Users Guide
Over Voltage & Under Voltage Relay: PAC-E500
Table of Contents
1 Overview........................................................................ 5
1.1 Features .............................................................................. 5 1.2 Functional Single Line Diagram ....................................... 6
2 Technical Data............................................................... 7
2.1 General Specifications ...................................................... 7
2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.3.1 2.3.2 2.3.3 2.3.4 Current Input............................................................................. 7 Rated Control Source............................................................... 7 Rated Frequency ...................................................................... 7 Contact Output ......................................................................... 7 Contact Input ............................................................................ 7 Case........................................................................................... 7 Over Voltage Protection ........................................................... 8 Under Voltage Protection......................................................... 8 Ground Over Voltage Protection ............................................. 8 Negative Phase Sequence Over Voltage Protection.............. 8 Under Frequency Protection ................................................... 9 Insulation Tests......................................................................... 9 Electromagnetic Compatibility Tests .................................... 10 Mechanical Tests .................................................................... 11 Environmental Conditions ..................................................... 11
3 Functional Description............................................... 12
3.1 Protection Functions ....................................................... 12
3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 Over Voltage............................................................................ 12 Under Voltage.......................................................................... 13 Ground Over Voltage.............................................................. 14 Negative Phase Sequence Over Voltage .............................. 16 Under Frequency .................................................................... 17 Control..................................................................................... 18 Measurement & Metering ....................................................... 19 Programmable Logic.............................................................. 19 Self Diagnosis......................................................................... 21 Communication ...................................................................... 21 Setting & Configuration Software ......................................... 22
2/76
4.2 Key Manipulation & Menu ............................................... 25 4.3 Initial Display.................................................................... 28 4.4 Menu Tree Display ........................................................... 28
4.4.1 DISPLAY Menu ........................................................................ 29
DISPLAY/STATUS .................................................................... 29 DISPLAY/STATUS/CONTACT INPUT...................................... 30 DISPLAY/STATUS/CONTACT OUTPUT.................................. 30 DISPLAY/STATUS/SELF DIAGNOSIS..................................... 30 DISPLAY/STATUS/PROTECTION ........................................... 31 DISPLAY/MEASURE ................................................................ 32 DISPLAY/SYSTEM INFO. ......................................................... 33 SETTING/SYSTEM ................................................................... 34 SETTING/SYSTEM/POWER SYSTEM ..................................... 35 SETTING/SYSTEM/CB CONTROL........................................... 36 SETTING/SYSTEM/ PT FUSE MONITOR ................................ 37 SETTING/SYSTEM/COM .......................................................... 37 SETTING/SYSTEM/DNP3.0 ...................................................... 38 SETTING/SYSTEM/CONTACT INPUT ..................................... 39 SETTING/SYSTEM/CONTACT OUTPUT ................................. 40 SETTING/SYSTEM/LED ........................................................... 42 SETTING/SYSTEM/PASSWORD ........................................... 43 SETTING/PROTECTION......................................................... 44 SETTING/PROTECTION/OV1 (59_1) ..................................... 45 SETTING/PROTECTION/OV2 (59_2) ..................................... 46 SETTING/PROTECTION/UV1 (27_1) ..................................... 47 SETTING/PROTECTION/UV2 (27_2) ..................................... 48 SETTING/PROTECTION/OVG1 (59G_1)................................ 49 SETTING/PROTECTION/OVG2 (59G_2)................................ 50 SETTING/PROTECTION/OVG3 (59G_3)................................ 51 SETTING/PROTECTION/NSOV (47) ...................................... 52 SETTING/PROTECTION/UF (81)............................................ 52 4.4.1.1. 4.4.1.2. 4.4.1.3. 4.4.1.4. 4.4.1.5. 4.4.1.6. 4.4.1.7.
4.4.2
SETTING Menu........................................................................ 34
4.4.2.1. 4.4.2.2. 4.4.2.3. 4.4.2.4. 4.4.2.5. 4.4.2.6. 4.4.2.7. 4.4.2.8. 4.4.2.9. 4.4.2.10. 4.4.2.11. 4.4.2.12. 4.4.2.13. 4.4.2.14. 4.4.2.15. 4.4.2.16. 4.4.2.17. 4.4.2.18. 4.4.2.19. 4.4.2.20.
4.4.3
3/76
4/76
1 Overview
PAC-E500, Over Current & Earth Fault Relay is a microprocessor-based numerical protection relay designed for the management and protection of a distribution feeder. PAC-E500 has the protection elements of Over Voltage (OVR), Under Voltage (UVR), Ground Over Voltage (OVGR), Negative Phase Sequence Over Voltage and Under Frequency. It uses Normal Inverse of TC curves (1 OVR and UVR, 2 OVGR). Also it provides the measurements of Lineto-Line voltage, 3 phase currents and voltages, Sequence Voltage, THD (Total Harmonic Distortion), frequency, and PT fuse fail monitor, and control functions for a circuit breaker. Programmable Logic is designed for the replacement of external wiring for the sequence logic and it has 48 configurable logic components. The configurations of contact inputs/outputs are very easy with Programmable Logic. Programmable Logic is specially designed software for easy maintenance and operation of PAC-E500.
1.1
FEATURES
Numerical-type Over Voltage (OVR), Ground Over Voltage (OVGR), Under Voltage, Negative Phase Sequence Over Voltage, and Under Frequency Protections Various TC Curves including 1 OVR and UVR, 2 OVGR. Digital Indication of Setting and Metering on LCD (2 Lines 16 Characters) Self-Diagnosis and Internal Status Monitoring Operation Blocking of Individual Relay Element by External Contact Inputs during the Relay Maintenance Configurable System Frequency (50 / 60Hz) Easy setting of 4 Contact Outputs and 4 Programmable LED to use Logic Contact Output: Available Trip and Signaling Contact Direct Trip/Close Control of 1 CB from Front Panel Locally and SCADA remotely Useful PC Application (Setting Tool) : System Configuration, Protection & Logic Setting, Monitoring & Measurement Self-Test Function of Contact Output by Manual Trip Emulation Access Security by Password for Setting Change and CB Control. Communication Interface - RS-232C (Front and Rear), RS485C (SCADA Communication) - Protocol: MODBUS, DNP3.0, IEC60870-5-103 Measurement: 3-phase voltages, Sequence Voltages, Thermal, Frequency EMI/EMC Performance Reinforced.
