I N ST A L LA T I ON I N S T R U C T I O S N
Features
Actuatorcan be m ountedin four differentpositions Perpendicular ountingflangeand squaredrive headelim inatelateral m forces on the stem Blow-outproof stem with thrust-bearing Teflon disc anddoubleO-ring designfor long service life* Thermalisolatingadapterbetween flangeand actuator Easydirect couplingof actuatorwith a singlescrew Non-corroding chrome-plated brass
Characterizing madeof Tefzel /Brassknownfor excellent disc strength and chemical resistance
Teflon seatswith O-ringsprovideconstantseatingforce againstthe ball and reducetorque requirement* Regulator Assembly Vent holesreducecondensation build-upin stem area
N C/F Valve Valve O : Closed-w ill open as voltageincreases. Actuatorswitch on CW. SpringAction: Will spring open upon power loss.
N C/F Valve Valve C : Closed-will open as voltageincreases. Actuatorswitch on CW. SpringAction: Will spring closedupon powerloss.
N O /F Valve Valve O penC : will close as voltage increases. Actuator switch on C CW. Spring Action: Will spring closedupon power loss.
N O /F Valve Valve O penO : w ill close as voltage increases. Actuator switch on C CW. Spring Action: Will spring open upon powerloss.
P IC C V s with MFT actuatorsare dependent their Minim um and M axim umPercentages rotation. on of Actuatorsmust be re-programmed differentMinimum and MaximumSettingsif actuatorset-upsmust be changed. for P leasecontactTechnical Salesfor information.
PIC C V s shall be installed,w ith flow in the directionof the arrow on the valve body. If installed backwards,there could be dam ageto either the diaphragmor the regulatortop. T he valveassem blycan be installed a verticalor horizontal in arrangem ent, long as the actuatoris positionedto avoid as condensation from drippingon theactuator.
800-543-9038 USA
866-805-7089 CANADA
2 2
Installation
Flow Pattern
P IC C Vcon sistsof a d ifferential pressureregulatorin serieswith a controlvalve. T he am ountof flow that passesthroughthe valveis controlledby the use of a pressureregulatorthat m ovesaccordingto the change in pressureaboveand below it. All pressurechangesare absorbed the pressureregulator allowing by the differentialpressureto be held constantover the control valve sectiontherebygiving the sam eflow.
Regulator Section C o n troValve l S ection
Ports sensepressuredrop and transferit through this channel belowregulator. Low pressurepulls regulatordown againstthe spring force.
PICCV Performance
Operating Differential Range of 5 50 PSI
14 12 10 8 6 4 2 0 0 5 10 15 20 25 30 35 40 45
50
% Ball Opening
100%
Assembly PressureIndependentCharacterizedControlValves ( IC C V ) (P
Warning! Valve shouldnot be usedfor com bustiblegas applications. as leaks and explosions G may result.Do not install in systems,which exceedthe ratingsof the valve. Avoid installationswhere valve m ay be exposedto excessive moisture,corrosive fumes,vibration,high ambienttemperatures, elements,or high traffic areas with potentialfor mechanical damage. Valve assemblylocationmust be within ambientratings of actuato If temperature r. is below -22F a heateris required. The valveassem blywill requireheat shielding,thermalisolation,or coolingif combined effectof mediumand ambienttemperatures conduction, convection, and radiation is above122Ffor prolongedtime periodsat the actuator. Visualaccessmust be provided.Assem bly ust be accessible routineschedule m for service. Contractorshouldprovideunionsfor removalfrom line and isolationvalves. Avoid excessive stresses. Mechanical supportmust be provided wherereducershave beenused and the piping systemmay haveless structuralintegrity than full pipe sizes. Sufficientupstreamand downstream piping runs must be providedto ensureproper valvecapacityand flow response.Five diam etersin each directionare recommended. Life span of valvestems and O -ringsis dependent maintainingnon-damaging on conditions.Poor water treatmentor filtration, corrosion,scale,other particulatecan result in dam ageto trim com ponents. watertreatm entspecialistshould be consulted. A
Mounting If field installinga spring return actuato disconnect r, powerand allowactuatorto spring closed.Flip actuatorover if necessay to achieveproper rotation direction. D O N O TU S E r T H ER E V E R S IN G IT C H D O THIS. SW TO Two-way Valves Mounting For NORMALLY CLOSED operation: The ball of the valvemust be rotatedso that the ball is C L O S E D flow. The actuator to shouldbe mountedwith the clampfully rotatedCW (R). Springreturn actuatorswill show the CW (R) sym bolnearthe clam p and position indicato. Depressing gearreleaseto r the move the clamprotatesnon-springreturn actuators. For NORMALLY OPEN operation: The ball of the valvemust be rotatedso that the ball is O P E Nto flow. The actuatorshould be mountedw ith the clam p fully rotatedCCW(L). Spring return actuatorswill show the C C W(L) sym bolnearthe clam p and positionindicato. Depressing gearreleaseto r the move the clamp rotatesnon-springreturn actuators.Thereare marks on the top of the valvestem , which indicatethe port directions.See the drawingson the followingpages.
1. 2. 3. 4. 5. 6.
7.
8. 9. 10.
800-543-9038 USA
866-805-7089 CANADA
Inspectshippingpackage, valve,linkage,and actuatorfor physicaldam age. If shippingdamagehas occurred notify appropriate carrie Do not install. r. If a replacem entrem ov existin valve linkag and actuato from the pipin system. , e g , e r g If actuatorand linkageare rem oved,they m ust be reinstalled correctl The y. actuatormust be rotatedso that the valveseatsproperlyfor close off. Install valvewith the proper ports as inlets and outlets. Flow directionarrows must be correct. Blow out all piping and thoroughly cleanbeforevalveinstallation. Cleanm ale pipe threadswith wire brush and rag. If threadshavebeendam aged or exposedto weathe, running a tap or die over the threadsmay straightenthem. r Cleanpipes,threads,and valvethreadsbeforeinstallation; check any foreign for materialthat can become lodged trim com ponents. in Strainersshould be cleaned after initial startup. Pipe sealingcom poundshould be applied sparinglyafter cleaningand may not be appliedto the two lead threadsof a screwedpipe, which are innermostinside the valve.Sealing com pound to be placedon m ale threadsonly. The purposeis to is lubricatethe pipes when tightening. Valve must be installedwith the stem towardsthe vertical,not below horizontal. Start the connectionby turning the valveor pipe by hand as far as possible.Be certainthe threadsmate by the feel of the connection. Use wrenches tighten the valveto the pipe. Do not over tighten or strip the to threads.Two wrenchesare necessay to avoid dam aging valve. r the
Assembly:
1 2 3 4 One screw attaches actuator to valve Four actuator mounting positions 2-way flow pattern Top of valve stem and arrow indicates direction of flow
CCW
4
Closed
Open
800-543-9038 USA
866-805-7089 CANADA
4 1
1 4
.9 .8
.9 .8
3 2 2
33 ... 100% Y= 0 Y = 0
.9 .8 .7 .6 .5 .4 .3
FO
FC
.2
.2 .4 .6 .8
Closed
Closed
Open
Open
Closed
Closed
AB
AB
Open
Open
Non-Spring Return
LR AR LF
Spring Return
AF
1 L
0 R
L
1 L 0 R
R CW
L CCW
R CW
CCW
R CW
Reversing switch and the direction the clamp is placed in before tightening the clamp determine the NO, NC relations.
