Sunteți pe pagina 1din 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

5.1 Axial Flow Fans


Contents

Novax Axial Flow Fans ACA - ACN ACW - ACD - ACG - ACP . . . . . . . . . . 3
One Rotor Several Fan Types . . . . . . . . . . . 3 ACA ACN ACW ACD . . . . . . . . . . . . . . . 3 ACG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ACP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Two types of blades . . . . . . . . . . . . . . . . . . . . . 3 Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Corrosion Classification . . . . . . . . . . . . . . . . . . 3 Adjustment of Blade Angles. . . . . . . . . . . . . . . 3

Accessories ACA Mounting foot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Accessories ACN Mounting foot, horizontal . . . . . . . . . . . . . . . . . . . . . . 23 Accessories ACG and ACP Mounting foot and diffuser . . . . . . . . . . . 24 Accessories ACG and ACP Mounting foot and diffuser . . . . . . . . . . . . 25 Accessories ACA, ACN, ACG and ACP . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Accessories ACA, ACN, ACG and ACP . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Accessories ACD, ACW . . . . . . . . . 28 Accessories ACD, ACW . . . . . . . . . 29 Accessories ACD, ACW . . . . . . . . . 30 Accessories ACD, ACW . . . . . . . . . 31 Acoustic diffuser - YAD. . . . . . . . . . . 33

Control of Speed by Means of Frequency Conversion . . . . . . . . . . . . . . . . . . . 4 Type Descriptions of ACA-ACD . . . . 5


ACA ACD for Installation in Ducting . . . . . . . 5 Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Type Descriptions of ACN-ACW . . . . 6


ACN ACW for Installation in Ducting. . . . . . . 6 Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Type Descriptions of ACG and ACP . . . . . . . . 7

Novax Combination key type ACA ACD . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Novax Combination key type ACN ACW . . . . . . . . . . . . . . . . . . . . . . . . . 8 Novax Combination key types ACG and ACP . . . . . . . . . . . . . . . . . . . . . . . 9 Performance Curves. . . . . . . . . . . . . 10
ACA ACD 60 Hz . . . . . . . . . . . . . . . . . . . . . 10 ACN ACW 60 Hz. . . . . . . . . . . . . . . . . . . . . 11 ACG 60 Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . 12 ACP 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Sound conditions. . . . . . . . . . . . . . . . 33 Technical Data for Accessories . . . . 34 Installation corrections . . . . . . . . . . . 36 Run up time of axial flow fans . . . . . 37 Smoke Extract Fans. . . . . . . . . . . . . . 38 Pump Room Fan type HGP . . . . . . . . 39 Product and Application 39
Range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 Number of Hub Diameters . . . . . . . . . . . . . . .39 Number of Blades . . . . . . . . . . . . . . . . . . . . .39 Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39

Dimension Sketches. . . . . . . . . . . . . 14
ACA Dimension sketches . . . . . . . . . . . . . . 14 ACD Dimension sketches . . . . . . . . . . . . . . 16 ACD Dimension sketches . . . . . . . . . . . . . . 17 ACN Dimension sketches . . . . . . . . . . . . . . 18 ACG and ACP Dimension sketches . . . . . . 19 ACW Dimension sketches . . . . . . . . . . . . . 20 ACW Dimension sketches . . . . . . . . . . . . . 21

Materials and Surface Treatment . . . . . . . . . . . . . . . . . . . . . . 39


Corrosion Classification . . . . . . . . . . . . . . . . .39 Duct on inlet and free outlet . . . . . . . . . . . . . .39 Description . . . . . . . . . . . . . . . . . . . . . . . . . . .40

Accessories . . . . . . . . . . . . . . . . . . . 22

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice MU 13073 0205 5.1 Axial Flow Fans Page 1 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax HGP Dimensions. . . . . . . . . . 41 Novax axial flow fan type HGP . . . . 42 Novax axial flow fan type HGP . . . . 43 Novax axial flow fan type HGP . . . . 44 Novax axial flow fan type HGP . . . . 45 Novax axial flow fan type HGP . . . . 46 Novax axial flow fan type HGP . . . . 47 Novax axial flow fan type HGP . . . . 48 Novax axial flow fan type HGP . . . . 49 Novax axial flow fan type HGP . . . . 50 Novax axial flow fan type HGP . . . . 51 Novax axial flow fan type HGP . . . . 52 Novax axial flow fan type HGP . . . . 53 Novax axial flow fan type HGP . . . . 54 Novax axial flow fan type HGP . . . . 55 Axial Flow Fan type HGC . . . . . . . . . 56 Product and Application 56
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Materials and Surface Treatment. . . . . . . . . . 56 Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Performance Curves HGC-250/160 57

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 2 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax Axial Flow Fans ACA ACN - ACW - ACD - ACG - ACP
The Novax fans are compact and robust, massproduced adjustable pitch axial flow fans. Novax is suited for a large number of air handling applications for marine installations. Distinguishing features of Novax are space economy, easy installation and high reliability.

ACP
For wall mounting with direct inlet and outlet.

Two types of blades


N.B.

The rotors are available with blades of glass fibre reinforced polyester (GRP) or aluminium. However, rotors with hub diameters = 403 and = 578 mm are only available with blades of aluminium. The two blade types have identical performance characteristics. In the temperature range of -20 C to +40 C the fans are normally equipped with GRP blades which are lighter and more resistant to corrosion. In the temperature range of -20 C to -40 C and +40 C to +70 C both blade types can be used, however, at reduced speeds and with special grease in motors. In the temperature range of 70 C to 100 C solely aluminium blades are used and at reduced speeds.

One Rotor Several Fan Types


blades.

The Novax rotor (the impeller) consists of two assembled hub discs with cavities to house the The rotor is provided with a hub boss for mounting onto a motor shaft. The blades of the rotor can be factory adjusted to any angle between 25 and 70 , dependent on size and speed. The rotor and motor assembly can be mounted in many different fan casing profiles suitable for a variety of applications.

Motors

The motors are asynchronous motors. Types ACN, ACG, ACW and ACP have flanged motors, whereas type ACA and ACD has a foot-mounted motor.

Corrosion Classification
The Novax fans are as standard designed for operation in unheated, low-corrosive environments according to the international standard EN ISO 12944-2, class 2 (low).

ACA ACN ACW ACD


For installation in ducting.

Adjustment of Blade Angles

The blade pitch may be adjusted to obtain different performances. In that case the motor output should be known and the rotor carefully aligned and balanced before starting. Please contact YORK Novenco before any such adjustment.

ACG
For duct connection with direct inlet.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 3 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Control of Speed by Means of Frequency Conversion


The performance curves on pages 10 13 show the nominal speeds for motors of 50 and 60 Hz and with speed control by frequency conversion with the maximum speeds indicated in the table below. Thus Novax fans are a serious alternative to cenThe brochure Blade angle tool for adjustment of blade angle is available on request. The Novax computer calculation program ensures accurate selection of type and size in view of air quantity, pressure, operating economy and sound. The program can be ordered on diskettes. trifugal fans with inlet vane control in ventilating and air conditioning systems with varying air quantity requirements. Both investment, operating costs as well as space requirements are smaller for Novax fans with the same performance. This is mainly due to falling prices of frequency converters, so even small installations can be economically speed controlled by means of frequency conversion. Max. speed of Novax rotors at 20C *
Hub diameter 160 230 280 330 380 403 578 * Reduced max. speed at higher or lower temperature. Rotor diameter 250
3865

315
3865

400
3865 4000

500
3865 4000 4012 3977

560
3865 3755 3686 3674

630
3575 3536 3448 3397

710
3275 3230 3215 3097

800
2980 2930 2973 2859

900

1000

1120

1250

1400 1600

2571 2660 2651 2179 2128 2324 2025 1957 1885 1804 1730 1685 1575 1595 1410

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 4 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Type Descriptions of ACA-ACD


ACD ACA

ACA ACD for Installation in Ducting


ameters from 160 to 578 mm.

The fan casing incl. of motor suspension is hot-dip galvanized. The fan casing is provided with an inspection door. The rotor unit is mounted directly on the motor shaft end. The direction of air flow for ACA is blade motor. The motor is a foot-mounted motor mounted on the outlet side and provided with electric cable extended through the fan casing to a terminal box for electrical connection. Pitch circle diameter of flange, number of holes and hole size as standard according to EUROVENT 1/2 for type ACA and according to DIN 24154 for ACD.

The series comprises 14 sizes with impeller diameters ranging from 250 to 1600 mm and 7 hub di-

Capacities

Air quantities from 0.1 to 55 m 3 /s and total pressures up to 1800 Pa. ACA casing consists of a short rolled welded steel tube with beaded flanges. ACD consists of a cylindrical casing with connecting flanges at both ends. The fan casing has a welded motor suspension of sheet steel.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 5 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Type Descriptions of ACN-ACW


ACN ACW

ACN ACW for Installation in Ducting


ameters from 160 to 578 mm.

The fan incl. of motor suspension is hot-dip galvanized. The direction of air flow for ACN and ACW is blade motor. The motor is a flanged motor mounted on the outlet side and provided with an electric cable extended through the fan casing to a terminal box for electrical connection. The fan casing is provided with an inspection door. Pitch circle diameter of flange, number of holes and hole size as standard according to EUROVENT 1/2 for type ACN and according to DIN 24154 for ACW.

The series comprises 14 sizes with impeller diameters ranging from 250 to 1600 mm and 7 hub di-

Capacities

Air quantities from 0.1 to 55 m3/s and total pressures up to 2000 Pa. The fan consists of a cylindrical casing with connecting flanges at both ends. The fan casing has a welded motor suspension of sheet steel which at the same time serves as a down-stream guide vane arrangement, ensuring an extremely high efficiency. The rotor unit is mounted directly on the motor shaft end.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 6 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Type Descriptions of ACG and ACP

Capacities Air quantities from 0.1 to 55 m3/s and total pressures up to 2000 Pa. The fan consists of a tubular casing with a bell mouth inlet for direct air intake and an outlet flange for duct connection. The rotor unit is mounted at the inlet with the motor facing the air intake. The direction of air flow for ACG is motor blade. The inlet is provided with a wire guard. On the outlet side of the rotor a downstream guide vane arrangement with a core is mounted ensuring a very high efficiency.

ACG for Duct Connection The series comprises 14 sizes with impeller diameters ranging from 250 to 1600 mm and 7 hub diameters from 160 to 578 mm.

The motor is a flanged motor with electrical connection in the terminal box. Pitch circle diameter of flange, number of holes and hole size as standard according to EUROVENT 1/2.

