.3 19.05(3/4) 41.3(1 5/8) 4 64

5.6X3+3.3 19.05(3/4) 41.3(1 5/8) 4 64

5.6x4 19.05(3/4) 41.3(1 5/8) 4 64

5.6x4 19.05(3/4) 41.3(1 5/8) 4 64

5.6x4 19.05(3/4) 41.3(1 5/8) 4 64

* The number of () means the number of max. connectable indoor units, when the connected capacity of indoor units is in the table below.

HP Model

Combination unit Independent unit

Capacity Cooling Heating Power Cooling Input Heating COP Cooling Heating Power Supply Dimensions(WxHxD)

kW kW kW kW

34 ARUN340LT2 ARUN140LT2 ARUN140LT2 ARUN60LT2


95.2 107.1 27.95 25.75 3.41 4.16

36 ARUN360LT2 ARUN160LT2 ARUN140LT2 ARUN60LT2


100.8 113.4 30.10 27.55 3.35 4.12

38 ARUN380LT2 ARUN160LT2 ARUN160LT2 ARUN60LT2


106.4 119.7 32.25 29.35 3.30 4.08

40 ARUN400LT2 ARUN160LT2 ARUN160LT2 ARUN80LT2


112.0 126.0 33.28 30.53 3.37 4.13

42 ARUN420LT2 ARUN140LT2 ARUN140LT2 ARUN140LT2


117.6 132.3 35.55 31.80 3.31 4.16

44 ARUN440LT2 ARUN160LT2 ARUN140LT2 ARUN140LT2


123.2 138.6 37.70 33.60 3.27 4.13

46 ARUN460LT2 ARUN160LT2 ARUN160LT2 ARUN140LT2


128.8 144.9 39.85 35.40 3.23 4.09

48 ARUN480LT2 ARUN160LT2 ARUN160LT2 ARUN160LT2


134.4 151.2 42.00 37.20 3.20 4.06

** Conditional Application To make 40~90m of pipe length after first branch refer to the part of installation of outdoor units in PDB

Note : LG Air Conditioners System


1. Capacities are based on the following conditions Cooling-Indoor temp. 27C[80.6F]DB / 19C[66.2F]WB Outdoor temp. 35C[95F]DB / 24C[75.2F]WB Interconnecting piping length 7.5m Level difference of zero Heating-Indoor temp. 20C[68F]DB / 15C[59F]WB Outdoor temp. 7C[44.6F]DB / 6C[42.8F]WB Interconnecting piping length 7.5m Level difference of zero

2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV : Electronic Expansion Valve

, V, Hz mm

3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 (12801607730)2 (12801607730)2 (12801607730)2 (12801607730)3 (12801607730)3 (12801607730)3 (12801607730)3 (12801607730)3 +(8061607730) +(8061607730) 285x2+175 62 485 5 +(8061607730) 285x2+175 62 485 5 285x2+240 63 570 2853 63 570 2853 63 570 6 2853 63 570 6 2853 63 570 6 Warm Gray 62 485 5 Propeller Fan(DC INV) DC Inverter Scroll / Constant speed Scroll 5 6 Gold fin R410A 4.5+8+8 4.5+8+8 4.5+8+8 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8 EEV FVC68D(PVE) 5.6x2+3.3 5.6x3 19.05(3/4) 41.3(1 5/8) 3 64 50~130% 200m/100m 19.05(3/4) 41.3(1 5/8) 3 64 285x2+175

26_27

CAUTION
A combination operation over 100% cause to reduce each indoor unit capacity Combination ratio(50~200%)
No. of outdoor unit Single unit Double unit Triple unit Over triple unit Connection Capacity 200% 160% 130% 130%

Weight kg Color Noise level dBA3 Fan Type Air flow rate [CMM] Compressor Type Number of compressors Heat Exchanger Refrigerant Type Charge kg Control Refrigerant Type Oil Charge l Piping Liquid Pipes mm(inch) Connections Gas Pipes mm(inch) Number of outdoor unit Number of maximum connectable indoor units Ratio of the connectable indoor units Longest piping length / Level difference **

We can guarantee the operation only within 130% Combination. If you want to connect more than 130% combination, please contact us and discuss the requirement like below. 1) If the operation of indoor unit is more than 130%, low airflow operation is recommended in all the indoor units. 2) If the operation of indoor unit is more than 130%, additional refrigerant is needed according to the headquarter guidance. 3) Over 130%, capacity is same as capacity of 130%, Same remark is valid for power input.

5.6x2+2.3 19.05(3/4) 34.9(1 3/8) 3 55

5.6x2+2.3 19.05(3/4) 41.3(1 5/8) 3 58

5.6x2+2.3 19.05(3/4) 41.3(1 5/8) 3 61

5.6x3 19.05(3/4) 41.3(1 5/8) 3 64

5.6x3 19.05(3/4) 41.3(1 5/8) 3 64

5.6x3 19.05(3/4) 41.3(1 5/8) 3 64

Simultaneous heating and cooling with one outdoor unit, MULTI V SYNC II. Your environment is ensured of optimum conditions regardless of season or space.

TECHNOLOGY
Your life will be upgraded through the state-ofthe-art technology of MULTI V SYNC II.

Heating

Cooling

Heating & Cooling Synchronous Operation


High COP up to 6.3 - When, cooling(40%) + heating(60%) Energy consumption can be decreased by 30%
Coefficient of Performance(COP)

> Cooling

40

Max. COP (6.3)

Outdoor Unit_MULTI V SYNC II

> Heating Heating <

Office

Equipment room

* Outdoor temperature : 7C DB / 6C WB * Indoor temperature : 20C DB / 15C WB


Heating operation ratio (%)

Long Piping Length


Level difference 100m 1st branch to farthest indoor 40[90m**] Longest piping length 150(200m**)

MULTI V SYNC II
Total piping length Longest piping length Longest piping length after 1st branch Level difference between ODU~IDU Level difference between IDU~IDU Level difference between ODU~ODU

1000m 150m(200m**) 40m[90m**] 100m 15m 5m

15m

LG Air Conditioners System

Cooling <
Total piping length 1000m

MULTI V SYNC II

Refer to the specifications for more information


** Conditional application To make 40~90m of pipe length after first branch, refer to the part of installation of outdoor units in PDB

AMC (Advanced Mode Change)


Optimum area AMC control provides an optimal cycle operation under any conditions.
- Real time pressure control - Optimal cycle in optimum area - Needed time to change mode : Max. 3min

28_29

Cooling

Wide Operation Range


Wide operation range
- Heating mode : - 20C WB ~ 16C WB - Cooling mode : - 5C DB ~ 43C DB - Synchronous mode : -10C DB ~ 27C DB

Synchronous Operation area


Enjoy a clean & comfortable life with MULTI V.

Heating

Simultaneous heating and cooling with one outdoor unit, MULTI V SYNC II. Your environment is ensured of optimum conditions regardless of season or space.

COMFORT
MULTI V SYNC II ensures the comfort of all users with flexible design and easy installation.

Double spiral tube heat exchanger


From outdoor Linear expansion valve

High Efficiency Heat Recovery Unit


High efficient double spiral tube

MULTI V SYNC II
Heating Cooling

Fast Response of Mode Change


When the user wants to change the indoor units operating mode (ex. cooling > heating), MULTI V SYNC II takes less time compared to the conventional. This fast response of mode change provides a more pleasant and comfortable air conditioning.

type SCI circuit


To indoor

Maximum 4 indoor units connectable

Max. 3minutes

2 phase fluid

per one HR unit


Easy installation with auto piping

Outdoor Unit_MULTI V SYNC II

detect function

Conventional
Heating Cooling

PRHR020

PRHR030

PRHR040

About 20minutes

MULTI V SYNC II

Flexible Connection of HR Unit


LGs heat recovery unit allows flexible connection both in series and in a row.
In series

MULTI V SYNC II
3 Piping HR unit 2 Piping

Conventional
3 Piping HR unit 2 Piping

Excellent Multiple HR Unit


LGs HR unit provides the flexible and convenient installation with lower cost.
LG needs less installation cost than the conventional LG Y branch 12 unit 5 unit 690m Conventional 57 unit 20 unit 840m

LG Air Conditioners System

Conventional

LG unique

LG unique
Y branch only Impossible

15m

HR unit Total piping length

* Assumed with 5 stories building

30_31

Impossible

In series only

20m

Y Branch

MULTI V SYNC II Free zoning!

Conventional
Inconvenient zoning!

Convenient Free Zoning


MULTI V SYNC II provides perfect individual zoning in each rooms for the users convenience.
Change point (Heat>Cool) Temp Change point (Cool>Heat) +T -T

Auto Changeover
Auto changeover automatically change operating mode cool and heat, to maintain optimum room temperature, so no need of changing the mode during the change of season.

Time Same mode operation in the different zones

09 New Feature
DC Inverter Compressor & Fan motor Black Box Function Night Silent Operation Fault Detect & Diagnosis Pump Down & Pump Out

MULTI V SYNC II simultaneous heating and cooling from a single outdoor unit!
* Specifications
HP Model Combination unit Independent unit

* Specifications
HP Model Combination unit Independent unit

8 10 12 14 16 18 20 ARUB80LT2 ARUB100LT2 ARUB120LT2 ARUB140LT2 ARUB160LT2 ARUB180LT2 ARUB200LT2 ARUB80LT2 ARUB100LT2 ARUB120LT2 ARUB140LT2 ARUB160LT2 ARUB100LT2 ARUB120LT2 ARUB80LT2 ARUB80LT2
22.4 25.2 5.28 5.73 4.24 4.40 3, 380~415, 50 1280x1607x730 240 58 190 DC Inverter Scroll 1 28.0 31.5 7.16 7.33 3.91 4.30 3, 380~415, 50 1280x1607x730 285 58 190 2 33.6 37.8 9.08 9.05 3.70 4.18 3, 380~415, 50 1280x1607x730 285 58 190 2 39.2 44.1 11.85 10.60 3.31 4.16 3, 380~415, 50 1280x1607x730 285 Warm Gray 58 Propeller Fan(DC INV) 190 190 DC Inverter Scroll / Constant speed Scroll 2 Gold fin R410A 8 8 8 8 EEV FVC68D(PVE) 3.3 9.52(3/8) 19.05(3/4) 15.88(5/8) 1 13(20) 5.6 9.52(3/8) 22.2(7/8) 19.05(3/4) 1 16(25) 5.6 12.7(1/2) 28.58(1 1/8) 19.05(3/4) 1 19(30) 50~200% 5.6 12.7(1/2) 28.58(1 1/8) 22.2(7/8) 1 23(35) 200m/100m 5.6 12.7(1/2) 28.58(1 1/8) 22.2(7/8) 1 26(40) 5.6+3.3 15.88(5/8) 28.58(1 1/8) 22.2(7/8) 2 29(36) 50~160% 5.6+3.3 15.88(5/8) 28.58(1 1/8) 22.2(7/8) 2 32(40) 8 8+8 8+8 2 380 3 380 3 44.8 50.4 14.00 12.40 3.20 4.06 3, 380~415, 50 285 58 50.4 56.7 12.44 13.06 4.05 4.34 3, 380~415, 50 240+285 61 56.0 63.0 14.36 14.78 3.90 4.26 3, 380~415, 50 240+285 61

Capacity Cooling kW Heating kW Power Cooling kW Input Heating kW COP Cooling Heating Power Supply , V, Hz Dimensions(WxHxD) mm Weight kg Color Noise level dBA3 Fan Type Air flow rate [CMM] Compressor Type Number of compressors Heat Exchanger Refrigerant Type Charge kg Control Refrigerant Type Oil Charge l Piping Liquid(flare) mm(inch) Connections Suction Gas mm(inch) Discharge Gas mm(inch) Number of outdoor unit Number of maximum connectable indoor units * Ratio of the connectable indoor units Longest piping length / Level difference **

1280x1607x730 (1280x1607x730)x2 (1280x1607x730)x2

Capacity Cooling kW Heating kW Power Cooling kW Input Heating kW COP Cooling Heating Power Supply , V, Hz Dimensions(WxHxD) mm Weight kg Color Noise level dBA3 Fan Type Air flow rate [CMM] Compressor Type Number of compressors Heat Exchanger Refrigerant Type Charge kg Control Refrigerant Type Oil Charge l Piping Liquid(flare) mm(inch) Connections Suction Gas mm(inch) Discharge Gas mm(inch) Number of outdoor unit Number of maximum connectable indoor units * Ratio of the connectable indoor units Longest piping length / Level difference **