5/76
1.2
27_1
27_2
59_1
59_2
52
47
81
59G_1 3
59G_2 ,3
59G_2 ,2,3
PAC-E500
Function Over Voltage Protection Under Voltage Protection Negative Phase Sequence Over Voltage Protection Under Frequency Protection Ground Over Voltage Protection CB (AC Circuit Breaker)
6/76
2 Technical Data
2.1 GENERAL SPECIFICATIONS
2.1.6 Case
Construction IP Protection Level Material Draw-out type IP51 Steel with Hard-Combustion Plastic Cover
7/76
2.2
PROTECTION ELEMENTS
8/76
2.3
ENVIRONMENTAL TESTS
Overall Electric Circuit Enclosure : 2kV Between Electric Circuits : 2 kV Between Contacts : 1 kV Applied Waveform: 1.250s Applied Time: Each Positive/Negative 3 times Overall Electric Circuit Enclosure Between Transducer Circuits Transducer Circuit Control Circuit Between Electric Circuits Between Contacts Terminals : 5kV : 5 kV : 5 kV : 3 kV : 3 kV
IEC60255-5
IEC60255-5
9/76
Electrostatic discharge
10/76
Voltage Waveform Current Waveform Output Impedance Applying Method Polarity Applied Count Applied Interval Compound Surge
: 1.2 50sec : 8 20sec : 2 : Asynchronous : Positive, Negative : 3 times : 30sec IEC60255-22-5 class
Control Source Circuit Common Mode 2.0 kV Differential Mode 1.0 kV Transducer Circuit Common Mode 2.0 kV Differential Mode 1.0 kV Contact Circuit Common Mode 2.0 kV Differential Mode 1.0 kV Applied Frequency :25MHz ~ 1GHz Electric Field Strength : 10V/m 80% AM modulation Applying Method : Front Distance from Antenna: Cross and Horizontality Dwell Time : 1sec
Radiated Susceptibility
Vibration
Impulse
11/76
3 Functional Description
3.1 PROTECTION FUNCTIONS
V : Voltage input Vs : Pickup Voltage setting Trip time for V/Vs 8 are identical to those for V/Vs = 8.
59_ PKP_ A 59_ PKP_ OR
VA > PICKUP
59_ PKP_ B
59_ PKP_ C VB > PICKUP 59_ OP_ A DELAY VC > PICKUP 59_ OP_ B 59_ OP_ OR
59_ OP_ C BLOCK = YES 59_ OP_ A MU LTIPLIER CON T IN #1 = ON . . . 59_ OP_ B 59_ OP_ OR
59_ OP_ C
VA / VB / VC : A/B/C
VA/VB/VC: A/B/C phase Feeder Voltage FUNCTION: Setting Function of Over Voltage
FUNCTION : Function MODE: Setting Mode MODE MODE : of Over Voltage PICKUP : PICKUP PICKUP: Setting Pickup of Over Voltage DELAY : of Over Voltage DELAY: Setting Delay DELAY Multiplier : MULTIPLIER Multiplier: Setting Multiplier Over BLOCK : BLOCK Voltage BLOCK: Setting Block of Over Voltage CONNECTION = PROT_BLK : CONNECTION PROT_BLK CONT IN #1~#4 =ON : Connection of Contact input is shown PROT_BLK CONNECTION-PROT_BLK: LOGIC "1" 59_PKP_A/B/C : Pickup 59_PKP_OR : Pickup 59_PKP_A/B/C: Each phase pickup for Over 59_OP_A/B/C : Operation Voltage 59_PKP_OR: The least 1 phase Operation 59_OP_OR : for Over Voltage is pickup
59_OP_A/B/C: Each phase Operation for Over Voltage 59_OP_OR: The least 1 phase for Over Voltage is Operation
12/76
8 T = TM (sec ) 2.2 V 1 Vs
T TM : Trip time in second : Time multiplier V : Voltage input Vs : Pickup Voltage setting
VA < PICKU P
27_ PKP_ B
27_ PKP_ C VB < PICKU P 27_ OP_ A DELAY VC < PICKU P 27_ OP_ B 27_ OP_ OR
27_ OP_ C BLOCK = YES 27_ OP_ A CON T IN #1 = ON . . . MULTIPLIER 27_ OP_ B 27_ OP_ OR
27_ OP_ C
Voltage
FUNCTION : Function FUNCTION: Setting Function of Under Voltage MODE : MODE MODE: Setting Mode of Under Voltage PICKUP : PICKUP DELAY : DELAY PICKUP: Setting Pickup of Under Voltage Multiplier : Setting Delay of Under Voltage DELAY: MULTIPLIER BLOCK : BLOCK Multiplier: Setting Multiplier Under Voltage CONNECTION = PROT_BLK : CONNECTION PROT_BLK BLOCK: Setting Block of Under Voltage CONT IN #1~#4 =ON : LOGIC "1" 27_PKP_A/B/C : Pickup CONT IN #1~#4-1: Contact input is LOGIC 1 27_PKP_OR : Pickup 27_OP_A/B/C : Operation 27_PKP_A/B/C: Operation 27_OP_OR : Each phase pickup for Under Voltage
27_PKP_OR: The least 1 phase for Under Voltage is pickup 27_OP_A/B/C: Each phase Operation for Under Voltage 27_OP_OR: The least 1 phase for Under Voltage is Operation
13/76
14/76
FU N CTION = EN ABLE
59G_PKP
VN > PICKUP
59G_OP MULTIPLIER
VN :
VN: Feeder Ground Voltage FUNCTION: Setting Function of Ground Over Voltage
FUNCTION : Function MODE: Setting Mode of Ground Over Voltage MODE : MODE PICKUP: Setting Pickup of Ground Over Voltage PICKUP : PICKUP DELAY: Setting Delay of Ground Over Voltage DELAY : DELAY Multiplier: Setting Multiplier Ground Over Voltage Multiplier : MULTIPLIER BLOCK: Setting Block of Ground Over Voltage BLOCK : BLOCK CONNECTION-PROT_BLK: CONNECTION is shown PROT_BLK CONNECTION = PROT_BLK : Connection of Contact input PROT_BLK CONT IN #1~#4-1: Contact input is LOGIC "1" CONT IN #1~#4 =ON : LOGIC 1
59G_PKP: Pickup for Ground Over Pickup 59G_PKP : Voltage 59G_OP: Ground Over Voltage 59G_OP : Operation for Operation
<Figure 3.1.3. OVG1 (59G_1), OVG2 (59G_2), OVG3 (59G_3) Logic Diagram>
15/76
47_ PKP
V2 > PICKU P
V2:V2 : Negative Phase Feeder Voltage FUNCTION: Setting Function of Negative Phase Sequence Over Voltage FUNCTION : Function PICKUP: Setting Pickup of NegativePICKUP Over Voltage PICKUP : Phase Sequence DELAY: Setting Delay of Negative Phase Sequence Over Voltage DELAY : DELAY BLOCK: Setting Block of Negative Phase Sequence Over Voltage BLOCK : BLOCK CONNECTION = PROT_BLK : CONNECTION PROT_BLK CONNECTION-PROT_BLK: Connection of Contact input is shown PROT_BLK CONT #1~#4-1: Contact input is LOGIC 1 CONT IN IN #1~#4 =ON : LOGIC "1"
47_PKP : Pickup 47_PKP: Pickup for Negative Phase Sequence Over Voltage 47_OP : Operation 47_OP: Operation for Negative Phase Sequence Over Voltage
16/76
CONT IN #1 = ON . . .