Capacities Air quantities from 0.1 to 50 m3/s and total pressures up to 1600 Pa. The fan consists of a short tubular casing with a bell mouth inlet for direct air intake and an outlet flange for duct connection. The rotor unit is mounted at the inlet with the motor facing the air intake. The direction of air flow for ACP is motor blade. The inlet is provided with a wire guard. ACP is used for direct exhaust through wall. ACP for Wall Mounting The series comprises 14 sizes with impeller diameters ranging from 250 to 1600 mm and 7 hub diameters from 160 to 578 mm. The motor is a flanged motor with electrical connection in the terminal box. Pitch circle diameter of flange, number of holes and hole size as standard according to EUROVENT 1/2.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 7 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax Combination key type ACA ACD


Hub diam.
160

Motor size (foot-mounted)


71 80 90 71 80 90 100 71 80 90 100 112 80 90 100 112 132 90 100 112 132 160 180 112 132 160 180 132 160 180 200 225 250 280

250

315

400

500

560

630

Rotor diameter 710 800 900

1000

1120

1250

1400

1600

230

280

330

380

403

578

Novax Combination key type ACN ACW


Hub diam.
160

Motor size (spec.motor)


71 80 90 71 80 90 100 71 80 90 100 112 80 90 100 112 132 90 100 112 132 160 180 112 132 160 180 132 160 180 200 225 250 280

250

315

400

500

560

630

Rotor diameter 710 800 900

1000

1120

1250

1400

1600

230

280

330

380

403

578

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 8 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax Combination key types ACG and ACP


Hub diam.
160

Motor size (flanged)


71 80 90 100 71 80 90 100 71 80 90 100 112 80 90 100 112 132 90 100 112 132 160 180 112 132 160 180 132 160 180 200 225 250

250

315

400

500

560

630

Rotor diameter 710 800 900

1000

1120

1250

1400

1600

230

280

330

380

403

578

Accessories
ACA ACD Horizontal mounting foot Vertical mounting plate Inlet cone with wire guard Counter flange Duct spigot Welding connection Flexible connection Silencer with or without pad Acoustic diffuser with pad Hood Damper Wire guard in casing (pressure side) Wire guard flange (pressure side) Brass lining Anti-vibration mountings Diffuser for outlet Downstream guide vane arrangement 3 1. 2. 3. Mounting a wire guard on the ACA, ACN or ACW requires an extra long casing due to the motor size. Brass lining is unavailable for some motor variants. ACP + downstream guide vane arrangement = ACG YAH YAA YAD HAN HAT SBC SBA
1

ACN ACW YAH YAA YAD HAN HAT SBC SBA


1

ACG YAH YAD SBC 2

ACP YAH YAD SBC 2

For assembly of 2 silencers type YAH use a standard clamping ring. Do not assemble more than 2 silencers by means of a standard clamping ring.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 9 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Performance Curves
ACA ACD 60 Hz
Total pressure, Pa 2000 1500 1000 500
tor mo ole 2-p

200 100 50

tor mo ole r 4-p oto le m r po 6o to le m po 8-

20 10 5

2 1 0.1

0.2

0.5

10

20

50

100
3

Air flow, q, m/s

The above curves show the duty ranges of the fan type irrespective the sizes and hub diameter. The fan performance are according to BS 848 1980, arrangement D (duct connection for inlet and outlet). If other arrangements are used, performance characteristics will vary.

Final selection of fan size, including calculation of blade pitch, power consumption, motor selection and sound level, is done by means of the Novax computer selection program; which is available on CD-ROM or www.york-novenco.com.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 10 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

ACN ACW 60 Hz
Total pressure, Pa 2000 1500 1000 500
m 2-po le o to r

tor le mo 4 -po r mo to 6-po le to r mo 8-po le

200 100 50

20 10 5

2 1

0.1

0.2

0.5

10

20

50
3

100

Air flow, q, m/s

The above curves show the duty ranges of the fan type irrespective the sizes and hub diameter. The fan performance are according to BS 848 1980, arrangement D (duct connection for inlet and outlet). If other arrangements are used, performance characteristics will vary.

Final selection of fan size, including calculation of blade pitch, power consumption, motor selection and sound level, is done by means of the Novax computer selection program; which is available on CD-ROM or www.york-novenco.com.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 11 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

ACG 60 Hz
Total pressure, Pa 2000 1500 1000 500
4-p o le 2-po r moto oto le m r

200 100 50

le 6-po

r moto le m 8-po otor

20 10 5

2 1 0.1

0.2

0.5

10

20

50

100
3

Air flow, q, m/s

The above curves show the duty ranges of the fan type irrespective the sizes and hub diameter. The fan performance are according to BS 848 1980, arrangement B (free inlet and ducted on outlet sides). If other arrangements are used, performance characteristics will vary.

Final selection of fan size, including calculation of blade pitch, power consumption, motor selection and sound level, is done by means of the Novax computer selection program; which is available on CD-ROM or www.york-novenco.com.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 12 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

ACP 60 Hz
Total pressure, Pa 2000 1500 1000 500
le 2-po or mot
otor le m 4-po otor le m 6-po
le 8-po moto r

200 100 50

20 10 5

2 1 0.1

0.2

0.5

10

20

50 100 3 Air flow, q, m/s

The above curves show the duty ranges of the fan type irrespective the sizes and hub diameter. The fan performance are according to BS 848 1980, arrangement A (free inlet and outlet sides). If other arrangements are used, performance characteristics will vary.

Final selection of fan size, including calculation of blade pitch, power consumption, motor selection and sound level, is done by means of the Novax computer selection program; which is available on CD-ROM or from www.york-novenco.com.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 13 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Dimension Sketches
ACA Dimension sketches
EUROVENT 1/2
P x R E L1

A B D N

C L

Hub diam.
A B D P R C E M L Weight,kg M L Weight,kg M L Weight,kg E M L Weight,kg M L Weight,kg M L 230-380 230-380 230 280 230-380 230 280 330 230-380 230 Weight,kg 280 330 380 E M L 230-380 230-380 160 160-380

Casing length L1

Motor type

250
310 280 250

315
385 355 315 8 10 3 200 182 315 14 187 315 14.2

400
480 450 400 8 12 3 200 182 315 17.6 187 315 17.6 193 350 18.3 200 207 340 19.5 212 340

Size (impeller diameter) 500 560 630 710


590 560 500 12 12 3 200 182 315 21.6 187 315 21.6 193 350 22.5 200 207 340 23.8 25.3 212 340 23.8 25.3 26.8 200 207 340 26.3 27.8 212 340 26.3 27.8 29.7 218 375 27.3 28.8 30.7 32.3 300 225 400 200 207 340 32.4 34.0 212 340 32.2 33.8 35.9 218 375 32.4 34.0 36.1 38.2 300 225 400 200 207 340 35.8 37.5 212 340 35.7 37.4 39.6 218 375 36.4 38.1 40.3 42.5 300 225 400 650 620 560 12 12 3 720 690 630 12 12 3 800 770 710 16 12 3

800
890 860 800 16 12 3

900
1000 970 900 16 15 4

300-500

All

4 10 3 200 182

1000 1100 1070 1000 16 15 4

-71

315 12

300

-80

-90

200 207 340 39.4 41.2 212 340 39.4 41.2 43.5 218 375 40.2 42.0 44.3 46.6 300 225 400

200 207 340 57.8 212 340 57.7 60.0 218 375 59.1 61.4 63.9 300 225 400

200

-71

-80 300

19.4

218 375 -90 20.1

218 375 24.6 26.1 27.6

218 375

300 400 -100 225 400

300 225 400

62.4 300 225 400

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 14 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Hub diam.
Weight,kg 230 280 330 380 280-380 280 330 380 330-380 330 380 380 380

Casing length L1

Motor type
-100

250

315

400
24.5

Size (impeller diameter) 500 560 630 710


30.1 31.6 33.0 232 33.3 34.8 36.7 38.3 232 425 35.2 37.1 38.7 251 475 38.3 39.9 400 270 585 47.3 38.7 40.3 42.4 44.5 232 425 40.5 42.6 44.7 251 475 43.5 45.6 400 270 585 52.9 283 625 52.2 40.3 42.0 41.2 46.4 232 425 45.4 47.6 49.8 251 475 48.7 51.0 400 270 585 59.2 283 625 59.0

800
48.1 49.9 52.2 54.5 232 425 50.4 52.7 55.0 251 475 54.0 56.3 400 270 585 65.0 283 625 64.5

900
71.5 73.8 76.3 232 425 71.6 73.9 76.4 251 475 75.9 78.4 400 270 585 93.5 283 625 93.3

1000

M L Weight,kg M L Weight,kg E M L Weight,kg M L Weight,kg

400

-112

425 32.0 33.5 251 475 34.8

84.1 232 425

-132

84.7 251 475 87.4 400 270 585 104.7 283 625 104.5

-160 500

380

-180

Hub diam. N
A B D P R C E M L Weight,kg M L Weight,kg M L Weight,kg M L Weight,kg E M L Weight,kg M L Weight,kg M L Weight,kg E M L Weight,kg 403-578

Casing length L1

Motor type

900
1000 970 900 16 15 4 4 375 295 500 101.2 314 545 103.3 119.7 333 655 107.0 123.4 346 1 695 1 122.4

1000
1100 1070 1000 16 15 4 4 375 295 500 110 314 545 112.8 130.0 333 655 116.9 134.1 346 695 116.8 134.0 505 358 725 157.2

Size (impeller diameter) 1120 1250 1400


1220 1190 1120 20 15 4 4 375 295 500 121.5 314 545 124.6 142.8 333 655 139.1 157.3 346 695 139.5 157.7 505 358 725 176 374 775 178.7 1360 1320 1250 20 15 6 6 375 295 500 173 314 545 176 195 333 655 193 212 346 695 194 213 505 358 725 241 374 775 245 393 850 247 1510 1470 1400 20 15 6 6

1600
1720 1680 1600 24 19 6

All 403 578 403-578 403 403 403-578 403 578 403-578 403 578 403-578 403 578 -180 -160 -132 500 -112

314 545 201.5 333 655 211.0 243.0 346 695 212.5 244.0 505 358 725 277 374 775 282 393 850 286 585 415 950 329

-200 578 630

-225

-250

578

710

-280

505 358 725 317 374 775 321 393 850 326 585 415 950 378

1.