CCW
Reversing switch and the choice of which side of the actuator to the actuator is placed on the valve determines the NO, NC relations.
All directions are looking down onto top of valve and actuator. Non-Spring Actuators: CW CCW R L Y=1 Y=0 Y is the signal voltage. Spring Return Actuators must be mounted so that the spring brings the actuator to the failsafe position the reversing switch does not affect the spring. It has an effect only on electrical NO, NC signal direction.
When replacing other valves note that the port designations may not be the same as the Belimo nomenclature. NO, NC, Common
or In and Out and variations of the Belimo designated may exist. DO NOT USE THE REVERSING SWITCH TO ATTEMPT TO COMPENSATE FOR INCORRECT MECHANICAL MOUNTING.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
The Pressur IndependenCharacterizeContro Valves can be piped in a parallel e t d l orientatio to achiev increase flow rates. n e d O ur PICC valve are availabl in flows to 100 GPM To achiev flows large than V s e . e r this, it is recommende to connec two of these valve in paralle leadin to a d t s l g commo m anifold To correctl operat these valves the Belim Mult Function n . y e , o i Technolog (MFT will be em ploye to utilize one commo contro signal. y ) d n l For examplethe first valve will be outfitted with an MFT actuato that will , r correspon to a 2-5 or 2.6 VDC signal The secon valv w oul be outfitte with an d . d e d d MFT actuato that woul correspon to a 6-10 VDC signal Thereforethrough a r d d . , singl 2-10 VDC output the full flow rang will be achievedThe actuators e , e . will be wired in a paralle arrangement The establishe configure P Code are l . d d s P-1013 for 2-5 VDC P-1011 for 2-6 VDC and P-1011 for 6-10 V DC. 7 , 8 , 9 This recomm ende applicatio provide the contro of flows up to 200 GPM by d n s l using two valves The top diagra detail valve piped in a paralle arrangement. . m s s l The botto diagra feature a typica singl pipin arrangement. m m s l e g If more than three valve are piped in parallel pleas call Belim to discuss s , e o contro options. l
H/CCOIL
P/T PORT
FLOW
P/T PORT
P/T PORT
DRAIN
FLOW
P/T PORT
P/T PORT
FLOW
8 8
9 9
Type 2-way NP T P2050B005 P2050B010 P2050B015 P2050B020 P2050B030 P2050B040 LF24-MFT US P2050B050 P2075B060 P2075B070 P2075B080 P2075B090 P2075B100 P IC C V-25-012 P IC C V-25-014 P IC C V-25-016 P IC C V-25-018 P IC C V-32-018 P IC C V-32-020 P IC C V-32-022 P IC C V-32-024 P IC C V-32-026 P IC C V-40-026 P IC C V-40-028 P IC C V-40-030 P IC C V-40-033 P IC C V-50-033 P IC C V-50-040 P IC C V-50-044 P IC C V-50-048 P IC C V-50-052 P IC C V-50-056 P IC C V-50-060 P IC C V-50-065 P IC C V-50-070 P IC C V-50-075 P IC C V-50-080 P IC C V-50-090 P IC C V-50-100 P IC C V-50-036 TF24-MFT US
Inches 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2
DN [mm] 15 15 15 15 15 15 15 20 20 20 20 20 25 25 25 25 32 32 32 32 32 40 40 40 40 50 50 50 50 50 50 50 50 50 50 50 50 50 50
LRX24-MFT
LRB24-3
PICC CV
Applications Water-side control of heatingand cooling systems,for AHUs,re-heatcoils, fan coil units, unit ventilatorsand heat pumps. Mode of Operation The Pressure Independent Characterized ControlValve is a two-wayvalvewhich com binesthe functionalityof a control valveand a pressureregulatingvalve,creatingone preciseproductwhich is unaffected pressure by variations in a system. Product Features Constantflow regardless pressurevariationsin of the system at every degreeof ball opening.Maximizes chiller T, preventing energizingadditionalchillers due to low T. Simplifiedvalvesizingand selection, Cv no calculations required. Actuator Specifications Controltype FloatingPoint,Non-Spring Multi-Function Technology (MFT) Non-Springand SpringReturn Manualoverride LR B,LRX ,LRC ,AF, A RX Electrical connection 3 ft [1m] cablewith conduit fitting (additional cablelengthsare available) Valve Specifications Service Flow characteristic Controllable flow range S izes Type of end fitting Materials Body Ball Stem S eat
30 33 33 36 40 44 48 52 56 60 65 70 75 80 90 100
AF24-MFT US
ARX24-MFT
forgedor cast brass,nickelplated chromeplatedbrass chromeplatedbrass Teflon P T F ESet Oring Viton Characterizing disc & brass 1- 2 T E F Z E L Packing 2 E PDMO-rings, lubricated Diaphragm & Nome reinfo x rced silicone 1- 2 polyeste reinfo r rced silicone Regulato component stainles steel/brass/Delri500AF r s s n Spring stainlesssteel Pressure rating 600 psi , , 1 400 psi 1, 1, 2 Mediatemp range 0F to 212F[-18C to 100C] C loseoff pressure 200 psi Maximumdifferential 5 to 50 psid pressureacrossvalve (range) Leakage ANSIClassIV (0.01% of rated valvecapacityat 50 psi differential)
Te fze is a registeredtradem ark DuPont l of
800-543-9038 USA
P2... Series PressureIndependentCharacterizedControlValves (PICCV) ChromePlated Brass Ball and B rass Ste m , N P TF em aleEnds
Application
The PressureIndependent Characterized ControlValve is typicallyused in air handlingunits on heatingand coolingcoils, and fan coil unit heatingor cooling coils. Someother commonapplications includeunit ventilatorsand VAV re- heat coils. This valveis suitablefor use in a hydronicsystemwith constantor variableflow. This valveis designed with MFT functionalitywhich facilitatesthe use of various control input. Valve Nominal Size Inches Close-off PSI 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 DN mm
SuitableActu ato rs
