GENERAL
AI-508, an economical and easy operated model of Yudian artificial intelligent industry controller, is specially designed for use in the industries of plastic machinery, food machinery, packaging machinery, baking machinery and environmental testing equipment. achieving precise control. Multiple thermocouples and RTDs are selectable. achieving accurate and stable measurement. Advanced modular structure, conveniently providing various outputs options, and making quick delivery and easy maintenance. High quality and performance hardware design, using high performance tantalum capacitor or ceramic capacitor. temperature. ISO9001 certification and CE certified, achieving world class level of quality, anti-interference ability and safety. Compared to competing models, it consumes less electricity, experiences less temperature shifting, provides higher stability and reliability and can work in a wider range of Integrated non-linear graduation tables, digital calibration and auto zero technology, and It features: Application of artificial intelligence control algorithm with auto tuning function, avoiding the overshoot problem of standard PID algorithm and
shows the basal function of instrument economical artificial intelligence temperature controller shows the front panel dimension : Front panel 9696mm(widthheight), cut out 9292mm, depth behind mounting surface 100mm Front panel 7272mm(widthheight), cut out 6868mm, depth behind mounting surface 95mm Front panel 4896mm(widthheight), cut out 4592mm, depth behind mounting surface 100mm Front panel 9648mm(widthheight), cut out 9245mm, depth behind mounting surface 100mm Selectable modules are as follows: Relay output module (Capacity: 2A/250VAC, only normally open terminal can absorb electrical spark) Relay output module (Capacity: 1A/250VAC, small volume) SSR voltage output module (30mA/5DC) TRIAC zero crossing trigger output module. TRIAC power module of current 5-500A) shows the module type of alarm output. N (or none) L1 L2 L5 no module installed Selectable modules are as follows: Suitable for single-phase power.
D2 Front panel 4848mm(widthheight), cut out 4545mm, depth behind mounting surface 95mm
W1 TRIAC no contact normally open discrete output module, suitable for AC contactors up to 80A, and has low interference and long life. Three phases TRIAC zero crossing trigger output module (can trigger three-phase of TRIAC, a pair of inversely parallel connected SCRs or
Relay contact output module (Capacity: 2A/250VAC, normal open terminal can absorb spark, support AL1 alarm output) Relay contact output module (Capacity: 1A/250VAC, small volume, support AL1 alarm output) Output module of dual normal open relay output (Capacity: 2A/250VAC, support AL1 and AL2 alarm output) no module installed
shows the module type of Auxiliary output (AUX). Selectable modules are as follows: N (or none) L1 L2 L5 Relay contact output module (Capacity: 2A/250VAC, normal open terminal can absorb spark, support AU1 alarm output) Relay contact output module (Capacity: 1A/250VAC, small volume, support AU1 alarm output) Output module of dual normal open relay outputs(Capacity: 2A/250VAC, support AU1 and AU2 alarm output) OUPT socket, but L2, which is smaller, can be installed instead. There is no AUX socket in D2 instruments. L5 module cant be installed in the
Note1: For instrument of dimension D2, because of its limited volume, when L1 or L5 module is installed in the ALM socket, L1 cant be installed in the Note2: K3 cant be installed in instruments with dimension D or D2. ALM socket of instrument with dimension D.
TECHNICAL SPECIFICATION
Input type : K, S, R, E, J, N, Pt100 Measurement range : K(01300), Temperature display resolution : 1 Control mode : On-off control mode Output mode (modularized) : L1 L2 G K1 K3 Relay contact output module (Normal open + normal close. Relay contact output module (Normal open + normal close. SSR voltage output module (DC 12V/30mA) TRIAC zero crossing trigger output module (can trigger TRIAC, a pair of inversely parallel connected SCRs or TRIAC power module with current rating of 5-500A) Three-phase TRIAC zero crossing trigger output module (can trigger TRIAC, 2 inversely parallel connected SCR or TRIAC power module of current 5-500A) Alarm function : High limit, low limit, and deviation high alarm. 50-60Hz. Power supply voltage rating : 100-240VAC, -15%, +10% ; Power consumption : 3W. Ambient : Temperature of -1060, humidity of 090RH% Reliability : repairing and returning rate 0.8% (according to the statistics data from 2003 to 2004.) Electromagnetic compatibility (EMC) : IEC61000-4-4: 4KV/5KHz; IEC61000-4-5: 4KV Capacity: 2A/250VAC or 30VDC/2A) Capacity: 1A/250VAC, small volume) or Artificial Intelligence control with auto tuning. S(01700), R(01600), E(0800), J(01000), N(01300), Pt100(-200800) Measurement accuracy : 0.3%FS1
W1 TRIAC no contact normal open discrete output module (Capacity: 100-240VAC/0.2A, instantaneous current 2A with time<20ms and period>5s)
PV
SV
Indicator lamps (MIO, OP1, OP2, AL1, AL2, AU1and AU2 indicate the I/O actions
A/M RUN/HOLD STOP
range (for example, the thermocouple or RTD circuit is break, or input specification sets wrong), the upper display window will alternately display orAL and the high limit or the low limit of PV, and the instrument will automatically stop output.