22 24 26 28 30 32 34 ARUB220LT2 ARUB240LT2 ARUB260LT2 ARUB280LT2 ARUB300LT2 ARUB320LT2 ARUB340LT2 ARUB140LT2 ARUB160LT2 ARUB140LT2 ARUB140LT2 ARUB160LT2 ARUB160LT2 ARUB140LT2 ARUB80LT2 ARUB80LT2 ARUB120LT2 ARUB140LT2 ARUB140LT2 ARUB160LT2 ARUB120LT2 ARUB80LT2
61.6 69.3 17.13 16.33 3.60 4.24 3, 380~415, 50 240+285 61 380 3 67.2 75.6 19.28 18.13 3.49 4.17 3, 380~415, 50 240+285 61 380 3 72.8 81.9 20.93 19.65 3.48 4.17 3, 380~415, 50 285+285 61 78.4 88.2 23.70 21.20 3.31 4.16 3, 380~415, 50 285+285 Warm Gray 61 Propeller Fan(DC INV) 84.0 94.5 25.85 23.00 3.25 4.11 3, 380~415, 50 285+285 61 89.6 100.8 28.00 24.80 3.20 4.06 3, 380~415, 50 285+285 61 380 4 95.2 107.1 26.21 25.38 3.63 4.22 3, 380~415, 50 240+285+285 63 570 5

(1280x1607x730)x2 (1280x1607x730)x2 (1280x1607x730)x2 (1280x1607x730)x2 (1280x1607x730)x2 (1280x1607x730)x2 (1280x1607x730)x3

380 380 380 DC Inverter Scroll / Constant speed Scroll 4 4 Gold fin R410A 4

Outdoor Unit_MULTI V SYNC II

8+8

8+8

8+8

8+8 EEV FVC68D(PVE)

8+8

8+8

8+8+8

5.6+3.3 15.88(5/8) 34.9(1 3/8) 28.58(1 1/8) 2 35(44)

5.6+3.3 15.88(5/8) 34.9(1 3/8) 28.58(1 1/8) 2 39(48)

5.6+5.6 19.05(3/4) 34.9(1 3/8) 28.58(1 1/8) 2 42(52) 50~160%

5.6+5.6 19.05(3/4) 34.9(1 3/8) 28.58(1 1/8) 2 45(56) 200m/100m

5.6+5.6 19.05(3/4) 34.9(1 3/8) 28.58(1 1/8) 2 49(60)

5.6+5.6 19.05(3/4) 34.9(1 3/8) 28.58(1 1/8) 2 52(64)

5.6+5.6+3.3 19.05(3/4) 34.9(1 3/8) 28.58(1 1/8) 3 55 50~130%

HP Model

Combination unit Independent unit

* The number of () means the number of max. connectable indoor units, when the connected capacity of indoor units is in the table below. ** Conditional Application To make 40~90m of pipe length after first branch refer to the part of installation of outdoor units in PDB

Note :
1. Capacities are based on the following conditions Cooling-Indoor temp. 27C[80.6F]DB / 19C[66.2F]WB Outdoor temp. 35C[95F]DB / 24C[75.2F]WB Interconnecting piping length 7.5m Level difference of zero Heating-Indoor temp. 20C[68F]DB / 15C[59F]WB Outdoor temp. 7C[44.6F]DB / 6C[42.8F]WB Interconnecting piping length 7.5m Level difference of zero

2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV : Electronic Expansion Valve

CAUTION
A combination operation over 100% cause to reduce each indoor unit capacity Combination ratio(50~200%)
No. of outdoor unit Single unit Double unit Triple unit Connection Capacity 200% 160% 130%

We can guarantee the operation only within 130% Combination. If you want to connect more than 130% combination, please contact us and discuss the requirement like below. 1) If the operation of indoor unit is more than 130%, low airflow operation is recommended in all the indoor units. 2) If the operation of indoor unit is more than 130%, additional refrigerant is needed according to the headquarter guidance. 3) Over 130%, capacity is same as capacity of 130%, Same remark is valid for power input.

Capacity Cooling kW Heating kW Power Cooling kW Input Heating kW COP Cooling Heating Power Supply , V, Hz Dimensions(WxHxD) mm Weight kg Color Noise level dBA3 Fan Type Air flow rate [CMM] Compressor Type Number of compressors Heat Exchanger Refrigerant Type Charge kg Control Refrigerant Type Oil Charge l Piping Liquid(flare) mm(inch) Connections Suction Gas mm(inch) Discharge Gas mm(inch) Number of outdoor unit Number of maximum connectable indoor units Ratio of the connectable indoor units Longest piping length / Level difference **

36 38 40 42 44 ARUB360LT2 ARUB380LT2 ARUB400LT2 ARUB420LT2 ARUB440LT2 ARUB140LT2 ARUB160LT2 ARUB160LT2 ARUB160LT2 ARUB160LT2 ARUB140LT2 ARUB140LT2 ARUB160LT2 ARUB160LT2 ARUB140LT2 ARUB80LT2 ARUB80LT2 ARUB80LT2 ARUB100LT2 ARUB140LT2
100.8 113.4 28.98 26.93 3.48 4.21 3, 380~415, 50 240+285+285 63 570 5 106.4 119.7 31.13 28.73 3.42 4.17 3, 380~415, 50 240+285+285 63 570 5 112.0 126.0 33.28 30.53 3.37 4.13 3, 380~415, 50 240+285+285 63 570 117.6 132.3 35.16 32.13 3.34 4.12 3, 380~415, 50 285+285+285 Warm Gray 63 Propeller Fan(DC INV) 570 123.2 138.6 37.7 33.6 3.27 4.13 3, 380~415, 50 285+285+285 63 570

46 ARUB460LT2 ARUB160LT2 ARUB160LT2 ARUB140LT2


128.8 144.9 39.85 35.40 3.23 4.09 3, 380~415, 50 285+285+285 63 570 6

48 ARUB480LT2 ARUB160LT2 ARUB160LT2 ARUB160LT2


134.4 151.2 42.0 37.2 3.20 4.06 3, 380~415, 50 285+285+285 63 570 6

LG Air Conditioners System

32_33

(1280x1607x730)x3 (1280x1607x730)x3 (1280x1607x730)x3 (1280x1607x730)x3 (1280x1607x730)x3 (1280x1607x730)x3 (1280x1607x730)x3

DC Inverter Scroll / Constant speed Scroll 5 6 6 Gold fin R410A

8+8+8

8+8+8

8+8+8

8+8+8 EEV FVC68D(PVE)

8+8+8

8+8+8

8+8+8

5.6+5.6+3.3 19.05(3/4) 41.3(1 5/8) 28.58(1 1/8) 3 58

5.6+5.6+3.3 19.05(3/4) 41.3(1 5/8) 34.9(1 3/8) 3 61

5.6+5.6+3.3 19.05(3/4) 41.3(1 5/8) 34.9(1 3/8) 3 64

5.6+5.6+5.6 19.05(3/4) 41.3(1 5/8) 34.9(1 3/8) 3 64 50~130% 200m/100m

5.6+5.6+5.6 19.05(3/4) 41.3(1 5/8) 34.9(1 3/8) 3 64

5.6+5.6+5.6 19.05(3/4) 41.3(1 5/8) 34.9(1 3/8) 3 64

5.6+5.6+5.6 19.05(3/4) 41.3(1 5/8) 34.9(1 3/8) 3 64

Economic and aesthetic space design MULTI V SPACE II is ideal for refined and luxurious living spaces.

COMFORT & SILENCE


The concept of the balcony is changed with the outdoor unit that does not generate hot air. Low noise and vibration technology of MULTI V SPACE II ensures a quiet environment.

MULTI V SPACE II
Hot air Building wind

Front Suction & Front Discharge


Right and left side air flow system High speed air discharging (7~8m/sec) No interference between each floors
7m/s 7m/s

(Efficiency reduction due to hot air back flow) Conventional


Interference between floors!

Outdoor Unit_MULTI V SPACE II

Right outoor Left outoor unit unit

No efficiency reduction!

MULTI V SPACE II

Conventional

Quiet Operation
The noise and vibration are reduced by
- Front discharge - Sealed structure of outdoor unit
LG Air Conditioners System

The indoor noise level is maintained at 30~40dBA, as quiet as being in the library

34_35

LG patents : 57items

LG Patent For MULTI V SPACE II


01 02 03 04 05 06 All technologies in the MULTI V SPACE II which make it a distinctive, unique unit have been applied for patents domestically and internationally. and, some of them have already been registered.
01 Whole structure (8 items) 02 Air handler structrue (18 items) 03 Separation of suction & discharge (6 items) 04 3-side heat exchange structure (3 items) 05 Louver structure /control (20 items) 06 Electrical part(2 items)

Enjoy a clean & comfortable life with MULTI V.

09 New Feature
Economic and aesthetic space design MULTI V SPACE II is ideal for refined and luxurious living spaces.
DC Inverter Compressor & Fan Motor Blackbox Function Night Silent Operation Pump Down

Duct application

Fan RPM Control

(E.S.P & Noise Control)


Duct

Enhanced installation flexibility (Duct application) No need of high static pressure exhaust fan and air guide
Discharging

Outdoor Unit_MULTI V SPACE II

Keeping capacity and noise level as desired

How to set up
- E.S.P control
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Step 1 >4mmAq < ESP < 6mmAq Step 2 >6mmAq < ESP < 8mmAq Step 3 >8mmAq < ESP < 10mmAq Step 4 >10mmAq < ESP < 12mmAq

1 2 3 4 5 6 7

8 9 10 11 12 13 14

* Specifications
HP Model Capacity Power Input COP Cooling Heating Cooling Heating Cooling Heating Independent unit kW kW kW kW kW kW , V, Hz mm kg

1 2 3 4 5 6 7

8 9 10 11 12 13 14

1 2 3 4 5 6 7

8 9 10 11 12 13 14

6 ARUN60LR2 (Right Discharge) ARUN60LL2 (Left Discharge)


16.0 18.0 4.7 4.9 3.40 3.67 3, 380~415, 50 750 x 1790 x 650 200 Warm Gray 49 4~12 Sirocco Fan 100 DC INV Scroll 1 Gold Fin R410A 5.2 EEV FVC68D(PVE) 2.3 9.52(3/8) 19.05(3/4) 1 9 50~130% 150m/50m

8 ARUN80LR2 (Right Discharge) ARUN80LL2 (Left Discharge)


21.7 23.0 6.7 6.7 3.24 3.43 3, 380~415, 50 750 x 1790 x 650 200 53 4~12 100 1

- Noise control
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Low blowing noise > Max - 100 rpm

LG Air Conditioners System

4-Step Modularized Design


Modularized design of the outdoor unit provides simpler installation and maintenance. Outdoor unit can be installed according to overall building construction schedule. Louver is provided locally

1steps Louver frame

2steps System louver

3steps Mechanical parts

4steps Fan parts

Power Supply Dimensions(WxHxD) Weight Color Noise level dBA3 E.S.P range mmAq Fan Type Air flow rate [CMM] Compressor Type Number of compressors Heat Exchanger Refrigerant Type Charge kg Control Refrigerant Type Oil Charge l Piping Liquid(flare) mm(inch) Connections Gas(Bazing) mm(inch) Number of outdoor unit Number of maximum connectable indoor units Ratio of the connectable indoor units Longest piping length / Level difference Note :
1. Capacities are based on the following conditions Cooling-Indoor temp. 27C[80.6F]DB / 19C[66.2F]WB Outdoor temp. 35C[95F]DB / 24C[75.2F]WB Interconnecting piping length 7.5m Level difference of zero

36_37

5.2

2.3 9.52(3/8) 19.05(3/4) 1 13

* Preliminary data (8HP model)

Heating-Indoor temp. 20C[68F]DB / 15C[59F]WB Outdoor temp. 7C[44.6F]DB / 6C[42.8F]WB Interconnecting piping length 7.5m Level difference of zero

*6HP (ARUN60LR2, ARUN60LL2) *8HP (ARUN80LR2, ARUN80LL2)

2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV : Electronic Expansion Valve

Indoor unit
If you need a highly efficient air conditioning system in your building, MULTI V is the right choice for you.

