Sunteți pe pagina 1din 6

ABB

ABB High Voltage Switchgear (Xiamen) Co.Ltd

220kv GIS
Guide of site testing of 220kv GIS
1

Voltage Drop Measurement of Main Circuit

SF6

GIS

GIS

Density relay Check


Compartment Leakage Check
SF6

Humidity Measurement
Earthing Check

VCT CT

VCT and CT Testing

SA

Surge Arrester Testing

Circuit Breaker Function Testing

Control Circuit Check

10

HV Testing of Main Circuit

11
12

HV Cable Testing
GIS

Remote Control Check

Page 1/5

5
D [2008-3-25]

ABB
ABB High Voltage Switchgear (Xiamen) Co.Ltd

Voltage Drop Measurement of Main Circuit


Purpose: To check whether the connection is good according to the default values. The default
values are listed on operation manual and factory routine test reports.
Testing equipment: Primary test system.
1

GIS
GIS

2
3

100A

Programma

4
4.1
4.2
4.3
4.4

E01
E01
E05
E05

E02Q8
E04Q8
E02Q8
E04Q8

E01
E01
E01
E01

Density relay Check

SF6

Purpose: To verify the preset value of density relay is consisted with design.
Testing equipment: Density monitor test set
1
2
3
4

SF6
SF6
SF6
GIS
)

Compartment Leakage Check

Purpose: To check the leakage rate of gas compartment.


Testing equipment: Leak-seeker
1
2
3
4

LS-790B
0.5%
GIS

(24
Page 2/5

SF6

5
D [2008-3-25]

ABB
ABB High Voltage Switchgear (Xiamen) Co.Ltd

) Humidity Measurement
Purpose: To check gas humidity of gas compartment.
Testing equipment: Dew-point measurement.
1
2
3

GIS

SF6
DP19

SF6

150PPM

250PPM

24
PPM
Earthing Ckeck

Purpose: To check the tightness of earthing connection.


Equipment: Torque wrench.
GIS

GIS
(

VCT

VCT and CT Testing

CT

Purpose: To check the character of VCT and CT.


Testing equipment: Character measurement device of transformer.
CT

1
CT
PT

PT

CT
PT
CT

PT

CT

PT

PT

CT
PT
CT PT
CT
SA

CT
PT

10KV

PT
Surge Arrester Testing

Purpose: To check the character of Surge Arrester.


Testing equipment: Character measurement device of Surge Arrester.
Page 3/5

5
D [2008-3-25]

ABB
ABB High Voltage Switchgear (Xiamen) Co.Ltd

SA

GIS
2
3

4
GIS
GIS

GIS
GIS
PT

Circuit Breaker Function Test


Purpose: To check the character of circuit breaker.
Testing equipment: Breaker analyzer system.
1

OCO

2
3

TM1600

010A

60ms
T 4 ms
21ms
T 2 ms
120s
6A/DC110V
3A/DC220V.
3A/DC110V 1.5A/DC220V.
6A/DC110V 2A/DC220V.
4
4.1

(
)

4.2
4.3
/
4.4

OCO
Page 4/5

5
D [2008-3-25]

ABB
ABB High Voltage Switchgear (Xiamen) Co.Ltd

Control Circuit Check


Purpose: To check the reliability of control circuit.
Equipment: Digital multimeter.
1
2
3
4

1KV
(
CT

PT

CT

PT

HV Testing of Main Circuit


Purpose: To verify the insulate capability of GIS.
Testing equipment: HV testing device.
1

GIS
(1

2
3
4
4.1

80%

A
B
C
D
4.2
4.3
4.4
4.5
4.6
5
5.1
5.2
5.3
5.4
GIS

PT

PT

GIS

63.5KV

PT

PT

PT
PT
GIS
24

CT
GIS

GIS
GIS

GIS

3KV

/
184KV

GIS A B C

5.5
5.6

GIS

Page 5/5

5
D [2008-3-25]

ABB
ABB High Voltage Switchgear (Xiamen) Co.Ltd

220KV

110KV

HV Cable Test

Purpose: To verify the insulate capability of HV cable.


Testing equipment: HV testing device.

GIS

24
GIS

GIS

Remote Control Check

Purpose: To check the reliability of remote control.


Equipment: Digital Multimeter.

Page 6/5

5
D [2008-3-25]

S-ar putea să vă placă și