Read this document carefully before using this device.

The guarantee will be expired by damaging of the device if you don't attend to the directions in the user manual. Also we don't accept any compensations for personal injury, material damage or capital disadvantages.

ENDA ETC4420 PID TEMPERATURE CONTROLLER


Thank you for choosing ENDA ETC4420 temperature controller.
* 48 x 48mm sized. * Selectable sensor type. * Automatic calculation of PID parameters (SELF TUNE).
Enter PID parameters of the system if they are known at the beginning. Otherwise, Self-Tune should be activated.
ETC 4420
CNT/AL2

* Soft-Start. * Communication vai RS-485 ModBus protocol (Optional). * Selectable SSR or relay control output. * Relay output can be programmable as second alarm or control output. * AL1 relay output for first alarm out. * Selectable Heat/Cool control. * Input offset feature. * In the case of sensor failure periodical running or relay state can be selected. * Parameter access protection on 3 levels. * Programming by using keypad or Modbus. * CE marked according to European Norms.

SSR
AL1

PV

SV SET

CSET

ASET
TEMPERATURE CONTROLLER

ENDA

TECHNICAL SPECIFICATIONS
Input type Pt 100 Resistance Thermometer Pt 100 Resistance Thermometer J (Fe-CuNi) Thermocouple K (NiCr-Ni) Thermocouple T (Cu-CuNi) Thermocouple S (Pt/0Rh-Pt) Thermocouple R (Pt13Rh-Pt) Thermocouple EN 60751 EN 60751 EN 60584 EN 60584 EN 60584 EN 60584 EN 60584 Temperature range F C -200...600 C -328... +1112 F -99.9...300.0 C -99.9...+543.0F 0... 600 C +32... +1112 F 0...1200C +32... +2192 F 0... 400C +32... +752 F 0...1600C +32... +2912 F 0...1600C +32... +2912F Accuracy 0,2% (of full scale) 0,2% (of full scale) 0,2% (of full scale) 0,2% (of full scale) 0,2% (of full scale) 0,2% (of full scale) 0,2% (of full scale) 1 digit 1 digit 1 digit 1 digit 1 digit 1 digit 1 digit

ENVIRONMENTAL CONDITIONS
Ambient/storage temperature 0 ... +50C/-25... +70C (with no icing) Max. Relative humidity 80% up to 31C decreasing linearly 50% at 40C . According to EN 60529 Front panel : IP65 Rated pollution degree Rear panel : IP20 Height Max. 2000m Do not use the device in locations subject to corrosive and flammable gases.

ELECTRICAL CHARACTERISTICS
Supply Power consumption Wiring Line resistance Data retention EMC Safety requirements 230V AC +10% -20%, 50/60Hz or 24V AC 10%, 50/60Hz. Max. 5VA 2.5mm screw-terminal connections For thermocouple max.100ohm, for 3 wired Pt 100 max. 20ohm EEPROM (minimum 10 years) EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for standard EN 61000-4-3) EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)

OUTPUTS
CONT./AL2 AL1 SSR out Life expectancy for relay Relay : 250V AC, 2A ( for resistive load), NO/NC. Selectable as Control or Alarm2 output. Relay : 250V AC, 2A ( for resistive load), NO/NC selectable. (Alarm1 output). Selectable logic control output. (Max 12V 20mA( Mechanical 30.000.000 operation; Electrical 300.000 operation

CONTROL
Control type Control algorithm A/D converter Sampling time Proportional band Integral time Derivative time Control period Hysteresis Output power Single set-point and alarm control On-Off / P, PI, PD, PID (selectable) 15 bits 500ms Adjustable between 0% and 100%. If Pb=0%, On-Off control is selected. Adjustable between 0.0 and 100.0 minutes Adjustable between 0.00 and 25.00 minutes Adjustable between 1 and 250 seconds Adjustable between 1 and 50C/F The ratio of power at a set point can be adjusted between 0% and 100%

HOUSING
Housing type Dimensions Weight Enclosure material Suitable for flush-panel mounting according to DIN 43 700. W48xH48xD87mm Approx. 250g (after packing) Self extinguishing plastics.

While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used. 1/4 ETC4420-E-02-R

SET
CSET ASET
If key is pressed while holding

SET
key, the programming mode is enabled.