Only for hub diameters 578

Dimensions in mm Weights in kg excl. motor Flanges: Pitch circle diameter, number of holes and hole size as standard according to EUROVENT 1/2.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 15 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

ACD Dimension sketches


DIN 24154 - Casing 6 or 10 mm

Hub Motor diam. N type 250


A B C D E L P R M Weight M Weight M Weight M Weight M Weight M Weight 230-380 230 280 230-380 230 280 330 230-380 230 280 330 380 -90 -80 -71 160 -71 -80 -90 160-380 All 334 292 6 250 276 360 8 12 182 21.5

315
409 / 407 366 8/8 315 314 400 8 12 182 187

400
494 / 492 448 6 / 10 400 415 520 12 12 182 187 193 207

500
594 / 592 551 6 / 10 500 455 560 12 12 182 187 193 207

Size (impeller diameter) 560 630 710


674 / 672 629 6 / 10 560 520 620 16 14 744 / 742 698 6 / 10 630 520 620 16 14 824 / 822 775 6 / 10 710 520 730 16 14

800
914 / 912 861 6 / 10 800 520 750 24 14

6 or 10 mm

900
1015 / 1012 958 6 / 10 900 727 850 24 14

1000
1115 / 1113 1067 6 / 10 1000 777 900 24 14

29.9 / 42.1 44.6 / 64.7 57.7 / 84.8 29.9 / 42.1 44.6 / 64.7 57.7 / 84.8 45.2 / 65.3 58.6 / 85.7 207 207 207 207 207 46.4 / 66.5 59.8 / 86.9 74.0 / 107.5 85.7 / 123.4 107.8 / 158.0 122.5 / 180.4 61.3 / 88.4 75.5 / 109.0 87.3 / 125.0 109.5 / 159.7 124.3 / 182.2 155.7 / 229.6 212 46.3 / / 66.4 218 212 212 212 212 212 212 59.8 / 86.9 73.9 / 107.4 85.6 / 123.3 104.6 / 154.8 122.5 / 180.4 61.3 / 88.4 75.4 / 108.9 87.2 / 124.9 109.4 / 159.6 124.3 / 182.2 155.6 / 229.5 62.8 / 89.9 77.3 / 110.8 89.3 / 127.0 111.6 / 161.8 126.6 / 184.5 157.9 / 231.8 218 218 218 85.7 / 123.4 87.3 / 125.0 89.4 / 127.1 91.5 / 129.2 218 108.4 / 158.6 110.1 / 160.3 112.3 / 162.5 114.5 / 164.7 218 218 218 123.3 / 181.2 125.1 / 183.0 156.9 / 230.8 127.4 / 185.3 159.2 / 233.1 129.7 / 187.6 161.7 / 235.6 185.6 / 272.7

47.0 / 67.1 60.6 / 87.7 74.9 / 108.4 62.1 / 89.2 76.4 / 109.9 63.6 / 90.7 78.3 / 111.8 79.9 / 113.4

Dimensions in mm Weights in kg excl. motor Flanges: Pitch circle diameter, number of holes and hole size as standard according to DIN 24154. Table cells with double entries state the value applying to 6 mm casings first followed by that for 10 mm casings. The values are separated by a slash for example (6 / 10).

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 16 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

ACD Dimension sketches


Casing 6 and 10 mm
Motor Hub diam. N type
M Weight M Weight M Weight M Weight M Weight 230-380 230 280 330 380 280-380 280 330 380 330-380 330 380 380 380 -100

400
225 48.1 / 68.2

500
225 62.2 / 89.3 63.7 / 90.8 65.2 / 92.3 232 64.0 / 91.1 65.5 / 92.6 251 66.8 / 93.9

560
225 76.7 / 110.2 78.2 / 111.7 80.1 / 113.6 81.7 / 115.2 232 78.7 / 112.2 80.6 / 114.1 82.2 / 115.7 251 81.7 / 115.2 83.3 / 116.8 270 86.0 / 119.5

Size (impeller diameter) 630 710 800


225 87.3 / 125.0 88.9 / 126.6 91.0 / 128.7 93.1 / 130.8 232 89.2 / 126.9 91.3 / 129.0 93.4 / 131.1 251 92.2 / 129.9 94.3 / 132.0 270 97.0 / 134.7 283 96.5 / 134.2 225 109.8 / 160.0 111.5 / 161.7 113.7 / 163.9 115.9 / 166.1 232 111.8 / 162.0 114.0 / 164.2 116.2 / 166.4 251 115.2 / 165.4 117.4 / 167.6 270 119.7 / 169.9 283 119.5 / 169.7 225 125.0 / 182.9 126.8 / 184.7 129.1 / 187.0 131.4 / 189.3 232 127.3 / 185.2 129.6 / 187.5 131.9 / 189.8 251 131.1 / 189.0 133.4 / 191.3 270 135.6 / 193.5 283 135.1 / 193.0

900
225 159.9 / 233.8 162.2 / 236.1 164.7 / 238.6 232 160.0 / 233.9 162.3 / 236.2 164.8 / 236.2 251 164.2 / 238.1 166.7 / 238.1 270 172.7 / 246.6 283 173.2 / 247.1

1000
225

189.3 / 276.4 232

-112

189.9 / 277.0 251 192.5 / 279.6 270 199.3 / 286.4 283 199.2 / 286.3

-132 -160 -180

Hub Motor diam. N type


A B C D E L P R M Weight M Weight M Weight M Weight M Weight M Weight M Weight M Weight

900
1015 / 1012 958 6 / 10 900 727 850 24 14 295 181.2 / 255.1 314 183.3 / 257.2 199.7 / 273.6 333 186.9 / 260.8 203.3 / 277.2 346 202.3 / 276.2

1000
1115 / 1113 1067 6 / 10 1000 777 900 24 14 295 206.2 / 293.3 314 208.9 / 296.0 226.1 / 313.2 333 213.3 / 300.4 230.5 / 317.6 346 212.8 / 299.9 230.0 / 317.1 358 239.8 / 326.9

Size (impeller diameter) 1120 1250


1255 / 1263 1200 6 / 10 1120 777 950 32 18 295 256.5 / 361.9 314 259.6 / 364.9 277.8 / 383.1 333 274.0 / 379.3 292.2 / 397.5 346 274.4 / 379.7 292.6 / 397.9 358 295.9 / 401.2 374 298.9 / 404.2 1385 / 1393 1337 6 / 10 1250 777 1060 32 18 295 304.5 / 435.7 314 307.8 / 439.0 326.7 / 457.9 333 324.7 / 455.9 343.6 / 474.8 346 325.7 / 456.9 344.6 / 475.8 358 348.6 / 479.8 374 352.6 / 483.8 393 355.2 / 486.4

1400
1535 / 1543 1491 6 / 10 1400 777 1120 32 18

1600
1745 / 1753 1663 6 / 10 1600 777 1120 40 18

403-578

All

403 403-578 403578 403-578 403578 403-578 403578

-112 -132

314 364.8 / 519.9 333 374.2 / 529.3 405.9 / 561.0 346 375.6 / 530.7 407.3 / 562.4 358 412.6 / 567.7 374 417.0 / 572.1 393 421.1 / 576.2 415 446.6 / 601.7

-160

-180

578

358 487.7 / 664.8 374 493.8 / 670.9 393 499.3 / 676.4 415 531.1 / 708.2

Dimensions in mm Weights in kg excl. motor Flanges: Pitch circle diameter, number of holes and hole size as standard according to DIN 24154. Table cells with double entries state the value applying to 6 mm casings first followed by that for 10 mm casings. The values are separated by a slash for example (6 / 10).

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 17 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

ACN Dimension sketches EUROVENT 1/2

P x R

Hub diam. N
A B D P R C L All 160-380 All

Motor type

250
310 280 250 4 10 2 360 11

315
385 355 315 8 10 2 400 14

400
480 450 400 8 12 3 520 27

500
590 560 500 12 12 3 560 42

560
650 620 560 12 12 3 620 55

Size (impeller diameter) 630 710 800 900 1000 1120 1250
720 690 630 12 12 3 620 60 800 770 710 16 12 3 730 73 890 860 800 16 12 3 750 82 1000 970 900 16 15 3 850 98 850 850 117 850 850 1100 1070 1000 16 15 3&4 900 134 650 750 750 900 154 750 750 900 900 650 750 850 167 650 750 850 950 950 750 750 750 850 184 750 750 850 950 950 1060 153 192 219 269 1220 1190 1120 20 15 3&4 1360 1320 1250 20 15 3&4

1400
1510 1470 1400 20 15 4

1600
1720 1680 1600 24 19 4

All

All

Max. weight excl. of motor -112 L 403 -132 -160 -180 Max. weight excl. of motor -132 -160 -180 L 578 -200 -225 -250 -280 Max. weight excl. of motor

850 850 850 202 850 850 950 950 1120 1120 329 900 1120 1120 1120 366

Dimensions in mm Weights in kg excl. motor Flanges: Pitch circle diameter, number of holes and hole size as standard according to EUROVENT 1/2. Mounting positions according to EUROVENT: ACN arrangement D, motor position B.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 18 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

ACG and ACP Dimension sketches


EUROVENT 1/2

ACG

ACP Size (impeller diameter) 630 710 800 900 1000 1120 1250 1400 1600
720 690 630 12 12 800 770 710 16 12 890 860 800 16 12 1000 970 900 16 15 1100 1070 1000 16 15 1220 1190 1120 20 15 1360 1320 1250 20 15 1510 1470 1400 20 15 1720 1680 1600 24 19

ACG and ACP


Hub diam. Motor N types
A B D P R All All

250
310 280 250 4 10

315
385 355 315 8 10

400
480 450 400 8 12

500
590 560 500 12 12

560
650 620 560 12 12

ACG
C J L Fmax
4)

All All 160 Max. weight excl. of motor

2.5 333 350 197 13

2.5 420 350 235 16

3 545 355 259 24 355

3 675 355 259 30 355 370 40

3 768

3 840

3 950

3 1055

3 1200

3 1332

3 1500

4 1650

4 1800

4 2000

L Fmax 4) 4) 230-578 Max. weight excl. of motor All

410 479 52

415 544 57

415 505 65

410 510 72

670 1) 494 139 2)

690 1) 552 171 2)

715 610 188 2

739 579 234 2)

739 644 258 2)

739 644 297 2)

250 26

ACP
C J L Fmax
4)

All All 160 Max. weight excl. of motor

2.5 333 200 197 9

2.5 420 200 235 11

3 545 205 259 15 205 250 18

3 675 205 259 19 205 370 28

3 768

3 840

3 950

3 1055

3 1200

3 1332

3 1500

4 1650

4 1800

4 2000

L Fmax
4)

230-578 Max. weight excl. of motor

All

260 479 38

265 544 42

265 505 48

260 510 53

420 3) 494 1062)

440 3) 552 134 2)

465 610 147 2)

489 579 188 2)

489 644 207 2)

489 644 238 2)

1) Type ACG-900/280 L = 430 and ACG-1000/380 L = 450. 2) Hub diameter 578 mm. For other hub diameters smaller weight.