Wall Mounted

Mirror

Indoor Unit

4Way Casstte

2Way Casstte

1Way Casstte

Low Static

LG Air Conditioners System

Built-in

High Static

38_39

M U LT I V indoor
49 50 52 56 60 61 62
Wall mounted ARTCOOL Ceiling Cassette Ceiling Concealed Duct Ceiling & Floor Ceiling Suspended Floor standing

Ceiling & Floor

Ceiling Suspended

Floor Standing - With Case

Floor Standing - Without Case

LG has been able to create a design conscious indoor unit that compliments any interior decoration. And they have improved air flow innovatively to realize worlds lowest noise, and provide a more pleasant and convenient indoor environment.

Aesthetic Design Low Noise 4 Vane Independent Operation Auto Elevation Grille

Aesthetic Design
You no longer have to be told what your air conditioner should look like. With LGs revolutionary ARTCOOL photo changeable, you can simply change the look of your air conditioner to what you want, when you want to.
ARTCOOL series with outstanding designs have received International Forum Design Award, Reddot Design Award and G Mark. Typing Office Conversation Library

Low Noise
Super light BLDC motor guarantees your enhanced comfortable indoor environment.

4 way CST

1 Vane, 1 Motor

4 Vanes Independent Operation


Vane angle control satisfies both users who like direct wind and indirect wind. and also it prevents cold air draft.

Indoor Unit

- How to change the picture


Direct air flow Indirect air flow

All vane operation

Individual vane operation

Easy vane angle control with a remote controller

1 : 20 0 : 30 Air flow rate control Individual vane angel control 2 : 40 5 : 70 4 : 60 3 : 50 LG Air Conditioners System

- Panel type

Auto Elevation Grille


Easy filter cleaning with elevation grille
Silver 07/09/12GSFV2 Gold 07/09/12GSFG2 Red 07/09/12GSFE2 White silver 07/09/12GSFH2

40_41

4 Way
4.5m

Conventional 3.5m

- ARTCOOL Mirror
4-Point support structure Mirror 07/09/12/15GSER2
18/24GS8R2

- Installed inside main body - Auto horizontal level - 4 points support - Memory for users level - Max. 4.5m length

Auto horizontal control

Memory for users level

Auto bottom detection


Max. 4.5m

Silver 07/09/12/15GSEV2
18/24GS8V2

Blue 07/09/12/15GSEB2
18/24GS8B2

STOP Memory
*Available for 24k ~ 48k Btu/h

LG has been able to create a design conscious indoor unit that compliments any interior decoration. And they have improved air flow innovatively to realize worlds lowest noise, and provide a more pleasant and convenient indoor environment.

Wide Jet Vane High Ceiling Mode Flexible Connection Appliaction of Ceiling Concealed Duct Appliaction of Built-in Duct Linear E.S.P Control

Air flow improvement

Wide Jet Vane


Wider!! 567mm

80mm
NEW Current

Improved wide and narrow vane will provide comfortable temperature distribution without air flow dead zone.
* For 4 way cassette (570 * 570), this function will be applied from May.

Application of Ceiling Concealed Duct


It is possible to make each rooms cool & warm with installing a chamber and a spiral duct.

487mm

Highlander
t 26 25 24 23 22 21 20 19 18

Even air distribution

Temp.
27C

Indoor Unit

Max. 9 discharging
15C

Current

t 26 25 24 23 22 21 20 19 18

Air flow dead zone

Temp.
27C

Application of Built-in Duct


Built-in duct has no need of duct space with using suction canvas and grille.

15C

LG Air Conditioners System

Conventional

4 way CST

High Ceiling Mode


High ceiling mode with phase-control algorithm is possible to apply as high as 3.6m of ceiling.
Grille Canvas

42_43

Flexible Connection
Flexible connection of remote controller
- Group control : 1 remote controller to several indoor units - Second remote control : 2 remote controllers to 1 indoor unit

Linear E.S.P Control


Air volume and sound are always kept as design regardless of E.S.P change using this technology , you can
Optimize duct work Installation Keep capacity & sound level as desired Simplify model numbers

Easy & solid attachment to the wall

The phase control motor technology offers money saving benefit to the installer.

wall

wall

*E.S.P is easily controlled by remote controller

LG has been able to create a design conscious indoor unit that compliments any interior decoration. And they have improved air flow innovatively to realize worlds lowest noise, and provide a more pleasant and convenient indoor environment.

Compact Size One Touch Type Panel Convenient Installation Easy Drain Installation 3Way Flexible Installation Sliding Type Filter

Compact Size
The indoor unit with slim and compact size has reduced the restriction which enables successful installation in various spaces.

Drain hose

Drain pump

Easy Drain Installation


It reduces the installation time by over 40% with elbow-less drain hose. Midget drain pump covers maximum 800mm high, featuring easy piping installation.
* Accessory (Drain hose) PHDHA05T 500mm 30EA PHDHA07T - 700mm 30EA PHDHA05B 500mm 5EA PHDHA07B 700mm 5EA

6.0 ~ 7.2 kW 8.3 ~ 11.0 kW conventional LG


218mm 288mm

Indoor Unit

204mm 246mm

3Way Flexible Installation One Touch Type Panel


It provides easy installation with a one-touch detachable panel. All sides (front, back, floor) are possible to install and connect to the outdoor unit.
LG Air Conditioners System

Back

Coner detachable design

Convenient Installation
Easy installation with corner detachable decoration panel.

Side

Floor

44_45

Refrigerant piping check

Drain leakage check

Drain leakage check

Hanger adjust

Sliding Type Filter


Anti-biotic filter Easy cleaning

Easy maintenance and extended product life with sliding type anti-biotic filter.

Hanger adjust

Hanger adjust

Sliding type

LG has been able to create a design conscious indoor unit that compliments any interior decoration. And they have improved air flow innovatively to realize worlds lowest noise, and provide a more pleasant and convenient indoor environment.

Neo Plasma Air Purifying System Digital Air Flow Control Swirl Swing Child Lock Function

Polluted Air
01 02 03 04

Clean Air
05

Neo Plasma Air Purifying System


LGs unique NEO Plasma air purifying system is equipped with 7 specialized filters in 5 separate stages to enhance its cleaning power. It reduces fine dust and mold, unpleasant odors and cigarette smoke as air passes through each filter.

Digital Air Flow Control


The air flow can be controlled to ensure maximum comfort and convenience.
Normal Jet cool Sleep mode

fast & even widely

speedy & powerful

indirectly & softly

Odor Free! Dust Free! Allergy Free!

Indoor Unit

Swirl swing (plaesant air) 01 Pre Filter The antibacterial pre-filter primarily reduces large dust, mold and quilt dust. 02 Nano Carbon Filter Nano-size carbon filters remove fine odorous particles from the household air resulting in a more pleasant environment.
What is Nano Carbon Ball?
Microscopic sized (1/1000000000) filter to ensure optimal filtration of odors.
200~500nm

Normal air flow

Swirl Swing
Swirl swing distributes air evenly throughout the room to ensure a more comfortable conditioned environment by adjusting the movement of the vane.

05 Plasma Filter The PLASMA Air Purifying System developed uniquely by LG not only reduces microscopic contaminants and dust, but also reduces house mites, pollen, and pet fur to reduce allergy and asthma symptoms.

Comparison of temperatures
LG Air Conditioners System

* Test Result Certification

03 Triple Filter The triple filter consists of three specialized filters to reduce the symptoms associated with various organic compounds including formaldehyde. It also has the ability to reduce unpleasant odors creating a more comfortable environment.

Bio Active Site

Bacteria, Virus

Nano Particle

Nano Particle

Nano Particle

Nano Particle

Vertical Temp. differences

Horizontal Temp. differences

46_47

Active State

Bacteria Selective Bacteriolysis Capture

Regeneration (Active State)

Indoor Temperature Distribution Chart


LG Healthy Dehumidification
By increasing the vane angle, a better approach of the actual temperature is possible to prevent over cooling.

Healthy Dehumidification
Dehumidification mode reduces uncomfortable humidity from the room without over cooling.

Distinctions from Conventional Filters


Nano Bio Fusion Filter
The bio enzyme destroys cell walls and nuclei of some bacteria and allergens.

04 Nano Bio Fusion Filter Nano bio fusion filters allow their nanosize bio enzymes to directly penetrate through cell walls of some bacteria and allergen to decompose its cell nuclei. Conventional

Conventional
Since the surrounding temperature is measured after the air from the unit is widely distributed, accurate approach of the air is not possible.
Destroy bacteria but allow part of them to survive

Simply inactivate bacteria

Wall Mounted
LG has been able to create a design conscious indoor unit that compliments any interior decoration. And they have improved air flow innovatively to realize worlds lowest noise, and provide a more pleasant and convenient indoor environment.

ARNU07GSEL2 / ARNU09GSEL2 ARNU12GSEL2 / ARNU15GSEL2 ARNU18GS5L2 / ARNU24GS5L2

LG Auto Clean

Conventional

Auto Clean
Auto clean helps to remove odor and save clean-up time. After using airconditioner, Auto clean makes the inner part of Air conditioner dry for 30 min. It removes mositure and mold so you can enjoy odor-free air and save time to clean up.

1 STEP Dries the evaporator with gentle low noise air from the fan by removing any remaining moisture.
Pressing the Auto Clean button will activate the automatic cleaning function after the cooling operation.

* Specifications
Model
Capacity Cooling

Unit

ARNU07GSEL2 ARNU09GSEL2 ARNU12GSEL2 ARNU15GSEL2 ARNU18GS5L2 ARNU24GS5L2


2.2 7,500 2.5 8,500 40 40 2.8 9,600 3.2 10,900 40 40 3.6 4.5 12,300 15,400 4.0 5.0 13,600 17,100 40 40 40 40 1, 220~240, 50 9 42 / 36 / 27 10.5 / 9 / 8.5 o 6.35(1/4) 12.7(1/2) 20/16 5.6 19,100 6.3 21,500 40 40 7.1 24,200 8.0 27,300 40 40

Indoor Unit

2 STEP Removes moulds through the neo plasma system.


Only the fan will operate to dry the inner part of the air conditioner in just 30 minutes.

Horizontal airflow control

Vertical airflow control

Air Flow Direction Control


Horizontal airflow control
- Adjust the horizontal airflow direction by manually moving the horizontal airflow direction vane by hand.

kW Btu/h Heating kW Btu/h Power Cooling W Input Heating W , V, Hz Power Supply Dimensions(WxDxH) mm Weight kg Noise level dBA3 Air flow rate H/M/L CMM Neo Plasma air purifying filter Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm
Note :

9 37 / 33 / 23 5.6 / 5 / 4.6 o 6.35(1/4) 12.7(1/2) 20/16

895x165x282 9 9 39 / 35 / 25 41 / 36 / 27 7 / 6.5 / 6 9.5 / 9 / 8.5 o o 6.35(1/4) 6.35(1/4) 12.7(1/2) 12.7(1/2) 20/16 20/16

1090x178x300 12 12 44 / 40 / 36 46 / 41 / 38 12 / 10.5 / 9 14 / 13 / 10 o o 6.35(1/4) 9.52(3/8) 12.7(1/2) 15.88(5/8) 20/16 20/16

LG Air Conditioners System

Vertical airflow
- The airflow direction can be adjusted as desired by using the remote controller.