Valve Model Technical Data Service Flow characteristic S ize Type of end fitting Materials Body Ball Stem S eatO-rings S eat Characterizing disc Packing Diaphragm Regulator components Spring Bodypressurerating Mediatemp. range Closeoff pressure Leakage Rangeability Differential pressure Valve accuracy Weight of valvebody chilledor hot water, 60% glycol equalpercentage , , 1 fem ale,NPT forgedbrass,nickelplated chromeplatedbrass chromeplatedbrass Viton Teflon PTFE & Brass 1 T E F Z E L 2 EPDMO-rings,lubricated & Nom exreinfo rced silicone 1 polyesterreinfo rced silicone stainlesssteel/brass stainlesssteel 600 PSI 0F to 212F[-18C to 100C] 200 PSI ANSIClassIV (0.01% of ratedvalve capacityat 50 psi differential) 100 : 1 5 to 50 PSID operatingrange 10% combination manufacturing of tolerances pressurevariations and = 2.52lbs = 2.52lbs 1 = 4.98lbs P2050B005 P2050B010 P2050B015 P2050B020 P2050B025 P2050B030 P2050B035 P2050B040 P2050B045 P2050B050 P2050B055 P2075B060 P2075B065 P2075B070 P2075B075 P2075B080 P2075B085 P2075B090 P2075B095 P2075B100 P IC C V-25-011 P IC C V-25-012 P IC C V-25-013 P IC C V-25-014 P IC C V-25-015 P IC C V-25-016 P IC C V-25-017 P IC C V-25-018 P IC C V-25-019
body has two differentflow capacities(.50 GPM to 2.5 GPM) (3 G PMto 5.5 GPM) 1 body has two differentflow capacities(11 GPM to 16 GPM) (17 GPM to 19 GPM) Tefzel and Teflon are registered trademarks Dupont of
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10 11 12 13 14 15 16 17 18 19
0.03 0.06 0.09 0.13 0.16 0.19 0.22 0.25 0.28 0.32 0.35 0.38 0.41 0.44 0.47 0.50 0.54 0.57 0.60 0.63 0.69 0.76 0.82 0.88 0.95 1.01 1.07 1.14 1.20
1 1 1 1 1 1 1 1 1
15 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25
TF24-MFT US
LF24-MFT US
LRB(X)24-3
Pump Only
800-543-9038 USA
866-805-7089 CANADA
P2... Series PressureIndependentCharacterizedControlValves (PICCV) ChromePlated Brass Ball and B rass Stem , N P TFem ale Ends
A pplication
The PressureIndependent Characterized ControlValve is typicallyused in air handlingunits on heatingand coolingcoils, and fan coil unit heatingor cooling coils. Someother comm onapplications includeunit ventilatorsand VAV re- heat coils. This valveis suitablefor use in a hydronicsystemwith constantor variableflow. This valveis designed with MFT functionalitywhich facilitatesthe use of various control input. Valve Nominal Size Flow Rate Liter/sec Inches Close-off PSI DN mm GPM
SuitableActu ators
Valve Model Technical Data Service Flow characteristic S ize Type of end fitting Materials Body Ball Stem S eatO-rings S eat Characterizing disc Packing Diaphragm Regulator components Spring Bodypressurerating Mediatemp.range Close-off pressure Leakag e
M40047 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.
Sprin g Retu rn
N on -Spring Retu rn
chilledor hot water, 60% glycol equalpercentage 1, 1, 2 female,NPT forgedor cast brass,nickelplated chromeplatedbrass chromeplatedbrass Viton Teflon P TFE T E F Z E L 2 EPDMO-rings,lubricated polyesterreinfo rced silicone stainlesssteel/brass/Delrin AF 500 stainlesssteel 400 PSI 0F to 212F[-18C to 100C] 200 PSI ANSIClassIV (0.01% of rated valve capacityat 50 psi differential) 100 : 1 5 to 50 PSIDoperatingrange 10% combination manufacturing of tolerances pressurevariations and 1 = 8.31 lbs 1 = 7.70 lbs 2 small = 9.38 lbs 2 large= 29.10lbs
2 body has two differentflow capacities(44 GPM to 80 GPM) (90 GPM & 100 GPM) Tefzel and Teflon are registered trademarks Dupont of
PICC V-32-018 PICC V-32-019 PICC V-32-020 PICC V-32-021 PICC V-32-022 PICC V-32-023 PICC V-32-024 PICC V-32-025 PICC V-32-026 PICC V-40-026 PICC V-40-027 PICC V-40-028 PICC V-40-029 PICC V-40-030 PICC V-40-031 PICC V-40-032 PICC V-40-033 PICC V-50-033 PICC V-50-034 PICC V-50-035 PICC V-50-036 PICC V-50-037 PICC V-50-038 PICC V-50-039 PICC V-50-040 PICC V-50-044 PICC V-50-048 PICC V-50-052 PICC V-50-056 PICC V-50-060 PICC V-50-065 PICC V-50-070 PICC V-50-075 PICC V-50-080 PICC V-50-090 PICC V-50-100
18 19 20 21 22 23 24 25 26 26 27 28 29 30 31 32 33 33 34 35 36 37 38 39 40 44 48 52 56 60 65 70 75 80 90 100
1.14 1.20 1.26 1.32 1.39 1.45 1.51 1.58 1.64 1.64 1.70 1.77 1.83 1.89 1.96 2.01 2.08 2.08 2.15 2.21 2.27 2.33 2.40 2.46 2.52 2.78 3.03 3.28 3.53 3.79 4.10 4.42 4.73 5.05 5.68 6.31
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
32 32 32 32 32 32 32 32 32 40 40 40 40 40 40 40 40 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200
AF24-MFT US
ARX24-MFT
11
1 12
Flow and Valve Sizing and Selection Instructions for Non-Spring Actuator Utilizing the FlowSetR
N O N -S P R IN G E T U R N C T U O R :LRB24-3 R A AT D EFA ULT S ET-U P: FlowSetR The factory setting corresponds the orderedflow rate (selected to from Belim o standardproductrange).The valvesfactory setting is s in open position(valvealways closes C W direction). in To s et o r a dju std esiredm ax im u m w (actuato, F lo w S etR flo r and valveare connected): 1. Fully close the valve via actuato contro signa or via manual r l l overrid (pres button and turn handl in clockwis e s e e direction). N O T E T he F low S etR fixed clockw is end stop purposely : e prevent the actuato from returnin to its full zero-degre s r g e position, eliminatin exces rotation. g s 2. Use the integrate hex tool in the actuato lever to turn adjustment d r screw in plus (+) or minus (-) directio in order to move scale n indicato to desire flow rate. A standar hex tool (i.e. Allen r d d wrench size 5/32 or 4mm can also be used to turn adjustment ) screw. P IC C flow can be field adjuste by usin a hex tool. Thereforethe V d g , maximu flow can be increase or decrease withi the valves m d d n adjustabl flow range. e
Integrated Hex Tool
E Q U IO N S S E D AT U
No equationsare required.Choosethe P IC CVthat has the closest G PM to the requirement and roundup to next available flow.