3) Type ACP-900/280 L = 280 and ACP-1000/380 L = 300. 4) Fmax is max. dimension based on motor make type ABB.

Dimensions in mm Weights in kg excl. motor Flanges: Pitch circle diameter, number of holes and hole size as standard according to EUROVENT 1/2. Mounting positions according to EUROVENT: ACG arrangement B, motor position A and ACP arrangement A, motor position A.
Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 19 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

ACW Dimension sketches


DIN 24154R Casing 6 mm
E

Hub diam. N
A B D E P R C L 160 - 380 All

Motor types

250
334 292 250

315
409 366 315 314 8 12 8 400 32

400
494 448 400 415 12 12 6 520 48

500
594 551 500 455 12 12 6 560 69

560
674 629 560 520 16 14 6 620 90

Size (impeller diameter) 630 710 800 900 1000 1120 1250 1400 1600
744 698 630 520 16 14 6 620 99 824 775 710 520 16 14 6 730 121 914 861 800 520 24 14 6 750 138 1015 958 900 727 24 14 6 850 166 850 850 182 850 850 1115 1067 1000 777 24 14 6 900 190 900 900 900 207 900 900 900 900 950 950 950 950 260 950 950 950 950 950 1060 1060 1060 1060 306 1060 1060 1060 1060 1060 1060 350 1120 1120 1120 351 1120 1120 1120 1120 1120 1120 425 1255 1200 1120 777 32 18 6 1385 1337 1250 777 32 18 6 1535 1491 1400 777 32 18 6 1745 1663 1600 777 40 18 6

All

276 8 12 6

All

360 23

Max. weight excl. motor (160 - 380) -112 -132 403 L -160 -180 Max. weight excl. motor (403) -132 -160 -180 578 -200 L -225 -250 -280 Max. weight excl. motor (578)

6 mm

1120 1120 1120 1120 497

217

243

300

Dimensions in mm Weights in kg excl. motor Flanges: Pitch circle diameter, number of holes and hole size as standard according to DIN 24154 R.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 20 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

ACW Dimension sketches


DIN 24154R - Casing 10 mm
E

Hub diam. N

Motor type

315
407 366 315 314 8 12 8 400 44

400
492 448 400 415 12 12 10 520 68

500
592 551 500 455 12 12 10 560 96

560
672 629 560 520 16 14 10 620 123

Size (impeller diameter) 630 710 800 900 1000 1120 1250 1400 1600
742 698 630 520 16 14 10 620 137 822 775 710 520 16 14 10 730 172 912 861 800 520 24 14 10 750 195 1012 958 900 727 24 14 10 850 239 850 850 256 850 850 1113 1067 1000 777 24 14 10 900 278 900 900 900 294 900 900 900 900 1263 1200 1120 777 32 18 10 1393 1337 1250 777 32 18 10 1543 1491 1400 777 32 18 10 1753 1663 1600 777 40 18 10

A B D E All All P R C L 160-380 All Max. weight excl. motor (160 - 380) -112 -132 L 403 -160 -180 Max. weight excl. motor (403) -132 -160 -180 L 578 -200 -225 -250 -280 Max. weight excl. motor (578)

10 mm

950 950 950 950 365 950 950 950 950 950

1060 1060 1060 1060 437 1060 1060 1060 1060 1060 1060 481

1120 1120 1120 506 1120 1120 1120 1120 1120 1120 580

291

330

405

1120 1120 1120 1120 675

Dimensions in mm Weights in kg excl. motor Flanges: Pitch circle diameter, number of holes and hole size as standard according to DIN 24154 R.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 21 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories
Lr

45

4 x M

80 F N 2 x 4 12 C L

80

Mounting foot for horizontal mounting of ACA

Fan diameter D
250 315 400 500 400 500 560

Hub diameter
160

Motor size
71 71-80 71-90 71-90 71-90 100 71-90 100-132 71-90 100-132 160 71-90 100-132 160-180 71-90 100-132 160-180 71-90 100-132 160-180 71-90 100-132 160-180 71-90 100-132 160-180

C
400 500 400 500 400 500 400 500 630 400 500 630 400 500 630 400 500 630 400 500 630 400 500 630

F
170 200 250 325 250 325 370

G
285 325 375 435 375 435 485

H
440 518 615 730 615 730 810

Lr
300 400 300 400 300 400 300 400 500 300 400 500 300 400 500 300 400 500 300 400 500 300 400 500

L
480 580 480 580 480 580 480 580 710 480 580 710 480 580 710 480 580 710 480 580 710 480 580 710

N
260 290 360 435 360 435

T
2

Weight kg
18.1 21.3 26.4 31.6 28.2 33.3 36.7 44.6 44.0 52.3 60.7 54.4 62.5 70.1 59.7 68.9 77.9 65.8 76.2 85.4 87.1 102.3 118.2 87.6 113.3 131.4

8 10 8 10

480

630 230 280 330 380

400

525

885

530

710

450

575

975

580 12 650 4

800

520

625

1070

900

590

725

1225

720

1000

670

785

1335

800

The stated weights are incl. of fan, mounting foot and frame but excl. of motor.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 22 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories ACA Mounting foot


Fan diameter D
900

Hub Motor size diameter


112-132 160-180 112-132 160-180 200 112-132

C
630 630 710 630 710 630 710 630 710 800 710 800

F
590

G
725

H
1225

Lr
500 500 630

L
710 710 790 710 790 710 790 710 790 880 790 880

N
720

Weight kg
144.5 147.2 157.3 161.3 186.7 172.1

12 800

1000

670

785

1335

1120 403 578

160-180 200-225 112-132 160-180 200-250 132 160-180 200-250 280 200-250 280

750

845

1455

500 630

880 4 980 14 1090

187 210.2 189.3 207.4 237 235.3 277.8 322.5 366.1 371.5 424.1

1250

810

895

1575

500 630 500

1400

920

970

1725

630 710 630 710

1600

1060

1070

1930

1230

The stated weights are incl. of fan, mounting foot and frame but excl. of motor

Accessories ACN Mounting foot, horizontal


Mounting foot for horizontal mounting of ACN
T H

2 braces from size 630 up to 1600

250
G C 1) M 1) U Weight, kg 240 296 170 8 1.5

315
280 336 200 8 2.8

400
330 454 250 8 3.8

500
390 494 325 10 4.4

560
440 554 370 12 7.2

Size (impeller diameter) 630 710 800 900*


480 554 400 12 11.4 530 664 450 12 13.2 580 684 520 12 14.9 680 784 590 12 21.0

1000* 1120
740 832 670 12 23.5 800 882 750 14 26.0

1250
850 992 810 14 32.6

1400
925 1052 920 14 34.6

1600
1025 1052 1060 14 46.5

* Applies to hub diameters 403 mm and 578 mm. For other hub diameters: Please order special dimension sketch 1) The stated data for C and M are based on max. length of casing. Other data applies for other casing lengths.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 23 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories ACG and ACP Mounting foot and diffuser


L L 150

D
G 4 x U CxM L1 x N 65

G P x R

P x R

50

YxY

4 x U

CxM L1 x N

65

Mounting foot, vertical, for vertical mounting of fans and hood type HAN

Mounting foot for ACP. Hub sizes 160 380.

Mounting foot for ACG. Hub sizes 160 380.

Mounting foot for ACP.

Mounting foot for ACG.

Mounting foot for ACG with short diffuser.

Mounting foot for ACG with long diffuser. Hub sizes 403 and 578.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 24 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories ACG and ACP Mounting foot and diffuser


250
Mounting plate, vertical Y Weight, kg G C M L1 N U Weight, kg G C M L1 N U Weight, kg G C M L1 N U Weight, kg L3 D1 B1 A3 P1 R1 Weight, kg G C M L1 N U Weight, kg L4 D2 B2 A4 P2 R2 Weight, kg 580 8 275 420 170 550 260 12 5.7 275 420 170 550 260 12 5.7

315 400
645 9 315 420 200 550 290 12 5.7 315 420 200 550 290 12 5.7 730 11 365 420 250 550 360 12 5.7 365 420 250 550 360 12 5.7

500
830 13 425 420 325 550 435 12 6.3 425 420 325 550 435 12 6.3

560
890 14 475 420 370 550 480 12 8.5 475 420 370 550 480 12 8.5

Size (impeller diameter) 630 710 800 900* 1000* 1120


960 15 515 570 400 700 530 12 10.2 515 570 400 700 530 12 10.2 1040 20 565 570 450 700 580 12 11.2 565 570 450 700 580 12 11.2 1130 23 615 570 520 700 650 12 12.2 615 570 520 700 650 12 12.2 1230 34 790 1000 900 1090 990 12 50.9 790 1000 900 1090 990 12 50.9 790 1120 900 1210 990 12 52.4 400 1000 1070 1103 16 15 33 790 1120 900 1210 990 12 52.4 900 1120 1190 1223 20 15 52 1330 38 850 1000 1000 1090 1090 12 53.1 850 1000 1000 1090 1090 12 53.1 850 1120 1000 1210 1090 12 57.2 500 1120 1190 1223 20 15 40 850 1120 1000 1210 1090 12 57.2 1000 1250 1320 1363 20 15 62 1450 42 910 1120 1120 1210 1210 12 61.8 910 1120 1120 1210 1210 12 61.8 910 1250 1120 1340 1210 12 61.8 560 1250 1320 1363 20 15 48 910 1250 1120 1340 1210 12 61.8 1100 1400 1470 1513 20 15 74

1250 1400 1600


1580 48 960 1120 1250 1210 1340 12 62.1 960 1120 1250 1210 1340 12 62.1 960 1250 1250 1340 1340 12 63.8 600 1400 1470 1513 20 15 57 960 1250 1250 1340 1340 12 63.8 1400 1600 1680 1723 24 15 102 1730 68 1035 1250 1400 1340 1490 12 68.6 1035 1250 1400 1340 1490 12 68.6 1035 1250 1400 1340 1490 12 68.6 800 1600 1680 1723 24 19 77 1035 1250 1400 1340 1490 12 68.6 1600 1800 1880 1923 24 19 123 1930 79 1135 1250 1600 1340 1690 12 76.7 1135 1250 1600 1340 1690 12 76.7 1135 1250 1600 1340 1690 12 76.7 800 1800 1880 1923 24 19 86 1135 1250 1600 1340 1690 12 76.7 1600 2000 2080 2123 24 19 139

Mounting foot and base frame, horizontal, for ACP

Mounting foot and base frame, horizontal, for ACG

Mounting foot and base frame, horizontal, for ACG with short diffuser

Short diffuser

Mounting foot and base frame, for ACG with long diffuser

Long diffuser

* Applies to hub diameters 403 and 578 mm. Please order special dimension sketch.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 25 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories ACA, ACN, ACG and ACP