1. Capacities are based on the following conditions Cooling-Indoor temp. 27C[80.6F]DB / 19C[66.2F]WB Heating-Indoor temp. 20C[68F]DB / 15C[59F]WB Outdoor temp. 35C[95F]DB / 24C[75.2F]WB Outdoor temp. 7C[44.6F]DB / 6C[42.8F]WB Interconnecting piping length 7.5m Interconnecting piping length 7.5m Level difference of zero Level difference of zero 2. Due to our policy of innovation some specifications may be changed without notification

48_49

* Accessories
Model
ARNU07GSEL2 Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU09GSEL2 ARNU12GSEL2 ARNU15GSEL2 ARNU18GS5L2 ARNU24GS5L2 Dry Contact
PQDSA PQDSB/ PQDSB1 PQDSBC

Weekly Program
SUNDAY MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY

The operator can set an on/off reservation of the air conditioner for a period of one week. LCD Wired Remote Controller
On/Off Test run mode Self-diagnosis 3-step fan speed selection Operation indication Room temperature

Wired remote controller

Wireless remote controller

Deluxe type

Standard type

Simple type

Simple type for hotel

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

Mirror
ARNU07GSF*2 / ARNU09GSF*2 ARNU12GSF*2
* 1: Photo changeable, V: Silver, E: Red, G: Gold, H: White Silver

ARNU07GSE*2 / ARNU09GSE*2 / ARNU12GSE*2 ARNU15GSE*2 / ARNU18GS8*2 / ARNU24GS8*2


* R : Mirror, B : Blue, V : Silver

Mirror

Silver

Gold

Indoor Unit_ARTCOOL Gallery / Mirror

Silver

Red

White Silver

Blue

* Photo changeable

* Panel type

* Specifications
Model Unit ARNU07GSF*2
2.2 7,500 2.5 8,500 35 35

* Specifications
ARNU09GSF*2
2.8 9,600 3.2 10,900 35 35 1, 220~240, 50 600x146x600 15 38 / 32 / 27 8.1 / 6.3 / 4.2 o 6.35(1/4) 12.7(1/2) 16.2/12.2

ARNU12GSF*2
3.6 12,300 4.0 13,600 35 35

Model

Unit

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 ARNU18GS8*2 ARNU24GS8*2


2.2 7,500 2.5 8,500 40 40 2.8 9,600 3.2 10,900 40 40 3.6 4.5 12,300 15,400 4.0 5.0 13,600 17,100 40 40 40 40 1, 220~240, 50 11.2 42 / 36 / 27 10.5 / 8 / 6 o 6.35(1/4) 12.7(1/2) 20/16 5.6 19,100 6.3 21,500 40 40 7.1 24,200 8.0 27,300 40 40

Capacity Cooling kW Btu/h Heating kW Btu/h Power Cooling W Input Heating W Power Supply , V, Hz Dimensions(WxDxH) mm Weight kg Noise level dBA3 Air flow rate H/M/L CMM Neo Plasma air purifying filter Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm

15 38 / 32 / 27 8.1 / 6.3 / 4.2 o 6.35(1/4) 12.7(1/2) 16.2/12.2

15 44 / 38 / 32 9.3 / 7.7 / 6.0 o 6.35(1/4) 12.7(1/2) 16.2/12.2


* Check up the note, refer to on the 49 page.

Capacity Cooling kW Btu/h Heating kW Btu/h Power Cooling W Input Heating W Power Supply , V, Hz Dimensions(WxDxH) mm Weight kg Noise level dBA3 Air flow rate H/M/L CMM Neo Plasma air purifying filter Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm
* Preliminary data (18 ~ 24k model)

11.2 37 / 33 / 23 7/6/4 o 6.35(1/4) 12.7(1/2) 20/16

915x169x282 11.2 11.2 39 / 35 / 25 41 / 36 / 27 8/7/5 10 / 8 / 6 o o 6.35(1/4) 6.35(1/4) 12.7(1/2) 12.7(1/2) 20/16 20/16

1170x173x315 13 13 37 / 34 / 31 43 / 37 / 32 14.4 / 13 / 11 17.9 / 14.4 / 12 o o 6.35(1/4) 9.52(3/8) 12.7(1/2) 15.88(5/8) 20/16 20/16
* Check up the note, refer to on the 49 page.

LG Air Conditioners System

50_51

* Accessories
Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU07GSF*2 ARNU09GSF*2
PQDSA PQDSB/ PQDSB1 PQDSBC

* Accessories
ARNU12GSF*2

Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point)

ARNU07GSE*2

ARNU09GSE*2

ARNU12GSE*2

ARNU15GSE*2

ARNU18GS8*2

ARNU24GS8*2

PQDSA PQDSB/ PQDSB1 PQDSBC

Wired remote controller

Wireless remote controller

Wired remote controller

Wireless remote controller

Deluxe type

Standard type

Simple type

Simple type for hotel

Deluxe type

Standard type

Simple type

Simple type for hotel

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

4 Way Cassette

(570*570)

4 Way Cassette

(840*840)

ARNU05GTRC2 / ARNU07GTRC2 ARNU09GTRC2 / ARNU12GTRC2 ARNU15GTQC2 / ARNU18GTQC2

ARNU24GTPC2 / ARNU28GTPC2 ARNU36GTNC2 / ARNU42GTMC2 ARNU48GTMC2

Indoor Unit_Ceiling Cassette

* Specifications
Model
Capacity Cooling Heating Power Input Power Supply Dimensions (WxDxH) Weight Cooling Heating Body Front panel Body Front panel

* Specifications
ARNU05GTRC2 ARNU07GTRC2 ARNU09GTRC2 ARNU12GTRC2 ARNU15GTQC2 ARNU18GTQC2
1.6 5,500 1.8 6,100 45 45 2.8 3.6 9,600 12,300 3.2 4.0 10,900 13,600 45 45 45 45 1, 220 ~ 240, 50 570 x 570 x 214 700x700x30 13.1 14.2 14.2 2.3 2.3 2.3 Morning Fog 36 / 35 / 33 36 / 35 / 34 36 / 35 / 34 7.5 / 7 / 6.6 8 / 7.5 / 7.1 8.7 / 8 / 7 o o o o o o 6.35(1/4) 6.35(1/4) 6.35(1/4) 12.7(1/2) 12.7(1/2) 12.7(1/2) 32/25 32/25 32/25 2.2 7,500 2.5 8,500 45 45 4.5 15,400 5.0 17,100 45 45 5.6 19,100 6.3 21,500 45 45

Unit
kW Btu/h kW Btu/h W W , V, Hz mm mm kg

Model
Capacity Cooling Heating Power Input Power Supply Dimensions (WxDxH) Weight Cooling Heating Body Front Panel Body Front Panel

Unit
kW Btu/h kW Btu/h W W , V, Hz mm mm kg kg

ARNU24GTPC2
7.1 24,200 8.0 27,300 33 33

ARNU28GTPC2
8.2 28,000 9.2 31,500 33 33

ARNU36GTNC2
10.6 36,200 11.9 40,600 144 144 1, 220 ~ 240, 50 840x840x246 950x950x25 23.5 4.5 Morning Fog 43 / 40 / 39 25 / 21 / 19 o o 9.52(3/8) 15.88(5/8) 32/25

ARNU42GTMC2
12.3 42,000 13.8 43,800 144 144

ARNU48GTMC2
14.1 48,100 15.9 51,200 144 144

570 x 570 x 256 15.5 2.5 37 / 36 / 35 11 / 10 / 9.3 o o 6.35(1/4) 12.7(1/2) 32/25 15.5 2.5 38 / 37 / 36 11.2 / 11 / 10 o o 6.35(1/4) 12.7(1/2) 32/25

840x840x204 20.8 4.5 38 / 35 / 31 17 / 15 / 13 o o 9.52(3/8) 15.88(5/8) 32/25 20.8 4.5 39 / 38 / 32 19 / 16 / 14 o o 9.52(3/8) 15.88(5/8) 32/25

840x840x288 25.6 4.5 47 / 44 / 42 30 / 27 / 24 o o 9.52(3/8) 15.88(5/8) 32/25 25.6 4.5 48 / 47 / 45 31 / 29 / 27 o o 9.52(3/8) 15.88(5/8) 32/25

13.1 2.3 36 / 35 / 33 7.5 / 7 / 6.6 o o 6.35(1/4) 12.7(1/2) 32/25

Panel Color Noise level Air flow rate H/M/L Neo Plasma air purifying filter Drain Pump Piping Liquid Connection Gas Drain(OD/ID)

dBA3 CMM

mm(inch) mm(inch) mm

Panel Color Noise level dBA3 Air flow rate H/M/L CMM Neo Plasma air purifying filter Drain Pump Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm

LG Air Conditioners System

* Check up the note, refer to on the 49 page.

* Check up the note, refer to on the 49 page.

* Accessories
Model
Dry Contact Front Panel Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU05GTRC2 ARNU07GTRC2 ARNU09GTRC2 ARNU12GTRC2 ARNU15GTQC2 ARNU18GTQC2
PQDSA PQDSB/ PQDSB1 PQDSBC PT-UQC

* Accessories
Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU24GTPC2 ARNU28GTPC2 ARNU36GTNC2
PQDSA PQDSB/ PQDSB1 PQDSBC PT-UMC PTEGM0 PTVK410 / PTVK420 / PTVK 430

52_53

ARNU42GTMC2

ARNU48GTMC2

Front Panel Auto Elevation Grille Ventilation Kit Wireless remote controller Wired remote controller

Wired remote controller

Wireless remote controller

Deluxe type

Standard type

Simple type

Simple type for hotel

Deluxe type

Standard type

Simple type

Simple type for hotel

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

2 Way Cassette
ARNU18GTLC2 / ARNU24GTLC2

1 Way Cassette
ARNU07GTJC2 / ARNU09GTJC2 ARNU12GTJC2

Indoor Unit_Ceiling Cassette

* Specifications
Model
Capacity Cooling Heating Power Input Power Supply Dimensions (WxDxH) Weight Cooling Heating Body Front Panel Body Front Panel

* Specifications
ARNU18GTLC2
5.6 19,100 6.3 21,500 70 70 1, 220 ~ 240, 50 830x550x225 1050x640x28.5 22 4 Morning Fog 40 / 35 / 30 13 / 12 / 10 o o 6.35(1/4) 12.7(1/2) 32/25 22 4 42 / 37 / 32 17 / 15 / 13 o o 9.52(3/8) 15.88(5/8) 32/25
* Check up the note, refer to on the 49 page.

Unit
kW Btu/h kW Btu/h W W , V, Hz mm mm kg kg dBA3 CMM

ARNU24GTLC2
7.1 24,200 8.0 27,300 70 70

Model
Capacity Cooling Heating Power Input Power Supply Dimensions (WxDxH) Weight Cooling Heating

Unit
kW Btu/h kW Btu/h W W , V, Hz mm mm kg kg dBA3 CMM

ARNU07GTJC2
2.2 7,500 2.5 8,500 40 40

ARNU09GTJC2
2.8 9,600 3.2 10,900 40 40 1, 220 ~ 240, 50 860x410x138 1070x480x20 11.5 1.5 Morning Fog 40 / 38 / 37 7.5 / 6.5 / 6 o o 6.35(1/4) 12.7(1/2) 32/25

ARNU12GTJC2
3.6 12,300 4.0 13,600 40 40

Body Front Panel Body Front Panel

11.5 1.5 40 / 38 / 37 7.5 / 6.5 / 6 o o 6.35(1/4) 12.7(1/2) 32/25

11.5 1.5 41 / 39 / 37 8/7/6 o o 6.35(1/4) 12.7(1/2) 32/25


* Check up the note, refer to on the 49 page.

LG Air Conditioners System

Panel Color Noise level Air flow rate H/M/L Neo Plasma air purifying filter Drain Pump Piping Liquid Connection Gas Drain(OD/ID)

mm(inch) mm(inch) mm

Panel Color Noise level Air flow rate H/M/L Neo Plasma air purifying filter Drain Pump Piping Liquid Connection Gas Drain(OD/ID)

mm(inch) mm(inch) mm

54_55

* Accessories
Model
Dry Contact Front panel Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU18GTLC2
PQDSA PQDSB/ PQDSB1 PQDSBC PT-HLC

* Accessories
ARNU24GTLC2

Model
Dry Contact Front panel Without case(1 contact point) With case(1 contact point) With case(2 contact point)

ARNU07GTJC2

ARNU09GTJC2
PQDSA PQDSB/ PQDSB1 PQDSBC PT-HJC

ARNU12GTJC2

Wired remote controller

Wireless remote controller

Wired remote controller

Wireless remote controller

Deluxe type

Standard type

Simple type

Simple type for hotel

Deluxe type

Standard type

Simple type

Simple type for hotel

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

Low Static Duct


ARNU07GB1G2 / ARNU09GB1G2 ARNU12GB1G2 / ARNU15GB1G2 ARNU18GB2G2 / ARNU24GB2G2

Built-in Duct
ARNU07GB3G2 / ARNU09GB3G2 ARNU12GB3G2 / ARNU15GB3G2 ARNU18GB4G2 / ARNU24GB4G2

Indoor Unit_Ceiling Concealed Duct

* Specifications
Model Unit ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2
2.2 7,500 2.5 8,500 30 30 2.8 9,600 3.2 10,900 30 30 3.6 4.5 12,300 15,400 4.0 5.0 13,600 17,100 30 30 30 30 1, 220 ~ 240, 50 21 38 / 37 / 36 0~4 8.5 / 7.5 / 6.5 6.35(1/4) 12.7(1/2) 32/25.4 9.5 / 8.5 / 7.5 6.35(1/4) 12.7(1/2) 32/25.4 10.5 / 9.5 / 8.5 6.35(1/4) 12.7(1/2) 32/25.4 11.5 / 10.5 / 9.5 6.35(1/4) 12.7(1/2) 32/25.4 16 / 14 / 12 6.35(1/4) 12.7(1/2) 32/25.4 19 / 17 / 15 9.52(3/8) 15.88(5/8) 32/25.4 5.6 19,100 6.3 21,500 80 80 7.1 24,200 8.0 27,300 80 80

* Specifications
Model Unit ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2 ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2
2.2 7,500 2.5 8,500 30 30 2.8 9,600 3.2 10,900 30 30 3.6 4.5 12,300 15,400 4.0 5.0 13,600 17,100 30 30 30 30 1, 220~ 240, 50 5.6 19,100 6.3 21,500 80 80 7.1 24,200 8.0 27,300 80 80

Capacity Cooling kW Btu/h Heating kW Btu/h Power Cooling W Input Heating W Power Supply , V, Hz Dimensions(WxDxH) mm Weight kg Noise level dBA3 E.S.P range mmAq Air flow rate H/M/L CMM Neo Plasma air purifying filter Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm

21 35 / 33 / 31

820x575x190 21 21 36 / 35 / 33 37 / 36 / 35

1100x575x190 26 26 43 / 40 / 37 40 / 37 / 34

* Check up the note, refer to on the 49 page.