PROCED U R E
1) ObtainrequiredGPM 2) Choosevalvem odelnum berthat has closestGPM rating (round up) 3) Verify that valvesize is not larger than pipe size and in general, do not selecta valveless than of the line size 4) Selectactuatorbasedupon selectionparameters above 5) Basedupon actuator/valve selection,verify close-offpressure (CO P)meets projectrequirements
Samplescale PICCV
O n Flo ating in tactu ato rs, run ning e is co nstant t depen dent Po the tim bu o n the o verallan gle of rotation.
Avoid disco nnectin g w S etR Flo from actu ato r r valve! If o necessa referto instruction ry, sheeton how toinstallFlow SetR to valve,and actuator FlowSetR. to
E X A M P L E F C V C ALCULATION O
800-543-9038 USA
866-805-7089 CANADA
P IC C V RunningTimes
All MFT actuatorshave constantrunningtime of 100 seconds.W hetherthey are set for on/off, floatingor proportionalcontrol, the runningtime remainsconstant. Note for FloatingPoint Controlwith LR...-3:Theseactuatorshavea constant running time. T he running time is dependent the modelnum beror FlowSetR on position as indicatedin the table below. Som e D D C controllersneedan adjustm ent the runningtime, otherwise they lose the positioninformation. In any of case,we recom m end position reset once a day. a
P2050B005 P2050B010 P2050B015 P2050B020 P2050B025 P2050B030 P2050B035 P2050B040 P2050B045 P2050B050 P2050B055 P2075B060 P2075B065 P2075B070 P2075B075 P2075B080 P2075B085 P2075B090 P2075B095 P2075B100 P IC C V-25-011 P IC C V-25-012 P IC C V-25-013 P IC C V-25-014 P IC C V-25-015 P IC C V-25-016 P IC C V-25-017 P IC C V-25-018 P IC C V-25-019 P IC C V-32-018 P IC C V-32-019 P IC C V-32-020 P IC C V-32-021 P IC C V-32-022 P IC C V-32-023 P IC C V-32-024 P IC C V-32-025 P IC C V-32-026
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10 11 12 13 14 15 16 17 18 19 18 19 20 21 22 23 24 25 26
45 61 73 79 84 75 77 79 81 83 87 55 57 59 61 63 65 69 71 81 60 62 64 67 69 86 65 67 78 N /A N /A N /A N /A N /A N /A N /A N /A N /A
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
800-543-9038 USA
866-805-7089 CANADA
P IC C V RunningTimes
800-543-9038 USA
866-805-7089 CANADA
P IC C V-40-026 P IC C V-40-027 P IC C V-40-028 P IC C V-40-029 P IC C V-40-030 P IC C V-40-031 P IC C V-40-032 P IC C V-40-033 P IC C V-50-033 P IC C V-50-034 P IC C V-50-035 P IC C V-50-036 P IC C V-50-037 P IC C V-50-038 P IC C V-50-039 P IC C V-50-040 P IC C V-50-044 P IC C V-50-048 P IC C V-50-052 P IC C V-50-056 P IC C V-50-060 P IC C V-50-065 P IC C V-50-070 P IC C V-50-075 P IC C V-50-080 P IC C V-50-090 P IC C V-50-100
26 27 28 29 30 31 32 33 33 34 35 36 37 38 39 40 44 48 52 56 60 65 70 75 80 90 100
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
F ig u re A
3a
All bypassvalvesare closed. No autom aticor manualbalancing valvesexist (or if they do, they m ust be set fully open and lockedso as not to interfere with the pressureindependency the PICCV). of Beloware the accepted procedures verifying/commissioning for pressureindependent control valves.
800-543-9038 USA
866-805-7089 CANADA
Field adjustm ent f m axim um o flow and /or flow ac cu ray. c (This functionis not a requirem ent. This procedure purely optional is and is not a m and atoy procedure properoperationof P IC C V r for valves.) Flow Accuracy the P IC C Vvalvebo dy is +/-10% .Howeve actuator of r, hysteresis installationcan havean effecton m easured and accuracy of the P IC C Vassem bly(actuator/valve) the field. The accuracy the in of P IC C Va ssem bly can im provedin the application. be The m axim umflow setting and/orflow accuracy be adjustedin the can field using the Belim oPC-Tool or Z TH -P IC C V w n on next page). (sho P leasecontactyour local B elim orepresentative obtain/puchase to r this tool or arrangeto havea Belim orepresentative the project visit site to m akeadjustments.
For additionalinform ationpertainingto the flow verificationand com m issioning usty, pleasevisit the w ebsiteof theseorganizations ind r that promotethe certificationand continuingeducationof industry professionals the Test and B alance in discipline. N E B B- National Environm ental Balancing Bureau,http://ww .nebb.org/ w TA B B- TestingAdjustingBalancing Bureau,http://ww .tabbcertified.org/ w
800-543-9038 USA
1 17
OperatingInstructions Z T H -P IC C V The ZTH-PICCV is a tool created to easily adapt the flow settings for the PICCV in the field. It directly connects to the Belimo actuator.
IMPORTANT: There are two ways to connect the tool to the actuators
3 Y
5 U
TQ
WT
BL
Tec hn ical Information Supply Communication 24 VAC/DC PP LRX24-MFT T F24 -MFT US L F24 -MFT US ARX24-MFT A F24-MFT GMX24-MFT T
ZTH-PICCV
RE-PROGRAMMING PROCESS:
Step 1 Conn ect cable to actuator port, twist to lock in place (or wire as above). Will display actuator for 5 seconds note this and compare to actuator being connected. Step 2 S tart PICCV PR OCE SS press OK will be displayed. Pre ss OK.