ASET

CSET

Entering from the programming mode to the run mode: If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the run mode is entered. SET Alternatively, the same function occurs first pressing key and then pressing keys together.
ASET

SET
CSET ASET

CSET ASET

Con.o.
ASET

ALr.o.
ASET

ConF.
ASET

S.tun.
ASET
Before starting sef-tune procedure, be sure A.tun parameter is YES in the SECU menu.

SECU.
ASET

Pb 4 t 4.0
td 1.00

Pb = Proportional band. Adjustable between 0% and 100% Setting Pb = 0% On-Off control is selected.
Ti = Integral time. Adjustable between 0.0 and 100.0 minutes. If ti = 0.0, integral effect is not used. Setting Pb = 0 this parameter is not seen. td = Derivative time. Adjustable between 0.00 and 25.00 minutes. If td = 0.00, derivation effect is not used. Setting Pb = 0 this parameter is not seen. Ct = Control period.
Adjustable between 1 and 250 seconds. Setting Pb = 0 and C.ot.S.= Out1 this parameter is not seen.

A1.Hy. 2 A1.tp. ndE.

A1.Hy. = Hysteresis of the Alarm1 output. Adjustable between 1 and 50C.


Function of Alarm1 output. Four kinds of functions can be selected. indE. = Independent dE. = Deviation bAnd = Band bAn.i. = Band with inhibition

nP. FE.cn.

A1.tP. =

inP. = Type of input and scale. Pt = Pt 100 -200 to +600C Pt.0 = Pt 100 -99.9 to +300.0C FE.cn. = J (Iron vs. Copper-Nickel) 0 to +600C nc.nA. = K (Nickel-Cr.vs. Nickel-Alum.) 0 to +1200C c.cn. = T (Copper vs. Copper-Nickel) 0 to +400C P10.r. = S (Platinum-10%Rhodium vs. Pt.) 0 to +1600C P13.r. = R (Platinum-13%Rhodium vs. Pt.) 0 to +1600C Note : If the selected input type is changed, the value of C.Hi.L, C.Lo.L , A.Hi.L., A.Lo.L. parameters changes automatically.

S.cod. 0
A.Con. P.yES

S.cod. = Security menu access code. It should be 666. A.Con. = Parameters of CoN.o menu access level code. nonE = Invisible P.yES = Modification can be done. P. no = Only visible.

S.Str. run
SET
CSET

C.Hi.L. 600

A1.St. A1.St. = The state of Alarm1. H. If independent or deviation alarm is

C.Hi.L. = Set point upper limit. If InP. or UnIt. parameters are changed, the maximum value of the C.Hi.L. parameter changes to the maximum scale value of the selected input. The minimum value is the value of C.Lo.L. parameter. C.LoL. = Set point lower limit.
If InP. or UnIt. parameters are changed, the minimum value of the C.Lo.L. parameter changes to the minimum scale value of the selected input. The maximum value is the value of C.Hi.L. parameter.

A.ALr. A.ALr.. = Parameters of ALr.o menu access level code. P.yES nonE = Invisible
Yes
Process value is equal or lower than 60%of the set point ?
P.yES = Modification can be done. P. no = Only visible.

Ct 20 P.SEt. 0

P.SEt. = The ratio of output power at the set point.Adjustable between 0% and 100%. If this parameter is set to 0, the output power becomes 0 at the set point. If it is adjusted to 50% output power becomes 50% at the set point. Using this parameter the energy requirements of the system is adjusted at the set point. So the set point can be achieved by minimum fluctuations and in the shortest time.Setting Pb = 0, this parameter is not seen. C.HYS. = Hysteresis of the control output. Adjustable between 1 and 50 C/F. Setting Pb = 0 this parameter is seen.

selected, this parameter can be Lo. and Hi. For Lo. alarm output is energized below the alarm set point. For Hi. alarm output is energized above the alarm set point. If band alarm is selected, this parameter can be bIHI or boHI. bIHI means alarm is activated inside the band.boHI means alarm is activated outside the band.

C.Lo.L. 0 oFFS. 0

A.CNF. A.CNf. = Parameters of ConF. menu access level code. P.yES nonE = Invisible
P.yES = Modification can be done. P. No = Only visible.

oFFS. = Offset value.


Offset value is added to the measurement value. Adjusted between -99 and +99C.The normal value is 0.