Capacity Cooling kW Btu/h Heating kW Btu/h Power Cooling W Input Heating W Power Supply , V, Hz Dimensions (WxDxH) mm Suction grille (WxDxH) Suction canvas (WxHxD) Weight kg Noise level dBA3 E.S.P range mmAq Air flow rate H/M/L CMM Neo Plasma air purifying filter Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm

21 37 / 34 / 33 8 / 6.5 / 5.5 6.35(1/4) 12.7(1/2) 32/25.4

820x575x190 910x359x56 821x274x(45~250) 21 21 39 / 35 / 34 40 / 37 / 34 0~4 9/7/6 6.35(1/4) 12.7(1/2) 32/25.4 10 / 8 / 6.5 6.35(1/4) 12.7(1/2) 32/25.4

21 41 / 40 / 37 11 / 10 / 8 6.35(1/4) 12.7(1/2) 32/25.4

1100x575x190 1188x359x56 1100x274x(45~250) 26 26 43 / 40 / 37 46 / 43 / 37 14 / 12 / 10 6.35(1/4) 12.7(1/2) 32/25.4 17 / 15 / 10 9.52(3/8) 15.88(5/8) 32/25.4

LG Air Conditioners System

56_57

* Accessories
Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2
PQDSA PQDSB/ PQDSB1 PQDSBC

* Accessories
Model
Dry Contact Suction Grille Suction Canvas Wireless remote controller Wired remote controller Without case(1 contact point) With case(1 contact point) With case(2 contact point)
PBSGB30 PBSC30

* Check up the note, refer to on the 49 page.

ARNU07GB3G2

ARNU09GB3G2

ARNU12GB3G2

ARNU15GB3G2

ARNU18GB4G2

ARNU24GB4G2

PQDSA PQDSB/ PQDSB1 PQDSBC PBSGB40 PBSC40

Wired remote controller

Wireless remote controller

Deluxe type

Standard type

Simple type

Simple type for hotel

Deluxe type

Standard type

Simple type

Simple type for hotel

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

* For using wireless remote controller, it needs to install standard wired remote controller. (Duct, Floor standing model.)

* For using wireless remote controller, it needs to install standard wired remote controller. (Duct, Floor standing model.)

High Static Duct


ARNU07GBHA2 / ARNU09GBHA2 ARNU12GBHA2 / ARNU15GBHA2 ARNU18GBHA2 / ARNU24GBHA2

High Static Duct


ARNU28GBGA2 / ARNU36GBGA2 ARNU42GBGA2 / ARNU48GBRA2 URNU76GB8A2 / URNU96GB8A2

Indoor Unit_Ceiling Concealed Duct

* Specifications
Model
Capacity Cooling

* Specifications
ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2
2.2 7,500 2.5 8,500 150 150 2.8 9,600 3.2 10,900 150 150 3.6 4.5 12,300 15,400 4.0 5.0 13,600 17,100 150 150 150 150 1, 220 ~240, 50 882x450x260 26 26 37 / 35 / 34 39 / 38 / 37 4~12 12 / 10 / 8.5 13.5 / 12 / 8.5 6.35(1/4) 6.35(1/4) 12.7(1/2) 12.7(1/2) 32/25 32/25 5.6 19,100 6.3 21,500 150 150 7.1 24,200 8.0 27,300 150 150

Unit

Model
Capacity Cooling

Unit

ARNU28GBGA2 ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 URNU76GB8A2 URNU96GB8A2


8.2 28,000 9.2 31,500 450 450 10.6 36,200 11.9 40,600 450 450 1182x450x298 38 44 / 42 / 40 6~16 25.9 / 24.1 / 21.8 9.52(3/8) 15.88(5/8) 32/25 38 46 / 44 / 42 6~14 32.3 / 29 / 25.3 9.52(3/8) 15.88(5/8) 32/25 12.3 14.1 42,000 48,100 13.8 15.9 43,800 51,200 450 450 450 450 1, 220 ~240, 50 1230x590x380 38 48 / 46 / 45 6~12 34.5 / 32.3 / 30.7 9.52(3/8) 15.88(5/8) 32/25 53 45 / 43 / 41 7~20 44.8 / 40.6 / 33.3 9.52(3/8) 15.88(5/8) 32/25 22.4 76,400 25.2 86,000 800 800 28.0 95,900 31.5 107,500 800 800

kW Btu/h Heating kW Btu/h Power Cooling W Input Heating W Power Supply , V, Hz Dimensions(WxDxH) mm Weight kg Noise level dBA3 E.S.P range mmAq Air flow rate H/M/L CMM Neo Plasma air purifying filter Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm

26 34 / 33 / 32 8.5 / 7.5 / 6 6.35(1/4) 12.7(1/2) 32/25

26 35 / 34 / 33 10 / 8.5 / 7.5 6.35(1/4) 12.7(1/2) 32/25

26.5 42.5 / 41 / 37 15.5 / 13.5 / 12.4 6.35(1/4) 12.7(1/2) 32/25

26.5 45 / 43 / 41 18.3 / 16.9 / 15.5 9.52(3/8) 15.88(5/8) 32/25

kW Btu/h Heating kW Btu/h Power Cooling W Input Heating W Power Supply , V, Hz Dimensions(WxDxH) mm Weight kg Noise level dBA3 E.S.P range mmAq Air flow rate H/M/L CMM Neo Plasma air purifying filter Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm

1562x688x460 87 50 / 48 / 48 12-25 64 / 50 / 50 9.52(3/8) 19.05(3/4) 32/25 72 / 64 / 64 9.52(3/8) 22.2(7/8) 32/25 87 52 / 50 / 50

LG Air Conditioners System

* Check up the note, refer to on the 49 page.

* Check up the note, refer to on the 49 page.

58_59

* Accessories
Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2
PQDSA PQDSB/ PQDSB1 PQDSBC

* Accessories
Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU28GBGA2 ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 URNU76GB8A2 URNU96GB8A2
PQDSA PQDSB/ PQDSB1 PQDSBC

Wired remote controller

Wireless remote controller

Wired remote controller

Wireless remote controller

Deluxe type

Standard type

Simple type

Simple type for hotel

Deluxe type

Standard type

Simple type

Simple type for hotel

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

* For using wireless remote controller, it needs to install standard wired remote controller. (Duct, Floor standing model.)

* For using wireless remote controller, it needs to install standard wired remote controller. (Duct, Floor standing model.)

Ceiling & Floor


ARNU09GVEA2 / ARNU12GVEA2

Ceiling Suspended
ARNU18GVJA2 / ARNU24GVJA2

Indoor Unit_Ceiling & Floor / Ceiling Suspended

* Specifications
Model
Capacity Cooling Heating

* Specifications
ARNU09GVEA2
2.8 9,600 3.2 10,900 30 30 1, 220 ~ 240, 50 900x200x490 13.7 36 / 32 / 28 7.6 / 6.9 / 6.2 6.35(1/4) 12.7(1/2) 20/16 13.7 38 / 36 / 30 9.2 / 7.6 / 6.9 6.35(1/4) 12.7(1/2) 20/16
* Check up the note, refer to on the 49 page.

Unit
kW Btu/h kW Btu/h W W , V, Hz mm kg dBA3 CMM

ARNU12GVEA2
3.6 12,300 4.0 13,600 30 30

Model
Capacity Cooling

Unit

ARNU18GVJA2
5.6 19,100 6.3 21,500 63 63 1, 220~240, 50 950x220x650 24.6 42 / 40 / 37 16 / 14 / 12 6.35(1/4) 12.7(1/2) 20/16

ARNU24GVJA2
7.1 24,200 8.0 27,300 63 63

Power Cooling Input Heating Power Supply Dimensions(WxDxH) Weight Noise level Air flow rate H/M/L Plasma air purifying filter Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm

kW Btu/h Heating kW Btu/h Power Cooling W Input Heating W Power Supply , V, Hz Dimensions(WxDxH) mm Weight kg Noise level dBA3 Air flow rate H/M/L CMM Neo Plasma air purifying filter Piping Liquid mm(inch) Connection Gas mm(inch) Drain(OD/ID) mm

LG Air Conditioners System

24.6 43 / 41 / 39 18 / 16 / 14 9.52(3/8) 15.88(5/8) 20/16


* Check up the note, refer to on the 49 page.

60_61

* Accessories
Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU09GVEA2
PQDSA PQDSB/ PQDSB1 PQDSBC

* Accessories
ARNU12GVEA2

Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point)

ARNU18GVJA2
PQDSA PQDSB/ PQDSB1 PQDSBC

ARNU24GVJA2

Wired remote controller

Wireless remote controller

Wired remote controller

Wireless remote controller

Deluxe type

Standard type

Simple type

Simple type for hotel

Deluxe type

Standard type

Simple type

Simple type for hotel

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

Floor Standing with case


ARNU07GCEA2 / ARNU09GCEA2 ARNU12GCEA2 / ARNU15GCEA2 ARNU18GCFA2 / ARNU24GCFA2

Floor Standing without case


ARNU07GCEU2 / ARNU09GCEU2 ARNU12GCEU2 / ARNU15GCEU2 ARNU18GCFU2 / ARNU24GCFU2

Indoor Unit_Floor Standing

* Specifications
Model
Capacity Cooling Heating Power Cooling Input Heating Power Supply Dimensions(WxDxH) Weight Noise level Air flow rate H/M/L Plasma air purifying filter Piping Liquid Connection Gas Drain(ID)

* Specifications
ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2
2.2 7,500 2.5 8,500 30 30 3.6 4.5 12,300 15,400 4.0 5.0 13,600 17,100 30 30 30 30 1, 220~240, 50 1067x203x635 27 27 27 37 / 35 / 33 38 / 37 / 35 36 / 34 / 32 10.5 / 9.5 / 8.5 11.5 / 10 / 9.5 9.5 / 8.5 / 7.5 6.35(1/4) 6.35(1/4) 6.35(1/4) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12 12 12 2.8 9,600 3.2 10,900 30 30 5.6 19,100 6.3 21,500 80 80 7.1 24,200 8.0 27,300 80 80

Unit
kW Btu/h kW Btu/h W W , V, Hz mm kg dBA3 CMM mm(inch) mm(inch) mm

Model
Capacity Cooling Heating Power Cooling Input Heating Power Supply Dimensions(WxDxH) Weight Noise level Air flow rate H/M/L Plasma air purifying filter Piping Liquid Connection Gas Drain(ID)

Unit
kW Btu/h kW Btu/h W W , V, Hz mm kg dBA3 CMM mm(inch) mm(inch) mm

ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2


2.2 7,500 2.5 8,500 30 30 2.8 9,600 3.2 10,900 30 30 3.6 4.5 12,300 15,400 4.0 5.0 13,600 17,100 30 30 30 30 1, 220~240, 50 20 38 / 37 / 35 11.5 / 10 / 9.5 6.35(1/4) 12.7(1/2) 12 5.6 19,100 6.3 21,500 80 80 7.1 24,200 8.0 27,300 80 80 1256x190x639 27 40 / 37 / 34 16 / 14 / 12 6.35(1/4) 12.7(1/2) 12 27 43 / 40 / 37 18 / 16 / 14 9.52(3/8) 15.88(5/8) 12

27 35 / 33 / 31 8.5 / 7.5 / 6.5 6.35(1/4) 12.7(1/2) 12

1345x203x635 34 34 40 / 37 / 34 43 / 40 / 37 16 / 14 / 12 18 / 16 / 14 6.35(1/4) 9.52(3/8) 12.7(1/2) 15.88(5/8) 12 12


* Check up the note, refer to on the 49 page.