LR X 2 -MFT 4
18
LR, AR, GM Series Use the interface on the top of the actu ator. (L ea ve all of the wires of the actua tor installed.)
TF, LF, AF Series Conn ect to the installed wires of the actuator.
OperatingInstructions Z T H -P IC C V
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
800-543-9038 USA
19
Step 3 NC (or NO) run to MAX? Press OK will be displayed. Pre ss OK. NOTE: if you need to chang the NO /NC actio n for the actuator, e then you must use the PC-Tool. Changing the switch will not accomplish this. Do not chang the Y1/Y2 switch. e
Step 4 Actuator will drive to current setting (MAX for NC, Min for NO). W hen it stops, adjust using + and buttons. As it is running, it will show actu al value as the actuator moves.
3%
Step 5 H OLD D OWN the or + button down to adjust setting. If you disengage the button, then the word stop app ears and will change to hold. W hen setting is chang ed as n e e d e pre ss OK. d, To re-test flow, drive actuator to 80% of current setting and then re-drive to setting. (Ex: setting 70%, drive to 56% or lower and then drive back to 70%.)
M40047 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.
Step 6 D isplay will sta te SAVE to MAX (if N C) or SAVE to M IN (if NO). Press OK.
Save to MAX?
ok
Step 7 Disconnect tool by twisting and re-cover connection port (or un-wire actuator). You do not need to wait until actuator stops runni to ng disconnect.
A d v n c e Mode a d Enter the configuration menu by pressing OK (hold button) while conn ecting the ZTH-PICCV to the actuator. Step through w ith arrow key to Advanced Mode menu Ch ange mode from 0 to 1 Unplug the ZTH-PIC CV W ith advance mode, change runtime, control signal d (2-10 VDC , 0-10 VDC).
disconnect tool
LRCB24-3(-S) Actuators,On/Off
Dimensions P ICC V with
2.6" [66] 6.5" [165] D146 3.22" [82] 1.69" [42] 2.34" [59.4] 0.78" [20]
FlowSetR Dimensions
B A
Models
DN A B C D E [mm] 4.68 [119] 4.47 [114] 4.05 [103] 2.34 [60] 0.99 [25] 15
20 4.90 [125] 4.94 [126] 4.05 [103] 2.34 [60] 25 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 0.99 [25] 1.60 [41]
Rate im puls voltag 800V, Contro pollutio degre 3, Type of action 1 (1.B for -S models) d e e l n e
24 VAC 20% 50/60 Hz 24 VDC 10% Powerconsumption running 1.5 W holding 0.2 W Transformer sizing 2 VA (class2 powersource) Electrical connection 3 ft, 18 GA,Plenumrated cable conduitconnector Overload protection electronicthroughout0 to 95 rotation Control On/Off,FloatingPoint Input impedance 600 Angleof rotation 90, adjustable with mechanical stop Directionof rotation reversiblewith protected switch Positionindication handle Manualoverride externalpush button Runningtime 95 seconds, constantindependent load of Humidity 5 to 95% RH, non-condensing 60730-1) (EN Ambienttemperature -22F to 122F [-30C to 50C] Storagetemperature -40Fto 176F [-40C to 80C] Housingtype N EM A2/IP54 Housingmaterial UL94-5 VA Agencylistings cULu acc. to UL60730-1A/-2-14 s , CAN /CSA E60730-1CSA C22. No. 24-93 CE acc. to , 2 , 89/336/EEC Noiselevel less than 35 dB (A) Qualitystandard ISO 9001
A pplication
The Pressure Independent Characterized ControlValve along with the LRCB24-3 is pairedtogetherspecifically use in HeatPum papplications precisely for to control the flow of condenser water. This assem bly suitablefor use in a is hydronicsystemwith constantor variableflow. Dim ensions P ICC V with
2.6" [66] 6.5" [165] D146 2.34" [59.4] 1.69" [42] 0.78" [20]
FlowSetR Dimensions
3.22" [82]
Models
C D
24 VAC 20% 50/60 Hz 24 VDC 10% Powerconsumption running 1.5 W holding 0.2 W Transformer sizing 2.5 VA (Class2 powersource) Electrical connection 18 G A plenumrated cable 1/2 conduitconnector 3 ft [1m] 10 ft [3m] 16 ft [5m] Overload protection electronicthroughoutrotation Control On/Off Input impedance 600 Angleof rotation 90, adjustable with m echanical stop Directionof Rotation reversiblewith protected switch Position indication handle Manualoverride externalpush button and handle Runningtime 40 secondconstantindependent load of Ambienttemperature -22 F 1 22 F [-30 C to 50 C] to Housing NEM A2 / IP54 HousingMaterial UL94-5 VA Agencylistings cULusacc.to UL60730-1A/-2-14, CAN/CSA E60730-1, CSAC22.2 N o. 24-9 3, C E acc. to 89/336/EEC (-S and Models)2006/95/EC Noiselevel max.35 d dB(A)
B A
DN [mm]
15 4.68 [119] 4.47 [114] 4.05 [103] 2.34 [60] 0.99 [25] 0.99 [25] 20 4.90 [125] 4.94 [126] 4.05 [103] 2.34 [60] 0.99 [25] 0.99 [25] 25 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [41] 1.60 [41]
Models
LRX120-3 Technical Data Control Powersupply On/Off,FloatingPoint 100 to 240 VAC, 50/60 Hz (nominal) 85 to 265 VAC,50/60 Hz (tolerance) Powerconsumption running 2 W holding 0.5 W Transformer sizing 4 VA (class2 powersource) Electrical connection conduitconnector 18 G A,plenumrated cable LRB120-3 3 ft [1m] 3 ft [1m] 10 ft [3m] 16 ft [5m] LRX120-3 Overload protection electronicthroughout0 to 95 rotation Input impedance 600 Angleof rotation 90, adjustable with mechanical stop Directionof rotation reversiblewith protected switch Positionindication handle Manualoverride externalpush button Runningtime LRB120-3 90 seconds, constantindependent load of LRX120-3 150 95 60 45 35 seconds, constantindependent load of Humidity 5 to 95% RH non-condensing (E N 60730-1) Ambienttemperature -22Fto 122F[-30C to 50C] Storagetemperature -40Fto 176F[-40C to 80C] Housing N EM A2/IP54 Housingmaterial UL94-5 VA Agencylistings cULusacc.to UL 60730-1A/-2-14, C A N /CS A 60730-1, AC22.2N o. 24-93, E CS C E acc. to 89/336/EEC (and 2006/95/EC for line voltageand/or-S versions) Noiselevel <35 dB(A) Qualitystandard ISO 9001 Ratedim pulsevoltage4kV, Controlpollutiondegree3, Type of action1 Valve Nomina Size l DN In. [mm]