DELAY
UV BLOCK = NO
VA > UV PICKUP
VB > UV PICKUP
VC > UV PICKUP
OC BLOCK = NO
IA < OC PICKUP
Frequency : A VA/VB/VC: A/B/C phase feeder VA/VB/VC : A/B/C voltage IA: A-phase feeder IA : A current
FUNCTION: Setting Function Function FUNCTION : of Under Frequency FREQ PICKUP: Setting FREQ PICKUP of Under Frequency e FREQ PICKUP : FREQ PICKUP DELAY: Setting Delay of DELAY DELAY : Under Frequency UV BLOCK : Block Frequency UV BLOCK: Setting Under Voltage Block of Under OC BLOCK : Block Under Frequency OC BLOCK: Setting Over Current Block of BLOCK : Under Frequency BLOCK: Setting Block of BLOCK CONNECTION = PROT_BLK : CONNECTION PROT_BLK CONNECTION-PROT_BLK: Connection of Contact input is shown PROT_BLK CONT IN #1~#4 =ON : LOGIC "1" CONT IN #1~#4-1: Contact input is LOGIC 1 81_OP: Operation for Under Frequency
81_PKP : Frequency 81_PKP: Pickup for Under Pickup 81_OP : Operation
17/76
3.2
ADDITIONAL FUNCTIONS
3.2.1 Control
PAC-E500 supports direct CB Trip/Close control function (One CB). Control functions of PAC-E500 also provide a local/remote selection for control location. As for remote control, PAC-E500 communicates with an upper master system (SCADA) through the rear RS485 port (Protocol: Modbus). To control CB, a contact input should be allocated for CB STATUS input (CB_OPENED or CB_CLOSED). If there are many contact inputs allocated for CB status, Contact Input #1 status is the first priority for CB control. In case no contact input is allocated for CB status, CB control function is not available and all LEDs related to CB control (Local/Remote, Open/Close) are off.
CB OPEN / CLOSE
This function performs trip (open)/close control actions of CB. CB Open or Close button on the front panel is activated only on the Local mode (L LED on). On the Remote mode, only control command from SCADA through communication is accepted. Before control command via front panel, SELECT button and Password enter are required first. SELECT button is the concept to prevent the mal-operation on the front panel and this concept is the same with SBO (Select Before Operate) concept in communication protocol, i.e. DNP3.0, where SCADA (master system) selects first the equipment to control remotely before setting out actual control command to keep other masters from selecting the same equipment so that control right is granted to that SCADA only. This dedicated concept is adopted equally to Local control and this is also used for mal-operation prevention of direct open/close command. After the correct password enter and SELECT button again, then a phrase that CB is selected is displayed on LCD and SELECT LED is blinking. After while, CB OPEN/CLOSE buttons are activated for 15 seconds.
18/76
Current
Voltage
Frequency Sequence
Logic
Input#1 Input#2 Input#3 Input#4 Input#5 Input#6 Input#7 Input#8 Input#1 Input#2 Input#3 Input#4 Input#5 Input#6 Input#7 Input#8 Input#1 Input#2 Input#3 Input#4 Input#5 Input#6 Input#7 Input#8 Input#1 Input#2 Input#3 Input#4 Input#5 Input#6 Input#7 Input#8
Contact Out #1 ~ #4
Logic
19/76
Protection elements
Input L_OFF L_ON CB_OPEN_CTL CB_CLOSE_CTL CONT_IN #1 CONT_IN #4 SYS_ERR PROT_PKP_OR PROT_OP_OR 59_1_PKP_OR 59_1_PKP_A 59_1_PKP_B 59_1_PKP_C 59_1_OP_OR 59_1_OP_A 59_1_OP_B 59_1_OP_C 59_2_PKP_OR 59_2_PKP_A 59_2_PKP_B 59_2_PKP_C 59_2_OP_OR 59_2_OP_A 59_2_OP_B 59_2_OP_C 27_1_PKP_OR 27_1_PKP_A 27_1_PKP_B 27_1_PKP_C 27_1_OP_OR 27_1_OP_A 27_1_OP_B 27_1_OP_C 27_2_PKP_OR 27_2_PKP_A 27_2_PKP_B 27_2_PKP_C 27_2_OP_OR 27_2_OP_A 27_2_OP_B 27_2_OP_C
Description Logic 0 Logic 1 CB Open Control (Local or Remote) CB Close Control (Local or Remote) Contact input#1 status Contact input#4 status Self-diagnosis error is occurred Any protection element is picked up Any protection element is operated At least 1 phase of 59_1 is picked up Phase A of 59_1 is picked up Phase B of 59_1 is picked up Phase C of 59_1 is picked up At least phase of 59_1 is operated Phase A of 59_1 is operated Phase B of 59_1 is operated Phase C of 59_1 is operated At least 1 phase of 59_2 is picked up Phase A of 59_2 is picked up Phase B of 59_2 is picked up Phase C of 59_2 is picked up At least phase of 59_2 is operated Phase A of 59_2 is operated Phase B of 59_2 is operated Phase C of 59_2 is operated At least 1 phase of 27_1 is picked up Phase A of 27_1 is picked up Phase B of 27_1 is picked up Phase C of 27_1 is picked up At least phase of 27_1 is operated Phase A of 27_1 is operated Phase B of 27_1 is operated Phase C of 27_1 is operated At least 1 phase of 27_2 is picked up Phase A of 27_2 is picked up Phase B of 27_2 is picked up Phase C of 27_2 is picked up At least phase of 27_2 is operated Phase A of 27_2 is operated Phase B of 27_2 is operated Phase C of 27_2 is operated
20/76
59G_1_PKP 59G_1_OP 59G_2_PKP 59G_2_OP 59G_3_PKP 59G_3_OP 47_PKP 47_OP 81_PKP 81_OP PT_FUSE_FAIL
59G_1 is picked up 59G_1 is operated 59G_2 is picked up 59G_2 is operated 59G_3 is picked up 59G_3 is operated 47 is picked up 47 is operated 81 is picked up 81 is operated PT_FUSE_FAIL is operated
3.2.5 Communication
Front 1 RS232 Port (19200 BPS, ModBus Protocol) For maintenance and Setting software (Engineering Tool) 1 RS232 Port (19200 BPS, ModBus Protocol) For maintenance and Setting software (Engineering Tool) 1 RS485 Port (300 ~ 38400 BPS, DNP3.0/Modbus/ IEC870-5-103 Protocol) For SCADA communication
Rear
21/76
22/76
4 Operational Description
4.1 FRONT PANEL CONSTRUCTION
- ,
Screw
23/76
4.1.2 LEDs
RUN (Green) ERROR (Red) PICK UP (Yellow) TRIP (Red) Programmable LED * 4 (Red) L (Red) R (Green) SELECT (Yellow) OPEN (Green) CLOSE (Red) RUN: Green is on when power is supplied. Test: Green is on and blinking when contact outputs are set out and during LCD/LED test on front panel. Red is on when self-diagnosis function detects device abnormalities. Relaying operation is inhibited. Details of abnormality are displayed on LCD, and even if the abnormal state returns to normal, LED is not reset to off but latched on. Manual RESET only returns to reset status. Yellow is on when a protection element is picked up. Red is on when any trip signal is outputted. LED is latched on until manual RESET. Red is on when each logic status (contact outputs #1~#4) is 1 (ON). Reset depends on Reset Type (Self/Manual) and Reset Delay time (0.00~60.00sec). Red is on in L/R LEDs when LOCAL control mode. (Any contact input should be allocated for CB status and password is required for control mode change.) Green is on in L/R LEDs when REMOTE control mode. (Any contact input should be allocated for CB status and password is required for control mode change.) Yellow is blinking when CB control is SELECTed. Green is on when contact input CB status is OPEN. (Any contact input should be allocated for CB status.) Red is on when contact input CB status is CLOSE. (Any contact input should be allocated for CB status.)