No

A1.P.e. oFF

C.HyS. 2

A1.p.e. = State of Alarm1 output in the case of sensor failure. If A1.p.e.= On , the alarm output is energized during the sensor failure. If A1.p.e.= oFF, the alarm output is not energized during the sensor failure. A2.Hy. = Hysteresis of the Alarm2 output. Adjustable between 1 and 50C. NOTE! If C.ot.S. =.out1, this parameter is not seen. A2.tP. = Function of Alarm2 output. Four kinds of functions can be selected. indE. = Independent dE. = Deviation bAnd = Band bAn.i. = Band with inhibition NOTE! If C.ot.S. = .out1, this parameter is not seen.

70 TE.H.

A.tun. yES

Unit. C

UnIt = The temperature unit. Selectable as C or F. Note : If the temperature unit is changed, the value of the UPL., Lol., A.UP.L., A.Lo.L. Parameters changes automatically. NOTE! IfInp parameter is selected TC or Pt100, this parameter is seen. A1.H.L = Alarm1 value upper limit. If InP. or UnIt. parameters are changed, the maximum value of the A1.H.L. parameter changes to the maximum scale value of the selected input type. Minimum of A1.H.L. parameter is the value of A1.L.L. parameter. A1.L.L. = Alarm1 value lower limit. If InP. or UnIt. parameters are changed, the minimum value of the A1.L.L. parameter changes to the minimum scale value of the selected input type. The maximum value is the value of A1.H.L. parameter. A2.H.L
= Alarm2 value upper limit. If InP. or UnIt. parameters are changed, the maximum value of the A2.H.L. parameter changes to the maximum scale value of the selected input type. Minimum of A2.H.L. parameter is the value of A2.L.L. parameter. NOTE! If C.ot.S. = .out1, this parameter is not seen. = Alarm2 value lower limit. If InP. or UnIt. parameters are changed, the minimum value of the A2.L.L. parameter changes to the minimum scale value of the selected input type. The maximum value is the value of A2.H.L. parameter.

A.tun. = Parameters of S.tun. menu access level code. no = Invisible yES = Self tune can be done.

A2.Hy. 2

A1.H.L. 600

C.StA. C.StA. = Configuration of the control output. C.StA. = HEAt means heating control. HEAt C.StA. = cooL means cooling control. Pr.Er. 0

Pr.Er. = This parameter is used to adjust the control output during a sensor failure. Adjustable between 0% and 100%. If this parameter is adjusted to a value closer to the energy requirements of the system at the set point, process temperature is prevented to rise or drop to dangerous levels.
= Type of control output Out1 = Out1 is control output. S.s.r = SSr control output. Out1 = Alarm2 output.

A2.tp. ndE.

A1.L.L. 0 A2.H.L. 600

25 REdY.

Press any key

25 Pd.t.

After PID is calculated

25 P.SE.t.

Press any key to deactivate the self-tune procedure.

SET

While holding
CSET

key, run message flashes. Then when

key is pressed,

C.oT.S. Out1

C.ot.S.

A2.St. A2.St. = The state of Alarm2. H. If independent or deviation alarm is

S.S.T.S. 0

S.S.t.S. = Soft Start timer set point value This parameter indicates the time to reach set point value when the device is first energized. Adjustable between 0 and 250 minutes. If 0 is selected, soft start feature will be enable and the device reaches set point value quickly. NOTE! Setting Pb = 0, soft start feature will be disable.

selected, this parameter can be Lo. and Hi. For Lo. alarm output is energized below the alarm set point. For Hi. alarm output is energized above the alarm set point. If band alarm is selected, this parameter can be bIHI or boHI. bIHI means alarm is activated inside the band. boHI means alarm is activated outside the band. NOTE! If C.ot.S. = .out1, this parameter is not seen.

A2.L.L. 0

A2.L.L.

self tune mode is entered if there is no probe failure. If process value is Appropriate to begin self tune, rEdY. message flashes. Then press any key to see Pid.t. message and self tune procedure begins.Process value must be equal or lower than 60%of the setpoint to begin self tune procedure. If not, tE.Hi. message flashes and device waits to decrease appropriate temperature to begin self tune. Then rEdY. message flashes and press any key to begin sellf tune procedure. Before self tune procedure, A.tun. parameter must be selected yES from the SECU menu.If self tune is achieved A.tun. parameter becomes no automatically and S.tun menu is canceled. Before self tune procedure, temperature setpoint value should be adjusted. When self tune procedure begins with no failure, Pid.t. message flashes and remains during the calculation of PID parameters. When PID parameters are calculated, P.SE.t. message flashes. Then the device heats until setpoint value according to PID parameters and calculates the energy requirement for stable temperature and writes P.SE.t. parameter as %and run mode enters. If any key is pressed while Pid.t. message flashes, self tune prosedure is deactivated before calculation of PID parameters. If any key is pressed while P.SE.t. message flashes, then self tune prosedure is deactivated as PID parameters are calculated and P.SE.t. parameter is done 0.

