Most advanced field team = Best after-sales services 2500 field engineers spread across all circles

Description
Capacity Multi Phase Logic Range of 5 to 50 KVA.

Specifications
PIU will work on 1Phase, 2phase or 3Phase. Input voltage range for single phase 140280V (L-N). Input voltage range for two phases 240480V (L-L)- Normal Range. Input voltage range for two phases 155480V (L-L). Wider Range. CNC Fabricated rack, using CRC Sheet duly powder coated, maximum required foot print area is 600(W) x 500(D) mm in case of Indoor application. IP 21 for Indoor Application & IP55 for Outdoor Application . The equipment will ensure IEC 60950 safety standards . All material & workmanship will be of professional quality to ensure MTBF requirement. The MTBF of the PIU is more than 70000 hrs. CE, Tested for safety, EMI/RFI, ERTL compliance. ? High-Speed micro controller. ? RMS for all voltage & current . True ? the inputs to the measurement board will be duly protected against All surge as per IEEE-62.41 ? measurement circuit will be rated at least twice of the maximum The input range, each independent for AMF & module. Real time & date-programmable. Last 500 events. For PC interface to adjust the critical data and unload the alarms, This Port will be used for configuration of PFCs. ? be able to read the energy from Meter via 485 port. Will ? be able to measure the DG energy (Cumulative KWH & Hrs). Will ? be able to measure the EB energy (Cumulative KWH & Hrs). Will ? be able to store data of DC energy meter fetched from power plants Will of cell-sites of the network. ? will be equipped with suitable GPRS modem / GPRS DTU and able to PIU process the data. ?will be able to connect via RS485 port to DC power plants for energy It meter reading or with any other specific equipment. ? above reading will be extendable to NOC / TOC through GPRS Modem. All Local storage of DC Energy will be available if meter goes faulty. Controller will be able to store energy data / performance data and alarms / events for last 500 events. ? communication will follow TOC protocol. Data

Mechanical IP Protection Safety MTBF Compliance

Micro Controller

Time Event Logs RS 232 Port (for ACME use only)

Energy

Data Transfer

Line Conditioning Module Type Power Rating Micro Controller based, true RMS, static line conditioner . As Per Requirement, rated at 100% capacity. Temperature rise of the device and transformers will be as per class F specs. Facility to operate on Voltage range - 240-480 Normal L-L, 155-480 Wide L-L / 140 280 L-N. 220 V +/- 10%.

Rated input voltage range Rated Output Voltage

Input Frequency Range Total Harmonic Distortion (THD) %of Voltage/Current Efficiency at rated load and rated input Voltage & 50 degree temperature Dynamic response time Response Time Protections: Voltage protection at incoming power input Voltage protection at MODULE Insulation Inter winding capacitance Input/Output isolation Winding In-rush Current Temperature Humidity Delays: DG on load

47-53 Hz. <3%. >97%. 400 V/micro-sec. <10 ms.

a) High Voltage Disconnect (HVD) 485/285V after 10 milliseconds. b) Low Voltage Disconnect (LVD) 240/155 /140V after 5 seconds. a) Input side HVD 245/485V; LVD 240/155 /140 V. b) Output side - HVD 250V (immediate); LVD 190V after 3 sec . >1000 mega ohms. <10 NF. 6KV. Double wound with copper foil shielding. 110 % for 60 Seconds. (-5 to 55 deg). RH 95% (max.).

After DG starts and supply is healthy.

Blackout delay DG cooling time DG start attempts

10 seconds between mains and DG contactor changeover. 5 minutes. Three attempts with delay between attempts ( 40 -40 -40 sec )(settable). After three very short mains restoration 10-10-20 minutes, DG will run for 2hrs (settable) continuously. Settable from 0 to 30 seconds. Automatic DG battery, SMPS charger with constant current charging facility (12V) . Charger suitable for charging the SMF/Conventional battery of upto150AH. Provision of Auto manual mode selection. Photoelectric type -2 No, Sensitivity 3% / ft.

DG Lock time Stop Command duration Battery charger & DG controller unit

Smoke Detector:

AC distribution unitMains MCCB, DG MCCB Load Distribution Aviation light- ( -48 Volt ) with inbuilt functional feature Auto Phase selector Of suitable ratings as per Product Capacity. Of suitable ratings for SMPS Rectifiers, Aircons, Lighting etc. as per Product Capacity. 6A. The PIU will be equipped with auto phase selector which will select any two best phase or single phase out of 3 Phase. There will be electrical/mechanical interlock between contactors to avoid short circuit in case of electronic failure. Factory set ("ON" at 38C and "OFF" at 36C). Mains/DG status, DG accumulated hours, DG voltage, DG Energy Measurement (DG KWH). Input Voltage, Output voltages for line conditioning module, Mains Energy Measurement (EB KWH). Battery running hrs (Accumulated). Mains ON, DG ON, Smoke/ Fire Alarm, Over Load, MODULE fail, Fuel Low, DG fail to start, DG fail to stop, Alternator fail, LLOP, Mains Fail, DG battery low, HCT/HWT, High Shelter temperature. Alarms will be extended to NOC / TOC through changeover contact (both 'NO', NC).
Mains fail, Door open/ Intruder, Low fuel level, Smoke/Fire, Load on DG, AC fail, Shelter high temperature, Rectifier fail, Low battery voltage, DC fuse fail, Common fault -- LLOP/Alt fault/HCT/HWT/V belt/Dg fail to start/DG fail to stop, Standard setting Settings in the PIU can be changed through Laptop only. Two types of separate logics are available to control 2 Nos. DGs & cater the Loads. 1. Dual DG Logic: This product controls two nos. of DGs & ensures their running in Swap mode of operation & also ensures switching ON another DG in case of any DG goes faulty. 2. Sequential DG Logic: This product controls two dissimilar capacity DGs & takes decision to run Higher Capacity, Lower Capacity or both DGs as per Load conditions. This is more suitable for sites where DG capacity up gradation is required.

Set point-for high temperature alarm DG set measurements Mains measurements Battery measurements LED Indications:
List of potential free dry contacts

Dual DG/Sequential DG Logics (Optional)

ACME TELE POWER LIMITED


Plot No. 2, Sector-34,E.H.T.P., Gurgaon 122001 (Haryana) India Ph: + 91 124 4817000, 4817777 Fax : + 91 124 4817111 E-mail: info@acme.in Website: www.acme.in