4.1.3 Keypad
UP ARROW DOWN RIGHT LEFT Menu Move, Menu Item Selection Menu Move, Value Change
Menu Move, Escape to Upper Menu / Cancel Item RESET Manual Reset of System Error and Trip LED MENU Enter into Menu Tree Display ENT Setting Value Enter and Confirm L/R Local / Remote Control Mode Change CONTROL SELECT CB Control Selection (Password) OPEN CB Trip Control CLOSE CB Close Control
24/76
4.2
25/76
26/76
MAIN Display
DISPLAY
STATUS
CONT IN#1 ~ 4 CONT OUT#1 ~ 4 MEMORY, SETTING, AD CONVERTER, CALIBRATION, PT FUSE MONITOR OV1(59_1), OV2(59_2), UV1(27_1), UV2(27_2), OVG1(59G_1), OVG2(59G_2), OVG3(59G_3), NSOV(47), UF(81)
PROTECTION
MEASURE
VOLT(VAB), VOLT(VBC), VOLT(VCA), VOLT(VA), VOLT(VB), VOLT(VC), VOLT(VN), CURR(IA), SEQ(V0), SEQ(V1), SEQ(V2), THD(VA), THD(VB), THD(VC), FREQUENCY Version Information POWER SYSTEM FREQUENCY, FREQ TRACK, PHS CT RATIO, PHS PT PRI, PHS PT SEC, GND PT PRI, GND PT SEC, PT CONNECT, FREQUENCY TRIP PULSE, CLOSE PULSE FUNCTION, POS UV PKP, NEG OV PKP, DELAY FUNCTION, SLAVE ADDR, BPS, PROTOCOL TX DELAY, LINK CONFIRM, LINK RETRY, LINK TIMEOUT, SBO TIMEOUT, WR TIME INT, COLD RESTART CONT IN#1 ~ 4 CONT OUT#1 ~ 4 LOGIC, INPUT1~8, RESET TYPE, RESET DELAY LOGIC, INPUT1~8, RESET TYPE, RESET DELAY
COM
DNP3.0
LED
LED#1 ~ 4
PASSWORD PROTECTION OV1(59_1) FUNCTION, MODE, PICKUP, DELAY, MULTIPLIER, BLOCK FUNCTION, MODE, PICKUP, DELAY, MULTIPLIER, BLOCK FUNCTION, MODE, PICKUP, DELAY, MULTIPLIER, BLOCK FUNCTION, MODE, PICKUP, DELAY, MULTIPLIER, BLOCK FUNCTION, MODE, PICKUP, DELAY, MULTIPLIER, BLOCK FUNCTION, MODE, PICKUP, DELAY, MULTIPLIER, BLOCK FUNCTION, MODE, PICKUP, DELAY, MULTIPLIER, BLOCK FUNCTION, PICKUP, DELAY, BLOCK FUNCTION, UV PICKUP, OC PICKUP, dF/dT PKP, FREQ PICKUP, DELAY, UV BLOCK, OC BLOCK, dF/dT BLOCK, BLOCK
OV2(59_2)
UV1(27_1)
UV2(27_2)
OVG1(59G_1)
OVG2(59G_2)
OVG3(59G_3)
NSOV(47)
UF(81)
COMMAND
27/76
4.3
INITIAL DISPLAY
Initial display divides normal and error display according to self-diagnosis. User takes proper action when self-diagnosis status except PT FUSE MONITOR is FAIL one or more and must reset manual after make normally self-diagnosis. LCD is indicated SYSTEM OK, when result of self-diagnosis is OK as following.
PAC - E 5 0 0 SY S T EM OK
4.4
To convert Initial Display into Menu Tree Display are operated through ENT and MENU buttons. Menu Tree Display is entered through MENU keypad button. Two display modes are alternated by MENU and Left keypad buttons. In the Menu Tree Display, 4 arrow keys determine the tree node and value change, and ENT key sets the determined values. All the menu items and set values take the rollover schemes using Up/Down keys. To convert Menu Tree Display into Initial Display are operated through Left arrow Escape keypad button and main menus first child nodes of the root consist of DISPLAY, SETTING, and COMMAND. DISPLAY menu shows status of I/O contacts, self-diagnosis results, starting and operating status of protection elements, metering of electric values, and software version of DSP. SETTING menu lets password for setting and control, analog circuit configuration, realtime system clock, CB setup, communication, input/output contacts and programmable LED setup, operation setup for protection elements, calibration data. COMMAND menu is used to test output contacts and LCD/LEDs of front-face display panel. In the following, each of the specific sub menus is explained.
PAC - E 5 0 0 S Y S T EM OK
MENU
D I S P L A Y
S E T T I N G
MENU
C O M M A N D
MENU
28/76
D I S P L A Y S T A T U S D I S P L A Y M E A S U R E D I S P L A Y S Y S T E M I NFO .
4.4.1.1. DISPLAY/STATUS DISPLAY menu is composed of CONTACT INPUT, CONTACT OUTPUT, SELF DIAGNOSIS, and PROTECTION sub menu. Each of sub menus shows contact input, contact output, self-diagnosis and operating status of protection elements.
D I S P L A Y S T A T U S S T A T U S C O N T A C T S T A T U S C O N T A C T S T A T U S S E L F D I AGNOS I S OU T PU T I NPUT
S T A T U S P R O T E C T I O N
29/76
4.4.1.2. DISPLAY/STATUS/CONTACT INPUT This menu displays On/Off status information of 4 contact inputs.
S T A T U S C O N T A C T I NPUT
CON T : OFF
I N# 1
1 / 4
CON T : OFF
I N# 2
2 / 4
CON T : OFF
I N# 3
3 / 4
CON T : OFF
I N# 4
4 / 4
4.4.1.3. DISPLAY/STATUS/CONTACT OUTPUT This menu displays On/Off status information of 4 contact outputs.
S T A T U S C O N T A C T OUT PUT CON T : OUT # 1 1 / 4
DE ENERG I Z ED OUT # 2 2 / 4
CON T :
DE ENERG I Z ED OUT # 3 3 / 4
CON T :
DE ENERG I Z ED OUT # 4 4 / 4
CON T :
DE ENERG I Z ED
4.4.1.4. DISPLAY/STATUS/SELF DIAGNOSIS This menu displays self-diagnosis results. System works normally if status of all selfdiagnosis except PT FUSE MONITOR is OK.
S T A T U S S E L F D I AGNOS I S MEMOR Y : OK 2 / 4 1 / 4
SE T T I NG : OK
30/76
AD :
CONV ER T ER OK
3 / 4
CA L I BRAT I ON : OK
4 / 4
4.4.1.5. DISPLAY/STATUS/PROTECTION This menu displays picked-up started and operated status of 9 protection elements. Phase elements show started and operated phases A, B, and C, and ground elements show PK and OP symbols, when the fault current is picked up and the relaying element is signaled to operate.