fL.Co. 5

fL.Co. = Coefficient of digital filter. Filter for display value. Adjustable between 1 and 32. If this parameter is 1, digital filter runs most quick. If the parameter is 31, the filter run most slow. The value of parameter should be increased in interference. d.adr. = Device address. Adjusable between 1 and 247. Difference addresses should be selected for every device.

d.adr. 1

Modification Of Parameter Diagram


C.HyS. 6
SET
CSET

C.HyS. 6
SET

SET
CSET

C.HyS. 5

SET
CSET

C.HyS. 6

SET
CSET

A2.P.e. A2.p.e. = State of Alarm2 output in the oFF case of sensor,failure. output is If A2.p.e.= On the alarm
energized during the sensor failure. If A2.p.e.= oFF, the alarm output is not energized during the sensor failure. NOTE! If C.ot.S. = .out1, this parameter is not seen.

baud Baud= Modbus baud rate. off Selectable 1200, 2400, 4800 and 9600.

If baud= off, Modbus communication will be disable.

When holding

key, the value of parameter flashes and using


CSET

keys the requested value can be adjusted.


If key is pressed and held 0.6 seconds, the value of the selected

parameter changes rapidly. If waited enough,the value increases 100 at each step. After 1 second following the release of the key, initial condition is returned.The same procedure is valid for the decrement key.

2/4

ETC4420-E-02-R

TERMS
ETC 4420
CNT/AL2

(7)

SSR
AL1

PV

( 1 ) Process value during normal operation Mnemonic parameter code during programming ( 2 ) Set point during normal operation.

SV SET

Data value during programming

( 3 ) Increment key during normal operation and programming Parameter selection key during programming ( 4 ) Decrement key during normal operation
ASET
TEMPERATURE CONTROLLER

CSET

If only this key is pressed in normal operation, software version number is seen. Parameter selection during programming

ENDA

( 5 ) Alarm set key during normal operation Menu selection key during programming ( 6 ) Heat set key during normal operation Parameter selection key during programming

( 1 ) PV display ( 2 ) SV display Character heights ( 3 ),( 4 ),( 5 ),( 6 ) Keypad ( 7 ) State indicator

4 digits 7 segment red LED 4 digits 7 segment yellow LED

PV display :7 mm SV display :7 mm Micro switch


3 red LEDs for Control, Alarm1 and SSR outputs

ALARM1 AND ALARM2 OUTPUT TYPES


Independent Alarm A1.tP.=indE
SV ON OFF

Deviation Alarm A1.tP.= DE.


SV ON OFF A.StA.= Hi

Band Alarm A1.tP.= bAnd


SV ON OFF A1.St.= boHi

ON OFF
a1.Hy. A1.Hy..

ON OFF A.StA.= Lo
A1.Hy. A1.Hy.

ON OFF A1.St.= biHi

ASV SV+ASV +300 (ASV min = beginning of scale -300 ASV max = end of scale) (ASV min. =-300, ASV max. = +300) (IfinP = Pt..0, ASV min. = -30.0, ASV max. = +30.0) SV = Set point of CONT output ASV = Set point of alarm output

SV-ASV 300

SV+ASV 300 ASV = Set point of AL1 output

SV =Set point of CONT output

(ASV min. = 0, ASV max. = +300) (IfinP = Pt..0, ASV min. = 0.0, ASV max. = +30.0)

Band Alarm With Inhibition A1.tP.= BAn.i.


SV+ASV SV SV-ASV ON OFF SV+ASV SV SV-ASV ON OFF

Band alarm is possible Band alarm is possible Beginning Beginning of procedure of procedure SV =Set point of CONT output ASV = Set point of AL1 output (ASV min. = 0, ASV max. = 300 )

MODIFICATION OF CONTROL AND ALARM SET POINTS


130 150
PV

SET
CSET

SV

C.SEt 150
SET
CSET

PV

SET
CSET

SV

C.SEt 149

PV

SET
SV

CSET

C.SEt 150

PV

When CSET is released, it returns to normal operation. SET CSET

SV

First, press and hold

key until the massage C.Set appears on the display. Then, the value is adjusted by using
PV

keys.