1
15 4.68 [119] 4.47 [114] 4.05 [103] 2.34 [60] 0.99 [25] 20 4.90 [125] 4.94 [126] 4.05 [103] 2.34 [60] 0.99 [25] 25 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [41]
800-543-9038 USA
866-805-7089 CANADA
Model
LRX24-M FT
24 VAC 20% 50/60 Hz 24 VDC 10% Powerconsumption running 2 W holding 1.2 W Transformer sizing 5 VA (class2 powersource) Electrical connection 18 G A plenumrated cable 1/2 conduitconnector 3 ft [1m] 10 ft [3m] 16 ft [5m] Overload protection electronicthroughout0 to 95 rotation Operating rangeY 2 to 10 VDC,4 to 20 mA (default) Variable(VDC,PW M,FloatingPoint, On/Off) Input impedance 100 k (0.1 mA), 500 1500 (PWM,FloatingPoint,On/Off) Feedback output U 2 to 10 VDC,0.5m A max V D CVariable Angleof rotation 90, adjust.with mechanical stop electronically variable Torque 45 in-lb [5 Nm] Directionof rotation reversiblewith protected switch Positionindication handle Manualoverride externalpush button Runningtime 100 seconds Variable(35 to 150 secs) Humidity 5 to 95% RH non condensing (E N 60730-1) Ambienttemperature -22Fto 122F[-30C to 50C] Storagetemperature -40Fto 176F[-40C to 80C] Housing NEM A2/IP54 Housingmaterial UL94-5 VA Agencylistings cULusacc.to UL60730-1A/-2-14, C A N /C S A 60730-1, S AC22.2 E C N o. 24-9 3, C E acc. to 89/336/EEC Noiselevel <35dB(A) Qualitystandard ISO 9001 Weight 1.5 lbs [0.7 kg]
Ratedim pulsevoltage800V, Controlpollutiondegree3, Type of action1 (1.B for -S models)
DN A B C D E F [mm] 4.68 [119] 4.47 [114] 4.05 [103] 2.34 [60] 0.99 [25] 0.99 [25] 15
20 25 4.90 [125] 4.94 [126] 4.05 [103] 2.34 [60] 0.99 [25] 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [41] 0.99 [25] 1.60 [41]
2 23
800-543-9038 USA
866-805-7089 CANADA
24
T F 2 4 -M F T S Actuators, Multi-FunctionTechnology U e
Dimensions P ICC V with
D158_09
Models
G C D
B A
24 VAC 20% 50/60 Hz 24 VDC 10% Powe consumption running 4 W r holding 1.25 W Transformer sizing 6 VA (class2 powersource) Electricalconnection conduitconnector 18 G A plenumrated cable ARB24-M FT 3 ft [1m] 3 ft [1m] 10 ft [3m] 16 ft [5m] ARX24-M FT Overload protection electronicthroughout0 to 95 rotation Operating rangeY 2 to 10 VDC,4 to 20 mA (default) Variable(VDC,PW M,FloatingPoint,On/Off) Input impedance 100 k (0.1 mA), 500 1500 (PW M,FloatingPoint,On/Off) Feedback output U 2 to 10 VDC,0.5 mA max V D CVariable Angleof rotation 90 electronically variablewith mech.stop Directionof rotation reversiblewith protected switch Positionindication handle Manualoverride externalpush button Runningtime ARB24-MFT 100 seconds Humidity 5 to 95% RH non-condensing (E N 60730-1) Ambienttemperature -22Fto 122F[-30C to 50C] Storagetemperature -40Fto 176F[-40C to 80C] Housing NEM A2/IP54 Housingmaterial UL94-5 VA Agencylistings cULusacc.to UL60730-1A/-2-14, C A N /C S A 60730-1, S AC 22.2N o. 24-93, E C C E acc. to 89/336/EEC Noiselevel <45 dB(A) Qualitystandard ISO 9 9001
In. DN A B C D E F [mm] 1 32 8.19 [208] 8.19 [208] 5.67 [144] 3.66 [93] 1.77 [45] 1.61 [41] 1 40 8.03 [204] 8.03 [204] 5.67 [144] 3.66 [93] 1.77 [45] 1.61 [41] 2 50 8.50 [216] 8.50 [216] 5.91 [150] 3.66 [93] 1.77 [45] 1.61 [41]
2 NPT with flows to 40 GPM.
3.3" [84]
D159_09
866-805-7089 CANADA
2.93" [74.5]
2.40" [61]
C D
B A
Models
TF24-M FT US
DN In. A B C D E F [mm] 15 4.68 [119] 4.47 [114] 4.05 [103] 2.34 [60] 0.99 [25] 0.99 [25]
M FT 24 VAC 20% 50/60 Hz 24 VDC 10% Powerconsumption running 2.5 W holding 1.0 W Transformer sizing 4 VA (class2 powersource) Electrical connection 3 ft, 18 G A plenumrated cable conduitconnector Overload protection electronicthroughout0 to 95 rotation Operating rangeY* 2 to 10 VDC 4 to 20 mA (w/500 , W resistor)ZG-R01 Input impedance 100k for 2 to 10 VDC(0.1 mA) 500 for 4 to 20 mA 1500 for PW M,Floatingpoint and On-Offcontrol Feedback output U* 2 to 10 VDC, 0.5 m A max Directionof rotation spring reversiblewith CW /CCW mounting motor reversiblewith built-in switch M echanical angleof rotation* 90 with mechanical stop Runningtime motor* 100 seconds spring <25 sec @ -4Fto 122F[-20C to 50C] <60 sec @ -22F [-30C] Angleof RotationAdaptation* Off (Default) Override control* Min. (Min Position)= 0% - ZS (Mid. Position)= 50% - Max.(Max.Position)= 100% Positionindication visualindicato 0 to 95 r, Humidity 5 to 95% RH, non-condensing Ambienttemperature -22 to 122 F (-30 to 50 C) Storagetemperature -40 to 176 F (-40 to 80 C) Housing NEM A2/IP42 Housingmaterial UL 94-5VA Noiselevel(max) running <35 dB (A) spring return <65 dB (A) Agencylistings cULu acc. to UL60730-1A/-2-14 s , CAN /CSA E60730-1CSA C22. No.24-93 CE acc to , 2 , 89/336/EEC Qualitystandard ISO 9001
* Variablewhenconfiguredwith MFT options Ratedim pulsevoltage0.8 kV, Controlpollutiondegree3, Type of action1.AA.