S T A T U S P R O T E C T I O N OV 1 ( 5 9 _ 1 ) PKP : ABC , OV 2 ( 5 9 _ 2 ) PKP : ABC , UV 1 ( 2 7 _ 1 ) PKP : ABC , UV 2 ( 2 7 _ 2 ) PKP : ABC , 1 / 9 OP : ABC 2 / 9 OP : ABC 3 / 9 OP : ABC 4 / 9 OP : ABC 5 / 9
OP : OP 6 / 9
OP : OP
7 / 9
OP : OP 8 / 9 OP : OP 9 / 9 OP : OP
31/76
4.4.1.6. DISPLAY/MEASURE This menu displays measurement and metering data of electric values. PAC-E500 has 1 current input and 4-voltage input. (Frequency is show according to input value of A-phase voltage.)
D I S P L A Y M E A S U R E VOL T ( VAB ) : 0 . 0 0 V , < 1 / 1 5 0 . 0 2 / 1 5 0 . 0 3 / 1 5 0 . 0 4 / 1 5 V , < 0 . 0 5 / 1 5 V , < 0 . 0 6 / 1 5 V , < 0 . 0 7 / 1 5 V , < 0 . 0 8 / 1 5 A , < 0 . 0 9 / 1 5 V , < 0 . 0
VOL T ( VA ) : 0 . 0 0
VOL T ( VB ) : 0 . 0 0
VOL T ( VC ) : 0 . 0 0
VOL T ( VN ) : 0 . 0 0
CURR ( I A ) : 0 . 0 0
SEQ ( V 0 ) : 0 . 0 0
SEQ ( V 1 ) : 0 . 0 0 V , <
1 0 / 1 5 0 . 0 1 1 / 1 5 V , < 0 . 0
SEQ ( V 2 ) : 0 . 0 0
32/76
THD ( VA ) : 0 . 0 %
1 2 / 1 5
THD ( VB ) : 0 . 0 %
1 3 / 1 5
THD ( VC ) : 0 . 0 %
1 4 / 1 5
FREQUENCY : 0 . 0 0Hz
1 5 / 1 5
4.4.1.7. DISPLAY/SYSTEM INFO. This menu is used to display the system information of DSP S/W versions for maintenance.
D I S P L A Y S Y S T E M I NFO . PAC - E 5 0 0 Ve r : V1 . 0 0
33/76
S E T T I N G S Y S T E M S E T T I N G P R O T E C T I O N
4.4.2.1. SETTING/SYSTEM SYSTEM menu is composed of POWER SYSTEM, CB CONTROL, PT FUSE MONITOR, COM, DNP3.0, CONTACT INPUT, CONTACT OUTPUT, LED, and PASSWORD. POWER SYSTEM is used for setting of frequency, frequency tracking, phase CT ratio and ground CT. CB CONTROL is used for time setting TRIP and CLOSE PULSE. PT FUSE MONITOR is used for time of CB pulse setting. COM is used for communication setting. DNP3.0 is used for setting of DNP when communication method is DNP3.0. CONTACT INPUT / OUTPUT and LED are used for setting contact input/output and Programmable LED respectively. PASSWORD is used when change password.
S E T T I N G S Y S T E M S Y S T E M P OW E R S Y S T E M C B CON T ROL SY S T EM
S Y S T E M P T FUSE MON I T OR
S Y S T E M C O M S Y S T E M D N P 3 . 0
34/76
S Y S T E M C O N T A C T S Y S T E M C O N T A C T S Y S T E M L E D S Y S T E M P A S S WO R D OU T PU T I NPUT
4.4.2.2.
SETTING/SYSTEM/POWER SYSTEM
POWER SYSTEM is used for setting of frequency, frequency tracking, phase CT ratio, phase PT primary, phase PT secondary, ground PT primary, ground PT secondary and PT connect.
S E T T I N G P OW E R S YS T EM FREQUENCY : 6 0 H z TRACK 2 / 1 0 1 / 1 0
FREQ :
D I SABLE CT 5 PT RAT I O3 / 1 0 : 5 PR I V 5 / 1 0 V 6 / 1 0 4 / 1 0
0 1 1 0 . 0 PT PR I
0 1 1 0 . 0 PT S EC V S EC V S EC V
1 1 0 . 0 PT
GND :
7 / 1 0
1 1 0 . 0 PT
GND :
35/76
8 / 1 0
1 1 0 . 0
GND : PT :
PT
S EC V
9 / 1 0
1 1 0 . 0
CONNEC T WY E
1 0 / 1 0
Item FREQUENCY FREQ TRACK PHS CT RATIO PHS PT PRI PHS PT PRI PHS PT SEC GND PT PRI GND PT PRI GND PT SEC PT CONNECT
Range 50Hz / 60Hz ENABLE/DISABLE 1 ~ 6000: 5 1 ~ 1000 0.0 ~ 999.9 50.0 ~ 250.0 0 ~ 1000 0.0 ~ 999.9 50.0 ~ 250.0 WYE / DELTA
Setting unit
Description Frequency setting Frequency tracking setting Phase CT ratio setting Ground CT ratio setting Phase PT Primary setting Phase PT Secondary setting Ground PT Primary setting Ground PT Primary setting Ground PT Secondary setting PT connect setting
4.4.2.3.
SETTING/SYSTEM/CB CONTROL
CLOSE : 5 . 0
36/76
4.4.2.4. SETTING/SYSTEM/ PT FUSE MONITOR PT FUSE MONITOR functions monitor of connecting transformer. FUSE MONITOR is composed of FUNCTION, POS UV PKP, NEG OV PKP and DELAY, used for setting of use or not of monitoring function, positive under voltage pickup, negative over voltage pickup and delay time of operation.
S E T T I N G P T FUSE MON I T OR F UNC T I ON : D I SABLE UV V PKP V 4 / 4 s 3 / 4 PKP 2 / 4 1 / 4
POS :
1 7 0 OV
NEG :
1 7 0
DELAY : 6 0 . 0 0
Description Setting of use or not Setting of positive under voltage pickup Setting of negative over voltage pickup Delay time setting of operation
4.4.2.5.
SETTING/SYSTEM/COM
COM menu is composed of FUNCTION, SLAVE ADDR, BPS, and PROTOCOL and each menu set up communication function, slave address, BPS and protocol.
S E T T I N G C O M F UNC T I ON : D I SABLE ADDR 1 3 / 4 3 0 0 2 / 4 1 / 4
SLAVE : BPS :
37/76
PROTOCOL : MOD B U S
4 / 4
Setting unit 1
Description Setting of use or not Slave address setting Setting of communication speed Protocol setting
4.4.2.6.
SETTING/SYSTEM/DNP3.0
DNP3.0 menu is composed of TX DELAY, LINK CONFIRM, LINK RETRY, LINK TIMEOUT, SBO TIMEOUT, WR TIME INT and COLD RESTART, and each menu set up Tx delay, Link confirm, Link retry, Link timeout, SBO timeout, Write time interval and Cold restart.