Flange standard: EUROVENT 1/2

Outlet wire guard

Wire guard for mounting in cas-

Inlet cone

Counter flange

Duct spigot

Flexible connection with 1 duct spigot

Flexible connection with 2 duct spigots

Welded spigots

250
Outlet wire guard Wire guard for mounting in casing Wire guard for mounting in flange V Weight, kg N J Weight, kg N J Weight, kg E1 A1 Weight, kg T Counter flange DF Weight, kg G Weight, kg LF Flexible connection Weight, kg w.1 spigot LF Weight, kg w.2 spigots LS t Welded spigots B A3 Weight, kg 1.3 29 0.1 19 246 0.1 29 310 0.1 200 333 4.5 4 260 0.7 55 1.0

315
43 0.2 29 310 0.1 43 396 0.2 200 420 5.5 4 325 1.1 55 1.4 1.7

400
68 0.3 43 396 0.2 68 496 0.3 205 545 9.5 4 410 1.5 55 1.9 2.3

500
55 0.5 68 496 0.3 88 556 0.3 205 675 12.5 4 510 2.2 55 2.4 3.0

560
69 0.6 88 556 0.3 55 626 0.5 260 760 17 4 570 2.4 55 2.7 3.5

Size (impeller diameter) 630 710 800 900 1000


87 0.8 55 626 0.5 69 706 0.6 265 840 19 4 640 2.7 55 3.1 3.8 111 0.9 69 706 0.6 87 796 0.8 265 947 22 4 720 3.0 55 3.5 4.3 137 1.1 87 796 0.8 111 896 0.9 260 1055 26 4 810 3.4 55 3.9 5.0 85 2.5 111 896 1.0 137 996 1.1 280 1200 32 8 910 8.5 85 5.9 7.8 106 3.0 137 996 1.1 85 1114 2.5 300 1333 38 8 1010 9.4 85 6.6 8.9

1120
133 3.6 85 1114 2.5

1250
133 3.6 106 1244 3.0

1400
171 4.2 133 1394 3.6

1600
218 5.7 171 1594 4.2

Inlet cone

320 1520 45 8 1130 10.2 85 7.4 10

320 1650 51 8 1260 12.2 85 8.5 11.6

320 1800 57 8 1410 14.2 85 9.5 13.1

320 2000 66 8 1610 17.2 85 11.3 20

Duct spigot

Min. 65 mm Max. 100 mm

Min. 110 mm Max. 175 mm

Min. 120 mm Max. 145 mm 2.3 100 4 280 310 3.1 3.0 100 4 355 385 3.9 4.2 100 4 450 480 5.4 5.5 100 4 560 590 6.7 6.2 100 4 620 650 7.5 6.9 120 6 690 720 15.0 7.8 120 6 770 800 16.9 8.8 120 6 860 890 19.0 13.7 120 6 970 1000 21.4

Min. 210 mm Max. 250 mm 15.5 150 6 1070 1100 29.0 17.4 150 6 1190 1220 32.4 20.2 150 6 1320 1360 36.2 22.7 150 6 1470 1510 40.5 26.6 150 6 1680 1720 46.3

Flanges: Pitch circle diameter, number of holes and hole size as standard according to EUROVENT 1/2. Dimensions A, B, D, P and R: See pages 14, 18 and 19 for the ACA, ACN, and ACP and ACG, respectively.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 26 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories ACA, ACN, ACG and ACP


Flange standard: EUROVENT 1/2

Silencer type YAH with or without core 250


D B All A P (number) R L2 N A2 Silencer Q type YAH Casing, mm Weight without core, kg Weight with core, kg H H1 Hood type M HAN C Weight, kg L Damper C type SBC Weight, kg 250 280 310 4 10 250 125 463 M8 0.9 6.2 7.9 361 180 598 2.5 13 360 2 8.5

Hood type HAN Size (impeller diameter) 630 710 800 900 1000
630 690 720 12 12 630 315 845 M10 0.9 27.6 40.8 694 450 1406 3 97 670 3 48 710 770 800 16 12 710 355 925 M10 0.9 33.8 52.1 744 506 1586 3 120 730 3 58 800 860 890 16 12 800 400 1015 M10 0.9 41.3 69.2 811 569 1766 3 151 810 3 82 900 970 1000 16 15 900 450 1115 M12 1.25 50.6 86.8 868 645 2016 3 206 910 3 101 1000 1070 1100 16 15 1000 500 1215 M12 1.25 61.1 109.6 890 710 2236 3 250 1010 4 149

Damper type SBC

315
315 355 385 8 10 315 160 526 M8 0.9 8.9 11.5 412 228 724 2.5 19 400 2 11.5

400
400 450 480 8 12 400 200 614 M10 0.9 12.5 16.8 476 290 906 3 40 520 3 23

500
500 560 590 12 12 500 250 715 M10 0.9 19.1 26.5 540 364 1106 3 58 560 3 31

560
560 620 650 12 12 560 280 775 M10 0.9 22.8 32.8 641 405 1266 3 79 620 3 40.5

1120
1120 1190 1220 20 15 1120 560 1335 M12 1.25 74.5 134.4 1140 800 2436 3 313 1130 4 183

1250
1250 1320 1360 20 15

1400
1400 1470 1510 20 15

1600
1600 1680 1720 24 19

1252 853 2810 4 625

1402 983 3110 4 776

1602 1153 3510 4 1020

Flanges: Pitch circle diameter, number of holes and hole size as standard according to EUROVENT 1/2 To prevent galvanic corrosion a special tape is put on the back of the brass lining prior to mounting

Thickness = 1 mm

L1

L2

250
Brass lining Hubs 160-380 Brass lining Hubs L1 L2 Weight, kg L1 L2 14 150 1

315
14 150 1.3

400
14 150 1.6

500
14 150 2.0

560
14 150 2.2

Size (impeller diameter) 630 710 800 900 1000


14 150 2.5 14 150 2.9 14 150 3.2 14 150 3.6 24 212 5.1 14 150 4.0 24 212 5.7

1120

1250

1400

1600

24 212 6.3

24 212 7.1

24 212 8.0

24 212 9.1

403 and 578 Weight, kg

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 27 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories ACD, ACW


Dimensions

Outlet wire guard


C

J
Inlet cone with wire guard

Mounting feet, horizontal position

Counter flange

Duct spigot

Flexible connection with 1 duct apigot

Flexible

connection

with 2 duct spigots

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 28 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories ACD, ACW


Dimensions Flange standard DIN 24154
Size (impeller diameter) 630 710 800 900 1000
630 698 737 16 14 480 544 400 530 12 252 290 352 840 265 8 23.5 55 0.5 69 0.6 744 644 8 6.7 742 652 8 6.0 55 3.2 65 100 3.8 120 145 6.9 710 775 817 16 14 530 654 450 580 12 276 326 376 947 265 8 26.9 69 0.6 87 0.8 824 724 8 7.5 822 732 8 6.7 55 3.5 65 100 4.3 120 145 7.8 800 861 907 24 14 580 674 520 650 12 293 351 397 1055 260 8 30.7 87 0.8 111 0.9 914 814 8 8.3 912 822 8 7.5 55 3.9 65 100 5.0 120 145 8.8 900 958 1007 24 14 680 774 590 720 12 375 449 365 1200 280 8 37.9 111 0.9 137 1.1 1015 915 8 9.3 1012 922 8 8.4 55 9.0 110 175 6.5 210 250 11.1 1000 1067 1108 24 14 740 824 670 800 12 449 536 406 1333 300 8 44.3 137 1.1 85 2.5 1115 1015 8 10.3 1113 1023 8 9.3 55 9.0 110 175 7.3 210 250 12.5

250
D B All A P (number) R H J K Mounting feet, N horizontal1) U Weight, kg Weight, kg L1 J Inlet cone, with wire G guard T Weight, kg V Wire guard, in tube Weight, kg V Wire guard, flange Weight, kg A5 Counter D5 flange. Casing C 6 mm Weight, kg A5 Counter D5 flange. Casing C 10 mm Weight, kg G Duct spigot Weight, kg LF Min. Flexible connection, LF Max. with 1 duct Weight, kg spigot with 1 duct LF Min. Flexible LF Max. connection, Weight, kg with 2 ducts with 2 spigots ducts 250 292 326 8 12 240 288 170 260 8 32 229 333 200 6 5.2 19 0.1 29 0.1 334 264 6 1.5 332 272 6 1.3 55 1.1 65 100 1.3 120 145 2.3

315
315 366 401 8 12 280 324 200 290 8 44 56 243 420 200 8 7.7 29 0.1 43 0.2 409 329 8 2.9 407 337 8 2.5 55 1.5 65 100 1.7 120 145 3.0

400
400 448 487 12 12 330 444 250 360 8 75 95 273 545 205 8 11.4 43 0.2 69 0.3 494 414 8 3.5 492 422 8 3.0 55 1.9 65 100 2.3 120 145 4.2

500
500 551 587 12 12 390 484 325 435 10 125 152 260 675 205 8 14.9 68 0.3 88 0.4 594 514 8 4.3 592 522 8 3.8 55 2.5 65 100 3.0 120 145 5.5

560
560 629 667 16 14 440 544 370 480 12 184 217 329 760 260 8 20.7 88 0.3 55 0.5 674 574 8 6.0 671 581 8 5.4 55 2.8 65 100 3.5 120 145 6.2

1120
1120 1200 1251 32 18 800 866 750 880 14 592 697 453 1520 320 12 62.4 85 2.5

1250
1250 1337 1380 32 18 850 976 810 980 14 679 810 453 1650 320 12 68 106 3.0

1400
1400 1491 1530 32 18 925 1036 920 1090 14 930 1086 491 1800 320 12 76.3 133 3.6

1600
1600 1663 1740 40 18 1025 1036 1060 1230 14 1009 1186 538 2000 320 15 98.2 171 4.2

1255 1135 12 20.5 1263 1143 12 20.6 90 8.2 110 175 8.2 210 250 14.0

1385 1265 12 22.8 1393 1273 12 22.9 90 9.1 110 175 9.5 210 250 16.2

1535 1415 12 25.4 1543 1423 12 25.6 90 10.3 110 175 10.5 210 250 18.0

1745 1615 15 39.2 1753 1623 15 93.4 90 11.7 110 175 12.6 210 250 21.6

1) Weights are incl. of max. hub and motor size.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 29 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories ACD, ACW


Dimensions Flange standard DIN 24154

Silencer type YAA with and without core

Damper type SBA

Hood type HAT for air intake and discharge


L1 L2

Brass lining

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 30 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Accessories ACD, ACW