20 35 / 33 / 31 8.5 / 7.5 / 6.5 6.35(1/4) 12.7(1/2) 12

978x190x639 20 20 37 / 35 / 33 36 / 34 / 32 10.5 / 9.5 / 8.5 9.5 / 8.5 / 7.5 6.35(1/4) 6.35(1/4) 12.7(1/2) 12.7(1/2) 12 12

LG Air Conditioners System

* Check up the note, refer to on the 49 page.

62_63

* Accessories
Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2 ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2
PQDSA PQDSB/ PQDSB1 PQDSBC

* Accessories
Model
Dry Contact Without case(1 contact point) With case(1 contact point) With case(2 contact point) ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2 ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2
PQDSA PQDSB/ PQDSB1 PQDSBC

Wired remote controller

Wireless remote controller

Wired remote controller

Wireless remote controller

Deluxe type

Standard type

Simple type

Simple type for hotel

Deluxe type

Standard type

Simple type

Simple type for hotel

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

PQRCUDS0*

PQRCUSA1

PQRCUCS0C

PQRCFCS0C

PQWRHDF0

* For using wireless remote controller, it needs to install standard wired remote controller. (Duct, Floor standing model.)

* For using wireless remote controller, it needs to install standard wired remote controller. (Duct, Floor standing model.)

Heat Recovery Ventilator


With todays concern for a healthy indoor environment, eco V is an integral component of HVAC system. eco V Using in the HVAC system allows contaminants to be removed quickly and effectively from the air-conditioned space.

Heat Recovery Ventilator


LGs heat recovery ventilation system, eco V, modulates the temperature and humidity of incoming fresh air to match indoor conditions. A balance is achieved between indoor and outdoor ambient, enabling the cooling or heating load placed on the air conditioning system to be reduced significantly.

(Heat Recovery ventilator)


LG Air Conditioners System

64_65

eco V
62 63 64 66
Features Installation & Maintenance Line-up Specifications

Features
High Efficiency Heat Exchanger Bypass Ventilation Strong Filter Function

Installation & Maintenance


Flexibility Installation Easy Cleaning and Changeable Filter

Supply air

High Efficiency Heat Exchanger


Efficiency and comfort is ensured by the high-efficiency energy recovery central core which recovers energy from the indoor air and transfers it to the fresh incoming air without mixing airstream.

Flexibility of Installation
Its possible to install the opposite direction of upper and lower part. It needs the only one inspection hole.

Exhaust air
Air Filter Air Filter

Outdoor air (Option)

High performance filter Deodorization filter

Indoor air
Normal installation of 2 units Reverse installation of 1 unit (Left unit)

Enthalpy Heat Exchange Mode


Damper

Bypass Mode
Damper

Bypass Ventilation
It switches automatically the ventilation mode (Enthalpy Heat Exchange Mode / Bypass Mode) according to the indoor/outdoor temperature.
Top

(Heat Recovery ventilator)

Inspection hole
Low

Low

Top

Easy Cleaning and Changing Filter


[Summer / Winter] [A change of season]

Door attached side panel and slide removable Enthalpy heat exchanger filter can be changed without additional maintenance.

LG Air Conditioners System

Air Filter

Strong Filter Function


Air filter
The air filter has collection efficiency above 80%, which means it can filter particles up to 0.3 m including tobacco of smoke and even floating particles from yellow sand.
Eco V unit Remove side panel

66_67

HEPA+Deodorization Filter (accessory)

HEPA + Deodorization filter (accessory)


The indoor air can be always kept fresh through these filters.

Yellow Sand filter (accessory)


This filter can make more comfortable and fresh environment through removing harmful to health 5~20m sandy dust over 99%.

Yellow Sand Filter (accessory)

Dust collection efficiency (%)

Pressure loss (Pa)

Remove free filter

Remove heat exchanger

High Efficiency Heat Exchanger

The LG heat recovery ventilation system, eco V is the solution for improving your indoor air quality.

Bypass Ventilation Strong Filter Function Flexibility of Installation Easy Cleaning and changeable Filter

LZ-H0106BA0
Power Supply [,V,Hz] _ 1, 220-240V, 50Hz Dimension [WxHxD]_ 204x509x509mm [8.03x23.23x23.23inch] Weight_ 24kg[52.91lb]

LZ-H0156BA0
Power Supply (, V, Hz) _ 1, 220~240V, 50Hz Dimension (WxHxD) _ 590x204x590mm (23.23x8.03x23.23 inch) Weight _ 24kg (52.91 lb)]

LZ-H0806BA0
Power Supply (, V, Hz) _ 1, 220~240V, 50Hz Dimension (WxHxD) _ 1062x365x1140mm (41.9x14.4x44.9 inch) Weight _ 67kg (147.7lb)

LZ-H1006BA0
Power Supply (, V, Hz) _ 1, 220~240V, 50Hz Dimension (WxHxD) _ 1062x365x1140mm (41.9x14.4x44.9 inch) Weight _ 67kg (147.7lb)

(Heat Recovery ventilator)

LZ-H0256BA0
Power Supply (, V, Hz) _ 1, 220~240V, 50Hz Dimension (WxHxD) _ 596x320x640mm (23.46x12.60x25.20 inch) Weight _ 27kg (59.51 lb)

LZ-H0356BA0
Power Supply (, V, Hz) _ 1, 220~240V, 50Hz Dimension (WxHxD) _ 988x273x1014mm (38.9x10.75x39.92 inch) Weight _ 45kg (99.2 lb)

LG Air Conditioners System

LZ-H1506BA0
Power Supply (, V, Hz) _ 1, 220~240V, 50Hz Dimension (WxHxD) _ 1313x737x1140mm (51.7x28.8x44.9 inch) Weight _ 146kg (321.9 lb)

68_69

LZ-H0506BA0
Power Supply (, V, Hz) _ 1, 220~240V, 50Hz Dimension (WxHxD) _ 988x273x1014mm (38.9x10.75x39.92 inch) Weight _ 52kg (114.7 lb)

LZ-H2006BA0
Power Supply (, V, Hz) _ 1, 220~240V, 50Hz Dimension (WxHxD) _ 1313x737x1140mm (51.7x28.8x44.9 inch) Weight _ 146kg (321.9 lb)

Heat Recovery Ventilator

eco V ensures the fresh enviroment in your life!

* Specifications
Item Nominal Capacity Power Supply
Step Current Power Input eco V Mode Air Flow External Static Pressure SH/H/L SH/H/L SH/H/L SH/H/L

* Specifications
Unit
CMH(L/S) ,V,Hz Amps W CMH(L/S) Pa(in.wg) % % % dBA SH/H/L SH/H/L SH/H/L SH/H/L Amps W CMH(L/S) Pa(in.wg) % % % dBA kg(lb) WxHxD Qty Size() mm(inch) EA mm(inch) EA EA EA mm(inch)

LZ-H0106BA0
100(28) 1, 220-240, 50 SUPER-HIGH/HIGH/LOW 0.32/0.3/0.28 68/60/50 100/100/90(59/59/53) 40/35/30(0.16/0.14/0.12) 78/78/80 68/68/70 58/58/60 28/26/20 -/-/-/-/-/-/-/-/-/-/-/-/-/-/-/-/-/-/Crossflow 24(52.91)

LZ-H0156BA0
150(42) 1, 220-240, 50 SUPER-HIGH/HIGH/LOW 0.36/0.36/0.35 83/80/78 150/150/100(42/42/28) 70/55/45(0.28/0.22/0.18) 75/75/79 62/62/69 55/55/59 32/30/22 -/-/-/-/-/-/-/-/-/-/-/-/-/-/-/-/-/-/Crossflow 24(52.91)

LZ-H0256BA0
250(69) 1, 220-240, 50 SUPER-HIGH/HIGH/LOW 0.55/0.5/0.34 130/115/80 250/250/180(69/69/50) 65/50/40(0.26/0.2/0.16) 80/80/85 70/70/78 64/64/68 32/28/21 -/-/-/-/-/-/-/-/-/-/-/-/-/-/-/-/-/-/Crossflow 27(59.51)

LZ-H0356BA0
350(97) 1, 220-240, 50 SUPER-HIGH/HIGH/LOW 1.40/1.33/0.9 205/195/170 350/350/210(97/97/58) 170/88/40(0.68/0.35/0.16) 83/83/87 80/80/85 78/78/83 33/28/23 SUPER-HIGH/HIGH/LOW 1.40/1.33/0.9 205/195/170 350/350/210(97/97/58) 170/88/40(0.68/0.35/0.16) -/-/-/-/-/-/33/28/23 Crossflow 45(99.20)

LZ-H0506BA0
500(139) 1, 220~240, 50 SUPER-HIGH/HIGH/LOW 1.51/1.39/1.06 260/225/200 eco V Mode 500/500/320(139/139/89) 150/60/28(0.60/0.24/0.11) 75/75/79 75/75/80 70/70/75 34/32/25 SUPER-HIGH/HIGH/LOW 1.51/1.39/1.06 260/225/200 Bypass Mode 500/500/320(139/139/89) 150/60/28(0.60/0.24/0.11) -/-/-/-/-/-/34/32/25 Crossflow 52(114.7) Step Current Power Input Air Flow

Item Nominal Capacity Power Supply


Step Current Power Input Air Flow External Static Pressure SH/H/L SH/H/L SH/H/L SH/H/L

Unit
CMH(L/S) ,V,Hz Amps W CMH(L/S) Pa(in.wg) % % % dBA SH/H/L SH/H/L SH/H/L SH/H/L Amps W CMH(L/S) Pa(in.wg) % % % dBA kg(lb) WxHxD Qty Size() mm(inch) EA mm(inch) EA EA EA mm(inch)

LZ-H0806BA0
800(222) 1, 220~240, 50 SUPER-HIGH/HIGH/LOW 2.8/2.7/2.6 405/360/320 800/800/660(222/222/183) 200/110/60(0.80/0.44/0.24) 79/79/82 70/70/75 65/65/70 36/34/30 SUPER-HIGH/HIGH/LOW 2.8/2.7/2.6 405/360/320 800/800/660(222/222/183) 200/110/60(0.80/0.44/0.24) -/-/-/-/-/-/36/34/30 Crossflow 67(147.7)
1062x365x1140 (41.9x14.4x44.9)

LZ-H1006BA0
1000(278) 1, 220~240, 50 SUPER-HIGH/HIGH/LOW 3.0/2.9/2.6 560/540/470 1000/1000/800(278/278/222) 160/90/50(0.80/0.44/0.24) 75/75/78 66/66/71 61/61/66 37/35/31 SUPER-HIGH/HIGH/LOW 2.8/2.7/2.4 560/540/470
1000/1000/800(278/278/222)

LZ-H1506BA0
1500(417) 1, 220~240, 50 SUPER-HIGH/HIGH/LOW 5.6/5.4/5.2 950/925/795 1500/1500/1200(417/417/333) 200/110/60(0.80/0.44/0.24) 79/79/82 70/70/75 65/65/70 39/37/33 SUPER-HIGH/HIGH/LOW 5.6/5.4/5.2 950/925/795
1500/1500/1200(417/417/333)

LZ-H2006BA0
2000(556) 1, 220~240, 50 SUPER-HIGH/HIGH/LOW 6.0/5.8/5.2 1020/970/860
2000/2000/1600(556/556/444)

160/90/50(0.80/0.44/0.24) 75/75/78 66/66/71 61/61/66 39/37/33 SUPER-HIGH/HIGH/LOW 5.6/5.4/4.8 1020/970/860


2000/2000/1600(556/556/444)

(Heat Recovery ventilator)

Temperature Exchange Efficiency SH/H/L

Temperature Exchange Efficiency SH/H/L

Enthalpy Exchange Efficiency

Heating(SH/H/L) Cooling(SH/H/L)

Enthalpy Exchange Efficiency

Heating(SH/H/L) Cooling(SH/H/L)

Noise Level(Sound Level, 1.5m) SH/H/L Step Current Power Input Bypass Mode Air Flow External Static Pressure

Noise Level(Sound Level, 1.5m) SH/H/L

External Static Pressure

160/90/50(0.80/0.44/0.24) -/-/-/-/-/-/37/35/31 Crossflow 67(147.7)


1062x365x1140 (41.9x14.4x44.9)

200/110/60(0.80/0.44/0.24) -/-/-/-/-/-/37/35/31 Crossflow 146(321.9)


1313x737x1140(51.7x28.8x44.9)