S E T T I N G D N P 3 . 0 TX : L I NK : DELAY 0 ms e c 2 / 7 1 / 7
CON F I RM
L I NK : L I NK : SBO : WR : COL D :
T I MEOU T 1 T I ME 0 ms e c I NT m i n
6 / 7
RESTART
7 / 7
D I SABLE
38/76
Item TX DELAY LINK CONFIRM LINK RETRY LINK TIMEOUT SBO TIMEOUT WR TIME INT COLD RESTART
Description Tx delay setting Link confirm setting Link retry setting Link timeout setting SBO timeout setting Write time interval setting Cold restart setting
4.4.2.7. SETTING/SYSTEM/CONTACT INPUT PAC-E500 has 4 Contact Input, it set each contact input CONTACT INPUT. There are NOT CONNECTED, CB OPENED, CB CLOSED, ANNUN RESET, PROT BLOCK and GENERAL INPUT in setting value of CONTACT INPUT. That CB may control, only if one or more contact inputs are allocated for CB Open/Closed status. In that case, CB is controlled the fastest contact input.
S E T T I N G C O N T A C T I NPUT CON T : I N# 1 1 / 4
NOT _ CONNEC T ED I N# 2 2 / 4
CON T :
NOT _ CONNEC T ED I N# 3 3 / 4
CON T :
NOT _ CONNEC T ED I N# 4 4 / 4
CON T :
NOT _ CONNEC T ED
Item
Setting unit
Basic value
Description
CONT IN #1~#4
NOT_CONNECTED
39/76
Description No effect Open CB, when input is logic 1. Close CB, when input is logic 1 Operate Annunciator Reset, if there is status change of Input Logic. Do action that protection element make BLOCK, when input is logic 1 and BLOCK of protection element is Yes. Used general Contact Input
4.4.2.8. SETTING/SYSTEM/CONTACT OUTPUT PAC-E500 has 4 Contact output and Contact output is set at CONTACT OUTPUT. There are LOGIC, 8 INPUT, RESET TYPE and RESET DELAY in setting value of Contact Output . Setting factor of LOGIC has OR8 and AND8 that are composed 8 Non-Inverting Input, and HALF-OR8 and HALF-AND8 that are composed 4 Non Inverting Input and 4 Inverting Input. Setting Factor of INPUT has System status, Contact Input/Output status and Operating status protection element, and RESET TYPE has two setting items; 1) SELF with RESET DELAY time and 2) MANUAL of LATCH type. RESET DELAY has Off Reset Delay time between 0.00sec ~ 60.00sec.
S E T T I N G C O N T A C T OUT PUT C O N T A C T C O N T OU T PU T
OU T # 1 OU T PU T
C O N T A C T C O N T
OU T # 2 OU T PU T
C O N T A C T C O N T
OU T # 3 OU T PU T
C O N T A C T C O N T
OU T # 4
I NPUT # 1 : L _OF F
I NPUT # 2 : L _OF F
3 / 1 1
40/76
I NPUT # 3 : L _OF F
4 / 1 1
I NPUT # 4 : L _OF F
5 / 1 1
I NPUT # 5 : L _OF F
6 / 1 1
I NPUT # 6 : L _OF F
7 / 1 1
I NPUT # 7 : L _OF F
8 / 1 1
9 / 1 1
RESET : SELF
1 0 / 1 1
RESET :
DELAY 1 1 / 1 1 s
6 0 . 0 0
Setting unit
Description Operator setting Input setting of Operator Form of Contact Output setting Off delay setting (Activated when RESET TYPE is SELF)
0.01sec
0.00sec
41/76
4.4.2.9.
SETTING/SYSTEM/LED
PAC-E500 provides 4 Programmable LED for the convenience of user. The setting method is same with CONTACT OUTPUT.
S E T T I N G L E D L E D L E D # 1 L E D L E D # 2 L E D L E D # 3 L E D L E D # 4
- LED (LED#1 ~ 4)
L E D L E D # 1 L OG I C : OR 8 2 / 1 1 1 / 1 1
I NPUT # 1 : L _OF F
I NPUT # 2 : L _OF F
3 / 1 1
I NPUT # 3 : L _OF F
4 / 1 1
I NPUT # 4 : L _OF F
5 / 1 1
I NPUT # 5 : L _OF F
6 / 1 1
I NPUT # 6 : L _OF F
7 / 1 1
I NPUT # 7 : L _OF F
8 / 1 1
I NPUT # 8 : L _OF F
9 / 1 1
42/76
RESET : SELF
TYPE
1 0 / 1 1
RESET :
DELAY 1 1 / 1 1 s
6 0 . 0 0
Setting unit
Description Operator setting Input setting of Operator Form of Contact Output setting Off delay setting (Activated when RESET TYPE is SELF)
0.01sec
0.00sec
4.4.2.10.
SETTING/SYSTEM/PASSWORD
There are 2 types of passwords for PAC-E500: Settings modification password and Control action password. Both passwords are same and 4-digit decimal 0~9 numbers and have the initial values of 0000 on delivery of PAC-E500.
S Y S T E M P A S S WO R D N EW : P A S S WO R D
* * * *
[PASSWORDS setting steps] 1) 2) 3) 4) 5) Right arrow key from PASSWORDS menu in Menu Tree Select which password to change using Up/Down keys and Right key Enter original settings modification password if required Change or select each of 4 digit values using arrow keys and ENT key Save setting changes in escaping SETTING menu or Change other values
43/76
4.4.2.11.
SETTING/PROTECTION
PROTECTION menu is composed of protection elements, OV1 (59_1), OV2 (59_2), UV1 (27_1), UV2 (27_1), OVG1 (59G_1), OVG2 (59G_2), OVG3 (59G_3), NSOV (47) and UF (81), and is used setting each of protection elements.
S E T T I N G P R O T E C T I O N P R O T E C T I O N O V 1 ( 5 9 _ 1 ) P R O T E C T I O N O V 2 ( 5 9 _ 2 ) P R O T E C T I O N U V 1 ( 2 7 _ 1 ) P R O T E C T I O N U V 2 ( 2 7 _ 2 ) P R O T E C T I O N O V G 1 ( 5 9 G _ 1 ) P R O T E C T I O N O V G 2 ( 5 9 G _ 2 ) P R O T E C T I O N O V G 3 ( 5 9 G _ 3 ) P R O T E C T I O N N S O V ( 4 7 ) P R O T E C T I O N U F ( 8 1 )
44/76
4.4.2.12. SETTING/PROTECTION/OV1 (59_1) OV1 (59_1) is Over Voltage protection including Definite Time-delayed. It operates Definite Time characteristic, when MODE is DEFINITE TIME, and operates voltage Inverse Time Delayed characteristic, when MODE is INVERSE CURVE.
P R O T E C T I O N O V 1 ( 5 9 _ 1 ) F UNC T I ON : D I SABLE 2 / 5 T I ME 3 / 5 V 4 / 5 s 4 / 5 1 / 5
MO D E : DEF I N I TE
P I CKUP : 1 7 0
DELAY : 6 0 . 0 0
MU L T I P L I E R : 1 0 . 0 0
BLOCK : NO
5 / 5
Setting unit
Description Protection Elements setting Operation Mode setting Pickup setting Operation delay time setting (Setting when Mode is Definite Time) Multiplier setting (Setting when Mode is Inverse Curve) Ban protection function It is set PROT_BLOCK of Contact Input, and banned protection function when Contact input status is Logic 1.