800-543-9038 USA
866-805-7089 CANADA
A F R XActuators, Multi-FunctionTechnology
Dimensions P ICC V with
3.78" [96] 7.64" [194] D128 4.49" [114] 2.28" [58] C D
F
B A
Models
LF24-M FT US LF24-M F-S US w/built-in Aux. Switch T Technical Data Control M FT Controlsignal 2 to 10 VDC Powerconsumption running 2.5 W holding 1 W Transformer sizing 5 VA (class2 powersource) Electrical connection 3 ft, 18 G A appliance cables (-S modelhas 2 cables) conduitconnector Overload protection electronicthroughout0 to 95 rotation Input impedance 100k for 2 to 10 VDC(0.1 mA) 500 for 4 to 20mA 750 for PWM 500 for on/off and floatingpoint Feedback 2 to 10 VDC,0.5 mA max Angleof rotation 95 Directionof rotation spring reversiblewith CW /CC W mounting motor reversiblewith built-in switch Positionindication visualindicator Runningtime <40 to 75 sec. (on-off) 100 seconds spring <25 sec.@ -4Fto +122F[-20C to +50C] <60 sec.@ -22F[-30C] Ambienttemperature -22 Fto 1 22 F [-30 C to 50 C] Housing N EM A2 Agencylistings UL 873, CSAC22.2No. 24 certified,CE Noiselevel m ax.62 dB(A) Qualitystandard ISO 9 9001
In.
15 4.68 [119] 4.47 [114] 4.05 [103] 2.34 [60] 0.99 [25] 0.99 [25] 20 4.90 [125] 4.94 [126] 4.05 [103] 2.34 [60] 0.99 [25] 0.99 [25] 25 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [41] 1.60 [41]
4.04
Models
AFRX 24-M FT US AFRX 24-MT-S US w/built-in Aux. Switches F Technical Data Control Controlsignal
MFT 24 VAC, +/- 20%, 50/60 Hz 24 VDC, +20% / -10% 7.5 W Powersupply Powerconsumption running 3 W holding 10 VA (Class 2 power source) 10 VA, class 2 power Transformer sizing Electrical connection A F B ... 3 ft, 18 GA appliance cable, 1/2" conduit connector -S models: two 3 ft, 18 gauge appliance cables with 1/2 conduit connectors A F X ... 3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance or plenum cables, with or without 1/2 conduit connector -S models: two 3 ft [1m], 10 ft [3m] or 16 ft [5m] appliance cables with or without 1/2" conduit connectors conduit connector Electrical connection 3 ft [1m], 18 GA appliance cable (-S m odelhas 2 cables) electronic throughout 0 to 95 rotation Overload protection 100 kW for 2 to 10 VDC (0.1 mA) Input impedance 500 W for 4 to 20 mA 1500 W for PWM, floating point and on/ off control 2 to 10 VDC, 0.5 mA max Feedback output 95 Angleof rotation Directionof Rotation spring reversible with CW/CCW mounting motor reversible with built-in switch visual indicator Positionindication hex crank Manualoverride Runningtime spring <20 sec @ -4F to 122F [-20 C to 50 C]; <60 sec @ -22F [-30 C] motor 150 seconds (default), variable (70 to 220 seconds) -22 to 122 F (-30 to 50 C) Ambienttemperature NEMA 2, IP54, Enclosure Type 2 Housing cULus acc. to UL60730-1A/-2-14, CAN/ Agencylistings CSA E60730-1:02, CE acc. to 2004/108/ EC & 2006/95/EC 40dB(A) motor @ 150 seconds, run Noiselevel time dependent 62dB(A) spring return n
Valve Nominal Size Dim ension(Inche [mm]) s s DN In. A B C D E F [mm] 1 32 8.19 [208] 8.19 [208] 5.67 [144] 3.66 [93] 1.77 [45] 1.61 [41] 1 40 8.03 [204] 8.03 [204] 5.67 [144] 3.66 [93] 1.77 [45] 1.61 [41] 2 50 8.50 [216] 8.50 [216] 5.91 [150] 3.66 [93] 1.77 [45] 1.61 [41]
2 NPT with flows to 40 GPM
3.93
99.9
E 2.64 [67]
F 2.64 [67]
G 12.83 [326]
H 21.90 [556]
2 x SPD 7A (2.5A )@ 250 VAC ,UL listed, T, one switch is fixed at +5,one is adjustable 25 to 85 (doubleinsulated)
2.5
63.5
102.7
800-543-9038 USA
866-805-7089 CANADA
Wiring for DamperActuators and ControlValves On/Of, and Floating Point, Spring Return,24V and f 120V 1
Dimensions P ICC V with
D132_09
Models
2 x SP D 7A (2.5A) @ 250 VA C,UL listed, T, one switch is fixed at +5,one is adjustable 25 to 85 (doubleinsulated)
M FT 2 to 10 VDC,(4 to 20 mAwith 500 resistor) 20% 50/60 Hz 24 VAC 24 VDC 10% Powerconsumption running 6 W holding 2.5 W Transformer sizing 10 VA, class2 power Electrical connection conduitconnector (-S modelhas 2 cables) 3 ft [1m], 18 G A appliance cable Overload protection electronicthroughoutrotation Input impedance 100 k for 2 to 10 VDC(0.1 mA) 500 for 4 to 20 mA 750 for PWM 1500 for on/off and floatingpoint Feedback output 2 to 10 VDC,0.5 mA m ax (variable) Angleof rotation 95 Directionof Rotation spring reversiblewith CW /CC W mounting motor reversiblewith built-in switch Positionindication visualindicator Manualoverride hex crank Runningtime motor 100 seconds spring <20 sec. Ambienttemperature -22 Fto 1 22 F [-30 C to 50 C] Housing N EM A2 / IP54 Agencylistings UL 873, CSAC22.2No. 24 certified,CE Noiselevel m ax.45 dB(A)
DN In. A B C D E F [mm] 1 32 8.19 [208] 8.19 [208] 5.67 [144] 3.66 [93] 1.77 [45] 1.61 [41] 1 40 8.03 [204] 8.03 [204] 5.67 [144] 3.66 [93] 1.77 [45] 1.61 [41] 2 50 8.50 [216] 8.50 [216] 5.91 [150] 3.66 [93] 1.77 [45] 1.61 [41]
2 NPT with flows to 40 GPM
A F Actuators, Multi-FunctionTechnology
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
On/Off, Spring Return, 24V Actuators: AF24 US, LF24 US, TFX24 US Notes: 24 VAC Transformer 1 2 Line Volts 3 4 1 Common Blk. 2 + Hot Wht. 1 Provide overload protection and disconnect as required. Actuators may be connected in parallel. 2 Power consumption must be observed. 3 May also be powered by 24 VDC. Meets cULus or UL and CSA requirements without 4 the need of an electrical ground connection.