ASET

A1.sE. 250

SV

ASET

A1.sE. 249

PV

SV

ASET

A1.sE. 250

PV

SV

ASET

When ASET is released, it returns to normal operation.


keys. . key.
ASET

First, press and hold

ASET

key, alarm setpoint value appears on the display. Then, the value is adjusted by using

If C.ot.S different from out1. Alarm1 and Alarm2 setpoint values can be adjusted in sequence when per press

NOTE: The maximum of C.SEt is the value of C.Hi.L. parameter and the minimum of it is the value of C.Lo.L. parameter.
If independent alarm is selected, A1.SE. and A2.SE.values can be adjusted between the limits of the full scale. If deviation alarm is selected, A1.SE. and A2.SE. values can be adjusted between -300 and +300. If band alarm is selected, A1.SE. and A2.SE. values can be adjusted between 0 and +300.

---150

Error Messages
PV PV SV

----

SV

150

PFA 150

PV

SV

PSC 150

PV

SV

Temperature value is higher than the scale

Temperature value is lower than the scale

Temperature sensor is broken or over temperature

Pt 100 or a sensor line is short circuited

3/4

ETC4420-E-02-R

DIMENSIONS
1
ETC 4420
CNT/AL2

Depth
87mm
For removing the device from the panel: - While pressing both side of the device in direction 1, push it in direction 2.

AN/SSR

PV

58mm

48mm

AL1
SV SET

CSET

ASET
TEMPERATURE CONTROLLER

ENDA

1
Connection cables
+0.6

Enviroment temperature measurement sensor

Panel cut-out
51mm 45 mm mm

Panel

Note 1) While panel mounting, additional distance required for connection cables should be considered. 2) Panel thickness should be maximum 9mm. 3) If there is no 100mm free space at back side of the device, it would be difficult to remove it from the panel.

CONNECTION DIAGRAM
ENDA ETC4420 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy. The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be close to the power cables or components. The installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations.

ENDA INDUSTRIAL ELECTRONICS


ETC4420-230VAC-RS PID TEMPERATURE CONTROLLER
RS- 485 RS-485 COM. SSR OUT

ENDA INDUSTRIAL ELECTRONICS


ETC4420-24VAC PID TEMPERATURE CONTROLLER
1 2 3
SSR OUT

80mm

Flush mounting clamp

45

+0.6

+ -

A 1 B 2

9 10 11 12 13

230V AC +10% -20% 50/60Hz 5VA CONT./AL2 AC 250V 2A RESISTIVE LOAD AL1 AC 250V 2A RESISTIVE LOAD

9 10 11 12 13

24V AC 10% 50/60Hz 5VA

Logic output of the instrument is not electrically insulated from the internal circuits. Therefore, when using a grounding thermocouple, do not connect the logic output terminals to the ground. Note 1) Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245. 2) In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it should be easily accessible by the operator.

+ -

4
5

+ -

4
5

CONT./AL2 AC 250V 2A RESISTIVE LOAD AL1 AC 250V 2A RESISTIVE LOAD

+
TC Pt 100

6 7
8

14
15

+
TC Pt 100

6 7
8

14
15

SN: XXXXXXXXX

SN: XXXXXXXXX

NOTE :
SUPPLY : 184-253V AC 9 or 99-121V AC 10 50/60Hz 5VA SENSOR INPUT :
7 8

Holding screw 0.4-0.5Nm

Equipment is protected throughout by DOUBLE INSULATION.

Line

Fuse F 100 mA 250V AC

switch 230V or 24V AC Supply

Neutral

Order Code : ETC44201 1- Supply Voltage 230VAC...230V AC 24VAC.....24V AC


SM...........9-30V DC / 7-24V AC

Fuse should be connected.

Cable size: 1,5mm

For resistance thermometer :


When 2 wired Pt 100 is used, terminals 6 and 7 must be short circuited. Pt 100

SSEL MHENDSLK ELEKTRONK SAN. VE TC. A.. Yukar Dudullu Barbaros Cd. Kutup Sok. No:20 34775 - MRANYE/STANBUL-TRKYE Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01 4/4 url : www.enda.com.tr

Use suitable compensation cables. Don't use jointed cables. Pay attention to the polarities of the thermocouple cables as shown in the figure right are connected to the .

TC

6 7
8

For J-K-T-S-R type thermocouple :

2- Modbus Option RS........RS-485 Modbus communication None....Dont support RS-485 Modbus communication

ETC4420-E-02-R