1V 0.01sec
0.01
10.00
BLOCK
YES/NO
NO
45/76
4.4.2.13. SETTING/PROTECTION/OV2 (59_2) OV2 (59_2) is Over Voltage protection including Definite Time-delayed. It operates Definite Time characteristic, when MODE is DEFINITE TIME, and operates voltage Inverse Time Delayed characteristic, when MODE is INVERSE CURVE.
P R O T E C T I O N O V 1 ( 5 9 _ 1 ) F UNC T I ON : D I SABLE 2 / 5 T I ME 3 / 5 V 4 / 5 s 4 / 5 1 / 5
MO D E : DEF I N I TE
P I CKUP : 1 7 0
DELAY : 6 0 . 0 0
MU L T I P L I E R : 1 0 . 0 0
BLOCK : NO
5 / 5
Setting unit
Description Protection Elements setting Operation Mode setting Pickup setting Operation delay time setting (Setting when Mode is Definite Time) Multiplier setting (Setting when Mode is Inverse Curve) Ban protection function It is set PROT_BLOCK of Contact Input, and banned protection function when Contact input status is Logic 1.
1V 0.01sec
0.01
10.00
BLOCK
YES/NO
NO
46/76
4.4.2.14. SETTING/PROTECTION/UV1 (27_1) UV1 (27_1) is Over Voltage protection including Definite Time-delayed. It operates Definite Time characteristic, when MODE is DEFINITE TIME, and operates voltage Inverse Time Delayed characteristic, when MODE is INVERSE CURVE.
P R O T E C T I O N U V 1 ( 2 7 _ 1 ) F UNC T I ON : D I SABLE 2 / 5 T I ME 3 / 5 V 4 / 5 s 4 / 5 1 / 5
MO D E : DEF I N I TE
P I CKUP : 1 7 0
DELAY : 6 0 . 0 0
MU L T I P L I E R : 1 0 . 0 0
BLOCK : NO
5 / 5
Setting unit
Description Protection Elements setting Operation Mode setting Pickup setting Operation delay time setting (Setting when Mode is Definite Time) Multiplier setting (Setting when Mode is Inverse Curve) Ban protection function It is set PROT_BLOCK of Contact Input, and banned protection function when Contact input status is Logic 1.
1V 0.01sec
0.01
10.00
BLOCK
YES/NO
NO
47/76
4.4.2.15. SETTING/PROTECTION/UV2 (27_2) UV1 (27_2) is Over Voltage protection including Definite Time-delayed. It operates Definite Time characteristic, when MODE is DEFINITE TIME, and operates voltage Inverse Time Delayed characteristic, when MODE is INVERSE CURVE.
P R O T E C T I O N U V 1 ( 2 7 _ 2 ) F UNC T I ON : D I SABLE 2 / 5 T I ME 3 / 5 V 4 / 5 s 4 / 5 1 / 5
MO D E : DEF I N I TE
P I CKUP : 1 7 0
DELAY : 6 0 . 0 0
MU L T I P L I E R : 1 0 . 0 0
BLOCK : NO
5 / 5
Setting unit
Description Protection Elements setting Operation Mode setting Pickup setting Operation delay time setting (Setting when Mode is Definite Time) Multiplier setting (Setting when Mode is Inverse Curve) Ban protection function It is set PROT_BLOCK of Contact Input, and banned protection function when Contact input status is Logic 1.
1V 0.01sec
0.01
10.00
BLOCK
YES/NO
NO
48/76
4.4.2.16. SETTING/PROTECTION/OVG1 (59G_1) OVG1 (59G_1) is Ground Over Voltage protection including Definite Time-delayed. It operates Definite Time characteristic, when MODE is DEFINITE TIME, and operates voltage Inverse Time Delayed characteristic, when MODE is INVERSE TRIP or INVERSE ALARM in accordance with each time characteristic curve.
P R O T E C T I O N O V G 1 ( 5 9 G _ 1 ) F UNC T I ON : D I SABLE 2 / 5 T I ME 3 / 5 V 4 / 5 s 4 / 5 1 / 5
MO D E : DEF I N I TE
P I CKUP : 1 7 0
DELAY : 6 0 . 0 0
MU L T I P L I E R : 1 0 . 0 0
BLOCK : NO
5 / 5
Setting unit
Description Protection Elements setting Operation Mode setting Pickup setting Operation delay time setting (Setting when Mode is Definite Time) Multiplier setting (Setting when Mode is Inverse Curve) Ban protection function It is set PROT_BLOCK of Contact Input, and banned protection function when Contact input status is Logic 1.
1V 0.01sec
0.01
10.00
BLOCK
YES/NO
NO
49/76
4.4.2.17. SETTING/PROTECTION/OVG2 (59G_2) OVG2 (59G_2) is Ground Over Voltage protection including Definite Time-delayed. It operates Definite Time characteristic, when MODE is DEFINITE TIME, and operates voltage Inverse Time Delayed characteristic, when MODE is INVERSE TRIP or INVERSE ALARM in accordance with each time characteristic curve.
P R O T E C T I O N O V G 2 ( 5 9 G _ 2 ) F UNC T I ON : D I SABLE 2 / 5 T I ME 3 / 5 V 4 / 5 s 4 / 5 1 / 5
MO D E : DEF I N I TE
P I CKUP : 1 7 0
DELAY : 6 0 . 0 0
MU L T I P L I E R : 1 0 . 0 0
BLOCK : NO
5 / 5
Setting unit
Description Protection Elements setting Operation Mode setting Pickup setting Operation delay time setting (Setting when Mode is Definite Time) Multiplier setting (Setting when Mode is Inverse Curve) Ban protection function It is set PROT_BLOCK of Contact Input, and banned protection function when Contact input status is Logic 1.
1V 0.01sec
0.01
10.00
BLOCK
YES/NO
NO
50/76
4.4.2.18. SETTING/PROTECTION/OVG3 (59G_3) OVG3 (59G_3) is Ground Over Voltage protection including Definite Time-delayed. It operates Definite Time characteristic, when MODE is DEFINITE TIME, and operates voltage Inverse Time Delayed characteristic, when MODE is INVERSE TRIP or INVERSE ALARM in accordance with each time characteristic curve.
P R O T E C T I O N O V G 3 ( 5 9 G _ 3 ) F UNC T I ON : D I SABLE 2 / 5 T I ME 3 / 5 V 4 / 5 s 4 / 5 1 / 5
MO D E : DEF I N I TE
P I CKUP : 1 7 0
DELAY : 6 0 . 0 0
MU L T I P L I E R : 1 0 . 0 0
BLOCK : NO
5 / 5
Setting unit
Description Protection Elements setting Operation Mode setting Pickup setting Operation delay time setting (Setting when Mode is Definite Time) Multiplier setting (Setting when Mode is Inverse Curve) Ban protection function It is set PROT_BLOCK of Contact Input, and banned protection function when Contact input status is Logic 1.