On/Off, Spring Return, 120V Actuators: AF120 US, LF120 US, TFX120 US Notes: 2 1 Neutral 2 + Hot 1 Provide overload protection and disconnect as required. Actuators may be connected in parallel. 2 Power consumption must be observed.
1 Line Volts
N H
3
M40047 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.
Meets cULus or UL and CSA requirements without 3 the need of an electrical ground connection.
Floating Point, Spring Return, 24V Actuators: LF24-3 (-S) US, TF24-3 (-S) US Notes: 1
Line Volts
a
24 VAC Transformer
Provide overload protection and disconnect as required. Actuators may be connected in parallel. Power consumption must be observed. May also be powered by 24 VDC. Note: TF24-3(S) must be powered by 24 VAC. Meets cULus, or UL or CSA requirements without the need of an electrical ground connection. Actuators with plenum rated cable do not have numbers on wires; use color coded instead. Actuators with appliance rated cable use numbers.
2 3
CW
CCW
4 5
LF24-3(-S) US TF24-3(-S) US
800-543-9038 USA
866-805-7089 CANADA
Wiring for DamperActuators and ControlValves 2 to 1 0 V D Ca nd 4 to 20 mA, Spring Return and Non-SpringReturn, 24V
On/Off and Floating Point, Non-Spring Return, 24V Actuators: ARB24-3, LRB24-3 On/Off 1 Line 24 VAC Transformer 2
B lk (1) C om m on
Floating Point
1 Line Volts 24 VAC Transformer 2 Blk (1) Red (2) Common +
Volts 3
a a open a closed
Red (2) +
3
Wht (3) +
Wht (3)
4
1 0 The indication of direction is valid for switch position 1. The indication of direction is valid for switch position 1.
1 0
ARB24-3 (-S)
ARB24-3 (-S)
1 0
LRB24-3 (-S)
LRB24-3 (-S)
1 Line Volts
Line Volts
2 +
3 +
4
TR24-3 US versions
8 6
TR24-3-T US
4 5 7
TR24-3 US 2 versions
5 6
TR24-3-T US
Notes: 1 2 Provide overload protection and disconnect as required. Actuators are provided with color coded wires. Wire numbers are provided for reference. Actuators may also be powered by 24 VDC. Meets cULus or UL and CSA requirements without the need of an electrical ground connection.
5 6 7 8
The TR24-3-T US actuators are provided with a numbered screw terminal strip instead of cable. Switch external and 3 to change rotation direction of or L/R wires 2 switch). TR24-3-T US, TR24-3 US, (does not have CW/CCW TR24-3-T US, TR24-3 US, actuators cannot be wired in parallel. TR24-3-T US, TR24-3 US, actuators need to be powered by 24 VAC.
Wiring for DamperActuators and ControlValves On/Off and Floating Point, Non-SpringReturn,24V
3 4
800-543-9038 USA
866-805-7089 CANADA
2 to 10 VDC and 4 to 20 mA, Spring Return 24V Actuators: AF24-SR US, LF24-SR US, and TF24-SR US
1 Line Volts 3 VDC/mA () 500 3 Y Input, 4 5 U Output, 2 to 10V 6
CW CCW
24 VAC Transformer
Notes:
2 1 Common 2 + Hot
1 2
Provide overload protection and disconnect as required. Up to four actuators may be connected in parallel with four actuators wired to one 500 resistor. Power consumption must be observed.
2 to 10V
3 4 5
Actuator may also be powered by 24 VDC. A 500 resistor converts the 4 to 20mA control signal to 2 to 10 VDC. (ZG-R01) Only connect common to neg. () leg of control circuits.
2 to 10 VDC and 4 to 20 mA, Non-Spring Return 24V Actuators: ARB24-SR, LRB24-SR and TR24-SR US
24 VAC Transformer
24 VAC Transformer
Line Volts
VD C/m A ()
500
1 Common 2 + Hot
7
Wht (3) Y 2 to 10V Input O rg (5) U 2 to 10V Outpu t
3 Y Input,
2 to 10V
1 0
5 U Output, 2 to 10V
1 0
LRB24-SR ARB24-SR
LRX24-SR ARX24-SR
Notes: 1 2 3 4 5 Provide overload protection and disconnect as required. Up to 4 actuators may be connected in parllel. Power consumption and input impedance must be observed. Actuators may also be powered by 24 VDC. Meets cULus or UL and CSA requirements without the need of an electrical ground connection. Actuators with plenum rated cable do not have numbers on wires; use color codes instead. Actuators with appliance cables are numbered.
6 7
800-543-9038 USA
Only connect common to neg. () leg of control circuits. A 500 resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.
203-791-8396 LATIN AMERICA
866-805-7089 CANADA
Two Position
1 Line Volts 3
24 VAC/DC Transformer
500
Position
()
C C W) ( LC W ( R )
MFT US
Floating Point
1
Line Volts
24 VAC Transformer
2
Blk (1) Com m on Wht (2) H ot +
24 VAC Transformer
1
Line Volts A 3
9
Control Signal ()
3 6
A B
8 2 to 10 VDC Feedback Signal 5
B C
2-10 VDC or 4 to 20 mA
(+)
500
1/4 watt
CCW CW
MFT US
Direction of rotation switch
CCW CW CCW CW
Notes:
PWM 24 VAC Transformer (AC only) Line Volts 6 Blk (1) Comm on Red (2) + Hot Wht (3) Y Input Wht (5) U Output(Grn)
5
CCW CW
1 2
Provide overload protection and disconnect as required. Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. Actuators may also be powered by 24 VDC. Position feedback cannot be used with a Triac sink
() (+)
33
MFT US
Wiring for DamperActuators and ControlValves M FT, Spring part number 40155) be contact closures. Return
6 7 8 9
Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. ZG-R01 may be used. Contact closures A & B also can be triacs. A & B should both be closed for triac source and open for triac sink. For triac sink the common connection from the actuator must be connected to the hot connection of the controller.
203-791-8396 LATIN AMERICA
800-543-9038 USA
866-805-7089 CANADA
34