AI AI
OPERATION DESCRIPTION
Set Value Setting: In basal display status, if the parameter lock Loc isn't locked, decrease the value, Parameter Setting: In basal display status, press pressing or and then press and hold for about 2 seconds can access Field Parameter Table. can modify a parameter. Press and hold Pressing can go to the next parameter; (don't release) can return to the preceding parameter. Press can access System Parameter Table. In basal display status, press to active the to increase the value, and decreasing or inscreasing value get quick. we can set setpoint (SV) by pressing or or . Press to to move to the digit expected to modify. Keep pressing , the speed of
simultaneously can escape from the parameter table. The instrument will escape auomatically from the parameter table if no Setting Loc=808 and then press
Artificial Intelligence control and auto tuning When AI control method is chosen (CtrL=APId), for 2 seconds, the At parameter will appear. auto-tuning process. appear again. the PID parameters can be obtained by running auto-tuning. Press to change the value of At from oFF to on, then press
After 2-3 times of on-off action, the instrument will obtain the for about 2 seconds until the "At" parameter So youd better set setpoint to an often-used value
If you want to escape from auto tuning status, press and hold
to confirm, then the auto tuning process will be cancelled. For the ovens with good heat preservation, the setpoint can be set at the highest applicable Depending on the system, the auto-tuning time can be from several seconds Generally, the smaller the value of
If the setpoint is different, the parameters obtained from auto-tuning are possible different. or middle value first, and then start auto-tuning. temperature. to several hours. It is forbidden to change SV during auto tuning.
Note 2:
Parameter CHYS (on-off differential, control hysteresis) has influence on the accuracy of auto-tuning. CHYS, the higher the precision of auto tuning. around setpoint due to the oscillation of input. CHYS is recommended to be 2.0. It is able to learn the process while working.
But CHYS parameter value should be large enough to prevent the instrument from error action The control effect at the first run after auto
Note 3:
tuning is probably not perfect, but excellent control result will be obtained after a period of time because of self-learning.
CtI
Control period
FILt
PV input filter
040
Loc
Parameter Lock
09999
System parameter table (set Loc=808 and then press Alarm Hysteresis
AHYS
Avoid frequent alarm on-off action because of the fluctuation of PV From right side to left side, the first, second and third digit of AOP individually indicate the alarm output terminal of HIAL, LoAL and HdAL. 0 shows no output. 1 HIAL
AOP
Alarm
output
assignment
outputted to AL1, AL2, AU1 or AU2. AOP = 1 HdAL onoF : On-off control
It shows that HIAL and HdAL are sent to AL1, and LoAL has no output. CtrL CHYS Control mode Control Hysteresis onoF, APId 0200 APId : AI PID control, high precision and no-overshoot CHYS is used for on-off control to avoid frequent on-off action of relay. For heating system, if PV > SV, output turns off; PV<SV-CHYS, output turns on. InP 0 InP Input specification 2 4 6 8-20 Scb Input Shift Selection Fru of K R E Spare Spare Input spec. InP 1 3 5 7 21 S Spare J N Pt100 -200 400 50C, 50F, 60C, 60F -999 3000 -999 3000 0 400 50C 0 021 0 Input spec. APId 2
Scb is used to make input shift to compensate the error produced by sensor or input signal. PV_after_compensation= PV_before_compensation + Scb. 50C: 50Hz, . 50F: 50Hz, . 60C: 60Hz, . 60F: 60Hz, . Input has maximum anti-interference ability to 50Hz frequency; Input has maximum anti-interference ability to 50Hz frequency; Input has maximum anti-interference ability to 60Hz frequency; Input has maximum anti-interference ability to 60Hz frequency;
SPL SPH
Minimum value that SV allowed to be. Maximum value that SV allowed to be.
Note:
The
compensation
1
100-240VAC~ COM
11
N/C
wires for different kinds of thermocouple are different, and should be directly
2 3 4 5 6 7 8 9 10
12 13 14 15 16 17 18
G2
OUTP
between
+ +
measurement error.
0-5V
ALM
+ 1-5V
+ +
19 20
COM COM
AUX
For instruments with dimension F, just clockwise rotate the graph 90 degree and the terminal numbers keep the same.
8
N/C
1
100-240VAC~
COM
6 7 8 9 10
2 3 4 5 6 7
9 10
G2
+ +
N/O COM
2
N/O
N/O
G2
OUTP
OUTP
3
11
AL1
4
12
+ +
5
13 14
ALM
COM COM
AUX
BX
G2
ZNR
100~380VAC
V
Load
BX
G2
ZNR
100~380VAC Load
Note: It is recommended to use the power module, which includes 2 pair of SCRs and diodes. less trigger current.