Dimensions
250
All D B A P (number) R L2 A2 Q Weight, kg without core d Weight, kg with core L2 A2 Q Weight, kg without core d Weight, kg with core H h M C Weight, kg L A1 C1 C2 Weight, kg L A1 C1 C2 Weight, kg L1 L2 Weight, kg L1 L2 Weight, kg 250 292 326 8 12 250 463 M10 30 125 32 250 471 M10 41 125 43 361 180 598 6 14 360 334 6 6 20 360 332 10 10 29 14 150 1

315
315 366 401 8 12 315 529 M10 45 160 47 315 536 M10 60 160 63 412 228 724 8 21 400 409 8 6 29 400 407 10 10 41 14 150 1.3

400
400 448 487 12 12 400 614 M10 62 200 65 400 622 M10 85 200 89 476 290 906 8 42 520 494 6 44 520 492 10 10 64 14 150 1.6

500
500 551 587 12 12 500 714 M10 86 250 91 500 722 M10 120 250 125 540 364 1106 8 61 560 594 6 57 560 592 10 10 85 14 150 2.0

560
560 629 667 16 14 560 774 M12 101 280 109 560 782 M12 143 280 150 641 405 1266 8 83 620 674 6 77 620 671 10 10 110 14 150 2.2

Size (impeller diameter) 630 710 800 900 1000


630 698 737 16 14 630 844 M12 121 315 131 630 852 M12 172 315 182 694 450 1406 8 101 670 744 6 91 670 742 10 10 132 14 150 2.5 710 775 817 16 14 710 924 M12 146 355 160 710 932 M12 210 355 222 744 506 1586 8 125 730 824 6 107 730 822 10 10 159 14 150 2.9 800 861 907 24 14 800 1014 M12 175 400 198 800 1022 M12 255 400 276 811 569 1766 8 156 810 914 6 143 810 912 10 10 207 14 150 3.2 900 958 1007 24 14 900 1114 M12 214 450 240 900 1122 M12 310 450 337 868 645 2016 8 212 910 1015 6 178 910 1012 10 10 257 14 150 3.6 24 212 5.1 1000 1067 1108 24 14 1000 1214 M12 255 500 290 1000 1222 M12 375 500 408 890 710 2236 8 254 1010 1115 6 215 1010 1113 10 10 312 14 150 4.0 24 212 5.7

1120
1120 1200 1251 32 18 1120 1334 M16 330 560 364 1120 1342 M16 465 560 509 1140 800 2436 10 330 1130 1255 6 266 1130 1263 10 10 380

1250
1250 1337 1380 32 18

1400
1400 1491 1530 32 18

1600
1600 1663 1740 40 18

Silencer type YAA, Casing 6 mm

Silencer type YAA, Casing 10 mm

Hood type HAT

1252 853 2810 10 641

1402 983 3110 10 794

1602 1153 3510 10 1050

Damper type SBA, Casing 6 mm

Damper type SBA, Casing 10 mm

Brass lining HUB 160-380 Brass lining HUB 403 and 578

24 212 6.3

24 212 7.1

24 212 8.0

24 212 9.1

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 31 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Acoustic diffuser - YAD

Acoustic diffuser type YAD 250-1600


Hub A1 (mm) (mm)
463 160 526 614 716 230 230 280 330 230 280 330 380 230 280 330 380 230 280 330 380 230 280 330 380 280 330 380 380 403 578 403 578 403 578 403 578 403 578 578 614 716

Size
250 Mini 315 400 500 400 500

B1 (mm)
280 355 450 560 450 560

Fan side D1 (mm)


253 318 404 504 404 504

N x R1 (pc. x mm)
4 x M8 8 x M8 8 x M8 12 x M10 8 x M10 12 x M10

A2 (mm)
614 716 776 846 776 846

Duct side B2 D2 P x R2 (mm) (mm) (pc. x mm)


450 560 620 690 620 690 404 504 564 634 564 634 8 x M10 12 x M10 12 x M10 12 x M10 12 x M10 12 x M10

L (mm)
250 315 400 500 400 500

Weight (kg)
12 17.5 23 30.5 24.5 32.5 34 40 40 41.5 44 46.5 46 40 51.5 56 62 64 70.5 73 77 79.5 83 86.5 94.5 98.5 108.5 122 116 132 138 157 154 129.5 193 198 248 274 320

560

776

620

564

12 x M10

926

770

714

16 x M10

560

Novax Medium

630

846

690

634

12 x M10

1011

960

804

16 x M10

630

710

926

770

714

16 x M10

1116

960

904

16 x M12

710

800

1016

860

804

16 x M10

1216

1070

1004

16 x M12

800

900 1000 900 1000 1120 1250 1400 1600

1116 1216 1116 1216 1333 1466 1613 1816

970 1070 970 1070 1190 1320 1460 1680

904 1004 904 1004 1124 1254 1404 1604

16 x M12 16 x M12 16 x M12 16 x M12 20 x M12 20 x M12 20 x M12 24 x M12

1336 1466 1336 1466 1613 1816 2013 2216

1190 1320 1190 1320 1470 1680 1880 2080

1124 1254 1124 1254 1404 1604 1804 2004

20 x M12 20 x M12 20 x M12 20 x M12 20 x M12 24 x M12 24 x M12 24 x M12

900 1000 900 1000 1120 1250 1400 1600

Novax Maxi

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 32 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Acoustic diffuser - YAD


Sound data (dB/A) and attenuation values
Octave band Type YAD 63 (Hz) 125 (Hz) 250 (Hz) 500 (Hz) 1000 (Hz) 2000 (Hz) 4000 (Hz) 8000 (Hz) OutCore Core Core Core Core Core Core Core Hub side diadiameter With- with With- with With- with With- with With- with With- with With- with With- with meter out out out out out out out out (m) (mm)
250 315 400 500 400 500 560 630 710 800 500 560 630 710 800 900 500 560 630 719 800 900 560 630 719 800 900 1000 900 1000 1120 1250 1400 900 1000 1120 1250 1400 1600 160 160 160 160 230 230 230 230 230 230 280 280 280 280 280 280 330 330 330 330 330 330 380 380 380 380 380 380 403 403 403 403 403 578 578 578 578 578 578 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 1 0 1 1 1 1 0 0 0 1 1 1 1 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 1 1 0 0 0 0 1 0 1 0 1 1 2 2 0 0 0 1 2 2 0 0 0 1 0 0 1 2 3 1 0 0 1 3 1 3 0 0 0 2 3 1 0 1 1 3 1 3 1 4 3 2 2 1 4 1 4 3 3 1 1 2 1 2 2 1 2 3 1 2 2 1 3 1 3 2 3 2 2 3 1 2 2 1 3 1 3 1 4 3 2 2 1 4 1 4 3 3 2 2 3 4 2 9 4 5 6 8 2 10 4 7 9 7 3 4 10 5 7 9 3 11 5 8 9 7 10 7 7 7 7 6 9 11 8 8 8 2 2 3 4 2 9 4 5 6 8 2 10 4 7 8 7 3 4 10 5 7 9 3 11 5 8 9 7 10 7 7 7 7 6 9 11 8 8 8 8 8 11 11 10 11 12 13 13 14 11 12 12 14 15 13 14 16 12 15 15 15 14 13 15 16 16 14 17 15 11 5 5 18 19 19 13 6 6 9 9 12 10 11 12 12 13 13 14 12 13 12 14 15 13 15 17 13 15 15 15 15 15 14 16 16 14 17 15 14 9 8 18 19 19 16 10 9 5 5 6 7 8 7 8 8 9 7 9 7 8 10 8 5 12 11 8 10 10 8 13 9 11 12 9 6 10 6 6 4 4 15 14 12 7 5 5 11 11 11 12 14 12 13 13 12 12 15 12 14 13 13 11 18 16 13 15 14 14 19 15 16 15 15 11 15 12 11 10 9 20 18 17 13 11 10 1 1 1 3 3 3 4 4 4 4 5 3 5 5 5 2 8 6 4 5 5 5 8 6 6 6 6 3 6 3 4 4 3 10 8 8 5 5 4 11 11 11 10 13 12 11 10 9 9 15 13 11 9 10 7 18 16 13 12 10 10 18 15 13 11 11 8 11 8 8 7 7 16 13 13 9 8 8 1 1 1 3 3 2 4 3 3 3 4 3 4 4 3 3 6 4 3 4 4 4 7 4 5 5 4 4 4 4 4 4 4 7 6 5 5 5 4 8 8 7 6 10 8 7 6 6 6 11 9 7 7 6 6 13 10 9 7 7 7 14 11 9 7 7 6 7 7 6 6 5 11 9 8 7 6 6 2 2 1 2 3 2 3 3 3 2 4 2 3 3 3 4 5 3 3 3 4 3 5 3 4 4 3 4 3 4 4 3 3 5 5 4 5 4 4 5 5 4 4 6 5 5 5 5 4 7 5 5 5 4 5 8 6 5 5 5 4 8 6 6 6 5 6 5 6 5 5 4 7 7 5 6 5 5

Sound data and attenuation values are based on measurings with Novax axial flow fan type ACG.

Sound conditions
Final calculation and selection of blade pitch power consumption, motor selection and sound level is done by means of the Novax computer selection program. This is available on CD-ROM and can also be downloaded from www.york-novenco.com.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 33 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Technical Data for Accessories


Silencer Type YAH and YAA Pressure Loss Without core: not essential. With core: 0.2 x p dF. 2 YAH silencers end to end: 0.35 x p dF (p dF = dynamic pressure of the fan). Example YAH/YAA-800 with core. Air quantity, qv = 5 m3 /s Air velocity, inlet = 10 m/s p dF = 60 Pa Pressure loss: 0.2 x 60 = 12 Pa Sound attenuation average values
Octave band
Without core With core

For inlet (ACN,ACA and ACW) silencers without core must be used.

63
0 2

125
1 4

250
10 10

500
13 17

1k
11 17

2k
9 15

4k
7 12

8k
7 11

Hz
dB dB

Hood Type HAN and HAT Pressure Loss Example HAN/HAT-800 for discharge. Air quantity, q v = 5 m3/s Air velocity, inlet = 10 m/s
pd

p d, inlet: 60 Pa Pressure loss: 0.8 x 60 = 48 Pa

Discharge (hood + discharge loss): 0.8 x p d. Inlet (hood only): 0.3 x p d. (p d = dynamic pressure, related to velocity in duct).