160/90/50(0.80/0.44/0.24) -/-/-

Temperature Exchange Efficiency SH/H/L

Temperature Exchange Efficiency SH/H/L

LG Air Conditioners System

Enthalpy Exchange Efficiency

Heating(SH/H/L) Cooling(SH/H/L)

Enthalpy Exchange Efficiency

Heating(SH/H/L) Cooling(SH/H/L)

-/-/-/-/37/35/31 Crossflow 146(321.9)


1313x737x1140(51.7x28.8x44.9)

Noise Level(Sound Level, 1.5m) SH/H/L

Noise Level(Sound Level, 1.5m) SH/H/L

Heat Exchanger Weight Dimension Duct work Supply Air Fan Exhaust Air Fan Filters

Type

Heat Exchanger Weight Dimension Duct work Supply Air Fan Exhaust Air Fan Filters

Type

590x204x590(23.23x8.03x23.23) 590x204x590(23.23x8.03x23.23) 596x320x640(23.46x12.60x25.20) 988x273x1014(38.9x10.75x39.92) 988x273x1014(38.9x10.75x39.92)

4 100(3.94) 1 Direct-Drive 1 Direct-Drive 2 Cleanable


580x10x113(22.83x0.39x4.45)

4 100(3.94) 1 Direct-Drive 1 Direct-Drive 2 Cleanable


580x10x113(22.83x0.39x4.45)

4 150(5.91) 1 Direct-Drive 1 Direct-Drive 2 Cleanable


580x10x175(23.23x0.39x6.89)

4 200(7.87) 1 Direct-Drive 1 Direct-Drive 2 Cleanable

4 200(7.87) 1 Direct-Drive 1 Direct-Drive 2 Cleanable

4 250(9.54) 1 Direct-Drive 1 Direct-Drive 2 Cleanable


1056x10x212.5(41.57x0.39x8.37)

4 250(9.54) 1 Direct-Drive 1 Direct-Drive 2 Cleanable


1056x10x212.5(41.57x0.39x8.37)

4+2

4+2

70_71

250(9.54)+350(13.77) 250(9.54)+350(13.77) 2 Direct-Drive 2 Direct-Drive 4 Cleanable


1056x10x212.5(41.57x0.39x8.37)

Qty Type Qty Type Qty Type Size(WxHxD)

Qty Type Qty Type Qty Type Size(WxHxD)

2 Direct-Drive 2 Direct-Drive 4 Cleanable


1056x10x212.5(41.57x0.39x8.37)

855x10x166(33.66x0.39x6.54) 855x10x166(33.66x0.39x6.54)

Notes:

1. eco mode - Enthalpy Heat Recovery Ventilation mode 2. Noise level : - The operating conditions are assumed to be standard. - Sound measured at 1.5m below the center the body. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Notes:

1. eco mode - Enthalpy Heat Recovery Ventilation mode 2. Noise level : - The operating conditions are assumed to be standard. - Sound measured at 1.5m below the center the body. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

& Accessory
(LG Network Solution)

V-net Line up
Remote Controller

Wireless Remote Controller

PQWRHDF0

Wired Remote Controller

Simple

PQRCUCSOC PQRCFCSOC

Standard

PQRCUSA1

& Accessory

Deluxe

PQRCUDS0 (White) PQRCUDS0B (Blue) PQRCUDS0S (Silver)

Central Controller

Simple Central Controller


(Function controller) (Scheduler)

PQCSB101S0 PQCSB101S0+PQCSC101S0 PQCSB101S0+PQCSD130A0

LG Air Conditioners System

AC Smart & 128 Unit Expansion Kit

PQCSW320A0E PQCSE440U0

72_73

ACP&AC Manager

PQCPA11A0E(Without IO) PQCPB11A0E(With IO) PQCSS520A0E(AC Manager)

BNU
( PQNFB16A1 ) PQNFB17B0 (BACnet)

V- n e t & A c c e s s o r y
74 76 84
Remote Controller Central Controller Accessory

Accessory

PDI, Remote temperature sensor, Dry contact, Cool/Heat selector, DO Kit Ventilation Kit (4Way Cassette), AHU Control kit & EEV kit, Refrigerant Charging Kit Air guide, Suction grille and canvas, Heat recovery unit, Header, Y branch

Remote Controller
Our air conditioning system can be controlled by various types of remote controllers providing general control to unique function.

Remote Controller
Wired Remote Controller Simple Wired Remote Controller Wireless Remote Controller

* Wired Remote Controller for Air-conditioner


Standard (WIDE)
Features Operating mode On / Off LED Room temp. Fan / Plasma / Swirl / Heater Vane control / Auto swing / Fan auto E.S.P function Reservation Timer function Child lock Electric failure compensation Wireless remocon receiver Master setting of indoor units T setting (For Auto Changeover) 2 Controllers to 1 indoor units
: Applicable for only MULTI V II SERIES

* Simple Wired Remote Controller


Simple
PQRCUSA1 On_Off / Fan speed / Mode / Temp. Weekly / Simple Max. 2 hours MULTI V SYNC II Features Operating mode Mode change Room temp Plasma Auto swing Child lock PQRCUCSOC On_Off / Fan speed / Mode / Temp. Cooling / Heating / Fan

PQRCUCSOC

& Accessory

PQRCUSA1

Simple for Hotel


Features PQRCFCSOC On_Off / Fan speed / Temp. Impossible Operating mode Mode change Room temp Plasma Auto swing Child lock

Deluxe
Features Operating mode Touch screen / LCD bak_light Room temp. Fan / Plasma / Swirl / Heater Vane control / Auto swing E.S.P function Reservation Timer function Child lock PQRCUDS0, PQRCUDS0B, PQRCUDS0S On_Off / Fan speed / Mode / Temp. Weekly / Simple

LG Air Conditioners System

PQRCFCSOC

PQRCUDS0 (White) PQRCUDS0B (Blue) PQRCUDS0S (Silver)

74_75

* Wireless Remote Controller


Features Operating mode Room temperature checking Chaos swing / Jet cool On_Off timer Sleep mode auto Main / Sub setting of indoor units T setting (for Auto Changeover)
: Applicable for only MULTI V II SERIES

* Wired Remote Controller for


Standard
Features On / Off LED Ventilation mode setting Rapid ventilation Power saving ventilation Reservation Electric failure compensation Child lock PZRCUSB0 Weekly / Simple Max. 2 hours Plasma / Heater / Humidifier Operating air volume

PQWRHDF0 On_Off / Fan speed / Mode / Temp. MULTI V SYNC II

PQWRHDF0

PZRCUSB0

Optional function

Simple Central Controller


A central controller for managing small sites Control up to 16 indoor units PQCSW320A0E PQCSB101S0 PQCSE440U0

AC Smart & 128 Unit Expansion Kit


For the mid sized buildings up to 64 or 128 indoor units can be controlled and monitored by touch screen central controller. Its possible to control and monitor the air conditioning system through web access, anywhere with computer.

Features Max. no of indoor units Individual control Lock function Mode change Malfunction indicator Dimension(mm) Power(V)

PQCSB101S0 16 indoor units On_Off Control Total / Individual Cooling / Heating LED lamp 120 x 120 x 20 DC 10V

& Accessory

Function Controller & Scheduler


It is possible to control, monitor and schedule the operation of indoor units by using these controller in company with a simple central controller PQCSB101S0 PQCSC101S0 PQCSB101S0 PQCSD130A0
*128 Indoor unit Expansion Kit: PQCSE440U0 *DO Kit : PQNFP00T0

LG Air Conditioners System

Combination
RS485 1.25mm2 X 2C (shield)
MULTI V PLUS II MULTI V SYNC II MULTI V SPACE II MULTI V MINI

Features Max. no of indoor units Individual control Lock function Mode change Malfunction indicator Schedule Dimension(mm) Power(V)

PQCSB101S0+PQCSC101S0 16 indoor units On_Off / Fan speed / Mode / Temp. Total / Individual Cooling / Heating / Fan Error display on LCD (120x120x20)+(70x120x14) DC 10V

PQCSB101S0+PQCSD130A0 16 indoor units On_Off / Fan speed / Mode / Temp. Total / Individual Cooling / Heating / Fan Error display on LCD Weekly (120x120x20)+(120x133x20) DC 10V AC Smart PQCSW320A0E

PI485

AC220V
DC Comm, Line

MULTI V PLUS MULTI V SYNC MULTI V SPACE

76_77

PMNFP14A0 (Max. 16 Indoors) PMNFP14A1 (Max. 48 Indoors) Single A, MULTI

PMNFP14A0

Single constant PHNFP14A0 (Ceiling & Floor, Duct) PSNFP14A0 (CST, RAC)

* 1 Function controller combined with max. 8 simple central contollers.

Eco-V PHNFP14A0

ACP (Advanced Control Platform)


Through embedded web control function in ACP one can control and monitor various functions of air-conditioner such as temperature setting, schedule, peak power control, etc. PQCPA11A0E (Without IO) PQCPB11A0E (With IO)

Application

ACP&AC Manager
AC Manager is suitable for large site because AC Manager is the S/W that can control Max. 16 ACP (Max.4,096 indoor units). PQCPA11A0E (Without IO) PQCPB11A0E (With IO) PQCSS520A0E (AC Manager)

Application
Multi Area Management
The product specially designed for multi area management. -Central control & monitor Max. 4,096 indoor units & Max.16 ACP

& Accessory

Max. 4,096 Indoor

Korean reference site.

ACP

AC Manager

LG Air Conditioners System

Combination

RS485 1.25mm2 X 2C (shield)

MULTI V PLUS II MULTI V SYNC II MULTI V SPACE II MULTI V MINI

78_79

AC Manager PQCSS520A0E

LAN

PI485

AC220V DC Comm, Line

Features
ACP PQCPA(B)11A0E
Max.no. of indoor units Control / Monitoring Schedule management Lock function Temperature range restriction Temperature limit function Auto Changeover function History function Peak control PDI monitoring Interlocking function Printing function 256 indoor units Temperature Monitoring Need of PDI -

MULTI V PLUS MULTI V SYNC MULTI V SPACE

HUB

PMNFP14A0 (Max. 16 Indoors) PMNFP14A1 (Max. 48 Indoors)

ACP (without IO) + AC Manager PQCPA11A0E+PQCSS520A0E


4,096 indoor units(16 ACP) Mode/Temp/Fan speed/Schedule Monitoring & Error history Need of PDI System setting, History, PDI

ACP (with IO) + AC Manager PQCPB11A0E+PQCSS520A0E


4,096 indoor units(16 ACP) Mode/Temp/Fan speed/Schedule Monitoring & Error history Need of PDI Fire sensor, Door sensor, Motion sensor... System setting, History, PDI PHNFP14A0 (Ceiling & Floor, Duct) PSNFP14A0 (CST, RAC) Internet PMNFP14A0 Single constant Single A, MULTI

PI485
PHNFP14A0

Eco-V

PDI (Power Distribution Indicator)


This device is an indicator for power consumption of the multi type air-conditioner used for common power line.

DO Kit
Do Kit is connected between ACP (AC Smart) and external devices. So ACP(AC Smart) can start and stop external devices such as light, pump, motor, etc.

PQNUD1S00

PQNFP00T0

AC Smart

Web Access

7" Touch Screen / GUI Direct Connect to LGAP

Easy Control
-Function Lock -Lock Schedule

Cooling Heating

- Remote Management Combination - Error Report via E-mail

Features
- Accumulated total power consumption indicated - Accumulated / Current power consumption of each indoor units indicated - Accumulated power consumption by month indicated - Max connectable no. of indoor units : 48 indoor units - 1 PDI per 1 outdoor unit - Power failure-proof function : Data back up on EEPROM even if power turns off - Connectable to PC based central controller - Simple connection with the remote metering system (RS485 approach)

Screen Saver
BUS _ A BUS _ B

-Automatic H/C Changeover -Temperature Limit -Temperature Range Multi Language Restriction -English, Italian, Spanish, -Time Limit Control French, German, Dutch, RussianPower of Load

Comfort Control

DI RS485 Easy Software Upgrade by USB Operation Report


ACP or AC Smart
Light Pump Motor etc

USB
L

DO Kit

& Accessory

Combination
Digital WHM (Local purchase)

-Operating Time, Percentage, History

Emergency
128 Indoor units Expansion Kit

LGAP
Multiple Local Controllers
-Master / Slave
Remote Controller Restriction Automatic Setting A/C and Vent.