1V 0.01sec
0.01
10.00
BLOCK
YES/NO
NO
51/76
4.4.2.19. SETTING/PROTECTION/NSOV (47) NSOV (47) is Negative Sequence Phase Over Voltage protection. In case of the negative phase voltage higher than pick-up, it operates Definite Time characteristic that has operate time.
P R O T E C T I O N N S O V ( 4 7 ) F UNC T I ON : D I SABLE 2 / 4 V 3 / 4 s 4 / 4 1 / 4
P I CKUP : 1 7 0
DELAY : 6 0 . 0 0
BLOCK : NO
Description Protection Elements setting Pickup setting Operation delay time setting (Setting when Mode is Definite Time) Ban protection function It is set PROT_BLOCK of Contact Input, and banned protection function when Contact input status is Logic 1.
BLOCK
YES/NO
NO
<Table 4.4.2.19.NSOV (47) Setting Item> 4.4.2.20. SETTING/PROTECTION/UF (81) UF (81) is Under Frequency protection. In case of the frequency of A-phase voltage lower than FREQ PICKUP, it operates and requisite fault detection is added when each Block element is set. Voltage is input lower than UV PICKUP when UV PICKUP is set and in case of under frequency the protection element doesnt operate blocked. And OC BLOCK and dF/dT BLOCK operate in the same way.
P R O T E C T I O N U F ( 8 1 ) F UNC T I ON : UV : D I SABLE P I CKUP 1 7 0 V 2 / 1 0 1 / 1 0
52/76
OC :
P I CKUP 1 0 . 0 0 A
3 / 1 0
dF / dT :
PKP Hz
4 / 1 0
- 1 0 . 0 0
FREQ :
P I CKUP Hz
5 / 1 0
6 5 . 0 0
6 / 1 0
7 / 1 0
8 / 1 0
dF / dT : NO
9 / 1 0
BLOCK : NO
1 0 / 1 0
Item FUNCTION UV PICKUP OC PICKUP dF/dT PKP FREQ PICKUP DELAY UV BLOCK OC BLOCK dF/dT BLOCK
Range ENABLE/DISABLE 5~170V 0.10 ~ 20.00*In -10.00 ~ -0.10Hz 45.00 ~ 65.00Hz 0.00 ~ 180.00sec YES/NO YES/NO YES/NO
Description Protection Elements setting Under Voltage Pickup setting Over Current Pickup setting Transient frequency Pickup setting Frequency Pickup setting
BLOCK
YES/NO
180.00sec Operation delay time setting NO Under Voltage Block setting NO Over Current Block setting NO Transient frequency Block setting Ban protection function It is set PROT_BLOCK of Contact NO Input, and banned protection function when Contact input status is Logic 1.
53/76
C O M M A N D C O N T OU T TEST
C O M M A N D P A N E L TEST
4.4.3.1.
DE ENERG I Z ED OUT # 2 2 / 4
CON T :
DE ENERG I Z ED OUT # 3 3 / 4
CON T :
DE ENERG I Z ED OUT # 4 4 / 4
CON T :
DE ENERG I Z ED
[CONT OUT TEST command steps] 1) 2) 3) 4) Right arrow key from CONT OUT TEST menu in Menu Tree Select test item of 16 contact outputs using Up/Down key and Right key Enter settings modification password if required Execute Energized or DeEnergized test using Up/Down key Run/Test LED blinking green or Error message 5) Left key to escape and Repeat steps 2~4 for other items
54/76
4.4.3.2. COMMAND/PANEL TEST PANEL TEST command is used to test LCD and LEDs on front-face display panel.
C O M M A N D P A N E L TEST TESTTESTTEST TEST TESTTESTTEST TEST
[PANEL TEST command steps] 1) Right arrow key from PANEL TEST menu in Menu Tree 2) Enter settings modification password and Right arrow key again 3) LCD and all LEDs blinking or Error message, and Return to Menu Tree
55/76
5.1
DIMENSIONED DRAWINGS
5.1.
57/76
5.2
EXTERNAL CONNECTIONS
AC or DC
SURGE
PWR+
PWR-
30
28
29
Internally Fused
PAC-E500 PAC-E100
5.2.2 CT Connections
Refer to the Table 5.2. Terminal Block Diagram Table in the above
PAC-E500
16 1
IA+ IA-
58/76
5.2.3 PT Connections
Refer to the Table 5.2. Terminal Block Diagram Table in the above.
PAC-E500
Fuse
Fuse
17 2 18 3 19 4
PAC-E500
Fuse
Fuse
Fuse
17 2 18 3 19 4
59/76
PAC-E500
Fuse
Fuse
Fuse
17 2 18 3 19 4
PAC-E500
20 20
VN+ VN-
60/76
+
6 21
T C
PAC-E500
TS1_NO TS1_COM
(Wet)
DC 125V
11 26
DI1_P DI1_N
PAC-E500
1: NA 2: TXD 1 3: RXD 4: NA 5: Signal Ground 5 6: NA 7: NA 9 Pins 8: NA RS232 9: NA D-sub Connector Female
Notebook PC
Pin No. 2 & 3
61/76
PAC-E500 SCADA
+ Chassis Grounded only (*) ZT : 120 (Terminal Resistor)
5
ZT (*) SHIELD
Twisted Pair
2:RS485_DATA+ 3:RS485_DATA5:RS485_COM
62/76
16
17
18
19
20
IA +
IA -
VA +
VA -
VB +
VB -
VC +
VC -
VN +
VN -
Current Inputs
Voltage Input
11
DI1_P
26
DI1_COM
12
DI2_P
27
DI2_COM
C o n t a c t I n p u t s
DIGITAL I/O C o n t a c t
TS1_NO
TS1_COM
21
TS2_NO
TS2_COM
22
13
DI3_P
TS3_NO
14
DI4_P
15
DI3_4_COM
DC AC or DC
O u t p u t s
TS3_COM
23
TS3_NC
TS4_NO
10
TS4_COM
24
28
POWER+
POWER
TS4_NC
25
29
POWER-
30
SURGE
DB-9
Front
DB-9
Rear
DB-9
Rear
63/76
6.1
SETTING SOFTWARE
Modification of settings or/and system configuration is generally performed using keypad buttons in the LCD menu on front panel of PAC-E500. But this job is handled item by item at one time. So, this setting tool is used to facilitate a batch job. Refer to the figure of RS232 connection in the previous section, and the ModBus protocol is used. All the data can be saved in files as project concept and the specific setting values are downloaded to PAC-E500 just by opening the saved project data file. Other functions include event data uploading & listing, fault data uploading, and data printing. : Certainly, COMport must be used 1 port of front or rear because RS232C port located front and rear panel of PACE500 is not communicate at the same time.
Caution
64/76
65/76
66/76
67/76
68/76
69/76
6.1.8 Monitor
Monitor display shows status monitoring of PAC-E500. Elements or status monitoring is composed of Measurement, Self Diagnosis, Protection Component, LED Output, Breaker and Contact Input/ Output, and there is Annun Reset button on front panels left. Refer to LCD setting menu on chapter 4 Operational Description for more detailed explanation.
70/76
71/76
72/76
73/76
74/76
1 2 3
1 2
1 2
75/76