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 34 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans


ptF = ps2 pt1 + y pdF ptF = total pressure, fan ps2 = static pressure pt1 = total pressure pdF = dynamic pressure, fan

Products

Diffusers By mounting a diffuser on the outlet side of the axial flow fan some of the dynamic loss which is generated when lowering the air velocity is recovered for static pressure, thus ensuring a better fan efficiency. This especially applies to free outlet fans, where the entire velocity energy otherwise would be lost. The diffusers for Novax fans are designed to obtain optimum recovery of the dynamic energy. The design pressure (ptF) of the fan is calculated according to the following formula: Recovery factor, y
Installation
Without diffuser With short diffuser With long diffuser

The recovery factor y is an expression for the reduction of the correction value 'a' under various installation conditions as stated in the opposite table.

Duct on outlet
1* a x 0.1 + 0.63 a x 0.15 + 0.40

Free outlet without duct


a a x 0.1 + 0.81 a x 0.15 + 0.47

* Measured combination in the computer selection program according to BS-848. For correction value a, please see the next page.

Example Fan type ACG, 1470 rpm with free outlet. qv = 20 m3/s. ps = 500 Pa. The following options are available in the Novax computer selection program: ACG-1250/403-6 41.9. a-factor: 1.25. pdF: 159 Pa, or: ACG-1400/403-6 37.8. a-factor: 1.19. pdF: 101 Pa. Calculation of ptF for fan without diffuser: ACG-1250: ptF = 500 0 + 1.25 x 159 = 699 Pa. ACG-1400: ptF = 500 0 + 1.19 x 101 = 620 Pa. Calculation of ptF for fan with long diffuser: ACG-1250: ptF = 500 0 + (1.25 x 0.15 + 0.47) x 159 = 604 Pa. ACG-1400: ptF = 500 0 + (1.19 x 0.15 + 0.47) x 101 = 565 Pa. The following calculation in the computer program (enter the calculated ptF) only applies to the specific type. The actual power saving when mounting a long diffuser will be: For ACG-1250/403-6: 17.5 15.0 = 2.5 kW. For ACG-1400/403/6: 15.7 14.3 = 1.4 kW.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 35 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Installation corrections
The Novax fan performance data have the normal installation methods of the fans. Correction value a The correction value a (from the computer selection program) is a loss factor, which, after multiplication by pdF, must be added to the calculated fan pressure (psF) at free outlet (arrangements A and C), or at a sudden change to a larger duct dimension than the fan outlet. The 'a' factor is related to the velocity loss (pd) resulting from the difference in the air velocity of the net area of the fan (the blade area) and the gross area of the outlet opening. The effect of the 'a' factor is reduced by mounting a diffuser on the outlet of the fan. See the previous page. For fans with duct connection on the outlet and unchanged dimensions (arrangements B and D) the 'a' factor is included in the published performance data and no correction is necessary. Duct on inlet and outlet Type ACA ACN ACW ACD (Arrangement D) ptF = pt2 pt1 = (ps2 (-ps1) + (pd2 pd1) if pd2 = pd1; ptF will be = (ps2 (-ps1)) Duct on inlet and free outlet Type ACA ACN ACW ACD (Arrangement C) ptF ptF = ps2 + (a x pdF) pt1 = ps2 ps1 + (a x pdF) pd1 psF
Designations and definitions Symbol
Mass flow Air quantity, volume flow Inlet diameter Outlet diameter Density Flow area Mean velocity of plane x Static pressure of plane x Dynamic pressure of plane x Total pressure of plane x Total pressure of fan Dynamic pressure of fan Static pressure of fan System loss Power consumption Correction value qm qv D1 D2 r A cx psx Pdx ptx ptF pdF psF pt p a

Unit
kg/s m3/s mm mm kg/m3 m2 m/s Pa Pa Pa Pa Pa Pa Pa kW

Formula
q v ----

q v ----Ax 0.5 x c2 psx + pdx 0.5 x c2 ptF pdF

Pressure (Pa) ptF = pt2 pt1 = ps2 + pd2 (ps1 + pd1) = (ps2 ps1) + (pd2 pd1) = ptF pdF (Definition). All inlet sizes of the fan are designated by subindex 1 and all outlet sizes by subindex 2.

Free outlet to the atmosphere gives pd2 = 0 and ps2 = 0

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 36 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Free inlet and duct on outlet Type ACG (Arrangement B) 1) With free inlet from the atmosphere where pt1 = 0 Pa ptF = ps2 + pd2 = psF + pdF 2) With inlet from chamber where pt1 0 Pa ptF ptF = ps2 + pd2 pt1 = ps2 + Pd2 (ps1 + pd1) 3) With inlet from a very large room where pd1 0 Pa pEF = ps2 ps1 + pd2

Free inlet and outlet Type ACP (Arrangement A) pdf = ps2 ps1

Run up time of axial flow fans


The run up time of axial flow fans is calculated on the basis of the formula: ts =
0.24 n ( Im + I v ) ---------------------------------------------------------- M s Mk Pv 4 10 P ------ + ------ ----- M M P
2

Where = run up time (S) = rated output of motor (kW) = required power of fan (kW) = fan speed (rpm) Ms ------ = the ratio between the starting torque of the M motor and the nominal torque. Mk ------ = the ratio between the maximum torque of the M motor and the nominal torque. Iv = the polar moment of inertia of the fan (kgm2) Im = the polar moment of inertia of the motor (kgm2) ts P Pv n

Please note that according to the international standards the torque of the motor can vary within the following limits: Ms: -15% + 25% of the catalogue value Mk: -10% + 0% of the catalogue value The above factors may increase the run up time more than calculated.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 37 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Smoke Extract Fans


The axial flow fans types ACN smoke and ACW smoke meet the requirements for smoke extract fans according to EN12101-3. EN12101-3 is a standard for smoke extract fans which lays down rules of how to verify the applicability of a product range within specified rules based on tests made on selected fans.
ACN size: Diameter/ Hub
ACN 400/160 ACN 400/230 ACN 500/160 ACN 500/230 ACN 500/280 ACN 500/330 ACN 560/230 ACN 560/280 ACN 560/330 ACN 560/380 ACN 630/230 ACN 630/280 ACN 630/330 ACN 630/380 ACN 710/230 ACN 710/280 ACN 710/330 ACN 710/380 ACN 800/230 ACN 800/280 ACN 800/330 ACN 800/380 ACN 900/280 ACN 900/330 ACN 900/380 ACN 900/403 ACN 900/578 ACN 1000/380 ACN 1000/403 ACN1000/578 ACN 1120/403 ACN 1120/578 ACN 1250/403 ACN 1250/578 ACN 1400/403 ACN 1400/578 ACN 1600/578 90 90/100 90 90/100 90/100/112 90/100/112/132 90/100 90/100/112 90/100/112/132 90/100/112/132/160 90/100 90/100/112 90/100/112/132 90/100/112/132/160/180 90/100 90/100/112 90/100/112/132 90/100/112/132/160/180 90/100 90/100/112 90/100/112/132 90/100/112/132/160/180 90/100/112/132/160/180 132/160/180 132/160/180/200 132/160 160/180 90/100/112/132/160/180 132/160/180 132/160/180/200 112/132/160/180 132/160/180/200/225 112/132/160/180 132/160/180/200/225/250 132/160/180 160/180/200/225/250/280 200/225/250/280

Furthermore, the calculation and engineering data were checked with a view to verifying whether the rules laid down in EN12101-3 are being observed Size Novax Smoke Extract Fans are as standard designed in 12 sizes with blade diameters from 400

High-temperature special motors: (Motor size)

mm to 1600 mm and hub diameters from 160 to 578 mm. Number of blades For hub 160 mm: 4 blades For hub 230 mm: 6 blades For hub 280 mm: 8 blades For hub 330 mm: 10 blades For hub 380 mm: 12 blades For hub 403 mm: 6 blades For hub 578 mm: 10 blades The following types of Novax smoke extract fans have been found to conform to EN12101-3 category C1: 300 C/1 hour. Please contact YORK Novenco for details on selection of Novax smoke extract fans.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 38 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Pump Room Fan type HGP


Product and Application
Axial flow fan with adjustable blades for application in marine ventilating system. The axial flow fan type HGP is for duct connection with direct outlet.

Materials and Surface Treatment


Hub Sendzimir galvanized sheet steel Blades Aluminium.

Range
mm.

9 sizes with impeller diameters from 315 to 1120 Air quantities from 0.18 to 22 m /s and total pressures up to 1300 Pa in duct suction side.
3

Casing and static parts Welded sheet steel, hot dip galvanized Wire guard AISI 304, mesh 13 x 13 mm

Number of Hub Diameters


5 - from 160 to 578 mm.

Corrosion Classification
12944.
Number of blades
4 6 10 12 10

As standard class C3 according to EN ISO 12944

Number of Blades
Hub dia. mm
160 230 330 380 578

and C5-1 (Very high) according to DS/EN ISO The standard designs of HGP fans are intended for operation in marine environments.

Duct on inlet and free outlet


Type HGP (Arrangement C) PtF = ps2 + (a pdF) pt1 PtF = ps2 ps1 + (a pdF) pd1 Free outlet to the atmosphere gives pd2 = 0 and ps2 = 0

Motors

Asynchronous motors. Dimension standard: IEC-72. Electrical standard: IEC-34. Insulation: Class F. Foot-mounted motors. Flame proof

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 39 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Drain pipe

Front

Back

The axial flow fan type HGP is applicable for ventilation of pump rooms and as fan in mechanical ventilating systems in which explosive gases might appear. It is designed according to the rules of the classification societies for Non-sparking fans for hazardous locations on board ships. Type HGP complies with the requirements of the classification societies for fans handling explosive gases. Flame-proof motor mounted outside the air stream Bearing assembly incorporating seals prevents gases from penetrating into the motor. Impeller cast in aluminium alloy rules out the risk of sparking in case of contact with the casing. HGP is available in 9 sizes from 315 mm to 1120 mm. Performance from 0.18 m3/s to 22 m3/s.

bearing housing and an external flexible coupling. The coupling is of spark proof design. The Novax rotor (the impeller) consists of two assembled hub discs with cavities to house the blades at preset angles. The rotor is provided with a hub boss for mounting onto a motor shaft. The cast aluminium blades of the rotor can be factory adjusted to any angle between 25 and 60, dependent on size and speed. The hot dip galvanized fan casing is provided with flanges on the inlet side according to DIN 24154 and with a wire guard of rustless steel type AISI 304 with a mesh size of 13 x 13 mm on the outlet side.