AC220V

Emergency Interlock
-Forced Off

LG Air Conditioners System

Pulse output (1,2, 4,6,8,10W/pulse)


AC 200V~240V 50/60Hz PQNUD1S00

PI485 RS485

80_81

or

* In the case of MULTI V II SERIES, dont need PI 485

BNU-LW Gateway

(Building Network Unit-

BNU-BAC Gateway

(Building Network Unit- BACnet)


Easy interface between BMS and LG air conditioner - Independence of BMS under the standard BMS
: Operation system based on BACnet Service.

Easy interface between BMS and LG air conditioner - Independence of BMS under the standard BMS
: Operation system based on LNS ( network service)

- No network installation needed PQNFB16A1 - Very widely applicable protocol( ) PQNFB17B0

Features
- Connection to using LONTALK protocol and LG Air-conditioner protocol - Process ability 64 units( including indoors and ventilators) Valid address for each unit : 0x00 ~ 0x3F - Self installation verification function using internet (Web server included) Setting gateway Diagnosis of communication status on LG Air-conditioner network - Connection to remote total management system (LG system)
Controlling On/Off command Operation mode setting Fan speed setting Lock setting Air flow setting Set temp. setting Monitoring items On/Off status report Operation mode status report Fan speed status report Lock status report Air flow status report Set temp. status report Error status report User mode status report
(for only ventilator)

Features
- Through embedded web control function in BACnet one can access the airconditioner and external devices through internet. - It can control 256 indoor units. ( A/C or Ventilator ) - External devices such as fire alarm, motion detector can be connected to gateway and their function can be interlinked with airconditioner operation.
Controlling On/Off command Operation mode setting Fan speed setting Lock setting Air flow setting Set temp. setting User mode setting (for only ventilator) Current space temp. status report Error status report User mode status report
(for only ventilator)

Monitoring items On/Off status report Operation mode status report Fan speed status report Lock status report Air flow status report

User mode setting (for only ventilator) Current space temp. status report

& Accessory

Combination

Combination BACnet
LON comm. line BMS system

LG Air Conditioners System

Network

Network

BACnet comm. line

BMS system

Lighting control

Remote checking

Utility control

Lighting control

Remote checking

Utility control

Indoor unit : Max. 64 units (Air-conditioner & ventilation) Other LON devices Indoor address : 00 ~ 3F
MULTI V PLUS II MULTI V SYNC II MULTI V SPACE II MULTI V MINI MULTI V PLUS MULTI V SYNC MULTI V SPACE

Indoor unit : Max. 256 units (Air-conditioner & ventilation) Other BACnet devices Indoor address : 00 ~ FF

82_83

RS485 1.25mm2 X 2C (shield)

RS485 1.25mm2 X 2C (shield)

MULTI V PLUS II MULTI V SYNC II MULTI V SPACE II MULTI V MINI PI485 MULTI V PLUS MULTI V SYNC MULTI V SPACE

PI485

PQNFB16A1

BNU-LW

PMNFP14A0 (Max. 16 Indoors) PMNFP14A1 (Max. 48 Indoors) PI485 Single A, MULTI

PMNFP14A0 (Max. 16 Indoors) PMNFP14A1 (Max. 48 Indoors)

BNU-BAC PQNFB17B0

PI485

Single A, MULTI

or
Simple central controller AC Smart

PMNFP14A0 PI485 PHNFP14A0


Outdoor unit Indoor unit

Eco-V

or
Simple central controller AC Smart

PMNFP14A0 PI485
Outdoor unit

Eco-V PHNFP14A0
Indoor unit

LGAP applied Air-conditioner

LGAP applied Air-conditioner

Remote Temperature Sensor


It can help to detect the exact room temperature at the optimal position. Model applied to Cassette, Duct type. Part supplied PQRSTA0
- Remote temperature sensor - Cable (15m) - Manual

Cool/Heat Selector
This switch enables selection of heating, cooling or fan mode. So it can prevent that cooling & heating mixing error occurs during the change of season. PRDSBM

Features Wiring diagram


1. Wire to the control box in the indoor unit by removing the existing thermistor and connect the extension cable its place. 2. Cut the extension cable to the appropriate length and connect the screw terminal of the remote sensor. 3. In the case of wired remote controller installed, set the temperature sensing slide s/w at MAIN mode.
Extension cable Connector

- Indoor unit control without central controller - Select operation mode : Cooling, Heating, Fan mode - Mode lock for cooling & heating mixing error-proof during the change of season.

Screw terminal connection Indoor unit

Combination
Fan Mode Mode Change

Cooling

Heating

Remote temperature sensor

& Accessory

Dry Contact module


It is connected between indoor units and external device, so it can be used for various purpose.

* PRDSBM is applicable for only MULTI V II Series.

Ventilation Kit (4Way Cassette)


Fresh air can be supplied from outside through this ventilation kit.
LG Air Conditioners System

PQDSB(A) / PQDSB1 / PQDSBC

PTVK410

PTVK420

PTVK430

Features
Contact point Power input Voltage / Non voltage input On_Off control Lock / Unlock Fan speed setting Thermo off Energy saving Expected temperature setting Error Monitoring Operation monitoring

Accessory
PQDSA(B) 1 contact point AC 220V from outside power source

Dimension

84_85

PQDSB1 1 contact point AC 24V from outside power source

PQDSBC 2 contact points DC 5V&12V from indoor unit PCB


Installation Bracket Bolt Screw

Models applied to
Ceiling Cassette - 4Way (24k ~ 48k Btu/h)

* PQDSBC is applicable for only MULTI V II Series.

AHU Control Kit & EEV Kit


Fresh air can be supplied from outside connecting AHU to Multi V Plus II.

Refrigerant Charging Kit

PRCKA0

PRLK048A0

PRAC1

Specifications
Model Name Control Kit EEV Kit PRCKA0 PRLK048A0 Weight(kg) NET 2.23 3.1 Gross 3.6 3.6 W 280 404.2 Dimension(mm) H 135 83 D 280 217 POWER 220~240V / 50HZ / 1Pha

Procedure
1. Arrange manifold, refrigerant charging kit, refrigerant vessel and scale 2. Connect manifold to the gas pipe service valve of outdoor uint as shown in the figure. 3. Connect manifold refrigerant charging kit. Use designated refrigerant charging kit. If designated refrigerant charging kit isnt used, the system may get damaged. 4. Connect refrigerant charging kit and refrigerant vessel. 5. Purge hose and manifold. 6. After 568 is displayed, open the valve and charge the refrigerant

Selection of evaporator
When selecting evaporator, Change Option PCB in EEV kit according to below table (Basic Option PCB is for 36k Btu/h )
Option PCB P/No EBR52358907 EBR52358908 EBR52358909 EBR52358910 EBR52358911 EBR52358912 Capacity (Btu/h) 28k 36k 42k 48k 76k 96k Allowed heat exchanger Volume (dm3/hr) 1.22~1.53 1.53~1.91 1.91~2.14 2.14~2.67 3.06~3.82 3.82~4.78 Allowed heat exchanger capacity (kW) 7~9 9~11 11~13 13~16 20~24 25~31 LG Air Conditioners System
(Main PCB)
Capacity setting 'Option PCB'

Application
Detail

Dimension

& Accessory

Manifold

202 133

Refrigerant Charging Kit (PRAC1)

* Saturated Suction Temperature (SST) = 6C, SH (Superheat)=5k, Air Temperature = 27C DB / 19C WB

Wiring diagram
Single Pipe Themistor
Return Air

Refrigerant

69

86_87

Error contents about auto refrigerant charging function


Supply Air

1. 329: Temperature range error (In case that indoor unit or outdoor unit is out of range) 2. 339: Low pressure descent error (In case the system runs at low pressure limit for over 10 minutes) 3. 349: Rapid refrigerant inflow (In case the liquid refrigerant flows in because of not using designated refrigerant charging kit) 4. 359: Instability error (In case the high/low pressure target doesnt get satisfied for some time after the starting operation)

Air Guide
Used to control the direction of air discharge by outdoor unit. Converts vertical discharge into horizontal discharge.
(2 Pipe-connection)

Heat recovery unit


(Applied to MULTI V SYNC II R410A)
PRHR020

Max. 4 indoor units can be connected by module design. Due to the automatic search algorithm for piping detection, easy installation and effectiveness is improved. Subcooling cycle in HR unit makes the system efficiency maximum.

PQAGA

Application

Dimension

(3 Pipe-connection)

PRHR030

(4 Pipe-connection)

PRHR040

Combination

Outdoor unit Indoor unit

Suction Grille and Canvas


High flexibility for a wide variety of applications PBSGB30 / PBSGB40 PBSC30 / PBSC40

Specifications
PRHR020 Max. connectable number of indoor units Max. connectable capacity of indoor units (Per port/unit) Nominal Input Net weight Dimensions (WxHxD) Piping connections Indoor unit unit liquid gas low pressure high Pressure cooling heating kW W W kg mm mm(inch) mm(inch) mm(inch) mm(inch) mm(inch) /V/Hz 9.52(3/8) 19.05(3/4) 19.05(3/4) 26 26 19 801x218x617 2 PRHR030 3 14.1 / 47 40 40 20 801x218x617 9.52(3/8) 15.88(5/8) 12.7(1/2) 28.58(1 1/8) 22.2(7/8) 1/220 ~ 240/50 12.7(1/2) 28.58(1 1/8) 22.2(7/8) PRHR040 4 40 40 21

& Accessory

Features
- High external static pressure facilitates unit use with flexible ducts of varying lengths. - When using suction panel, unit requires only 270mm of ceiling space. - Blends unobtrusively with any interior decoration.

LG Air Conditioners System

801x218x617

Models applied to
- Ceiling concealed duct _ Built-in type
Capacity (Btu/h)

Outdoor liquid

Power supply
18k 24k

88_89

Type Grille Canvas

Model
PBSGB30 PBSGB40 PBSC30 PBSC40

7k

9k

12k

15k

Dimension
C A B A PBSGB30 PBSGB40 910 1188 B 359 359 C 56 56 PBSC30 PBSC40 B A 821 1100 B 274 274 C 42~250 42~250 C

Header for connection of indoor units


* MULTI V PLUS II, MULTI V MINI, MULTI V SPACE II
(unit:mm) (unit:mm)

Y Branch pipe for connection of indoor units


* MULTI V PLUS II, MULTI V MINI, MULTI V SPACE II
(unit:mm) (unit:mm)

Model 4 branch ARBL054

Gas Pipe

Liquid Pipe

Model 7 branch ARBL107

Gas Pipe

Liquid Pipe

Model

Gas Pipe

Liquid Pipe

Model

Gas Pipe

Liquid Pipe

If you need a highly efficient air conditioning system in your building, MULTI V is the right choice for you.

ARBLN01621

ARBLN07121

7 branch ARBL057

10 branch ARBL1010

NEO Plasma Air Purifying System

Auto Clean

ARBLN03321 4 branch ARBL104 10 branch ARBL2010

ARBLN14521

Jet Cool

Sleep Mode Auto Operation

Y Branch pipe for connection of outdoor units


* MULTI V PLUS II (2 Outdoor units)
(unit:mm)

* MULTI V SYNC II
(unit:mm)

Model

Low Pressure Gas Pipe

Liquid Pipe

High Pressure Gas Pipe

Healthy Dehumidification

Auto Restart

* MULTI V PLUS II (3 Outdoor units)


(unit:mm)

& Accessory

Model

Connection of Gas Pipe

Connection of Liquid Pipe

Model

Connection of Gas Pipe

Connection of Liquid Pipe

ARBLB01621

(Heat pump only)

Hot Start

4-Way Air Deflection

ARCNN20

ARCNN20 ARBLB03321 LG Air Conditioners System

( Wired remote ) controller only


Soft Dry Operation Mode

Child Lock Function

Swirl Swing

ARCNN30

( Wired remote ) controller only


Two Thermistor Control

Weekly Program

ARBLB07121

90_91

* MULTI V SYNC II (2 Outdoor units)


(unit:mm)

* MULTI V SYNC II (3 Outdoor units)


(unit:mm)

Model

Low Pressure Gas Pipe

Liquid Pipe

High Pressure Gas Pipe

Model

Low Pressure Gas Pipe

Liquid Pipe

High Pressure Gas Pipe

Low Standby Power

( Wired remote ) controller only


Changable Panel

ARBLB14521 ARCNB20 ARCNB20

( Wired remote ) controller only


SYNC ( MULTI Vonly ) model

Group Control

ARCNB30

Auto Changeover

Second Remote Control