Description

HGP is a sturdy fan with flange on the inlet side especially designed for installation on stand-pipe on deck of a ship. The fan is upward blowing and consists of a fan casing, an impeller, an explosion proof electric motor and a coupling arrangement consisting of a
All outside machined surfaces must be treated with Dinitro 112. Type HGP 315/160 400/230
80 B 90 L 50 Hz Motor 80 B 100 L 80 B 90 L 60 Hz Motor 80 B 100 L

500/330
90 L 100 L 132 S 90 L 112 M 132 S

630/380
100 L 132 M 160 L 100 L 112 M 132 M

710/380
132 S 160 L 112 M 132 S

800/380

900/578

1000/578
160 L

1120/578
180 L 225 S

132 M 132 M 160 M

180 M 180 M 200 L

200 L 160 L 200 L 225 S

180 L

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 40 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax HGP Dimensions


Positions according to DIN 24154

Px R
Size HGP (impeller diameter) HGP-315 HGP-400 HGP-500 HGP-630 HGP-710 HGP-800 HGP-900 HGP-1000 HGP-1120
A B C D1 D2 D3 L P R a b c d Weight, kg 536 400 8 315 366 402 800 8 12 295 335 170 190 69 676 500 8 400 448 487 985 12 12 342 430 213 236 104 846 630 8 500 551 587 1178 12 12 392 530 256 296 163 1046 800 10 630 698 735 1426 16 14 448 690 288 360 241 1146 900 10 710 775 815 1463 16 14 465 710 288 356 266 1286 1000 10 800 861 905 1639 24 14 509 800 330 400 329 1448 1120 10 900 958 1027 1913 24 14 639 900 374 450 599 1608 1250 10 1000 1067 1127 2097 24 14 691 1000 406 500 717 1798 1400 12 1120 1200 1247 2311 32 18 742 1120 449 560 862

Weight without motor

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 41 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 50 Hz The curves are based on air density r = 1.20 kg/ the blade pitch, form part of the type designation, e.g. HGP-315-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. m3. The curve numbers (30 to 55), representing

HGP-315 1380 r.p.m.


80

Static pressure, Pa

60

40

20

0 0
0.07

30 0.1 0.2 0.3

35 0.4

40

55 45 50 0.5

Power consumption, kW

Motor for -315 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-080.

0.06 0.05 50 0.04 45 0.03 40 0.02 0.01 0 0.1 0.2 30 35

55

0.3

0.4

0.5

Air flow rate, m /s

HGP-315 2790 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 42 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 50 Hz The curves are based on air density r = 1.20 kg/ the blade pitch, form part of the type designation, e.g. HGC-400-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. Motor for -400 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-080, DNGW-100. m3. The curve numbers (30 to 55), representing

HGP-400 1450 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

HGP-400 2880 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 43 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 50 Hz The curves are based on air density = 1.20 kg/ the blade pitch, form part of the type designation, e.g. HGP-500-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. Motor for -500 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-090, DNGW-100 and DNGW-132. m3. The curve numbers (30 to 55), representing

HGP-500 1450 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

HGP-500 2905 r.p.m.


1600 1400

Static pressure, Pa

1200 1000 800 600 400 200 0 0 1 2 30 35 40 3 45 4 50 55 5

Power consumption, kW

6 55 5 4 3 2 35 1 0 0 2 30 1 3 4 5 40 45 50

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 44 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 50 Hz The curves are based on air density = 1.20 kg/ m3. The curve numbers (30 to 55), representing the blade pitch, form part of the type designation, e.g. HGP-630-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. Motor for -630 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-100, DNGW-112, DNGW-132 and DNGW-160.

HGP-630 1450 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

HGP-630 2920 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 45 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 50 Hz The curves are based on air density = 1.20 kg/ the blade pitch, form part of the type designation, e.g. HGP-710-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. Motor for -710 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-132. m3. The curve numbers (30 to 55), representing

HGP-710 1450 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

HGP-710 2880 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 46 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 50 Hz The curves are based on air density = 1.20 kg/ m3. The curve numbers (30 to 55), representing the blade pitch, form part of the type designation, e.g. HGP-800-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. Motor for -800 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-132 and DNGW-160. Motor for -900 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-180 and DNGW-200.

HGP-800 1450 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

HGP-900 1450 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 47 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 50 Hz The curves are based on air density = 1.20 kg/ the blade pitch, form part of the type designation, e.g. HGP-1000-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. Motor for -1000 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-160, DNGW-200 and DNGW-225. Motor for -1120 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-180 and DNGW-225. m3. The curve numbers (30 to 55), representing

HGP-1000 1450 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

HGP-1120 1450 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 48 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 60 Hz The curves are based on air density = 1.20 kg/ m3. The curve numbers (30 to 55), representing the blade pitch, form part of the type designation, e.g. HGP-315-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980.

HGP-315 1750 r.p.m.

Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-080.

Power consumption, kW

Motor for -315

Static pressure, Pa

Air flow rate, m3/s

HGP-315 3490 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 49 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 60 Hz The curves are based on air density = 1.20 kg/ m3. The curve numbers (30 to 55), representing the blade pitch, form part of the type designation, e.g. HGP-400-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980.

HGP-400 1770 r.p.m.

Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-080, DNGW-090 and DNGW-100.

Power consumption, kW

Motor for -400

Static pressure, Pa

Air flow rate, m3/s

HGP-400 3490 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 50 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 60 Hz The curves are based on air density = 1.20 kg/ m3. The curve numbers (30 to 55), representing e.g. HGP-500-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980.

HGP-500 1770 r.p.m.


400

Static pressure, Pa

the blade pitch, form part of the type designation,

300

200

100

30 0 1

35

40 2

45

50

55 3

Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-090, DNGW-100 and DNGW-132.

Power consumption, kW

Motor for -500

1.5 55 1 50 45 0.5 35 40 30 0 0 1

Air flow rate, m /s

HGP-500 3490 r.p.m.


1500

Static pressure, Pa

1000

500

30 0 1 2 3

35

40 4

45

50 5

55

Power consumption, kW

10

55 50

5 40 30 0 0 1 2 35

45

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 51 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 60 Hz The curves are based on air density = 1.20 kg/ the blade pitch, form part of the type designation, e.g. HGP-630-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. Motor for -630 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-100, DNGW-112 and DNGW-132. Motor for -710 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-112 and DNGW-132. m3. The curve numbers (30 to 55), representing

HGP-630 1770 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

HGP-710 1770 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 52 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 60 Hz The curves are based on air density = 1.20 kg/ the blade pitch, form part of the type designation, e.g. HGP-800-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. Motor for -800 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-132 and DNGW-160. Motor for -900 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-180 and DNGW-200. m3. The curve numbers (30 to 55), representing

HGP-800 1770 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

HGP-900 1770 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 53 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 60 Hz The curves are based on air density = 1.20 kg/ m3. The curve numbers (30 to 55), representing the blade pitch, form part of the type designation, e.g. HGP-1000-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980.

HGP-1000 1165 r.p.m.

Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-160, DNGW-200 and DNGW-225.

Power consumption, kW

Motor for -1000

Static pressure, Pa

Air flow rate, m3/s

HGP-1000 1770 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 54 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Novax axial flow fan type HGP


Performance Curves - 60 Hz The curves are based on air density = 1.20 kg/ the blade pitch, form part of the type designation, e.g. HGP-1120-45. The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980. Motor for -1120 Mounting B3 (form A, DIN 42673) Class F insulation. Enclosure IP56. Flameproof enclosure EEx de IIC T4. Type DNGW-180. m3. The curve numbers (30 to 55), representing

HGP-1120 1165 r.p.m.

Power consumption, kW

Static pressure, Pa

Air flow rate, m3/s

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 55 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Axial Flow Fan type HGC


Product and Application
The axial flow fan type HGC is applicable for ventilation of pump rooms and as fan in mechanical ventilating systems in which explosive gases might occur and is designed according to the rules of the classification societies for Non-sparking fans for hazardous locations on board ships. Type HGC complies with the requirements of the classification societies for fans handling explosive gases. Flame-proof motor mounted outside the air stream. Bearing assembly incorporating seals prevents gases from penetrating into the motor. Impeller cast in aluminium alloy rules out the risk of sparking in case of contact with the casing.

The impeller, consisting of a hub and a number of aerofoil blades, is carefully balanced statically as well as dynamically. The Novax rotor (the impeller) consists of two assembled hub discs with cavities to house the blades at preset angles. The rotor is provided with a hub boss for mounting onto a shaft. The blades of the rotor can be factory adjusted to any angle between 25 and 60, dependent on speed of rotor. The bearing assembly comprises deep-grove ball bearings (lubricated for life), shaft, housing, flexible coupling and gas-tight seals.

Range

The fan is available with impeller diameter 250 mm and hub diameter 160 mm. Air quantities from 0.1 to 0.5 m3/s and total pressures up to 250 Pa in duct suction side.

Description
Axial flow fan type HGC consists of fan casing, weather hood, impeller, bearing assembly and electric motor. The fan casing is designed with a view to attaining the best possible flow condition and the lowest possible loss in pressure. On the inside it is provided with a brass lining opposite to the impeller. The lower edge of the casing is provided with a flange for mounting the fan on top of a standpipe or post. A protective screen of galvanized wire is fitted at the upper end of the casing. The weather hood consists of a low conical top plate and a skirt providing effective protection against rough weather and spray.

Materials and Surface Treatment


Casing Heavy gauge steel plate, hot-dip galvanized and brass lining. The weather hood Heavy gauge steel plate, hot-dip galvanized. Blades Aluminium alloy (cast).

Motors

The motor, naturally cooled, is flame-proof in compliance with EEXde II C T4, approved by the classification societies. The fan can be mounted with the following 3 motor frame sizes 71 - 80 -90.

Fran size
250

A
594

H*

C
319

D
250

E
292

G
330

J
8

K
11,5

T
8

Weight/kg**
17

* H-dimension depends on motor size. ** Excl. motor

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 56 of 58 5.1 Axial Flow Fans

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Performance Curves HGC-250/160


Total pressure, Pa

300

60 Hz 3490 rpm max. 0.4 kW

200

50 Hz 2790 rpm max. 0.2 kW

100 60 Hz 1770 rpm max. 0.06 kW

50 Hz 1380 rpm max. 0.03 kW 0 0 0.1 0.2 0.3 0.4 0.5 0.6 Air flow, q, m/s
3

The above curves show the exhaust capacity of the fan type HGC-250/160.

The fan performance is for duct connection for inlet and free discharge The curve are based on measurements in a measuring set-up giving the same result and using the same definitions as AMCA 210-1985 and BS 848 part 1 1980.

Motor for 250/160 Mounting B5 Class F insulation Enclosure IP56 Flameproof enclosure EEx de IICT4.

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice 5.1 Axial Flow Fans Page 57 of 58

HI-PRES MARINE & OFFSHORE

5.1 Axial Flow Fans

Products

Owing to continued product development YORK Novenco reserves the right to introduce alterations without prior notice Page 58 of 58 5.1 Axial Flow Fans

S-ar putea să vă placă și